The System 2000 is an expandable multi-zone Fire Alarm Control Panel designed with maximum flexibility and modularity
as a basic requirement. The heart of the system is the Central Processor Unit (CPU-2000) module which monitors and
directs the actions of all other modules in the system. Up to seven additional modules may be installed in various configurations. Internal communications are accomplished over a high-speed serial bus.
The CPU-2000 is provided with the Basic Equipment package. This module provides two Style Z and/or Style Y notification appliance circuits, Form-C alarm and trouble contacts, Remote Station alarm and trouble outputs, and a Municipal
Master Box output. A main power supply (MPS-24AF/MPS-24AFE or MPS-24BF/MPS-24BFE) and an initiating zone
module (IZ-4F or IZ-8F) must be added to make the basic system functional.
The basic system can be expanded using one or more of the following optional modules or boards:
IZ-8F Initiating Zone Module
IZ-4F Initiating Zone Module
IZE-AF Initiating Zone Expander
IC-4F Notification Circuit Module
ICE-4F Notification Circuit Expander
CR-4F Control Relay Module
AVPS-24F/AVPS-24FE Audio-Visual Power
Supply
CRE-4F Control Relay Expander
TC-2F Time Control Module
System expansion must comply with:
The physical limitations of the cabinet configuration.
The electrical limitations of the system power supplies (see Appendix A).
The capacity of the standby batteries (see Appendix A).
TC-4F Time Control Module
AFM-16ATF Annunciator Fixed Module
AFM-32AF Annunciator Fixed Module
AFM-16AF Annunciator Fixed Module
AFM-16ATX Annunciator Fixed Module
AFM-32AX Annunciator Fixed Module
UDACT-F Universal Digital Alarm Communicator Trans-
mitter
1.2KEY FEATURES
Distributed microprocessor electronics.
Field programmable in nonvolatile memory.
Alarm and trouble resound.
Plug-in terminal blocks for ease of field wiring and service.
On/Off status indicators on all notification appliance circuits and control relays.
4
S2000 15017 Rev H 10/08/96 P/N 15017:H
1.3RELATED DOCUMENTATION
Before proceeding, the installer should be familiar with the following documents.
NFPA STANDARDS:
NFPA 12 Installation, Maintenance, and Use of Carbon Dioxide Extinguishing Systems
NFPA 12A Installation, Maintenance, and Use of Halon 1301 Extinguishing Systems
NFPA 12B Installation, Maintenance, and Use of Halon 1211 Extinguishing Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
NFPA 72-1993 Installation, Maintenance, and Use of Central Station Signaling Systems.
NFPA 72-1993 Local Protective Signaling Systems
NFPA 72-1993 Auxiliary Protective Signaling Systems
NFPA 72-1993 Use of Remote Station Protective Signaling Systems
NFPA 72-1993 Use of Proprietary Protective Signaling Systems
NFPA 72-1993 Automatic Fire Detectors
NFPA 72-1993 Installation, Maintenance, and Use of Notification Appliances for Protective Signaling Systems
NFPA 72-1993 Testing Procedures for Signaling Systems
UNDERWRITERS LABORATORIES DOCUMENTS:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for the Hearing Impaired
UNDERWRITERS LABORATORIESOF CANADA (ULC) LISTED
Standard CAN/ULC-S527-M87
OTHER:
EIA-485 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
** Applicable Local and State Building Codes
** Requirements of the Local Authority Having Jurisdiction
S2000 15017 Rev H 10/08/96 P/N 15017:H
5
1.4MINIMUM SYSTEM CONFIGURATIONS
At a minimum, the following Sensiscan components are required for compliance with NFPA standards 12, 12A, 12B and 72-
1993.
BE-2000 Basic Equipment Package which includes:
CPU-2000 Central Processor Module, Vented Dress Panel, CHS-4F Chassis, and connecting
cables.
An IZ-4F or IZ-8F Initiating Zone Module for up to eight Style B initiating device circuits.
The Main Power Supply (MPS-24AF/MPS-24AFE or MPS-24BF/MPS-24BFE)
Standby Batteries - refer to Standby Power Requirements, Appendix A.
A Sensiscan 2000 Cabinet (CAB-A3F or CAB-B3F)
In addition, the following equipment is required for the specific NFPA standards listed below.
An NFPA 72-1993 Proprietary Protected Premises Control Unit requires:
Potter Electronic Signal Co. Transmitter (Model EFT-C) with transformer (Model ULT, Stock. Number 1000391).
An NFPA 72-1993 Central Station Protected Premises Control Unit requires:
UDACT-F, 911A Digital Communicator or an Ademco No. 678 UL-F Digital Communicator
Sprinkler Supervisory and/or Waterflow Alarm Service requires a Control Relay Module.
An NFPA-12 Minimum Carbon Dioxide Extinguishing Control Unit, NFPA-12A Halon 1301 Fire Extinguishing Control
Unit, NFPA-12B Halon 1211 Fire Extinguishing Control Unit requires:
TC-2F or TC-4F Time Control Module.
NOTE
For wiring diagrams and more information on these applications, refer to Section6.
6
S2000 15017 Rev H 10/08/96 P/N 15017:H
SECTION TWO: INVENTORY
The Sensiscan 2000 is offered under a Basic Equipment (BE-2000) package which provides the CPU-2000 module, the
VP-1F Vented Dress Panel, one CHS-4F Chassis, interconnecting cables and instruction manuals.
Other Components include modules and devices not provided in the Basic Equipment package. These components also
include several items necessary to complete a basic system, such as the main power supply, initiating modules, notification
modules, and control relay modules. See Section One for minimum system requirements.
This installation manual covers a basic system. For information on other devices, refer to the installation manuals of the
following products:
This module is the heart of the system. It controls and monitors the system modules
and provides a full accounting of system status. In addition, the CPU contains two
notification appliance circuits, a Remote Signaling Municipal Tie Circuit, and FormC alarm and trouble contacts. Field programming of the system is accomplished from
this module via the use of the Programming Key. Slide-in labels for programming,
control, and system operation are provided with the CPU, as well as end-of-line and
dummy load resistors.
Power Ribbon
(71085)
Main Bell Power Harness
(71093)
End-of-Line Resistor
(ELR)
4.7K, 1/2 watt (71252)
Power Harness
(71086)
Dummy Load Resistor
4.7K, 1/2 watt (71245)
First-Row Ribbon Cable
(71087)
VP-1F Vented Dress Panel
Covers the top row of modules in the
cabinet.
KEY #___ PWD#___
Programming
Key (PKB)
CHS-4 Chassis
For the mounting of up to four modules or four AVPS-24F
Audio-Visual Power Supplies. The CHS-4 occupies one
row in the CAB-A3F or CAB-B3F cabinet.
8
S2000 15017 Rev H 10/08/96 P/N 15017:H
2.2POWER SUPPLIES
MPS-24AF/MPS-24AFE
The MPS-24AF supplies the regulated power needed to run system modules. It
also supplies up to 3 amps of regulated notification appliance power, permitting
the use of a variety of standard UL-listed 24 VDC Notification Appliances
(refer to the FireLite Device Compatibility Document, Document 15384 for a
complete list of notification appliances). Up to one amp of resettable power is
available for four-wire smoke detectors. The MPS-24AF contains an integral
battery charger for 9.5 to 55 AH batteries.
MPS-24BF/MPS-24BFE
The MPS-24BF supplies the regulated power needed to run the system's modules. It also supplies up to 2.0 amps of RMS-regulated notification appliance
power, permitting the use of a variety of standard UL-listed 24 VDC notification appliances (see Document 15384 for a complete list). Up to 200mA of
resettable power is available for four wire smoke detectors. The MPS-24BF
contains an integral battery charger capable of charging batteries in the 6.5 to
17 AH range. Includes two sets of battery cables, one with 1/4" lug-type connectors for larger batteries and one set with 3/16" lug-type connectors.
AVPS-24F/AVPS-24FE AUDIO VISUAL POWER SUPPLY
Supplies power to notification appliance circuits only. Unfiltered, unregulated, 3.0 amps
maximum. Assumes one position on the CHS-4 Chassis. Provided with a trouble cable
for connection to the main power supply. See Document 15384 for a list of compatible,
UL-listed notification appliances. The AVPS-24F may be installed under any module
except the CPU or modules with expander board installed.
BP-3F BATTERY DRESS PANEL
Covers the main power supply and the batteries in the
cabinet (provides dead-front where required).
S2000 15017 Rev H 10/08/96 P/N 15017:H
9
2.3MODULES
IZ-8F INITIATING
ZONE MODULE
This module provides eight
Style B initiating device circuits. Circuits are power limited and can be programmed for
standard fire, Waterflow Alarm,
Supervisory service, Non
Alarm or Command Inputs.
Also provided are eight end-ofline and eight dummy load resistors.
IZ-4F INITIATING
ZONE MODULE
This module provides four
Style B initiating device circuits. Circuits are power limited and user programmable for
standard fire, Waterflow Alarm
or Supervisory service. Also
provided are four end-of-line
and four dummy load resistors.
IZE-AF INITIATING
ZONE EXPANDER
Converts the eight initiating device circuits on the Initiating
Zone Module (IZ-8F) to Style
D operation. The expander
plugs into the bottom of the IZ8F.
Note: This module will not support an IZE-AF Expander.
End-of-Line Resistor (ELR)
4.7K, 1/2 watt (71252)
Dummy Load Resistor
4.7K, 1/2 watt (71245)
10
RS-1459 MODULE
The RS-1459 module is used in conjunction with
the Remote Station or Municipal Box Output. The
RS-1459 is NOT required for the Municipal Box
Circuit if wiring remains in conduit, wire length is
less than 1000 meters, and wiring does not cross
any power lines. All conditions must be met according to page 23 of this manual (refer to Figure4-3). For more information on the RS-1459 module, refer to the RS-1459 Product Installation Drawing, Document 50519.
S2000 15017 Rev H 10/08/96 P/N 15017:H
IC-4F INDICATING CIR-
CUIT MODULE
ICE-4F INDICATING CIR-
CUIT EXPANDER
Provides four notification appliance
circuits for Style Y or Style Z operation. Maximum signaling current is
3.0 amps (3 amps max per circuit).
Circuits are field programmable to
respond to a single initiating zone, a
group of zones, or all initiating
zones. End-of-line resistors, dummy
load resistors, and an Auxiliary Bell
Power Harness are provided with
each module. For California Code see Figure 4-7.
CR-4F CONTROL RELAY
MODULE
Provides four standard dry FormC alarm contacts rated for 5 amps
@ 120 VAC or 30 VDC (resistive).
Each relay is field programmable
to respond to a single device circuit, a group of circuits, or all initiating device circuits.
Expands the IC-4F to a total of eight
notification appliance circuits (either
Style Y or Style Z). Circuit ratings
are identical to those of the IC-4F.
An Auxiliary Bell Power Harness is
provided with each expander. The
expander plugs into the back of the
IC-4F.
TC-2F/TC-4F TIME
CONTROL MODULE
The TC-2F module can be
configured for one of five
functions. Pre-signal evacuation or dual code evacuation,
and standard release service,
triple-coded release, or IRI release. For more information,
refer to the TC-2F Manual.
The TC-4F can provide either
four releasing circuits or four
power-limited dual code
evacuation circuits. For more information, refer to the TC4F Manual.
THE UNIVERSAL DIGITAL
ALARM COMMUNICATOR/
TRANSMITTER
The UDACT-F may be used with
the FireLite MS-9200 and
Sensiscan 2000 control panels.
The UDACT-F transmits system
status to UL-Listed Central Station
Receivers via the public switched
telephone network. The UDACTF is compact in size and may be
mounted inside the host control
panel or may mount externally in
a separate enclosure. EIA-485 annunciator communications bus
and 24 volt (nominal) connections are required. The UDACT-F
is capable of reporting 198 points or 56 zones when used with
the MS-9200 and 56 zones when used with the Sensiscan 2000.
S2000 15017 Rev H 10/08/96 P/N 15017:H
CRE-4F CONTROL
RELAY EXPANDER
Expands the capacity of the
Control Relay Module (CR4F) to eight Form-C alarm relays. Relays are identical to
those on the CR-4F. The expander plugs into the back of
the CR-4F or IC-4F.
11
2.4EQUIPMENTFORTHE SENSISCAN 2000
F-ELR
The F-ELR Resistor Assortment is required for use in Canada. It includes a variety of ELR
values for supervising IZ or IC circuits. The desired resistor mounts to a single ELR plate (illustrated). Included with the F-ELR:
The CHS-4F expansion chassis package is required for all CAB-B3F installations. The CHS-4F includes the CHS-4 Chassis, the MP-1F Module Dress
Panel (illustrated), and an Expander Ribbon Cable.
AFM-16ATX
The AFM-16ATX Annunciator Control Module contains 16 red alarm and 16 yellow trouble LEDs, 16 momentary touchpad switches for controlling each point, a system trouble LED, an ON LINE/POWER LED, and a local piezo sounder with
a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator. The AEM-16ATFAnnunciator Expander Module expands the AFM-16ATX by 16 system points. One to three of these expander modules
can be supported by an AFM-16ATX to a maximum of 64 system points.
MP-1F Module Dress Panel
AFM-32AX
The AFM-32AX Annunciator Control Module contains 32 red alarm LEDs, a System Trouble LED,
an ON LINE/POWER LED, and a local piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator. The AEM-32ATF ExpanderModule expands the AFM-32AX by 32 system points. One expander module can be supported by
an AFM-32AX, providing a maximum of 64 points.
AFM-16ATF
The AFM-16ATF Annunciator Fixed Module contains 16 red alarm and 16 yellow trouble LEDs,
16 momentary touch-pad switches, a system trouble LED, an ON LINE/POWER LED, and a local
piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator. Only One annunciator may be used in a system.
AFM-32AF
The AFM-32AF Annunciator Fixed Module contains 32 red alarm LEDs, a System Trouble LED,
an ON LINE/POWER LED, and a local piezo sounder with a Local Silence/Acknowledge switch
for audible indication of alarm and trouble conditions. Only one annunciator may be used in a
AFM-16ATX
system.
AFM-16AF
The AFM-16AF Fixed Annunciator module is intended for use in systems that require 16 alarm annunciator points or less.
Only one annunciator may be used in a system.
12
S2000 15017 Rev H 10/08/96 P/N 15017:H
2.5CABINETS
The CAB-A3F and CAB-B3F cabinet assemblies consist of a backbox and a locking door with two keys. The backbox and
door can be ordered separately or as a complete package.
CAB-A3F
CAB-B3F
TR-A3R/TR-B3R TRIM RING
For semi-flush mounting of the cabinet
S2000 15017 Rev H 10/08/96 P/N 15017:H
13
SECTION THREE: I NSTALLATION
The control panel's modules communicate with the CPU
through a common ribbon cable connection.
The following procedures, diagrams, and instructions must be followed precisely to avoid damage to the control panel and
its associated equipment. Reliability depends to a great extent upon proper installation and maintenance.
Cabinet - Mount the cabinet and draw all field wiring through the knockouts provided. If the door is left-hanging,
❏❏
❏
❏❏
mount door hardware now, due to the main power supply resting on lower hinge.
NOTE
Do not draw wiring into the bottom nine inches of the cabinet or conflict with the power
supply and batteries may result.
Main Power Supply - Mount the main power supply to the cabinet as illustrated in Figure 3-3. Do not wire anything
❏❏
❏
❏❏
at this time!
Chassis- Mount all chassis. Refer to Figure 3-2 for installation of the CHS-4 chassis.
❏❏
❏
❏❏
Audio Visual Supplies - If any optional audio visual power supplies are to be employed, mount them to the chassis.
❏❏
❏
❏❏
Refer to Figure 3-4 for mounting of the AVPS-24F/AVPS-24FE to the CHS-4.
Audio Visual Cables - Connect the trouble cable(s) and Auxiliary Bell Power Harness to the audio visual power
❏❏
❏
❏❏
supply as illustrated in Figure 5-4.
❏❏
❏
❏❏
Preliminary System Wiring- The main power supply and any audio visual power supplies should be wired at this
time while the terminals are readily accessible. Refer to Section Five to wire the main power supply, audio visual
power supplies or the R45-24.
14
S2000 15017 Rev H 10/08/96 P/N 15017:H
Module Ribbon Cables - Connect the 1st Row Ribbon Cable to the CPU as illustrated in Figure 3-8. For each
❏❏
❏
❏❏
additional row of modules installed in the cabinet, connect an Expander Row Ribbon Cable to the CPU.
CPU - Install the CPU module in the top left cabinet position as illustrated in Figure 3-7. Connect the Power Ribbon
❏❏
❏
❏❏
and Power Harness between the CPU and the main power supply as illustrated in the respective figure in Section Four.
Module Expander Boards - If expander boards are to be used with a module, install as illustrated in Figure 3-5.
❏❏
❏
❏❏
Modules - Mount each module in its respective chassis position as illustrated in Figure 3-6. Connect the CPU Row
❏❏
❏
❏❏
Ribbon Cable and the Expander Row Ribbon (in CAB-B3F installations) to the modules. Field-wire each module,
using the following figures for reference:
CPU-2000Figure 4-3, 4-4
IZ-8F or IZ-4F (Style B)Figure 4-5
IZ-8F requires IZE-AF (for Style D)Figure 4-6
IC-4F/ICE-4FFigure 4-7 (ICE-4F Optional)
CR-4F/CRE-4FFigure 4-8 (CRE-4F optional)
TC-2F(Refer to the TC-2F Manual)
TC-4F(Refer to the TC-4F Manual)
AFM-16ATF, AFM-32AF,AFM-16AF,
AFM-16ATX,AFM-32AX(Refer to respective manual.)
UDACT-FFigure 6-1
Power-on-check - Apply AC power to the control panel. Do not connect the batteries at this time! To silence the
❏❏
❏
❏❏
audible trouble sounder, push the ACKNOWLEDGE switch on the CPU. The system should reflect the following
status.
On the CPU
Green AC POWER indicator should be on.
The BATTERY FAIL indicator will be on due to the absence of batteries.
SYSTEM TROUBLE and POWER FAILURE indicators should be on due to the absence of batteries.
MODULE FAILURE indicator may light shortly after AC power is applied (applies only to a system that has
not been previously configured).
On each module
The yellow trouble indicators may come on approximately ten seconds after AC power is applied (applies
only to a system that has not previously been configured).
On each AVPS
The yellow trouble indicators will light due to the absence of batteries.
On the main power supply
Failure of the AC POWER indicator, or the presence of indications not mentioned above may suggest an installation
problem. Carefully review the installation instructions to isolate the source.
Programming - To configure and program the system, refer to field programming in Section Seven.
❏❏
❏
❏❏
Batteries - Once the system has been programmed and is functional, connect the batteries. Ensure that all indicators
❏❏
❏
❏❏
except AC POWER are extinguished.
Testing - Fully field test the system by conducting the test procedure in Section Nine.
❏❏
❏
❏❏
Dress Panels - Complete installation of the system by installing the cabinet door first, followed by the dress panels
❏❏
❏
❏❏
(VP-1F and MP-1F).
S2000 15017 Rev H 10/08/96 P/N 15017:H
15
FIGURE 3-1 : MOUNTTHECABINETBACKBOX
Mount the backbox in a clean, dry, vibration free area, using the four
holes provided in the back surface of the cabinet.
Grounding Cable
17-15/16
FIGURE 3-2: INSTALLA CHS-4
Install a CHS-4 in each row of the cabinet that will employ Sensiscan 2000 modules. For proper grounding of
the modules to the cabinet, connect a grounding cable to
one of the chassis mounting screws as illustrated.
FIGURE 3-3: INSTALLTHE MAIN POWER
SUPPLY
Place the MPS-24AF/MPS-24AFE (shown) or MPS-24BF/
MPS-24BFE into the bottom of the cabinet, ensuring that
the upper bracket engages the support bracket on the cabinet. Secure the bottom of the power supply to the bottom
cabinet support with the provided screws.
FIGURE 3-4: INSTALLTHE AVPS
16
CHS-4
Install any optional AVPS-24F/AVPS-24FE over the screw
AVPS
S2000 15017 Rev H 10/08/96 P/N 15017:H
mounts on the CHS-4 and secure with the two provided nuts.
FIGURE 3-5: MOUNTING MODULE EXPANDERS
Module
Step 1:
Attach four standoffs to the
module using the four screws
provided.
ExpanderModule
Step 2:
Insert the pins on the expander board into
the connector on the module and press the
two boards together, ensuring that the pins
are properly aligned.
FIGURE 3-6: MOUNTING MODULESINTHE CHASSIS
Step 1:
Angle the module into the cabinet so that the upper
board edge slips into the cabinet slot as shown.
Step 2:
Push the upper end of the module into the cabinet and secure
with two module screws. Straighten LEDs so that they extend
from the board at a 90 degree angle.
Expander/Module
Step 3:
Secure the module/expander assembly with the four nuts and lock
washers provided.
Cabinet
Cabinet
S2000 15017 Rev H 10/08/96 P/N 15017:H
17
FIGURE 3-7: MOUNTINGTHE CPU-2000
Step 1:
Insert the CPU Module into the left-most
cabinet slot, angling the front end of the
module into position as shown.
Step 2:
Push the back end of the module down into the
cabinet and pull down until the upper board
engages the slot on the chassis as shown.
Bottom View
18
Step 3:
Align the module screws with the
thread-holes on the chassis and secure
in place.
Mount the RS-1459 to two studs in any position on the back of the CHS-4. Use the provided standoffs and screws to mount
the module. Refer to Figure 4-3 for information on wiring the module.
RS-1459
CHS-4
S2000 15017 Rev H 10/08/96 P/N 15017:H
19
SECTION FOUR: FIELD WIRINGTHE MODULES
The IC-4F Notification Circuit Module, as well
as the IZ, CR and TC modules feature removable
terminal blocks that ease installation and servicing of the control panel.
20
S2000 15017 Rev H 10/08/96 P/N 15017:H
4.1UL POWER-LIMITED WIRING REQUIREMENTS
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpowerlimited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram
for the Sensiscan 2000 is shown below.
Nonpowerlimited
circuits
Power-limited
circuits
Nonpower-limited
circuits
Power-limited
circuits
Power-limited
circuits
Po werlimited
circuits
Power supplies in bottom of cabinet - see Figure 4-2
Figure 4-1: Typical Wiring Diagram for UL Power-limited Wiring Requirements
S2000 15017 Rev H 10/08/96 P/N 15017:H
21
4.2UL POWER-LIMITED WIRING REQUIREMENTS - POWER SUPPLIES
The diagram below shows a typical Sensiscan 2000 installation and is provided as a guide for proper wiring placement. The
AC and battery wiring are not power-limited. A separation of at least 0.25" must be maintained between power-limited and
nonpower-limited wiring. Install the tie wraps and adhesive squares as indicated below.
Adhesive square and tiewrap on back of cabinet
affixing power-limited
wiring.
22
Adhesive square and
tie-wrap on back of
cabinet and on top of
power supply chassis
affixing nonpowerlimited wiring.
Figure 4-2: Power-limited and Nonpower-limited Wiring for Power Supplies
Use only compatible, UL-listed notification appliances (see the Device Compatibility Document, 15378). Max current per circuit is 3.0
amps, subject to the limitations of the power
supply.
Style Y
4.7K, 1/2 watt ELR,
Part # 71252.
Non-Supervised
Remote Station Outputs
Non-Supervised, Power-limited
(Standby polarity shown)
24 VDC (nominal). 10 mA max rated
current. Internal resistance = 1360 ohms
(nominal).
Intended for connection to the polarity
reversal circuit of a remote station receiving unit (Fire-Lite Model RS-82) having
compatible ratings.
Remote Station
Trouble Output
Remote Station
Alarm Output
Municipal Box Output
Nonpower-limited, supervised for
open circuits. Max. Current (short
circuit) = 0.6 amps. Max. Voltage
(open circuit) = 27.6 VDC. Max.
Wire Resistance = 5 ohms.
Municipal Box Ratings
Trip current = 0.25 Amps (min)
Coil voltage = 3.65 VDC (min)
Coil resistance = 14.6 ohms (max)
UL-listed
24 VDC
Polarized Bell
UL-listed
24 VDC
Polarized Horn
Style Z
System
Trouble
Contacts
(power-limited
source only)
2A @ 30VDC
1A @ 120VAC
(resistive)
Programmable
Alarm
Contacts
(power-limited
source only)
5A @ 30VDC
5A @ 120VAC
(resistive)
Figure 4-3: Field Wiring the CPU
Municipal box wiring
must be run in conduit.
Municipal Box Output
Nonpower-limited and supervised (for open circuits). Wiring can leave the building.
1)The Remote Station Alarm Output and the Municipal Box Output must not be used simultaneously.
2)Notification appliance circuits, Remote Station Trouble output, and the Remote Station Alarm output are power-
limited and may be connected to limited-energy cable.
3)Wire notification appliances according to the manufacturer's instructions packaged with each device.
4)Terminal blocks will accept #12 to #22 AWG wire.
5)Size notification circuit wire for a maximum drop of 2 volts DC at the last device on the circuit.
6)The RS-1459 module is required when the Remote Station or Municipal Box Output is connected to a circuit that
exits the protected premises. Exception - The RS-1459 module is not required for the Municipal Box Circuit if
ALL of the following conditions exist: (1) wiring is in conduit, (2) wire length is less than 1000 meters, and (3)
wiring does not cross any power lines.
S2000 15017 Rev H 10/08/96 P/N 15017:H
23
Loading...
+ 51 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.