Firex 592SC, 591S User Manual

The professional choice in fire safety.
The NEW remote accessories are designed to be used with Firex duct smoke detectors to provide the most complete functionality ever available in such a device.
The remote accessory is available with either the single gang remote indicator/control (591 models), or with the addition of a single gang strobe assembly (592 models). Both versions are compatible with standard Decora style cover plates (choice of white, red or stainless steel). A strobe-only version (593 models) is available for retrofit upgrade of “controller only” installations.
Visual indication of detector Pilot, Trouble and Alarm Functions
Selectable audible indication of Alarm, Trouble or both
Buzzer Silence function, with silenced indication and “ringback” following condition correction
Lamp/Buzzer test function
Key-Operated detector Test and Reset functions
Lever-operated “No-Tools” terminal block
Port for plugging in the optional strobe assembly
Black “DUCT SMOKE DETECTOR” decal included for front plate
Blue “SMOKE”, red “FIRE” strobe lens decals included for both horizontal and vertical mounting
Strobe Connection
The strobe assembly provides visual indication of alarm conditions, and is connected to the indicator/control assembly via the provided polarized connector.
To install the strobe module, simply plug the provided connector onto the pins as indicated on the rear of the indicator/control module. Snap the strobe lens into the cover plate, and install cover plate following completion of remote module wiring.
NOTE: The strobe and audible buzzer features are not ADA compliant, and not intended for life safety notification or evacuation purposes (public mode). These functions are for duct smoke detector status indication only (private mode).
Duct Smoke Detector Remote Accessories
Universal Voltage Models Compatible with 230 VAC, 115 VAC, 24 VAC or 24 VDC operation
2650-760 Ionization • 2650-761 Photoelectric 2650-660 Ionization • 2650-661 Photoelectric 2650-560 Ionization • 2650-561 Photoelectric
NEW ACCESSORIES
591S
592SC
Audible Buzzer Configuration
There are two jumpers located on the rear of the indicator/control assembly. To enable audible buzzer operation for Alarm or Trouble conditions, simply leave the jumpers in place. To disable either or both functions, remove the appropriate jumper(s).
TBL
ALM
Buzzer will
function on
both Alarm
and Trouble
Conditions
TBL
ALM
Buzzer will
function on
on Alarm
Condition
only
TBL
ALM
Buzzer will
function
on Trouble
Condition
only
TBL
ALM
Buzzer
will not
function
on Alarm
or Trouble
Conditions
591 Series Remote Accessory Controllers
591W Remote Indicator/Control Assembly w/White Single Gang Cover Plate 591R Remote Indicator/Control Assembly w/Red Single Gang Cover Plate 591S Remote Indicator/Control Assembly w/Stainless Steel Single Gang Cover Plate
592 Series Remote Accessory Controllers with Strobe
592WC Remote Indicator/Control Assembly w/Strobe Assembly (Clear Lens); White Double Gang Cover Plate 592WO Remote Indicator/Control Assembly w/Strobe Assembly (Opaque Lens); White Double Gang Cover Plate 592RC Remote Indicator/Control Assembly w/Strobe Assembly (Clear Lens); Red Double Gang Cover Plate 592RO Remote Indicator/Control Assembly w/Strobe Assembly (Opaque Lens); Red Double Gang Cover Plate 592SC Remote Indicator/Control Assembly w/Strobe Assembly (Clear Lens); Stainless Steel Double Gang Cover Plate 592SO Remote Indicator/Control Assembly w/Strobe Assembly (Opaque Lens); Stainless Steel Double Gang Cover Plate
593 Series Remote Accessory Strobes (as an optional field upgrade kit for existing installed 591 Series Controllers)
593RC Strobe Assembly (Clear Lens); Red Double Gang Cover Plate 593RO Strobe Assembly (Opaque Lens); Red Double Gang Cover Plate 593SC Strobe Assembly (Clear Lens); Stainless Steel Double Gang Cover Plate 593SO Strobe Assembly (Opaque Lens); Stainless Steel Double Gang Cover Plate 593WC Strobe Assembly (Clear Lens); White Double Gang Cover Plate 593WO Strobe Assembly (Opaque Lens); White Double Gang Cover Plate
Products
Controls Americas
515 South Promenade Avenue Corona California 92879-1736 USA Cust. Svc. Telephone +1 800 951 5526 Cust. Svc. Facsimile +1 630 260 7299 iccacustomerservice@invensys.com
3505 Laird Road Unit #14 Mississauga Ontario L5L 5Y7 Canada Cust. Svc. Telephone +1 800 387 7978 Cust. Svc. Facsimile +1 905 828 1265 iccacustomerservice@invensys.com
Technical Service
Telephone +1 800 445 8299 Facsimile +1 630 260 723 technicalservice@invensys.com
© 2006 Invensys Controls Americas 6/06 - #150-1991
Power Requirements: Standby 13mA
Alarm LED 22mA Trouble with Buzzer 33mA Trouble Silenced 33mA Trouble without Buzzer 13mA Alarm with Buzzer 37mA Alarm Silenced with Buzzer 37mA Alarm with Buzzer and Strobe 154mA Alarm Silenced with Buzzer and Strobe 157mA Lamp Test with Buzzer 62mA Lamp Test with Buzzer Silenced 52mA
Sound Pressure: 60db @ 10 ft.
Dimensions: Single Gang Plate:
4-1/2” (114.3 mm) H x 2-3/4” (69.85 mm) W
Double Gang Plate:
4-1/2” (114.3 mm) H x 4-1/2” (114.33 mm) W
Wiring: 14-28 AWG. Solid or Stranded
Approvals: U.L. Listed for use with Firex duct
smoke detectors including all 2650 Series duct smoke detectors UL URRQ, URRQ7.S7425 / CSFM / MEA
Silence and Ringback Functions
On the occasion where an audible alarm or trouble condition needs to be silenced while the detector condition is inspected and remedied, the indicator/control module provides a silence function. The slide switch located on the front of the module is pushed DOWN to activate the silence function.
Upon correction of the notified condition, the silenced buzzer will resume sounding. The ringback feature serves as a reminder to reset the silence switch to the “normal”, UP position.
Note that the strobe module, when installed, will not stop operating when the silence function is engaged.
Wiring
For appropriate duct detector wiring terminals, please refer to detector and remote accessory installation instructions.
T
H
R
E
E
Y
E
A
R
W
A
R
R
A
N
T
Y
R
US
LISTED
268A Listed
MEA ACCEPTED
Normal
“Standby”
Mode
Silenced
Mode
T
I
N
S
I
G
A
L
C
I
L
F
F
O
O
R
E
N
T
I
A
A
T
S
S
T
L
A
A
T
H
E
S
S
R
F
I
A
R
M
E
E
E
C
R
I
V
Loading...