The Firex®5700 Heat Alarm offers contractors the same reliability and quality they have long depended on from the leader in fire safety technology. The Firex Heat Alarm, Model 5700, is a fixed temperature unit that detects heat at 135°F (57°C) or greater. It relies on a thermistor that is sensitive only to temper­ature. When the temperature reaches 135°F (57°C) or greater, the alarm is triggered. The 5700 requires 120V AC power and includes a 9V battery back-up for added protection in the event of a power failure. The 5700 heat alarm is interconnectable with other AC/DC Firex heat alarms, smoke alarms, smoke/co combo alarms, and carbon monoxide alarms. Up to 11 other smoke alarms and smoke/co combo alarms can be interconnected, and 6 Firex heat alarms and carbon monoxide alarms for a total of not more than 18 devices. Contractors have been installing the best selling Firex smoke alarms for over 20 years and will appreciate the design similarities when installing Firex heat alarms. Both products utilize a Quick Connect wire harness, an optional tamper-resist feature and a unique power connector that prevents interconnection with incompatible heat alarms, smoke alarms or security systems.
5700 Features and Benefits
Heat alarms are sensitive only to a fixed temperature Less
nuisance alarms due to contamination, dust and insects
Installation design and features similar to other Firex®Smoke Alarms Contractor familiarity
with installation
Interconnects with other Firex Smoke Alarms, CO Alarms, Smoke/CO Alarms, and Heat Alarms Compatible with contractor
preferred Firex products
Large, easy to use push-to-test button Quickly locate and access
test button to test all alarm functions once installation is complete
LED — Green “power-on” LED confirms constant AC power and red LED displays alarm/battery status
Incorporates Firex installer-focused innovations Fastest and easiest
installation available
9 Volt battery back-up (included)
Provides extra protection during power outages
Attractive, low-profile design —
Our contemporary StyleLine design™ is a favorite among consumers
Why Install a Firex Heat Alarm?
Some environments can trigger nuisance alarms in conventional smoke alarms due to shifts in temperature and humidity as well as dust, fumes and insects. Heat alarms are intended for use in the locations listed below because they are virtually unaffected by these adverse conditions:
• Kitchens • Unfinished Attics • Basements
• Garages • Boiler Rooms • Other areas where high levels of dust and fumes are present
Heat alarms should always be interconnected with smoke alarms to provide early warning when fire is present.
5
Year Limited Warranty
Description
Item 5700
Technical Specifications
Architectural Specifications
Shipping Specifications
This heat alarm should be installed in accordance with the NFPA’s Standard 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA
02269) and any local codes that apply. Use #18 AWG minimum solid or stranded wire. When interconnecting,
maximum wire length between any two is 1,500 feet for #18 AWG or 4,000 feet for #14 AWG (20 OHMS loop resistance).
DO NOT connect to any other type or model of heat or smoke alarm. Connect heat alarms to a single AC branch circuit. If local codes do not permit, be sure the neutral wire is common to both phases.
Installation of Heat Alarm
Individual Carton Dimensions 5-1/4" x 2-11/16"x 5-1/4" Master Carton Quantity 10 Master Carton Dimensions 15-3/4" x 11-1/4"x 6" Master Carton Weight 7.62 lbs.
150-1344E
Side View
Mounting Bracket
The heat alarm shall be a StyleLine design™ (2-1/8" high, 5" diameter), powered by 120V AC, 60Hz source with a 9-volt battery back-up. The alarm shall have a fixed temperature sensor set to alarm at nominal 135°F (57°C). The alarm shall be rated at no greater than .05W in standby. Operating temperature range shall be between -10°F and 158°F; 10%-93% relative humidity; 100% solid state circuits over an input range of 100-130V AC. A green continuous power on indicator shall be a built-in light emitting diode (LED) in the standby condition; a second red blinking LED shall indicate that a sufficient 9-volt battery back-up is present; when activated; the initiating alarm red LED shall flash while the interconnected alarms remain extinguished. The test switch shall activate the alarm function by electronically simulating a temperature greater than 135°. The alarm shall mount to a single gang box, 4" octagon junction box, or a square to round drywall ring without screw removal. It shall have a Quick Connect molded harness, pigtail wiring and separate mounting bracket. It shall meet the requirements of U.L. Standard 539 and 217.
5"
2.125"
Item 5700 Model ADH Product Weight 8.6 ounces Operating Temperature -10°F to 158°F (-23°C to 70°C) Interconnect Qty Up to 18 Firex devices maximum: 12 smoke alarm
items 5000, 4618 and 46182 (model FADC), 4518 (model ADC) and 4480 (model PAD). Up to 6 heat, car­bon monoxide or smoke and carbon monoxide combi­nation alarms maximum; Firex carbon monoxide alarm item 6045 (model COQ8), Firex smoke and carbon monoxide combination alarm item 7000 (model FADCQ) or Firex heat alarm item 5700 (model ADH).
Electrical Rating 120V AC, 60HZ, 50mA max, 9 Volt Battery Back-up Alarm Point 135°F (57°C) fixed temperature
triggers alarm
Horn Output 85 decibels at 10 feet Listing U.L. 539 and 217 U.L. Recommended Coverage 2500 square feet U.L. Recommended Spacing 50 feet Maximum Distance from Wall 25 feet
Item 5700
©2003 Invensys Climate Controls Americas
3505 Laird Road Unit #14 Mississauga Ontario L5L 5Y7 Canada Cust. Service Telephone +1 800 668 6958 Cust. Service Facsimile +1 905 828 1265
Visit us on the web at
www.icca.invensys.com
Climate Controls Americas
191 E. North Avenue Carol Stream Illinois 60188 USA Cust. Service Telephone +1 800 951 5526 Cust. Service Facsimile +1 630 260 7299
For Technical Service
Telephone +1 800 445 8299 Facsimile +1 630 260 7299 mctechservices@invensys.com
Loading...