Firex G-6, H, GC, PG40, FXW-R Instructions Manual

SMOKE ALARM FEATURES
Model PG40 and GC smoke alarms can be interconnected with as many as 11 other specific model smoke alarms (Model G-6, as many as 5).
Model GC features False Alarm Control™ that temporarily silences nuisance alarms.
Loud alarm horn—85 decibels at 10 feet—sounds to alert you to a fire emergency.
This alarm incorporates the internationally recognized horn sig­nal for evacuation. During alarm mode, the horn produces three short beeps followed by a 2 second pause and then repeats. This pattern is somewhat different than the previous alarm sound, which continually beeped.
Model FXW-R is a direct replacement for Firex models FX1014, FX1020, FX1106, and FXW-1A. Model FXW-R cannot be inter­connected with any other smoke alarm.
Test button checks smoke alarm operation.
IMPORTANT SAFETY INFORMATION PLEASE
READ AND SAVE THESE INSTRUCTIONS
WARNING
This smoke alarm requires constant 120-volt, AC power to operate.
It will not work if AC power is not connected or has failed or been inter­rupted for any reason. DO NOT turn off AC power to quiet false alarms. Open windows or fan the air around smoke alarm to silence it. The Push-to-Test button accurately tests all smoke alarm functions. DO NOT use any other test method. Test smoke alarm weekly. We recommend you install smoke alarms that operate from both battery and AC power. Having smoke alarms that work from two different power sources can give extra protection in case of a dead battery or an AC power failure. If you have repeated false alarms, move the smoke alarm to a different location, or install specialized smoke alarms with a False Alarm Control or a photoelectric sensor.
This smoke alarm should be installed only by a licensed, quali­fied electrician. Observe and follow all local and national electrical
and building codes for installation.
This smoke alarm is designed to be used INSIDE a single family household only. In multi-family buildings, each individual living unit
should have its own smoke alarms. It is not designed for use in common areas, stairwells, or common hallways in multi-family buildings.
This smoke alarm is not designed for buildings which require complete fire alarm systems. Buildings of this type include hotels,
motels, dormitories, hospitals, nursing homes, and group homes. This is true even if they were once single family homes.
DO NOT connect this smoke alarm to any other smoke alarm or devices except as specifically listed in this manual. Model PG40, GC
and FXW-R smoke alarms can be interconnected with up to 11 other spe­cific model smoke alarms (Model G-6, as many as 5). DO NOT use exter- nal bug screens or alarm guards. This may cause improper operation.
!
1
Smoke Alarm
®
©2000 Maple Chase Company
MODEL G-6, H, GC
PG40 and FXW-R
PLEASE READ AND SAVE THIS MANUAL
Installer: Please leave this manual with the occupier (or, in the case of a house in multiple operation, with the owner)
120V AC Ionization Smoke Alarm
110-427G
The ionization type alarms are generally more effective at detect­ing fast, flaming fires that consume combustible materials rapid­ly and spread quickly. Sources of these fires may include paper burning in a waste container or a grease fire in the kitchen. The photoelectric type alarms are generally more effective at detect­ing slow, smoldering fires that smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding.
Smoke alarms sound their alarm horns when they detect smoke.
They do not detect heat, flame, or gas. They will not operate if smoke does not reach the smoke alarm.
We recommend that you install a smoke alarm in every room and on every level of the home. Smoke may not reach the smoke alarm
for many reasons. For example, if a fire starts in a remote part of the home, on another level, in a chimney, wall, roof, or on the other side of a closed door, smoke may not reach the smoke alarm in time to alert household members. A smoke alarm will not promptly detect a fire EXCEPT in the area or room in which it is installed.
Model G-6, PG40, GC and FXW-R smoke alarms meet all NFPA requirements for new and existing homes. Per the National Fire
Protection Association (NFPA) Standard 72, Chapter 2, this type of smoke alarm can be used to meet the minimum requirements for new and existing residential dwellings. The standard requires that smoke alarms for new residential dwellings be AC powered and interconnect­ed. Therefore, Model G-6, PG40, and GC can be used to meet the min­imum requirements for new construction residential dwellings.
Smoke alarms may not alert every household member every time. The alarm horn is loud in order to alert persons to a potential
danger. However, there may be limiting circumstances where a household member may not hear the alarm (e.g., outdoor or indoor noise, sound sleepers, drug or alcohol usage, the hard of hearing, etc.). If you suspect this smoke alarm may not alert a household member, install and maintain specialty smoke alarms. Household members must hear the alarm’s warning sound and quickly respond to it to reduce the risk of damage, injury, or death which may result from fire. If a household member is hard of hearing, install special smoke alarms with lights or vibrating devices to alert occupants.
This smoke alarm will not provide adequate escape or rescue time in extremely fast moving fires. Fast fires include gas fires,
flammable liquid fires, or fires set on purpose. The smoke alarm will not give adequate escape time to people very close to the fire. Such examples might be, children playing with matches or smokers who fall asleep and drop a cigarette into their bed.
Smoke alarms have limitations. This smoke alarm is not foolproof and is not warranted to protect lives or property from fire. Smoke alarms are not a substitute for insurance. Homeowners and renters should insure their lives and property. In addition, it is possible for the smoke alarm to fail at any time. For this reason, you must test
the smoke alarm weekly and replace it every 10 years.
SMOKE ALARM PLACEMENT
Maple Chase recommends complete coverage protection achieved by installing a smoke alarm in every room of your home. The National Fire Protection Association’s (NFPA) MINIMUM requirement for locat­ing smoke alarms in family living units is detailed in NFPAStandard 72, Chapter 2. It reads as follows:
“2-2.1.1.1 Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each addi­tional story of the family living unit including basements and excluding crawl spaces and unfinished attics. In new construction a smoke detector also shall be installed in each sleeping room."
Further, section 2-2 2.1 states that: “In new construction, where more than one smoke detector is required by 2-
2.1, they shall be so arranged that operation of any smoke detector shall cause the alarm in all smoke detectors within the dwelling to sound."
The NFPA, 1993 Edition, Appendix A, however, clearly points out that: “The required number of smoke detectors [as defined in the paragraphs
above] may not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke detectors. For this reason, it is recommended that the householder con­sider the use of additional smoke detectors for those areas for increased protection. The additional areas include: basement, bed­rooms, dining room, furnace room, utility room, and hallways not pro­tected by the required smoke detectors.”
Further, the California State Fire Marshal states that the minimum number of required smoke alarms is not enough to give the earliest warning under all conditions. The California State Fire Marshal states that:
“Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke detector installed in each separate sleeping area (in the vicinity, but outside the bedrooms), and heat or smoke detectors in the living rooms, dining rooms, bedrooms, kitchens, hallways, attics, furnace rooms, closets, utility and storage rooms, basements and attached garages.”
It is clear from the above abstracts that the earliest warning of a developing fire is best achieved by the installation of smoke alarms in all rooms and areas of the residence. Accordingly, Maple Chase recommends that you install smoke alarms in every room of your residence, even though this is not required by the typical code or standard.
FOR MAXIMUM COVERAGE, WE RECOMMEND THAT YOU INSTALL A SMOKE ALARM IN EVERY ROOM OF THE HOME, INCLUDING BASEMENTS AND FINISHED ATTICS. In addition, we recommend interconnecting all smoke alarms capable of being interconnected.
Maple Chase recommends a minimum of two smoke alarms in every home, no matter how small the home (including efficiency apart­ments). Maple Chase also recommends maximum coverage by installing smoke alarms in both required and recommended locations as illustrated and described.
2
SMOKE ALARM PLACEMENT (Cont’d)
Existing Homes:
The NFPArequires a smoke alarm on
every level and outside each sleeping area in existing construction. An existing household with one level and one sleep­ing area is required to have one smoke alarm.
ADDITIONAL SMOKE ALARM
PLACEMENT INFORMATION:
If a bedroom area hallway is more than 30 feet long, install a smoke alarm at each end.
In basements, install a smoke alarm on the ceiling at the bottom of the stairwell.
Install a smoke alarm at the top of a first-to-second floor stairwell.
Install a smoke alarm as close to the center of the ceiling as possible. If this is not practical, mount no closer than 4 inches from a wall or corner. Also, if local codes allow wall mounting, you may install smoke alarms on walls between 4 and 12 inches from ceiling/wall intersections.
Install a smoke alarm in each room that is divided by a partial wall (either coming down from the ceiling at least 24 inches, or coming up from the floor).
Install smoke alarms on peaked, cathedral, or gabled ceilings 3 feet from the highest point (measured horizontally).
Install a smoke alarm in lived-in or finished attics.
NOTE: For mobile homes built before 1978, install smoke alarms on
inside walls between 4 and 12 inches from the ceiling. (Older mobile homes have little or no insulation in the ceiling.) This is especially important if the ceiling is unusually hot or cold.
3
Bedroom
Bedroom
Bedroom
Bedroom
Kitchen
O
O
O
O
Living Room
SINGLE STORY RESIDENCE/APARTMENT
Bedroom
Basement
Living Room
Hall
Kitchen
Bedroom Bedroom
O
O
O
TWO STORY RESIDENCE
New Construction Homes:
The NFPArequires AC-powered, inter­connected smoke alarms to be installed inside each bedroom, outside each bedroom area, and on every level of the home. They also require a minimum of two AC-powered, interconnected smoke alarms in any new construction home.
Bedroom
Bedroom
Bedroom
Bedroom
Kitchen
Living Room
SINGLE STORY RESIDENCE/APARTMENT
Bedroom
Basement
Living Room
Hall
Kitchen
Bedroom Bedroom
O
TWO STORY RESIDENCE
Hall
O
Utility Room
Utility Room
O
Hall
Mobile Home Installation:
• For minimum protection, smoke alarms should be installed in compli­ance with H.U.D. Manufactured Home Construction Safety Standards Title 24 CFR, Section 3280.208 and Section 3282.
• For additional protection, see single story residence smoke alarm requirements/recommendations for existing homes and new construc­tion above.
Key
NFPA minimum REQUIRED smoke alarm locations
O Additional Smoke Alarm RECOMMENDED by
Maple Chase, NFPA, and California State Fire Marshal
RECOMMENDED type with False Alarm Control™
--- Denotes interconnection
4 IN
(01m )
4 IN
(01m )
MNIMUM
12 IN
(03 m )
MAXMUM
CELING
SDE
WALL
ACCEPTABLE HERE
NEVER HERE
TOP OF DETECTOR ACCEPTABLE HERE
8"
STUB WALL
SOFFIT
ACCEPTABLE N
THIS AREA
PEAKED CEILING
3 ft
Loading...
+ 5 hidden pages