
INDICATORS COLOUR INDICATION
COMMON FAULT Yellow On when a fault condition has occurred, or if
no other fault Led is on, this indicates 24v
auxiliary fuse failure.
COMMON FIRE Red On when a FIRE condition has occurred or
EVACUATE has been operated.
ZONES 1-4 FAULT Yellow Flashes if a detector is removed from its base,
or an open/short circuit zone wiring fault.
Illuminated when a zone is disabled and
flashes when in walktest.
ZONES 1-4 FIRE Red Illuminated during a FIRE condition in this
zone. Flashes when a device is being tested
during walktest.
SUPPLY Green Illuminated while power is being supplied to
the panel.
SUPPLY FAULT Yellow Flashes during a mains or battery supply
failure.
ALARM FAULT/ Yellow Flashes when a fault on the sounder wiring
DISABLED occurs. Illuminated if alarm lines are disabled.
DISABLED Yellow Illuminated when Zones and/or alarm are
disabled. The specific zone or alarm fault led
will also be lit.
TEST Yellow Illuminated when Walktest function selected.
SYSTEM FAULT Yellow Illuminated if the panel has malfunctioned and
an attempt to reset the system automatically
has been made. Flashes if an error in the
system software has been detected – Requires
attention.
ALARM SILENCED Yellow Illuminated if the sounders on the alarm
circuits during a fire/evacuation condition
have been switched off or silenced.
EARTH FAULT Yellow Will flash if a fault occurs with the earthing.
QUICK USER GUIDE FOR 1, 2 & 4 ZONE FIRE PANELS
FTEN1, FTEN2, & FTEN4
1, 2 & 4 ZONE
FIRE DETECTION AND
ALARM CONTROL PANELS
INSTALLATION INSTRUCTIONS
USER GUIDE
LOG BOOK
tec tec
EN54EN54EN54EN54
FIREFIREFIREFIRE

PANEL SPECIFICATIONS
1. Certified to EN54 Pt2: 1997 and EN54 Pt4: 1997, and is suitable for
National installation requirements.
2. Five coded push buttons to control :RESET, EVACUATE, SILENCE ALARMS, SILENCE BUZZER, LAMP TEST,
WALK TEST, DISABLE and EXIT
3. LED Indicators:- General fire - General fault - 1/2/4 zone fire - 1/2/4
zone fault - Supply - Supply fault – Disabled - Alarm fault/disabled Test - System fault - Alarm silenced - Earth fault.
4. Zone end of line component that is polarised - Red end to Zn+ and
Black end to Zn-.
5. Two sets of auxiliary volt free contacts for fire and fault - Max.
current per contact set 2A at 30V dc.
6. Internal sounder - Minimum level 50dBA @ 1m.
7. Features:
USER ZONE AND ALARM DISABLE
USER LAMP TEST
ZONES MONITORED FOR OPEN CIRCUIT, SHORT CIRCUIT AND
DETECTOR REMOVAL
ALARM OUTPUTS MONITORED FOR OPEN AND SHORT CIRCUIT
AC AND DC POWER SUPPLY MONITORED
WALK TEST OPERATION
EARTH LEAKAGE DETECTOR AND SYSTEM FAULT MONITORING
1 & 2 zone 4 zone
8 Two sets of alarm outputs - 300mA max 1A max
total alarm output current
9. Power supply - Input 230v +10% -15% ac i/p 50Hz
Battery - Sealed lead acid 12v7Ahr
10. Auxiliary fused output 250mA
(fuse monitored) 24v
11. Class change input (CC) YES
12. Pulse Alert input (BA) YES
13. Open collector - FIRE output (CF) YES
14.
Volt free relay - FAULT output
YES
S
YSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
3
33
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
T
ESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERAL FAULTGENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIREGENERAL FIRE
F
AULT /DISABLE
/ TEST
F
AULT /DISABLEFAULT / DISABLE
/ TEST/ TEST
FIREFIREFIRE
SILENCE
B
UZZER
SILENCESILENCE
B
UZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMP TESTLAMPTESTLAMP TEST
RESETRESETRESET
RESETRESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
E
N54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
END OF LINE COMPONENT
ON LAST DETECTOR
Zone +Ve
RED
Zone -Ve
BLACK
AUX 2AUX 1
N/C
N/C
COM
COM
N/O
N/O
AL 2
ZN 1 ZN 2 ZN 3 ZN 4
+
++
+
+
+
D
C
Zone -Ve
BLACK
EOL COMPONENT
ON ANY UNUSED ZONE
AUX 2
FLT 1
FLT 2
N/C
N/C
N/C
COM
COM
COM
COM
N/O
N/O
N/O
N/O
AL 2
AL1
ZN 1 ZN 2 ZN 3 ZN 4
+
++
+
+
+
DD
D
C
TYPICAL PANEL WIRING
NO SPURS ALLOWED
E
END OF LINE RESISTOR
ON LAST SOUNDER
AUX 2AUX 1
FLT 1
FLT 2
N/C
N/C
N/C
COM
COM
COM
COM
N/O
N/O
N/O
N/O
AL 2
ZN 1 ZN 2 ZN 3 ZN 4
+
++
BA
CF
CC
COM
D
D
SSS
C
tec tec
EN54EN54EN54EN54
FIREFIREFIREFIRE
Coded Push Buttons
LED indicators
This manual provides the necessary guidance for the correct installation and commissioning of the
FIREtec EN54 1, 2 & 4 zone (EN54 Pt2: 1997 and EN54 Pt4: 1997 approved) fire panels. Persons
carrying out system design and installation should be competent and familiar with the relevant code
of practice relating to the installation of fire detection and alarm systems within buildings.
Key
NO Normally Open Contact
NC
Normally Closed Contact
C Common Contact
AL Alarm Line
CC
Class Change Input
BA Pulse Alert Input
CF Common Fire Output
COM
Common 0v
AUX Auxiliary Outputs
AUX
BATT
AC AC
Z1
COMBACC
CF
Z2 Z3 Z4
AL1 AL2
AUX1
NC
COM
NO
AUX2FAULT 1
FAULT 2
NC
COM
NO
NC
COM
NO
NC
COM
NO
Schematic for One, Two and Four Zone Firetec Panels
3
3
3
3

INSTALLATION PROCEDURE
The following instructions must be followed, however
it is recommended that the installation is delayed
until all the building or maintenance work is
completed. Building work near the panel may result
in damage.
Remove the fire panel from the packaging, but retain
this for the future storage of panel parts during
installation.
A) To remove the front – remove the screw located
under the bottom edge of the panel using Allen
key provided, pull the bottom edge out then lift
up. Store the panel front face down in the
packing box tacking care of the led light guides
on the back.
B) Box Mounting - Once the cable entry routes have
been decided, remove the appropriate knockouts
situated on the top and back of the box by
carefully knocking out from the inside outwards.
Note the entry point for the mains cable is
through a knockout which is located at the back
of the back box – see below. Ensure that the
back box is securely and flush fitted to the fabric
of the building. The box should be mounted at
such a height that the push buttons and LED’s
are at eye level. When mounting the box take
care not to damage the pcb in the box. Remove
any debris.
C) Feed the required cable into the box then make
off a reasonable working length, (identify each
of the cables).
Conduct all installation tests on
the cables with the detectors and other
electronic devices disconnected. Failure to
observe this could result in serious damage to
the detectors etc.
SYSTEM DESIGN GUIDE
When installing the system the designer should ensure:-
1. The installation complies with the relevant code of practise for
installations.
2. The mains supply is switched via a double pole isolator.
3. All detectors are sighted in accordance with British standard
recommendations.
4. That detector and alarm sounder circuits have NO SPURS.
5. It is recommended that the cabling used for detector and alarm
circuits is 1.5mm
2
Fire Protected, 2-core + screen complying with
BS7629, BS7846 and BSEN60702 (BS6207).
6. That detectors and callpoints used are compatible with the panel,
and that only devices recommended by the supplier are used.
7. The correct end of line component is used on the detection and
alarm circuits (including those not used), These components must be
fitted after the last detector, callpoint or sounder.
8. The total current consumption for each zone of detectors does not
exceed 4mA
9. The detector bases are connected as shown and must be fitted with a
diode for detector removal fault.Otherwise the removal of a detector
from a base will prevent subsequent detectors and call-points on the
zone from functioning.
10. The sounders must have a series blocking diode with suppression
components fitted that only allows current to flow through the
sounders when the control panel pcb is wired as shown.
11. Sounder current consumption should not exceed the panel
maximum. The maximum load for each set of contacts is 1A, however
the total sounder current should not exceed that shown in table for
panel specification.
12. That if a 24V auxiliary output is used for powering an auxiliary
circuit, the battery standby period is checked to ensure that the
maximum duration required for the installation can still be achieved.
E
NSURE THAT MAINS SUPPLY
IS SWITCHED WITH A DOUBLE
POLE ISOLATOR OF A MINIMUM
R
ATING OF 3AMPS
L
N
E
NO SPURS ALLOWED
END OF LINE COMPONENT
O
N LAST DETECTOR
Zone +Ve
RED
Z
one -Ve
BLACK
DD
OUT+
OUT-
IN+IN-
L1 IN
-R
L1 OUT
L2
DIODE
L1
IN
-R
L1
OUT
L2
DIODE
END OF LINE
DEVICE
KNOCKOUT FOR MAINS
CABLE ENTRY POINT IS
AT REAR OF BACK BOX
E
KNOCKOUTS FOR FIELD WIRING ENTRY
POINTS ON TOP AND BACK OF BOX
L
1- REMOVE SCREW
2- PULL BOTTOM OUT
3- LIFT UP
A
llen key
KNOCKOUT FOR MAINS
CABLE ENTRY POINT IS
AT REAR OF BACK BOX
KNOCKOUTS FOR FIELD WIRING ENTRY
POINTS ON TOP AND BACK OF BOX

INSTALLATION PROCEDURE (continued)
D) Connect the cables from the zones (detectors)
and alarms (sounders) to the pcb as shown in
diagrams, ensuring that there are
NO spurs from
the main circuit. Fit the end-of-line component
onto the last detector or call-point of each zone
circuit. The end-of-line resistor used on the alarm
circuit can be connected either way round. For
any unused circuits, leave the end-of-line
component / resistor in the terminal block
located on the pcb.
E) The panel has several optional inputs and
outputs.
• AUX 1 & 2-Are volt free relay contacts which
change over when the alarm sounds –Used for
switching auxiliary equipment.
• AUX 24V - a 24v DC power supply used to power
auxiliary equipment.
• CLASS CHANGE- wire a switch between COM and
CC terminals to make the sounders operate.
• PULSE ALERT- wire a switch to terminals BA and
COM to make the sounders pulse.
• FAULT- Volt free changeover relay contacts that
duplicates the common fault indicator. Used to
drive a remote fault indicator.
TYPICAL PANEL WIRING
NO SPURS ALLOWED
E
ND OF LINE COMPONENT
ON LAST DETECTOR
Zone +Ve
RED
Zone -Ve
BLACK
EOL COMPONENT
O
N ANY UNUSED ZONE
TYPICAL ALARM WIRING
AL2 WIRED AS AL1
END OF LINE RESISTOR
ON LAST SOUNDER
AUX 2AUX 1
FLT 1
REMOTE INDICATOR
FLT 2
N/C
N/C
N/C
N/C
COM
COM
COM
COM
N/O
N/O
N/O
N/O
AL 2
AL1
F4
1A
(T)1A(T)
F3
ZN 1 ZN 2 ZN 3 ZN 4
+
++
-
+
+
+
+
AUX
24V
O/P
BA
CF
CC
COM
F5 250mA(T)
F6 6.3A(T)
TF
AC
BATT
MAINS
CABLE ENTRY
CABLE CLAMP
FUSE F6 = BATTERY SUPPLY (6.3A)
FUSE F5 = AUXILLIARY OUTPUT (250mA)
FUSE F4 = ALARM CIRCIUT 1 (1A)
FUSE F3 = ALARM CIRCUIT 2 (1A)
BATTERY
L
N
250Va.c 1A(T)
20*5mm FUSE
CONTROL PCB
EARTH
DD
D
SSS
C
Key: D = Detector
C = Call-point
S = Sounder
- - + +- - + +
IN-
IN-
IN+
IN+
OUT+
OUT+
OUT-
OUT-
BELL
2ND
SND
1ST
SND
COM
SOUNDER
To sounder circuit
To sounder circuitTo sounder circuit
DETECTOR AND CALL POINT CONNECTIONS
SOUNDER AND BELL CONNECTIONS

LEVEL 2a USER CODE - 3545
Enter this code to gain access to the top row of
instructions. A small yellow led to the left of the word
RESET will light indicating that this row of functions
can now be activated by pressing the appropriate
button above it. The functions are as follows:-
1. RESET - is used to return the fire alarm system to
the normal clear condition, resetting any fire
alarm detectors, silencing all sounders and
resetting other devices connected to the panel.
2. SILENCE BUZZER – Causes the internal buzzer to
be switched off during a fire or fault condition.
Any subsequent fault or fire activation on another
zone will cause the buzzer to be re sounded.
3. SILENCE ALARMS - Used to turn off the external
alarm sounders after a fire activation the Alarm
Silenced led is also illuminated. The panel will
however continue to indicate the fire condition
and the internal buzzer will continue to bleep.
Any subsequent fire activation on another zone
will re-sound the fire alarm sounders.
PANEL COMMISSIONING
The total system should be tested in accordance with
the National requirements. Summary as follows:-
1. The complete installation should be checked to
ensure that all the cables have been correctly
installed in accordance with the National
regulations.
2. All the cables must be insulation tested with high
voltage test sets prior to the sounders and bases
/ detectors being connected.
3. The earth to the panel must be tested.
4. All detectors and sounders must be correctly
wired, with no spurs, and correctly fitted to the
bases.
5. End of line components / resistors (of the correct
value) must be fitted to the end of each circuit.
6. Connect the battery and switch on the mains
supply.
7. Test the panel as described in the USER GUIDE
8. Test every detector, call-point and sounder.
9. HAND-OVER TO THE USER - as follows:a)
Teach the user how to operate the panel and
test the system, using the USER GUIDE
b)
Issue drawings of the wiring.
c) Issue the appropriate certificates.
FLUSH MOUNTING BEZEL
An optional flush mounting bezel is available, which
allows the panel to be semi-flush to the wall up to the
front plastic cover.
1. Remove the front cover. Remove the knockouts
to be used
2. Note – the bezel has edges on the two sides and
the bottom, the top has no edges to allow full
access to the cable entries.
3. Slide the bezel over the metal box and fix in place
(with the screws provided) through the holes
near the transformer and the pcb.
4. Slots in the bezel allow the depth to be adjusted
by 22mm
5. Hole size = 298mm x 260mm, max hole depth =
56mm. The bezel width = 20mm.
6. Fix the box into the hole using the normal
mounting holes, the adjust the bezel back to the
wall, tighten the screws taking care not to
damage any components.
7. Continue the installation as normal.
USER GUIDE FOR 1, 2 & 4 ZONE FIRE PANELS
The panel supplied is a modern highly sophisticated fire control panel utilising the latest technology to
combine performance and reliability with ease of operation.
PANEL BASICS
The panel is controlled by the five push buttons mounted on the front.
To gain access to the panels functions either of two 4 digit USER CODE’s must be entered via the push buttons.
- This is used to prevent unauthorised access.
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
22111
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
A
LARM FAULT/
D
ISABLED
A
LARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
A
LARM
SILENCED
A
LARMALARM
SILENCEDSILENCED
G
ENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
R
ESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
B
UZZER
SILENCESILENCE
B
UZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
G
ENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/
TEST
FAULT/ DISABLEFAULT / DISABLE
/
TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
E
ARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
ALARM
S
ILENCED
ALARMALARM
S
ILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
S
ILENCE
B
UZZER
S
ILENCESILENCE
B
UZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
E
XITEXITEXIT
EVACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
R
ESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
S
ILENCE
BUZZER
S
ILENCESILENCE
BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
ADDITIONAL INSTRUCTIONS FOR
ELECTROMAGNETIC COMPATIBILITY
When used as intended this product complies with
EMC Directive (89/336/EEC) and the UK EMC
regulations 1992 (SI 2372/1992) by meeting the
limits set by the standards, EN 55022: 1998 and EN
50130-4 1996. The following installation guidelines
must be followed.
1. External cables must be connected using the
knockouts provided.
2. When routing cables inside the product they
must be:-
a)Kept as short as possible.
b)Routed close to the housing
c)Kept as far as possible from the electronics.
Any modifications other than those stated in this
manual, or any other use of this product may cause
interference and it is the responsibility of the user to
comply with the EMC and Low Voltage Directive.
• CF -an open collector current limited output to a
remote indicator which duplicates the common
fire indicator. Connect the +ve wire to CF terminal
and -ve to COM.
Connect the mains supply cable to the fused terminal
block, using the knockout in the bottom or back
nearest to it, and keeping it away from the other
wiring. Fit the 12v battery into the bottom right hand
corner of the box and connect the red and black wires.
It is important to ensure correct polarity of battery
wires. Switch on the mains supply. Commission the
system as described below.

3. WALK TEST - This function allows the user to test
fire detectors and callpoints on the system.
To put a zone into Walktest – Enter user code
5344. Press 3 – WALKTEST. The FAULT led of the
first available zone flashes quickly.
Press 4 to select this zone for testing. This causes the
fault led of the selected zone to flash slowly –
showing that this zone is in test along with the test
led being illuminated.
If a zone is in Walktest, the TEST led is lit and the
FAULT led of the corresponding zone flashes slowly.
PERFORM WALKTEST
Walk round and test detectors and/or call points in
this zone. When a device is triggered the sounders will
sound a few seconds and then silence. The relevant
FIRE zone indicator on the panel will be flashed.
DESELECT WALKTEST
When all of the detectors and/or call points have
been tested in the zone, re-enter the access code
(5344), Press 3 and then Press 4 to deselect this
zone. The zone in Walktest must be deselected
before another zone can be put into Walktest. Only
one zone can be put into Walktest at any one time, all
other zones operate as normal.
SELECT NEXT WALKTEST
Re-enter the access code (5344), Press 3 and then
Press 3 to advance to the next zone that is available
for Walktesting. The FAULT led of the next zone
flashes quickly.
Press 4 to select zone for
walktesting. Perform Walktest.
Press 5 To exit from this menu.
4. EVACUATE – This is used to activate the fire
alarm sounders. But does not trigger any device
connected to the auxiliary contacts (Typically a
digital communicator and/or heating/ventilation
controls) The internal buzzer will sound and the
GENERAL FIRE indicator will be illuminated.
5. LAMP TEST - This option illuminates all the LED’s
and twice beeps the internal buzzer. After 3
seconds the LED’s revert back to their previous
state and the panel to its normal condition.
LEVEL 2b USER CODE 5344
Enter this code to gain access to the bottom row of
instructions. The lower yellow led will light indicating
that this row of functions can now be activated by
pressing the appropriate button above it. The
functions are as follows:-
1.
RESET - is used to return the fire alarm system to
the normal clear condition, resetting any fire
alarm detectors, silencing all the sounders, and
resetting other devices connected to the panel.
2.
SILENCE BUZZER – Causes the internal buzzer to
be switched off during a fire or fault condition.
Any subsequent fault or fire activation on another
zone will cause the buzzer to be re sounded.
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
22111
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
A
LARM FAULT/
D
ISABLED
A
LARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
A
LARM
SILENCED
A
LARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
E
ARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2211
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
D
ISABLED
ALARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/
TEST
F
AULT/ DISABLEFAULT / DISABLE
/
TEST/ TEST
FIREFIREFIRE
SILENCE
B
UZZER
SILENCESILENCE
B
UZZERBUZZER
S
ILENCE
A
LARMS
S
ILENCESILENCE
A
LARMSALARMS
E
XITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
S
YSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
2211
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
T
ESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/TEST
F
AULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
A
LARMS
SILENCESILENCE
A
LARMSALARMS
E
XITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONESZONES
22211
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
D
ISABLED
ALARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/
TEST
F
AULT/ DISABLEFAULT / DISABLE
/
TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
S
ILENCE
A
LARMS
S
ILENCESILENCE
A
LARMSALARMS
EXITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
E
N54EN54EN54
FIREFIREFIRE
S
YSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONES
2211133444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
T
ESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
G
ENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/
TEST
FAULT/ DISABLEFAULT / DISABLE
/
TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
3
33
444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
ALARM
S
ILENCED
ALARMALARM
S
ILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
S
ILENCE
B
UZZER
S
ILENCESILENCE
B
UZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
E
XITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
R
ESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
S
ILENCE
BUZZER
S
ILENCESILENCE
BUZZERBUZZER
1
11
tec tec
E
N54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
22111
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
A
LARM FAULT/
D
ISABLED
A
LARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
S
ILENCE
BUZZER
S
ILENCESILENCE
BUZZERBUZZER
SILENCE
A
LARMS
SILENCESILENCE
A
LARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
1
11
tec tec
E
N54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
S
YSTEM FAULTSYSTEM FAULTSYSTEM FAULT
E
ARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
T
ESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/TEST
F
AULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
S
ILENCE
A
LARMS
S
ILENCESILENCE
A
LARMSALARMS
EXITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE

FRONT PANEL INDICATORS- show the
following:-
1.
GENERAL FIRE > red led – illuminates during a
fire or evacuation condition.
2. ZONES 1- 4 FIRE > red led’s - Illuminate when a
fire occurs on the relevant zone. The GENERAL
FIRE led will also be illuminated at the same time.
The fire led will flash during Walktest condition.
3.
GENERAL FAULT> yellow led - illuminates when
any a fault with the panel has occurred. The
specific FAULT led is flashed, or if no other FAULT
led is on, this indicates an auxiliary fuse failure.
4. ZONES 1-4 FAULT > yellow led’s – Flashes the
relevant zone led during a fault condition but is
illuminated to indicate a zone that is disabled or
is in Walktest. When in the Walktest menu the
appropriate led flashes quickly.
5.
SUPPLY > green led - Illuminated all the time.
6.
SUPPLY FAULT > yellow led – Flashes indicating
a power supply fault has occurred. Check mains
and battery connections as well as pcb fuses.
7. DISABLED > yellow led - illuminates when a fire
zone has been isolated, along with the relevant
zone fault led on steady.
8.
ALARM FAULT/DISABLED > yellow led –
Flashes when the panel detects a fault in the
sounder wiring. Common fault also illuminated. Is
illuminated when the alarms are disabled along
with the disabled led.
9.
TEST > yellow led - illuminates when the panel
is set to walktest mode.
10.
SYSTEM FAULT > yellow led - illuminates
if the panel has been restarted by the
supervisory circuit or is flashed if a
corruption of the software in the
microcontroller has been detected.
11.
ALARM SILENCED > yellow led –
Illuminates when the sounders on the
alarm circuits have been switched off
during a fire/evacuation – The alarm
condition still remains.
12.
EARTH FAULT > yellow led – flashes if a fault
with the earthing of the system has occurred.
4. DISABLE - If a fault occurs or work is being
carried out on a zone or alarm circuit, it is
possible to disable the zone(s) and alarm circuit
from the system without affecting the other
zones. If a zone or alarm is disabled, the
DISABLED led and the FAULT led(s) of the
corresponding zone(s) or alarm will be lit.
TO DISABLE A ZONE OR ALARM
Enter user code 5344. Press 4 – DISABLE. The
FAULT led of zone 1 (if it is not in Walktest)
flashes quickly.
Press 3 to advance to next zone/alarm
OR
Press 4 to disable the appropriate zone or
alarm. This causes the FAULT led of the selected
zone/alarm to be illuminated – showing that it is
disabled along with the DISABLE led being
illuminated.
Press 5 To exit from this menu.
TO RE-ENABLE DISABLED ZONES OR ALARMS
Enter user code 5344. Press 4 – DISABLE. The
FAULT led of zone 1 flashes quickly.
Press 3 to advance to appropriate zone. Press 4
to re-enable a zone/alarm. If a zone/alarm is
being re-enabled, the illuminated FAULT led of
the re-enabled zone is cleared and moves to the
next zone/alarm.
Press 5 to exit from this menu.
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2211
3
33
444
S
UPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
ALARM
S
ILENCED
ALARMALARM
S
ILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
1
11
tec tec
E
N54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
221
1
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
A
LARM FAULT/
D
ISABLED
A
LARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
A
LARM
SILENCED
A
LARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
G
ENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
F
IREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONES
2211133444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
A
LARM FAULT/
DISABLED
A
LARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
A
LARM
SILENCED
A
LARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
E
XITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
E
N54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONES
2211133444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
D
ISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
A
LARM
S
ILENCED
A
LARMALARM
S
ILENCEDSILENCED
G
ENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/
TEST
FAULT/ DISABLEFAULT / DISABLE
/
TEST/ TEST
FIREFIREFIRE
SILENCE
B
UZZER
SILENCESILENCE
B
UZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
E
XITEXITEXIT
EVACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
W
ALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
3
33222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
1
11
tec tec
EN54EN54EN54
FIREFIREFIRE
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
DISABLED
ALARM FAULT/ALARM FAULT/
DISABLEDDISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
GENERALFIREGENERAL FIRE
FAULT/ DISABLE
/TEST
FAULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
SILENCE
ALARMS
SILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
EVACUATEEVACUATEEVACUATE
LAMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
Thomas BettsThomas Betts
Thomas Betts
Z
ONESZONESZONES
222111
333
444
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE
/ TEST
FAULT / DISABLEFAULT / DISABLE
/ TEST/ TEST
FIREFIREFIRE
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
Thomas BettsThomas Betts
Thomas Betts
S
UPPLYSUPPLY
ZONESZONESZONES
222111
3
33
444
SUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLED
A
LARM FAULT/
DISABLED
A
LARM FAULT/
DISABLEDDISABLED
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE
/ TEST
FAULT / DISABLEFAULT / DISABLE
/ TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
RESETRESET
RESETRESET SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIRE
T
SYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULT
SUPPLYSUPPLYSUPPLY
ZONESZONESZONES
2
22111
333
4
44
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE
/ TEST
FAULT / DISABLEFAULT / DISABLE
/ TEST/ TEST
FIREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
RESETRESET
RESETRESET SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
ZONESZONESZONES
222111
333
444
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE
/ TEST
FAULT / DISABLEFAULT / DISABLE
/ TEST/ TEST
FIREFIREFIRE
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
Thomas BettsThomas Betts
Thomas Betts
SYSTEM FAULTSYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULTEARTH FAULT
S
UPPLYSUPPLYSUPPLY
ZONESZONESZONES
222111
333
444
SUPPLY FAULTSUPPLY FAULTSUPPLY FAULT
DISABLEDDISABLEDDISABLED
ALARM FAULT/
D
ISABLED
ALARM FAULT/ALARM FAULT/
D
ISABLEDDISABLED
TESTTESTTEST
ALARM
SILENCED
ALARMALARM
SILENCEDSILENCED
GENERALFAULTGENERAL FAULT
G
ENERALFIREGENERAL FIRE
F
AULT/ DISABLE
/TEST
F
AULT/ DISABLEFAULT / DISABLE
/TEST/ TEST
F
IREFIREFIRE
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
S
ILENCE
ALARMS
S
ILENCESILENCE
ALARMSALARMS
EXITEXITEXIT
E
VACUATEEVACUATEEVACUATE
L
AMPTESTLAMPTESTLAMP TEST
RESETRESET
RESETRESET
WALK TESTWALK TESTWALK TEST DISABLEDISABLEDISABLE
333222 444 555
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997
SILENCE
BUZZER
SILENCESILENCE
BUZZERBUZZER
111
tec tec
EN54EN54EN54
FIREFIREFIRE
ZONESZONES
222111
33
44
GENERAL FAULTGENERAL FAULT
GENERAL FIREGENERAL FIRE
FAULT / DISABLE
/ TEST
FAULT / DISABLEFAULT / DISABLE
/ TEST/ TEST
FIREFIREFIRE
EN54-2 : 1997EN54-2 : 1997EN54-2 : 1997 EN54-4 : 1997EN54-4 : 1997EN54-4 : 1997

DATE TIME EVENT ACTION REQUIRED
D
ATE
INITIALS
C
OMPLETED
SYSTEM MAINTENANCE
The following checks are recommended in accordance with national requirements. Make an entry
in the log book every time a test is performed. Example of routine testing is shown below:
1. Daily Inspection - Check the SUPPLY indicator is illuminated and inspect for any fault
indicators showing or sounder operating, and that any previous faults have been attended to.
2.
Weekly Test – Perform a lamp test, ensure all indicators illuminate. Put the panel into WALK
TEST and operate a call point or detector to test the system, followed by panel reset. Each
week choose a different zone and call point or detector in rotation.
3
Quarterly Test – Check all previous log book entries and verify that all remedial action has
been taken. Operate a call point or detector on each zone to test the fire alarm as in 2 above.
Return the panel to its normal state, then isolate the mains supply and perform an EVACUATE
to ensure that the battery is capable of supplying the alarm sounders.
4.
Annual Test – As in 2 and 3 above but test all call points and detectors for correct operation.
Using the double pole isolator, verify that the terminals of the mains terminal block are secure
and that the wires are securely fixed in place.
5.
Every 2-3 years – Have the smoke detectors checked or changed by a fire alarm engineer to
ensure correct operation and freedom from potential false alarms.
6.
Every 5 years – replace the sealed lead acid battery.
LOG BOOK
This log book should be maintained by a responsible person who should ensure that every entry is
properly recorded. An ‘event’ should include fire alarms (real and false), faults, tests, temporary
disconnections or zone isolations and the dates of service engineers visits and the work carried out.
Name and Address
Person responsible Date
Person responsible Date
Person responsible Date
The system was installed by
and is maintained under contract by until
Tel number who should be contacted if service is required.

DATE TIME EVENT ACTION REQUIRED
D
ATE
INITIALS
C
OMPLETED
USER CODE BUTTON ACTION
3545 1 – Reset Return the system to a normal condition after
a fire or fault has occurred. This should only
be performed when the fire or fault has been
identified and alarms have been silenced.
2 – Silence Buzzer Stops the sounding of the internal buzzer.
LEVEL 2a 3 – Silence Alarms Turns off the fire alarm sounders after the fire
condition has been identified.
4 – Evacuate Activates the fire alarms sounders to evacuate
the building. Other outputs will not be
triggered.
5 – Lamp Test Illuminates all the leds and operates the
internal buzzer. Resets after about 3 seconds.
5344 1 – Reset Return the system to a normal condition after
a fire or fault has occurred. This should only
be performed when the fire or fault has been
identified and alarms have been silenced.
2 – Silence Buzzer Stops the sounding of the internal buzzer.
LEVEL 2b 3 –Walktest Allows detectors and callpoints to be tested
on the zones. The sounders will sound for 1
second then reset. Zones in test condition are
indicated on the panel.
4 – Disable Allows zones & alarms to be disabled if a fault
occurs or work is being carried out in an area.
This does not affect the operation of any other
zones. Select as follows:
Enter code
5344 and Press 4
3 - Moves flashing light to the required zone.
4 - Selects/deselects the zone/alarm.
5 - To exit the function
5 – Exit Exit from Level 2b function
QUICK USER GUIDE FOR 1, 2 & 4 ZONE FIRE PANELS