Fire-Lite Alarms Sensiscan 200 User Manual

12 Clintonville Road Northford, CT 06472 203-484-7161 FAX: 203-484-7118
The Sensiscan 200
Installation, Operation, and Programming Manual
Document # 15032 11/1/96 Rev:
C
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 72-
1993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are
not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49O C/32-120O F
and at a relative humidity of 85% RH (non-condensing) at 30O C/86O F.
However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a nominal room temperature of 15-27O C/60-80
F.
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system may operate erratically or can
be damaged when subjected to lightning induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.
O
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
installation.
Fire Alarm System Limitations
An automatic fire alarm system - typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm control
with remote notification capability can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Further-
more, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.
While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
FCC Warning
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with each
device. System inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of all inspections should
be kept.
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user will be required
to correct the interference at his own expense.
Technical Publishing Document PRECAULG.PM6 12/31/96
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-
tions du Canada.
Table of Contents
Section One: General Information ............................................................................................. 4
Section Tw o: Inventory......................................................................................................... ....... 7
The Basic Equipment Package......................................................................................... 8
Optional Modules.............................................................................................................. 9
Communicators .............................................................................................................. 11
Optional Components..................................................................................................... 12
Section Three: Installation ....................................................................................................... 13
Installation Outline .......................................................................................................... 1 3
Mounting the Po wer Supplies ......................................................................................... 15
Connecting the CPU Ribbon Cable ................................................................................ 16
Mounting the CPU .......................................................................................................... 16
Mounting Expander Modules .......................................................................................... 17
Mounting Modules in the Cabinet ................................................................................... 18
UL Power-limited Wiring Requirements .......................................................................... 19
Section Four: Field Wiring the Modules ................................................................................. 20
CPU T erminal Connections............................................................................................. 21
Dummy loading unused circuits...................................................................................... 22
The EIA interface............................................................................................................ 22
Wiring the Modules......................................................................................................... 23
Section Five: P ower Supplies.................................................................................................. 30
The Main Pow er Supply.................................................................................................. 30
MPS-24BPCC Harness Connections ............................................................................. 32
Wiring the AVPS-24F...................................................................................................... 33
Section Six: Applications ........................................................................................................ 34
Waterflow Alarm ............................................................................................................. 34
Supervisory Service ....................................................................................................... 34
Central Station................................................................................................................ 34
Digital Alarm Communicator Transmitters....................................................................... 34
Tee-Tapping.................................................................................................................... 39
Four-Wire Smoke Detectors ........................................................................................... 40
Notification Appliance Circuit Po wer Configurations....................................................... 41
Remote Command Inputs............................................................................................... 43
Section Seven: Programming................................................................................................... 46
Entering Passwords........................................................................................................ 46
Reconfigure Mode .......................................................................................................... 46
Access Security.............................................................................................................. 46
System Programming ..................................................................................................... 47
Extended Programming Features................................................................................... 51
Section Eight: Operating the Control P anel............................................................................ 53
CPU Circuits ................................................................................................................... 54
Modules .......................................................................................................................... 55
Disabling/Enabling Circuits............................................................................................. 56
Section Nine: T esting & Maintenance...................................................................................... 57
Periodic Testing and Service .......................................................................................... 57
Operational Checks ........................................................................................................ 57
Battery Checks ............................................................................................................... 58
Walk Test ........................................................................................................................ 58
Appendix A: Supply Calculations ........................................................................................... 59
Appendix B: Canadian Requirements .................................................................................... 64
Programming Log ..................................................................................................................... 65
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
3
Section One:
General Information
Introduction
The Sensiscan 200 is an expandable multi-zone Fire Alarm Control Panel based on a modular design for maximum flexibility. The heart of the system is the Central Processor Unit (CPU) module which monitors and directs the actions of all other modules in the system. Up to two other modules may be installed in various configurations. Internal communications are accomplished over a high-speed serial bus.
The CPU-2000 is provided with the BE-200 Basic Equipment package. This module provides two Style Z and/or Style Y Notification Appliance Circuits, Form-C alarm and trouble contacts, Remote Station alarm and trouble outputs, and a Municipal Master Box output.
An initiating zone module (IZ-4F or IZ-8F) and a CAB-200 cabinet must be added to make the basic system functional.
The basic system can be expanded using one or more of the following optional modules or boards:
• IZ-8F Initiating Zone Module
• IZ-4F Initiating Zone Module
• IZ-4AF Initiating Zone Module
• IZE-AF Initiating Zone Expander
• IC-4F Indicating Circuit Module
• ICR-4LF Combination Output Module
• ICE-4F Indicating Circuit Expander
• AVPS-24F Audio-Visual Power Supply
• CR-4F Control Relay Module
• CR-4LF Control Relay Module
• CRE-4F Control Relay Expander
• TC-2F Time Control Module
• TC-4F Time Control Module
• UDACT-F Universal Digital Alarm Communicator Transmitter
System expansion must comply with:
• The physical limitations of the cabinet configuration.
• The electrical limitations of the system power supply (see Appendix A).
• The capacity of the standby batteries (see Appendix A).
Key Features
• Distributed microprocessor electronics.
• Field programmable in nonvolatile memory.
• Manual Disable control for all Notification Appliance Circuits and control relays.
• Alarm verification, with device type discrimination.
• Walk Test, with zone change indication.
• Serial annunciators, including LCD and custom annunciators.
• Multiple hazard release control modules.
• Programmable software timers including positive alarm sequence.
4
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Before proceeding, the installer should be familiar with the following documents and standards (as appropriate):
NFPA Standards:
NFPA 13 Sprinkler System. NFPA 72-1993 Installation, Maintenance, and Use of Central Station Signaling Systems. NFPA 72-1993 National Fire Alarm Code for Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems, Automatic Fire Detectors, Notification Appliances for Fire Alarm Systems, and Testing Procedures for Signaling Systems.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers - Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances
Underwriters Laboratories of Canada (ULC) listed
Standard CAN/ULC-S527-M87
Other:
EIA-485 Serial Interface Standards NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
5
Minimum System Configurations
At a minimum, the following components are required for compliance with NFPA standards 12, 12A, 12B, and 72-1993. Supervisory listing is for local systems only.
1. BE-200 Basic Equipment Package which includes: Central Processor Module (CPU-2000), Main Power Supply (MPS-24BPCC), transformer
(4000TA), interconnecting cables, mounting hardware and an instruction manual.
2. An IZ-4F, IZ-4AF or IZ-8F Initiating Zone Module for up to eight Style B Initiating Device Circuits.
3. Standby Batteries - refer to Standby Power Requirements, Appendix A.
4. Cabinet (CAB-200).
In addition, the following equipment is required for the specific NFPA standards listed below:
An NFPA 72-1993 Central Station Protected Premises Control Unit requires:
5. Fire-Lite UDACT-F, Noti•Fire 911A Digital Communicator or the Fire•Lite MS-5012 Control
Communicator.
An NFPA-12 Minimum Carbon Dioxide Extinguishing Control Unit, NFPA-12A Halon 1301 Fire Extinguishing Control Unit, NFPA-12B Halon 1211 Fire Extinguishing Control Unit or NFPA - 13 requires:
5. TC-2F or TC-4F Time Control Module.
For wiring diagrams and more information on these applications, refer to Section 6.
6
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Section Two:
Inventory
The Sensiscan 200 is offered under a Basic Equipment (BE-200) package which provides the CPU module, Main Power Supply, interconnecting cables and an instruction manual.
Components include modules and devices not provided in the Basic Equipment package. These components also include several items necessary to complete a basic system, such as an initiating module and cabinet. See Section One for Minimum System Requirements.
This installation manual covers system basics. For information on special applications, refer to the following installation manuals:
tnemucoD
rebmuN
09351seludoMrotaicnunnAseireSX-MFAehT 07951eludoMdexiFrotaicnunnAehT 17951eludoMlortnoCemiTF2-CTehT 27951
26305eludoMlortnoCrotaicnunnAFR8-MCAehT 01251eludoMlortnoCrotaicnunnAFA61-MFAehT 48351tnemucoDytilibitapmoCeciveDetiL-eriF 55005eludoMrevirDpmaLseireSF23-MDLehT 94005rotacinummoCmralAlatigiDlasrevinUF-TCADU
rettimsnarT
emaNtnemucoD
eludoMlortnoCemiTF4-CTehT
A500-00260-47rotacinummoCA119eriF-itoN 91505gniwarDnoitallatsnItcudorP9541-SR 65005slangiSyrosivrepuSrofstnemeriuqeRnaidanaC
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
7
The Basic Equipment Package
CPU-2000 Central Processor Module
This module is the heart of the system. It controls and monitors the system modules and provides a full accounting of system status. In addition, the CPU contains two Notification Appliance Circuits, a Remote Signaling Municipal Tie Circuit, and Form-C alarm and trouble contacts. Field programming of the system is accomplished from this module via the use of the Programming Key. Includes End-of-Line and Dummy Load resistors.
KEY #___ PWD#___
End-of-Line Resistor
4.7K, 1/2 watt (71252)
MPS-24BPCC
The MPS-24BPCC supplies the regulated power needed to run the system modules. It also supplies up to 2.0 amps of regulated notification appliance power, permitting the use of a variety of standard UL listed 24 VDC notification appliances (see the Device Compatibility Document for a complete listing). Up to 200 mA of resettable power is available for four wire smoke detectors. The MPS-24BPCC contains an integral battery charger capable of charging batteries in the 6.5 to 17 amp-hour range (Note: 15-17AH batteries require a separate battery cabinet). Includes two sets of battery cables, one for large battery terminals and one for small terminals. Note: For reorders, specify an "MPS-24BRB" (for
Dummy Load Resistor
4.7K, 1/2 watt (71245)
4000TA Transformer
Programming Key
(PKB)
Replacement Board
).
Module Ribbon Cable
(75171)
Power Ribbon
(75170)
8
Main Bell Power Harness
(75169)
Power Harness
(75168)
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Positive Battery Cable (red)
(71071)
Negative Battery Cable (black)
(71072)
Series Interconnect
(71070)
Modules
IZ-8F Initiating
Zone Module
This module provides eight Style B Initiating Device Cir­cuits. Circuits are power limited and can be pro­grammed by the user for standard fire, Waterflow Alarm, Supervisory service, Non Alarm or Command In­puts. Also provided are eight End-of-Line and eight Dummy Load Resistors.
IZE-AF Initiating
Zone Expander
Converts the eight Initiating De­vice Circuits on the Initiating Zone Module (IZ-8F) to Style D operation. The expander plugs into the bottom of the IZ-8F.
IZ-4F Initiating
Zone Module
This module provides four Style B Initiating Device Cir­cuits. Circuits are power limited and are user pro­grammable for standard fire, Waterflow Alarm, Supervisory service, Non Alarm or Command Inputs. Also provided are End-of­Line Resistors and Dummy Load Resistors.
Note: This module will not support the IZE-AF Initiat­ing Zone Expander module.
IZ-4AF Initiating
Zone Module
This module provides four Style D Initiating Device Circuits. Circuits are power limited and user program­mable for standard fire, Waterflow Alarm, Supervi­sory service, Non-Alarm or Command inputs.
End-of-Line Resistors
Note: This module will not support an IZE-AF Initiat­ing Zone Expander module.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Dummy Load Resistors
9
Modules
TC-2F/TC-4F Time
Control Module
The TC-2F module is in­tended for single-hazard re­lease and can be config­ured for standard release service triple coded re­lease, or IRI release. It in­cludes abort and manual release circuits and an ad­justable timer and display. For more information refer to the TC-2F Manual.
The TC-4F can provide ei­ther four releasing circuits or four two-stage evacua­tion circuits. Each circuit in­cludes a cross-zone option and delay timer option. For more information refer to the TC–4F Manual.
CR-4LF Control
Relay Module
Provides four standard dry Form-C alarm contacts rated for 5 amps @ 120 VAC or 28 VDC (resistive). Each relay is field programmable to respond to a single Initiating Device Cir­cuit, a group of circuits, or all Initiating Device Circuits.
ICR-4LF Combination Output Module
Provides two standard dry Form-C alarm contacts rated for 5 amps @ 120 VAC or 28 VDC (resistive) and two Style Y Notification Appliance Cir­cuits. All relays and circuits are field programmable. Also provided are: End-Of-Line Resistors, Dummy Load Re­sistors, and Auxiliary Bell Power Harness.
One Auxiliary Bell Power
Harness
Two End-of-Line
Resistors
4.7K, 1/2 watt (71252)
Two Dummy Load
Resistors
4.7K, 1/2 watt (71245)
RS-1459 Module
The RS-1459 module is used in conjunction with the Remote Station or Municipal Box Output. When the RS-1459 is employed, an AVPS-24F audio visual power supply cannot be installed. The RS-1459 is NOT required for the Municipal Box Circuit if wiring remains in conduit, wire length is less than 1000 meters, or wiring does not cross any power lines. All conditions must be met according to Figure 4-1. Refer to Figures 3-1 and 4-1. For more information on the RS-1459 module, refer to the RS-1459 Product Installation Drawing.
10
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Modules
IC-4F Indicating
Circuit Module
Provides four Notification Appliance Circuits for Style Y or Style Z opera­tion. Maximum signaling current is 3.0 amps (3 amps max per circuit). Cir­cuits are field programma­ble to respond to a single initiating zone, a group of zones, or all initiating zones. ELRs, Dummy Load Resistors, and an Auxiliary Bell Power Har­ness (shown below) are provided with each mod­ule. For California Code programming, consult the factory.
CR-4F Control Relay Module
Provides four standard dry Form-C alarm contacts rated for 5 amps @ 120 VAC or 30 VDC (resistive). Each relay is field programmable to re­spond to a single Initiating Device Circuit, a group of cir­cuits, or all Initiating Device Circuits.
ICE-4F Indicating
Circuit Expander
Expands the IC-4F to a total of eight Notification Appliance Cir­cuits (either Style Y or Style Z). Circuit ratings are identical to those of the IC-4F. An Auxiliary Bell Power Harness is provided with each expander. The ex­pander plugs into the back of the IC-4F.
Auxiliary Bell Power Harness
CRE-4F Control Relay
Expander
Expands the capacity of the Control Relay Module (CR-4F) to eight Form-C alarm relays. Relays are identical to those on the CR-4F. The expander plugs into the back of the CR–4F, IC­4F, TC-2F or TC-4F.
UDACT-F Universal Digital Alarm Communicator Transmitter
Transmits system sta­tus to UL Listed Central Station Receivers via the public switched telephone network. It is capable of reporting up to 56 software zones.
Communicators
911A Digital Communicator Transmitter
Is a three-zone module designed to provide for off­premises monitoring of this fire alarm control panel. For stand-alone installations, use the 911AC kit that includes a transformer and an enclosure(s) for both the 911A and the transformer. Refer to the Notifire 911A manual, Document #74-06200-005-A.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
11
Optional Components
AVPS-24F Audio-Visual Power Supply
Supplies power to Notification Appliance Circuits only. Special Purpose power (unfiltered, unregulated) rated for
3.0 amps maximum. Provided with a Trouble Cable (below) for connection to the Main Power Supply.
Trouble Cable
(P/N 71033)
CAB-200 Cabinet
The cabinet is 17" high by 14-1/2" wide for recessed mounting between wall studs. Includes a backbox (illus­trated) and door.
DP-200 Dress Panel
Mounts to the cabinet to cover system components.
12
TR-200 Trim Ring
For semi-flush mounting of the cabinet.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Section Three:
Installation
The control panel's modules communicate with the CPU through a common ribbon cable connection.
Installation Outline
The following procedures, diagrams, and instructions must be followed precisely to avoid damage to the control panel and its associated equipment. Reliability depends to a great extent upon proper installation and maintenance.
Cabinet - Mount the cabinet and draw all field wiring through the knockouts provided. NOTE: Use only one
of the two knockouts provided on the bottom of the cabinet. The batteries will cover the other knockout. Main Power Supply - Mount the Main Power Supply to the cabinet as illustrated in Figure 3-1.
anything at this time!
Transformer - Mount the Transformer to the cabinet as illustrated in Figure 3-1.
Audio Visual Supplies - If an optional AVPS-24F is to be employed, mount it to the cabinet (see Figure 3-1).
Audio Visual Cables - If employing an AVPS-24F, connect the AVPS Trouble Cable. Connect the Auxiliary
Bell Power Harness to the AVPS–24F. Refer to Section Five to connect these cables.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Do not wire
13
Preliminary System Wiring - The Main Power Supply (and AVPS-24F, if employed) should be wired at this time
while their terminals are readily accessible. Refer to Section Five. Module Ribbon Cables - Connect the Module Ribbon Cable to the CPU as illustrated in Figure 3-2.
CPU - Install the CPU module in the top left cabinet position as illustrated in Figure 3-3. Connect the Power Ribbon
and Power Harness between the CPU and the Main Power Supply as illustrated in the respective figure in Section Five.
Module Expander Boards - If expander boards are to be used with a Sensiscan 200 modules, install as illustrated
in Figure 3-4. Modules - Mount each module in its respective chassis position as illustrated in Figure 3-5. Connect the CPU
Row Ribbon to each module. Field-wire each module, using the following figures for reference:
CPU Figure 4-1, 4-2 and 4-3 IZ-8F/IZ-4F Figure 4-4 and 4-5 IZ-4AF Figure 4-6 IC-4F/ICE-4F Figure 4-7 CR-4F/CRE-4F Figure 4-8 CR-4LF Figure 4-9 ICR-4LF Figure 4-10 For the following devices, refer to their respective installation manual: TC-2F, TC-4F, ACM-8RF, LDM
Series, AFMX Series, 911A Communicator, and UDACT-F. Power-on-check - Apply AC power to the system.
trouble sounder, push the ACKNOWLEDGE switch on the CPU. The system should reflect the following status:
On the CPU
✓✓
Green AC POWER indicator should be on.
✓✓ ✓✓
SYSTEM TROUBLE and POWER FAILURE indicators should be on due to the absence of batteries.
✓✓ ✓✓
MODULE FAILURE indicator may light shortly after AC power is applied (applies only to a system that
✓✓
has not been previously configured).
On each module
✓✓
The yellow trouble indicators may come on approximately 10 seconds after AC power is applied (applies
✓✓
only to a system that has not previously been configured).
On each AVPS-24F
✓✓
The yellow trouble indicators will light due to the absence of batteries.
✓✓
On the Main Power Supply
✓✓
The BATTERY FAIL indicator will be on due to the absence of batteries.
✓✓
Failure of the AC POWER indicator, or the presence of indications not mentioned above may suggest an installation problem. Carefully review the installation instructions to isolate the source.
Programming - Refer to Section Seven.
Do not connect the batteries at this time!
To silence the audible
Batteries - Once the system has been programmed and is functional, connect the batteries. Ensure that all
indicators except AC POWER are extinguished. Testing - Fully field test the system by conducting the test procedure in Section Nine.
Dress Panels - Complete installation of the system by installing the cabinet door and the optional dress panel.
14
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Mount the Main Power Supply here with the screws provided.
Mounting Configuration Mount the AVPS-24F Audio Visual Power Supply here
with nuts and lock washers provided.
Mount the Transformer here with nuts and lock washers provided.
Optional Mounting Configuration
When using the Remote Station or Municipal Box Output, the RS-1459 interface board must be used (refer to Figure 4-1).
Mount the RS-1459 here with standoffs, nuts and lock washers provided.
Note: The AVPS-24F cannot be installed when the RS-1459 is being used.
Figure 3-1: Mounting Power Supplies
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
15
CPU Row Ribbon
Plug into uppermost connector on CPU.
L-Series Row Ribbon
Plug into second connec­tor on CPU.
Assigns mod-
ules to positions 6 and 7.
Figure 3-2: Connecting Row
Ribbon Cables to the CPU
(Cables to be connected to modules later)
Figure 3-3: Mounting the CPU
L-Series modules (IC-4RLF, CR-4LF)
Module
Position 6
Module
Position 7
Step 1:
Insert the CPU Module into the left-most cabinet slot, angling the front end of the module into position as shown.
Cabinet
Step 2:
Push the back end of the module down into the cabinet and pull down until the upper board engages the slot on the chassis as shown.
Cabinet
Step 3:
Align the supplied module screws with the thread-holes on the chassis and secure in place.
16
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Figure 3-4: Mounting Module Expanders
Module
Step 1:
Attach four standoffs to the module using the four screws provided.
Figure 3-5: Mounting L-Series Expansion Modules
Expander Module
Step 2:
Insert the pins on the expander board into the connector on the module and press the two boards together, ensur­ing that the pins are properly aligned.
Expander/Module
Step 3:
Secure the module/expander assembly with four nuts and lock washers provided.
This arrangement will fit in the right most position only.
Note:
L-Series modules should not be mounted be­hind other L-Series mod­ules.
L-Series Module Module
For Module Installation:
Attach four standoffs to the module using the four screws provided. Attach L-Series Module to standoffs using mounting holes. Secure the assembly with four nuts and lock washers.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
L-Series Module
Expander/Module
For Expander/Module Combination:
Attach the L-Series Module to the Expander/Mod­ule combination using the four standoffs provided. Secure the entire assembly with the four nuts and lock washers.
17
Figure 3-6: Mounting Modules in the Cabinet
Step 1:
Angle the module into the cabinet so that the upper board edge slips into the cabinet slot as shown.
Cabinet
Step 2:
Push the upper end of the module into the cabinet and secure with the two module screws provided. Straighten LEDs so that they extend from the board at a 90 degree angle.
Cabinet
18
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the Sensiscan 200 is shown below.
Power-limited circuits
Nonpower-limited circuits
Power-limited circuits
Nonpower-limited circuits
AC Power
Figure 3-7: Typical Wiring Diagram for UL Power-limited Requirements
Notes:
1) The power-limited Remote Station Alarm Output and the nonpower-limited Municipal Box Output must not be used simultaneously.
2) Mounting two or more modules in the same chassis position requires that all modules be either power-limited or nonpower-limited;
mixing is not allowed. Following is a list of Power-limited and Nonpower-limited modules:
Power-limited Modules
IZ-8F IZE-AF IZ-4F IZ-4AF IC-4F ICE-4F ICR-4LF CR-4F (with power-limited label) CR-4LF (with power-limited label) CRE-4F (with power-limited label) TC-2F (Notification mode) TC-4F (Notification mode) Fire-Lite Serial Annunciators
Nonpower-limited Modules
CR-4F (no power-limited label) CR-4LF (no power-limited label) CRE-4F (no power-limited label) TC-2F (Releasing mode) TC-4F (Releasing mode)
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
19
Section Four:
Field Wiring the Modules
The following procedures, diagrams, and instructions must be followed precisely to avoid damage to the control panel and its associated equipment. Reliability depends to a great extent upon proper installation and maintenance.
The system's modules feature removable terminal blocks that ease installation and servicing of the control panel.
20
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Figure 4-1: CPU Terminal Connections
Typical Supervised Power Limited Notification Appliance Circuits
Use only compatible, UL listed notification appliances (see the Device Compatibility Document). Max current per circuit is 3.0 amps, subject to the limitations of the power supply.
Style Y
4.7K, 1/2 watt ELR, Part # 71252.
UL listed
24 VDC
Polarized Bell
UL listed
24 VDC
Polarized Horn
Style Z
Remote Station Outputs
Non-Supervised, Power Limited
(Standby polarity shown)
Wiring can leave the building
24 VDC (nominal). 10 mA max rated current. Internal resistance = 1360 ohms (nominal).
Intended for connection to the polarity reversal circuit of a remote station receiving unit (Fire-Lite Model RS-82) having compatible ratings.
Remote Station Trouble Output
General Trouble
Contacts
(power-limited source
only) 2A @ 30VDC 1A @ 120VAC
(resistive)
Remote Station
Alarm Output
General
Alarm
Contacts
(power-limited source
5A @ 30VDC
5A @ 120VAC
(resistive)
Local Energy Municipal Box
Trip current = 0.25 Amps (min) Coil voltage = 3.65 VDC (min) Coil resistance = 14.6 ohms (max)
Municipal box wiring must be run in conduit.
Municipal Box
Output
Supervised (for
open circuit)
Wiring can leave
the building
only)
Max Current = (short circuit) = 0.6 Amps Max Voltage = (open circuit) = 27.6 VDC
Notes:
Max Wire Resistance = 5 Ohms
1) The Remote Station Alarm Output and the Municipal Box Output must not be used simultaneously.
2) Notification Appliance Circuits, Remote Station Trouble output, and the Remote Station Alarm output are power limited and
may be connected to limited-energy cable.
3) Wire Notification Appliances according to the manufacturer's instructions packaged with each device.
4) Terminal blocks will accept #12 to #22 AWG wire.
5) Size notification circuit wire for a maximum drop of 2 volts DC.
6) The RS-1459 module is required when the Remote Station or Municipal Box Output is connected to a circuit that exits the
protected premises. Exception - The RS-1459 module is not required for the Municipal Box Circuit if ALL of the following conditions exist: (1) wiring is in conduit, (2) wire length is less than 1000 meters, (3) wiring does not cross any power lines and (4) must not be in the vicinity of any high voltage..
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
21
Loading...
+ 48 hidden pages