FIREPOWER MS-10UD-7 User Manual

MS-5UD/MS-10UD(E) Series
Five Zone Fire Alarm Control Panel Ten Zone Fire Alarm Control Panel
General
Each of these FACPs is compatible with System Sensor’s microprocessor-based i smoke detectors can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory “freeze” signal when the ambient temperature falls below the detector rating. Additionally, both the MS-5UD-3 and MS­10UD-7 are compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, waterflow devices, tamper switches, and other normally-open contact devices. Refer to the Fire•Lite Device Compatibility Document for a complete listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm, Trouble, and Supervisory) and 24 VDC special applica­tion resettable and nonresettable power outputs. The FACPs supervise all wiring, AC voltage, battery level and telephone line integrity.
Activation of a compatible smoke detector or any normally­open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, sound the piezo sounder at the FACP, activate the communicator and FACP alarm relay, and operate an optional module used to notify a remote station or initiate an auxiliary control function.
New options include a UL listed printer, PRN-6F and FireLite’s ACT Internet Monitoring module. The FireWatch Series inter­net monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet saving the monthly cost of two telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line.
NOTE: The MS-10UD-7E offers the same features as the MS­10UD-7 but allows connection to 240 VAC. Unless otherwise specified, the information in this data sheet applies to both the 120 VAC and the 240 VAC versions of these panels.
NOTE: For ULC-listed models, see df-60440.
Features
• Listed to UL Standard 864, 9th edition.
• Built-in DACT (Digital Alarm Communicator/Transmitter).
• Style B (Class B) IDC (Initiating Device Circuit)
MS-5UD-3 - five IDCs.MS-10UD-7 - ten IDCs.
• Style Y (Class B) NAC (Notification Appliance Circuit) - spe­cial application power
MS-5UD-3 - four NACs.MS-10UD-7 - four NACs.
• Notification Appliances may be programmed as
Silence Inhibit.Auto-Silence.
3
series detectors. These conventional
DF-52416:C • A3-20
Control/Communicators
52416cov.jpg
– Strobe Synchronization for System Sensor, Wheelock,
Gentex, Faraday, or Amseco devices.
Selective Silence (horn-strobe mute).Temporal or Steady Signal.Silenceable or Nonsilenceable.
• Optional CAC-5X Style Z (Class A) Converter Module for NACs and IDCs (2 required for MS-10UD-7).
• Form-C Relays for Alarm, Trouble and Supervisory - Con­tact Ratings 2.0 A@ 30 VDC or 30 VAC (resistive).
• 3.0 A total system current for MS-5UD-3.
• 7.0 A total system current for MS-10UD-7.
• Optional Dress Panel DP-51050
• Optional Trim Ring TR-CE for semi-flush mounting.
• 24 volt operation.
• Low AC voltage sense.
• Alarm Verification.
• PAS (Positive Alarm Sequence).
• Automatic battery trickle charger.
• Up to eight ANN-BUS annunciators:
Optional 8 zone Relay Module ANN-RLY.Optional LED Annunciator Module ANN-LED,Optional Remote Annunciator ANN-80.Optional Remote Printer Gateway ANN-S/PG.Optional LED Annunciator Driver ANN-I/O.
• Optional 4XTMF module (conventional reverse polarity/city box transmitter).
PROGRAMMING AND SOFTWARE:
• Can be programmed at the panel with no special software or additional equipment.
• Programmable Make/Break Ratio.
• Upload/Download (local or remote) of program and data via integral DACT.
DF-52416:C • 05/12/2009 — Page 1 of 4
USER INTERFACE:
• Built-in DACT (Digital Alarm Communicator/Transmitter).
• Integral 80-character LCD display with backlighting and keypad.
• Real-time clock/calendar with automatic daylight savings adjustments.
• ANN-BUS for connection to remote annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red)
• SUPERVISORY (yellow)
• TROUBLE (yellow)
• AC POWER (green)
• ALARM SILENCED (yellow)
CONTROL BUTTONS
• ACKNOWLEDGE
• ALARM SILENCE
• SYSTEM RESET (lamp test)
•DRILL
Terminal Blocks
AC Power – TB1:
• MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A.
• MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
3.80 A.
• MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.
Wire size: minimum 14 AWG (2.00 mm²) with 600 V insulation. Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
• Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 A. Supervised, nonpower-limited.
• Maximum Charger Capacity: 18 AH battery for MS-5UD-3, and 26 AH battery for MS-10UD-7(E). [Two 18 Ah batteries can be housed in the FACP cabinet. Larger batteries require separate battery box such as the BB-26 or BB-55.]
• Minimum Battery Size: 7 AH.
Page 2 of 4 — DF-52416:C • 05/12/2009