The Sensiscan 200 is an expandable multi-zone Fire Alarm Control Panel based on a modular design for
maximum flexibility. The heart of the system is the Central Processor Unit (CPU) module which monitors and
directs the actions of all other modules in the system. Up to two other modules may be installed in various
configurations. Internal communications are accomplished over a high-speed serial bus.
The CPU-2000 is provided with the BE-200 Basic Equipment package. This module provides two Style Z and/or
Style Y Notification Appliance Circuits, Form-C alarm and trouble contacts, Remote Station alarm and trouble
outputs, and a Municipal Master Box output.
An initiating zone module (IZ-4F or IZ-8F) and a CAB-200 cabinet must be added to make the basic system
functional.
The basic system can be expanded using one or more of the following optional modules or boards:
• IZ-8F Initiating Zone Module
• IZ-4F Initiating Zone Module
• IZ-4AF Initiating Zone Module
• IZE-AF Initiating Zone Expander
• IC-4F Indicating Circuit Module
• ICR-4LF Combination Output Module
• ICE-4F Indicating Circuit Expander
• AVPS-24F Audio-Visual Power Supply
• CR-4F Control Relay Module
• CR-4LF Control Relay Module
• CRE-4F Control Relay Expander
• TC-2F Time Control Module
• TC-4F Time Control Module
• UDACT-F Universal Digital Alarm
Communicator Transmitter
System expansion must comply with:
• The physical limitations of the cabinet configuration.
• The electrical limitations of the system power supply (see Appendix A).
• The capacity of the standby batteries (see Appendix A).
Key Features
• Distributed microprocessor electronics.
• Field programmable in nonvolatile memory.
• Manual Disable control for all Notification Appliance Circuits and control relays.
• Alarm verification, with device type discrimination.
• Walk Test, with zone change indication.
• Serial annunciators, including LCD and custom annunciators.
• Multiple hazard release control modules.
• Programmable software timers including positive alarm sequence.
4
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Before proceeding, the installer should be familiar with the following documents and
standards (as appropriate):
NFPA Standards:
NFPA 13 Sprinkler System.
NFPA 72-1993 Installation, Maintenance, and Use of Central Station Signaling Systems.
NFPA 72-1993 National Fire Alarm Code for Local, Auxiliary, Remote Station and Proprietary Fire
Alarm Systems, Automatic Fire Detectors, Notification Appliances for Fire Alarm Systems, and
Testing Procedures for Signaling Systems.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
Underwriters Laboratories of Canada (ULC) listed
Standard CAN/ULC-S527-M87
Other:
EIA-485 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
5
Minimum System Configurations
At a minimum, the following components are required for compliance with NFPA standards 12, 12A,
12B, and 72-1993. Supervisory listing is for local systems only.
1. BE-200 Basic Equipment Package which includes:
Central Processor Module (CPU-2000), Main Power Supply (MPS-24BPCC), transformer
(4000TA), interconnecting cables, mounting hardware and an instruction manual.
2. An IZ-4F, IZ-4AF or IZ-8F Initiating Zone Module for up to eight Style B Initiating Device Circuits.
3. Standby Batteries - refer to Standby Power Requirements, Appendix A.
4. Cabinet (CAB-200).
In addition, the following equipment is required for the specific NFPA standards listed below:
An NFPA 72-1993 Central Station Protected Premises Control Unit requires:
5. Fire-Lite UDACT-F, Noti•Fire 911A Digital Communicator or the Fire•Lite MS-5012 Control
Communicator.
An NFPA-12 Minimum Carbon Dioxide Extinguishing Control Unit, NFPA-12A Halon 1301 Fire Extinguishing
Control Unit, NFPA-12B Halon 1211 Fire Extinguishing Control Unit or NFPA - 13 requires:
5. TC-2F or TC-4F Time Control Module.
For wiring diagrams and more information on these applications, refer to Section 6.
6
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Section Two:
Inventory
The Sensiscan 200 is offered under a Basic Equipment (BE-200) package which provides the CPU module, Main
Power Supply, interconnecting cables and an instruction manual.
Components include modules and devices not provided in the Basic Equipment package. These components
also include several items necessary to complete a basic system, such as an initiating module and cabinet. See
Section One for Minimum System Requirements.
This installation manual covers system basics. For information on special applications, refer to the following
installation manuals:
This module is the heart of the system. It controls and monitors the system
modules and provides a full accounting of system status. In addition, the CPU
contains two Notification Appliance Circuits, a Remote Signaling Municipal Tie
Circuit, and Form-C alarm and trouble contacts. Field programming of the
system is accomplished from this module via the use of the Programming Key.
Includes End-of-Line and Dummy Load resistors.
KEY #___ PWD#___
End-of-Line Resistor
4.7K, 1/2 watt (71252)
MPS-24BPCC
The MPS-24BPCC supplies the regulated power needed to run
the system modules. It also supplies up to 2.0 amps of regulated
notification appliance power, permitting the use of a variety of
standard UL listed 24 VDC notification appliances (see the
Device Compatibility Document for a complete listing). Up to
200 mA of resettable power is available for four wire smoke
detectors. The MPS-24BPCC contains an integral battery
charger capable of charging batteries in the 6.5 to 17 amp-hour
range (Note: 15-17AH batteries require a separate battery
cabinet). Includes two sets of battery cables, one for large
battery terminals and one for small terminals. Note: For
reorders, specify an "MPS-24BRB" (for
Dummy Load Resistor
4.7K, 1/2 watt (71245)
4000TA Transformer
Programming Key
(PKB)
Replacement Board
).
Module Ribbon Cable
(75171)
Power Ribbon
(75170)
8
Main Bell Power Harness
(75169)
Power Harness
(75168)
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Positive Battery Cable (red)
(71071)
Negative Battery Cable (black)
(71072)
Series Interconnect
(71070)
Modules
IZ-8F Initiating
Zone Module
This module provides eight
Style B Initiating Device Circuits. Circuits are power
limited and can be programmed by the user for
standard fire, Waterflow
Alarm, Supervisory service,
Non Alarm or Command Inputs. Also provided are
eight End-of-Line and eight
Dummy Load Resistors.
IZE-AF Initiating
Zone Expander
Converts the eight Initiating Device Circuits on the Initiating
Zone Module (IZ-8F) to Style D
operation. The expander plugs
into the bottom of the IZ-8F.
IZ-4F Initiating
Zone Module
This module provides four
Style B Initiating Device Circuits. Circuits are power
limited and are user programmable for standard
fire, Waterflow Alarm,
Supervisory service, Non
Alarm or Command Inputs.
Also provided are End-ofLine Resistors and Dummy
Load Resistors.
Note: This module will not
support the IZE-AF Initiating Zone Expander module.
IZ-4AF Initiating
Zone Module
This module provides four
Style D Initiating Device
Circuits. Circuits are power
limited and user programmable for standard fire,
Waterflow Alarm, Supervisory service, Non-Alarm or
Command inputs.
End-of-Line Resistors
Note: This module will not
support an IZE-AF Initiating Zone Expander
module.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Dummy Load Resistors
9
Modules
TC-2F/TC-4F Time
Control Module
The TC-2F module is intended for single-hazard release and can be configured for standard release
service triple coded release, or IRI release. It includes abort and manual
release circuits and an adjustable timer and display.
For more information refer
to the TC-2F Manual.
The TC-4F can provide either four releasing circuits
or four two-stage evacuation circuits. Each circuit includes a cross-zone option
and delay timer option. For
more information refer to
the TC–4F Manual.
CR-4LF Control
Relay Module
Provides four standard dry
Form-C alarm contacts rated
for 5 amps @ 120 VAC or 28
VDC (resistive). Each relay is
field programmable to respond
to a single Initiating Device Circuit, a group of circuits, or all
Initiating Device Circuits.
ICR-4LF Combination
Output Module
Provides two standard dry
Form-C alarm contacts rated
for 5 amps @ 120 VAC or 28
VDC (resistive) and two Style
Y Notification Appliance Circuits. All relays and circuits
are field programmable. Also
provided are: End-Of-Line
Resistors, Dummy Load Resistors, and Auxiliary Bell
Power Harness.
One Auxiliary Bell Power
Harness
Two End-of-Line
Resistors
4.7K, 1/2 watt (71252)
Two Dummy Load
Resistors
4.7K, 1/2 watt (71245)
RS-1459 Module
The RS-1459 module is used in conjunction with the
Remote Station or Municipal Box Output. When the
RS-1459 is employed, an AVPS-24F audio visual
power supply cannot be installed. The RS-1459 is NOT
required for the Municipal Box Circuit if wiring remains
in conduit, wire length is less than 1000 meters, or
wiring does not cross any power lines. All conditions
must be met according to Figure 4-1. Refer to Figures3-1 and 4-1. For more information on the RS-1459
module, refer to the RS-1459 Product Installation
Drawing.
10
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Modules
IC-4F Indicating
Circuit Module
Provides four Notification
Appliance Circuits for
Style Y or Style Z operation. Maximum signaling
current is 3.0 amps (3
amps max per circuit). Circuits are field programmable to respond to a single
initiating zone, a group of
zones, or all initiating
zones. ELRs, Dummy
Load Resistors, and an
Auxiliary Bell Power Harness (shown below) are
provided with each module. For California Code
programming, consult the
factory.
CR-4F Control Relay
Module
Provides four standard dry
Form-C alarm contacts rated
for 5 amps @ 120 VAC or 30
VDC (resistive). Each relay is
field programmable to respond to a single Initiating
Device Circuit, a group of circuits, or all Initiating Device
Circuits.
ICE-4F Indicating
Circuit Expander
Expands the IC-4F to a total of
eight Notification Appliance Circuits (either Style Y or Style Z).
Circuit ratings are identical to
those of the IC-4F. An Auxiliary
Bell Power Harness is provided
with each expander. The expander plugs into the back of the
IC-4F.
Auxiliary Bell Power Harness
CRE-4F Control Relay
Expander
Expands the capacity of the
Control Relay Module (CR-4F)
to eight Form-C alarm relays.
Relays are identical to those on
the CR-4F. The expander plugs
into the back of the CR–4F, IC4F, TC-2F or TC-4F.
UDACT-F Universal
Digital Alarm
Communicator
Transmitter
Transmits system status to UL Listed Central
Station Receivers via
the public switched
telephone network.
It is capable of reporting
up to 56 software
zones.
Communicators
911A Digital Communicator Transmitter
Is a three-zone module designed to provide for offpremises monitoring of this fire alarm control panel.
For stand-alone installations, use the 911AC kit that
includes a
transformer
and an
enclosure(s)
for both the
911A and the
transformer.
Refer to the
Notifire 911A
manual,
Document #74-06200-005-A.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
11
Optional Components
AVPS-24F Audio-Visual Power Supply
Supplies power to Notification Appliance Circuits only.
Special Purpose power (unfiltered, unregulated) rated for
3.0 amps maximum. Provided with a Trouble Cable
(below) for connection to the Main Power Supply.
Trouble Cable
(P/N 71033)
CAB-200 Cabinet
The cabinet is 17" high by 14-1/2"
wide for recessed mounting between
wall studs. Includes a backbox (illustrated) and door.
DP-200 Dress Panel
Mounts to the cabinet to cover system
components.
12
TR-200 Trim Ring
For semi-flush mounting of the cabinet.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Section Three:
Installation
The control panel's modules communicate with the
CPU through a common ribbon cable connection.
Installation Outline
The following procedures, diagrams, and instructions must be followed precisely to avoid damage to the
control panel and its associated equipment. Reliability depends to a great extent upon proper installation and
maintenance.
Cabinet - Mount the cabinet and draw all field wiring through the knockouts provided. NOTE: Use only one
❑❑
❑
❑❑
of the two knockouts provided on the bottom of the cabinet. The batteries will cover the other knockout.
Main Power Supply - Mount the Main Power Supply to the cabinet as illustrated in Figure 3-1.
❑❑
❑
❑❑
anything at this time!
Transformer - Mount the Transformer to the cabinet as illustrated in Figure 3-1.
❑❑
❑
❑❑
Audio Visual Supplies - If an optional AVPS-24F is to be employed, mount it to the cabinet (see Figure 3-1).
❑❑
❑
❑❑
Audio Visual Cables - If employing an AVPS-24F, connect the AVPS Trouble Cable. Connect the Auxiliary
❑❑
❑
❑❑
Bell Power Harness to the AVPS–24F. Refer to Section Five to connect these cables.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Do not wire
13
Preliminary System Wiring - The Main Power Supply (and AVPS-24F, if employed) should be wired at this time
❑❑
❑
❑❑
while their terminals are readily accessible. Refer to Section Five.
Module Ribbon Cables - Connect the Module Ribbon Cable to the CPU as illustrated in Figure 3-2.
❑❑
❑
❑❑
CPU - Install the CPU module in the top left cabinet position as illustrated in Figure 3-3. Connect the Power Ribbon
❑❑
❑
❑❑
and Power Harness between the CPU and the Main Power Supply as illustrated in the respective figure in Section
Five.
Module Expander Boards - If expander boards are to be used with a Sensiscan 200 modules, install as illustrated
❑❑
❑
❑❑
in Figure 3-4.
Modules - Mount each module in its respective chassis position as illustrated in Figure 3-5. Connect the CPU
❑❑
❑
❑❑
Row Ribbon to each module. Field-wire each module, using the following figures for reference:
CPUFigure 4-1, 4-2 and 4-3
IZ-8F/IZ-4FFigure 4-4 and 4-5
IZ-4AFFigure 4-6
IC-4F/ICE-4FFigure 4-7
CR-4F/CRE-4FFigure 4-8
CR-4LFFigure 4-9
ICR-4LFFigure 4-10
For the following devices, refer to their respective installation manual: TC-2F, TC-4F, ACM-8RF, LDM
Series, AFMX Series, 911A Communicator, and UDACT-F.
Power-on-check - Apply AC power to the system.
❑❑
❑
❑❑
trouble sounder, push the ACKNOWLEDGE switch on the CPU. The system should reflect the following status:
On the CPU
✓✓
✓ Green AC POWER indicator should be on.
✓✓
✓✓
✓ SYSTEM TROUBLE and POWER FAILURE indicators should be on due to the absence of batteries.
✓✓
✓✓
✓ MODULE FAILURE indicator may light shortly after AC power is applied (applies only to a system that
✓✓
has not been previously configured).
On each module
✓✓
✓ The yellow trouble indicators may come on approximately 10 seconds after AC power is applied (applies
✓✓
only to a system that has not previously been configured).
On each AVPS-24F
✓✓
✓ The yellow trouble indicators will light due to the absence of batteries.
✓✓
On the Main Power Supply
✓✓
✓ The BATTERY FAIL indicator will be on due to the absence of batteries.
✓✓
Failure of the AC POWER indicator, or the presence of indications not mentioned above may suggest an
installation problem. Carefully review the installation instructions to isolate the source.
Programming - Refer to Section Seven.
❑❑
❑
❑❑
Do not connect the batteries at this time!
To silence the audible
Batteries - Once the system has been programmed and is functional, connect the batteries. Ensure that all
❑❑
❑
❑❑
indicators except AC POWER are extinguished.
Testing - Fully field test the system by conducting the test procedure in Section Nine.
❑❑
❑
❑❑
Dress Panels - Complete installation of the system by installing the cabinet door and the optional dress panel.
❑❑
❑
❑❑
14
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Mount the Main Power Supply
here with the screws provided.
Mounting Configuration
Mount the AVPS-24F Audio
Visual Power Supply here
with nuts and lock washers
provided.
Mount the Transformer
here with nuts and lock
washers provided.
Optional Mounting Configuration
When using the Remote Station or
Municipal Box Output, the RS-1459
interface board must be used (refer to
Figure 4-1).
Mount the RS-1459 here with standoffs,
nuts and lock washers provided.
Note: The AVPS-24F cannot be
installed when the RS-1459 is being
used.
Figure 3-1: Mounting Power Supplies
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
15
CPU Row Ribbon
Plug into uppermost
connector on CPU.
L-Series Row Ribbon
Plug into second connector on CPU.
Assigns mod-
ules to positions 6 and 7.
Figure 3-2: Connecting Row
Ribbon Cables to the CPU
(Cables to be connected to modules later)
Figure 3-3: Mounting the CPU
L-Series modules
(IC-4RLF, CR-4LF)
Module
Position 6
Module
Position 7
Step 1:
Insert the CPU Module into the left-most cabinet slot,
angling the front end of the module into position as
shown.
Cabinet
Step 2:
Push the back end of the module down into the
cabinet and pull down until the upper board engages
the slot on the chassis as shown.
Cabinet
Step 3:
Align the supplied module screws with the thread-holes on the chassis and secure in place.
16
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Figure 3-4: Mounting Module Expanders
Module
Step 1:
Attach four standoffs to the
module using the four
screws provided.
Figure 3-5: Mounting L-Series Expansion Modules
Expander
Module
Step 2:
Insert the pins on the expander board
into the connector on the module and
press the two boards together, ensuring that the pins are properly aligned.
Expander/Module
Step 3:
Secure the module/expander
assembly with four nuts and
lock washers provided.
This arrangement will fit in
the right most position only.
Note:
L-Series modules
should not be mounted behind other L-Series modules.
L-Series Module Module
For Module Installation:
Attach four standoffs to the module using
the four screws provided. Attach L-Series
Module to standoffs using mounting holes.
Secure the assembly with four nuts and
lock washers.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
L-Series Module
Expander/Module
For Expander/Module Combination:
Attach the L-Series Module to the Expander/Module combination using the four standoffs provided.
Secure the entire assembly with the four nuts and
lock washers.
17
Figure 3-6: Mounting Modules in the Cabinet
Step 1:
Angle the module into the cabinet so that the upper
board edge slips into the cabinet slot as shown.
Cabinet
Step 2:
Push the upper end of the module into the cabinet and
secure with the two module screws provided.
Straighten LEDs so that they extend from the board at
a 90 degree angle.
Cabinet
18
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited
and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
A typical wiring diagram for the Sensiscan 200 is shown below.
Power-limited
circuits
Nonpower-limited
circuits
Power-limited
circuits
Nonpower-limited
circuits
AC Power
Figure 3-7: Typical Wiring Diagram for UL Power-limited Requirements
Notes:
1)The power-limited Remote Station Alarm Output and the nonpower-limited Municipal Box Output must not be used simultaneously.
2) Mounting two or more modules in the same chassis position requires that all modules be either power-limited or nonpower-limited;
mixing is not allowed. Following is a list of Power-limited and Nonpower-limited modules:
CR-4F (no power-limited label)
CR-4LF (no power-limited label)
CRE-4F (no power-limited label)
TC-2F (Releasing mode)
TC-4F (Releasing mode)
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
19
Section Four:
Field Wiring the Modules
The following procedures, diagrams, and instructions must be followed precisely to avoid
damage to the control panel and its associated equipment. Reliability depends to a great extent
upon proper installation and maintenance.
The system's modules feature removable
terminal blocks that ease installation and
servicing of the control panel.
20
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Figure 4-1: CPU Terminal Connections
Typical Supervised Power Limited Notification
Appliance Circuits
Use only compatible, UL listed notification appliances (see the
Device Compatibility Document). Max current per circuit is 3.0
amps, subject to the limitations of the power supply.
Style Y
4.7K, 1/2 watt ELR,
Part # 71252.
UL listed
24 VDC
Polarized Bell
UL listed
24 VDC
Polarized Horn
Style Z
Remote Station Outputs
Non-Supervised, Power Limited
(Standby polarity shown)
Wiring can leave the building
24 VDC (nominal). 10 mA max rated current.
Internal resistance = 1360 ohms (nominal).
Intended for connection to the polarity reversal
circuit of a remote station receiving unit (Fire-Lite
Model RS-82) having compatible ratings.
Remote Station
Trouble Output
General
Trouble
Contacts
(power-limited source
only)
2A @ 30VDC
1A @ 120VAC
(resistive)
Remote Station
Alarm Output
General
Alarm
Contacts
(power-limited source
5A @ 30VDC
5A @ 120VAC
(resistive)
Local Energy
Municipal Box
Trip current = 0.25 Amps (min)
Coil voltage = 3.65 VDC (min)
Coil resistance = 14.6 ohms (max)
Municipal box
wiring must be
run in conduit.
Municipal Box
Output
Supervised (for
open circuit)
Wiring can leave
the building
only)
Max Current = (short circuit) = 0.6 Amps
Max Voltage = (open circuit) = 27.6 VDC
Notes:
Max Wire Resistance = 5 Ohms
1)The Remote Station Alarm Output and the Municipal Box Output must not be used simultaneously.
2)Notification Appliance Circuits, Remote Station Trouble output, and the Remote Station Alarm output are power limited and
may be connected to limited-energy cable.
3)Wire Notification Appliances according to the manufacturer's instructions packaged with each device.
4)Terminal blocks will accept #12 to #22 AWG wire.
5)Size notification circuit wire for a maximum drop of 2 volts DC.
6)The RS-1459 module is required when the Remote Station or Municipal Box Output is connected to a circuit that exits the
protected premises. Exception - The RS-1459 module is not required for the Municipal Box Circuit if ALL of the following
conditions exist: (1) wiring is in conduit, (2) wire length is less than 1000 meters, (3) wiring does not cross any power lines and
(4) must not be in the vicinity of any high voltage..
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
21
Loading...
+ 48 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.