Firex 2650-661, 2650-660 User Manual

TThhee pprrooffeessssiioonnaall cchhooiiccee iinn ffiirree ssaaffeettyy..
FIREX®the recognized leader in residential fire protection, brings you the latest in duct smoke detection technology. FIREX
®
Duct Smoke Detectors provide early detection of smoke and products of combustion present in air moving through an HVAC duct. These devices are designed for prevention of smoke recirculation in areas by the air handling systems. Fans, blowers, and complete systems may be shut down in the event of smoke detection. Our universal voltage models will operate on any one of four input voltages.
Air sampling is accomplished by two tubes, which protrude into the duct. An exhaust tube of one standard length (7'') is provided with each FIREX
®
Duct Smoke Detector. Intake sampling tubes, which must be ordered separately, are available in three standard lengths.
Duct smoke detector mounting is accomplished by the use of a mounting template and four sheet metal screws, which are provided.
Front Mounted Test / Reset Button
Provides quick and accurate testing of system.
Duct Smoke Detectors
Universal Voltage Models 230 VAC, 115 VAC, 24 VAC or 24 VDC operation
2650-660 Ionization • 2650-661 Photoelectric
High Temperature Design
Rated to 155˚F (ionization model) for rooftop and other installations where high temperatures can cause problems.
Interconnect Up to 30 Models
Up to 30 models can be interconnected to provide complete HVAC system protection–controlling all connected blowers, fans and dampers.
Alerts When Dirty
Automatically indicates when maintenance is required.
• Four sheet metal screws provide easier mounting
• UL 268A Listed
• Factory set tube alignment
• Mechanical installation without cover removal
• Built-in power supply
• Installation template included
• Large terminal connection screws
• Power supervisory relay included
• Two independent form “C” alarm contacts standard
• Compatible with building automation & fire alarm systems
• Dust filtering included in detector head
• No additional screens or filters to clean
• Common or individual remote reset
• Common or individual fan shutdown relay operation
• Common or individual remote alarm indication,
i.e. red LED, horn, strobe
• Common or individual head removed remote indication
• One horn/strobe operated by up to 15 detectors
T
H
R
E
E
Y
E
A
R
W
A
R
R
A
N
T
Y
Additional Features
Installation Flexibility
Fast and easy mounting to rectangular ducts.
Wiring
Item:
2650-660 - 115 Volt AC, 230 Volt AC, 24 Volt AC,
or 24 Volt DC ionization
2650-661 - 115 Volt AC, 230 Volt AC, 24 Volt AC
or 24 Volt DC photoelectric 532 - Sampling tube for 6'' to 2.5' duct widths 533 - Sampling tube for 2.5' to 5.0' duct widths 534 - Sampling tube for 5.0' to 10.0' duct widths
Power Requirements:
115 Volt AC operation @ 5 mA standby, 15 mA alarm 230 Volt AC operation @ 12 mA standby, 16 mA alarm 24 Volt AC operation @ 20 mA standby, 50 mA alarm 24 Volt DC operation @ 20 mA standby, 50 mA alarm
Relay Contact Rating:
Alarm contacts, two form “C” rated at 10 Amps @ 230 VAC resistive Trouble contact, one form “C” rated 10 Amps @ 230 VAC resistive
Radioactive Element:
For model 2650-660 only, Americium 241; 0.9 Micro-Curies
Sensitivity:
Factory set
Air Velocity:
500 to 3000 feet/minute
Approval:
Underwriters Laboratories Listed (UL 268A)
Ambient Temperature:
-5ºF to 155ºF (-23º to 68ºC) Model 2650-660
-5ºF to 120ºF (-23º to 48ºC) Model 2650-661
Humidity:
10% to 85% R.H.
Material:
18 ga. steel backbox, clear plastic ABS-94VO cover
Finish:
Textured gray finish
Maximum net weight:
4.0 pounds
Mounting:
Template and necessary hardware supplied
Dimensions:
9'' H x 7'' W x 2.25'' D (22.9 cm H x 17.8 cm W x 5.7 cm D)
Air duct smoke detectors shall be Firex®‚ item number 2650-660 ionization type (2650-661 for photoelectric). The detectors shall be listed by Underwriters Laboratories to verify operational characteristics in accordance with U.L. 268A standard and local code requirements. The detectors shall operate at an ambient temperature up to 155°F (2650-661 photoelectric, 120°F) and air velocities from 500 feet per minute to 3,000 feet per minute. A custom fitted NEMA 3R rated Firex‚ Weatherproof Enclosure item number 590 shall be used for indoor or outdoor locations that require protection from environmental elements.
The detector housing shall be of 18 gauge steel construction with a special ABS-94VO high strength plastic cover for maximum durability. Complete mechanical installation of the unit must be performed without removal of detector cover to prevent dirt and debris from entering unit. The plastic cover shall be clear to allow full visibility of the internal components for future visual inspections.
Detector heads contained within the unit shall not require separate filters or screens which must be maintained or replaced to insure that unit is fully operational. The housing shall accept either
ionization or photoelectric type detector heads as required.
Terminal connections shall be of screw type and be a minimum of #6 screw for easy wiring during installation. Terminals shall be provided for remote pilot and alarm indication.
Visual indicators shall be mounted at an angle on the front housing for pilot and alarm status to allow easy viewing from lower elevations during routine inspections. A manual test/reset switch shall also be provided on the front of the detector for unit testing during standby conditions or rou­tine inspections.
Product Specifications
Engineers & Architects Specifications
FIREX® Duct Smoke Detector
Powe r Connections (See Below)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
12.0A 12.0A 10.0A
Remote
Accessories
Alarm
Contacts
*Trouble Contacts
115 VAC Operation
115 VAC
@ 50/60 Hz
Input
0.1 A. Max.
1 2 3
GNH
4 5 67
230 VAC Operation
230 VAC
@ 50/60 Hz
Input
0.1 A. Max.
1 2 3
GN H
4 5 67
24 VAC Operation
24 VAC
@ 50/60 Hz
Input
0.2 A. Max.
1 2 3 4 5 67
24 VDC Operation
24 VDC
Input
0.1 A. Max.
1 2 3 4 5 67
+
* Trouble contacts are
shown in non-energized condition. Normal operation contacts will be reversed.
T
H
R
E
E
Y
E
A
R
W
A
R
R
A
N
T
Y
Controls Americas
515 South Promenade Avenue Corona California 92879-1736 USA Cust. Svc. Telephone +1 800 951 5526 Cust. Svc. Facsimile +1 630 260 7299 iccacustomerservice@invensys.com
3505 Laird Road Unit #14 Mississauga Ontario L5L 5Y7 Canada Cust. Svc. Telephone +1 800 387 7978 Cust. Svc. Facsimile +1 905 828 1265 iccacustomerservice@invensys.com
Technical Service
Telephone +1 800 445 8299 Facsimile +1 630 260 723 technicalservice@invensys.com
See sell sheet 150-1661 and 150-1991 for listing of accessories © 2006 Invensys Controls Americas 6/06 - #150-1610D