Five Zone Fire Alarm Control Panel
Ten Zone Fire Alarm Control Panel
General
The MS-5UD-3 is a five-zone FACP (Fire Alarm Control Panel)
and the MS-10UD-7(E) is a ten-zone FACP. These control panels provide reliable fire signaling protection for small to
medium-sized commercial, industrial, and institutional buildings. Both panels include built-in communicators for Central
Station Service and remote upload/download.
Each of these FACPs is compatible with System Sensor’s
microprocessor-based i
smoke detectors can transmit a maintenance trouble signal to
the FACP indicating the need for cleaning and a supervisory
“freeze” signal when the ambient temperature falls below the
detector rating. Additionally, both the MS-5UD-3 and MS10UD-7 are compatible with conventional input devices such
as two- and four-wire smoke detectors, pull stations, waterflow
devices, tamper switches, and other normally-open contact
devices. Refer to the Fire•Lite Device Compatibility Document
for a complete listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits),
three programmable Form-C relays (factory programmed for
Alarm, Trouble, and Supervisory) and 24 VDC special application resettable and nonresettable power outputs. The FACPs
supervise all wiring, AC voltage, battery level and telephone
line integrity.
Activation of a compatible smoke detector or any normallyopen fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicating LED, sound the
piezo sounder at the FACP, activate the communicator and
FACP alarm relay, and operate an optional module used to
notify a remote station or initiate an auxiliary control function.
New options include a UL listed printer, PRN-6F and FireLite’s
ACT Internet Monitoring module. The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit
monitoring of alarm signals over the Internet saving the
monthly cost of two telephone lines. Although not required, the
secondary telephone line may be retained providing backup
communication over the public switched telephone line.
NOTE: The MS-10UD-7E offers the same features as the MS10UD-7 but allows connection to 240 VAC. Unless otherwise
specified, the information in this data sheet applies to both the 120
VAC and the 240 VAC versions of these panels.
• Integral 80-character LCD display with backlighting and
keypad.
• Real-time clock/calendar with automatic daylight savings
adjustments.
• ANN-BUS for connection to remote annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red)
• SUPERVISORY (yellow)
• TROUBLE (yellow)
• AC POWER (green)
• ALARM SILENCED (yellow)
CONTROL BUTTONS
• ACKNOWLEDGE
• ALARM SILENCE
• SYSTEM RESET (lamp test)
•DRILL
Terminal Blocks
AC Power – TB1:
• MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A.
• MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
3.80 A.
• MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.
Wire size: minimum 14 AWG (2.00 mm²) with 600 V insulation.
Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
• Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC
@ 1.4 A. Supervised, nonpower-limited.
• Maximum Charger Capacity: 18 AH battery for MS-5UD-3,
and 26 AH battery for MS-10UD-7(E). [Two 18 Ah batteries
can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or BB-55.]
Refer to the Fire•Lite Device Compatibility Document for compatible listed devices.
Form C Relays – TB8:
• Relay 1 (factory default programmed as Alarm Relay)
• Relay 2 (factory default programmed as fail-safe Trouble
Relay)
• Relay 3 (factory default programmed as Supervisory Relay)
Special Application Resettable Power – TB9:
• Jumper selectable by JP31 for resettable or nonresettable
power.
• Operating voltage: 24 VDC nominal.
• Maximum available current: 500 mA - appropriate for powering four-wire smoke detectors.
• Power-limited circuit.
Refer to the Fire•Lite Device Compatibility Document for listed
compatible devices.
Remote Sync Output - TB2: Remote power supply synchronization output, only required for the MS-5UD-3. 24 VDC nominal special application power. Maximum current is 40 mA.
End-of-Line Resistor: 4.7K ohm. Supervised and power-limited circuit.
phone output ports for internet communications over customer
provided ethernet internet connection. Requires compatible
Teldat Visoralarm Central Station Receiver. Can use DHCP or
static IP. (See data sheet df-52424 for more information.)
IPBRKT: Mounting kit for IPDACT in common enclosure.
IPSPLT: Y Adaptor option to allow connection of both panel
dialer outputs to one cable input to IPDACT (sold separately).
OPTIONAL MODULES
CAC-5X: Optional (Class A) Converter Module. Converts Style
B (Class B) Initiating Device Circuits to Style D (Class A); and
Style Y (Class B) Notification Appliance Circuits to Style Z
(Class A). Connects to J2 on the MS-5UD-3 and MS-10UD7(E) main circuit board and to J7 on the MS-10UD-7(E).
NOTE: Two Class A Converter Modules are required for the tenzone panel.
4XTMF: Transmitter module. Provides a supervised output for
local energy municipal box transmitter and alarm and trouble
reverse polarity. Includes a disable switch and disable trouble
LED. A module jumper option allows the reverse polarity circuit
to open with a system trouble condition if no alarm conditions
exists. Mounts to the main circuit board connectors J4 and J5.
COMPATIBLE ANNUNCIATORS
ANN-80: Remote LCD Annunciator. Mimics the information
displayed on the FACP’s LCD. Red. (For white, order: ANN-
80-W.)
ANN-LED: LED Annunciator with three LEDs for each zone:
Alarm, Trouble, and Supervisory. Mounts in the DP-51050(B)
dress panel. (For white, order: ANN-80-W.)
ANN-RLED: LED Annunciator with three alarm (red) indicators for up to 30 input zones or addressable points. (See DF-
60241).
ANN-RLY: Relay module. Mounts inside the cabinet. Provides
ten Form C relays.
ANN-S/PG: Serial/parallel printer gateway. Provides a connection for a serial or parallel printer.
ANN-I/O: Driver module. Provides connections to a user-supplied graphic annunciator.
ACCESSORIES
DP-51050: Optional dress panel. Restricts access to the system wiring while allowing access to the membrane switch
panel.
BB-26: Battery backbox, holds up to two 25 AH batteries and
CHG-75.
BB-55: Battery backbox, holds up to two 25 AH batteries.
TR-CE: Optional trim-ring for semi-flush mounted cabinets.
PRN-6F: UL listed printer.
Product Line Information
MS-5UD-3: Five-zone, 24-volt Fire Alarm Control Panel
(includes backbox, FLPS-3 power supply, technical manual,
and a frame & post operating instruction sheet).
MS-10UD-7: Ten-zone, 24-volt Fire Alarm Control Panel
(includes backbox, FLPS-7 power supply, technical manual,
and a frame & post operating instruction sheet).
MS-10UD-7E: Same as above with 240 VAC FLPS-7.
IPDACT, IPDACT-2/2UD Internet Monitoring Module:
Mounts in bottom of enclosure with optional mounting kit (PN
IPBRKT). Connects to primary and secondary DACT tele-
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.
Agency Listings and Approvals
The listings and approvals below apply to the basic MS-5UD-3
and MS-10UD-7 control panels. In some cases, certain modules or applications may not be listed by certain approval
agencies, or listing may be in process. Consult factory for latest listing status.
• UL Listed: File S624
• FM Approved
• CSFM: 7165-0075:214
• MEA: MEA: 333-07-E
NOTE: For ULC-listed models, see df-60440.
NFPA Standards
The MS-5UD/MS-10UD(E) Series complies with the following
NFPA 72 Fire Alarm Systems requirements:
– LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
–AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTMF).
– REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble, 4XTMF is required.)
–PROPRIETARY (Automatic, Manual and Waterflow).
– CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
–OT, PSDN (Other Technologies, Packet-switched Data
Network)
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.