FIREtec FTEN1, FTEN2, FTEN4 Quick User Manual

INDICATORS COLOUR INDICATION
COMMON FAULT Yellow On when a fault condition has occurred, or if
no other fault Led is on, this indicates 24v auxiliary fuse failure.
COMMON FIRE Red On when a FIRE condition has occurred or
EVACUATE has been operated.
ZONES 1-4 FAULT Yellow Flashes if a detector is removed from its base,
ZONES 1-4 FIRE Red Illuminated during a FIRE condition in this
zone. Flashes when a device is being tested during walktest.
SUPPLY Green Illuminated while power is being supplied to
the panel.
SUPPLY FAULT Yellow Flashes during a mains or battery supply
failure.
ALARM FAULT/ Yellow Flashes when a fault on the sounder wiring DISABLED occurs. Illuminated if alarm lines are disabled.
DISABLED Yellow Illuminated when Zones and/or alarm are
disabled. The specific zone or alarm fault led will also be lit.
TEST Yellow Illuminated when Walktest function selected.
SYSTEM FAULT Yellow Illuminated if the panel has malfunctioned and
an attempt to reset the system automatically has been made. Flashes if an error in the system software has been detected – Requires attention.
ALARM SILENCED Yellow Illuminated if the sounders on the alarm
circuits during a fire/evacuation condition have been switched off or silenced.
EARTH FAULT Yellow Will flash if a fault occurs with the earthing.
QUICK USER GUIDE FOR 1, 2 & 4 ZONE FIRE PANELS
FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE
FIRE DETECTION AND ALARM CONTROL PANELS
INSTALLATION INSTRUCTIONS
USER GUIDE
LOG BOOK
tec tec
EN54EN54EN54EN54
FIREFIREFIREFIRE
Document EN02/08.02
PANEL SPECIFICATIONS
1. Certified to EN54 Pt2: 1997 and EN54 Pt4: 1997, and is suitable for National installation requirements.
2. Five coded push buttons to control :­RESET, EVACUATE, SILENCE ALARMS, SILENCE BUZZER, LAMP TEST,
WALK TEST, DISABLE and EXIT
3. LED Indicators:- General fire - General fault - 1/2/4 zone fire - 1/2/4 zone fault - Supply - Supply fault – Disabled - Alarm fault/disabled ­Test - System fault - Alarm silenced - Earth fault.
4. Zone end of line component that is polarised - Red end to Zn+ and Black end to Zn-.
5. Two sets of auxiliary volt free contacts for fire and fault - Max. current per contact set 2A at 30V dc.
6. Internal sounder - Minimum level 50dBA @ 1m.
7. Features: USER ZONE AND ALARM DISABLE USER LAMP TEST ZONES MONITORED FOR OPEN CIRCUIT, SHORT CIRCUIT AND
DETECTOR REMOVAL ALARM OUTPUTS MONITORED FOR OPEN AND SHORT CIRCUIT AC AND DC POWER SUPPLY MONITORED WALK TEST OPERATION EARTH LEAKAGE DETECTOR AND SYSTEM FAULT MONITORING
1 & 2 zone 4 zone
8 Two sets of alarm outputs - 300mA max 1A max
total alarm output current
9. Power supply - Input 230v +10% -15% ac i/p 50Hz Battery - Sealed lead acid 12v7Ahr
10. Auxiliary fused output 250mA (fuse monitored) 24v
11. Class change input (CC) YES
12. Pulse Alert input (BA) YES
13. Open collector - FIRE output (CF) YES
14.
Volt free relay - FAULT output
YES
S
YSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
3
33
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
T
ESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERAL FAULTGENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIREGENERAL FIRE
F
AULT /DISABLE
/ TEST
F
AULT /DISABLEFAULT / DISABLE
/ TEST/ TEST
FIREFIREFIRE
SILENCE B
UZZER
SILENCESILENCE B
UZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMP TESTLAMPTESTLAMP TEST
RESETRESETRESET
RESETRESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
E
N54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
END OF LINE COMPONENT ON LAST DETECTOR
Zone +Ve RED
Zone -Ve BLACK
AUX 2AUX 1
N/C
N/C
COM
COM
N/O
N/O
AL 2
ZN 1 ZN 2 ZN 3 ZN 4
+
++
+
+
+
D
C
Zone -Ve BLACK
EOL COMPONENT ON ANY UNUSED ZONE
AUX 2
FLT 1
FLT 2
N/C
N/C
N/C
COM
COM
COM
COM
N/O
N/O
N/O
N/O
AL 2
AL1
ZN 1 ZN 2 ZN 3 ZN 4 +
++
+
+
+
DD
D
C
TYPICAL PANEL WIRING
NO SPURS ALLOWED
E
END OF LINE RESISTOR ON LAST SOUNDER
AUX 2AUX 1
FLT 1
FLT 2
N/C
N/C
N/C
COM
COM
COM
COM
N/O
N/O
N/O
N/O
AL 2
ZN 1 ZN 2 ZN 3 ZN 4
+
++
BA
CF
CC
COM
D
D
SSS
C
tec tec
EN54EN54EN54EN54
FIREFIREFIREFIRE
Coded Push Buttons
LED indicators
This manual provides the necessary guidance for the correct installation and commissioning of the FIREtec EN54 1, 2 & 4 zone (EN54 Pt2: 1997 and EN54 Pt4: 1997 approved) fire panels. Persons carrying out system design and installation should be competent and familiar with the relevant code of practice relating to the installation of fire detection and alarm systems within buildings.
Key
NO Normally Open Contact NC
Normally Closed Contact
C Common Contact
AL Alarm Line CC
Class Change Input
BA Pulse Alert Input
CF Common Fire Output COM
Common 0v
AUX Auxiliary Outputs
AUX
BATT
AC AC
Z1
COMBACC
CF
Z2 Z3 Z4
AL1 AL2
AUX1
NC
COM
NO
AUX2FAULT 1
FAULT 2
NC
COM
NO
NC
COM
NO
NC
COM
NO
Schematic for One, Two and Four Zone Firetec Panels
3
3
3
3
INSTALLATION PROCEDURE
The following instructions must be followed, however it is recommended that the installation is delayed until all the building or maintenance work is completed. Building work near the panel may result in damage.
Remove the fire panel from the packaging, but retain this for the future storage of panel parts during installation.
A) To remove the front – remove the screw located
under the bottom edge of the panel using Allen key provided, pull the bottom edge out then lift up. Store the panel front face down in the packing box tacking care of the led light guides on the back.
B) Box Mounting - Once the cable entry routes have
been decided, remove the appropriate knockouts situated on the top and back of the box by carefully knocking out from the inside outwards. Note the entry point for the mains cable is through a knockout which is located at the back of the back box – see below. Ensure that the back box is securely and flush fitted to the fabric of the building. The box should be mounted at such a height that the push buttons and LED’s are at eye level. When mounting the box take care not to damage the pcb in the box. Remove any debris.
C) Feed the required cable into the box then make
off a reasonable working length, (identify each of the cables).
Conduct all installation tests on the cables with the detectors and other electronic devices disconnected. Failure to
observe this could result in serious damage to the detectors etc.
SYSTEM DESIGN GUIDE
When installing the system the designer should ensure:-
1. The installation complies with the relevant code of practise for installations.
2. The mains supply is switched via a double pole isolator.
3. All detectors are sighted in accordance with British standard recommendations.
4. That detector and alarm sounder circuits have NO SPURS.
5. It is recommended that the cabling used for detector and alarm circuits is 1.5mm
2
Fire Protected, 2-core + screen complying with
BS7629, BS7846 and BSEN60702 (BS6207).
6. That detectors and callpoints used are compatible with the panel, and that only devices recommended by the supplier are used.
7. The correct end of line component is used on the detection and alarm circuits (including those not used), These components must be fitted after the last detector, callpoint or sounder.
8. The total current consumption for each zone of detectors does not exceed 4mA
9. The detector bases are connected as shown and must be fitted with a diode for detector removal fault.Otherwise the removal of a detector from a base will prevent subsequent detectors and call-points on the zone from functioning.
10. The sounders must have a series blocking diode with suppression components fitted that only allows current to flow through the sounders when the control panel pcb is wired as shown.
11. Sounder current consumption should not exceed the panel maximum. The maximum load for each set of contacts is 1A, however the total sounder current should not exceed that shown in table for panel specification.
12. That if a 24V auxiliary output is used for powering an auxiliary circuit, the battery standby period is checked to ensure that the maximum duration required for the installation can still be achieved.
E
NSURE THAT MAINS SUPPLY
IS SWITCHED WITH A DOUBLE
POLE ISOLATOR OF A MINIMUM
R
ATING OF 3AMPS
L N E
NO SPURS ALLOWED
END OF LINE COMPONENT O
N LAST DETECTOR
Zone +Ve RED
Z
one -Ve
BLACK
DD
OUT+
OUT-
IN+IN-
L1 IN
-R
L1 OUT
L2
DIODE
L1 IN
-R
L1 OUT
L2
DIODE
END OF LINE
DEVICE
KNOCKOUT FOR MAINS CABLE ENTRY POINT IS AT REAR OF BACK BOX
E
KNOCKOUTS FOR FIELD WIRING ENTRY
POINTS ON TOP AND BACK OF BOX
L
1- REMOVE SCREW
2- PULL BOTTOM OUT
3- LIFT UP
A
llen key
KNOCKOUT FOR MAINS CABLE ENTRY POINT IS AT REAR OF BACK BOX
KNOCKOUTS FOR FIELD WIRING ENTRY
POINTS ON TOP AND BACK OF BOX
3
3
3
3
INSTALLATION PROCEDURE (continued)
D) Connect the cables from the zones (detectors)
and alarms (sounders) to the pcb as shown in diagrams, ensuring that there are
NO spurs from the main circuit. Fit the end-of-line component onto the last detector or call-point of each zone circuit. The end-of-line resistor used on the alarm circuit can be connected either way round. For any unused circuits, leave the end-of-line component / resistor in the terminal block located on the pcb.
E) The panel has several optional inputs and
outputs.
• AUX 1 & 2-Are volt free relay contacts which change over when the alarm sounds –Used for switching auxiliary equipment.
• AUX 24V - a 24v DC power supply used to power auxiliary equipment.
• CLASS CHANGE- wire a switch between COM and CC terminals to make the sounders operate.
• PULSE ALERT- wire a switch to terminals BA and COM to make the sounders pulse.
• FAULT- Volt free changeover relay contacts that duplicates the common fault indicator. Used to drive a remote fault indicator.
TYPICAL PANEL WIRING
NO SPURS ALLOWED
E
ND OF LINE COMPONENT
ON LAST DETECTOR
Zone +Ve RED
Zone -Ve
BLACK
EOL COMPONENT O
N ANY UNUSED ZONE
TYPICAL ALARM WIRING
AL2 WIRED AS AL1
END OF LINE RESISTOR ON LAST SOUNDER
AUX 2AUX 1
FLT 1
REMOTE INDICATOR
FLT 2
N/C
N/C
N/C
N/C
COM
COM
COM
COM
N/O
N/O
N/O
N/O
AL 2
AL1
F4
1A (T)1A(T)
F3
ZN 1 ZN 2 ZN 3 ZN 4 +
++
-
+
+
+
+
AUX 24V O/P
BA
CF
CC
COM
F5 250mA(T)
F6 6.3A(T)
TF AC
BATT
MAINS
CABLE ENTRY
CABLE CLAMP
FUSE F6 = BATTERY SUPPLY (6.3A) FUSE F5 = AUXILLIARY OUTPUT (250mA) FUSE F4 = ALARM CIRCIUT 1 (1A) FUSE F3 = ALARM CIRCUIT 2 (1A)
BATTERY
L
N
250Va.c 1A(T) 20*5mm FUSE
CONTROL PCB
EARTH
DD
D
SSS
C
Key: D = Detector
C = Call-point S = Sounder
- - + +- - + +
IN-
IN-
IN+
IN+
OUT+
OUT+
OUT-
OUT-
BELL
2ND SND
1ST SND
COM
SOUNDER
To sounder circuit
To sounder circuitTo sounder circuit
DETECTOR AND CALL POINT CONNECTIONS
SOUNDER AND BELL CONNECTIONS
LEVEL 2a USER CODE - 3545
Enter this code to gain access to the top row of instructions. A small yellow led to the left of the word RESET will light indicating that this row of functions can now be activated by pressing the appropriate button above it. The functions are as follows:-
1. RESET - is used to return the fire alarm system to
the normal clear condition, resetting any fire alarm detectors, silencing all sounders and resetting other devices connected to the panel.
2. SILENCE BUZZER – Causes the internal buzzer to
be switched off during a fire or fault condition. Any subsequent fault or fire activation on another zone will cause the buzzer to be re sounded.
3. SILENCE ALARMS - Used to turn off the external
alarm sounders after a fire activation the Alarm Silenced led is also illuminated. The panel will however continue to indicate the fire condition and the internal buzzer will continue to bleep. Any subsequent fire activation on another zone will re-sound the fire alarm sounders.
PANEL COMMISSIONING
The total system should be tested in accordance with the National requirements. Summary as follows:-
1. The complete installation should be checked to ensure that all the cables have been correctly installed in accordance with the National regulations.
2. All the cables must be insulation tested with high voltage test sets prior to the sounders and bases / detectors being connected.
3. The earth to the panel must be tested.
4. All detectors and sounders must be correctly wired, with no spurs, and correctly fitted to the bases.
5. End of line components / resistors (of the correct value) must be fitted to the end of each circuit.
6. Connect the battery and switch on the mains supply.
7. Test the panel as described in the USER GUIDE
8. Test every detector, call-point and sounder.
9. HAND-OVER TO THE USER - as follows:­a)
Teach the user how to operate the panel and test the system, using the USER GUIDE
b)
Issue drawings of the wiring.
c) Issue the appropriate certificates.
FLUSH MOUNTING BEZEL
An optional flush mounting bezel is available, which allows the panel to be semi-flush to the wall up to the front plastic cover.
1. Remove the front cover. Remove the knockouts to be used
2. Note – the bezel has edges on the two sides and the bottom, the top has no edges to allow full access to the cable entries.
3. Slide the bezel over the metal box and fix in place (with the screws provided) through the holes near the transformer and the pcb.
4. Slots in the bezel allow the depth to be adjusted by 22mm
5. Hole size = 298mm x 260mm, max hole depth = 56mm. The bezel width = 20mm.
6. Fix the box into the hole using the normal mounting holes, the adjust the bezel back to the wall, tighten the screws taking care not to damage any components.
7. Continue the installation as normal.
USER GUIDE FOR 1, 2 & 4 ZONE FIRE PANELS
The panel supplied is a modern highly sophisticated fire control panel utilising the latest technology to combine performance and reliability with ease of operation.
PANEL BASICS
The panel is controlled by the five push buttons mounted on the front. To gain access to the panels functions either of two 4 digit USER CODE’s must be entered via the push buttons.
- This is used to prevent unauthorised access.
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
22111
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
A
LARM FAULT/
D
ISABLED
A
LARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
A
LARM
SILENCED
A
LARMALARM
SILENCEDSILENCED
G
ENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
R
ESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE B
UZZER
SILENCESILENCE B
UZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
G
ENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /
TEST
FAULT/ DISABLEFAULT / DISABLE /
TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
E
ARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
TESTTESTTEST
ALARM S
ILENCED
ALARMALARM S
ILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
S
ILENCE
B
UZZER
S
ILENCESILENCE
B
UZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
E
XITEXITEXIT
EVACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
R
ESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
S
ILENCE
BUZZER
S
ILENCESILENCE
BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
ADDITIONAL INSTRUCTIONS FOR ELECTROMAGNETIC COMPATIBILITY
When used as intended this product complies with EMC Directive (89/336/EEC) and the UK EMC regulations 1992 (SI 2372/1992) by meeting the limits set by the standards, EN 55022: 1998 and EN 50130-4 1996. The following installation guidelines must be followed.
1. External cables must be connected using the knockouts provided.
2. When routing cables inside the product they must be:-
a)Kept as short as possible. b)Routed close to the housing c)Kept as far as possible from the electronics.
Any modifications other than those stated in this manual, or any other use of this product may cause interference and it is the responsibility of the user to comply with the EMC and Low Voltage Directive.
• CF -an open collector current limited output to a remote indicator which duplicates the common fire indicator. Connect the +ve wire to CF terminal and -ve to COM.
Connect the mains supply cable to the fused terminal block, using the knockout in the bottom or back
nearest to it, and keeping it away from the other wiring. Fit the 12v battery into the bottom right hand corner of the box and connect the red and black wires.
It is important to ensure correct polarity of battery wires. Switch on the mains supply. Commission the
system as described below.
3. WALK TEST - This function allows the user to test fire detectors and callpoints on the system.
To put a zone into Walktest – Enter user code
5344. Press 3 – WALKTEST. The FAULT led of the first available zone flashes quickly.
Press 4 to select this zone for testing. This causes the fault led of the selected zone to flash slowly – showing that this zone is in test along with the test led being illuminated.
If a zone is in Walktest, the TEST led is lit and the FAULT led of the corresponding zone flashes slowly.
PERFORM WALKTEST
Walk round and test detectors and/or call points in this zone. When a device is triggered the sounders will sound a few seconds and then silence. The relevant FIRE zone indicator on the panel will be flashed.
DESELECT WALKTEST
When all of the detectors and/or call points have been tested in the zone, re-enter the access code (5344), Press 3 and then Press 4 to deselect this zone. The zone in Walktest must be deselected before another zone can be put into Walktest. Only one zone can be put into Walktest at any one time, all other zones operate as normal.
SELECT NEXT WALKTEST Re-enter the access code (5344), Press 3 and then
Press 3 to advance to the next zone that is available
for Walktesting. The FAULT led of the next zone flashes quickly.
Press 4 to select zone for
walktesting. Perform Walktest.
Press 5 To exit from this menu.
4. EVACUATE – This is used to activate the fire
alarm sounders. But does not trigger any device connected to the auxiliary contacts (Typically a digital communicator and/or heating/ventilation controls) The internal buzzer will sound and the GENERAL FIRE indicator will be illuminated.
5. LAMP TEST - This option illuminates all the LED’s
and twice beeps the internal buzzer. After 3 seconds the LED’s revert back to their previous state and the panel to its normal condition.
LEVEL 2b USER CODE 5344
Enter this code to gain access to the bottom row of instructions. The lower yellow led will light indicating that this row of functions can now be activated by pressing the appropriate button above it. The functions are as follows:-
1.
RESET - is used to return the fire alarm system to the normal clear condition, resetting any fire alarm detectors, silencing all the sounders, and resetting other devices connected to the panel.
2.
SILENCE BUZZER – Causes the internal buzzer to be switched off during a fire or fault condition. Any subsequent fault or fire activation on another zone will cause the buzzer to be re sounded.
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
22111
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
A
LARM FAULT/
D
ISABLED
A
LARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
A
LARM
SILENCED
A
LARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
E
ARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2211
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ D
ISABLED
ALARM FAULT/ALARM FAULT/ D
ISABLEDDISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/
TEST
F
AULT/ DISABLEFAULT / DISABLE
/
TEST/ TEST
FIREFIREFIRE
SILENCE B
UZZER
SILENCESILENCE B
UZZERBUZZER
S
ILENCE A
LARMS
S
ILENCESILENCE A
LARMSALARMS
E
XITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
1
1
S
YSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
2211
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
T
ESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/TEST
F
AULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE A
LARMS
SILENCESILENCE A
LARMSALARMS
E
XITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
1
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONESZONES
22211
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ D
ISABLED
ALARM FAULT/ALARM FAULT/ D
ISABLEDDISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/
TEST
F
AULT/ DISABLEFAULT / DISABLE
/
TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
S
ILENCE A
LARMS
S
ILENCESILENCE A
LARMSALARMS
EXITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
E
N54EN54EN54
FIREFIREFIRE
1
S
YSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONES
2211133444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
T
ESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
G
ENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /
TEST
FAULT/ DISABLEFAULT / DISABLE /
TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
ZONES
3
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
3
33
444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
TESTTESTTEST
ALARM S
ILENCED
ALARMALARM S
ILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
S
ILENCE
B
UZZER
S
ILENCESILENCE
B
UZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
E
XITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
R
ESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
S
ILENCE
BUZZER
S
ILENCESILENCE
BUZZERBUZZER
1
11
tec tec
E
N54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
22111
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
A
LARM FAULT/
D
ISABLED
A
LARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
S
ILENCE
BUZZER
S
ILENCESILENCE
BUZZERBUZZER
SILENCE A
LARMS
SILENCESILENCE A
LARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
1
11
tec tec
E
N54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
S
YSTEM FAULTSYSTEM FAULTSYSTEM FAULT
E
ARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
T
ESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/TEST
F
AULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
S
ILENCE
A
LARMS
S
ILENCESILENCE
A
LARMSALARMS
EXITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
FRONT PANEL INDICATORS- show the
following:-
1.
GENERAL FIRE > red led – illuminates during a fire or evacuation condition.
2. ZONES 1- 4 FIRE > red led’s - Illuminate when a fire occurs on the relevant zone. The GENERAL FIRE led will also be illuminated at the same time. The fire led will flash during Walktest condition.
3.
GENERAL FAULT> yellow led - illuminates when any a fault with the panel has occurred. The specific FAULT led is flashed, or if no other FAULT led is on, this indicates an auxiliary fuse failure.
4. ZONES 1-4 FAULT > yellow led’s – Flashes the relevant zone led during a fault condition but is illuminated to indicate a zone that is disabled or is in Walktest. When in the Walktest menu the appropriate led flashes quickly.
5.
SUPPLY > green led - Illuminated all the time.
6.
SUPPLY FAULT > yellow led – Flashes indicating a power supply fault has occurred. Check mains and battery connections as well as pcb fuses.
7. DISABLED > yellow led - illuminates when a fire zone has been isolated, along with the relevant zone fault led on steady.
8.
ALARM FAULT/DISABLED > yellow led – Flashes when the panel detects a fault in the sounder wiring. Common fault also illuminated. Is illuminated when the alarms are disabled along with the disabled led.
9.
TEST > yellow led - illuminates when the panel is set to walktest mode.
10.
SYSTEM FAULT > yellow led - illuminates if the panel has been restarted by the supervisory circuit or is flashed if a corruption of the software in the
microcontroller has been detected.
11.
ALARM SILENCED > yellow led – Illuminates when the sounders on the alarm circuits have been switched off during a fire/evacuation – The alarm condition still remains.
12.
EARTH FAULT > yellow led – flashes if a fault with the earthing of the system has occurred.
4. DISABLE - If a fault occurs or work is being carried out on a zone or alarm circuit, it is possible to disable the zone(s) and alarm circuit from the system without affecting the other zones. If a zone or alarm is disabled, the DISABLED led and the FAULT led(s) of the corresponding zone(s) or alarm will be lit.
TO DISABLE A ZONE OR ALARM
Enter user code 5344. Press 4 – DISABLE. The FAULT led of zone 1 (if it is not in Walktest) flashes quickly.
Press 3 to advance to next zone/alarm
OR
Press 4 to disable the appropriate zone or alarm. This causes the FAULT led of the selected zone/alarm to be illuminated – showing that it is disabled along with the DISABLE led being illuminated.
Press 5 To exit from this menu.
TO RE-ENABLE DISABLED ZONES OR ALARMS
Enter user code 5344. Press 4 – DISABLE. The FAULT led of zone 1 flashes quickly.
Press 3 to advance to appropriate zone. Press 4 to re-enable a zone/alarm. If a zone/alarm is being re-enabled, the illuminated FAULT led of the re-enabled zone is cleared and moves to the next zone/alarm.
Press 5 to exit from this menu.
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2211
3
33
444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
TESTTESTTEST
ALARM S
ILENCED
ALARMALARM S
ILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
1
11
tec tec
E
N54EN54EN54
FIREFIREFIRE
1
1
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
221
1
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
A
LARM FAULT/
D
ISABLED
A
LARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
A
LARM
SILENCED
A
LARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
G
ENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
F
IREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
1
1
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONES
2211133444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
A
LARM FAULT/
DISABLED
A
LARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
A
LARM
SILENCED
A
LARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
E
XITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
E
N54EN54EN54
FIREFIREFIRE
ZONES
3
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONES
2211133444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
TESTTESTTEST
A
LARM
S
ILENCED
A
LARMALARM
S
ILENCEDSILENCED
G
ENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /
TEST
FAULT/ DISABLEFAULT / DISABLE /
TEST/ TEST
FIREFIREFIRE
SILENCE B
UZZER
SILENCESILENCE B
UZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
E
XITEXITEXIT
EVACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
ZONES
3
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ DISABLED
ALARM FAULT/ALARM FAULT/ DISABLEDDISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE /TEST
FAULT/ DISABLEFAULT / DISABLE /TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
SILENCE ALARMS
SILENCESILENCE ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
Thomas BettsThomas Betts
Thomas Betts
Z
ONESZONESZONES
222111
333
444
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE / TEST
FAULT / DISABLEFAULT / DISABLE / TEST/ TEST
FIREFIREFIRE
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
Thomas BettsThomas Betts
Thomas Betts
S
UPPLYSUPPLY
ZONESZONESZONES
222111
3
33
444
SUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLED
A
LARM FAULT/
DISABLED
A
LARM FAULT/
DISABLEDDISABLED
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE / TEST
FAULT / DISABLEFAULT / DISABLE / TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
RESETRESET
RESETRESET SILENCE
BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIRE
T
SUPPLY FAULT
ALARM FAUL
T/
SYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
22111
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE / TEST
FAULT / DISABLEFAULT / DISABLE / TEST/ TEST
FIREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
RESETRESET
RESETRESET SILENCE
BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULT
ZONESZONESZONES
222111
333
444
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE / TEST
FAULT / DISABLEFAULT / DISABLE / TEST/ TEST
FIREFIREFIRE
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
Thomas BettsThomas Betts
Thomas Betts
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/ D
ISABLED
ALARM FAULT/ALARM FAULT/ D
ISABLEDDISABLED
TESTTESTTEST
ALARM SILENCED
ALARMALARM SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
G
ENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/TEST
F
AULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
F
IREFIREFIRE
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
S
ILENCE ALARMS
S
ILENCESILENCE ALARMSALARMS
EXITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE BUZZER
SILENCESILENCE BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
ZONESZONES
222111
33
44
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE / TEST
FAULT / DISABLEFAULT / DISABLE / TEST/ TEST
FIREFIREFIRE
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
3
4
DATE TIME EVENT ACTION REQUIRED
D
ATE
INITIALS
C
OMPLETED
SYSTEM MAINTENANCE
The following checks are recommended in accordance with national requirements. Make an entry in the log book every time a test is performed. Example of routine testing is shown below:
1. Daily Inspection - Check the SUPPLY indicator is illuminated and inspect for any fault
indicators showing or sounder operating, and that any previous faults have been attended to.
2.
Weekly Test – Perform a lamp test, ensure all indicators illuminate. Put the panel into WALK TEST and operate a call point or detector to test the system, followed by panel reset. Each week choose a different zone and call point or detector in rotation.
3
Quarterly Test – Check all previous log book entries and verify that all remedial action has been taken. Operate a call point or detector on each zone to test the fire alarm as in 2 above. Return the panel to its normal state, then isolate the mains supply and perform an EVACUATE to ensure that the battery is capable of supplying the alarm sounders.
4.
Annual Test – As in 2 and 3 above but test all call points and detectors for correct operation. Using the double pole isolator, verify that the terminals of the mains terminal block are secure and that the wires are securely fixed in place.
5.
Every 2-3 years – Have the smoke detectors checked or changed by a fire alarm engineer to ensure correct operation and freedom from potential false alarms.
6.
Every 5 years – replace the sealed lead acid battery.
LOG BOOK
This log book should be maintained by a responsible person who should ensure that every entry is properly recorded. An ‘event’ should include fire alarms (real and false), faults, tests, temporary disconnections or zone isolations and the dates of service engineers visits and the work carried out.
Name and Address
Person responsible Date Person responsible Date Person responsible Date The system was installed by and is maintained under contract by until Tel number who should be contacted if service is required.
DATE TIME EVENT ACTION REQUIRED
D
ATE
INITIALS
C
OMPLETED
DATE TIME EVENT ACTION REQUIRED
D
ATE
INITIALS
C
OMPLETED
DATE TIME EVENT ACTION REQUIRED
D
ATE
INITIALS
C
OMPLETED
USER CODE BUTTON ACTION
3545 1 – Reset Return the system to a normal condition after
a fire or fault has occurred. This should only be performed when the fire or fault has been identified and alarms have been silenced.
2 – Silence Buzzer Stops the sounding of the internal buzzer.
LEVEL 2a 3 Silence Alarms Turns off the fire alarm sounders after the fire
condition has been identified.
4 – Evacuate Activates the fire alarms sounders to evacuate
the building. Other outputs will not be triggered.
5 – Lamp Test Illuminates all the leds and operates the
internal buzzer. Resets after about 3 seconds.
5344 1 – Reset Return the system to a normal condition after
a fire or fault has occurred. This should only be performed when the fire or fault has been identified and alarms have been silenced.
2 – Silence Buzzer Stops the sounding of the internal buzzer.
LEVEL 2b 3 –Walktest Allows detectors and callpoints to be tested
on the zones. The sounders will sound for 1 second then reset. Zones in test condition are indicated on the panel.
4 – Disable Allows zones & alarms to be disabled if a fault
occurs or work is being carried out in an area. This does not affect the operation of any other zones. Select as follows: Enter code
5344 and Press 4 3 - Moves flashing light to the required zone. 4 - Selects/deselects the zone/alarm. 5 - To exit the function
5 – Exit Exit from Level 2b function
QUICK USER GUIDE FOR 1, 2 & 4 ZONE FIRE PANELS
Loading...