Firex 10000 User Manual

©2006 INVENSYS CONTROLS AMERICAS
Carbon Monoxide Alarm
110-1125C
SERIES 10000 MODEL COE: 120 V AC/DC CARBON MONOXIDE ALARM WITH BATTERY BACKUP
SERIES 10200 MODEL COE-B: DC ONLY CARBON MONOXIDE ALARM
SERIES 10400 MODEL COEA: 120 V AC CARBON MONOXIDE ALARM
PLEASE READ AND SAVE THIS ENTIRE MANUAL
Electrical rating: 120V AC, 60Hz, 0.05amp Single or multiple station CO alarm Model COE includes 9V battery back-up
TABLE OF CONTENTS
About This Carbon Monoxide Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Specifications and Important Product Information . . . . . . . . . . . . . . . . . . . . . . . .1
Where to Install This CO Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
How To Install This CO Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
1. Installing an AC With Battery Back-Up Alarm . . . . . . . . . . . . . . . . . . . . . . . .3
2. Interconnecting AC Only and AC/DC Alarms . . . . . . . . . . . . . . . . . . . . . . . .3
If the Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Chart : Understanding the LED Lights and Horn Patterns . . . . . . . . . . . . . . .5 & 6
Troubleshooting the CO Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 & 6
Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Symptoms of CO Poisoning and sources of CO in the home
Testing and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Service and Warranty Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
The following symbols identify the most important safety messages in this manual.
When you see this symbol, be aware that if the
DANGER
WARNING
CAUTION
About this Carbon Monoxide Alarm:
message is ignored, the hazard WILL result in SEVERE bodily injury or death.
When you see this symbol, be aware that if the
message is ignored, the hazard CAN cause SEVERE bodily injury or death.
When you see this symbol, be aware that if the
message is ignored, the hazard CAN or WILL cause MINOR bodily injury.
This CO alarm is designed to detect carbon monoxide gas. It is NOT designed to detect smoke, fire, or any other type of gas. If this CO alarm sounds its alarm
horn, DO NOT assume that it is a false alarm. The alarm horn requires your immediate action.
WARNING
Individuals with medical problems may consider using warning devices which provide audible and visual signals for carbon monoxide concentrations under 30ppm.
SPECIFICATIONS AND IMPORTANT
PRODUCT INFORMATION
Product Features
Monthly Self-Test: Approximately every 30 days this alarm performs a silent internal system test to verify sensor operation utilizing True Gas Testing. True Gas Testing verifies that the CO sensor is nearing the end of its service life. Traditional CO alarms test the sensor by simulating an alarm condition electrically. This is the first CO sensor that runs a diagnostic test by generating a very small and harmless amount of hydrogen gas. If the sensor is working properly, it WILL NOT chirp. If the alarm chirps during the monthly self-testing, it is indicating a problem with the unit. Refer to the charts on pages 5 and 6 for the appropriate actions to take should this occur. You must still test the alarm weekly to verify
proper horn operation.
Trigger Alarm Locator™ (TAL™): Most interconnect tests trigger all alarm horns simultaneously for the duration of the test. This unique system alternates between a 10 second ALL ON cycle and a 50 second cycle where only the initiating alarm is sounding.
Alarm Controlled Interconnect Test: In an interconnected system, this feature will alarm the local unit first, then quiet the local unit while the remote units alarm.
Smart Quiet™ Low Battery 1: Allows the homeowners to silence the low battery chirp for up to 10 hours, giving them time to go back to sleep and/or purchase a fresh replacement battery.
Smart Quiet™ Low Battery 2: Indicates the battery no longer has enough voltage to adequately protect in the event of a power outage or a battery-only installation. The Smart Quiet™ feature will no longer silence the chirp. THE BATTERY MUST BE REPLACED IMMEDIATELY.
Required Power Supply (Series 10000 and 10400 only)
• This CO alarm requires constant 120-volt, AC power AND/OR a working 9-volt battery to operate properly. This alarm WILL NOT work if AC power is not connected or has failed or been interrupted for any reason AND the battery is removed, drained or improperly connected. DO NOT use any other kind of battery except as specified in this manual.
1
NOTE: AC/DC alarms offer added protection in the event of a power failure or a drained battery.
• DO NOT remove or disconnect the battery or turn off AC power to quiet unwanted alarms. This will remove your protection. This alarm features a Quick Quiet™ False Alarm Control button which, when activated, will quiet unwanted CO alarms for up to 6 minutes.
Installation/Interconnect
• This CO alarm should be installed only by a licensed qualified electrician. Observe and follow all local and national electrical and building codes for installation.
• Unique power connector prevents interconnection with incompatible smoke and combination alarms or security systems.
• This CO alarm may be interconnected with as many as 12 other Firex model FADC, AD, ADC, PAD, G, or TPCI smoke alarms, and as many as 5 Firex model ADH heat alarms or COE and COEA CO alarms for a total of not more than 18 interconnected devices.
WARNING
• DO NOT connect this CO alarm to any other type of smoke, CO, heat, or com-
bination alarm or auxiliary device except those listed in this manual.
• While AC and AC/DC smoke, CO and heat alarms can be interconnected,
ONLY when AC power is ACTIVE will ALL units ALARM when one unit senses a hazardous condition. WHEN AC power is DISCONNECTED, INTERRUPTED OR NOT PRESENT FOR ANY REASON, ONLY AC/DC UNITS WILL CONTINUE TO SEND AND RECEIVE SIGNALS AND SOUND AN ALARM IN RESPONSE TO THE PRESENCE OF SMOKE. WHEN power is DISCONNECTED, INTERRUPTED OR NOT PRESENT FOR ANY REASON, AC powered smoke, CO, or heat alarms WILL NOT OPERATE!
Compliance and Proper Applications
• This CO alarm is designed to be used inside a single-family household. In multi-family buildings, each individual living unit should have its own alarms. It is not a substitute for a complete commercial alarm system. It should be used only as supplemental protection in hotels, motels, dormitories, hospitals, nursing homes, or group homes.
• This product is intended for use in ordinary indoor locations of family living units. It is not designed to measure compliance with Occupational Safety and Health Administration (OSHA) commercial or industrial standards.
NOTE: Enclosed with this CO alarm are two labels detailing actions to take in the event of an alarm. One should be placed next to the CO alarm; the other should be placed near a source of fresh air. Please provide the telephone num­ber of the emergency provider and a qualified technician on each label.
WHERE TO INSTALL THIS CO ALARM
About Locating CO Alarms
Carbon monoxide gas can be anywhere and everywhere. CO gas is equal to or slightly lighter than air, and disperses evenly with the air in a room. Therefore, install this CO alarm where air circulation is best. Since most CO fatalities occur while families are sleeping, we recommend that you install at least one CO alarm in the hallway outside each separate sleeping area and one inside each bedroom or sleeping area.
We also recommend that you install a CO alarm on every separate living level of the home where household members frequently spend time, as well as in the basement.
This CO alarm can share the interconnect wire of smoke and heat alarms, BUT this alarm will remain silent if smoke or high heat is detected by the interconnected smoke and heat alarms. Therefore it is necessary to install both a CO alarm and smoke alarm or a smoke/CO combination alarm in those areas to be fully protected.
This alarm will indicate only the presence of carbon monoxide gas at the sensor. Carbon monoxide gas may be present in other areas.
BEDROOM BEDROOM BATH
FURNACE
ROOM
BASEMENT
single story double story
FIGURE 1
CAUTION
LIVED-IN ATTIC
BEDROOM BATH BEDROOM
LIVING ROOM
FURNACE BASE­MENT
FIGURE 2
BEDROOM BATH
BEDROOM
FAMILY/GREAT ROOM
KITCHEN
ROOM
KITCHEN
LIVING ROOM
UTILITY
ROOM
BASE­MENT
BATH
split level
FIGURE 3
KEY: CO Alarm Locations
WARNING
DO NOT install CO alarms:
• Near bathrooms or in shower areas. Steam and aerosol sprays can disable the alarm.
• In closets, crawlspaces, unused attics, or unheated areas where surrounding air temperatures man go below 40ºF (4.4ºC) or above 100ºF (37.8ºC).
• Within five feet of any fuel-burning appliance (stove, kerosene heater, furnace, fireplace, etc.).
• Within one foot of any wall, corner, or other dead air space.
• In rooms where chemicals or cleaning supplies are frequently used (paint, hair spray, thinner, etc.). Allow plenty of ventilation in rooms where chemicals are used.
• Directly above a sink, bathtub or basin.
• Directly above or below air exchange or heating vents.
• Behind drapes, furniture, or appliances that could block air flow to the CO alarm.
WARNING
This unit cannot be used in recreational vehicle applications.
HOW TO INSTALL THIS CO ALARM
This alarm can be mounted and operated in one of three ways: 1. Battery (DC)
Only Stand Alone, 2. AC With a Junction Box, and 3. Interconnected AC Only and AC/DC Alarms.
2
Do not use super glue or silicon caulk on or near the alarm! Fumes from these products can coat and permanently damage the sensor.
Installing a Battery (DC) Only Stand-Alone Alarm
Model COE-B (10200 Series)
CAUTION
1. Remove the mounting plate. Hold the alarm and turn the mounting plate clockwise
to separate it from the back of the alarm.
2. Hold the mounting plate against the ceiling or wall in the desired position and use
a pencil to trace the mounting holes.
3. Use a 3/16” (5mm) drill bit to drill through the center of the outlines you made in
Step 2.
4. Insert screw anchors into the drilled holes. If necessary, gently tap anchors with
a hammer until they are flush with the mounting surface.
5. Attach the mounting plate to the mounting surface with the mounting screws
provided.
6. Position the alarm on the mounting plate and turn clockwise to lock it into place.
7. Pull out the battery activation strip. The alarm will respond with one yellow
light flash.
8. Test the alarm. See “TESTING AND MAINTENANCE” for details.
Installing With a Junction Box
Models COE (10000 Series) and COEA (10400 Series)
ELECTRICAL SHOCK HAZARD. Turn off power at the main fuse box or circuit breaker by removing the fuse or switching the circuit breaker to the OFF position.
WARNING
This CO alarm should be installed only by a qualified electrician. Carbon Monoxide alarm installation must be in accordance with the requirements of Article 760 of the National Electrical Code and any local codes that may apply.
• Install CO alarm on any 4-inch or single gang junction box only.
1. From box of CO alarm, remove mounting plate.
2. Align recessed slots on plate with mounting holes of any 4-inch or single gang junction box.
3. Gently pull household wires through center hole of plate.
4. Secure plate to junction box using mounting screws.
5. With a small wire connector, connect white wire from connector plug to white household wire.
6. Connect black wire from connector plug to black household wire.
7. To interconnect alarms, connect yellow wire from connector to interconnect wire between other combination or smoke alarms.
DANGER
Before starting, see “INTER­CONNECTING AC and AC/DC ALARMS.”
NOTE: For a single-station alarm,
cover yellow wire with electrical tape and tuck into junction box.
8. Attach connector plug to pins on back of combination alarm. Plug will only fit one way and will snap into place. Gently tug connector to be sure it is attached securely.
9. Position the CO alarm to mounting plate and turn clockwise to lock into place.
10. Turn on power at main fuse box or circuit breaker.
11. Test CO alarm. See “TESTING THE CO ALARM.”
12. Model COE only: Activate the battery. Remove arrow tab and close battery
door. The yellow light will flash as door is closed.
WHITE
YELLOW
BLACK
FOR INTERCONNECT: USE #18 AWG MINIMUM WIRE
WHITE
YELLOW
BLACK
WHITE
BLACK
TO NEUTRAL
TO 120V AC
Interconnecting AC Only and AC/DC Alarms
DANGER
ELECTRICAL SHOCK HAZARD. Turn off power at the main fuse box or circuit breaker by removing the fuse or switching the circuit breaker to the OFF position.
WARNING
This CO alarm should be installed only by a qualified electrician. Carbon Monoxide alarm installation must be in accordance with the requirements of Article 760 of the National Electrical Code and any local codes that may apply.
• Use #18 AWG minimum solid or stranded wire. When interconnecting, maximum wire length between any two is 1,500 feet for #18 AWG or 4,000 feet for #14 AWG (20 OHMS loop resistance).
• This CO alarm may be interconnected with as many as 12 other Firex model FADC, AD, ADC, PAD, G or TCPI smoke alarms, and as many as 6 Firex model ADH heat alarms or COE and COEA CO alarms for a total of not more than 18 interconnected devices. DO NOT connect to any other type or model combination smoke, or CO alarm.
WARNING
While AC and AC/DC smoke, CO and heat alarms can be interconnected, ONLY when AC power is ACTIVE will ALL units ALARM when one unit senses a haz­ardous condition. WHEN AC power is DISCONNECTED, INTERRUPTED OR NOT PRESENT FOR ANY REASON, ONLY AC/DC UNITS WILL CONTINUE TO SEND AND RECEIVE SIGNALS AND SOUND AN ALARM IN RESPONSE TO THE PRES­ENCE OF SMOKE., CO, OR HEAT, AS DETERMINED BY THE MODEL OF ALARM THAT IS PRESENT. WHEN power is DISCONNECTED, INTERRUPTED OR NOT PRESENT FOR ANY REASON, AC powered smoke, CO, or heat alarms WILL NOT OPERATE.
• Connect CO and smoke alarms to a single dedicated AC branch circuit. If local codes do not permit such a wiring configuration or connection, be sure the neutral wire is common to both circuits or phases.
Installing AC/DC CO Alarms as Replacements with Interconnected Legacy Firex Alarms
Model COE and COEA CO alarms are designed to be used as replacement units for all Firex AC and AC/DC CO alarms with a low voltage interconnect line. All models listed use a 3-wire interconnect system. To interconnect with other models, please call our free technical support line at (800) 445-8299.
3
IMPORTANT! READ BEFORE INSTALLING THIS CO ALARM WITH EXISTING
In residential homes, there are two ways smoke and CO alarms are hardwire installed and interconnected. One uses 4 wires, the other uses 3 wires.
CO alarms can be used with both 4 and 3 wire systems.
COEA
1. Identify whether the installed system uses 3 or 4 wires to interconnect.
2. If a 4-wire system is installed, change the system to a 3-wire by connecting the independent interconnect wires (yellow and blue) at any point in the system.
3. Smoke alarms generally don’t require any changes (other than replacement every ten years).
4. Replace older CO alarms on the new 3-wire system with COE and COEA CO alarms. These alarms can discriminate between signals coming from a smoke alarm and signals coming from a CO alarm. Older model CO alarms converted to 3-wire cannot. So when any alarm is triggered, all the older CO alarms will sound, creating confusion about which danger is actually present.
To Install a CO alarm as a Replacement:
1. Turn off AC power at circuit breaker or main fuse box.
2. Remove old alarm from mounting bracket.
3. Disconnect wire connector from back of unit.
4. Remove wire nuts and connect new wire connector to household wiring. Be certain not to cross the wiring.
5. Connect wire connector to back of alarm.
6. If mounting bracket is the same, reattach alarm to mounting bracket. Feed wiring back through hole in mounting surface.
7. Turn on power at main fuse box or circuit breaker.
8. Test CO alarm. See “TESTING THE CO ALARM.”
9. Model COE only: Activate the battery. Remove arrow tab and close battery yellow light will flash as door is closed.
INTERCONNECTED FIREX ALARMS
The model
COE and
IF THE ALARM SOUNDS
If Your CO Alarm Sounds (and you are not testing it)
Carbon Monoxide has no taste, feel or smell – but it can be FATAL.
IF 1 RED LIGHT IS FLASHING AND THE HORN SOUNDS 4 ALARMS APPROXI­MATELY EVERY FIVE SECONDS, IT INDICATES THE PRESENCE OF CO WHICH CAN BE FATAL. YOU MUST QUICKLY DO THE FOLLOWING:
1. Operate Test/Reset button;
2. Call your emergency services [fire department or 911]
3. Immediately move to fresh air — outdoors or by an open door/window. Make cer­tain that all persons are accounted for. Do not reenter the premises or move away from the open door/window until the emergency services responders have arrived, the premises have been aired out, and your alarm remains in its normal condition.
4. After following steps 1 - 3, if your alarm reactivates within a 24 hour period, repeat steps 1 - 3 and call a qualified appliance technician (__________________) to inves­tigate sources of CO from fuel burning equipment and appliances, and to inspect for proper operation of this equipment. If problems are identified during this inspection, have the equipment serviced immediately. Note any combustion equip­ment not inspected by the technician and consult the manufacturers’ instructions or contact the manufacturers directly for more information about CO safety and this equipment. Make sure that motor vehicles are not, and have not been, operat­ing in an attached garage or adjacent to the residence.
If the CO alarm sounds its alarm horn again, it has sensed CO. This is not a false alarm.
TO TEMPORARILY SILENCE AN ALARM
NOTE: These features temporarily quiet alarms, but do not disable the sensor.
Quick Quiet™CO Reset
Pushing the Smart Button initiates the CO reset, which quiets all alarms, includ­ing the one you touched.
This means the unit nearest you triggered the alarm.
WARNING
Smart Quiet
Pushing the Smart Button quiets all alarms EXCEPT the one that triggered the alarm.
This means the unit still sounding triggered the alarm.
These features help you identify the trigger alarm(s) and areas of immediate danger to avoid under alarm conditions. After one minute if a dangerous condition persists all units will go back into alarm the initiating alarm will sound for 50 seconds. This 10-second/50-second alarm
pattern will keep repeating until the air is cleared and the immediate danger has passed.
MOVE AWAY from areas where you hear trigger alarms sounding if at all possible. DO NOT IGNORE the trigger alarm(s), and be aware that an extremely
dangerous situation exists at that location(s) in your home.
Trigger Alarm Locator
: all alarms will sound for 10 seconds, then just
Latching LED Alarm Indicator
The Latching LED Alarm Indicator activates automatically, and helps you identify the original trigger alarm(s) in an interconnected series after a smoke or CO event.
CO Alarm - after a CO alarm condition, the single RED light on the triggering alarm(s) blinks 3 times every 10 seconds until manually reset.
Smart Quiet™ for Low Battery Alert
You can silence the Low Battery Alert for up to 10 hours by pressing and releasing the Smart Button. The sensor remains active. This allows you and your family to go back to sleep or gives you time to purchase a replacement battery. It is important that you replace the battery as soon as possible to continue your protection!
4
UNDERSTANDING THE ALARM
CONDITION
AC power is present
Standby condition
Push-to-Test
(Local Test Only)
Press-and-Hold
(Local and Interconnect Tests)
Smart Quiet™ Low-Battery #1
Smart Quiet™ Low-Battery #2
Fault condition
Local CO condition is detected
HORN
Horn beeps once per minute
Horn beeps once per minute
Horn sounds two quick beeps every minute
Horn sounds 4 short tone patterns every 5 seconds
Local CO condition is latched
Quick Quiet™ CO Reset is activated
Remote signal is received from another CO alarm
DANGER
PROBLEM
GREEN light is not on.
Alarm does not sound and lights do not flash when unit(s) is tested.
NOTE: Push and hold
Smart Button for at least 5 to 10 seconds if unit does not
sound!
SOLUTION
1. Alarm may be functioning properly on DC (battery)
2. Check AC power supply at fuse box or breaker panel.
3. Alarm wiring is improperly connected. Have wiring
1. Check that AC power is turned on (GREEN light ON);
2. Turn off power. Remove alarm from mounting plate
3. Clean alarm (see “Cleaning” on page 8).
Horn sounds 4 short tone pat­terns every 5 seconds
TROUBLESHOOT
Always turn off power at main fuse box or circuit breaker before taking troubleshooting action.
power if YELLOW light flashes once per minute.
checked by a licensed electrician. Retest the alarm.
check that a good battery is inserted correctly in the battery compartment; check that the battery door is tightly closed.
and check that connector plug is securely attached.
Interconnected smoke, heat, or CO alarms do not sound when Button is pushed to test units
.
Smart
1. Press and hold the Smart Button longer until the second set of two quick beeps sounds to initiate the remote test.
2. Check that remote alarms are receiving power and functioning properly
3. Alarm interconnect circuit problem. Replace and retest.
4. On DC (battery powered) interconnected alarms, remove alarm from mounting bracket and check that the connector plug is securely attached.
5. On an interconnected series with both AC and AC/DC powered units, wiring may have been improperly connected. Have wiring checked by a licensed electrician. Retest all alarms in the series.
5
LED AND HORN PATTERNS
LIGHTS
GREEN light ON
YELLOW light blinks once per minute
YELLOW light blinks during horn ramp-up.
RED blinks 4 times right after horn sounds.
YELLOW light blinks during horn ramp-up.
RED blinks 4 times right after horn sounds.
YELLOW light flashes 2 times per minute after horn beeps
YELLOW light flashes 3 times per minute after horn beeps
YELLOW light flashes constantly after horn beeps
RED light flashes 4 times right after horn
SMART BUTTON KEY
Quick push activates a local Push-to-Test sequence
Press and RELEASE button before you hear the third chirp. The system will perform a single local test cycle.
Press and HOLD button. The system will perform a single local test cycle, then repeat the interconnect test until you release the button.
Quick press will eliminate the low-battery warning for about 10 hours
Smart Button WILL NOT silence the low battery chirp! Replace battery immediately!
Press to check the alarm again. Replace alarm if it remains in the fault condition.
Quick press activates CO Reset
RED light flashes 3 times every 10 seconds
RED light flashes 1 time every 10 seconds
WARNING
DO NOT disconnect the battery or AC power to quiet an unwanted alarm. This will remove
your protection. Use Quick Quiet™ False Alarm Control by pushing the Smart Button.
PROBLEM
The horn beeps once, then two beeps, then three beeps, pauses, and then sounds the full alarm when using the Smart Button to test.
Quick press erases the CO latched signal
Quick press activates Smart Quiet™ Trigger Alarm locator for Model COE and COEA alarms.
SOLUTION
The alarm is operating properly. The Firex patented Horn Ramp-Up feature lets you start the test sequence and move away from the unit before the full alarm horn sounds.
Alarm sounds; no hazard present.
The alarm beeps once a minute and YELLOW light flashes.
Horn beeps twice a minute and YELLOW light flashes.
For Technical Support: PH: (800) 445-8299 Email: technical service@invensys.com Website: www.icca.invensys.com/firex
Take Emergency Safety Actions in all alarm situations! If no hazard proves to be present: Test the alarm to check for proper functioning. Clean the alarm. (See TESTING AND MAINTENANCE.) Check that the alarm is placed properly. (See AGENCY RECOMMENDATIONS FOR ALARM PLACEMENT.)
The battery needs to be replaced. Turn off power and replace the battery. (See “REPLACING THE BATTERY” in “TESTING AND MAINTENANCE”.) Push the Smart Button to temporarily quiet the low battery signal for 10 hours.
Push the Smart Button to allow alarm to reset and self test. If fault signal continues, alarm is no longer providing protection and must be replaced.
6
IMPORTANT SAFETY INFORMATION
CO Home Safety Tips
CO poisoning is often caused by equipment failures due to poor maintenance, prod-
uct defects, and damaged parts. The following tips can help prevent CO within your home:
1. Have all fuel-burning appliances inspected and cleaned yearly by a qualified serv­ice technician. The furnace, water heater, and stove are some of the leading sources of CO.
2. Clean fireplace vents and chimney regularly. A blocked chimney could cause a backdraft of CO into the home. Do not seal chimney. This will cause a backdraft of CO into the home.
3. Do not seal a draft hood or exhaust vent to any appliance. This will trap dangerous CO inside the house.
4. Do not close off or confine your fuel-burning appliances in a closed area. They need plenty of ventilation to operate properly.
5. Do not use liquid propane (LP) or charcoal grills or operate any gasoline powered equipment indoors.
6. Allow for plenty of ventilation when using a kerosene heater. Do not use in small areas.
Preventive maintenance, common sense, and a CO detection device are some of the best methods of preventing CO poisoning. However, a dangerous situation can happen to anyone at any time.
The following list illustrates some danger signs of CO presence.
1. Soot and dirt build-up seeping out of chimney or other exhaust vents.
2. A mostly yellow (rather than clear blue) burner flame or pilot flame in gas appliances.
3. A draft of air coming from an appliance, chimney, or vents.
4. Car idling in an open or closed attached garage, or near a home.
If you have flu-like symptoms or suspect CO poisoning, seek medical assistance immediately!
Symptoms of Carbon Monoxide Poisoning
CO poisoning has many symptoms. Some are very similar to the flu, the effects of intoxication, or drug usage. In many CO cases, people feel ill and stay home to rest. This only compounds the CO poisoning because they stay in the home where CO is present.
As CO levels rise, the symptoms become more extreme. At low levels people will suffer headaches and mild nausea. At higher levels unconsciousness, heart failure, and even death can occur. The following symptoms are related to CARBON MONOX­IDE POISONING and should be discussed with ALL members of the household:
Mild Exposure: Slight headache, nausea, vomiting, fatigue (often described as flu-like symptoms).
Medium Exposure: Severe throbbing headache, drowsiness, confusion, fast heart rate.
Extreme Exposure: Unconsciousness, convulsions, cardio-respiratory failure, death.
Many cases of reported carbon monoxide poisoning indicate that while victims are aware they are not well, they become so disoriented they are unable to save themselves by either exiting the building or calling for assistance. Also, young children, the elderly, and household pets may be the first affected by CO poisoning.
The important factor with any CO poisoning, however, is time. At high levels, CO can cause death in just minutes. At lower levels, it could take from hours to days of con­stant CO exposure to have the same life-threatening effect.
The chart below illustrates the symptoms of CO poisoning by concentration of CO and its effect over time.
Slight headache within 2-3 hours.
Frontal headache within 1-2 hours.
Dizziness, nausea, and convulsions within 45 minutes. Insensible within 2 hours.
Headache, dizziness, and nausea within 20 minutes. Death within 2 hours.
Headache, dizziness, and nausea within 5-10 minutes. Death within 30 minutes.
Headache, dizziness, 1-2 minutes. Death in less than 15 minutes.
Death in less than 3 minutes
1000200 300 400 500 600 700 800 900 1000 1100 1200
Concentration of CO in air (ppm)
Conditions That Can Cause CO Levels to Change.
The following conditions can result in transient CO situations in the home.
1. Excessive spillage or reverse venting of fuel burning appliances caused by outdoor ambient conditions, such as:
a. Wind direction and/or velocity, including high gusts of wind. Heavy air in the
vent pipes (cold/humid air with extended periods between cycles).
b. Negative pressure differential resulting from the use of exhaust fans.
c. Simultaneous operation of several fuel burning appliances competing for limited
internal air.
d. Vent pipe connections vibrating loose from clothes dryers, furnaces, or
water heaters.
e. Obstruction in the vent pipe or unconventional vent pipe designs which can
amplify the above situations.
2. Extended operation of unvented fuel burning devices (range, oven, fireplace, etc.).
3. Temperature inversions which can trap exhaust gasses near the ground.
4. Car idling in an open or closed attached garage, or near a home.
7
TESTING AND MAINTENANCE
Testing
Stand-alone units: Test each alarm regularly to be sure it is operating properly.
Interconnected units: Test each alarm in an interconnected system regularly.
• The Smart Button accurately tests all functions. DO NOT use an open flame to test this CO alarm. You may ignite and damage the smoke alarm or your home.
• Test alarms weekly and upon returning from vacation or when no one has been in the household for several days.
IMPORTANT! Refer to “Understanding the Alarm LEDs and Horn Patterns” chart so you understand how to tell if your alarm is operating properly.
Maintenance and Care
DANGER
ELECTRICAL SHOCK HAZARD. Turn off power at main service panel by removing fuse or switching appropriate circuit breaker to OFF position BEFORE cleaning CO alarm or replacing the battery.
Cleaning
IMPORTANT: Do not attempt to remove the cover or clean inside the alarm. THIS WILL VOID YOUR WARRANTY.
Clean the cover at least once a month using the soft brush or wand attachment to a vacuum cleaner. Be sure all the vents are free of debris. If necessary, use a damp cloth to clean residual dirt. Do not use abrasive cleansers or spray the alarm with cleaning agents or waxes, especially cleaners containing ammonia. These liquids may impair the performance of sensors. Do not submerge the alarm in water.
Replacing the Battery (Model COE and COE-B)
Replace the battery at least once a year or immediately when the low battery warning activates. If a replacement battery is not immediately available, push the Smart Button to silence the Low Battery Warning for approximately 10 hours. If alarm does not silence, replace the battery immediately.
Use only Eveready 522, Duracell MN 1604 or Ultralife U9VL-J batteries! DO NOT USE ANY OTHER TYPE OF BATTERY. DO NOT USE RECHARGEABLE BATTER­IES. Refer to the Installation section if you are not familiar with the proper way to install a new battery.
WARNING
WARRANTY INFORMATION
5-YEAR LIMITED CO ALARM WARRANTY
Invensys Controls Americas warrants to the original consumer purchaser each new CO alarm to be free from defects in material and workmanship under normal use and service for a period of five (5) years from the date of purchase. Invensys Controls Americas agrees to repair or replace, at its option, any defective CO alarm provided it is returned with postage prepaid and with proof of purchase date to Invensys Controls Americas. This warranty does not cover damage resulting from accident, misuse or abuse or lack of reasonable care of the product. This warranty is in lieu of all other express warranties, obligations or liabilities. THE IMPLIED WAR­RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF FIVE (5) YEARS FROM THE DATE OF PURCHASE FOR THE CO ALARM. Some states do not allow limitations on how long an implied warranty lasts, so the above limitations may not apply to you. IN NO CASE SHALL INVENSYS CONTROLS AMERICAS BE LIABLE FOR ANY INCIDENTAL OR CON­SEQUENTIAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY ITS NEGLIGENCE OR FAULT. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other legal rights which vary from state to state. This product meets all the requirements of U.L. Standard 2034.
Where to send your alarm for service
Not attempt to repair this combination alarm. Doing so will void your warranty. If the alarm is not operating properly, see “Troubleshooting.” If you must
return an alarm under warranty, send the alarm in a well-padded envelope with postage prepaid, a note describing the nature of the difficulty, and proof of date of purchase to:
In U.S.: In Canada:
Invensys Controls Americas Invensys Controls Americas
28C Leigh Fisher Blvd. Service de réparation El Paso Texas 79906 3505 Laird Road - Unit #14 United States of America Mississauga Ontario L5L 5Y7
If the CO alarm is no longer under warranty, have a licensed electrician replace the CO alarm immediately with a comparable Firex brand alarm.
For Technical Support: Phone: (800) 445-8299 Email: technicalservice@invensys.com Website: www.icca.invensys.com/firex
Controls Americas
191 E. North Avenue Carol Stream Illinois 60188 ©2006 Invensys Controls Americas 110-1125C
8
Loading...