FIREPOWER SK-4 User Manual

SK-4 & SK-4E Fire Alar m
Control Panel
4-zone fire protection at a price that won’t bur n your budget.
The SK-4 and SK-4E (SK-4/E) are four zone conventional fire alarm control panels (FACPs) that bring the latest in microprocessor technology to conventional fire controls. The SK-4 is a 120 VAC FACP and the SK-4E is a 240 VAC FACP. These FACPs provide reliable fire signaling protection
for small- to medium-sized commercial, industrial, and institutional buildings. For more information about the SK-4/E system, or to locate your nearest source, please call
1-800-446-6444, or in Minnesota, call 763-493-6435.
FIRE ALARM CONTROL PANEL
Description
The four zone SK-4/E is a 24 VDC FACP that provides four Class B initiating device circuits and two Class B notification appliance circuit (NAC).
The SK-4/E NAC protocol includes the ability to silence audible devices while strobes continue to flash, using only a single pair of wires. The SK-4/E is also compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device activates audible and visual signaling devices, illuminates an indicating LED, sounds the piezo sounder at the F
alarm relay, and operates an
ACP
F optional module used to notify a remote station or initiate an auxiliary control function.
The SK-4/E is compatible with System
®I3
Sensor advanced features such as drift compensation, maintenance alert, and freeze warning. synchronization of audio/visual devices is provided, using three selections for manufacturer protocol.
ACP, activates the
detectors providing
Automatic
Features
• Four Style B (Class B) initiating device circuits (IDCs)
• Two Style Y (Class B) notification appliance circuit (NAC)
• Optional module converts all IDCs and NACs to Class A (PN SK-CAC4)
• Support for synchronization of standard ANSI audible signals and ADA compliant strobes per NFPA72
• Selectable for System Sensor, Wheelock, and Gentex protocols
• Selective silence feature allows manual silence of horns while strobes continue to flash on the same NAC
• Program for combination tamper supervisory monitor and waterflow alarm on one zone
• Silent or audible walk test operation mode
• Alarm verification selectable per zone
• Program each zone for supervisory or fire with separate red and yellow LEDs
• Disable switches provided per zone
• Program NACS for – Silence inhibit
– Auto silence – Strobe synchronization
emporal or steady signal
T
– – Silenceable or nonsilenceable – Disable
Form C alarm, trouble, and
• supervisory relays
• 3A total usable current 6A total usable current with optional
• second transformer (PN SK-TRM24 or SK-TRM24E)
• Optional dress panel (PN SK-DP2/4)
Electrical Specifications
SK-4 Primary AC: 120 VAC @ 50/60 Hz, 2.3A
SK-4E Primary
1.15A
Wiring: 14 AWG (2.0 mm insulation min
AC: 240 VAC @ 50 Hz,
2
) with 600 V
SK-4
Initiating Device Circuits (IDCs)
Operating Voltage: 22 VDC nominal; power-limited Standby Current: 4 mA Alarm Current: 15 mA min Short-circuit Current: 40 mA max Loop Resistance: 100Ω max EOL Resistor: 4.7K Ω, 1/2 watt
NACs
Signaling Current: 2.5A with standard transformer or 5A total (2.5A optional transformer EOL Resistor: 4.7K Ω, 1/2 watt
Form C Relays
ypes: Trouble, alarm, and
T supervisory Contact Ratings: 2A @ 30 VAC, resistive
per NAC) with additional
@ 24 VDC
, power-limited
FIRE ALARM CONTROL PANEL
SK-4 & SK-4E Fire Control Panel
Engineering Specifications
The contractor shall provide a completely electrically supervised fire alarm control panel Silent Knight Model SK-4/E. The system shall contain a fire alarm control panel capable of operating and supervising smoke detection devices, alarm notification devices, and an on-board annunciator. It shall be compatible with a digital communicator accessory.
The fire alarm control panel shall have a power limited supply, four Class B initiation circuits which shall accommodate heat detectors, smoke detectors, and manual pull stations. Smoke detection shall be achieved with either 2- or 4-wire detectors that are compatible with the system. The initiation inputs
hall be programmable as 1) verification zones in which detectors are automatically reset one time before signaling an alarm condition; or 2)
s combination waterflow supervisory zones that allows the FACPto distinguish between an alarm switch (waterflow device) and a supervisory switch (tamper) installed on the same circuit. The FACPshall have two 2.5 amp or 5 amp (with an additional optional standard transformer) programmable notification outputs. It shall have dedicated relays for alarm, trouble, and supervisory. It shall have two power outputs, one resettable and one non­resettable, each rated at 500 mA.
The FACPshall have an on-board annunciator to indicate alarm, supervisory, trouble, and maintenance conditions. The annunciator must include LEDs for AC, GENERALTROUBLE, ALARM SILENCE, WALK TEST, EARTH FAULT, AND LOW BATTERY. The annunciator shall also contain LEDs to annunciate fire alarms, troubles, supervisory for ACKNOWLEDGE, ALARM, SILENCE, RESET, and WALK TEST. The annunciator must also have separate DISABLE switches for each zone and notification circuit.rr
, and maintenance by zone. The FACPmust be fully operational from the annunciator and include buttons
Electrical Specifications (cont) Auxiliary Output
Resettable and non-resettable Operating Voltage: 24 VDC nominal Current: 500 mA max, power-limited; total current for nonresettable power, resettable power and two NACs must not exceed 6.0A (requires additional transformer)
Battery
Type: Sealed lead acid only Charging Circuit: 27.6 VDC @ 0.8A max normal flat charge Charging Capacity: 18 AH Size: 7 AH max allowed in FACP. Larger batteries can housed in an RBB accessory cabinet
Compatible Initiating and NAC Devices
See SK document PN 52612.
Mechanical Specifications
Cabinet Backbox Dimensions:
14.5" W x 15" H x 3" D (36.83 W x 38.10 H x 7.62 D cm)
Cabinet Door:
14.677" W x 15.342" H x 0.375" D (37.28 W x 38.97 H x 0.95 D cm)
Cabinet Color: Red Telephone Requirements:
FCC Part 15 and Part 68 approved
ype of Jack: RJ31X (two required)
T
Installation
The SK-4/E can be surface mounted using two key slots at the top of the backbox and two additional 0.25” diameter holes at the bottom, or semi­flush mounted using the optional Trim Ring P/N TR-1-R
Approvals
NFPA 72; UL Listed; CSFM 7165-0559: 145; MEA 297-01-E-3
Ordering Information SK-4
120 VAC Four Zone Conventional FACP
SK-4E
AC Four Zone Conventional
240 V FACP
Accessories SK-DP2/4
Dress Panel. panel controls but restricts access to system wiring.
SK-CAC4
Class AConvertor. Converts Style B (Class B) IDCs to Style D (Class A) and Style B (Class B) NACs to Style Z (Class
Allows access to the
A)
SK-4XTM
Transmitter Module. Provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity.
SK-4XLM
LED Interface Module.
SK-XRM24
110 Volt Transformer 3–6A.
SK-XRM24E
220 Volt Transformer 3–6A.
SK-RZA4
Remote Annunciator.
SK-4XZM
Zone Relay Module.
RBB
Remote Battery Box Accessory Cabinet. Use if back up batteries are too large to fit into F Dimensions: 16”W x 10”H x 6”D
Digital Communicator Accessories 5104B
Six-zone fire control communicator
5129
Four channel slave fire communicator
ACP cabinet.
This document is not intended to be used for installation purposes. W keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Silent Knight 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369-4927.
Phone: (800) 328-0103, Fax: (763) 493-6475.
e try to
MADE IN AMERICA
FORM# 350305 Rev
Copyright © 2006 Silent Knight
. C 12/06
Loading...