The Sensiscan 200 is an expandable multi-zone Fire Alarm Control Panel based on a modular design for
maximum flexibility. The heart of the system is the Central Processor Unit (CPU) module which monitors and
directs the actions of all other modules in the system. Up to two other modules may be installed in various
configurations. Internal communications are accomplished over a high-speed serial bus.
The CPU-2000 is provided with the BE-200 Basic Equipment package. This module provides two Style Z and/or
Style Y Notification Appliance Circuits, Form-C alarm and trouble contacts, Remote Station alarm and trouble
outputs, and a Municipal Master Box output.
An initiating zone module (IZ-4F or IZ-8F) and a CAB-200 cabinet must be added to make the basic system
functional.
The basic system can be expanded using one or more of the following optional modules or boards:
• IZ-8F Initiating Zone Module
• IZ-4F Initiating Zone Module
• IZ-4AF Initiating Zone Module
• IZE-AF Initiating Zone Expander
• IC-4F Indicating Circuit Module
• ICR-4LF Combination Output Module
• ICE-4F Indicating Circuit Expander
• AVPS-24F Audio-Visual Power Supply
• CR-4F Control Relay Module
• CR-4LF Control Relay Module
• CRE-4F Control Relay Expander
• TC-2F Time Control Module
• TC-4F Time Control Module
• UDACT-F Universal Digital Alarm
Communicator Transmitter
System expansion must comply with:
• The physical limitations of the cabinet configuration.
• The electrical limitations of the system power supply (see Appendix A).
• The capacity of the standby batteries (see Appendix A).
Key Features
• Distributed microprocessor electronics.
• Field programmable in nonvolatile memory.
• Manual Disable control for all Notification Appliance Circuits and control relays.
• Alarm verification, with device type discrimination.
• Walk Test, with zone change indication.
• Serial annunciators, including LCD and custom annunciators.
• Multiple hazard release control modules.
• Programmable software timers including positive alarm sequence.
4
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 5
Before proceeding, the installer should be familiar with the following documents and
standards (as appropriate):
NFPA Standards:
NFPA 13 Sprinkler System.
NFPA 72-1993 Installation, Maintenance, and Use of Central Station Signaling Systems.
NFPA 72-1993 National Fire Alarm Code for Local, Auxiliary, Remote Station and Proprietary Fire
Alarm Systems, Automatic Fire Detectors, Notification Appliances for Fire Alarm Systems, and
Testing Procedures for Signaling Systems.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
Underwriters Laboratories of Canada (ULC) listed
Standard CAN/ULC-S527-M87
Other:
EIA-485 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
5
Page 6
Minimum System Configurations
At a minimum, the following components are required for compliance with NFPA standards 12, 12A,
12B, and 72-1993. Supervisory listing is for local systems only.
1. BE-200 Basic Equipment Package which includes:
Central Processor Module (CPU-2000), Main Power Supply (MPS-24BPCC), transformer
(4000TA), interconnecting cables, mounting hardware and an instruction manual.
2. An IZ-4F, IZ-4AF or IZ-8F Initiating Zone Module for up to eight Style B Initiating Device Circuits.
3. Standby Batteries - refer to Standby Power Requirements, Appendix A.
4. Cabinet (CAB-200).
In addition, the following equipment is required for the specific NFPA standards listed below:
An NFPA 72-1993 Central Station Protected Premises Control Unit requires:
5. Fire-Lite UDACT-F, Noti•Fire 911A Digital Communicator or the Fire•Lite MS-5012 Control
Communicator.
An NFPA-12 Minimum Carbon Dioxide Extinguishing Control Unit, NFPA-12A Halon 1301 Fire Extinguishing
Control Unit, NFPA-12B Halon 1211 Fire Extinguishing Control Unit or NFPA - 13 requires:
5. TC-2F or TC-4F Time Control Module.
For wiring diagrams and more information on these applications, refer to Section 6.
6
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 7
Section Two:
Inventory
The Sensiscan 200 is offered under a Basic Equipment (BE-200) package which provides the CPU module, Main
Power Supply, interconnecting cables and an instruction manual.
Components include modules and devices not provided in the Basic Equipment package. These components
also include several items necessary to complete a basic system, such as an initiating module and cabinet. See
Section One for Minimum System Requirements.
This installation manual covers system basics. For information on special applications, refer to the following
installation manuals:
This module is the heart of the system. It controls and monitors the system
modules and provides a full accounting of system status. In addition, the CPU
contains two Notification Appliance Circuits, a Remote Signaling Municipal Tie
Circuit, and Form-C alarm and trouble contacts. Field programming of the
system is accomplished from this module via the use of the Programming Key.
Includes End-of-Line and Dummy Load resistors.
KEY #___ PWD#___
End-of-Line Resistor
4.7K, 1/2 watt (71252)
MPS-24BPCC
The MPS-24BPCC supplies the regulated power needed to run
the system modules. It also supplies up to 2.0 amps of regulated
notification appliance power, permitting the use of a variety of
standard UL listed 24 VDC notification appliances (see the
Device Compatibility Document for a complete listing). Up to
200 mA of resettable power is available for four wire smoke
detectors. The MPS-24BPCC contains an integral battery
charger capable of charging batteries in the 6.5 to 17 amp-hour
range (Note: 15-17AH batteries require a separate battery
cabinet). Includes two sets of battery cables, one for large
battery terminals and one for small terminals. Note: For
reorders, specify an "MPS-24BRB" (for
Dummy Load Resistor
4.7K, 1/2 watt (71245)
4000TA Transformer
Programming Key
(PKB)
Replacement Board
).
Module Ribbon Cable
(75171)
Power Ribbon
(75170)
8
Main Bell Power Harness
(75169)
Power Harness
(75168)
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Positive Battery Cable (red)
(71071)
Negative Battery Cable (black)
(71072)
Series Interconnect
(71070)
Page 9
Modules
IZ-8F Initiating
Zone Module
This module provides eight
Style B Initiating Device Circuits. Circuits are power
limited and can be programmed by the user for
standard fire, Waterflow
Alarm, Supervisory service,
Non Alarm or Command Inputs. Also provided are
eight End-of-Line and eight
Dummy Load Resistors.
IZE-AF Initiating
Zone Expander
Converts the eight Initiating Device Circuits on the Initiating
Zone Module (IZ-8F) to Style D
operation. The expander plugs
into the bottom of the IZ-8F.
IZ-4F Initiating
Zone Module
This module provides four
Style B Initiating Device Circuits. Circuits are power
limited and are user programmable for standard
fire, Waterflow Alarm,
Supervisory service, Non
Alarm or Command Inputs.
Also provided are End-ofLine Resistors and Dummy
Load Resistors.
Note: This module will not
support the IZE-AF Initiating Zone Expander module.
IZ-4AF Initiating
Zone Module
This module provides four
Style D Initiating Device
Circuits. Circuits are power
limited and user programmable for standard fire,
Waterflow Alarm, Supervisory service, Non-Alarm or
Command inputs.
End-of-Line Resistors
Note: This module will not
support an IZE-AF Initiating Zone Expander
module.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Dummy Load Resistors
9
Page 10
Modules
TC-2F/TC-4F Time
Control Module
The TC-2F module is intended for single-hazard release and can be configured for standard release
service triple coded release, or IRI release. It includes abort and manual
release circuits and an adjustable timer and display.
For more information refer
to the TC-2F Manual.
The TC-4F can provide either four releasing circuits
or four two-stage evacuation circuits. Each circuit includes a cross-zone option
and delay timer option. For
more information refer to
the TC–4F Manual.
CR-4LF Control
Relay Module
Provides four standard dry
Form-C alarm contacts rated
for 5 amps @ 120 VAC or 28
VDC (resistive). Each relay is
field programmable to respond
to a single Initiating Device Circuit, a group of circuits, or all
Initiating Device Circuits.
ICR-4LF Combination
Output Module
Provides two standard dry
Form-C alarm contacts rated
for 5 amps @ 120 VAC or 28
VDC (resistive) and two Style
Y Notification Appliance Circuits. All relays and circuits
are field programmable. Also
provided are: End-Of-Line
Resistors, Dummy Load Resistors, and Auxiliary Bell
Power Harness.
One Auxiliary Bell Power
Harness
Two End-of-Line
Resistors
4.7K, 1/2 watt (71252)
Two Dummy Load
Resistors
4.7K, 1/2 watt (71245)
RS-1459 Module
The RS-1459 module is used in conjunction with the
Remote Station or Municipal Box Output. When the
RS-1459 is employed, an AVPS-24F audio visual
power supply cannot be installed. The RS-1459 is NOT
required for the Municipal Box Circuit if wiring remains
in conduit, wire length is less than 1000 meters, or
wiring does not cross any power lines. All conditions
must be met according to Figure 4-1. Refer to Figures3-1 and 4-1. For more information on the RS-1459
module, refer to the RS-1459 Product Installation
Drawing.
10
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 11
Modules
IC-4F Indicating
Circuit Module
Provides four Notification
Appliance Circuits for
Style Y or Style Z operation. Maximum signaling
current is 3.0 amps (3
amps max per circuit). Circuits are field programmable to respond to a single
initiating zone, a group of
zones, or all initiating
zones. ELRs, Dummy
Load Resistors, and an
Auxiliary Bell Power Harness (shown below) are
provided with each module. For California Code
programming, consult the
factory.
CR-4F Control Relay
Module
Provides four standard dry
Form-C alarm contacts rated
for 5 amps @ 120 VAC or 30
VDC (resistive). Each relay is
field programmable to respond to a single Initiating
Device Circuit, a group of circuits, or all Initiating Device
Circuits.
ICE-4F Indicating
Circuit Expander
Expands the IC-4F to a total of
eight Notification Appliance Circuits (either Style Y or Style Z).
Circuit ratings are identical to
those of the IC-4F. An Auxiliary
Bell Power Harness is provided
with each expander. The expander plugs into the back of the
IC-4F.
Auxiliary Bell Power Harness
CRE-4F Control Relay
Expander
Expands the capacity of the
Control Relay Module (CR-4F)
to eight Form-C alarm relays.
Relays are identical to those on
the CR-4F. The expander plugs
into the back of the CR–4F, IC4F, TC-2F or TC-4F.
UDACT-F Universal
Digital Alarm
Communicator
Transmitter
Transmits system status to UL Listed Central
Station Receivers via
the public switched
telephone network.
It is capable of reporting
up to 56 software
zones.
Communicators
911A Digital Communicator Transmitter
Is a three-zone module designed to provide for offpremises monitoring of this fire alarm control panel.
For stand-alone installations, use the 911AC kit that
includes a
transformer
and an
enclosure(s)
for both the
911A and the
transformer.
Refer to the
Notifire 911A
manual,
Document #74-06200-005-A.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
11
Page 12
Optional Components
AVPS-24F Audio-Visual Power Supply
Supplies power to Notification Appliance Circuits only.
Special Purpose power (unfiltered, unregulated) rated for
3.0 amps maximum. Provided with a Trouble Cable
(below) for connection to the Main Power Supply.
Trouble Cable
(P/N 71033)
CAB-200 Cabinet
The cabinet is 17" high by 14-1/2"
wide for recessed mounting between
wall studs. Includes a backbox (illustrated) and door.
DP-200 Dress Panel
Mounts to the cabinet to cover system
components.
12
TR-200 Trim Ring
For semi-flush mounting of the cabinet.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 13
Section Three:
Installation
The control panel's modules communicate with the
CPU through a common ribbon cable connection.
Installation Outline
The following procedures, diagrams, and instructions must be followed precisely to avoid damage to the
control panel and its associated equipment. Reliability depends to a great extent upon proper installation and
maintenance.
Cabinet - Mount the cabinet and draw all field wiring through the knockouts provided. NOTE: Use only one
❑❑
❑
❑❑
of the two knockouts provided on the bottom of the cabinet. The batteries will cover the other knockout.
Main Power Supply - Mount the Main Power Supply to the cabinet as illustrated in Figure 3-1.
❑❑
❑
❑❑
anything at this time!
Transformer - Mount the Transformer to the cabinet as illustrated in Figure 3-1.
❑❑
❑
❑❑
Audio Visual Supplies - If an optional AVPS-24F is to be employed, mount it to the cabinet (see Figure 3-1).
❑❑
❑
❑❑
Audio Visual Cables - If employing an AVPS-24F, connect the AVPS Trouble Cable. Connect the Auxiliary
❑❑
❑
❑❑
Bell Power Harness to the AVPS–24F. Refer to Section Five to connect these cables.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Do not wire
13
Page 14
Preliminary System Wiring - The Main Power Supply (and AVPS-24F, if employed) should be wired at this time
❑❑
❑
❑❑
while their terminals are readily accessible. Refer to Section Five.
Module Ribbon Cables - Connect the Module Ribbon Cable to the CPU as illustrated in Figure 3-2.
❑❑
❑
❑❑
CPU - Install the CPU module in the top left cabinet position as illustrated in Figure 3-3. Connect the Power Ribbon
❑❑
❑
❑❑
and Power Harness between the CPU and the Main Power Supply as illustrated in the respective figure in Section
Five.
Module Expander Boards - If expander boards are to be used with a Sensiscan 200 modules, install as illustrated
❑❑
❑
❑❑
in Figure 3-4.
Modules - Mount each module in its respective chassis position as illustrated in Figure 3-5. Connect the CPU
❑❑
❑
❑❑
Row Ribbon to each module. Field-wire each module, using the following figures for reference:
CPUFigure 4-1, 4-2 and 4-3
IZ-8F/IZ-4FFigure 4-4 and 4-5
IZ-4AFFigure 4-6
IC-4F/ICE-4FFigure 4-7
CR-4F/CRE-4FFigure 4-8
CR-4LFFigure 4-9
ICR-4LFFigure 4-10
For the following devices, refer to their respective installation manual: TC-2F, TC-4F, ACM-8RF, LDM
Series, AFMX Series, 911A Communicator, and UDACT-F.
Power-on-check - Apply AC power to the system.
❑❑
❑
❑❑
trouble sounder, push the ACKNOWLEDGE switch on the CPU. The system should reflect the following status:
On the CPU
✓✓
✓ Green AC POWER indicator should be on.
✓✓
✓✓
✓ SYSTEM TROUBLE and POWER FAILURE indicators should be on due to the absence of batteries.
✓✓
✓✓
✓ MODULE FAILURE indicator may light shortly after AC power is applied (applies only to a system that
✓✓
has not been previously configured).
On each module
✓✓
✓ The yellow trouble indicators may come on approximately 10 seconds after AC power is applied (applies
✓✓
only to a system that has not previously been configured).
On each AVPS-24F
✓✓
✓ The yellow trouble indicators will light due to the absence of batteries.
✓✓
On the Main Power Supply
✓✓
✓ The BATTERY FAIL indicator will be on due to the absence of batteries.
✓✓
Failure of the AC POWER indicator, or the presence of indications not mentioned above may suggest an
installation problem. Carefully review the installation instructions to isolate the source.
Programming - Refer to Section Seven.
❑❑
❑
❑❑
Do not connect the batteries at this time!
To silence the audible
Batteries - Once the system has been programmed and is functional, connect the batteries. Ensure that all
❑❑
❑
❑❑
indicators except AC POWER are extinguished.
Testing - Fully field test the system by conducting the test procedure in Section Nine.
❑❑
❑
❑❑
Dress Panels - Complete installation of the system by installing the cabinet door and the optional dress panel.
❑❑
❑
❑❑
14
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 15
Mount the Main Power Supply
here with the screws provided.
Mounting Configuration
Mount the AVPS-24F Audio
Visual Power Supply here
with nuts and lock washers
provided.
Mount the Transformer
here with nuts and lock
washers provided.
Optional Mounting Configuration
When using the Remote Station or
Municipal Box Output, the RS-1459
interface board must be used (refer to
Figure 4-1).
Mount the RS-1459 here with standoffs,
nuts and lock washers provided.
Note: The AVPS-24F cannot be
installed when the RS-1459 is being
used.
Figure 3-1: Mounting Power Supplies
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
15
Page 16
CPU Row Ribbon
Plug into uppermost
connector on CPU.
L-Series Row Ribbon
Plug into second connector on CPU.
Assigns mod-
ules to positions 6 and 7.
Figure 3-2: Connecting Row
Ribbon Cables to the CPU
(Cables to be connected to modules later)
Figure 3-3: Mounting the CPU
L-Series modules
(IC-4RLF, CR-4LF)
Module
Position 6
Module
Position 7
Step 1:
Insert the CPU Module into the left-most cabinet slot,
angling the front end of the module into position as
shown.
Cabinet
Step 2:
Push the back end of the module down into the
cabinet and pull down until the upper board engages
the slot on the chassis as shown.
Cabinet
Step 3:
Align the supplied module screws with the thread-holes on the chassis and secure in place.
16
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 17
Figure 3-4: Mounting Module Expanders
Module
Step 1:
Attach four standoffs to the
module using the four
screws provided.
Figure 3-5: Mounting L-Series Expansion Modules
Expander
Module
Step 2:
Insert the pins on the expander board
into the connector on the module and
press the two boards together, ensuring that the pins are properly aligned.
Expander/Module
Step 3:
Secure the module/expander
assembly with four nuts and
lock washers provided.
This arrangement will fit in
the right most position only.
Note:
L-Series modules
should not be mounted behind other L-Series modules.
L-Series Module Module
For Module Installation:
Attach four standoffs to the module using
the four screws provided. Attach L-Series
Module to standoffs using mounting holes.
Secure the assembly with four nuts and
lock washers.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
L-Series Module
Expander/Module
For Expander/Module Combination:
Attach the L-Series Module to the Expander/Module combination using the four standoffs provided.
Secure the entire assembly with the four nuts and
lock washers.
17
Page 18
Figure 3-6: Mounting Modules in the Cabinet
Step 1:
Angle the module into the cabinet so that the upper
board edge slips into the cabinet slot as shown.
Cabinet
Step 2:
Push the upper end of the module into the cabinet and
secure with the two module screws provided.
Straighten LEDs so that they extend from the board at
a 90 degree angle.
Cabinet
18
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 19
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited
and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
A typical wiring diagram for the Sensiscan 200 is shown below.
Power-limited
circuits
Nonpower-limited
circuits
Power-limited
circuits
Nonpower-limited
circuits
AC Power
Figure 3-7: Typical Wiring Diagram for UL Power-limited Requirements
Notes:
1)The power-limited Remote Station Alarm Output and the nonpower-limited Municipal Box Output must not be used simultaneously.
2) Mounting two or more modules in the same chassis position requires that all modules be either power-limited or nonpower-limited;
mixing is not allowed. Following is a list of Power-limited and Nonpower-limited modules:
CR-4F (no power-limited label)
CR-4LF (no power-limited label)
CRE-4F (no power-limited label)
TC-2F (Releasing mode)
TC-4F (Releasing mode)
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
19
Page 20
Section Four:
Field Wiring the Modules
The following procedures, diagrams, and instructions must be followed precisely to avoid
damage to the control panel and its associated equipment. Reliability depends to a great extent
upon proper installation and maintenance.
The system's modules feature removable
terminal blocks that ease installation and
servicing of the control panel.
20
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 21
Figure 4-1: CPU Terminal Connections
Typical Supervised Power Limited Notification
Appliance Circuits
Use only compatible, UL listed notification appliances (see the
Device Compatibility Document). Max current per circuit is 3.0
amps, subject to the limitations of the power supply.
Style Y
4.7K, 1/2 watt ELR,
Part # 71252.
UL listed
24 VDC
Polarized Bell
UL listed
24 VDC
Polarized Horn
Style Z
Remote Station Outputs
Non-Supervised, Power Limited
(Standby polarity shown)
Wiring can leave the building
24 VDC (nominal). 10 mA max rated current.
Internal resistance = 1360 ohms (nominal).
Intended for connection to the polarity reversal
circuit of a remote station receiving unit (Fire-Lite
Model RS-82) having compatible ratings.
Remote Station
Trouble Output
General
Trouble
Contacts
(power-limited source
only)
2A @ 30VDC
1A @ 120VAC
(resistive)
Remote Station
Alarm Output
General
Alarm
Contacts
(power-limited source
5A @ 30VDC
5A @ 120VAC
(resistive)
Local Energy
Municipal Box
Trip current = 0.25 Amps (min)
Coil voltage = 3.65 VDC (min)
Coil resistance = 14.6 ohms (max)
Municipal box
wiring must be
run in conduit.
Municipal Box
Output
Supervised (for
open circuit)
Wiring can leave
the building
only)
Max Current = (short circuit) = 0.6 Amps
Max Voltage = (open circuit) = 27.6 VDC
Notes:
Max Wire Resistance = 5 Ohms
1)The Remote Station Alarm Output and the Municipal Box Output must not be used simultaneously.
2)Notification Appliance Circuits, Remote Station Trouble output, and the Remote Station Alarm output are power limited and
may be connected to limited-energy cable.
3)Wire Notification Appliances according to the manufacturer's instructions packaged with each device.
4)Terminal blocks will accept #12 to #22 AWG wire.
5)Size notification circuit wire for a maximum drop of 2 volts DC.
6)The RS-1459 module is required when the Remote Station or Municipal Box Output is connected to a circuit that exits the
protected premises. Exception - The RS-1459 module is not required for the Municipal Box Circuit if ALL of the following
conditions exist: (1) wiring is in conduit, (2) wire length is less than 1000 meters, (3) wiring does not cross any power lines and
(4) must not be in the vicinity of any high voltage..
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
21
Page 22
4.7K, 1/2-watt Resistor,
Part # 71245.
4.7K, 1/2W Resistor
Part # 71245
An unused notification circuit can be terminated with one dummy-load resistor (illustrated above on Terminals 1-4) or with two
If the Municipal Box Output is not to be
used, it must be terminated with a
dummy-load resistor.
jumpers (illustrated above on Terminals 5-8).
Figure 4-2: Dummy-loading of Unused Circuits
EIA-485 Interface
EIA-485 (+)
EIA-485 (-)
22
Figure 4-3: The EIA-485 Interface
The control panel communicates with the serial annunciator modules of the AFMX and LDM Series
through the EIA–485 interface on the CPU. The EIA terminal block is installed on the lower CPU
board. Maximum distance is 6000 feet. Maximum resistance is 100 ohms.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 23
Figure 4-4: NFPA Style B Field Wiring of
Initiating Zone Modules (IZ-4F7, IZ-8F)
ABCD E*F*G*H*
b+ b- b+ b- b+ b- b+ b- b+ b- b+ b- b+ b- b+ b-
AE
BF
CG
4.7K, 1/2 watt ELR, Part # 71252.
Manual Pull Station
UL-listed 2-wire
Photo smoke detector
2
5
DH
1)Initiating Device Circuits are supervised, power limited and may be connected to
limited-energy cable, except for initiating devices that require 24 VDC power.
2)Use only the compatible, UL-listed 2-wire smoke detectors that are listed in the Device
Compatibility Document.
3)For connection of 4-wire smoke detectors, refer to Section Six.
4)Wire initiating devices according to the manufacturer's instructions packaged with
each device.
5)For Canada, model F-ELR End-of-Line Resistor Assembly required.
6)Maximum line resistance is 100 ohms.
7)IZ-4F contains only circuits A, B, C and D.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
UL-listed 2-wire
Ion smoke detector
2
Typical NFPA Style B
Initiating Device Circuit
Dummy load all unused circuits
with 4.7K ELR (71245).
23
Page 24
Figure 4-5: Style D Field Wiring of IZ-8F Initiating Zone Module
with IZE-AF Expander
ABCD E FGH
a+ a- a+ a- a+ a- a+ a- a+ a- a+ a- a+ a- a+ a-
Manual Pull Station
UL-listed 2-wire
Photo smoke detector
UL-listed 2-wire
Ion smoke detector
2
b+ b- b+ b- b+ b- b+ b- b+ b- b+ b- b+ b- b+ b-
2
AE
BF
CG
Typical NFPA Style D
Initiating Device Circuit
Jumper all unused circuits
24
DH
1)Initiating Device Circuits are supervised, power limited and may be con-
nected to limited-energy cable, except for initiating devices that require 24 VDC
power.
2)Use only the compatible, UL listed 2-wire smoke detectors are listed in
the Device Compatibility Document.
3)For connection of 4-wire smoke detectors, refer to Section Six.
4)Wire initiating devices according to the manufacturer's instructions packaged
with each device.
5)The IZ-4F does not support the IZE-AF Expander and therefore cannot be wired for
Style D circuits.
6)Maximum line resistance is 100 ohms.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 25
Manual Pull Station
Figure 4-6: Style D Field Wiring of
IZ-4AF Initiating Zone Module
ABCD A BCD
CIRCUIT OUTCIRCUIT RETURN
b+ b- b+ b- b+ b- b+ b-
A
a+ a- a+ a- a+ a- a+ a-
UL-listed 2-wire
Photo smoke detector
2
B
C
UL-listed 2-wire
Ion smoke detector
2
Typical NFPA
D
Style D
Initiating Device
AA
Circuit
Jumper all unused circuits
1)Initiating Device Circuits are supervised, power limited and may be connected to limited-energy cable, except
for initiating devices that require 24 VDC power.
2)Use only the compatible, UL listed 2-wire smoke detectors are listed in the Device Compatibility Document.
3)For connection of 4-wire smoke detectors, refer to Section Six.
4)Wire initiating devices according to the manufacturer's instructions packaged with each device.
5)Maximum line resistance is 100 ohms.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
25
Page 26
Figure 4-7: NFPA Style Y / Z Field Wiring of Notification Circuit
Module (IC-4F) and Expander (ICE-4F)
E F G H
b+ a+ a- b- b+ a+ a- b- b+ a+ a- b- b+ a+ a- b-
Notification Appliance
A B C D
b+ a+ a- b- b+ a+ a- b- b+ a+ a- b- b+ a+ a- b-
AE
Optional ICE-4F Indicating Circuit Expander. Positions E,
F, G, and H are active only with this board installed.
Typical
NFPA Style Y
Circuit
4.7K, 1/2 watt ELR,
Part # 71252.
5
Typical
NFPA Style Z
Notification Appliance
Circuit
UL- listed
24 VDC
Polarized Bells
UL-listed
24 VDC
Polarized Horns
B F
Jumper
unused
circuits
CG
DH
Cut this for California Code
1) Notification Appliance Circuits are supervised, power limited and may be connected to energy-limited cable.
2) Wire Notification Appliances according to the manufacturer's instructions packaged with each device.
3) Max current per circuit is 3.0 amps, subject to the limitations of the source of power (MPS–24BPCC or AVPS-24F).
4) For Canada, model F-ELR End-of-Line Resistor Assembly required.
5) Size wiring for a maximum voltage drop of 2 volts at the end of the Notification Appliance Circuit.
Jumper
unused
circuits
6) The IC-4F is California Code programmable (microprocessor Rev. B or higher). To program for California Code, cut diode D35.
26
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 27
Figure 4-8: Field Wiring of the Control Relay Module (CR-4F)
and Control Relay Expander (CRE-4F)
EFGH
no nc c no nc c no nc c no nc c
ABCD
no nc c no nc c no nc c no nc c
* Optional CRE-4F Control Relay Expander. Positions E, F, G and H
are active only with this board installed.
1)These Form-C gold-plated, silver alloy relay contacts are for
2)UL contact ratings are 5 amps @ 125 volts AC (resistive) or 30
3)Activation of a CR-4F or CRE-4F relay occurs automatically
AE
medium duty switching and for Pilot Duty.
volts DC (resistive) and 2 amps @ 125 volts AC (inductive).
when an alarm is detected on a selected (programmed) Initiating Device Circuit.
Note: Refer to the Power-limited label located on the FACP door.
Make a notation on the label for each circuit being employed as a
Nonpower-limited circuit. (Refer to the example on the label).
BF
CG
D H
Non-power-limited and power-limited wiring must have a minimum
distance of 0.25" wire to wire and must enter and exit from different
knockouts. If this module is used to drive nonpower-limited and
power-limited circuits, please follow the instructions:
Relay 1
Relay 2
Relay 3
Relay 4
NO
NC
NO
NC
NO
NC
NO
NC
Power-limited
C
C
C
C
Circuit
Power-limited
Circuit
no connection
Nonpower-limited
Circuit
Nonpower-limited
Circuit
1) Skip a set of dry contacts to maintain the 0.25" required space
OR
2) If this module is needed to drive power-limited and nonpower-
Typical Form-C Control
Relay in Standby Position
between power-limited and nonpower-limited circuits. The wiring
of this module must follow UL Power-limited Wiring Requirements.
limited relays that are next to each other, refer to the figure to the
left showing a typical connection.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
27
Page 28
Figure 4-9: Field Wiring of the L-Series Control Relay Module (CR-4LF)
ABCD
no nc c no nc c no nc c no nc c
1)These Form-C gold-plated, silver alloy relay contacts are for
medium duty switching and for Pilot Duty.
2)UL contact ratings are 5 amps @ 125 volts AC (resistive) or 30
volts DC (resistive) and 2 amps @ 125 volts AC (inductive).
3)Activation of a CR-4LF relay occurs automatically when an
alarm is detected on a selected (programmed) Initiating
Device Circuit.
28
Typical Form-C Control
Relay in Standby Position
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 29
Figure 4-10: Field Wiring of the L-Series Combination Output Module
(ICR-4LF)
Typical
NFPA Style Y
Notification
Appliance
Circuit
4.7K, 1/2 watt ELR,
Part # 71252.
+ - + - no nc c no nc c
#1 #2
}
Notification
Appliance
Circuits
5
UL-listed
Polarized Bells
Polarized Horns
}
Form C Relays
Power-limited
24 VDC
UL-listed
24 VDC
}
Typical Form-C Control
Relay in Standby Position
1)Notification Appliance Circuits are supervised, power limited
and may be connected to energy-limited cable.
}
2)Use only the compatible, UL-listed Notification Appliances
listed in the Device Compatibility Document.
3)Wire Notification Appliances according to the manufacturer's
instructions packaged with each device.
4)Max current per circuit is 3.0 amps, subject to the limitations
of the source of power (MPS = 2.0 amps; AVPS-24F=3.0
amps total).
5)For Canada, model F-ELR End-of-Line Resistor Assembly
required.
6)Size wiring for a maximum voltage drop of 2 volts at the end
of the Notification Appliance Circuit.
7)Form-C gold-plated, silver alloy relay contacts are for medium duty switching and for Pilot Duty.
as power-limited circuits.
8)UL contact ratings are 5 amps @ 125 volts AC (resistive) or
30 volts DC (resistive) and 2 amps @ 125 volts AC (inductive).
9)Activation of a CR-4LF relay occurs automatically when an
alarm is detected on a selected (programmed) Initiating
Device Circuit.
They must be used
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
29
Page 30
Section Five:
Power Supplies
The Main Power Supply
The MPS-24BPCC Main Power Supply is capable of powering the control panel continuously during standby and
alarm conditions. A total of 750 mA amps @ 24 VDC regulated is available from the power supply for operating
the system during Standby conditions.
Figures 5-1 and 5-2 illustrate connections for primary and secondary power to the main power supply, as well as
terminal and harness connections for the control panel.
AC Power Requirements
Primary power required for the MPS-24BPCC Main Power Supply is 120 VAC, 50/60 Hz, 1.8 amps.
Connecting the Primary Power Source
With the breaker at the main power distribution panel turned off, remove the plastic insulating cover from Terminal
Block TB1 on the main power supply and connect the system primary power source. Connect the service ground
to TB1 terminal 2. Ground the power supply assembly to the cabinet with a Chassis Ground cable (71073) to TB1
Terminal 2. Connect the primary Neutral line to TB1 Terminal 3 and the primary Hot line to TB1 Terminal 4. Do
not route 120 VAC wiring in the same conduit as other circuits. After completion of these connections reinstall
the plastic insulating cover over the terminal strip. Leave the main power breaker off until installation of the entire
system is complete.
Connecting the Secondary Power Source (24 VDC)
Secondary power (batteries) is required to support the system during loss of primary power. These batteries
reside in the control panel cabinet. Connect the Battery Positive Cable to TB3 Terminal 1 (+) and the Battery
Negative Cable to TB3 Terminal 2 (-).
will be made just after initial primary system power-up. Batteries may be installed in external cabinet BB-17,
cabinet limit-17AH.
Do not connect the Battery Interconnect Cable at this time. This connection
Earth Fault Detection
The MPS-24BPCC automatically employs detection of earth faults in the system.
Four-Wire Smoke Detector Power (24 VDC)
Up to 200mA of current for 24 VDC four-wire smoke detectors can be drawn from TB2 Terminals 1 (+) and
2 (-). Power is removed from these terminals during system reset (unless Jumper JP1 is removed). This regulated
four-wire smoke detector power is power-limited but must be supervised via an end-of-line Power Supervision
Relay. The power supervision relay is energized by the four-wire power circuit and its contact must be connected
in series with an IZ-4F or IZ–8F circuit as shown in Figures 6-5 and 6-6.
Annunciator Power (24 VDC)
Up to 200 mA of current suitable for powering an AFMX or LDM Annunciators can be drawn from TB2 Terminals
1 (+) and 2 (-). This power is filtered, regulated, power-limited, and is supervised by the annunciator (
Communications
Notification Appliance Power (24 VDC)
Up to 2.0 amps of regulated current for powering notification appliances can be drawn from TB2 Terminals 3(+)
and 4(–). Power is not removed from these terminals during system reset.
annunciators (or any device requiring filtered 24 VDC power) to this circuit or damage may result!
System Harness Connections
Internal power for the system is provided via the Power Harness (76100). Connect this harness from P2 on the
main power supply to the CPU. Signaling between the CPU and the main power supply is accomplished through
connection of the Power Ribbon (71087) to P3 on the MPS-24BPCC.
error).
Do not connect AFMX or LDM
Loss of
30
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 31
Figure 5-1: Field Wiring the Main Power Supply
Removal disables
battery charger
* Cut JP1 to make 4-Wire
Smoke Detector Power on
TB2 Terminals 1 and 2 a
non-resettable circuit.
Trouble Cable
To Optional
Do not
cut JP3
AVPS–24
(see Figure 5-3) and
Trouble Contacts on
UDACT-F if UDACT-F is
configured for "Receive
Only" (see UDACT-F
Manual)
Earth
Fault
-
Earth
Fault
+
2 1
Battery
Failure
AC
Power
Secondary Power
27.6 VDC, 6.5 to 17 AH. Supervised and
power-limited. Fast charge = 0.75 amps
(typical), trickle charge = 20 mA (typical).
amps (in alarm) max. Power is supervised by output module
(such as an IC-4F).
This output is not suitable for powering Annunciators!
Cut R55 to disable
Earth Fault Detection
Hot Neutral
Primary Power
Earth Ground
Connect to chassis
with a Grounding
Cable Assembly
(Cable # 71073).
Earth/Service
Ground
- +
Common Four-Wire Smoke Detector/Annunciator Power
+24 VDC (20.4-26.4, 200 mV ripple), 200 mA max. Filtered, regulated and
resettable. Power-limited but when used for 4-wire smoke detectors, the power
run must be supervised by a UL Listed Power Supervision Relay.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
31
Page 32
Figure 5-2: Main Power Supply Harness Connections
Main Bell Power
Harness (75169)
Connect Blue Wire to MPS TB2
Terminal 3 (+). Connect Black
Wire to MPS TB2 Terminal 4 (-).
J5
J6
If powering a notification appliance circuit or time
control module from the MPS, connect the Bell Power
Harness from J6 on the CPU to J5 on the particular
output module.
Bottom
View of
IC-4F
IC-4F
ICE-4F
Power Ribbon
(75170)
CPU
Transformer Harness
connection
Power Harness
(75168)
MPS-24BPCC
32
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 33
Figure 5-3: Field Wiring the AVPS-24F
Audio Visual P ower Supply
AC Power Requirements
AC power required for the AVPS-24F is
120 VAC, 50/60 Hz, 1.0 amps.
+24 VDC Special Purpose Power
Unfiltered, unregulated, power-limited (3.0
amps max). Use power harness to provide
power to notification circuit or time control
modules (connect to J5 on IC-4F or ICE-4F).
(Bottom
view)
IC-4F
ICE-4F
Auxiliary Bell Power Harness
Note orientation of connectors
Connect the AVPS Trouble
Cable to P4 on the MPS.
Trouble
LED
Chassis
Connect to a suitable
ground or to TB1-2 on the
Main Power Supply (see
Figure 5-1).
No connection
+ -
1 2 3 4 5 6
Secondary
Power
to
MPS
Terminals
5 (+) & 6 (-)
Primary Power
Neutral Hot
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
33
Page 34
Section Six:
Applications
Waterflow Alarm
A waterflow alarm device may be connected to an Initiating Device Circuit (zone) provided that the circuit is
programmed to activate at least one Notification Appliance Circuit and one of the following conditions are met:
✔ ✔
✔ The Initiating Device Circuit is programmed for waterflow operation
✔ ✔
OR
✔ ✔
✔
The Notification Appliance Circuit is programmed as non-silenceable.
✔ ✔
Supervisory Service
Supervisory Devices: Normally open supervisory devices may be connected to any Initiating Device Circuit
provided that the circuit is programmed for supervisory operation. This circuit must be dedicated to supervisory
devices.
Central Station
This control panel can be employed as a protected premises Control Unit (meeting the requirements of NFPA 721993 Remote Station and Central Station) when used in conjunction with a compatible, UL listed Digital Alarm
Communicator such as the Noti•Fire 911A or UDACT-F.
Digital Alarm Communicator Transmitters (DACT)
The Fire Alarm Control Panel (FACP) will support a Digital Alarm Communicator Transmitter (DACT) provided
that the panel is configured and programmed for DACT operation. Software P/N 73452 (or higher) will support
DACT’s that are activated via relay contacts (Notifier 911A), while Software P/N 73611 (or higher) will support
the Fire-Lite UDACT-F via the EIA-485 Annunciator Port.
The FACP must be programmed for DACT operation (see the Extended Programming Section). Programming
the FACP for DACT operation will delay the reporting of an AC loss condition for approximately eight hours
(Software P/N 73452 or higher) and modify the EIA-485 Annunciator Port protocol (Software P/N 73611 or
higher) for UDACT-F operation. The modified protocol is compatible with the AFMX and LDM Annunciators.
34
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 35
DACT continued
Annunciators and a UDACT-F can be connected to the EIA-485 Annunciator Port simultaneously. However,
the modified EIA-485 protocol alters the assignment of the first eight yellow annunciator LED’s as follows:
The FACP must be programmed for an annunciator whenever it's connected to a UDACT-F since the
UDACT-F receives the FACP status on the EIA-485 Annunciator Port. If the FACP is connected to both
annunciators and a UDACT-F, all devices except one must be configured as receive only. Refer to the table
below for configuration and supervision arrangements.
seciveD
dellatsnI
F-TCADU
ylnO
noitarugifnoCnoisivrepuSnoitarugifnoCnoisivrepuS
timsnarT/evieceR584-AIEaiVelbacilppatoN
timsnarT/evieceR584-AIEaiV
dnaF-TCADU
rotaicnunnA
ylnOevieceR
timsnarT/evieceR584-AIEaiV
1) Additional annunciators may be employed in the Receive Only Mode. The wiring to these annunciators will be supervised only if
the power and the EIA-485 circuits are wired sequentially and the Receive/Transmit device is connected last.
2) The UDACT-F’s Comm Fail Output (TB3, pin #2) must be connected to P4 pin #1 (lower pin) on the FACP power supply.
3) The power and the EIA-485 circuits are wired sequentially (the FACP connects to the annunciator and the annunciator connects
to the UDACT-F).
F-TCADU)1etoN(rotaicnunnA
mmoCF-TCADUaiV
)2etoN(tuptuOliaF
evieceR1sserddA
ylnO
1sserddA
timsnarT/evieceR
evieceR1sserddA
ylnO
desivrepusnU
584-AIEaiV
584-AIEaiV
)3etoN(
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
35
Page 36
The UDACT-F is capable of repor ting the status of each zone (circuit) on the Sensiscan 200.
The UDA CT-F reports alarms and troubles on inputs and reports only troubles on outputs. Beware
of 'gaps' in the reporting of input circuits. The gaps depend upon the mounting location and
F A CP configuration.
Note: L Series modules report troubles using points 41 to 44 and 49 to 52.
The Sensiscan 200 has a maximum of 16 inputs.
The UDA CT -F m ust be mounted remotely in an ABS-8RF or UBS-1F enclosure and may be placed
up to 6000 feet aw ay from the control panel. All power must be removed from the control panel
before making any connections to prevent circuit damage. The EIA-485 serial interface is
connected between the control panel and UDACT-F using twisted, shielded pair wire. Power
should be wired from the control panel's main power supply (MPS-24BPCC) 24 VDC (nominal)
filtered power supply output to TB1 on the UDACT-F.
Figure 6-1A: External UDACT-F Connection in ABS-8RF
Supervised and Power
Limited EIA-485 and
power connections
ABS-8R
To Phone
Lines
(Supervised)
P/N 29090
Sensiscan
200
Cabinet
Install 120 ohm
EOL resistor (P/N:
Sensiscan 200
1)Ferrite cores are recommended for all applications.
2)Recommended wire is 12 AWG to 18 AWG twisted pair.
3)Shielded wire is not required (unless mandated by local AHJ).
If shielded wire is used, connect only one end of shield:
a)Shield may be connected to cabinet (earth ground) at fire alarm panel, or
b)Shield may be connected to TB1 Terminal 5 (Shield) at UDACT-F.
to prevent accidental grounding. Do not connect both ends of shield under any circumstance since a ground fault may
result.
4)Conduit is recommended for external wire runs. Consult local building codes.
5)Connect Ground Strap (supplied with ABS-8RF enclosure) from Earth Ground terminal on UDACT-F to a solid building earth
ground. Conduit alone will not provide a reliable earth ground.
6)UDACT-F may be located up to 6000 feet away from the host control panel.
7)Refer to Specifications for power requirements.
71244) on TB1
terminals 3 & 4 if
last or only device
on EIA-485 line.
UDAC T-F in ABS-8RF
(Shown with cover remov ed)
The shield end that is not connected should be insulated
Solid Earth
Ground
Connection
36
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 37
No connection
to top pin
Lower pin
connects to
TB3, pin #2 on
UDA CT-F
(Comm Fail)
Required for supervision
if UDAC T-F is operated
in "receive only" mode.
Fire-Lite Alarms cable P/
N 75148 may be
-
Filtered, regulated,
+
resettable, power
ordered for this purpose.
limited 24 VDC
Figure 6-1B: MPS-24BPCC Connection to UDACT-F
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
37
Page 38
Figure 6-2: 911A Digital Communicator Connection
The Noti-Fire 911A Digital Alarm Communicator Transmitter (DACT) is a three-zone module designed to provide
for off-premises monitoring of this fire alarm control panel. For stand-alone installations, use the 911AC kit that
includes a transformer and an enclosure(s) for both the 911A and the transformer. The 911A is self-powered in
this mode and is triggered by the alarm and/or trouble contacts received from the control panel. It communicates
with a digital receiver by means of one of two transmission formats, BFSK or Pulsed Fast Single Round format.
Power Requirements: 24VDC, 30 mA in Normal; 138 mA while communicating; 166.8 mA with alarm & trouble
relays while communicating. Retard time and Reset time must be programmed for zero second when connecting
the alarm initiating circuit to an existing control panel.
For more detailed instructions refer to the Noti-Fire 911A manual, Document #74-06200-005-A. Note: The 911A
is not FM-approved.
+24 VDC
27.6 VDC
Trouble
Common
CPU
Alarm
27.6 VDC
911A
Note: Wiring between the FACP
and 911A must be in conduit.
UPCA119SPM
mralA
nepoyllamroN
stcatnoc
elbuorT
nepoyllamroN
stcatnoc
CDV42+
nommoC
CDV6.72+
Red
41-1BT7dna6
51-1BT9dna8
9-1BT01
11-1BT11
23-2BT
44-2BT
15-2BT
38
Black
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 39
Tee-Tapping
One Tee-Tap will be allowed on Style Y Notification Appliance Circuits if a 10K End-of-Line Resistor (Part #
71274) is used on each branch as shown in Figure 6-3.
Note: Factory Mutual (FM) recommends this application not be used.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
39
Page 40
Four-Wire Smoke Detectors
Initiating devices requiring 24 VDC operating power can be wired as illustrated in Figures 6-4 and 6-5.
-
IZ-4AF
or IZ-8F with IZE-AF
Initiating Device Circuit
+
+
-
IDC(+)
IDC(-)
24 VDC (+)
Common (-)
C
+24 VDC
-0 VDC
NC
24VDC Power Supply
Power-limited, UL listed for Fire
Protective Signaling
MPS-24BPCC
TB2 Term. 1 (+) & 2 (-)
IZ-4F or IZ-8F
Initiating Device Circuit
24VDC Power Supply
Power-limited, UL listed for Fire
Protective Signaling
MPS-24BPCC
TB2 Term. 1 (+) & 2 (-)
UL-listed 24 VDC
Four-Wire Smoke Detectors
UL Listed Power
Supervision
Relay
+
Figure 6-4:
-
+
-
+
-
Employing Four-Wire Smoke Detectors (Style D)
All connections are supervised and power limited
4.7K
NC
IDC(+)
IDC(-)
24 VDC (+)
Common (-)
UL-listed 24 VDC
Four-Wire Smoke Detectors
ELR
C
+24 VDC
-0 VDC
UL Listed Power
Supervision
Relay
Figure 6-5:
Employing Four-Wire Smoke Detectors (Style B)
All connections are supervised and power limited
Notes on Style B and Style D field wiring:
1) The Power Supervision Relay coil leads must be connected to the last detector base 24V screw terminal.
2) Calculation of the maximum allowable resistance in the 24VDC detector power wiring:
RMAX = (20.6 - VOM)
(N)(IS) + (NA)(IA) + (IR)
RMAX — is the maximum total resistance of the 24-volt power circuits.
VOM —is the minimum operating voltage of the detector or end of line relay, whichever is greater, in volts.
N —is the total number of detectors on the 24V supply loop.
IS—is the detector current in standby.
NA —is the number of detectors on the 24V power loop which must function at the same time in alarm.
IA —is the detector current in alarm.
IR —is the end-of-line relay current.
40
where:
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 41
Notification Appliance Circuit Power Configurations
The total current drawn from a Notification Appliance Circuit cannot exceed 3.0 amps
(subject to the limitations of the power supply). Figure 6-6 illustrates some of the
typical power supply/Notification Appliance Circuit configurations possible.
These two Notification
Appliance Circuits share 2.0
amps.
These six
Notification Appliance
Circuits share 2.0 amps.
These ten
Notification Appliance
Circuits share 2.0 amps.
MPS
AVPS-24F
J5
ICE-
4F
J5
CPU
Module
J5
IC-4F
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
These two Notification Appliance Circuits share 2.0
amps.
These four Notification Appliance Circuits share the
total 3.0 amps of current on
the AVPS-24F.
41
Page 42
MPS
MPS
AVPS-24F
Figure 6-6: Typical Supply/Notification
Circuit Configurations (continued)
J5
CPU
J6
J5
ICR-4LF
J6
J5
CPU
J6
J5
ICR-4LF
J6
These four
Notification
Appliance Circuits
share 2.0 amps
These two
Notification
Appliance
Circuits share
2.0 amps and
these two
Notification
Appliance
Circuits share
3.0 amps
42
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 43
Remote Command Inputs
The function of Acknowledge, Signal Silence, and Reset can be executed from remote switches. The switches
are wired to IZ-8F circuits which must be programmed for this special operation. Additional functions are outlined
below.
Presignal Inhibit: Zone 1. Program zone as non-alarm and supervisory. This command is used to inhibit
presignal operation. Upon entering presignal, the CPU checks zone 1 on all IZ-8F modules. If the zone is active
(shorted), all presignal or PAS operation will be ignored.
Emergency Alert: Zone 5. Program zone as non-alarm and supervisory. Use as an evacuation signal for
tornados, bomb-scares and other non-fire emergency situations. If the control panel is not in alarm, activation
(short) on zone 5 will activate all Notification Appliance Circuits and output relays, that are mapped to zone 5, with
a steady signal. Programmed March Time or Temporal code is ignored. A fire alarm will take priority over an
emergency alert. Notification Appliance Circuit used for fire must be programmed for MTC or Code 3 operation.
Emergency Alert is for local signalling only, do not map to "Remote Signalling/Municipal Tie" outputs.
Acknowledge: Zone 6. Program circuit as non-alarm and supervisory. Use to remotely execute an Acknowledge
command without the need of an AFM-16ATX annunciator.
Signal Silence: Zone 7. Program circuit as non-alarm and supervisory. Use to remotely execute the Signal
Silence command without the need of an AFM-16ATX annunciator.
System Reset: Zone 8. Program circuit as non-alarm and supervisory. Use to execute the Reset function without
the need of an AFM-16ATX annunciator.
Presignal
Inhibit
Emergency
Alert
Acknowledge
Signal
Silence
Reset
IZ-8F
Figure 6-7: Remote Command Input Connections
1) Initiating circuits used as command circuits are supervised, power limited, and may be connected to limited-energy cable.
2) Maximum line resistance allowed due to wiring is 100 ohms.
Acknowledge, Signal Silence and System Reset Switches (Style B).
Use circuit "E" for Emergency Alert,
"F" for Acknowledge, "G" for Signal Silence, and "H" for Reset.
ABCDEFGH
ññ ññ ññññ
B+ B- B+ B- B+ B- B+ B- B+ B- B+ B- B+ B- B+ B-
IZ-8F
A
Presignal Inhibit
B
(standard zone)
C
(standard zone)
D
(standard zone)
E
Emergency Alert
F
Acknowledge
G
Signal Silence
H
System Reset
Style B
4.7K ELR
P/N 71252
Presignal Inhibit
Switch
B+ B-
1)Switches used to control Presignal Inhibit, Acknowledge, Signal
Silence or System Reset must be key operated, located within a
locked cabinet, or arranged to provide equivalent protection
against unauthorized use.
2)Switches must be UL listed to switch 30 VDC at 50mA.
3)If a key operated switch is used, the key should be removable in
both open and closed positions, when used for Presignal Inhibit.
The keys should be removable in the open position only when
used for Acknowledge, Signal Silence or System Reset.
Dummy load all unused
circuits with 4.7K ELR,
Part # 71245
44
4)The Presignal Inhibit, Emergency Alert, Acknowledge, Signal
Silence or System Reset functions can be controlled by a relay
contact from a CR-4F/CRE-4F Relay Module, which can be operated from switches on AFM-16ATX, AEM-16ATF, AFM-16ATF, or
LDM-32F Annunciators.
5)Locate Acknowledge, Signal Silence and System Reset switches
adjacent to a system annunciator so that system status is
available to the operator.
6)Remote Command Circuits are supervised and power limited.
Maximum wire resistance per circuit is 100 ohms. Circuits wired
for Style B operation requires a 4.7K ELR (P/N 71252) at the end
of the line.
Acknowledge, Signal Silence and System Reset Switches (Style D).
Use circuit "E" for Emergency Alert,
"F" for Acknowledge, "G" for Signal Silence, and "H" for Reset.
ABCDEFGH
сс сссссс
A+ A- A+ A- A+ A- A+ A- A+ A- A+ A- A+ A- A+ A-
B+ B- B+ B- B+ B- B+ B- B+ B- B+ B- B+ B- B+ B-
IZ-8F
A
Presignal Inhibit
B
(standard zone)
C
(standard zone)
E
Emergency Alert
F
Acknowledge
G
Signal Silence
Style D
Presignal Inhibit
Switch
Jumper all unused
circuits as shown
D
(standard zone)
1)Switches used to control Presignal Inhibit, Acknowledge, Signal Silence or System Reset must be key operated, located
within a locked cabinet or arranged to provide equivalent protection against unauthorized use.
2)Switches must be UL listed to switch 30 VDC at 50mA.
3)If a key operated switch is used, the key should be removable in both open and closed positions, when used for Presignal
Inhibit. The keys should be removable in the open position only when used for Acknowledge, Signal Silence or System Reset.
4)The Presignal Inhibit, Emergency Alert, Acknowledge, Signal Silence or System Reset functions can be controlled by a relay contact
from a CR-4F/CRE-4F Relay Module, which can be operated from switches on AFM-16ATX, AEM-16ATF, or LDM-32F Annunciators.
5)Locate Acknowledge, Signal Silence and System Reset switches adjacent to a system annunciator so that system status
is available to the operator.
6)Remote Command Circuits are supervised and power limited. Maximum wire resistance per circuit is 100 ohms. Circuits
wired for style B operation requires a 4.7K ELR (P/N 71252) at the end of the line.
H
System Reset
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
45
Page 46
Section Seven: Programming
General
The control panel is programmed entirely by using the four switches on the CPU. The eight LEDs are used to show
the programmer the status of programming. Each of these LEDs has two states - flashing and steady. On the
programming label, two functions are associated with each LED. The function marked with an "F" is indicated by
a flashing LED. The function marked with a "S" is indicated by steady LED illumination.
Preparing for Programming
Slide programming label into Dress Panel. Insert the Programming Key through the dress panel into Plug J11
on the CPU. Wait until ENTER PASSWORD LED and PRESS ENTER LED flash, then enter password.
Entering Passwords
There are four different programming modes, each with its own password. They are as follows:
Reconfigure: 123-1231 System Programming: 123-1232 Extended Features: 123-3211 Clear Program
312-1233 After entering the appropriate password digits, press the ENTER switch.
Clear Program
Before reconfiguring the system, we recommend clearing the CPU's memory. To do this use the PROGRAM
CLEAR function. After PREPARING FOR PROGRAMMING enter the password 312-1233 then press and hold
the ENTER key. The LEDs on the modules will go through a scrolling sequence until finally only the ENTER
PASSWORD and PRESS ENTER LEDs are lit (approx. 10 sec.). PROGRAM CLEAR is now complete and the
system is ready for reconfiguration. NOTE: Program clear should only be executed on new systems or ones that
have been significantly changed because all previous programming will be removed!
Reconfigure Mode
Upon entering the
reconfigured the first time it is programmed and any time a module is removed or added. The
sets new modules to the following default conditions: (the program for modules that have been previously
reconfigured remains unchanged)
✔✔
✔ No circuits are selected for waterflow, supervisory, or circuit verification.
✔✔
✔ ✔
✔ No circuits are selected for coded output.
✔ ✔
✔✔
✔ Control relays are non-silenceable.
✔✔
After entering the Reconfigure password and pressing CHANGE STATE key, the PASSWORD ACCEPTED LED
and the RECONFIGURE LED will illuminate. All correctly-installed modules will light their LEDs as follows:
IZ-8F: All red and yellow LEDs
IZ-4F, IZ-4AF: All red and yellow LEDs
IC-4F, ICR-4LF: Four green LEDs on left. All eight will light if an expander has been installed.
CR-4F, CR-4LF: Four yellow LEDs on left. All eight will light if an expander has been installed
TC-2F TC-4F: All eight green LEDs will light.
Press the ESCAPE switch to store the system
configuration. Programming will advance to programming of the system.
Access Security
Additional access security for the system
can be obtained by setting a switch on the
lower CPU board to the
tion. When set to the
the system will still give the impression that
it can be programmed, but pressing the
ENTER key will not result in the storing of
any program data — all work will be lost.
Reconfigure Mode
Write Inhibit
Write Inhibit
position,
, the CPU identifies what modules are in the system. The system must be
Reconfigure Mode
✔ ✔
✔ All Notification Appliance Circuits are silenceable.
✔ ✔
✔✔
✔ All circuits are mapped for general alarm.
✔✔
The Security
Switch can be
found in one of two
locations on the
CPU.
posi-
Write Enable
Position
Write Inhibit
Position
46
Note: The panel's Disable feature will not function with Write Inhibit selected.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 47
System Programming
System programming may be entered directly by password or is automatically entered after reconfiguring the
panel.
After entering the system programming password (123-1232), the green PASSWORD ACCEPT LED and the
yellow PROGRAM/SERVICE LED will illuminate. Programming of the system is performed sequentially. The first
function to be programmed is WATERFLOW.
Waterflow Operation
Notification Appliance Circuits and other outputs that are activated in response to an alarm
on a waterflow initiating circuit cannot be silenced by the SIGNAL SILENCE switch.
Programming Waterflow Circuits
The WATERFLOW LED will flash to indicate the
control panel is ready to be programmed for
waterflow circuits.
A flashing yellow initiating circuit LED serves as
the pointer. It shows the programmer what
circuit is being programmed at that time. Press
the STATE CHANGE switch to select or deselect this circuit for waterflow alarm. The red LED
on that circuit will illuminate when that circuit has
been selected. Pressing the POINT SELECT A
switch advances the pointer to the next initiating
circuit. Pressing the POINT SELECT B switch
moves the pointer to the previous initiating circuit.
When all waterflow circuits have been selected,
press the FUNCTION SELECT switch to store
the WATERFLOW programming information
and advance programming to the next function
— SUPERVISORY.
Supervisory Operation
Activation of a device on a circuit programmed
for supervisory will light the supervisory LED.
The system trouble LED and the system trouble outputs will not be activated. Supervisory circuits can be mapped
to controlled outputs. Circuits can detect the difference between the normally open supervisory switch and a break
in the field wiring.
Programming Supervisory Circuits
The Supervisory LED will illuminate steadily on the CPU. The pointer LED will be at the first initiating circuit. Use
the STATE CHANGE switch to select or deselect that circuit for supervisory. The POINT SELECT switches move
the pointer to the other initiating circuits. When all Supervisory circuits have been programmed, press the
FUNCTION SELECT switch to store the programming information and advance programming to the next function
— SILENCEABLE.
Note: Circuit programmed for both supervisory and non-alarm performs special functions. See Remote Command
Inputs.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
47
Page 48
Silenceable Operation
Silenceable circuits are controlled output circuits that, when activated, can be silenced by pressing the signal
silence key on the CPU. Do Not program the Remote Signalling / Municipal Tie output for silenceable operation.
Programming Silenceable Circuits
The SILENCEABLE LED will flash on the CPU. The pointer is represented by a flashing yellow LED on the first
output circuit. Use the STATE CHANGE switch to select or deselect the circuit for silenceable operation. The
green LED will illuminate when the circuit has been selected as silenceable. Use the POINT SELECT switches
to move the pointer to the other output circuits.
When all silenceable circuits have been programmed, press the FUNCTION SELECT switch to store the
programming information and advance programming to the next function — CODED CIRCUITS.
Coded Circuit Operation
Selecting controlled outputs for coded operation enables those outputs to pulse a selected code chosen later in
the programming process (see code type). Outputs that are not selected for coded operation will turn on steady.
Programming Coded Circuits
The CODED CIRCUIT LED will illuminate steadily on the CPU. The pointer will be at the first output circuit. Use
the STATE CHANGE switch to select or deselect the circuit for coded operation. Use the POINT SELECT
switches to move the pointer to the other output circuits.
When all coded circuits have been selected, press the FUNCTION SELECT switch to store the programming
information and advance programming to the next function — CODE TYPE.
Code Type Selection
Allows for the selection of March Time Code (110 beats per minute) or Temporal (3-3-3) coding for circuits
programmed as coded in the previous step. Code type selection is on a system basis, therefore all coded circuits
will sound the same code. Circuits that were not selected as coded are unaffected by Code Type selection.
Notes:
1)DO NOT program the Remote Signalling/Municipal Tie output for coded operation
2)Special requirements are necessary for coded circuit selections when using the TC-2F and TC-4F module. Refer to respective Time
Control manual for details.
3)If the Emergency Alert option is to be employed, circuits used for fire must be selected as coded. See "Remote Command Inputs".
Programming Code Type
The CODE TYPE LED flashes. Use the STATE CHANGE switch to chose between the two codes:
Code Type
Green LED for Notification Appliance Circuit 1 on-Temporal
Yellow LED for Notification Appliance Circuit 1 on-March Time Code
Temporal
March Time
When code type is programmed, press the FUNCTION SELECT switch to store the programming information and
advance the programming to the next function — VERIFIED ZONES.
Verified / PAS
Alarm Verification increases the time required to initiate an alarm from two wire smoke detectors. When the
system detects an alarm on an initiating circuit programmed for verification, it will automatically reset the power
to that circuit. Power is then reapplied, beginning a verification period. Any alarm detected during this period will
initiate an immediate system alarm.
48
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 49
Verification should only be used on circuits where the false alarm rate cannot be reduced to an acceptable level
by other means. Only alarm signals from two-wire smoke detectors can be verified since four-wire smoke
detectors are not reset during verification. Both two-wire smoke detectors and N.O. shorting-type initiating
devices may be connected to the same circuit, although verification will not affect the contact type devices.
Positive Alarm Sequence (PAS)
PAS adds a 15 second, post-alarm delay to signal activation. Pressing the ACKNOWLEDGE or SILENCE key
before 15 seconds has expired will change the timer to its full value (1, 2, OR 3 MINUTES) programmed.
For proper operation of PAS, the following conditions must be met:
1) The control panel must be located so that an alarm signal can be acknowledged by trained personnel within
15 seconds.
2) The system must be equipped with a presignal bypass switch.
3) The system must be configured so that activation of a second automatic fire detector bypasses presignal and
immediately activates alarm signals. To accomplish this, the installer must employ AIM-200 modules to
provide point annunciation of initiating points OR install one smoke detector per conventional initiating device
zone.
4) Zones selected for PAS operation shall contain smoke detectors only. These zones may not contain other
initiating devices such as manual stations, heat detectors, waterflow indicators, etc.
A fire alarm system that fails to meet the above requirements for PAS service will be classified as a
presignal system only.
Programming Verified or PAS Zones
The VERIFIED / PAS LED will illuminate steady. The pointer will be at the first initiating circuit. Use the STATE
CHANGE switch to select or deselect the circuit for verification. Use the POINT SELECT switches to move the
pointer to the other initiating circuits.
When all VERIFIED / PAS ZONES are programmed press the FUNCTION SELECT switch to store programing
information and advance programming to the next function — NON ALARM INPUTS.
Non Alarm Inputs
A non-alarm input is an initiating circuit that, upon activation, will not light the System Alarm LED or cause the piezo
to sound, will not latch, will self-restore and can be mapped to activate output circuits. Note: If the system is in
alarm, or enters an alarm condition, non-alarm inputs WILL latch.
When a short circuit occurs on a non-alarm circuit, the IZ red LED is turned on, but the System Alarm LED and
the piezo sounder are not activated. Non-alarm points have a lower priority compared to regular IZ alarm zones.
Non-alarm circuits are "tracking" (non-latching) in that they turn on when the circuit is shorted and turn off when
the circuit returns to normal (unless the system is in alarm). Non-alarm circuits use the I/O map capability of the
control panel and the mapped controls simply turn on/off as the non-alarm point turns on/off. Non-alarm circuits
are supervised for opens. Note: Circuits programmed for both supervisory and non-alarm perform special
functions. See Remote Command Inputs.
Applications
Non-Alarm circuits are used to monitor devices that are not fire initiating sensors. Examples of these applications
are:
✔✔
✔ Sensors such as thermostats or timers could be connected to Non-Alarm points and used to open/close
✔✔
ventilation dampers connected to S200 outputs. In the event of a fire situation, the control panel could force the
dampers in one position or the other, and subsequent non alarm state changes would be ignored.
✔✔
✔ A manual drill switch could be connected to an IZ point and used to manually test the alarm system without
✔✔
causing a System Alarm or activating a Remote Station.
✔✔
✔ Door locks connected to CR-4F/CRE-4F modules could be unlocked when a fire is detected by the control
✔✔
panel. A Non-Alarm point could be used to manually unlock/lock the doors in non-fire situations.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
49
Page 50
Programming Non-Alarm Inputs
The NON ALARM INPUTS LED will flash. The pointer will be at the first initiating circuit. Use the STATE CHANGE
switch to select or deselect the circuit as a Non Alarm Input. The left-hand LED (red) on each point will illuminate
when the circuit is selected, and will extinguish when the circuit has been deselected. Use the POINT SELECT
switches to move the pointer to the other output circuits. Press the FUNCTION SELECT switch to store this
programming and proceed to programming the next function — ANNUNCIATOR INSTALL.
Annunciator/UDACT-F Installation
Annunciator/UDACT-F installation programming allows the programmer to tell the panel if a serial annunciator or
UDACT-F has been installed.
Programming Annunciator Installation
The ANNUNCIATOR INSTALL LED will illuminate steadily. An illuminated green LED for
Notification Appliance Circuit #2 represents an installed annunciator. Use the STATE
CHANGE switch to select or deselect annunciator installation. After programming annun-
Annunciators
None
Annun
ciator installation, press the FUNCTION SELECT key to store the programming information
and advance programming to the next function.
Silence Inhibit
The SILENCE INHIBIT function prevents the operation of the Signal Silence switch for 30 seconds, 60 seconds
or 5 minutes after the output circuits have been activated.
Programming Silence Inhibit
The SILENCE INHIBIT LED will flash. Use the STATE CHANGE switch to select
Silence Inhibit time as represented by the Alarm Relay LEDs.
After programming Silence Inhibit press the FUNCTION SELECT switch to store this
information and select the next function — I/O Map.
Silence Inhibit
None
30 Sec
60 Sec
5 min
Input/Output MAP
The I/O map is the assignment of output circuits to be activated by particular initiating circuits. Unmapped initiating
circuits will not generate a system alarm. Unmapped controlled outputs will not operate.
Programming the I/O MAP
The I/O Map LED will illuminate steadily. The red LED pointer will illuminate steadily on the selected initiating
circuit. A yellow flashing LED points to an output circuit. Pressing the STATE CHANGE switch will select or
deselect the output circuit to be activated by the initiating circuit. Use the POINT B SELECT to scroll through each
of the output circuits and the STATE CHANGE switch to select/deselect the outputs (after scrolling through all of
the output circuits it will cycle back to the first).
After each of the output circuits has been selected/deselected, press the POINT A SELECT switch to move the
red pointer to the next initiating circuit. Continue mapping outputs for each initiating circuit.
After programming the I/O map, press the FUNCTION SELECT key to store I/O map programmed. If you do notpress the FUNCTION SELECT switch after programming the I/O Map, the I/O map will not be saved. Yellow
LEDs on initiating circuits show unmapped circuits. Press ESCAPE switch to return to I/O mapping, or ENTER
switch to return to Waterflow. Remove the Programming Key to exit programming mode.
Note: After the system has been programmed, the Programming Key must be removed to transfer
the programming information from temporary memory storage to nonvolatile memory.
50
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 51
Extended Programming Features
These features are available in CPU EPROM U4 software numbered 73167 (or greater).
The AUTO SILENCE feature will automatically turn off all silenceable circuits after a pre-programmed delay. The
delay timer starts after a system alarm. Any subsequent alarms which occur before the auto silence activates
will restart the delay countdown at zero.
The PRESIGNAL DELAY delays the activation of all silenceable circuits mapped to a zone in alarm for a preprogrammed length of time. A subsequent alarm aborts the delay and re-maps all alarm points. Pressing the
SIGNAL SILENCE switch before the delay time has expired aborts the delayed activation of the silenceable
circuits.
The Positive Alarm Sequence (PAS) function adds a timer. After a first alarm, the timer is set for 15 seconds.
If nothing happens in that 15 seconds, all signals are activated. If an ACKNOWLEDGE or SILENCE key (including
annunciator keys) is pressed before 15 seconds, the timer changes to its full value (1, 2, or 3 minutes).
Note: When Pre-Signal Delay has been selected, at least one Notification Appliance Circuit must be programmed
as non-silenceable. This will ensure that at least one notification circuit will sound immediately after initiation of
an alarm condition.
Note: NFPA 72 requires the installation of a Day/Night/Weekend switch that can override PAS operation. This
can be accomplished by using a normally open switch to close an IZ-8F that has been programmed for NONALARM and SUPERVISORY operation. Note: That zone cannot have a Notification Appliance Circuit mapped
to it.
The switch totally inhibits all presignal function. On entering presignal mode, the CPU checks zone 1 in module
1. If this is an IZ-8F zone set for NON-ALARM and SUPERVISORY, and it is
active
(switch is on), all presignal
and PAS operation will be ignored.
DACT - (UDACT-F)
When a Digital Alarm Communicator Transmitter (Notifier 911A) is used, the reporting of an AC Loss condition
must be delayed. With software P/N 73452 (or higher), this function can be selected under extended programming
features. When selected, the CPU's trouble contacts will not be activated for loss of AC power until approximately
8 hours after loss of power occurs.
Software P/N 73611 (or higher) is required to support the Fire-Lite UDACT-F. When using a UDACT-F, the
"DACT" mode must be selected under the extended programming feature and "Annun" under programming.
The CALIFORNIA CODE mode adds a ten second timer. When an alarm occurs, the timer is started. At the end
of the ten second period, all silenceable circuits are shut off for five seconds. At the end of the five seconds, the
circuits are turned on again for 10 seconds. This cycle repeats indefinitely.
In the event of an acknowledged alarm, the REMINDER mode pulses the piezo every 15 seconds. If an
acknowledged trouble exists, but not an alarm, the piezo is pulsed every two minutes.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
51
Page 52
Programming
To program the features of AUTO
SILENCE, PRESIGNAL DELAY, and
CALIFORNIA CODE, key in the
password 123-3211 and push ENTER.
In addition to PASSWORD ACCEPTED and PROGRAM/SERVICE
LEDs, the NON-ALARM LED will
flash on the CPU.
Press the ENTER switch to scroll
through the options for AUTO SILENCE until the LEDs reflect the desired choice.
Press the FUNCTION SELECT
switch to store the option setting in
memory and advance to the next
point to be programmed. Again, press
the ENTER switch until the LEDs reflect the desired choice, followed by
the FUNCTION SELECT switch to
store the data.
To exit extended programming at any
time, remove the programming key.
The 123-3211 password does not allow access to any other program features and does not cause the system
to reconfigure.
CPU
52
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 53
Section Eight:
Operating the Control Panel
CPU LED Indicators
AC POWER: A green LED that indicates the presence of normal AC power.
This LED is turned off when the AC line voltage falls below normal.
SYSTEM ALARM: A red LED that indicates an alarm condition. This LED
initially flashes during alarm (the CPU will also sound a continuous audible
tone). Silencing or acknowledging the alarm(s) turns the audible tone off and
causes the LED to illuminate steadily. Subsequent alarms will resound the
audible tone and flash their LEDs. Alarm signals latch until the control panel
is reset.
SUPERVISORY SIGNAL A yellow LED that indicates activation of a circuit
programmed to monitor supervisory devices.
SYSTEM TROUBLE: Indicates the presence of a trouble condition in the
system.
AC
POWER
SYSTEM
ALARM
SUPERVISORY
SIGNAL
SYSTEM
TROUBLE
ANNUNCIATOR/
MODULE FAILURE
ANNUNCIATOR OR MODULE TROUBLE: Indicates a trouble in a module
in the control unit or in a remote annunciator.
AC/BATT/GND FAULT: Indicates 1) that a power supply is not functioning
correctly, 2) AC line voltage is below normal, 3) improper battery voltage, or
4) that a ground fault exists. Additional information is displayed on internal
AC/BATT/GND
FAULT
SIGNAL
SILENCE
DISABLED
CIRCUITS
LEDs located on power supply assemblies.
ACKNOWLEDGE
SIGNAL SILENCE: Indicates that an output circuit is silenced. Indication will
SILENCE TONE
1
remain until the reset switch is depressed.
DISABLED CIRCUITS: Indicates that a circuit(s) within the system has been
SIGNAL
SILENCE
2
manually disabled.
CPU Control Switches
ACKNOWLEDGE (SILENCE TONE): Depressing Acknowledge turns the
audible tone off and switches LED operation from flashing to steady. A
SYSTEM
RESET
LAMP TEST
DISABLE/ENABLE
3
subsequent trouble or alarm will resound the audible tone and flash appropriate LEDs.
SIGNAL SILENCE: Returns all silenceable outputs, which were automatically activated by the alarm condition,
to their non-alarm state. A subsequent alarm can reactivate alarm outputs.
SYSTEM RESET: The System Reset Switch will reset the system provided that the alarm condition is clear.
Holding this switch depressed will sequentially light (lamp test) all LEDs.
LAMP TEST: The Lamp Test Switch illuminates all the LEDs in the system for as long as the switch is held down.
This switch can also be used to disable or enable individual circuits.
Note:
The CPU produces a pulsed tone for troubles, disabled outputs, and supervisory conditions. A continuous tone
is generated for alarms.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
53
Page 54
CPU Circuits
The CPU Module contains: 1) Two supervised Notification
Appliance Circuits that can be used to control evacuation
signaling devices such as bells, chimes, horns, and
strobes. 2) An alarm relay that can control external devices such as elevators, and doors. 3) A Remote Signaling/Municipal Tie output for connection to a municipal fire
department, central station, or a remote monitoring station.
Notification Appliance Circuit #1
Notification Appliance Circuit #2
Municipal Box/Remote Signaling Tie
Green LEDs: Each output has a green
LED that indicates activation of that circuit.
Form-C Alarm Relay
Yellow LEDs: Each output circuit has a yellow LED that
indicates trouble conditions or disabled outputs. New troubles
are indicated by a flashing LED.
54
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 55
IZ-4F
IZ-4F, IZ-4AF and IZ-8F Initiating
Zone Modules
Each Initiating Zone Module (IZ) will
monitor up to eight initiating zones
(groups) of initiating devices (smoke
detectors, pull stations, heat detectors) for alarm signals. It also checks
the integrity of the building wiring
between the module and the initiating devices. The IZ module conveys
the status of the initiating zones and
their wiring to the CPU module and
at the direction of the CPU will light
the appropriate LEDs to display
alarm and trouble conditions (broken wire, inactive circuit, etc.).
The red LEDs indicate alarm conditions. New alarms are indicated by a
flashing LED and a steady audible
tone. Silencing an alarm turns the
audible tone off and causes the LED
to illuminate steadily.
The yellow LEDs indicate an initiating zone trouble or a disabled zone.
New troubles are indicated by a
flashing LED and a pulsed audible
tone. Silencing a trouble turns the
audible tone off and switches LED
operation from flashing to steady. A
subsequent trouble from a different
initiating zone will resound the audible tone and flash its LED. Trouble
signals will self-restore as soon as the
trouble conditions are corrected.
IC-4F
IC-4F Indicating Circuit Module
Each Indicating Circuit Module
(IC) will control and monitor up to
eight Notification Appliance Circuits (with an ICE-4F expander
installed) of evacuation signaling
devices, such as bells, chimes,
horns, and lights. The IC module
conveys the status of the Notification Appliance Circuits and their
wiring to the CPU module and at
the direction of the CPU will light
the appropriate LEDs to display
activation and trouble conditions
(broken wire, inactive circuit). The
Notification Appliance Circuits
activate automatically during an
alarm condition according to a
program instructions stored in
CPU nonvolatile memory. This
module is also programmable for
California Code.
The green LEDs indicate an activated Notification Appliance Circuit.
The yellow LEDs indicate a notification circuit trouble or a disabled
circuit. New troubles are indicated
by a flashing LED and a pulsed
audible tone. Silencing a trouble
turns the audible tone off and
causes the LED to illuminate
steadily. A subsequent trouble
from a different circuit will resound
the audible tone and flash the associated trouble LED. Trouble signals will self-restore as soon as
the trouble condition has been
corrected.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
CR-4F
CR-4F and CR-4LF Control Relay Modules
Each Control Relay Module (CR)
controls up to eight relays (with a
CRE-4F expander installed),
which can be connected to control
external devices including elevators, doors, and air handling equipment. These relays will be activated automatically during an
alarm condition according to program instructions stored in CPU
module's memory.
The green LEDs indicate that the
associated control relay has been
activated.
The yellow LEDs indicate that the
associated control relay output
has been disabled.
NOTE: ICR-4LF Notification Appliance Circuits function like those
on IC-4F. Relays function as on
the CR-4F.
55
Page 56
Disabling/Enabling Circuits
For servicing of the system, input or output circuits can be disabled.
To disable a circuit, a 1-2-3 key sequence must be entered and the operator must advance to the circuit to be
disabled.
1) Press the LAMP TEST switch and hold it in throughout
the remainder of this procedure.
2) Press 1, 2, 3. If any circuits have been previously
disabled, they will be indicated by illumination of their
left-hand LED (red for initiating circuits, green for all
others).
The position of the circuit pointer is indicated by the
flashing yellow LED.
To move forward in the circuit map, press Switch 3
(SYSTEM RESET). To move backward in the
circuit map, press Switch 2 (SIGNAL SILENCE).
3) Move forward or reverse until the pointer stops at the
circuit to be disabled.
ACKNOWLEDGE
SILENCE TONE
1
SIGNAL
2
SILENCE
SYSTEM
RESET
3
LAMP TEST
DISABLE/ENABLE
4) Press Switch 1 (ACKNOWLEDGE) to turn on the
left-hand LED on the circuit to be disabled. When this
LED is on, the circuit has been disabled.
A circuit can be re-enabled by pressing Switch 1 until
the left-hand LED goes out.
5) Repeat steps 3 and 4 until all disabling/enabling has
been accomplished.
6) Release the LAMP TEST switch to exit Disable/Enable
mode. The control panel will return to operation with the
selected circuits disabled.
Caution: Disabling a circuit will reduce or eliminate fire protection.
56
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 57
Section Nine:
Testing & Maintenance
Acceptance Test
Upon completion of the original installation and following subsequent modifications, a complete operational test
should be conducted on the entire installation for the purpose of verification of compliance with the applicable
NFPA standards. Testing should be conducted by a factory-trained distributor in the presence of a representative
of the Authority Having Jurisdiction and the Owner's Representative. Follow procedures contained in NFPA 721993, Chapter 7, "Inspection, Testing and Maintenance."
Periodic Testing and Service
Periodic testing and servicing of the system, all initiating devices and notification appliances, and any other
associated equipment is essential to insure proper and reliable operation. Testing and servicing should be in
accordance with the schedules and procedures outlined in: 1) NFPA 72-1993, Chapter 7, "Inspection, Testing and
Maintenance," and 2) the service manuals and instructions for the peripheral devices contained in your system.
Correct any trouble condition or malfunction immediately.
Operational Checks
Between formal periodic testing and servicing intervals, the following operation checks should be performed
monthly or more frequently when required by the Authority Having Jurisdiction.
1) Check that the green "AC POWER" LED is illuminated.
2) Check that all yellow LEDs are off.
3) Holding "SYSTEM RESET" depressed should sequentially light all system LEDs.
4) Before proceeding, a) notify fire department and/or central alarm receiving station if alarm conditions are
transmitted; b) notify facility personnel of test so that alarm sounding devices are ignored during test
period; c) when necessary, activation of alarm notification appliances can be prevented by disabling those
circuits.
5) Activate an Initiating Device Circuit via an alarm initiating device and check that all active notification
appliances function. Reset the alarm initiating device, the control panel, and any other associated
equipment.
6) Repeat Step 5 for each Initiating Device Circuit.
7) Remove AC power, activate an Initiating Device Circuit via an alarm initiating device and check that active
notification appliances sound, and alarm indicators illuminate. Measure the battery voltage while
notification appliances are activated. Replace any battery with a terminal voltage less than 21.6 volts.
Replacement batteries may be obtained from control panel manufacturer. Minimal replacement battery
capacity is indicated on the control panel marking label. Reapply AC Power. Note: This test requires fully
charged batteries, if batteries are new or discharged due to a recent power outage, allow the control panel
to charge batteries for 48 hours before testing.
8) Check that all yellow LEDs are off and that the green "AC POWER" LED is illuminated.
9) Notify fire, central station and/or building personnel that test is complete.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
57
Page 58
Battery Checks
Maintenance-free sealed lead-acid batteries do not require the addition of water or electrolyte. They are charged
and are maintained in a fully charged state by the main power supply's float charger during normal system
operation. A discharged battery will charge at 0.75 amps (typically) and obtain its float voltage of 27.6 volts within
48 hours.
Replace any battery that is leaking or damaged. Replacement batteries may be obtained from Fire-Lite Alarms,
Inc. Minimal replacement battery capacity is indicated on the control panel marking label. To check battery and
system, Refer to Section "Operational Checks" above.
Caution!
Batteries contain Sulfuric Acid which can cause severe burns to the skin and eyes and damage to fabrics.
In the event a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or eyes
with water for at least 15 minutes. For eyes, seek immediate medical attention. A good neutralizing
solution for Sulfuric Acid is water and household baking soda. Care should be taken to insure proper
handling of the battery to prevent short-circuiting. Accidental shorting of the leads from uninsulated
work benches, tools, bracelets, rings, and coins should be avoided. Shorting the battery leads can
damage the battery, equipment, and could cause injury to personnel.
Walk Test
In order to execute Walk Test from the control panel, the PKB Programming Key must be inserted into the CPU.
Enter the Walk Test password (123-1233). The PASSWORD ACCEPTED LED will light and the WALK TEST LED
will flash. Activate an initiating device and all output circuits that are programmed as silenceable will activate for
approximately four seconds. If a device on the same initiating device circuit is activated more than once, the
outputs will activate for one second. This alternate timing scheme enables the tester to determine if devices
intended to be installed on a certain initiating circuit are in fact on that circuit. Once an initiating circuit has been
activated, its red LED will flash. All of the red LEDs on the initiating circuit modules will illuminate. The green LEDs
on all Notification Appliance Circuits that are silenceable will illuminate.
Testing Initiating Circuits for Trouble
Inducing a trouble into an initiating circuit will activate all output circuits that are programmed as silenceable. The
outputs will remain activated until the trouble is cleared. After a circuit is tested for trouble, the yellow LED for that
circuit will flash.
Testing Notification Appliance Circuits for Trouble
Inducing a trouble into a notification circuit will activate the particular circuit and pulse the circuit at one second
on/off rate until the trouble is cleared.
Exiting Walk Test
To exit Walk Test, remove the programming key.
NOTE: Fire protection capabilities are removed during walk-test.
58
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 59
Appendix A:
Supply Calculations
Section A.1: The 120VAC Fire Alarm Circuit
The control panel requires connection to a separate dedicated VAC fire alarm circuit, which must be labeled "FIRE
ALARM." This VAC circuit must connect to the line side of the main power feed of the protected premises. No
other equipment may be powered from the fire alarm circuit. The VAC circuit wire run must run continuously,
without any disconnect devices, from the power source to the fire alarm control panel. Overcurrent protection for
this circuit must comply with Article 760 of the National Electrical Code as well as local codes. Use #12 AWG wire
with 600-volt insulation for this circuit.
epyTeciveD
F42-SPVA
CCPB42-SPM1X8.1=8.1
fo#
seciveD
[
]
X0.1=
tnerruC
)spma(
deriuqeRtnerruChcnarBCArofnmuloCmuS
=spma
tnerruClatoT
Table A-1: 120 VAC Fire Alarm Circuit
Use Table A-1 to determine the total amount of current, in AC amps, that the AC service must be capable of
supplying to the system.
The power supply must be capable of powering the system under all operating conditions. Use Table A-2A to
determine power supply loading and verify that the loading is within the limits permitted. Use Table A-2B and A2C to determine secondary (battery) power requirements.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
59
Page 60
S200 System Current Draw Calculation Table
(Table A-2A)
Note: The Primary Power Source Non-Alarm Current and Alarm Current columns of this table are not battery
calculations. They are simply current calculations to confirm that the MPS can supply enough current to support
the system during Primary Non-Fire Alarm and Fire Alarm conditions.
Note: Throughout these current calculation tables, the word "primary" refers to the FACP's primary source of
power, i.e. 120 VAC power. The word "secondary" refers to the FACP's backup batteries (or any other 24 VDC
uninterruptable, regulated power supply listed for Fire Protective Signaling and connected in place of the
batteries).
Part One - Non-Fire Alarm Current (Primary Power Source): This column of Table A-2A allows the user to
calculate the current that will be drawn from the MPS during a non-fire alarm condition, with AC power applied.
This current draw cannot exceed 0.750 amp. This column does not account for current drawn from TB2-3 and TB24 in Non-Fire Alarm conditions which is limited to 0.800 amp, exclusive of the 0.750 amp limit on the Non-Fire
Alarm Current Load. Current drawn from TB2-1 and TB2-2 cannot exceed 0.20 amp at any time and must be
included in the 0.750 amp limit.
Part Two - Fire Alarm Current (Primary AC Power): The second column of Table A-2A allows the system
designer to determine the current load that must be supported by the MPS during a fire alarm condition with
primary power applied. This current drawn during a fire alarm cannot exceed 0.750 amp. This column does not
account for current drawn from TB2-3 and TB2-4 in Fire Alarm which is limited to 2.0 amps exclusive of the 0.750
amp Fire Alarm Load.
Note: Typically, a system should be designed around the capacity to activate all output circuits and relays, and
support fire alarms on no less than 10% of initiating device circuits (subject to the requirements of the Local
Authority Having Jurisdiction (LAHJ).
Concerning 4-wire detectors: In Table A-2A, the current to be entered for 4-wire smoke detectors is the
manufacturer's rated fire alarm current minus the manufacturer's rated non-fire alarm current. The maximum 4wire detector current from TB2-2 is 200 mA.
Concerning notification appliances: The MPS provides a regulated supply for notification appliance circuits,
permitting the use of any 24 VDC notification appliances UL listed for Fire Alarm Systems. The maximum
notification appliance current is 2.0 amps.
Part Three - Non-Fire Alarm Current (Secondary battery power): The last column of Table A-2A allows the
system designer to calculate the secondary non-fire alarm current. This is the current that will be drawn from the
secondary source in a non-fire alarm condition during AC power loss. This figure is required to complete the
standby battery calculations. After adding up all the individual current draws, the total figure is then transferred
to Table A-2C.
1)Current drawn from TB2-1 and TB2-2 cannot exceed 200 mA at anytime.
2)The load on the regulator cannot exceed 750 mA.
3)This table does not account for current drawn from TB2-3 and TB2-4, which is limited to 800 mA in Standby and 2.0 amps in
Alarm, exclusive of the 750 mA limit on the regulator. Standby current from TB2-3 and TB2-4 must be included in Table A-2B.
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
61
Page 62
Maximum Secondary Power Fire Alarm Current Draw
Use Table A-2B to determine the maximum current requirements of secondary power source during fire alarm
conditions. The total obtained in Table A-2B is the amount of current that the batteries must be capable of
supplying. This figure will be used in Table A-2C to determine the size of the batteries needed to support five
minutes of fire alarm operation.
Table A-2B assumes that while in a fire alarm condition, the batteries must feed the main power supply and any
additional supplies (AVPS-24F) with the maximum rated power each supply can provide. Note: Due to the
maximum rating of 9 amps imposed when using PS-12250 batteries, it may be necessary to calculate the exact
requirements of the secondary supply. In that case, add the Secondary Non-Fire Alarm Load obtained in Table
A-2A to the total fire alarm current draw of all Notification Appliances in the system and substitute that figure in
Table A-2B for the Main Power Supply and any additional supplies.
epyTeciveDrebmuNledoM
fo#
seciveD
CCPB42-SPM1X39.2=
tnerruC
)spma(
tnerruClatoT
:seilppuSrewoP
42-SPVA
[
]
X0.3=
=spma
daoLmralAyradnoceSrofnmuloCmuS
Table A-2B: Maximum Secondary Power Fire Alarm Current Draw
Table A-2C: Secondary Power Standby and Fire Alarm Load
1)NFPA 72-1993 Local, Central Station and Proprietary Fire Alarm Systems require 24 hours of standby power followed by five minutes
in alarm. NFPA 72-1993 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby power followed by five minutes
in alarm. Batteries installed in a system powered by a generator need to provide at least four hours of standby power.
2)The total amp hours required cannot exceed 17 AH.
3) Factory Mutual Systems require 90 hours of standby for protection/deluge applications.
62
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Page 63
Calculating battery size needed
Table A-2C sums the standby and alarm loads to
arrive at the battery size, in ampere hours, needed
to support the system. Each MPS has a specific
range of batteries that can be charged properly.
Select batteries that meet or exceed the Total Ampere-Hours calculated and the are within the acceptable charger range:
BatteryVoltage Number Part
SizeRatingRequiredNumber
Canadian installations require the use of modified
modules and annunciators used for supervisory zones.
The modified units have the red LED covered up so that
illumination of this LED under supervisory condition will
not be visible to the user. For more information, refer to
the "Addendum for Canadian Requirements for Supervisory Signals.
Red LED
Yellow LED
Initiating
Zone
Supervisory
covered by label
Zone
Operation:
The Trouble LED (yellow) will flash at one of two rates to distinguish between trouble and supervisory conditions.
Supervisory - fast flash (approximately 160 pulses per minute).
Trouble condition - slower flash (approximately 60 pulses per minute).
Acknowledging the control panel will silence the audible tone and change flashing LEDs to steady operation.
NORMAL STANDBY OPERATION: 1) The green AC POWER indicator must be lit, 2) all alarm (red LEDs) and trouble
indicators (yellow LEDs) should be off.
ALARM CONDITION: Activation of a compatible detector or any normally open fire alarm initiating device will result in the
following action by the Sensiscan 200 control panel: 1) activate alarm notification, control, and signaling outputs as
programmed, 2) light the Red SYSTEM ALARM LED and the associated initiating circuit alarm LED(s), and 3) A steady audible
tone will sound until the alarm is acknowledged or silenced. The controlled outputs will remain activated and the associated
alarm LEDs will flash until the alarm has been silenced or acknowledged, or the system has been reset.
If PRESIGNAL DELAY has been pro-
grammed, the activation of all
able
output circuits will be delayed by
the time marked at right. For Positive
Alarm Sequence (PAS): If the ACKNOWLEDGE or SILENCE keys are
not pressed within 15 seconds of initiation of a first (and only) alarm, output
signals will be activated. Otherwise,
the programmed PAS 1, 2, or 3-minute
time delay will take effect.
ACKNOWLEDGE (SILENCE TONE): Depressing the ACKNOWLEDGE switch will turn the audible tone off and switch
operation of associated LED(s) from flashing to steady. New alarms and/or troubles will resound the audible tone and flash
their associated LED(s).
ALARM SILENCING PROCEDURE: Alarm Notification
Appliance Circuits, control relays and signalling circuits that
have been programmed as silenceable may be silenced by
depressing the SIGNAL SILENCE switch on the CPU control
panel (top left module). Subsequent alarms will reactivate
alarm outputs.
SIGNAL SILENCE should not pressed until it is
determined that an evacuation of the building is not required!
silence-
None selected
❑❑
❑
❑❑
1 Minute
❑❑
❑
❑❑
2 Minutes
❑❑
❑
❑❑
3 Minutes
❑❑
❑
❑❑
PAS 1 Minute
❑❑
❑
❑❑
PAS 2 Minutes
❑❑
❑
❑❑
PAS 3 Minutes
❑❑
❑
❑❑
If ALARM SILENCE has been programmed, all
silenceable output circuits will be shut off after
the time marked at right.
None selected
❑❑
❑
❑❑
5 Minutes
❑❑
❑
❑❑
10 Minutes
❑❑
❑
❑❑
20 Minutes
❑❑
❑
❑❑
❑❑
❑
If SIGNAL SILENCE INHIBIT has
been programmed, Signal Silence will not function for the inhibit time marked at right.
❑❑
❑❑
❑
❑❑
❑❑
❑
❑❑
❑❑
❑
❑❑
None selected
30 Seconds
1 Minute
5 Minutes
ALARM RESET: After locating and correcting the alarm condition, reset the control panel by depressing the SYSTEM
RESET switch on the CPU control panel (top left module).
DISABLE/ENABLE: Refer to the Sensiscan 200 Installation Manual. WARNING: Disabling a circuit will reduce
or eliminate fire protection.
TROUBLE CONDITION: Activation of a trouble signal
under normal operation indicates a condition that requires immediate correction. Carefully note which indicators (LEDs) are illuminated and contact your local
service representative. The audible tone may be silenced by depressing the ACKNOWLEDGE switch,
subsequent trouble(s) will reactivate the audible tone.
Trouble LEDs will continue to display the trouble
condition(s) until the trouble(s) is corrected.
Programmer: Mark the check-boxes above as appropriate. This sheet must be framed and mounted adjacent to control panel.
Local Service Representative
Name:
Company:
Address:
Telephone:
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.