While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so lo-
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
Precau-Lg.p65 01/18/2000
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used
in accordance with the instruction manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which
is designed to provide reasonable protection against such interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
1.3: Controls and Indicators ...............................................................................................................................15
FIGURE 1-3: Display and Keypad ......................................................................................................15
1.5: Digital Communicator.................................................................................................................................16
2.6: Digital Communicator.................................................................................................................................30
2.7: UL Power-limited Wiring Requirements ....................................................................................................31
FIGURE 2-9: Typical Wiring Diagram for UL Power-limited Requirements ....................................31
2.8: Installation of Optional Modules.................................................................................................................32
FIGURE 2-10: Installation of CAC-10F Module ................................................................................32
FIGURE 2-11: Wiring NACs and IDCs for Class A Operation ..........................................................32
FIGURE 2-12: Installation & Wiring of NAC-REM Module .............................................................33
3.1: Entering Program Mode ..............................................................................................................................39
FIGURE 3-1: Control Panel Keypad ...................................................................................................40
3.3: Program Options..........................................................................................................................................40
3.3.1: Level 1 - Main Panel Options ...........................................................................................................40
TABLE 3-1: Zone Functions ...............................................................................................................44
TABLE 3-2: Event Code Changes for ID Contact Format ..................................................................46
FIGURE 4-1: New and Old Keypad/Display.......................................................................................65
4.1: Switch Functions in Normal Mode..............................................................................................................65
4.2: LED Display and Status LEDs ....................................................................................................................67
FIGURE 4-2: Phone Connectors and LEDs.........................................................................................68
4.3.1: Fire Alarm Response.........................................................................................................................69
4.3.2: Fire Alarm Restoral...........................................................................................................................70
4.3.3: System Supervisory Condition Response .........................................................................................70
4.3.4: System Supervisory Restoral Response ............................................................................................70
4.3.12: Fire Drill..........................................................................................................................................73
4.4: Central Station Communications.................................................................................................................74
TABLE 4-1: Format Selection Addresses (16+42) Programming Level 1..........................................75
TABLE 4-2: Format Selection Address Explanation...........................................................................76
5.1: Walk Test Mode ...........................................................................................................................................79
5.2: History Mode...............................................................................................................................................80
TABLE 5-1: History Mode Messages..................................................................................................81
5.3.1: Zones .................................................................................................................................................82
5.3.2: AC Line .............................................................................................................................................83
5.4: Lamp Test ....................................................................................................................................................84
6.2: Downloading Initiated at Control Panel......................................................................................................88
6.3: Downloading Initiated at a Service Terminal..............................................................................................89
6.4: Uploading Initiated at a Service Terminal...................................................................................................89
6.5: Simultaneous Data Transfers.......................................................................................................................90
A.1: Main Power Supply ...................................................................................................................................92
TABLE A-2: Regulated Load in Standby
TABLE A-3: Regulated Load in Alarm
TABLE 6-3: FUNCTION MODES .....................................................................................................118
Document 50193 Rev. E 01/30/02 P/N: 50193:E7
Notes
8
Document #50193 Rev.E 01/30/02 P/N 50193:E
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Central Station Signaling Systems Protected Premises Unit
(Automatic, Manual and Waterflow), Local Fire Alarm Systems and Remote Station Fire Alarm
Systems.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
FCPS-24F Field Charger/Power SupplyDocument #50079
LDM Series Lamp Driver ModulesDocument #50055
LED-10 AnnunciatorDocument #50400
ACM-8RF Annunciator Control Relay Module Document #50362
PK-5210UD ManualDocument #50363
Document #50193 Rev. E 01/30/02 P/N 50193:E
9
MS-5210UD Terminals and Connectors
10
Document #50193 Rev.E 01/30/02 P/N 50193:E
Product Description
CHAPTER 1Product Description
The MS-5210UD is a combination control panel and digital communicator all on one circuit board. It is a 10-zone
panel, which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors,
four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include two Notification
Appliance Circuits (NACs) expandable to four, two programmable Form-A relays (option module with two Form-C
relays can be added), EIA-485 port to interface with remote annunciators and optional remote relay modules plus a
printer port.
The integral communicator transmits system status (alarms, troubles, AC loss, others) to UL-listed central stations via
the public switched telephone network. The control panel has a built-in programmer. It also supervises all wiring,
AC voltage, telephone line input voltage/current and battery level.
The control panel may be programmed or interrogated off site via the public switched telephone network. Any IBM
compatible personal computer with Windows™ 3.1 or greater, with a 1200 baud Hayes™ compatible modem and
Fire•Lite Upload/Download software P/N PK-5210UD, may serve as a Service Terminal. This allows downloading
of any portion or all of the program and upload of any portion or all of the program, history file, walktest data, current
status and system voltages. The MS-5210UDE offers the same features as the MS-5210UD but allows connection to
220/240 VAC input.
Note that unless otherwise specified, the term MS-5210UD shall be used in this manual to refer to both the
MS-5210UD and the MS-5210UDE Fire Control Communicators.
1.1Product Features
• Selectable as Local Fire Panel or Fire Panel/Communicator
• Programmable Zone ID: 2-Wire Smoke; Pull Station; Normally-Open Contact; Supervisory; Supervisory
Auto-resettable; Waterflow (silenceable); Waterflow (nonsilenceable); Remote Switch for Reset, Silence,
Acknowledge and Drill; Standard and Auto-reset Critical and Noncritical Process Monitoring
• 10 Style B (Class B) Initiating Device Circuits (IDCs)
• Two NFPA Style Y (Class B) Notification Appliance Circuits (NACs)
• CAC-10F Option Module to convert all 10 IDCs to Style D (Class A) and convert two Style Y (Class B) NACs
to Style Z (Class A)
• 3.6 amps of system power expandable to 6.6 amps
• Remote Relay Option Module (ACM-8RF) providing one 5.0 amp relay per zone
• Built-in Programmer
• Built-in Voltmeter
• Telephone Line Active LED Indicators
• Communication Confirmation (Kissoff) LED
• Disable report by event
• Programmable Event Codes
• 24 Volt Operation
• Real Time Clock and Calendar
• Trouble Reminder
• Alarm Verification
Document #50193 Rev. E 01/30/02 P/N 50193:E
11
Product Features
• Interfaces with Fire•Lite annunciators (requires LED-10IM Option Module)
LED-10 Series Remote Annunciator provides one red alarm and one yellow trouble LED per zone
LDM-32F Graphic Annunciator
ACS Series LED Annunciators
• Small Size 16.900" (42.9 cm) X 14.500" (36.8 cm) X 4.625" (11.8 cm)
• History File with 256 Event Storage
• Silence Inhibit per Notification Appliance Circuit
• Auto-Silence per Notification Appliance Circuit
• Touchtone/Rotary Dialing per telephone line
• Programmable Make/Break Ratio
• Fuseless Design
• Printer Interface Module (PRT-24)
• NAC-REM Option Module adds two Form-C relays and two Style Z (Class A) NACs
• Print Real-time System Status
• Print History, Walktest Files, Program Contents and Troubleshoot mode voltages
• PK-5210UD Upload/Download Software Kit
• Number of dial attempts (5 minimum, 10 maximum)
• Programmable Zone Delay (waterflow only)
• Low AC Voltage Sense
• One-man silent or audible Walktest
• Optional Dress Panel Coverplate (DP-5210UD)
FIGURE 1-1:
Optional DP-5210UD
12
Document #50193 Rev.E 01/30/02 P/N 50193:E
Product Features
FIGURE 1-2:
MS-5210UD Panel
24 VDC
Power
Tra nsformer
NAC-REM
Expander
Module
Four Character
7-Segment LED
Display
Tra nsformer
Programmable
Relays
Notification
Appliance
Circuits
Class A
Converter
Module
10 Input
Zones
LED-10IM
Interface
Module
Connector
Printer
Interface
Module
Connector
PROM (U14)
Primary &
Secondary
Phone Lines
1
Keypad
Holds up to 12 AH Batteries,
Up to 60 Hrs. of Standby
1
Software for the Fire Control Communicator is located in a PROM inserted in the IC socket labeled U14. The
MS-5210UD and MS-5210UDE each contain unique software. For specific panel software information, refer to the
MS-5210UD/MS-5210UDE Field Software Change Procedure Document #50479.
Document #50193 Rev. E 01/30/02 P/N 50193:E
13
Specifications
1.2Specifications
AC Power - TB1
MS-5210UD: 120 VAC, 60 Hz, 2.3 amps
MS-5210UDE: 220/240 VAC, 50 Hz, 1.2 amps
2
Wire size: minimum #14 AWG (2.0 mm
Battery (lead acid only) - J1
Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour battery (MS-5210UD cabinet holds maximum 12 Amp Hour battery.
Larger batteries require Fire•Lite BB-17F or other UL listed battery cabinet)
Initiating Device Circuits TB5 and CAC-10F Option Module
Detector Zones 1 through 10
Power-limited Circuitry
Operation: All zones NFPA Style B - Convert to Style D using CAC-10F Class A Converter Module
Normal Operating Voltage: 24 VDC (ripple = 100 mV maximum)
Alarm Current: 15 mA
Short Circuit Current: 42 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K, ½ watt (Part #27072 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Fire•Lite Device Compatibility Chart for listed compatible devices.
Total DC current available from this output is up to 500 mA
Power-limited Circuitry. Recommended maximum Standby current is 150 mA
Refer to Fire•Lite Device Compatibility Chart for compatible listed devices
1.3Controls and Indicators
1
Front Panel Switches
RESET
SILENCE
MODE
Up Arrow (ACK)
Down Arrow (ACK)
1st EVENT
ENTER/STORE
Digits 0 through 9
Letters A through F
Displays
Alarm - red LED
Trouble - yellow LED
Supervisory - yellow LED
AC Power - green LED
Four, Seven Segment Displays - red
Primary Phone Line Active - red LED
Secondary Phone Line Active - red LED
'Kissoff' Signal from Central Station - green LED
Silence - yellow LED
Modem - green LED
FIGURE 1-3:
Display and Keypad
Local Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, supervisory and critical process monitoring conditions
1.4Circuits
Input Circuits
Ten input circuits provide Style B (Class B) configuration standard and may be converted to Style D (Class A) by
installing the CAC-10F module. Input circuits may be used as standard fire control panel zones, remote input
switches (Acknowledge, Silence, Drill, Reset) or as standard or auto-resettable critical and noncritical process
monitoring. All ten Initiating Device Circuits accept Normally-Open contact devices and two-wire smoke
detectors.
1. Total current for nonresettable power, four-wire smoke power, and four Notification Appliance Circuits
amps.
Total system current in excess of 3.6 amps requires the XRM-24 Transformer (XRM-24E for 220/240 VAC applica-
tions) and 12 Amp Hour or 18 Amp Hour batteries.
Document #50193 Rev. E 01/30/02 P/N 50193:E
must not exceed 6.0
15
Digital Communicator
Output Circuits
• 24 Volt Resettable Power Output 500 mA
• 24 Volt Nonresettable Power Output 500 mA
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger (up to 18 AH batteries)
•Printer Port
• EIA-485 Port (interfaces to LED-10 Annunciator, AFM Series and LDM Graphic Series Annunciators and
ACM-8RF Remote Relay Module)
Notification Appliance Circuits
Two Notification Appliance Circuits Style Y (Class B) configurable for Style Z (Class A) using the CAC-10F
option module.
Relays
Two dry Form-A relay contacts programmable for system alarm, system trouble, system supervisory (standard
and autoresettable), standard and autoresettable process monitoring or communications failure are provided.
Contacts are rated 2.0 amps @ 30 VDC (resistive). Two additional Form-C relay contacts programmable for
alarm, trouble, standard and autoresettable supervisory, standard and autoresettable process monitoring or communications fail are available using the NAC-REM (NAC/Relay) option module. Contacts are rated 2.0 amps @
30 VDC and 0.6 amps at 125 VAC (resistive).
Printer Port
EIA-232 compatible, fully supervised and programmable for 2400, 4800 and 9600 Baud. Only one printer may
be connected to the port. Consult the factory for recommended printers.
EIA-485 Port
EIA-485 compatible port on the LED-10IM option module supports up to 32 LED-10 Remote Annunciators or 32
sets of ACM-8RF Relay Modules or 32 AFM Series Annunciators or 32 LDM Series Annunciators or any combination of the four devices totalling 32.
Tele phon e Lin es
Fully supervised at all times, voltage is sensed to 4 volts and current is sensed to 5 mA.
Battery Charger
Battery Charger will charge up to 18 AH batteries. The MS-5210UD cabinet holds a maximum of 12 AH batteries. The Fire•Lite BB-17F is required to hold 18 AH batteries. The charger is rated for 850 mA maximum current.
1.5Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the
Primary and Secondary phone lines. Telephone line 'Active' red LEDs are provided as well as a green 'Kissoff' LED.
The integral digital communicator provides the following functions:
16
• Line Seizure - takes control of the phone lines disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone network
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) number - default is Touch-Tone
, programmable to rotary
• For tone burst or touchtone type formats: discern proper 'Ack' and 'Kissoff' tone(s) - the frequency and time
duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
Document #50193 Rev.E 01/30/02 P/N 50193:E
Components
• Communicate in the following formats:
✓
12 Tone Burst Type: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
✓
3 Touchtone Types:
4 + 1 Ademco Express
4 + 2 Ademco Express
Ademco Contact ID (Refer to Table 4-3 on page 78).
1.6Components
Main Circuit Board
The main circuit board contains the system's CPU, power
supply, other primary components and wiring interface connectors. Optional modules plug in and are mounted to the
main circuit board. The main circuit board is delivered premounted in the cabinet.
Cabinet
The cabinet is red with an attractive navy blue front overlay.
The backbox measures 16.900" (42.9 cm) X 14.500"
(36.8 cm) X 4.625"(11.8 cm) and provides space for two batteries (up to 12 Amp Hours). Also available is an optional
dress panel, DP-5210UD, which mounts inside the cabinet.
Transformer Assembly
One 100VA transformer is provided standard
with the panel. An optional 100VA transformer, XRM-24 (XRM-24E for the
MS-5210UDE), is available to provide maximum accessory power.
Batteries
The cabinet provides space for 12 Amp Hour
batteries (larger batteries up to 18 Amp Hour
batteries, use the listed Fire•Lite BB-17F
battery box). Batteries must be ordered separately
Document #50193 Rev. E 01/30/02 P/N 50193:E
FIGURE 1-4:
Standard
Optional
XRM-24(E)
Transformer Assemblies
17
Optional Modules
1.7Optional Modules
LED-10IM
The LED-10IM Interface Module provides an EIA-485 port to support the LED-10 Series Remote Annunciator,
LDM Series Annunciator, ACS Series Annunciator and ACM-8RF Relay Modules. EIA-485 wiring is supervised
for open circuits by this module. The LED-10IM mounts to connector J6 in the upper right corner of the main
board. Refer to Figure 2-14, “LED-10IM Installation,” on page 35.
ACM-8RF Relay Module
The ACM-8RF option module provides eight Form-C relays rated a 5.0 amps each. The Relay Module connects
to the EIA-485 port off of the LED-10IM option module. Relays are assigned to each of the 10 Initiating Device
Circuits. Refer to Figure 2-17, “Wiring LED-10IM to ACM-8RF,” on page 36, for additional information.
PRT-24 Printer Interface Module
The Printer Interface Module may be used to connect a printer to the control panel for the purpose of printing a
history report, walktest file, troubleshoot report, program entries or current system status. Printers require separate external primary power. Connect the PRT-24 module (with cable) to the serial EIA-232 port on the printer.
The module mounts to the J4 connector on the main circuit board.
Note that an EDP listed printer must be used if printer will be permanently attached (Refer to Figure 2-13,
“Remote Printer Connections,” on page 34). The Baud rate is programmable (“Program Options” on page 40).
CAC-10F Module
The CAC-10F Module can be used to convert the 10 Style B (Class B) Initiating Device Circuits to 10 Style D
(Class A) IDCs and the two Style Y (Class B) Notification Appliance Circuits to two Style Z (Class A) NACs.
The CAC-10F module connects to J10 on the main circuit board. (Refer to Figure 2-10 on page 32).
NAC-REM Module
The NAC-REM (NAC/Relay) Module can be used to add two Style Z (Class A) NACs and two Form-C relays.
The module connects to J7 on the main circuit board. (Refer to Figure 2-12 on page 33).
1.8Optional Accessories
Dress Panel
A red dead-front dress panel (DP-5210UD) is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel.
Battery Box
The Fire•Lite BB-17F battery box may be used to house
two batteries greater than 12 Amp Hour to a maximum of
18 Amp Hour. The battery box mounts directly below the
cabinet, centered to the main circuit board (Refer to Figure
2-2, “FACP Backbox and Battery Box,” on page 25). The
BB-17F is red and is provided with knockouts.
FIGURE 1-5:
BB-17F Battery Box
PK-5210UD Program Kit
The PK-5210UD Program Kit includes three 3½" diskettes plus Instruction Manual P/N 50363. When the software is loaded into an IBM compatible computer, it creates an off-line Service Terminal that allows any
MS-5210UD panel to be uploaded or downloaded over standard telephone lines. Requires panel firmware P/N:
MS52102.0 or greater.
18
Document #50193 Rev.E 01/30/02 P/N 50193:E
Optional Accessories
LED-10 Series Annunciator (LED Zone Type Annunciator)
The LED-10 Series is a 10 zone LED annunciator which mounts on a 3-gang electrical box and provides LED
indication of the following:
• Alarm Zones 1 through 10
• Trouble Zones 1 through 10
• AC Power (green)
• System Alarm (red)
• System Trouble (yellow)
• System Supervisory (yellow)
• Alarm Silence (yellow)
FIGURE 1-6:
LED-10 Series Annunciator
A local trouble sounder and switches for remote Acknowledge, Silence, Drill and Reset are also provided. Wiring is
inherently supervised by the FACP. Slide-in paper labels
permit an easy change of zone information. DIP switches
allow the enabling and disabling of the local piezo sounder
(with approval of local AHJ), enabling and disabling of the
mechanical keyswitch which may be used to prevent unauthorized use of the function switches and selection of
annunciator receive/transmit mode (Refer to Figure 2-15 on
page 35).
Note that the LED-10 Series Remote Annunciator requires the use of the LED-10IM Interface Module.
ACS Series Annunciators (LED Zone Type)
The ACS Series Annunciators remotely display system status. The annunciators display zone alarm and trouble
status. In addition, they provide remote Acknowledge, Silence, Reset and Drill functions. The ACS Series
Annunciators require the use of the LED-10IM Interface Module. For more detailed information, refer to the
appropriate annunciator manual.
ACM-16ATF - The Annunciator Control Module-16ATF
✓
FIGURE 1-7:
ACM-16ATF
contains 16 red alarm and 16 yellow trouble LEDs, a system trouble LED, an ON LINE/POWER LED and a local piezo sounder
with switches for Acknowledge, Silence, Reset and Drill. The
ACM-16ATF has rotary address switches and will accept up to 3
AEM-16ATF Expanders. The ACM-16ATF can be mounted in a
Fire•Lite ABS-1F or ABF-1F backbox. Refer to the
ACM-16ATF Manual for detailed information. Note that only
one ACM-16ATF is required to annunciate 10 zones of alarm and
trouble, provided '8 Point Shift' function is selected. Refer to
Annunciator Manual P/N 51480 for additional information.
AEM-16ATF - The Annunciator Expander Module-16ATF con-
✓
nects to the ACM-16ATF and adds 16 sets of red alarm LEDs and
yellow trouble LEDs. Up to three AEM-16ATFs may be added to
an ACM-16ATF but only one is required. Note that one
AEM-16ATF is required with an ACM-16ATF to annunciate 10
zones of alarm and trouble as well as general system status provided '8 Point Shift' function is not selected. Refer to Annunciator
Manual P/N 51480 for additional information.
Document #50193 Rev. E 01/30/02 P/N 50193:E
19
Optional Accessories
AFM-16ATF - The Annunciator Fixed Module-16ATF
✓
contains 16 red alarm and 16 yellow trouble LEDs, a
system trouble LED, an ON LINE/POWER LED and a
local piezo sounder with switches for Acknowledge,
Silence, Reset and Drill. The AFM-16ATF is fixed at
address '1' and communication is via the EIA-485 data
line. The AFM-16ATF can be mounted in a Fire•Lite
ABS-1F or ABF-1F backbox. Refer to the AFM-16AT
Manual for detailed information.
AFM-16AF - The Annunciator Fixed Mod-
✓
ule-16AF has 16 red alarm LEDs. Multiple
annunciators may be used by setting all annunciators to Receive Only, except the last AFM-16AF
in line. Each annunciator's address is internally
fixed at '1' and communication is via the EIA-485
data line. The Local Silence/Acknowledge
switch functions as local lamp test and silence for
annunciator piezo. LEDs include On-Line and
System Trouble indicators. The AFM-16AF
Annunciator can be mounted in a standard 4gang electrical box. Refer to the AFM-16AF
Manual for detailed information.
FIGURE 1-8:
FIGURE 1-9:
AFM-16ATF
AFM-16AF
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power
and control for a maximum of three expander modules (expander modules are not required when interfacing to the
MS-5210UD). The LDM-32F and LDM-E32F have output connectors which are used to drive lamps or LEDs
and input connectors which are used for remote switch functions. The LDM Series requires the use of the
LED-10IM Interface Module. Refer to the LDM Series Lamp Driver Modules Manual for a complete description.
Refer to Figure 2-18, “Wiring LED-10IM to LDM-32F,” on page 37 for wiring details.
LDM-32F - The Lamp Driver Module has 32
✓
FIGURE 1-10:
LDM-32F Module
alarm lamp/LED driver outputs which sink current to system common (-) on activation. A single positive (+) voltage is required to supply total
operating power for all lamps or LEDs when all
drivers are activated. The LDM-32F provides a
separate driver for system trouble and inputs for
a local lamp test switch. A maximum of 16
external control switches may be wired to the
LDM-32F. DIP switch SW3 is used to enable or
disable the onboard piezo sounder, enable remote
switch functions, select a flashing LED function
for new alarms and troubles and other functions.
Switch SW4 is used to configure the module to
annunciate 32 alarms or 16 alarms and 16 troubles. A green ON-LINE LED flashes to indicate
ongoing communications with the host FACP.
One LDM-32F supports up to three LDM-E32F
modules. The LDM-32F is supplied with four
standoffs and screws for mounting to a CHS-4L
chassis or custom backbox.
20
Document #50193 Rev.E 01/30/02 P/N 50193:E
Optional Accessories
FCPS-24F(E) Remote Power Supply (System Power Expansion)
The FCPS-24F (FCPS-24FE for 220/240 VAC applications) is a compact, remote power supply and battery
charger. This remote power supply consists of a filtered 24 VDC output that may be configured to drive up to four
Notification Appliance Circuits [four Style Y (Class B) or two Style Z (Class A) and two Style Y (Class B)].
Alternately, the four Notification Appliance Circuits may be used as auxiliary regulated power configured for
resettable or nonresettable operation.
The FCPS-24F(E) may be used in a number of different applications. It may be used as a remotely mounted power
supply and battery charger powering up to four, coded or noncoded, Notification Appliance Circuits. Alternately,
any or all of these circuits may be used as 24 VDC output circuits capable of powering four-wire smoke detectors
or any device that requires filtered power. These circuits may be configured as resettable or nonresettable outputs
to expand FACP auxiliary system power.
FIGURE 1-11:
FCPS-24F(E)
Notification Appliance Circuit
Control Input #1 (from FACP)
Notification Appliance Circuit
Control Input #2 (from FACP)
Style Y/Style Z Notification Appli-
ance Circuit or 24 VDC Output #1
Style Y Notification Appliance
Circuit or 24 VDC Output #2
Style Y/Style Z Notification Appli-
ance Circuit or 24 VDC Output #3
Style Y Notification Appliance
Circuit or 24 VDC Output #4
AC Power
Specific Application
Powe r
FCPS Trouble
Contact Output
Battery Charger
One of the most common applications for the FCPS-24F(E) remote power supply utilizes the NAC expander
mode. In this application, one or two Notification Appliance Circuits (NACs) are connected from the main FACP
NAC output(s) to the remote power supply Control Input circuits. When these Control Input circuits activate (due
to reverse polarity of the NAC output), the power supply will activate its corresponding outputs. NAC Control
Input #1 controls power supply output circuits #1 and #2. NAC Control Input #2 controls output circuits #3 and
#4.
During the inactive state, the remote power supply supervises its NAC field wiring for short and open circuits. If
a fault is detected, the supply will enter a trouble condition and illuminate the corresponding NAC trouble LED
(Output Circuits 1-4), however, once the Notification Appliance Circuits are activated, the supervision is disabled
and the circuits are no longer supervised. Supervision of other power supply faults such as low battery, Earth
Fault, AC loss and battery charger failure will continue and may be monitored via the independent trouble relay
contact.
If a specific application requires that all four outputs activate at the same time, only one NAC control input from
the FACP is necessary. For this application, The Notification Appliance Circuit from the FACP is wired into NAC
Control Input #1 of the remote supply and then a pair of wires are connected from NAC Control Output #1 to NAC
Control Input #2. Refer to the FCPS-24F(E) Installation, Operation and Application Manual for a complete
description and examples of applications.
Document #50193 Rev. E 01/30/02 P/N 50193:E
21
Telephone Requirements and Warnings
1.9Telephone Requirements and Warnings
1.9.1 Telephone Circuitry:
Ringer Equivalence Number (REN) = 0.6B
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.
1.9.2 Digital Communicator:
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Manufacturer:Fire•Lite
One Fire-Lite Place
Northford, CT 06472
Product Model Number: MS-5210UD
FCC Registration Number: 1W6USA-74525-AL-E
Ringer Equivalence: 0.6B
Note: The FCC ID label is located on the inside of the FACP door.
1.9.3 Telephone Company Rights and Warnings:
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this control panel. The telephone
company, however, is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided, except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
22
Document #50193 Rev.E 01/30/02 P/N 50193:E
Installation
CHAPTER 2Installation
2.1Mounting Options
The cabinet may be either semi-flush or surface mounted. The door
is removable during the installation period by opening and lifting the
door off the pin hinges. The cabinet mounts using two key slots and
two additional 0.250" (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two
securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount
the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible
with sufficient room to easily install and maintain the panel. Locate
the top of the cabinet approximately five feet above the floor with the
hinge mounting on the left. Determine the number of conductors
required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s)
and pull the required conductors into the box. Note that there are no
knockouts on the left (hinged) side of the cabinet. All wiring should
be in accordance with the National and/or Local codes for fire alarm
systems.
2.2Backbox Mounting
✓
Open the door and lift the door off the pin hinges.
✓
Remove the main PC board assembly by unscrewing the four screws in the corners of the board. Set the
board aside in a safe, clean place. Avoid static discharge which may damage the board.
✓
Mark and predrill holes for the top two keyhole mounting bolts using the dimensions illustrated in
Figure 2-1.
✓
Install two upper fasteners in the wall with the screw heads protruding.
✓
Using the upper 'keyholes', mount the backbox over the two screws.
✓
Mark and drill the lower two holes.
✓
Mount backbox, install remaining fasteners and tighten.
✓
When the location is dry and free of construction dust, reinstall the main PC board.
Document #50193 Rev. E 01/30/02 P/N 50193:E
23
Backbox Mounting
Draw wires through the respective knockout locations.
FIGURE 2-1:
Left Side
(3.81 cm)
1.50“
1.62“
(4.115 cm)
Back
of
Box
Cabinet Dimensions and Knockout Locations
2.00"
(5.08 cm)
2.00"2.00"2.00"2.00"
14.5"
11.5"
(3.81 cm)
(3.81 cm)
(3.14 cm)
Hinges
1.50“
1.50“
1.235"
11.062"
(28.10 cm)
4.445 cm
1.75“
2.00"
To p
(36.83 cm)
(29.21 cm)
4.445 cm
1.75“
(42.926 cm)
16.9“”
Back
of
Box
Right Side
(3.81 cm)
1.50“
(4.115 cm)
1.62“
1.62“
(4.115 cm)
1.50“
(3.81 cm)
(3.81 cm)
4.6“
(11.68 cm)
Hinge
1.50“
1.58“
1.75“
(4.445 cm)
11.5“
Back of Box
Bottom
(29.21 cm)
1.75“
(4.445 cm)
4.5“
Back
of
Box
(11.43 cm)
24
Document #50193 Rev.E 01/30/02 P/N 50193:E
Backbox Mounting
FIGURE 2-2:
FACP Backbox and Battery Box
TR-4-R
Optional BB-17F
When batteries larger than 12 Amp Hour are being used, the BB-17F battery box (or equivalent) must be installed. To
install the BB-17F:
Mount the FACP cabinet to the wall.
1.
Remove knockouts on the bottom of the FACP cabinet and top of the BB-17F.
2.
Using conduit, hang the BB-17F from the FACP cabinet making sure there is at least ½" of clearance between
3.
the two cabinets.
Anchor the BB-17F to the wall.
4.
Document #50193 Rev. E 01/30/02 P/N 50193:E
25
Operating Power
2.3Operating Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power
!
before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules
or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the MS-5210UD is
120 VAC, 60 Hz, 2.3 amps and for the MS-5210UDE is 220/240 VAC, 50 Hz, 1.2 amps. Run a pair of wires (with
ground conductor) from the protected premises main breaker box to TB1 of the main circuit board. As per the
National Electric Code, use 14 AWG (2.00 mm
equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and
may not contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper
panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00
2
)] to one of the transformer mounting studs. Do not use conduit for the Earth Ground connection since this does
mm
not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J1 on the main circuit board using the
plug-in connector and cable provided. The battery charger is current-limited and capable of recharging sealed lead
acid type batteries. The charger shuts off when the system is in alarm or if the battery voltage drops too low (below
17.4 VDC). See “Battery Calculations” on page 91 for calculation of the correct battery rating.
2
, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics.
!
If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate
medical attention.
FIGURE 2-3:
Operating Power Connections
Connect Earth Ground Wire to
Transformer mounting stud
26
Document #50193 Rev.E 01/30/02 P/N 50193:E
Input Circuits
2.4Input Circuits
The control panel has 10 zone input circuits. The maximum loop resistance limit for each input circuit is 100 ohms.
All field wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly
annunciated as well as communicated to a central station.
Each zone is a Style B (Class B) Initiating Device Circuit (IDC) designed to accept any Normally-Open contact
device and conventional 2-wire, 24 volt smoke detectors. Refer to Figure 2-4, “Style B Initiating Device Circuit Connections,” on page 28, for information on wiring Style B circuits. Use the CAC-10F Option Module (Refer to Figure
2-11, “Wiring NACs and IDCs for Class A Operation,” on page 32) to convert all 10 circuits to Style D (Class A).
Each zone is power-limited to 7.26 mA in standby and 42 mA in alarm.
The zones may be programmed as shown below. The factory default is 2-wire smoke detector for all zones:
• 2-wire Smoke Detector (factory default)
• Pull Station
• Normally-Open Contact Device(s)
• Supervisory
• Supervisory, auto-resettable
• Waterflow, silenceable
• Waterflow, nonsilenceable
• Reset
• Silence
• Drill
•Acknowledge
• Auto-resettable critical and noncritical process monitoring
• Critical and noncritical process monitoring
A maximum of five waterflow devices may be used on any circuit programmed as a waterflow zone per NFPA 72.
Four-wire smoke detectors may be connected to any zone. Resettable power is provided via TB2 Terminals 3 and 4.
Refer to the Fire•Lite Device Compatibility Document for a list of compatible smoke detectors.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any
zone. This is not recommended, however, since specific and detailed reports will not be possible (particularly critical
when using Contact ID format). For example, the report of general fire alarm versus pull station fire alarm or smoke
detector fire alarm could not be distinguished.
Note that Process Monitoring
refers to circuits which do not specifically tie into elements of the fire system as defined
by NFPA codes. With the exception of burglary functions, process monitoring circuits could be used to monitor any
nonfire functions such as water temperature, room temperature, door open/closed, gas leakage, chemical leakage, etc.
Process Monitoring may be accomplished for Local, Remote and Central Station type services in the following ways:
• Central and Remote Station - When a critical process is detected, the DACT will transmit the critical process
alarm to the Central or Remote Station.
• Local - When a critical process is detected, the relays (fail-safe) programmed to transfer will deenergize. The
ACM-8RF Remote Relay Module can only be used with noncritical process monitoring.
Document #50193 Rev. E 01/30/02 P/N 50193:E
27
Output Circuits
FIGURE 2-4:
UL listed compatible 2-wire smoke detector
Style B Initiating Device Circuit Connections
Style B (Class B) Initiating Device Circuit (supervised and power-limited).
Heat Detector
½watt, P/N: 71252 UL listed.
4.7K,
UL listed compatible 2-wire smoke detector
Manual Pull StationManual Pull Station
Heat Detector
Dummy Load all unused circuits (P/N: 71245)
2.5Output Circuits
DC Power Output Connections
All DC power outputs are power-limited.
FIGURE 2-5:
Tele phon e Circui ts
Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 (Primary) and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage
of an RJ31X style interconnection. Refer to Figure 2-8, “Wiring Phone Jacks,” on page 30.
Auxiliary Power Connections
Nonresettable Power (500 mA)
24 VDC filtered, regulated, nonresettable power can be obtained
from TB2 Terminals 1(+) and 2(-).
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, regulated, resettable power
for 4-wire smoke detectors can be obtained
from TB2 Terminals 3(+) and 4(-)
28
Document #50193 Rev.E 01/30/02 P/N 50193:E
Output Circuits
Notification Appliance Circuits
The MS-5210UD provides two Notification Appliance Circuits standard as Style Y (Class B). Each circuit is
capable of 3.0 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
3.6 amps with the standard transformer, 6.0 amps if an optional XRM-24 Transformer (XRM-24E for the
MS-5210UDE) is installed. Circuits are supervised and power-limited. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.
All Notification Appliance Circuits may be programmed as follows:
• Silenceable
• Enabled/Disabled
• Auto Silence, 5 to 30 minutes
• Nonsilenceable
• Silence Inhibited
• March Time, Temporal or California rates.
FIGURE 2-6:
Notification Appliance Circuit Connections
Style Y (Class B) Notification Appliance Circuit (supervised and power-limited).
Polarized Horn
Polarized Horn
Note: Notification Appliance Circuit polarity
shown in alarm
state.
4.7K ohm,
½ watt. {/N: 71252 UL listed
Polarized BellPolarized Bell
Polarized Horn
Polarized Horn
Dummy Load all unused circuits (P/N: 71245)
Standard Relays
The control panel provides two Form-A relays rated for 2.0 amps @ 30 VDC (resistive). Two Form-C relays can
be added by installing the optional NAC-REM (NAC/Relay) module.
FIGURE 2-7:
Programmable Relay Terminals
Relay connections may be power-limited or nonpower-limited, provided that a minimum of
0.25" is maintained between conductors of power-limited and nonpower-limited circuits.
Relays automatically change to
Normally Closed (energized)
when programmed for activation
on Trouble.
Document #50193 Rev. E 01/30/02 P/N 50193:E
29
Digital Communicator
2.6Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line control/command is made
possible via double line seizure as well as usage of an RJ31X style interconnection. It is critical that the panel's dig-
ital communicator be located as the first device on the incoming telephone circuit to properly function.
The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone
lines is required as shown in Figure 2-8.
FIGURE 2-8:
Wiring Phone Jacks
Primary Lines - Incoming
Telco Phone Lines
Green Wire
Tip
Red Wire
Ring
Green Wire
Tip
Red Wire
Ring
To premise phonesTo premise phones
Tip
Ring
Secondary Lines - Incoming
Telco Phone Lines
Ring
Tip
Note: Shorting bars
inside RJ31X Jack
removed during male
plug insertion
7 foot (2.13 m)
cables (MCBL-7)
not supplied -
order separately
30
Primary Phone Line PH1
Modular
Secondary Phone Line PH-2
Female
Connectors
Male Plug Connectors
Document #50193 Rev.E 01/30/02 P/N 50193:E
UL Power-limited Wiring Requirements
2.7UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all
power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or
conduits. A typical wiring diagram for the MS-5210UD is illustrated in Figure 2-9.
FIGURE 2-9:
Power-limited Circuit
Note that power-lim-
ited wiring is con-
nected to terminal
block below the
installed circuit board
Typical Wiring Diagram for UL Power-limited Requirements
Nonpower-limited
Circuits
Power-limited Circuits
Power-limit ed
Circuit
AC Power
Document #50193 Rev. E 01/30/02 P/N 50193:E
31
Installation of Optional Modules
2.8Installation of Optional Modules
CAC-10F Class A Converter Module
The CAC-10F Module can be used to convert the 10 Style B (Class B) Initiating Device Circuits to 10 Style D
(Class A) IDCs and the two Style Y (Class B) Notification Appliance Circuits to two Style Z (Class A) NACs. J1
of the module plugs into connector J10 of the MS-5210UD, which is located at the top center of the FACP main
circuit board.
Install the two supplied metal standoffs in the holes on the main circuit board (refer to Figure 2-10). Carefully
align the two connectors and press the CAC-10F module securely into place. Make certain the pins are properly
aligned to prevent bending or breaking of any pins. Secure the CAC-10F module to the standoffs using the two
supplied screws. It is important that the supplied screw and washer be used to secure the module to the metal
standoff. This is necessary in order to help protect against electrical transients.
FIGURE 2-10:
Installation of CAC-10F Module
metal standoff
J1 - on back of module
metal standoff
Wire the Style Z (Class A) Notification Appliance Circuits (NACs) using TB4 of the MS-5210UD and TB1 of the
CAC-10F module. Wire the Style D (Class A) Initiating Device Circuits (IDCs) using TB5 of the MS-5210UD and
TB2 of the CAC-10F module. Make certain to observe polarity when connecting the devices to the circuits. The B+
and A+ terminals must comprise the feed and return for the positive side of a device and the B- and A- terminals must
comprise the feed and return for the negative side of a device. To configure any of the zones for Class B when the
CAC-10F is installed, simply wire to the B+ and B- inputs on TB5 of the main circuit board and install the EOL resistor across the end of the circuit. Do not wire to the corresponding A+ and A- terminals on TB2 of the CAC-10F module. Refer to Figure 2-10 and Figure 2-11.
FIGURE 2-11:
Wiring NACs and IDCs for Class A Operation
32
Document #50193 Rev.E 01/30/02 P/N 50193:E
All unused terminals
must be jumpered.
Jumper A+ to B+ and
A- to B-.
Installation of Optional Modules
NAC-REM (NAC/Relay Expander Module)
The NAC-REM Module can be used to add two Style Y (Class B) or Style Z (Class A) NACs (1.5 amps maximum
each) and two Form-C relays to the MS-5210UD. Connector J1 of the NAC-REM module plugs into connector J7
which is located at the top left corner of the MS-5210UD main circuit board.
Install the two supplied metal standoffs into the FACP main circuit board. Ensure that the metal standoff is
installed in the position indicated in Figure 2-12. Carefully align the two connectors and press the NAC-REM
module securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any pins.
It is important that the supplied screw and washer be used to secure the module to the metal standoff. This is necessary in order to help protect against electrical transients.
FIGURE 2-12:
Installation & Wiring of NAC-REM Module
NAC #3
Style Z (Class A) supervised and power-limited.
NAC #4
Style Y (Class B) supervised and power-limited.
4.7K ohm,
½ watt Part #71252 UL listed.
PRT-24 Printer Interface Module
A remote printer may be permanently or temporarily connected to provide a hardcopy printout of normal current
system status and activity, program entries, history file, troubleshoot mode voltages and walktest data. The
PRT-24 provides an EIA-232 conversion to adapt to most 40 and 80 column printers.
!
CAUTION: DO NOT connect a printer to the Fire Alarm Control Communicator if a
panel. Circuit damage may result
Metal Standoff
.
Document #50193 Rev. E 01/30/02 P/N 50193:E
ground fault exists on the
33
Installation of Optional Modules
Installation - Remote printers require a separate external primary power source. Also required is the
PRT-24 which includes the Printer Interface Module and a 6-foot (1.83 m) interface cable prewired to
a DB25 connector. Connect the interface cable to the PRT-24 as illustrated in Figure 2-13. Insert the
two supplied standoffs into mounting holes near the J4 connector on the main circuit board. Connect
the Printer Interface board to J4 on the main circuit board, press onto standoffs and connect the
attached cable to the serial EIA-232 port on the printer. The printer may be placed a maximum of 50
feet (15.24 m) from the panel. Note that a ground fault may occur on the control panel when this connection is made. For this reason, it is important that there be no preexisting ground fault on the panel.
For permanent printer connection, a ground fault is not allowed.
Printer Configuration - The PRT-24 is required. Also refer to the documentation supplied with your
printer. Set the printer's options as listed in Table 2-1 . Baud rate is programmable to 2400, 4800 or
9600.
FIGURE 2-13:
TAB LE 2- 1:
Printer Settings
Typical Printer
Under the MENU area:
COMMUNIC. SETUP:
DATA BITS:7
PAR IT Y:EV EN
STOP BIT:1 STOP
BAUD RATE:MUST MATCH FACP SETTING
Remote Printer Connections
J1 located on back of PRT-24 board
34
DB-25P Front View
PRT-24 connection to main board
Document #50193 Rev.E 01/30/02 P/N 50193:E
Installation of Optional Modules
LED-10IM - EIA-485 Interface Module
The LED-10IM Interface Module provides an EIA-485 port to support the LED-10 Series Remote Annunciator,
LDM Series Annunciator, AFM Series Annunciator and the ACM-8RF Relay Module and supervises the EIA-485
wiring for open circuits. The LED-10IM mounts to connector J6 in the upper right corner of the main board.
Install the two supplied standoffs into the FACP main circuit board. Ensure that the metal standoff is installed in
the position indicated in Figure 2-14. Carefully align the two connectors and press the LED-10IM module
securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any pins. It is
important that the supplied screw and washer be used to secure the module to the metal standoff. This is necessary
in order to help protect against electrical transients.
FIGURE 2-14:
LED-10IM Installation
metal standoff
LED-10 Series Remote LED Annunciator
The LED-10 Series Annunciator connects to the MS-5210UD via the LED-10IM Interface Module. It is recommended that overall foil/braided-shielded, twisted pair cable with a maximum length of 6,000 feet (1,800 m) @ 18
AWG (0.75 m m
2
) be used. Regulated power can be supplied by the MS-5210UD or a remote UL listed filtered,
regulated power supply such as the Fire•Lite FCPS-24.
FIGURE 2-15:
Wiring LED-10IM to LED-10 Series
Top V iew
LED-10 Series Annunciator
Earth Ground
-24 VDC
+24 VDC
+ EIA-485
-
Earth
Ground
- 24 VDC
+ 24 VDC
Shield
Document #50193 Rev. E 01/30/02 P/N 50193:E
LED-10 Series Annunciator
LED-10IM
35
Installation of Optional Modules
ACM-8RF Remote Relay Module
FIGURE 2-16:
ABS-8R Enclosure
The ACM-8RF Module provides eight Form-C relays with contacts rated for
5.0 amps. Relays can be assigned to each of the ten Initiating Device Circuits (two ACM-8RF relay modules are required). The module is installed
on the EIA-485 line using the LED-10IM Interface Module. Communication
wiring is supervised by the FACP. Power for the module must be
power-limited. Refer to the ACM-8RF Manual for UL power-limited wiring
requirements and switch SW4 receive/transmit selection option.
Removable terminal blocks are provided for ease of installation and
servicing. DIP switch SW3 allows assignment of relays to FACP IDCs. The
ACM-8RF module can be mounted remotely in an ABS-8RF annunciator
surface-mount backbox.
ACM-8RF Address and SW3 DIP Switch Settings - Each of the ten
MS-5210UD IDCs can be assigned to an ACM-8RF relay. Two relay modules are required, with both set to the
same address. Use the decade rotary switches to set the address (i.e. for address '01', position the first [left] switch
so the arrow points to '0' and the second [right] switch so the arrow points to '1'). “Level Three - Option Module
Selections” on page 60, Annunciator Maximum Monitored Address (02-03).
✓
To assign the first eight relays of the first ACM-8RF Relay Module to FACP IDCs 1 through 8, set
ACM-8RF SW3 DIP switches 2 and 5 ON and 1, 3, 4, 6, 7 and 8 OFF.
✓
To assign the first two relays of the second ACM-8RF Relay Module to FACP IDCs 9 and 10, set
ACM-8RF SW3 DIP switches 3 and 5 ON and 1, 2, 4, 6, 7 and 8 OFF.
FIGURE 2-17:
Wiring LED-10IM to ACM-8RF
ACM-8RF
NO
C
NC
To Next Device
Power-limited 24 VDC
IN (-) OUT
(-) OUT
(+) IN (+)
SYS COM
SYS COM
24 VDC
24 VDC
EARTH
Left
Decade
Switch
Right
Decade
Switch
36
LED-10IM
Document #50193 Rev.E 01/30/02 P/N 50193:E
Installation of Optional Modules
LDM-32F Lamp Driver Module
The Lamp Driver Module is used to provide an interface to a custom graphic annunciator. The LDM-32F has 32
alarm lamp/LED driver outputs which sink current to system common (-) on activation. A single positive (+) voltage is required to supply total operating power for all lamps or LEDs when all drivers are activated. The
LDM-32F provides a separate driver for system trouble and inputs for a local lamp test switch. A maximum of 16
external control switches may be wired to the LDM-32F. DIP switch SW3 is used to enable or disable the onboard
piezo sounder, enable remote switch functions, select a flashing LED function for new alarms and troubles and
other functions. A green ON LINE LED flashes to indicate ongoing communications with the host FACP. The
LDM-32F is supplied with four standoffs and screws for mounting to a CHS-4L chassis or custom backbox.
The LDM-32F is installed on the EIA-485 line using the LED-10IM Interface Module. Communications wiring is
supervised by the FACP. Power for the module must be power-limited.
LDM-32F Switch Settings - Use the decade rotary switches to set the address (i.e. for address '02', position switch
SW1 [top] so the arrow points to '2' and switch SW2 [bottom] so the arrow points to '0').
FIGURE 2-18:
Wiring LED-10IM to LDM-32F
To Next Device
+
EIA-485
-
LED-10IM
-
+
Power-limited
24 VDC Source
Document #50193 Rev. E 01/30/02 P/N 50193:E
LDM-32F
37
Installation of Optional Modules
ACM-16ATF and AFM-16ATF Annunciators
The Annunciator Control Modules-16ATF and 16ATF each contain 16 red alarm and 16 yellow trouble LEDs, a
system trouble LED, an ON LINE/POWER LED and a local piezo sounder with switches for FACP Acknowledge, Silence, Reset and Drill. The ACM-16ATF has rotary address switches and is installed on the EIA-485 line
using the LED-10IM Interface Module.
AFM-16AF Annunciator
The Annunciator Fixed Module-16AF has 16 red alarm LEDs. The annunciator address is fixed at '1' and communication is via the EIA-485 line using the LED-10IM Interface Module. The Local Silence/Acknowledge
switch functions as a local lamp test and silence for the annunciator piezo sounder. LEDs include ON LINE/
POWER and System Trouble.
FIGURE 2-19:
Wiring LED-10IM to ACM-16ATF
To Next Device
-
EIA-485
+
38
-
+
Po we r -l im i te d
24 VDC Source
LED-10IM
Document #50193 Rev.E 01/30/02 P/N 50193:E
Programming Instructions
CHAPTER 3Programming Instructions
This section describes programming the panel from the onboard keyboard or the remote site upload/download software which allows programming the control panel off premises. Programming of the control panel is possible at any
time except when an alarm condition is present or during a fire drill.
The control panel has been designed for many different types of applications. After examining your specific application, review the programming options and choose the entries best suited for your system.
The control panel has a built-in intelligent programmer. All programming selections are stored in nonvolatile Electrically-Erasable Programmable Read-Only Memory (EEPROM). This ensures that the control panel will remember all
entries made in programming mode even if both AC and battery power are removed. Invalid entries cause a 'beep'
from the onboard piezo sounder.
The user must program the primary and secondary phone numbers, account numbers and 24 hour test report times for
each central station account and the current time and date. The control panel comes with factory chosen options/features already programmed. Other options/features may be programmed if desired. If all factory default settings are
acceptable, programming is complete.
Successful entry into Program Mode from the keypad shuts off the fire protection and places the panel into trouble. A
'system off normal' message is transmitted to the central station. Programming via the PK-5210UD upload/download
software is accomplished with the fire protection active/on.
3.1Entering Program Mode
Program Mode is divided into four levels:
Main Panel Options
1.
Event Codes/Transmission Formats
2.
Option Module Selections
3.
Upload/Download
4.
Each level of Program Mode is entered by pressing the MODE key and then keying in the program mode entry code
(7764) and pressing the [ENTER/STORE] key.
7764 spells PROG on a Touch-Tone phone
☛
If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key. Note that as
information is entered into the control panel, the digits will scroll across the display from right to left:
---7
--77
-776
7764
You are allowed a pause of up to 10 seconds in between each number while entering the code. After pressing the
[ENTER/STORE] key, the control panel will be in Program Mode and will display P--1, with the 1 flashing. If the
[ENTER/STORE] key is pressed, Level 1 (Main Panel Options) will be selected for programming. If Level 2 (Event
Codes/Transmission Formats), Level 3 (Option Module Selections) or Level 4 (Upload/Download) is keyed in and
then the [ENTER/STORE] key pressed, the corresponding Level will be selected for programming. You are allowed
up to ten minutes of idle time at this point before starting your programming, otherwise, the control panel will return
to Normal Mode. You also have a maximum of 10 minutes between any key stroke. All entries made prior to the 10
minute time-out are valid and are stored.
®
Document #50193 Rev. E 01/30/02 P/N 50193:E
39
Switch Functions
Once in any of the four levels of the Programming Mode, the control panel will:
• Blink the Trouble LED
• Activate the trouble relay
• Disable the Notification Appliance Circuit(s)
• Disable the alarm relay
•Display 00_F
• Ignore all other keys other than those mentioned in this section
• Continue to communicate any events not previously acknowledged at a central station prior to entering Programming Mode
While in any of the four levels of Programming Mode, the first three locations on the left of the display represent the
memory address and the last location (farthest right) represents the contents of the memory address. The first address
displayed is shown below:
00_F
(address)(data)
3.2Switch Functions
The function of each switch in program mode is illustrated below:
FIGURE 3-1:
Control Panel Keypad
No function in Program Mode
- Select operating mode
- Increment memory address
Address entry keys are 0 to 9
Data entry keys are 0 to 9 and A to F
- Decrement memory address
Once = First memory address
Twice = Type any address
- Save data, go to next address
3.3Program Options
3.3.1 Level 1 - Main Panel Options
Note that the factory default setting for Location 56 is '0' for Control Panel only. This keeps the communicator off
until location 56 is changed to ‘1’ for panel/communicator. Once location 56 is set to ‘1’ and a valid phone number
is entered, entry into the program mode will cause transmission of the 'System Off Normal' report.
Primary Central Station Phone Number (00-15)
The first sixteen addresses, 00-15, are factory set to 'F' (from 00_F to 15_F). Programming is typically done as
follows:
✓
If your phone number is 484-7161, press 4.
✓
The display will read 00_4.
✓
Press [ENTER/STORE] to save the entry to memory and increment to the next address 01_F.
40
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
✓
Enter the remaining numbers in their respective addresses as shown below:
Entry
Address
4 8 4 7 1 6 1 F F F F F F F F F
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as
dialed numbers and the hexadecimal digits representing the following functions:
• A = * on a Touch-Tone phone keypad
• B = # on a Touch-Tone phone keypad
• C = look for secondary dial tone for up to two seconds (then dial anyway)
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must be entered in all unused phone number locations)
Primary Central Station Number Communication Format (16)
One location is needed to select the Communication Format to the primary phone number. Address 16 is used for
this purpose. The default ( factory setting) for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
Note: Consult you Central Station for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes. See Table 3-3 through Table 3-8 .
!
CAUTION: Default entries for event codes (as shown in Table 3-3 through Table 3-8 ) are programmed into memory each time address '16' is altered. Be certain to double check entries after programming the zone functions,
addresses 64 - 73. Program the format first, then program the zone(s) function. Do not alter while the communicator is active.
Primary Central Station Number Account Code (17-20)
The four locations at addresses 17-20 default to all '0s'. Valid entries are 0-9 and A-F. The number of digits
entered must match the format selection. If programming '2, 3, 4 or 5' into address 16, enter three digits (one digit
each in locations 17, 18 and 19 - location 20 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into
address 16, enter four digits (one digit each in locations 17, 18, 19 and 20).
Document #50193 Rev. E 01/30/02 P/N 50193:E
41
Program Options
Primary Central Station Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four
locations, from addresses 21-24. The default is 00:00 (12:00 midnight). The limits for each location are as follows (do not use values of A-F as entries):
21: enter 0, 1 or 2
22: enter 0-9
23: enter 0-5
24: enter 0-9
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (25)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of ‘0’. If other test report times are needed, enter 1=12hr,
2=8hr or 3=6hr.
Secondary Central Station Phone Number (26-41)
Programming is similar to programming the primary phone number located at addresses 00 - 15. The defaults are
also all 'Fs'.
Entry
Address
F F F F F F F F F F F F F F F F
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Secondary Central Station Number Communication Format (42)
Programming is the same as the primary number's Communication Format at address 16. Default entry is 'E',
Contact ID Format. Choose one entry from the list below:
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format
chosen, the control panel automatically programs all of the event codes. See Table 3-3 through Table 3-8 .
!
CAUTION: Default entries for event codes (as shown in Table 3-3 through Table 3-8 ) are programmed into
memory each time address '42' is altered. Be certain to double check entries after programming the zone functions, addresses 64 - 73. Program the format first, then program the zone(s) function. Do not alter entry while the
communicator is active.
42
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
Secondary Central Station Number Account Code (43-46)
Four locations at addresses 43-46 default to all '0s'. Valid entries are 0-9 and A-F. The number of digits entered
must match the format selection. If programming '2, 3, 4 or 5' into address 42, enter three digits (one digit each in
locations 43, 44 and 45 - location 46 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into address 42,
enter four digits (one digit each in locations 43, 44, 45 and 46).
Secondary Central Station Number 24-Hour Test Time (47-50)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 2 takes up four
locations, from addresses 47-50. The default is 00:00 (12:00 midnight). The limits for each location are as follows (do not use values of A-F as entries):
47: enter 0, 1 or 2
48: enter 0-9
49: enter 0-5
50: enter 0-9
Secondary Central Station Number 24/12/8/6 Hour Test Time (51)
The test message sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to
be sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter 1=12hr,
2=8hr or 3=6hr.
Alarm Presignal (52)
Alarm Presignal is used to delay Notification Appliance Circuit(s) activation while allowing for visual verification
by a person. Once a zone triggers an alarm, the mainboard piezo sounder and the annunciator piezo sounder turn
on steady, the alarm LEDs on the FACP and annunciator flash, the FACP display indicates the activated zone, the
annunciator zone LED flashes and the Notification Appliance Circuits are held off for 15 seconds. During this
time, if the Silence or Acknowledge switch is pressed, the piezos are silenced and the notification appliances may
be held off for up to three minutes. (See Alarm Presignal Delay Timer Address 53-55). After the programmed
delay period, the notification appliances will activate if the source of the alarm is not cleared. Presignal does not function for zones defined as Waterflow, Supervisory, Process Monitoring or zones defined as Remote Switches.
Factory default is '0' for no alarm presignal. Enter '1' to select alarm presignal. During alarm presignal, access to
other modes is prevented and the communicator will not transmit a signal to the central station signifying that the
alarm presignal sequence has been initiated.
!
!
CAUTION: ACM-8RF relays will activate during the Alarm Presignal sequence.
Alarm Presignal Delay Timer (53-55)
The Alarm Presignal Timer is factory set to 120 seconds (2 minutes), with addresses 53=1, 54=2 and 55=0. The
timer may be programmed from 0 to 179 seconds. Location 52 must be set to '1'.
Communicator/Fire Panel Selection (56)
Leaving address 56 at '0' causes the control panel to operate as a fire panel only. Selecting '1' will make it operate
as a fire panel/communicator.
Backup Reporting (57)
Leaving address 57 at '0' means that reports will be transmitted to the secondary Central Station phone number
only if attempts to communicate to the primary Central Station phone number are unsuccessful. Programming a '1'
causes all reports to be transmitted to both the primary and secondary Central Station phone numbers. Programming a '2' causes reports to go to the first available receiver.
CAUTION: Do not alter this entry while the communicator is active.
Touchtone/Rotary Select for Primary Phone (58)
A '0' programmed in this address by the factory triggers Touchtone dialing over the primary phone line. Select '1'
for rotary dialing.
Document #50193 Rev. E 01/30/02 P/N 50193:E
43
Program Options
Make/Break Ratio for Primary Phone (59)
Use this address only if you have chosen '1' for address 58. The Make/Break ratio is factory set to '0' which is 67/
33 ratio, but may be changed to '1' which is 62/38 ratio.
Touchtone/Rotary Select for Secondary Phone (60)
A '0' programmed in this address by the factory triggers Touchtone dialing over the secondary phone line. Select
'1' for rotary dialing.
Make/Break Ratio for Secondary Phone (61)
Use this address only if you have chosen '1' for address 60. The Make/Break ratio is factory set to '0' which is 67/
33 ratio, but may be changed to '1' which is a 62/38 ratio.
Address (62)
Leave entry as default of '0'.
Address (63)
Leave entry as default of '0'.
Zones 1 through 10 Function Selection (64-73)
The ten zones on the control panel may be programmed as shown in Table 3-1 . Program entries alter zone function, transmittal priority and, as a result of altering the zone definition, the transmitted event code message is automatically changed. Remote switch entries 9, A, B and C cause the zone function to be altered to match the FACP
keypad entries. Initial closure (or shorting) of a switch causes the switch function to occur. The switch must be
returned to its normal position.
TABLE 3-1:
Program EntryFunction
1. For remote switch applications, use Fire•Lite P/N: AKS-1F or equivalent UL listed switch.
4Supervisory, autoresettable. Self restore function, is not latched by the control panel
5Waterflow, silenceable. Silencing of Silenceable Notification Appliance Circuits allowed
6
7Critical and noncritical process monitoring
8Autoresettable process monitoring
9
A
B
C
Waterflow, nonsilenceable. Silencing of Silenceable Notification Appliance Circuits not
allowed. Must clear waterflow alarm condition and press reset key
Remote reset switch
Remote silence switch
Remote acknowledge switch
Remote manual evacuate (drill) switch
1
1
1
1
Zone 1 Function Selection (64)
Factory default for zone 1 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
44
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
Zone 2 Function Selection (65)
Factory default for zone 2 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 3 Function Selection (66)
Factory default for zone 3 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 4 Function Selection (67)
Factory default for zone 4 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 5 Function Selection (68)
Factory default for zone 5 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 6 Function Selection (69)
Factory default for zone 6 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 7 Function Selection (70)
Factory default for zone 7 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 8 Function Selection (71)
Factory default for zone 8 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Zone 9 Function Selection (72)
Factory default for zone 9 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact
device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Document #50193 Rev. E 01/30/02 P/N 50193:E
45
Program Options
Zone 10 Function Selection (73)
Factory default for zone 10 is '0' for 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-Open contact device; '3' for Supervisory; '4' for Supervisory, autoresettable; '5' for Waterflow, silenceable; '6' for Waterflow,
nonsilenceable; '7' for critical and noncritical process monitoring; '8' for autoresettable process monitoring; '9' for
remote reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual
evacuate (drill) switch.
Note: Programming any zone to function as supervisory or supervisory autoresettable will cause the defaulted
zone alarm event codes (see note in Table 3-2 ) to be automatically changed. The defaulted code of '1' is changed
to '8' for formats 3+1 and 4+1 Standard and Expanded, 4+2 Expanded and 4+1 Express (refer to Table 3-3 and
Table 3-6 ). The defaulted codes of 11 through 1A are changed to 81 through 8A accordingly for formats 4+2
Standard and 4+2 Express (refer to Table 3-4 and Table 3-7 ). Programming any zone to function as process
monitoring (Zone Function Selections 7 or 8) will cause the alarm event code to be automatically programmed as
'0' or '00' which disables the report. Be certain to reprogram the alarm event code for each process monitoring
zone. Restoral codes remain unchanged from factory defaults.
When using Contact ID Format, zone alarm and zone restoral event codes change automatically as shown in
Table 3-2 . Be certain to reprogram alarm event codes when selecting process monitoring functions. Zone fault
and disable event codes may also be user programmed (refer to “Ademco Contact ID Format Event Code
Descriptions” on page 109).
Programming a zone as a remote switch causes no transmission of an alarm or alarm restoral event code. The
zone wiring continues to be supervised for opens whereas a short simulates closure of a reset, silence, drill or
acknowledge switch. Zone fault and zone restoral codes continue to be transmitted.
TABLE 3-2:
Zone Function SelectionFunctionZone Alarm/Restoral Event Code
1.
Event Code Changes for ID Contact Format
02-wire Smoke111
1Pull Station115
2N.O. Contact Device110
3Supervisory200
4Autoresettable Supervisory200
5Waterflow (silenceable)113
6Waterflow (nonsilenceable)113
7Process Monitoring
8Autoresettable Process Monitoring
9Reset SwitchN/A
ASilence SwitchN/A
BAcknowledge SwitchN/A
CDrill SwitchN/A
000
000
1
1
Be certain to program appropriate process monitoring functions (refer to “Ademco Contact ID Format
Event Code Descriptions” on page 109).
Waterflow Retard Timer (74-75)
A delay may be added prior to declaring a Waterflow type of alarm. Delays up to 89 seconds are allowed. The
default for addresses 74 and 75 are '00' (no additional delay). Valid entries for 74 are 0 through 8 and for 75 are 0
through 9. Program an entry into these addresses only if entering a '5' or '6' in any of the addresses 64 through 73.
Be careful to include any built-in delays of the waterflow device.
46
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
Alarm Verification (76)
Alarm verification works only on zones programmed as 2-wire smoke detector zones. After detecting an alarm,
the panel removes power from all zones for six seconds, resetting all 2-wire smoke detectors. Power is reapplied
and a 12 second retard period allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent alarms by the same initiating zone are ignored. An alarm detected on any other 2-wire detector zone during
the retard period will cause immediate verified alarms. A subsequent alarm on the initiating zone occurring within
the confirmation time will cause a verified alarm.
!
CAUTION: Mixing devices on zones designated as 2-wire smoke zones is not recommended. The communicator
will not
transmit a signal to the central station signifying that alarm verification is in progress.
Note that during the alarm verification period, access to other modes of operation is prevented.
FIGURE 3-2:
Detector Alarm Verification
Detector Zone goes into Alarm
Different Detector Zone Alarms
Verification Timing Diagram
6 Sec.
RESET
Alarm IgnoredControl Panel Processes Alarm if Same Detector Zone is Still in Alarm
18 Sec.0 Sec.
RETARD
ALARM VERIFICATION PERIOD
CONFIRMATION TIME
0
Control Panel Immediately Processes Alarm
120 Sec.
120906030
Factory default selection is no verification which is '0'. Entering a '1' enables verification. Consult the Local
Authority Having Jurisdiction (LAHJ) prior to altering this address.
AC Loss Reporting Delay (77)
Enter a digit of 0 - 9 or A - F corresponding to the number of hours to be delayed in reporting the loss of AC
power. Factory default is 6 hour delay. The valid entries are '0' = 6 hours, '1' = 7 hours, '2' = 8 hours, '3' = 9 hours,
'4' = 10 hours, '5' = 11 hours, '6' = 12 hours, '7' = 15 hours, '8' = 16 hours, '9' = 17 hours, 'A' = 18 hours, 'B' = 19
hours, 'C' = 20 hours, 'D' = 21 hours, 'E' = 22 hours, 'F' = 23 hours.
Programmable Relay #1 (78)
Relay #1 on TB3 of the MS-5210UD main circuit board can be programmed to activate for any one of seven
FACP conditions. The factory default for address 78 is '0' for activation on alarm. Program a '1' for supervisory,
'2' for supervisory autoresettable, '3' for trouble, '4' for communication fail, '5' for process monitoring or '6' for process monitoring autoresettable.
Programmable Relay #2 (79)
Relay #2 on TB3 of the MS-5210UD main circuit board can be programmed to activate for any one of seven
FACP conditions. The factory default for address 79 is '3' for activation on trouble. Program a '0' for alarm, '1' for
supervisory, '2' for supervisory autoresettable, '4' for communication fail, '5' for process monitoring or '6' for process monitoring autoresettable.
Notification Appliance Circuit #1 Enable (80)
Notification Appliance Circuit #1 may be programmed as '0' for silenceable, '1' for nonsilenceable or '2' for disabled. Factory default is '0' for silenceable. Note: Consult the Local Authority Having Jurisdiction (LAHJ) prior
Setting address 81 to '1' prohibits silencing of Notification Appliance Circuit #1 for one minute after initiation of
an alarm. Factory default is '0' for no silence inhibit of Notification Appliance Circuit #1.
Notification Appliance Circuit #1 may be autosilenced after a programmed time interval between 5 and 30 minutes. Enter '1' for 5 minute autosilence; '2' for 10 minute autosilence; '3' for 15 minute autosilence; '4' for 20
minute autosilence; '5' for 25 minute autosilence; or '6' for 30 minute autosilence. The factory default is '0' for no
autosilence.
Coding of Notification Appliance Circuit #1 (83)
Coding of Notification Appliance Circuit #1 is selectable for the following: '1' for March Time (120ppm); '2' for
California (10 seconds On, 5 seconds Off); or '3' for Temporal (
ond Off,
½ second On, 1
½ seconds Off and then repeat). Factory default is '0' for steady (no coding).
½ second On,
½ second Off,
½ second On,
Notification Appliance Circuit #2 Enable (84)
Notification Appliance Circuit #2 may be programmed as '0' for silenceable, '1' for nonsilenceable or '2' for disabled. Factory default is '0' for silenceable. Note: Consult the Local Authority Having Jurisdiction (LAHJ) prior
Setting address 85 to '1' prohibits silencing of Notification Appliance Circuit #2 for one minute after initiation of
an alarm. Factory default is '0' for no silence inhibit of Notification Appliance Circuit #2.
Notification Appliance Circuit #2 may be autosilenced after a programmed time interval between 5 and 30 minutes. Enter '1' for 5 minute autosilence; '2' for 10 minute autosilence; '3' for 15 minute autosilence; '4' for 20
minute autosilence; '5' for 25 minute autosilence; or '6' for 30 minute autosilence. The factory default is '0' for no
autosilence.
Coding of Notification Appliance Circuit #2 (87)
Coding of Notification Appliance Circuit #2 is selectable for the following: '1' for March Time (120ppm); '2' for
California (10 seconds On, 5 seconds Off); or '3' for Temporal (
ond Off,
½ second On, 1
½ seconds Off and then repeat). Factory default is '0' for steady (no coding).
½ second On,
½ second Off,
½ second On,
Trouble Reminder (88)
Factory default '0' disables the trouble reminder feature. Selecting '1' will cause a reminding beep (after the
Silence or Acknowledge switch is pressed) every 15 seconds during an alarm and beep every two minutes during
a trouble condition. The beeps from the onboard piezo sounder will occur until the alarm or fault is cleared.
Programming the Real-Time Clock and Calendar (89-999)
Entering an address greater than 88 will cause a display of the current time. On initial power-up, the clock will
start running from the factory setting of 00:01 (military time). The far left digit will be flashing, indicating that
this is the first digit to be programmed.
Note that the software for the MS-5210UD operates the internal clock based upon 60 Hz. The software for the
MS-5210UDE operates the internal clock based upon 50 Hz.
• Programming Hours and Minutes
- To program the first hour digit, press the corresponding number on the
keypad and then press [ENTER/STORE]. For example, to program 08:00 AM, press '0' on the keypad and
then [ENTER/STORE]. The digit 2nd from the left will start flashing. Enter the second hour digit and press
[ENTER/STORE]. In the previous example, the number '8' would be pressed on the keypad followed by the
[ENTER/STORE] key. This completes the Hours setting. The digit 2nd from the right should now be flash-
ing on the display. Select the first digit for the minutes by pressing the corresponding number on the keypad
and then the [ENTER/STORE] key. The digit on the far right of the display will now be flashing. Select the
second digit for the minutes by pressing the corresponding number on the keypad and then the [ENTER/STORE] key. The Minutes setting is now complete. If during programming of the time an invalid digit is
selected (i.e. 3 or higher for the first digit) the FACP piezo sounder will beep and the digit will continue to
blink until a valid entry is made.
½ sec-
48
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
• Programming Year - After entering the last digit corresponding to minutes (far right digit), the display will
read 1996 with the digit '9', second from the right, flashing. Press [ENTER/STORE] if acceptable. To change
the year, enter a digit. Entering a zero '0' will change the display to the year 2000. Press the [ENTER/STORE] key. Repeat for the digit to the far right.
• Programming Month/Day
- After the year is entered, the display will show four digits representing the month
and day of the software release date. The month is represented by the two digits on the left and the day by the
two digits on the right. The digit on the far left will be flashing. The month and day are set the same way as
the hours and minutes. Once the last digit corresponding to the day is entered, the display will show the contents of address '00'. The real time clock/calendar keeps track of leap years automatically.
End Programming/Exit to Alternate Program Level
Exit Programming Mode by pressing MODE, followed by the 4-digit code corresponding to an alternate mode of
operation, then press [ENTER/STORE]. To enter a different Programming Level, press MODE and then press
the [ENTER/STORE] key. The display will show P__1 with the '1' flashing. Press the digit (2, 3 or 4) of the Programming Level to be accessed.
During Program Mode, if no key is pressed within 10 minutes, the panel will revert to Normal Mode.
3.3.2 Level Two - Event Codes/Transmission Formats
Each option of the Program Mode is entered by keying in the program mode entry code (7764) and pressing the
[ENTER/STORE] key.
7764 spells PROG on a Touch-Tone
☛
®
phone
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key.
Your are allowed a pause of up to 10 seconds in between each number while entering the code. After pressing the
[ENTER/STORE] key, the control panel will be in Program Mode and display P__1, with the '1' flashing. Press 2 on
the keypad and then the [ENTER/STORE] key to select the Event Code/Transmission Formats Level for programming. You are allowed up to ten minutes of idle time at this point before starting your programming, otherwise, the
control panel will go back to Normal Mode. You also have a maximum of 10 minutes between any key stroke. All
entries made prior to the 10 minutes time-out are valid and are stored.
Upon entering the Event Codes/Transmission Formats Level in programming mode, the following will be displayed
on the FACP 7-Segment Display.
00_1
(address)(data)
The first three locations on the left of the display represent the memory address 00 of the Format Chart previously
selected in address 16 of the Main Panel Options section of programming mode. The last location 1 (farthest right)
represents the contents of memory address 00 which is the format setting. The only value which can be altered in the
Format Charts is the setting which is the last digit to the right. To change the value, key in the new digit. Use the Up
and Down Arrow keys to increment to the next address or decrement to the previous address.
When desired changes have been completed, exit programming mode by pressing the MODE key, followed by the
4-digit code for an alternate mode and then the [ENTER/STORE] key. To enter a different Programming Level,
press MODE and then press the [ENTER/STORE] key. The display will show P__2 with the '2' flashing. Press the
digit (1, 3 or 4) of the Programming Level to be accessed. During Program Mode, if no key is pressed within 10 minutes, the panel will revert to Normal Mode.
The Format Charts which may be selected in the Main Panel Options (Level 1) section of the Programming Mode are
shown on the following pages of this section. Format charts for the Primary and Secondary Central Station Numbers
are included.
Document #50193 Rev. E 01/30/02 P/N 50193:E
49
Program Options
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 16 in Program Mode Level 1, the data shown in Table 33 is automatically programmed for the Primary Central Station phone number event codes. Enter '0' for the setting to disable the report.
TABLE 3-3:
Event Codes, Primary Central Station Number
AddressDescriptionSetting
0Primary # Zone 1 Alarm Code
1Primary # Zone 2 Alarm Code
2Primary # Zone 3 Alarm Code
3Primary # Zone 4 Alarm Code
4Primary # Zone 5 Alarm Code
5Primary # Zone 6 Alarm Code
6Primary # Zone 7 Alarm Code
7Primary # Zone 8 Alarm Code
8Primary # Zone 9 Alarm Code
9Primary # Zone 10 Alarm Code
10Primary # Zone 1 Disabled Code4
11Primary # Zone 2 Disabled Code4
12Primary # Zone 3 Disabled Code4
13Primary # Zone 4 Disabled Code4
14Primary # Zone 5 Disabled Code4
15Primary # Zone 6 Disabled Code4
16Primary # Zone 7 Disabled Code4
17Primary # Zone 8 Disabled Code4
18Primary # Zone 9 Disabled Code4
19Primary # Zone 10 Disabled Code4
20Primary # Drill Code9
21Primary # AC Fault Code9
22Primary # Zone 1 Fault CodeF
23Primary # Zone 2 Fault CodeF
24Primary # Zone 3 Fault CodeF
25Primary # Zone 4 Fault CodeF
26Primary # Zone 5 Fault CodeF
27Primary # Zone 6 Fault CodeF
28Primary # Zone 7 Fault CodeF
29Primary # Zone 8 Fault CodeF
30Primary # Zone 9 Fault CodeF
31Primary # Zone 10 Fault CodeF
32Primary # Earth Fault Code6
33Primary # Low Battery Fault Code6
34Primary # No Battery Fault Code6
35Primary # Telco Primary Line Fault Code6
36Primary # Telco Secondary Line Fault Code6
37Primary # NAC #1 Fault Code6
38Primary # NAC #2 Fault Code6
39Primary # NAC #3 Fault Code6
40Primary # NAC #4 Fault Code6
41Primary # NAC #1 Disable Code4
42Primary # NAC #2 Disable Code4
43Primary # NAC #3 Disable Code4
44Primary # NAC #4 Disable Code4
45Primary # Comm Trouble Primary # Code6
46Primary # Comm Trouble Secondary # Code6
47Primary # Printer Fault Code6
48Primary # Annunciator Fault Code6
49Primary # 485 Comm Trouble Code6
50Primary # System Off Normal Code6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
50
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
TABLE 3-3:
Event Codes, Primary Central Station Number
AddressDescriptionSetting
51Primary # Zone 1 Alarm Restore CodeE
52Primary # Zone 2 Alarm Restore CodeE
53Primary # Zone 3 Alarm Restore CodeE
54Primary # Zone 4 Alarm Restore CodeE
55Primary # Zone 5 Alarm Restore CodeE
56Primary # Zone 6 Alarm Restore CodeE
57Primary # Zone 7 Alarm Restore CodeE
58Primary # Zone 8 Alarm Restore CodeE
59Primary # Zone 9 Alarm Restore CodeE
60Primary # Zone 10 Alarm Restore CodeE
61Primary # Zone 1 Disabled Restore Code5
62Primary # Zone 2 Disabled Restore Code5
63Primary # Zone 3 Disabled Restore Code5
64Primary # Zone 4 Disabled Restore Code5
65Primary # Zone 5 Disabled Restore Code5
66Primary # Zone 6 Disabled Restore Code5
67Primary # Zone 7 Disabled Restore Code5
68Primary # Zone 8 Disabled Restore Code5
69Primary # Zone 9 Disabled Restore Code5
70Primary # Zone 10 Disabled Restore Code5
71Primary # Drill Restore Code9
72Primary # AC Fault Restore Code9
73Primary # Zone 1 Fault Restore CodeD
74Primary # Zone 2 Fault Restore CodeD
75Primary # Zone 3 Fault Restore CodeD
76Primary # Zone 4 Fault Restore CodeD
77Primary # Zone 5 Fault Restore CodeD
78Primary # Zone 6 Fault Restore CodeD
79Primary # Zone 7 Fault Restore CodeD
80Primary # Zone 8 Fault Restore CodeD
81Primary # Zone 9 Fault Restore CodeD
82Primary # Zone 10 Fault Restore CodeD
83Primary # Earth Fault Restore CodeA
84Primary #Low Battery Fault Restore CodeA
85Primary # No Battery Fault Restore CodeA
86Primary # Telco Primary Line Fault Restore CodeA
87Primary # Telco Secondary Line Fault Restore CodeA
88Primary # NAC #1 Fault Restore CodeA
89Primary # NAC #2 Fault Restore CodeA
90Primary # NAC #3 Fault Restore CodeA
91Primary # NAC #4 Fault Restore CodeA
92Primary # NAC #1 Disable Restore Code5
93Primary # NAC #2 Disable Restore Code5
94Primary # NAC #3 Disable Restore Code5
95Primary # NAC #4 Disable Restore Code5
96Primary # Comm Trouble Primary # Restore CodeA
97Primary # Comm Trouble Secondary # Restore CodeA
98Primary # Printer Fault Restore CodeA
99Primary # Annunciator Fault Restore CodeA
100Primary # 485 Comm Trouble Restore CodeA
101Primary # System Off Normal Restore CodeA
102Primary # System Test Report9
103Primary # System Abnormal Test ReportF
104Primary # Request for Up/Download7
105Primary # Successful Upload7
106Primary # Successful Download7
107Primary # Failed Up/Download7
1. Zones programmed as supervisory alarm transmit as Code 8 instead of Code 1.
Document #50193 Rev. E 01/30/02 P/N 50193:E
51
Program Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' are entered for address 16 in Program Mode Level 1, the data shown in Table 3-4 is automatically
programmed for the Primary Central Station phone number event codes. Enter '00' for the setting to disable the
report.
TABLE 3-4:
Event Codes, Primary Central Station Number
AddressDescriptionSetting
0-1Primary # Zone 1 Alarm Code
2-3Primary # Zone 2 Alarm Code
4-5Primary # Zone 3 Alarm Code
6-7Primary # Zone 4 Alarm Code
8-9Primary # Zone 5 Alarm Code
10-11Primary # Zone 6 Alarm Code
12-13Primary # Zone 7 Alarm Code
14-15Primary # Zone 8 Alarm Code
16-17Primary # Zone 9 Alarm Code
18-19Primary # Zone 10 Alarm Code
20-21Primary # Zone 1 Disabled Code41
22-23Primary # Zone 2 Disabled Code42
24-25Primary # Zone 3 Disabled Code43
26-27Primary # Zone 4 Disabled Code44
28-29Primary # Zone 5 Disabled Code45
30-31Primary # Zone 6 Disabled Code46
32-33Primary # Zone 7 Disabled Code47
34-35Primary # Zone 8 Disabled Code48
36-37Primary # Zone 9 Disabled Code49
38-39Primary # Zone 10 Disabled Code4A
40-41Primary # Drill Code97
42-43Primary # AC Fault Code92
44-45Primary # Zone 1 Fault CodeF1
46-47Primary # Zone 2 Fault CodeF2
48-49Primary # Zone 3 Fault CodeF3
50-51Primary # Zone 4 Fault CodeF4
52-53Primary # Zone 5 Fault CodeF5
54-55Primary # Zone 6 Fault CodeF6
56-57Primary # Zone 7 Fault CodeF7
58-59Primary # Zone 8 Fault CodeF8
60-61Primary # Zone 9 Fault CodeF9
62-63Primary # Zone 10 Fault CodeFA
64-65Primary # Earth Fault Code61
66-67Primary # Low Battery Fault Code62
68-69Primary # No Battery Fault Code63
70-71Primary # Telco Primary Line Fault Code64
72-73Primary # Telco Secondary Line Fault Code65
74-75Primary # NAC #1 Fault Code66
76-77Primary # NAC #2 Fault Code67
78-79Primary # NAC #3 Fault Code68
80-81Primary # NAC #4 Fault Code69
82-83Primary # NAC #1 Disable Code4B
84-85Primary # NAC #2 Disable Code4C
86-87Primary # NAC #3 Disable Code4D
88-89Primary # NAC #4 Disable Code4E
90-91Primary # Comm Trouble Primary # Code6A
92-93Primary # Comm Trouble Secondary # Code6B
94-95Primary # Printer Fault Code6C
96-97Primary # Annunciator Fault Code6D
98-99Primary # 485 Comm Trouble Code6E
100-101Primary # System Off Normal Code6F
11
12
13
14
15
16
17
18
19
1A
1
1
1
1
1
1
1
1
1
1
52
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
TABLE 3-4:
Event Codes, Primary Central Station Number
AddressDescriptionSetting
102-103Primary # Zone 1 Alarm Restore CodeE1
104-105Primary # Zone 2 Alarm Restore CodeE2
106-107Primary # Zone 3 Alarm Restore CodeE3
108-109Primary # Zone 4 Alarm Restore CodeE4
110-111Primary # Zone 5 Alarm Restore CodeE5
112-113Primary # Zone 6 Alarm Restore CodeE6
114-115Primary # Zone 7 Alarm Restore CodeE7
116-117Primary # Zone 8 Alarm Restore CodeE8
118-119Primary # Zone 9 Alarm Restore CodeE9
120-121Primary # Zone 10 Alarm Restore CodeEA
122-123Primary # Zone 1 Disabled Restore Code51
124-125Primary # Zone 2 Disabled Restore Code52
126-127Primary # Zone 3 Disabled Restore Code53
128-129Primary # Zone 4 Disabled Restore Code54
130-131Primary # Zone 5 Disabled Restore Code55
132-133Primary # Zone 6 Disabled Restore Code56
134-135Primary # Zone 7 Disabled Restore Code57
136-137Primary # Zone 8 Disabled Restore Code58
138-139Primary # Zone 9 Disabled Restore Code59
140-141Primary # Zone 10 Disabled Restore Code5A
142-143Primary # Drill Restore Code98
144-145Primary # AC Fault Restore Code93
146-147Primary # Zone 1 Fault Restore CodeD1
148-149Primary # Zone 2 Fault Restore CodeD2
150-151Primary # Zone 3 Fault Restore CodeD3
152-153Primary # Zone 4 Fault Restore CodeD4
154-155Primary # Zone 5 Fault Restore CodeD5
156-157Primary # Zone 6 Fault Restore CodeD6
158-159Primary # Zone 7 Fault Restore CodeD7
160-161Primary # Zone 8 Fault Restore CodeD8
162-163Primary # Zone 9 Fault Restore CodeD9
164-165Primary # Zone 10 Fault Restore CodeDA
166-167Primary # Earth Fault Restore CodeA1
168-169Primary #Low Battery Fault Restore CodeA2
170-171Primary # No Battery Fault Restore CodeA3
172-173Primary # Telco Primary Line Fault Restore CodeA4
174-175Primary # Telco Secondary Line Fault Restore CodeA5
176-177Primary # NAC #1 Fault Restore CodeA6
178-179Primary # NAC #2 Fault Restore CodeA7
180-181Primary # NAC #3 Fault Restore CodeA8
182-183Primary # NAC #4 Fault Restore CodeA9
184-185Primary # NAC #1 Disable Restore Code5B
186-187Primary # NAC #2 Disable Restore Code5C
188-189Primary # NAC #3 Disable Restore Code5D
190-191Primary # NAC #4 Disable Restore Code5E
192-193Primary # Comm Trouble Primary # Restore CodeAA
194-195Primary # Comm Trouble Secondary # Restore CodeAB
196-197Primary # Printer Fault Restore CodeAC
198-199Primary # Annunciator Fault Restore CodeAD
200-201Primary # 485 Comm Trouble Restore CodeAE
201-203Primary # System Off Normal Restore CodeAF
204-205Primary # System Test Report99
206-207Primary # System Abnormal Test Report91
208-209Primary # Request for Up/Download71
210-211Primary # Successful Upload72
212-213Primary # Successful Download73
214-215Primary # Failed Up/Download74
1. Zones programmed as supervisory alarm transmit as 81, 82, 83, 84, 85, 86, 87, 88, 89, 8A
(instead of 11, 12, 13, 14, 15, 16, 17, 18, 19, 1A).
Document #50193 Rev. E 01/30/02 P/N 50193:E
53
Program Options
Ademco Contact ID Format
If 'E' is entered for address 16 in Program Mode Level 1, the data shown in Table 3-5 is automatically programmed for the Primary Central Station phone number event codes. Enter '000' for the setting to disable the
report. The Setting entry is programmable, the Zone Number cannot be changed. Restoral code settings match
the settings shown with the addition of an 'R' code transmitted. Refer to page 109 for additional information.
TABLE 3-5:
Event Codes, Primary Central Station Number
AddressDescriptionSettingZone No.
0-2Primary # Zone 1 Alarm Code
3-5Primary # Zone 2 Alarm Code
6-8Primary # Zone 3 Alarm Code
9-11Primary # Zone 4 Alarm Code
12-14Primary # Zone 5 Alarm Code
15-17Primary # Zone 6 Alarm Code
18-20Primary # Zone 7 Alarm Code
21-23Primary # Zone 8 Alarm Code
24-26Primary # Zone 9 Alarm Code
27-29Primary # Zone 10 Alarm Code
111
111
111
111
111
111
111
111
111
111
1
1
1
1
1
1
1
1
1
1
30-32Primary # Zone 1 Disabled Code570001
33-35Primary # Zone 2 Disabled Code570002
36-38Primary # Zone 3 Disabled Code570003
39-41Primary # Zone 4 Disabled Code570004
42-44Primary # Zone 5 Disabled Code570005
45-47Primary # Zone 6 Disabled Code570006
48-50Primary # Zone 7 Disabled Code570007
51-53Primary # Zone 8 Disabled Code570008
54-56Primary # Zone 9 Disabled Code570009
57-59Primary # Zone 10 Disabled Code570010
60-62Primary # Drill Code604000
63-65Primary # AC Fault Code301000
66-68Primary # Zone 1 Fault Code380001
69-71Primary # Zone 2 Fault Code380002
72-74Primary # Zone 3 Fault Code380003
75-77Primary # Zone 4 Fault Code380004
78-80Primary # Zone 5 Fault Code380005
81-83Primary # Zone 6 Fault Code380006
84-86Primary # Zone 7 Fault Code380007
87-89Primary # Zone 8 Fault Code380008
90-92Primary # Zone 9 Fault Code380009
93-95Primary # Zone 10 Fault Code380010
96-98Primary # Earth Fault Code310000
1. Refer to Table 3-1 for list of zone alarm event codes.
001
002
003
004
005
006
007
008
009
010
54
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 42 in Program Mode Level 1, the data shown in Table 3-6
is automatically programmed for the Secondary Central Station phone number event codes. Enter '0' for the setting to disable the report.
TABLE 3-6:
Event Codes, Secondary Central Station Number
AddressDescriptionSetting
216Secondary # Zone 1 Alarm Code
217Secondary # Zone 2 Alarm Code
218Secondary # Zone 3 Alarm Code
219Secondary # Zone 4 Alarm Code
220Secondary # Zone 5 Alarm Code
221Secondary # Zone 6 Alarm Code
222Secondary # Zone 7 Alarm Code
223Secondary # Zone 8 Alarm Code
224Secondary # Zone 9 Alarm Code
225Secondary # Zone 10 Alarm Code
226Secondary # Zone 1 Disabled Code4
227Secondary # Zone 2 Disabled Code4
228Secondary # Zone 3 Disabled Code4
229Secondary # Zone 4 Disabled Code4
230Secondary # Zone 5 Disabled Code4
231Secondary # Zone 6 Disabled Code4
232Secondary # Zone 7 Disabled Code4
233Secondary # Zone 8 Disabled Code4
234Secondary # Zone 9 Disabled Code4
235Secondary # Zone 10 Disabled Code4
236Secondary # Drill Code9
237Secondary # AC Fault Code9
238Secondary # Zone 1 Fault CodeF
239Secondary # Zone 2 Fault CodeF
240Secondary # Zone 3 Fault CodeF
241Secondary # Zone 4 Fault CodeF
242Secondary # Zone 5 Fault CodeF
243Secondary # Zone 6 Fault CodeF
244Secondary # Zone 7 Fault CodeF
245Secondary # Zone 8 Fault CodeF
246Secondary # Zone 9 Fault CodeF
247Secondary # Zone 10 Fault CodeF
248Secondary # Earth Fault Code6
249Secondary # Low Battery Fault Code6
250Secondary # No Battery Fault Code6
251Secondary # Telco Primary Line Fault Code6
252Secondary # Telco Secondary Line Fault Code6
253Secondary # NAC #1 Fault Code6
254Secondary # NAC #2 Fault Code6
255Secondary # NAC #3 Fault Code6
256Secondary # NAC #4 Fault Code6
257Secondary # NAC #1 Disable Code4
258Secondary # NAC #2 Disable Code4
259Secondary # NAC #3 Disable Code4
260Secondary # NAC #4 Disable Code4
261Secondary # Comm Trouble Primary # Code6
262Secondary # Comm Trouble Secondary # Code6
263Secondary # Printer Fault Code6
264Secondary # Annunciator Fault Code6
265Secondary # 485 Comm Trouble Code6
266Secondary # System Off Normal Code6
267Secondary # Zone 1 Alarm Restore CodeE
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Document #50193 Rev. E 01/30/02 P/N 50193:E
55
Program Options
TABLE 3-6:
Event Codes, Secondary Central Station Number
AddressDescriptionSetting
268Secondary # Zone 2 Alarm Restore CodeE
269Secondary # Zone 3 Alarm Restore CodeE
270Secondary # Zone 4 Alarm Restore CodeE
271Secondary # Zone 5 Alarm Restore CodeE
272Secondary # Zone 6 Alarm Restore CodeE
273Secondary # Zone 7 Alarm Restore CodeE
274Secondary # Zone 8 Alarm Restore CodeE
275Secondary # Zone 9 Alarm Restore CodeE
276Secondary # Zone 10 Alarm Restore CodeE
277Secondary # Zone 1 Disabled Restore Code5
278Secondary # Zone 2 Disabled Restore Code5
279Secondary # Zone 3 Disabled Restore Code5
280Secondary # Zone 4 Disabled Restore Code5
281Secondary # Zone 5 Disabled Restore Code5
282Secondary # Zone 6 Disabled Restore Code5
283Secondary # Zone 7 Disabled Restore Code5
284Secondary # Zone 8 Disabled Restore Code5
285Secondary # Zone 9 Disabled Restore Code5
286Secondary # Zone 10 Disabled Restore Code5
287Secondary # Drill Restore Code9
288Secondary # AC Fault Restore Code9
289Secondary # Zone 1 Fault Restore CodeD
290Secondary # Zone 2 Fault Restore CodeD
291Secondary # Zone 3 Fault Restore CodeD
292Secondary # Zone 4 Fault Restore CodeD
293Secondary # Zone 5 Fault Restore CodeD
294Secondary # Zone 6 Fault Restore CodeD
295Secondary # Zone 7 Fault Restore CodeD
296Secondary # Zone 8 Fault Restore CodeD
297Secondary # Zone 9 Fault Restore CodeD
298Secondary # Zone 10 Fault Restore CodeD
299Secondary # Earth Fault Restore CodeA
300Secondary #Low Battery Fault Restore CodeA
301Secondary # No Battery Fault Restore CodeA
302Secondary # Telco Primary Line Fault Restore CodeA
303Secondary # Telco Secondary Line Fault Restore CodeA
304Secondary # NAC #1 Fault Restore CodeA
305Secondary # NAC #2 Fault Restore CodeA
306Secondary # NAC #3 Fault Restore CodeA
307Secondary # NAC #4 Fault Restore CodeA
308Secondary # NAC #1 Disable Restore Code5
309Secondary # NAC #2 Disable Restore Code5
310Secondary # NAC #3 Disable Restore Code5
311Secondary # NAC #4 Disable Restore Code5
312Secondary # Comm Trouble Primary # Restore CodeA
313Secondary # Comm Trouble Secondary # Restore CodeA
314Secondary # Printer Fault Restore CodeA
315Secondary # Annunciator Fault Restore CodeA
316Secondary # 485 Comm Trouble Restore CodeA
317Secondary # System Off Normal Restore CodeA
318Secondary # System Test Report9
319Secondary # System Abnormal Test ReportF
320Secondary # Request for Up/Download7
321Secondary # Successful Upload7
322Secondary # Successful Download7
323Secondary # Failed Up/Download7
56
1. Zones programmed as supervisory alarm transmit as Code 8 instead of Code 1.
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' are entered for address 42 in Program Mode Level 1, the data shown in Table 3-7 is automatically
programmed for the Secondary Central Station phone number event codes. Enter '00' for the setting to disable the
report.
TABLE 3-7:
Event Codes, Secondary Central Station Number
AddressDescriptionSetting
216-217Secondary # Zone 1 Alarm Code
218-219Secondary # Zone 2 Alarm Code
220-221Secondary # Zone 3 Alarm Code
222-223Secondary # Zone 4 Alarm Code
224-225Secondary # Zone 5 Alarm Code
226-227Secondary # Zone 6 Alarm Code
228-229Secondary # Zone 7 Alarm Code
230-231Secondary # Zone 8 Alarm Code
232-233Secondary # Zone 9 Alarm Code
234-235Secondary # Zone 10 Alarm Code
236-237Secondary # Zone 1 Disabled Code41
238-239Secondary # Zone 2 Disabled Code42
240-241Secondary # Zone 3 Disabled Code43
242-243Secondary # Zone 4 Disabled Code44
244-245Secondary # Zone 5 Disabled Code45
246-247Secondary # Zone 6 Disabled Code46
248-249Secondary # Zone 7 Disabled Code47
250-251Secondary # Zone 8 Disabled Code48
252-253Secondary # Zone 9 Disabled Code49
254-255Secondary # Zone 10 Disabled Code4A
256-257Secondary # Drill Code97
258-259Secondary # AC Fault Code92
260-261Secondary # Zone 1 Fault CodeF1
262-263Secondary # Zone 2 Fault CodeF2
264-265Secondary # Zone 3 Fault CodeF3
266-267Secondary # Zone 4 Fault CodeF4
268-269Secondary # Zone 5 Fault CodeF5
270-271Secondary # Zone 6 Fault CodeF6
272-273Secondary # Zone 7 Fault CodeF7
274-275Secondary # Zone 8 Fault CodeF8
276-277Secondary # Zone 9 Fault CodeF9
278-279Secondary # Zone 10 Fault CodeFA
280-281Secondary # Earth Fault Code61
282-283Secondary # Low Battery Fault Code62
284-285Secondary # No Battery Fault Code63
286-287Secondary # Telco Primary Line Fault Code64
288-289Secondary # Telco Secondary Line Fault Code65
290-291Secondary # NAC #1 Fault Code66
292-293Secondary # NAC #2 Fault Code67
294-295Secondary # NAC #3 Fault Code68
296-297Secondary # NAC #4 Fault Code69
298-299Secondary # NAC #1 Disable Code4B
300-301Secondary # NAC #2 Disable Code4C
302-303Secondary # NAC #3 Disable Code4D
304-305Secondary # NAC #4 Disable Code4E
306-307Secondary # Comm Trouble Primary # Code6A
308-309Secondary # Comm Trouble Secondary # Code6B
310-311Secondary # Printer Fault Code6C
312-313Secondary # Annunciator Fault Code6D
314-315Secondary # 485 Comm Trouble Code6E
316-317Secondary # System Off Normal Code6F
318-319Secondary # Zone 1 Alarm Restore CodeE1
11
12
13
14
15
16
17
18
19
1A
1
1
1
1
1
1
1
1
1
1
Document #50193 Rev. E 01/30/02 P/N 50193:E
57
Program Options
TABLE 3-7:
Event Codes, Secondary Central Station Number
AddressDescriptionSetting
320-321Secondary # Zone 2 Alarm Restore CodeE2
322-323Secondary # Zone 3 Alarm Restore CodeE3
324-325Secondary # Zone 4 Alarm Restore CodeE4
326-327Secondary # Zone 5 Alarm Restore CodeE5
328-329Secondary # Zone 6 Alarm Restore CodeE6
330-331Secondary # Zone 7 Alarm Restore CodeE7
332-333Secondary # Zone 8 Alarm Restore CodeE8
334-335Secondary # Zone 9 Alarm Restore CodeE9
336-337Secondary # Zone 10 Alarm Restore CodeEA
338-339Secondary # Zone 1 Disabled Restore Code51
340-341Secondary # Zone 2 Disabled Restore Code52
342-343Secondary # Zone 3 Disabled Restore Code53
344-345Secondary # Zone 4 Disabled Restore Code54
346-347Secondary # Zone 5 Disabled Restore Code55
348-349Secondary # Zone 6 Disabled Restore Code56
350-351Secondary # Zone 7 Disabled Restore Code57
352-353Secondary # Zone 8 Disabled Restore Code58
354-355Secondary # Zone 9 Disabled Restore Code59
356-357Secondary # Zone 10 Disabled Restore Code5A
358-359Secondary # Drill Restore Code98
360-361Secondary # AC Fault Restore Code93
362-363Secondary # Zone 1 Fault Restore CodeD1
364-365Secondary # Zone 2 Fault Restore CodeD2
366-367Secondary # Zone 3 Fault Restore CodeD3
368-369Secondary # Zone 4 Fault Restore CodeD4
370-371Secondary # Zone 5 Fault Restore CodeD5
372-373Secondary # Zone 6 Fault Restore CodeD6
374-375Secondary # Zone 7 Fault Restore CodeD7
376-377Secondary # Zone 8 Fault Restore CodeD8
378-379Secondary # Zone 9 Fault Restore CodeD9
380-381Secondary # Zone 10 Fault Restore CodeDA
382-383Secondary # Earth Fault Restore CodeA1
384-385Secondary #Low Battery Fault Restore CodeA2
386-387Secondary # No Battery Fault Restore CodeA3
388-389Secondary # Telco Primary Line Fault Restore CodeA4
390-391Secondary # Telco Secondary Line Fault Restore CodeA5
392-393Secondary # NAC #1 Fault Restore CodeA6
394-395Secondary # NAC #2 Fault Restore CodeA7
396-397Secondary # NAC #3 Fault Restore CodeA8
398-399Secondary # NAC #4 Fault Restore CodeA9
400-401Secondary # NAC #1 Disable Restore Code5B
402-403Secondary # NAC #2 Disable Restore Code5C
404-405Secondary # NAC #3 Disable Restore Code5D
406-407Secondary # NAC #4 Disable Restore Code5E
408-409Secondary # Comm Trouble Primary # Restore CodeAA
410-411Secondary # Comm Trouble Secondary # Restore CodeAB
412-413Secondary # Printer Fault Restore CodeAC
414-415Secondary # Annunciator Fault Restore CodeAD
416-417Secondary # 485 Comm Trouble Restore CodeAE
418-419Secondary # System Off Normal Restore CodeAF
420-421Secondary # System Test Report99
422-423Secondary # System Abnormal Test Report91
424-425Secondary # Request for Up/Download71
426-427Secondary # Successful Upload72
428-429Secondary # Successful Download73
430-431Secondary # Failed Up/Download74
58
1. Zones programmed as supervisory alarm transmit as 81, 82, 83, 84, 85, 86, 87, 88, 89, 8A.
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
Ademco Contact ID Format
If 'E' is entered for address 42 in Program Mode Level 1, the data shown in Table 3-8 is automatically programmed for the Secondary Central Station phone number event codes. Enter '000' for the setting to disable the
report. The Setting entry is programmable, the Zone Number cannot be changed. Restoral code settings match the
settings shown with the addition of an 'R' code transmitted. Refer to page 99 for additional information.
TABLE 3-8:
Event Codes, Secondary Central Station Number
AddressDescriptionSettingZone No.
216-218Secondary # Zone 1 Alarm Code
219-221Secondary # Zone 2 Alarm Code
222-224Secondary # Zone 3 Alarm Code
225-227Secondary # Zone 4 Alarm Code
228-230Secondary # Zone 5 Alarm Code
231-233Secondary # Zone 6 Alarm Code
234-236Secondary # Zone 7 Alarm Code
237-239Secondary # Zone 8 Alarm Code
240-242Secondary # Zone 9 Alarm Code
243-245Secondary # Zone 10 Alarm Code
111
111
111
111
111
111
111
111
111
111
1
1
1
1
1
1
1
1
1
1
246-248Secondary # Zone 1 Disabled Code570001
249-251Secondary # Zone 2 Disabled Code570002
252-254Secondary # Zone 3 Disabled Code570003
255-257Secondary # Zone 4 Disabled Code570004
258-260Secondary # Zone 5 Disabled Code570005
261-263Secondary # Zone 6 Disabled Code570006
264-266Secondary # Zone 7 Disabled Code570007
267-269Secondary # Zone 8 Disabled Code570008
270-272Secondary # Zone 9 Disabled Code570009
273-275Secondary # Zone 10 Disabled Code570010
276-278Secondary # Drill Code604000
279-281Secondary # AC Fault Code301000
282-284Secondary # Zone 1 Fault Code380001
285-287Secondary # Zone 2 Fault Code380002
288-290Secondary # Zone 3 Fault Code380003
291-293Secondary # Zone 4 Fault Code380004
294-296Secondary # Zone 5 Fault Code380005
297-299Secondary # Zone 6 Fault Code380006
300-302Secondary # Zone 7 Fault Code380007
303-305Secondary # Zone 8 Fault Code380008
306-308Secondary # Zone 9 Fault Code380009
309-311Secondary # Zone 10 Fault Code380010
312-314Secondary # Earth Fault Code310000
315-317Secondary # Low Battery Fault Code302000
318-320Secondary # No Battery Fault Code311000
321-323Secondary # Telco Primary Line Fault Code351000
324-326Secondary # Telco Secondary Line Fault Code352000
327-329Secondary # NAC #1 Fault Code321001
330-332Secondary # NAC #2 Fault Code322002
333-335Secondary # NAC #3 Fault Code326003
336-338Secondary # NAC #4 Fault Code327004
339-341Secondary # NAC #1 Disable Code521001
342-344Secondary # NAC #2 Disable Code522002
345-347Secondary # NAC #3 Disable Code526003
348-350Secondary # NAC #4 Disable Code527004
351-353Secondary # Comm Trouble Primary # Code354001
354-356Secondary # Comm Trouble Secondary # Code354002
357-359Secondary # Printer Fault Code336000
360-362Secondary # Annunciator Fault Code330001
363-365Secondary # 485 Comm Trouble Code330002
366-368Secondary # System Off Normal Code308000
369-371Secondary # System Test Message602000
372-374Secondary # System Abnormal Test Message608000
375-377Secondary # Upload/Download Request Code411000
378-380Secondary # Upload Successful Code416000
381-383Secondary # Download Successful Code412000
384-386Secondary # Upload/Download Failed Code413000
1. Refer to Table 3-1 for a list of zone alarm event codes.
001
002
003
004
005
006
007
008
009
010
Document #50193 Rev. E 01/30/02 P/N 50193:E
59
Program Options
3.3.3 Level Three - Option Module Selections
Each option of the Program Mode is entered by keying in the program mode entry code (7764) and pressing the
[ENTER/STORE] key.
7764 spells PROG on a Touch-Tone
☛
®
phone
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key.
You are allowed a pause of up to 10 seconds in between each number while entering the code. After pressing the
[ENTER/STORE] key, the control panel will be in Program Mode and display P__1, with the '1' flashing. Press 3
on the keypad and then the [ENTER/STORE] key to choose the Option Module Selections. You are allowed up to
ten minutes of idle time at this point before starting your programming, otherwise, the control panel will return to
Normal Mode. You also have a maximum of 10 minutes between any keystroke. All entries made prior to the 10
minute time-out are valid and are stored.
Upon entering the Option Modules Selections in programming mode, the following will be displayed on the FACP
7-Segment Display.
00_0
(address)(data)
The first three locations on the left of the display represent the memory address 00_ of the first Option Module
(CAC-10F Converter Card). The last location 0 (farthest right) represents the contents of memory address '00', which
indicates that the card is not installed. To install the card, press '1' on the keypad. Use the Up and Down Arrow keys
to increment to the next address or decrement to the previous address.
When desired changes have been completed, exit programming mode by pressing the MODE key, followed by the
4-digit code for an alternate mode and then the [ENTER/STORE] key. To enter a different Programming Level,
press MODE and then press the [ENTER/STORE] key. The display will show P__3 with the '3' flashing. Press the
digit (1, 2 or 4) of the Programming Level to be accessed. During Program Mode, if no key is pressed within 10 minutes, the panel will revert to Normal Mode.
Following are the various option modules and their addresses.
CAC-10F Class A Converter Card (00)
The factory default entry of '0' in address 00 informs the FACP that there is no CAC-10F Class A Converter Card
installed in the panel. When a CAC-10F is installed, '1' must be entered for this address.
LED-10IM EIA-485 Interface Module (01)
The factory default entry of '0' indicates to the panel that an LED-10IM is not installed. Enter a '1' in address 01 if
an LED-10IM EIA-485 Interface Module is installed.
Annunciator Maximum Monitored Address (02-03)
Annunciator addresses may be set from a value of '01' through '32'. Enter the value of the highest or maximum
address value selected on any annunciator or ACM-8RF connected to the EIA-485 port off of the LED-10IM.
Devices which may be connected to the EIA-485 port include LDM graphic annunciators, ACS LED type annunciators, LED-10 Series annunciators and ACM-8RF relay modules. Included on the LDM, LED-10 Series and
ACM-8RF are switches which select an address from 01 to 32. For each device added or connected to the
EIA-485 port via the LED-10IM, select an address on each
, with the exception of the ACM-8RF (refer to the
applications section of the ACM-8RF Manual). Addresses must be sequential with no gaps allowed. For example, if 13 devices are connected to the EIA-845 port, the maximum monitored address value entered into locations
02-03 must be 02 = '1' and 02 = '3'. If 25 devices are connected to the EIA-485 port, the maximum monitored
address entered into locations 02-03 must be 02 = '2' and 03 = '5'.
All devices connected to the EIA-485 are fully supervised by the FACP. Note that AFM annunciators occupy
address '01'. The address of these annunciators cannot be altered. When using AFM devices with ACS series
annunciators, LDMs, LED-10 Series and ACM-8RFs, be certain that none of the other devices are set to address
'01'. Factory default entry is 02 = 0 and 03 = 1.
60
Document #50193 Rev.E 01/30/02 P/N 50193:E
Program Options
Printer Installed (04)
The factory default entry of '0' in address 04 informs the FACP that a printer is not connected to the panel. This
entry must be changed to '1' if a printer is connected. The PRT-24 printer interface module must be installed on J4
of the MS-5210UD main circuit board before a printer can be installed.
Printer Baud Rate (05)
Address 05 is used to set the Baud Rate when a printer is connected to the MS-5210UD. The factory default entry
is '0' for 2400 Baud. Enter '1' for 4800 Baud or '2' for 9600 Baud. An entry in address 05 is valid only if a printer
has been enabled in address 04.
NAC/Relay Option Module (06)
A Notification Appliance Circuit/Relay Option (NAC-REM) Module is available which adds two Style Z
(Class A) NAC circuits (NACs 3 and 4) and two programmable Form-C relays (Relays 3 and 4). The factory
default setting for address 06 is '0' for no module installed. This entry must be changed to '1' if the NAC/Relay
module is installed.
Programmable Relay 3 Definition (07)
This address programs Relay 3 if the NAC/Relay Option Module has been enabled in address 06. The factory
default entry for Relay 3 is '1' for supervisory. Enter '0' for alarm; '2' for supervisory autoresettable; '3' for trouble;
'4' for communication fail; '5' for process monitoring; '6' for autoresettable process monitoring.
Programmable Relay 4 Definition (08)
This address programs Relay 4 if the NAC/Relay Option Module has been enabled in address 06. The factory
default entry for Relay 4 is '4' for communication fail. Enter '0' for alarm; '1' for supervisory; '2' for supervisory
autoresettable; '3' for trouble; '5' for process monitoring; '6' for autoresettable process monitoring.
NAC #3 Type Selection (09)
This address programs NAC #3 if the NAC/Relay Option Module has been enabled in address 06. The factory
default entry for NAC #3 is '0' for enabled and silenceable. Enter '1' for enabled and nonsilenceable or '2' for disabled.
NAC #3 Silence Inhibit (10)
This address is used for the silence inhibit feature on NAC #3 if the NAC/Relay Option Module has been enabled
in address 06. The factory default entry for NAC #3 is '0' for no silence inhibit. Enter '1' to enable the silence
inhibit feature for NAC #3. This will prevent the silencing of NAC #3 for one minute following activation of an
alarm.
NAC #3 Autosilence (11)
This address is used for the autosilence feature on NAC #3 if the NAC/Relay Option Module has been enabled in
address 06. The factory default entry for NAC #3 is '0' for no autosilence. If you wish NAC #3 to be automatically silenced after one of the following lengths of time (requires prior approval of Local AHJ), enter '1' for 5 minutes; '2' for 10 minutes; '3' for 15 minutes; '4' for 20 minutes; '5' for 25 minutes; or '6' for 30 minutes.
NAC #3 Signal Coding (12)
This address is used to select coding for NAC #3 if the NAC/Relay Option Module has been enabled in address
06. The factory default entry for NAC #3 is '0' for steady output (no coding). Enter '1' for March Time coding
(120 ppm); '2' for California Time coding (10 secs. On, 5 secs. Off); or '3' for Temporal Time coding (½ sec. On, ½
sec. Off, ½ sec. On, ½ sec. Off, ½ sec. On, 1½ secs. Off, and then repeat sequence).
NAC #4 Type Selection (13)
This address programs NAC #4 if the NAC/Relay Option Module has been enabled in address 06. The factory
default entry for NAC #4 is '0' for enabled and silenceable. Enter '1' for enabled and nonsilenceable or '2' for
disabled.
Document #50193 Rev. E 01/30/02 P/N 50193:E
61
Program Options
NAC #4 Silence Inhibit (14)
This address is used for the silence inhibit feature on NAC #4 if the NAC/Relay Option Module has been enabled
in address 06. The factory default entry for NAC #4 is '0' for no silence inhibit. Enter '1' to enable the silence
inhibit feature for NAC #4. This will prevent the silencing of NAC #4 for one minute following activation of an
alarm.
NAC #4 Autosilence (15)
This address is used for the autosilence feature on NAC #4 if the NAC/Relay Option Module has been enabled in
address 06. The factory default entry for NAC #4 is '0' for no autosilence. If you wish NAC #4 to be automatically silenced after one of the following lengths of time (requires prior approval of Local AHJ), enter '1' for 5 minutes; '2' for 10 minutes; '3' for 15 minutes; '4' for 20 minutes; '5' for 25 minutes; or '6' for 30 minutes.
NAC #4 Signal Coding (16)
This address is used to select coding for NAC #4 if the NAC/Relay Option Module has been enabled in address
06. The factory default entry for NAC #4 is '0' for steady output (no coding). Enter '1' for March Time coding
(120 ppm); '2' for California Time coding (10 secs. On, 5 secs. Off); or '3' for Temporal Time coding (½ sec. On,
½ sec. Off, ½ sec. On, ½ sec. Off, ½ sec. On, 1½ secs. Off, and then repeat sequence).
Supervisory Annunciation (17)
This address, when programmed to a '1', causes the annunciators (LDM, AFM, LED-10 Series) to indicate a
supervisory alarm by turning on the appropriate yellow zone LED only. The yellow zone LED blinks at a ½ second ON/½ second OFF rate in alarm. It blinks at a 1 second ON/1 second OFF rate if the supervisory zone is in
fault. Should both an alarm and a fault occur on a supervisory zone at the same time, the alarm takes priority and
the blink rate is ½ second ON/½ second OFF.
The non-supervisory function will turn on the red zone alarm LED for any type of zone function. The blink rate at
the annunciators is 1 second ON/1 second OFF for fire alarm, ½ second ON/½ second OFF for supervisory alarm
and ¼ second ON/¼ second OFF for process monitored alarm. The default entry is '0' for non-supervisory
annunciation. Enter '1' for Supervisory Annunciation.
Note: UL requires slide-in labels on all annunciators to be clearly marked as to the function of each zone.
!
CAUTION: When selecting this function, be aware that ACM-8RF relays programmed for alarm will not
for supervisory alarms.
activate
3.3.4 Level Four - Upload/Download Option
Each option of the Program Mode is entered by keying in the program mode entry code (7764) and pressing the
[ENTER/STORE] key.
7764 spells PROG on a Touch-Tone
☛
If an incorrect key is entered, reenter the proper 4-digit code before
You are allowed a pause of up to 10 seconds in between each number while entering the code. After pressing the
[ENTER/STORE] key, the control panel will be in Program Mode and display P__1, with the '1' flashing. Press 4
on the keypad and then the [ENTER/STORE] key to choose the Upload/Download Option. You are allowed up to
ten minutes of idle time at this point before starting your programming, otherwise, the control panel will return to
Normal Mode. You also have a maximum of 10 minutes between any key stroke. All entries made prior to the 10
minute time-out are valid and are stored.
62
Document #50193 Rev.E 01/30/02 P/N 50193:E
®
phone
pressing the [ENTER/STORE] key.
Program Options
Upon entering the Upload/Download Option in programming mode, the following will be displayed on the FACP
LCD.
00_0
(address)(data)
The first three locations on the left of the display represent the memory address 00. The last location 0 (farthest right)
represents the contents of memory address 00 which is the first digit of the Panel Identification Number. To change
the Panel ID Number, key in the first of the four digits for the ID. Increment to the next address and key in the second
number. Continue until all digits are programmed. Use the Up and Down Arrow keys to increment to the next
address or decrement to the previous address.
When desired changes have been completed, exit programming mode by pressing the MODE key, followed by the
4-digit code for an alternate mode and then the [ENTER/STORE] key. To enter a different Programming Level,
press MODE and then press the [ENTER/STORE] key. The display will show P__4 with the '4' flashing. Press the
digit (1, 2 or 3) of the Programming Level to be accessed. During Program Mode, if no key is pressed within 10 minutes, the panel will revert to Normal Mode.
The MS-5210UD can be programmed remotely from a PC using a modem and the telephone line. Information can
also be retrieved from the FACP with the same method. The Upload/Download Option allows an operator to set the
necessary parameters to allow the uploading and downloading of data between the FACP and PC.
Following are the various parameters and their addresses.
Panel Identification Number (00-03)
The Panel Identification Number is a 4-digit code (valid digits being 0-F) that is used to identify the installed
panel. This code is separate form the 8-digit secret code loaded in by the Service Terminal. It is important to program this 4-digit code at the job site the first time that downloading is performed so that the called Service Terminal can identify the control panel. Factory default is '0000'. (Future use).
Service Terminal Number 1 Phone Number (04-19)
Addresses 04 through 19 are reserved for the Service Terminal Number 1 phone number. Factory default is all Fs.
Valid entries are 0-9 plus A, B, C, D and E. Use 'F' to designate the end of the phone number.
Ring Count on Primary Phone Line (20-21)
Use this address to designate the number of rings allowed on the primary phone line prior to answering an incoming call from a Service Terminal. Factory default is 25 meaning the panel will not answer an incoming call until
25 rings are detected. This entry may be programmed up to a maximum of 25 rings. A setting of 00 prevents the
panel from answering incoming calls.
FAX/Answer Machine, Primary Phone Line (22)
This entry is used when the primary phone line is being shared with a FAX, answering machine or other device.
Factory default is '0', no sharing of the primary phone line. An entry of '1' indicates that another device is sharing
the primary phone line. The panel will wait for three consecutive calls from the Service Terminal spaced 30 seconds apart, before responding.
Service Terminal Number 2 Phone Number (23-38)
Addresses 23 through 38 are reserved for the Service Terminal Number 2 phone number. Factory default is all Fs.
Valid entries are 0-9 plus A, B, C, D and E. Use 'F' to designate the end of the phone number.
Ring Count on Secondary Phone Line (39-40)
Use this address to designate the number of rings allowed on the secondary phone line prior to answering an
incoming call from a Service Terminal. Factory default is 25, meaning the panel will not answer an incoming call
until 25 rings are detected. This entry affects the secondary phone line only. This entry may be programmed up to
a maximum of 25 rings. A setting of 00 prevents the panel from answering incoming calls.
Document #50193 Rev. E 01/30/02 P/N 50193:E
63
Program Options
FAX/Answer Machine, Secondary Phone Line (41)
Factory default is '0' for no sharing of the secondary phone line with a FAX, answering machine or other device.
An entry of '1' allows the panel to wait for three consecutive calls spaced 30 seconds apart from the Service Terminal before responding.
Upload/Download Reports Sent to Secondary Central Station Phone #, Backup or Always (42)
Leaving address 42 = 0 means that reports for request for 'upload/download', 'successful upload', 'successful
download' and 'failed upload/download' will be sent to the secondary Central Station phone number only if
attempts to the primary Central Station phone number are unsuccessful. Programming a '1' causes all reports to be
transmitted to both primary and secondary phone numbers. Factory default is '0' for secondary backup only.
Enter '1' to transmit to both Central Station phone numbers. Enter '2' to transmit to the first available receiver.
CAUTION: Do not alter entry while the communicator is active.
!
3.3.5 Default Programming
To return all program entries in all four levels to their factory original settings, perform the following steps only when
the system is idle in Normal standby condition:
Press the MODE key followed by the 4-digit code 3337 and press the [ENTER/STORE] key.
3337 spells DEFP (DEFault Programming) on a Touch-Tone
☛
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key.
®
phone.
Within five seconds, repeat this entry by again pressing the MODE key followed by the 4-digit code 3337 and
pressing the [ENTER/STORE] key. The display will read 3337 while the E
2
nonvolatile memory (storage area
for all programming options) is being reprogrammed with the original default settings. When reprogramming is
complete, the display will be blank.
64
Document #50193 Rev.E 01/30/02 P/N 50193:E
Operating Instructions
CHAPTER 4Operating Instructions
FIGURE 4-1:
New and Old Keypad/Display
New - with ACK letteringOld - without ACK lettering
The MS-5210UD has several modes of operation including Normal, Program, Walk Test, Troubleshoot, History,
Lamp Test, Print and Upload/Download. There are also four function modes which include Drill, Zone Enable/Disable, NAC Enable/Disable and Default Programming. Upon initial power-up, the system will be in Normal Mode.
This section discusses operation of the control panel in the Normal Mode.
4.1Switch Functions in Normal Mode
RESET
The System Reset switches reset the system and any smoke detectors. Reset switches may be located on the FACP
keypad (illustrated in Figure 4-1), any of the ten zones programmed as a remote reset switch, remotely on any of
the LED-10 Series annunciators, the LDM graphic annunciators, or the AFM series annunciators. If any of the
System Reset Switches are pressed, the control panel will:
✓Clear the display and status LEDs
✓Turn off the Notification Appliance Circuits
✓Reset all zones by temporarily removing power
✓Silence the onboard piezo sounder
✓Store 'reset' message in the History file
✓Restore all system relays to normal
✓Temporarily remove power from the resettable power output TB2 Terminals 3 and 4
✓Output 'reset' message to printer
Any alarm, supervisory or trouble condition that exists after a system reset, will resound the system, reactivating
normal system activity. Upon release of a System Reset Switch, the FACP display will read rES_ for 6 seconds.
Document #50193 Rev. E 01/30/02 P/N 50193:E
65
Switch Functions in Normal Mode
SILENCE
Silence switches may be located on the FACP keypad (illustrated in Figure 4-1), any of the ten zones programmed
as a remote silence switch, remotely located on any of the LED-10 Series annunciators, the LDM graphic annunciators, or the AFM series annunciators. The Silence Switch performs the same functions as the System
Acknowledge switch. In addition, if any of the System Silence switches are pressed, the following will occur:
✓
The silenceable Notification Appliance Circuits will be turned OFF
✓
The main circuit board silence LED will be turned ON
✓
The SILn message will be displayed (where n = NAC #)
✓
The system piezo sounders will be shut OFF
✓
'NAC #N Silenced' message will be stored in the History file
✓
'NAC #N Silenced' message will be sent to the printer
Upon the occurrence of a subsequent event (alarm or trouble), System Silence is overridden and the control panel
will respond to the new event. The System Silence switches will be ignored for nonsilenceable waterflow type
alarms.
ACKNOWLEDGE/STEP
Acknowledge/Step switches (Up/Down arrow keys) are located on newer model FACP keypads (refer to Figure 4-
1), remotely located on any of the LED-10 Series annunciators, the LDM graphic annunciators, or the AFM series
annunciators and an option exists that allows any of the ten zones to be programmed to function as a remote
Acknowledge switch.
The Acknowledge/Step switch silences the system piezo sounders and changes all flashing system LEDs to
steady. An acknowledge message is sent to the printer and history files. The Step function permits scrolling
through multiple stored events during normal, history and walktest modes.
When more than one event exists, the first press of the Acknowledge/Step switch silences the system piezo sounders and changes all flashing system LEDs to steady. The second press of the switch stops the scrolling and holds
the event on the display for five seconds. Subsequent pressing of the switch 'steps' through each active event. The
Acknowledge/Step switch must be pressed within 15 seconds to prevent NACs from turning on if alarm presignal
is selected. For additional information on alarm presignal, refer to “Programming Instructions” on page 39.
Note: Software P/N: MS-52102.0 or greater supports the Acknowledge key function at the FACP keypad.
DRILL
Drill switches may be located on any of the ten zones programmed as a remote drill switch, remotely on any of the
LED-10 Series annunciators, the LDM graphic annunciators, or the AFM series annunciators. To perform a drill
from any of these switches, the Drill switch must be pressed and held for two seconds (time to prevent accidental
activation). The MS-5210UD turns on all NACs and turns off the system silence LEDs. The message shown on
the display is dril. The drill message is sent to the printer and history files. The system silence keys will silence
all silenceable NACs during a fire drill.
To perform a drill from the FACP, press the MODE key followed by the code 3745 then press [ENTER/STORE]. The display will read dril. The alarm relay is not activated. There is an option to transmit the fire drill
report code to the Central Station. During a fire drill, the SILENCE key will silence all silenceable NACs and the
RESET key restores the panel to normal. All zones remain active during a fire drill.
MODE
Pressing the Mode switch followed by a valid 4-digit numerical code and [ENTER/STORE] selects one of the
six modes of operation.
To enter Normal Mode from any other mode press MODE then 6676 [ENTER/STORE].
6676 spells NORM on a Touch-Tone
☛
®
phone.
1st EVENT
The 1st Event switch along with the Up Arrow and Down Arrow keys, are used to display any presently active
alarm and/or fault conditions present in the system. Press the 1st Event switch at any time to display the first
event (alarm and/or trouble) that occurred.
66
Document #50193 Rev.E 01/30/02 P/N 50193:E
LED Display and Status LEDs
DOWN ARROW (ACK)
Use the Down Arrow key to view other events (older) that have occurred and are active (not yet cleared). It also
acknowledges the event by silencing the local piezo sounder.
UP ARROW (ACK)
Use the Up Arrow key to view other events (newer) that have occurred and are active (not yet cleared). It also
acknowledges the event by silencing the local piezo sounder.
[ENTER/STORE]
Refer to the individual mode descriptions in previous sections of this manual. In Normal Mode, this key is used
after pressing the MODE key followed by a 4-digit mode code followed by the [ENTER/STORE] key.
4.2LED Display and Status LEDs
LED Display
Four 7-Segment red LED characters provide visual annunciation of status, events and messages. A list of messages that may appear on the display in Normal Mode is shown below:
d__1 Zone 1 DisabledF__9Trouble Zone 9
d__2 Zone 2 DisabledF_10Trouble Zone 10
d__3 Zone 3 DisabledF_85Annunciator Bus Fault
d__4 Zone 4 DisabledF__AAnnunciator Fault
d__5 Zone 5 DisabledF__EEarth Fault
d__6 Zone 6 DisabledF__PPrinter Fault
d__7 Zone 7 DisabledLo_bLow Battery
d__8 Zone 8 Disabledno_bNo Battery
d__9 Zone 9 DisabledPH_1Primary C.S. No. Comm. Fault
d_10 Zone 10 DisabledPH_2Secondary C.S. No. Comm. Fault
d_b1 NAC/Bell #1 DisabledbEL1Bell 1 Fault
d_b2 NAC/Bell #2 DisabledbEL2Bell 2 Fault
d_b3 NAC/Bell #3 DisabledbEL3Bell 3 Fault
d_b4 NAC/Bell #4 DisabledbEL4Bell 4 Fault
drLL Fire Drillno_1Primary Phone Line Fault
E__1 Zone 1 Enabledno_2Secondary Phone Line Fault
E__2 Zone 2 EnabledPA_1Process Monitoring Alarm Zone 1
E__3 Zone 3 EnabledPA_2Process Monitoring Alarm Zone 2
E__4 Zone 4 EnabledPA_3Process Monitoring Alarm Zone 3
E__5 Zone 5 EnabledPA_4Process Monitoring Alarm Zone 4
E__6 Zone 6 EnabledPA_5Process Monitoring Alarm Zone 5
E__7 Zone 7 EnabledPA_6Process Monitoring Alarm Zone 6
E__8 Zone 8 EnabledPA_7Process Monitoring Alarm Zone 7
E__9 Zone 9 EnabledPA_8Process Monitoring Alarm Zone 8
E_10 Zone 10 EnabledPA_9Process Monitoring Alarm Zone 9
A__1 Alarm Zone 1PA10Process Monitoring Alarm Zone 10
A__2 Alarm Zone 2SIL1NAC/Bell #1 Silenced
A__3 Alarm Zone 3SIL2NAC/Bell #2 Silenced
A__4 Alarm Zone 4SIL3NAC/Bell #3 Silenced
A__5 Alarm Zone 5SIL4NAC/Bell #4 Silenced
A__6 Alarm Zone 6SU_1Supervisory Alarm Zone 1
A__7 Alarm Zone 7SU_2Supervisory Alarm Zone 2
A__8 Alarm Zone 8SU_3Supervisory Alarm Zone 3
A__9 Alarm Zone 9SU_4Supervisory Alarm Zone 4
A_10 Alarm Zone 10SU_5Supervisory Alarm Zone 5
F__1 Trouble Zone 1SU_6Supervisory Alarm Zone 6
F__2 Trouble Zone 2SU_7Supervisory Alarm Zone 7
F__3 Trouble Zone 3SU_8Supervisory Alarm Zone 8
F__4 Trouble Zone 4SU_9Supervisory Alarm Zone 9
F__5 Trouble Zone 5SU10Supervisory Alarm Zone 10
F__6 Trouble Zone 6_AC_AC Power Loss
F__7 Trouble Zone 7rES_System Reset
F__8 Trouble Zone 8
Document #50193 Rev. E 01/30/02 P/N 50193:E
67
LED Display and Status LEDs
System Fire Alarm LED
A red LED that flashes when a fire alarm condition is detected during the alarm presignal period. It turns on
steady when the system silence or acknowledge switches are pressed.
System Trouble LED
A yellow LED that blinks to indicate that a fault or abnormal condition exists and that the fire alarm system may
be inoperative. It turns on steady when a system silence or acknowledge switch is pressed.
AC Power On LED
A green LED that remains on while the AC power supply is within correct limits. If this indicator fails to light
under normal conditions, service the system immediately.
Supervisory LED
A yellow LED that blinks to indicate the need for action in connection with the supervision or maintenance of
sprinklers, extinguishing systems or other protective systems.
System Silence LED
A yellow LED that turns on to indicate that an Alarm or Trouble condition exists in the system, but Notification
Appliance Circuits (if programmed as silenceable) and local piezo sounder have been silenced.
Primary Line Active LED
A red LED that indicates the primary phone line is active.
Secondary Line Active LED
A red LED that indicates the secondary phone line is active.
Kiss-Off LED
A green LED that blinks when a Central Station has acknowledged receipt of each transmitted message or when a
portion of up or download data has been accepted from a Service Terminal.
Modem LED
A green LED that stays on steady during modem types of communications.
FIGURE 4-2:
Phone Connectors and LEDs
Kissoff LED
Primary Phone Line
68
Primary Active LED
Secondary Phone Line
Secondary Active LED
Modem LED
Document #50193 Rev.E 01/30/02 P/N 50193:E
Operation
4.3Operation
Normal Mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When
no alarm or trouble conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED).
The Notification Appliance Circuits will be off, all relays are in their normal state, the onboard piezo sounder will be
off and the printer (if connected) will not be printing. The Primary and Secondary Phone Line Active LEDs are off
since the communicator is not active.
All alarm and system trouble conditions are annunciated on the control panel's display. The control panel will maintain an 'active event list' which will consist of all alarms, supervisory alarms and system troubles currently active and
not cleared, requiring immediate service. When the system is cleared and restored to normal, the display will be
blank. All alarms and troubles are stored in a history file and may be recalled at any time.
Higher priority events take precedence over lower priority events. Display and reporting of System Status is done on
a priority basis. Priorities are, from highest to lowest:
Alarms
1.
Supervisory Alarms
2.
System Troubles
3.
Process Monitoring Alarms
4.
If the events to be displayed consist of alarms and disabled zones only (no troubles), the control panel will scroll them
on the display. As each new alarm occurs, it will be displayed immediately on the display for five seconds. After this
five second period, the display will scroll all alarms in the system. Pressing the 1st Event key or one of the 'ACK'
keys will stop the scrolling. The 1st Event key will also cause the display to show the First alarm that occurred after
the panel was last reset, cleared of all active events and placed into normal mode. Operation of the Up and Down
arrow keys will display all remaining events in sequence.
If events to be displayed include system troubles, only one event is displayed at a time and there is no scrolling. The
event displayed is the highest priority. Pressing the 1st Event key will cause the display of the first event that occurred
after the panel was last reset, cleared of all active events and placed into normal mode. Operation of the Up and Down
arrow keys will display all remaining events in order of their occurrences.
4.3.1 Fire Alarm Response
The control panel will, upon detection of an alarm condition, cause the following:
• Blink the FACP alarm LED (1 second On, 1 second Off)
• Display the alarm message (i.e. A__1 Alarm on Zone 1)
• Communicate the alarm to the Central Station
• Store the alarm in the History File
• Turn the Notification Appliance Circuits on
• Turn the piezo sounder on steady
• Turn on appropriate zone relay output (ACM-8RF)
• Turn on any system relays (main circuit board) programmed for alarm activation
• Output alarm message to printer
• Terminate upload or download communications
• Blink all remote annunciator general alarm LEDs (1 second On, 1 second Off)
• Blink all remote annunciator zone alarm LEDs (1 second On, 1 second Off)
Note that when any zone is programmed as a supervisory or process monitored zone, it will not be processed in the
same manner as a conventional alarm zone. Refer to “System Supervisory Condition Response” on page 70 and
“Process Monitored Alarm Response” on page 72.
Document #50193 Rev. E 01/30/02 P/N 50193:E
69
Operation
4.3.2 Fire Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system reset switch has been pressed
(pull stations have been reset, smoke detectors have reset and no smoke is present, waterflow has stopped). The control panel will perform the following upon restoral of all active alarms:
• Turn off the FACP alarm LED
• Clear the 4-character display
• Send all 'Zone Restoral' messages to the Central Station
• Turn off the Notification Appliance Circuits
• Turn off the piezo sounder
• Turn off appropriate zone relay output (ACM-8RF)
• Turn off any system relays (main circuit board) programmed for alarm activation
• Output alarm restoral message to printer
• Terminate upload or download communications
• Turn off all remote annunciator general alarm LEDs
• Turn off all remote annunciator zone alarm LEDs
4.3.3 System Supervisory Condition Response
Program zones for Supervisory in applications where a waterflow sensing device has been employed and the wiring
to the waterflow valve and/or a tamper switch is to be monitored. If the tamper switch has been activated (Normally
Open contacts close), a supervisory alarm condition will occur.
When a supervisory condition occurs, the control panel will cause the following:
• Blink the FACP supervisory LED (½ second On, ½ second Off)
• Display the following message: SUXX (XX=Zone Number)
• Communicate the supervisory condition to the Central Station
• Store the 'supervisory' message in the History File
• Pulse system piezo sounders (½ second On, ½ second Off)
• Turn on appropriate zone relay output (ACM-8RF)
• Turn on any system relays (main circuit board) programmed for supervisory activation
• Output system supervisory message to printer
• Terminate upload or download communications
• Blink all remote annunciator general supervisory alarm LEDs (½ second On, ½ second Off)
• Blink all remote annunciator zone supervisory alarm LEDs (½ second On, ½ second Off)
4.3.4 System Supervisory Restoral Response
When the supervisory condition has been cleared (condition is restored and the reset switch has been pressed), the
control panel will perform the following:
• Turn off the supervisory LED
• Clear the display of the 'SUXX'
• Communicate a supervisory restoral message to the Central Station
• Shut off system piezo sounders
• Turn off appropriate zone relay output (ACM-8RF)
• Turn off any system relays (main circuit board) programmed for supervisory activation
• Output system supervisory restoral message to printer
• Terminate upload or download communications
• Turn off all remote annunciator general supervisory alarm LEDs
• Turn off all remote annunciator zone supervisory alarm LEDs
Note that for any zone programmed for Supervisory autoresettable, the Reset key does not need to be pressed to clear
the zone (supervisory condition).
70
Document #50193 Rev.E 01/30/02 P/N 50193:E
Operation
4.3.5 Trouble Condition Response
The control panel will perform the following upon detection of one or more trouble conditions:
• Blink the FACP trouble LED (1 second On, 1 second Off)
• Blink all annunciator general system trouble LEDs
• Blink all affected zone trouble LEDs on all system annunciators
• Activate any FACP trouble relay(s) if programmed for trouble activation
• Display the appropriate trouble message(s) in priority fashion from the highest priority to the lowest. Note that
the Up arrow key, Down arrow key or 1st Event key must be pressed to view the messages.
• Communicate the trouble conditions to the Central Station
• Store the trouble conditions in the History File
• Sound system piezo sounders at a rate of 1 second On, 1 second Off
• Output the system trouble messages to the printer
• Terminate upload or download communications
Note that when AC Brownout occurs, the AC LED is turned off and the Trouble LED blinks. Should the brownout condition remain, it will be transmitted to the Central Station after a delay (see Program Address 77 in the Level 1 Main
Panel Options section).
Possible trouble messages that may appear on the display are as follows:
_AC_AC Loss (shown only when requested)
d__1 Zone 1 DisabledF__10 Trouble Zone 10
d__2 Zone 2 Disabledd_b1Bell 1 Disabled
d__3 Zone 3 Disabledd_b2Bell 2 Disabled
d__4 Zone 4 Disabledd_b3Bell 3 Disabled
d__5 Zone 5 Disabledd_b4Bell 4 Disabled
d__6 Zone 6 DisabledF__AAnnunciator Fault
d__7 Zone 7 DisabledF__PPrinter Fault
d__8 Zone 8 DisabledF__EEarth Fault
d__9 Zone 9 DisabledLo_bLow Battery
d_10 Zone 10 Disabledno_bNo Battery
F__1 Trouble Zone 1PH_1Primary C.S. No. Comm. Fault
F__2 Trouble Zone 2PH_2Secondary C.S. No. Comm. Fault
F__3 Trouble Zone 3bEL1Bell 1 Fault
F__4 Trouble Zone 4bEL2Bell 2 Fault
F__5 Trouble Zone 5bEL3Bell 3 Fault
F__6 Trouble Zone 6bEL4Bell 4 Fault
F__7 Trouble Zone 7no_1Primary Phone Line Fault
F__8 Trouble Zone 8no_2Secondary Phone Line Fault
F__9 Trouble Zone 9
4.3.6 Trouble Condition Restoral
The control panel performs the following upon restoral of all trouble conditions:
• The trouble LED is shut Off
• FACP trouble relay(s) deactivate if programmed for trouble activation
• If the trouble was loss of AC power, the control panel will turn on the AC LED upon restoral
• Clear the FACP display of trouble message(s)
• Communicate the restored trouble condition(s) to the Central Station
• Output the system trouble restoral message to the printer
• Terminate upload or download communications
• Turn off the system general trouble LED on all system annunciators if all trouble conditions are cleared
• Turn off all affected zone trouble LEDs on all system annunciators
Document #50193 Rev. E 01/30/02 P/N 50193:E
71
Operation
4.3.7 Process Monitored Alarm Response
Upon detection of a critical or noncritical process monitored alarm condition on any zone, the control panel will:
• Display the alarm message PAXX (where XX = zone number)
• Communicate the alarm code programmed for the activated zone
• Store the alarm in the History File
• Pulse the piezo sounder at a ¼ second On, ¼ second Off
• Turn on appropriate zone relay output (ACM-8RF)
• Turn on any system relays (main circuit board) programmed for process alarm activation
• Output alarm message to printer
• Terminate upload or download communications
• Blink all remote annunciator zone alarm LEDs (¼ second On, ¼ second Off)
4.3.8 Process Monitored Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system reset switch has been pressed
(process monitored alarm devices reset). The control panel will perform the following upon restoral of all active process monitored alarms:
• Clear the 4-character display
• Communicate the alarm restoral code programmed for the activated zone
• Store the alarm restoral message in the History File
• Turn off the piezo sounder
• Turn off appropriate zone relay output (ACM-8RF)
• Turn off any system relays (main circuit board) programmed for process alarm activation
• Output alarm restoral message to printer
• Terminate upload or download communications
• Turn off all remote annunciator zone alarm LEDs
Note that for any zone programmed for autoresettable process monitored alarm, the reset key does not need to be
pressed to clear the zone.
4.3.9 OFF Normal Reporting
Removing the panel from Normal Mode and placing it into Troubleshoot, Walktest or Program Mode causes a transmission of an 'off normal' fault message. Returning the panel to Normal Mode causes a transmission of a 'return to
normal' restoral message.
4.3.10Zone Disable/Enable
The zone disable feature may be used to disable any zone in the system. While in Normal Mode or Walktest Mode,
zones may be disabled if they are normal, in trouble or alarmed. If the panel is in alarm, the silence switch must be
pressed first before zone disable will function in Normal Mode.
To disable a zone, press the MODE key once, (the display will go blank). You then have 10 seconds to start entering
the code 3472. Next, press the [ENTER/STORE] key.
®
phone.
72
3472 spells DISA on a Touch-Tone
☛
Document #50193 Rev.E 01/30/02 P/N 50193:E
Operation
A flashing lower case d will appear on the far left of the display. Next, press the zone number to be disabled. The
number will appear on the far right display character. Press [ENTER/STORE]. The zone is disabled. All system
annunciators will show zone troubles and general trouble status. Note that the trouble relay is activated and the trouble LED blinks.
The zone disable message will remain on the display until the zone is reenabled. To reenable a zone, press the MODE
key once (the display will go blank). You then have 10 seconds to start entering the code 3622. Next, press the
[ENTER/STORE] key.
3622 spells ENAB on a Touch-Tone
☛
®
phone.
A flashing upper case E will appear on the left of the display. Next, press the zone number to be enabled. The number will appear on the far right display character. Press [ENTER/STORE]. The zone is reenabled. Note that the
trouble relay is restored to normal and the FACP trouble LED is off and all system annunciator zone trouble LEDs are
off.
4.3.11NAC (bell) Disable/Enable
The NAC/bell disable feature may be used to disable any of the four main panel NAC/bell circuits. While in Normal
Mode, NACs may be disabled if they are normal, in trouble or alarmed.
To disable an NAC/bell, press the MODE key once (the display will go blank). You then have 10 seconds to start
entering the code 3472. Next, press the [ENTER/STORE] key.
3472 spells DISA on a Touch-Tone
☛
®
phone.
A flashing lower case d will appear on the far left of the display. Next, press the b key followed by the NAC number
to be disabled. The b and the NAC number will appear on the far right display characters. Pressing [ENTER/STORE] will disable the NAC. All system annunciators will show general trouble status and the main panel display
will show the NAC disabled message, turn on the system trouble LED and activate relays programmed for system
trouble.
The NAC disable message will remain on the display until the circuit is reenabled. To reenable an NAC, press the
MODE key once (the display will go blank). You then have 10 seconds to start entering the code 3622. Next, press
the [ENTER/STORE] key.
3622 spells ENAB on a Touch-Tone
☛
®
phone.
A flashing upper case E will appear on the left of the display. Next, press the b key followed by the NAC number to
be enabled. The b and the NAC number will appear on the far right display characters. Pressing [ENTER/STORE]
will reenable the NAC. Note that relays programmed as trouble are restored to normal and the FACP trouble LED is
off and all system annunciator general trouble LEDs are off.
4.3.12Fire Drill
The DRILL (manual evacuate) feature turns on all Notification Appliance Circuits (if programmed as enabled) and
turns off the silence LED. To perform a fire drill, press the MODE key followed by the code 3745 then the [ENTER/STORE] key. The display will read drLL. The alarm relay is not activated. There is an option to transmit the fire
drill report code to the Central Station.
3745 spells dril on a Touch-Tone
☛
®
phone.
During a fire drill, the SILENCE key will silence the silenceable Notification Appliance Circuits and the RESET key
restores the panel to normal. All zones remain active during a fire drill.
Document #50193 Rev. E 01/30/02 P/N 50193:E
73
Central Station Communications
4.4Central Station Communications
The control panel transmits zone and system status reports to central stations via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two
7-foot (2.13 m) telephone cords P/N MCBL-7 may be used for this purpose.
The control panel supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault
in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound,
the yellow trouble LED will blink, the 4-character display will show either 'no_1' (primary phone line) or 'no_2' (secondary phone line), depending upon which telephone line has the fault, and the trouble condition will be reported to a
central station over the remaining good phone line.
The control panel comes with line seizure capability provided for both the primary and secondary telephone line
interfaces. Any time that the control panel needs to make a call to a central station, line seizure will disconnect any
local premises phones sharing the same telephone line.
All transmissions to central stations will be sent over the Primary Central Station phone line. In the event of noisy
phone lines, transmissions will be sent over the backup Secondary phone line.
Two phone numbers must be programmed, the Primary Central Station phone number and the Secondary Central Station phone number. There are three options for transmission to the central station:
• All messages are always sent to the Primary Central Station phone number with the Secondary Central Station
phone number for emergency backup purposes only.
• All reports are sent to both central station phone numbers.
• Reports are sent to the first available central station phone number only.
If 10 total attempts to communicate are unsuccessful, system relays programmed for Communications Failure will be
activated. The FACP will also display 'PH1' for Communicator Failure to the Primary Central Station phone number
or 'PH2' for Communicator Failure to the Secondary Central Station phone number.
The MS-5210UD meets NFPA 72 National Fire Code reporting requirements for the type of signal, condition and
location of the reporting premises. The general priority reporting structure is:
Zone Alarms and Restores
1.
Zone Trouble and Restores
2.
System Troubles and Restores
3.
24-hour test
4.
74
Document #50193 Rev.E 01/30/02 P/N 50193:E
Central Station Communications
The control panel is capable of reporting detailed messages depending upon the format in use. Table 4-1 shows the
reporting structure for all formats.
TABLE 4-1:
Format Selection Addresses (16+42) Programming Level 1
Format #
0, 2, 4, 6, 8
Report
3+1/4+1/Standard
4+1 Express
AlarmSSS(S) A
Alarm RestoreSSS(S) RA
Zone Trouble
(Zone Open)
SSS(S) TZ
Zone Trouble RestoreSSS(S) RTZ
System TroubleSSS(S) TS
System Trouble RestoreSSS(S) RTS
Zone DisableSSS(S) DZ
Zone Disable RestoreSSS(S) RDZ
Format #
3, 5, 7, 9
3+1/4+1/Expanded
SSS(S) A
AAA(A) Z
SSS(S) RA
RARARA(RA) Z
SSS(S) TZ
TZTZTZ(TZ) Z
SSS(S) RTZ
RTZ RTZRTZ(RTZ ) Z
SSS(S) TS
TSTSTS(TS) Y
SSS(S) RTS
RTS RTSRTS(RTS ) Y
SSS(S) DZ
DZDZDZ(DZ) Z
SSS(S) RDZ
RDZRDZRDZ(RDZ) Z
Format #
1, A, C
4+2/Standard
4+2 Express
Format #
B, D
4+2/Expanded
SSSS AA2SSSS AZ
SSSS RARA2SSSS RAZ
SSSS TZTZ2SSSS TZZ
SSSS RTZRTZ2SSSS RTZZ
SSSS TSTS2SSSS TSY
SSSS RTSRTS2SSSS RTSY
SSSS DZDZ2SSSS DZZ
SSSS RDZRDZ2SSSS RDZZ
Bell DisableSSS(S) DBSSS(S) DBSSSS DBDB2SSSS DBDB2
Bell Disable RestoreSSS(S) RBSSS(S) RBSSSS RBRB2SSSS RBRB2
No Battery RestoreSSS(S) RNSSS(S) RNSSSS RNRN2SSSS RNRN2
AC LossSSS(S) PSSS(S) PSSSS PP2SSSS PP2
AC Loss RestoreSSS(S) RPSSS(S) RPSSSS RPRP2SSSS RPRP2
Fire DrillSSS(S) FdSSS(S) FdSSSS FdFd2SSSS FdFd2
Fire Drill RestoreSSS(S) RFdSSS(S) RFdSSSS RFdRFd2SSSS RFdRFd2
Supervisory ConditionSSS(S) V
Supervisory Condition
Restore
SSS(S) RV
SSS(S) V
VVV(V) Z
SSS(S) RV
RVRVRV(RV ) Z
SSSS VV2SSSS VZ
SSSS RVRV2SSSS RVZ
Test ReportSSS(S) XSSS(S) XSSSS XX2SSSS XX2
Up or DownloadSSS(S) UDSSS(S) UDSSS UDUD2SSS UDUD2
Refer to Table 4-2 for an explanation of each letter code in Table 4-1 .
Refer to Table 4-3 for a list of compatible receivers.
Document #50193 Rev. E 01/30/02 P/N 50193:E
75
Central Station Communications
TABLE 4-2:
Format Selection Address Explanation
Where:
SSS or SSSS= Subscriber ID
A= Alarm (1st digit)
A2= Alarm (2nd digit)
Z= Zone Number
RA= Alarm Restore (1st digit)
RA2= Alarm Restore (2nd digit)
TZ= Zone Trouble (1st digit)
TZ2= Zone Trouble (2nd digit)
RTZ= Zone Trouble Restore (1st digit)
RTZ2= Zone Trouble Restore (2nd digit)
TS= System Trouble (1st digit)
TS2= System Trouble (2nd digit)
RTS= System Trouble Restore (1st digit)
RTS2= System Trouble Restore (2nd digit)
DZ= Zone Disable (1st digit)
DZ2= Zone Disable (2nd digit)
RDZ= Zone Disable Restore (1st digit)
RDZ2= Zone Disable Restore (2nd digit)
DB= Bell Disable (1st digit)
DB2= Bell Disable (2nd digit)
RB= Bell Disable Restore (1st digit)
RB2= Bell Disable Restore (2nd digit)
L= Low Battery (1st digit)
L2= Low Battery (2nd digit)
RL= Low Battery Restore (1st digit)
RL2= Low Battery Restore (2nd digit)
N= No Battery (1st digit)
N2= No Battery (2nd digit)
RN= No Battery Restore (1st digit)
RN2= No Battery Restore (2nd digit)
P= AC Loss (1st digit)
P2= AC Loss (2nd digit)
RP= AC Loss Restore (1st digit)
RP2= AC Loss Restore (2nd digit)
FD= Fire Drill (1st digit)
FD2= Fire Drill (2nd digit)
RFD= Fire Drill Restore (1st digit)
RFD2= Fire Drill Restore (2nd digit)
V= Supervisory Condition (1st digit)
V2= Supervisory Condition (2nd digit)
RV= Supervisory Condition Restore (1st digit)
RV2= Supervisory Condition Restore (2nd digit)
X= Test Report (1st digit)
X2= Test Report (2nd digit)
Y= A Trouble corresponding to the following:
1 = Earth Fault
2 = Not Used
3 = Not Used
4 = Telco Primary Line Fault
5 = Telco Secondary Line Fault
6 = NAC #1 Fault
7 = NAC #2 Fault
8 = NAC #3 Fault
9 = NAC #4 Fault
A = Communication Failure to Primary Number
B = Communication Failure to Secondary Number
C = Printer Fault
D = Annunciator Fault
E = 485 Communication Failure
F = System Off Normal
UD= Upload/Download (1st digit)
UD2= Upload/Download (2nd digit)
Note that for Expanded Reporting, the control panel automatically adds the digit corresponding to the zone number,
and the second digit corresponding to any system trouble condition. Only the first digit is programmable.
76
Document #50193 Rev.E 01/30/02 P/N 50193:E
Central Station Communications
4.4.1 Transmittal Priorities
The integral communicator transmits highest priority events first. Events in terms of priority are listed below in
descending order:
Alarms (Highest Priority Level)
1.
Pull Stations
Waterflow
Smoke Detector
Other Alarm Types
Supervisory Zone
2.
System Troubles
3.
Zone/NAC Disabled
Fire Drill
AC Fail (after delay)
Zonal faults
Earth fault
Low battery/No battery
Telephone line fault
Notification Appliance Circuits fault
Communication Trouble
Printer Trouble
Annunciator Trouble
EIA-485 fault
System Off Normal
Process Monitoring Alarm
Restoral Reports
4.
Zone Alarm
Supervisory
Zone(s) enabled
Fire Drill
AC
Zone fault
Earth
Battery
Telephone Line
Notification Appliance Circuits
Communication
Printer
Annunciator
EIA-485
System Off Normal
Process Monitoring Restored
System Test (Lowest Priority)
5.
Red LEDs are provided on the control panel circuit board to identify which telephone line is activated. Also, a green
LED labeled 'Kissoff', will turn on whenever the control panel has successfully transmitted reports to the Central Station. The 'Kissoff' LED may turn on several times during communications with a central station.
Document #50193 Rev. E 01/30/02 P/N 50193:E
77
Central Station Communications
The following table contains UL listed receivers compatible with the MS-5210UD.
TABLE 4-3:
Compatible UL Listed Receivers
Format #
(Addresses 16 & 42)
04+1 Ademco Express
14+2 Ademco Express
23+1/Standard/1800/2300
33+1/Expanded/1800/2300
43+1/Standard/1900/1400
53+1/Expanded/1900/1400
64+1/Standard/1800/2300
74+1/Expanded/1800/2300
84+1/Standard/1900/1400
94+1/Expanded/1900/1400
A4+2/Standard/1800/2300
B4+2/Expanded/1800/2300
C4+2/Standard/1900/1400
D4+2/Expanded/1900/1400
EAdemco Contact ID
(1) With 685-8 Line Card with Rev 4.4d software.
(2) With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A software.
(3) Rev. 4.0 software.
(4) FBI CP220FB Rec-11 Line Card with Rev 2.6 software and a memory card with Rev 3.8 software.
(5) Model 6500 with Rev 600 software.
(6) Model 6000 with Rev 204 software.
(7) With Rev B control card at Rev 1.4 software and Rev C line card at Rev 1.5 software.
(8) Model 2 only.
(9) Version 1.62 software.
Ademco
685(1)
Silent Knight
9000 (2)
ITI
CS-4000 (3)
FBI
CP220FB
Osborne Hoffman
Models 1 & 2
Radionics
6000 (6)
Radionics
6500 (5)
Sescoa
3000R (7)
Surguard
MLR-2 (9)
✔✔✔
✔✔✔
✔✔✔✔
✔✔✔✔
✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
✔✔✔
✔✔✔
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(8)
✔
✔ ✔✔✔ ✔
✔✔✔
✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
✔✔✔
✔✔✔
✔✔✔✔
78
Document #50193 Rev.E 01/30/02 P/N 50193:E
Servicing
CHAPTER 5Servicing
5.1Walk Test Mode
The MS-5210UD provides the capability to perform a one-man walktest of the system without triggering the communicator, the ACM-8RF zone relays, the system annunciators or the alarm output relay. Walk Test Mode allows for
testing of the 10 zones (initiating device circuits). Zones defined as Reset, Acknowledge, Silence, Drill, Autoresettable Process Monitoring or Process Monitoring are not part of the one-man walktest function. Zones defined as Pull
Station, Normally-Open Contact, two or four-wire smoke detector, waterflow or supervisory are functionally tested in
Walk Test Mode. An audible or silent walktest may be performed.
For an audible walktest, the first initiating device activated on a zone will cause the Notification Appliance Circuits to
turn on for four seconds. Subsequent device activations on the same zone will cause the Notification Appliance Circuits to turn on for one second. Any smoke detectors that are activated will be reset. Zonal faults (open circuits) will
cause the NAC to remain on steadily. Prior to entering Walk Test Mode, check to be certain that all system faults have
been cleared.
Note that trouble relays will be activated while the control panel is in Walk Test Mode. Placing the control panel into
Walk Test Mode will only be possible if the system has no active alarms.
Pressing the MODE key followed by the 4-digit code 9255 and then pressing the [ENTER/STORE] key will place
the control panel into Walk Test Mode.
9255 spells WALK on a Touch-Tone
☛
®
phone.
An S will be displayed on the left most character and a flashing 0 on the far right character. For audible walktest,
press the [ENTER/STORE] key. For silent walktest, press the 1 key followed by the [ENTER/STORE] key.
Once in Walk Test Mode, the control panel will immediately:
• Blink the trouble LED
• Activate the trouble relay
• If an audible walktest is performed, the MS-5210UD will turn on the Notification Appliance Circuits for four
seconds for the first alarm on a zone. Subsequent alarms will sound for one second. Troubles cause the NACs
to remain on. For a silent walktest, all NAC outputs remain off.
• Disable the alarm relay
• Display all alarm conditions as they occur.
• Display all zone troubles as they occur.
• Display all system troubles as they occur
• Transmit 'off normal' message to Central Station(s)
• Continue to communicate any events not acknowledged at a central station prior to entering Walk Test Mode
During Walk Test Mode, zonal activity is displayed in real time as it occurs. At the end of walktesting the system, the
display will show the last event that occurred. To view all events stored during walktest, use the Up arrow, Down
arrow and 1st Event keys. The Down arrow key moves the walktest list to show older (previous) events. The Up
arrow key moves the walktest list to show newer (more recent) events. Pressing the 1st Event key at any time will
cause the display of the first event stored upon initial entry into Walk Test Mode. While in Walk Test Mode, the control panel will store up to 256 events in the Walk Test File for later recall and display. A printer may be connected to
the panel during walktest. All walktest events are printed in real-time as they occur.
Zone disable mode may be used while in Walk Test Mode. Should a faulty device require repair, the zone may be disabled while the repair is performed. This allows the user to return the system to Normal Mode, enabling all other
zones. This also prevents triggering of a false alarm.
Document #50193 Rev. E 01/30/02 P/N 50193:E
79
History Mode
To return the control panel to Normal Mode, press the MODE key followed by the 4- digit code 6676 and then the
[ENTER/STORE] key. To go to any other mode, press the MODE key followed by the appropriate 4-digit code and
then the [ENTER/STORE] key. To go from silent walktest to audible walktest (or vice versa), press the MODE key
followed by the [ENTER/STORE] key. S__0 or S__1 will appear in the display. Simply alter the '0' or '1' entry then
press the [ENTER/STORE] key. Any delay between key entries greater than 10 seconds causes the control panel to
remain in Walk Test Mode.
The control panel will automatically revert back to Normal Mode if no system activity has occurred for 60 minutes.
This would include pressing any keys or activity on any zone. Exiting Walk Test Mode leaves the Walk Test file in
memory such that it may be printed in Print Mode. Subsequent entries into Walk Test Mode will delete the Walk Test
file.
During an audible walktest, if a device remains latched in alarm (such as a Pull Station that is not reset after activation), subsequent testing of devices on the same zone will not
trigger the NACs. Be certain to reset or clear each
device after testing.
Note that remote site upload or download is possible when the system is in Walk Test Mode.
5.2History Mode
All Normal Mode events are stored in a History File list for future recall. Recall is possible via the 4-character display or via an optional printer. See the following page for a list and description of each event displayed.
This History File list is a first-in, first-out (FIFO) buffer. Only the most recent events may be called up from memory.
Old events will be overwritten, i.e. pushed out of the FIFO. The number of stored events is 256. The History File is
kept in E
2
memory. Complete power loss will not erase the list.
Pressing the MODE key followed by the 4-digit code 4478 and then the [ENTER/STORE] key places the control
panel into History Mode. The most recent event will be displayed. This will not occur if there are any active alarm
conditions present. The fire protection remains active in History Mode. If an alarm occurs, the panel will automatically exit History Mode.
4478 spells HIST on a Touch-Tone
☛
®
phone.
Once in History Mode, the control panel will:
• Display all events as they occurred since the last time the History File list was cleared (the most recent event
being displayed first)
• Ignore all keys except those mentioned in this section
• Continue to communicate any events not previously acknowledged at the Central Station prior to entering
History Mode.
The Down arrow key moves the History File to show older (previous) events. The Up arrow key moves the History
File to show newer (most recent) events.
80
Document #50193 Rev.E 01/30/02 P/N 50193:E
History Mode
Shown below is the list of messages as they will appear on the display:
TABLE 5-1:
DISPLAYEVENTDISPLAYEVENT
ACn_Acknowledge key pressedF__EEarth Fault
A__!Zone 1 AlarmF__AAnnunciator Fault
A__2Zone 2 AlarmF__PPrinter Fault
A__3Zone 3 AlarmF_85Annunciator Bus Fault
A__4Zone 4 Alarmd__1Zone 1 disabled
A__5Zone 5 Alarmd__2Zone 2 disabled
A__6Zone 6 Alarmd__3Zone 3 disabled
A__7Zone 7 Alarmd__4Zone 4 disabled
A__8Zone 8 Alarmd__5Zone 5 disabled
A__9Zone 9 Alarmd__6Zone 6 disabled
A_10Zone 10 Alarmd__7Zone 7 disabled
SU_1Supervisory 1 Alarmd__8Zone 8 disabled
SU_2Supervisory 2 Alarmd__9Zone 9 disabled
SU_3Supervisory 3 Alarmd_10Zone 10 disabled
SU_4Supervisory 4 AlarmdrLLFire Drill
SU_5Supervisory 5 AlarmE__1Enable Zone 1
SU_6Supervisory 6 AlarmE__2Enable Zone 2
SU_7Supervisory 7 AlarmE__3Enable Zone 3
SU_8Supervisory 8 AlarmE__4Enable Zone 4
SU_9Supervisory 9 AlarmE__5Enable Zone 5
SU10Supervisory 10 AlarmE__6Enable Zone 6
PA_1Process Alarm Zone 1E__7Enable Zone 7
PA_2Process Alarm Zone 2E__8Enable Zone 8
PA_3Process Alarm Zone 3E__9Enable Zone 9
PA_4Process Alarm Zone 4E_10Enable Zone 10
PA_5Process Alarm Zone 5d_b1Disable bell 1
PA_6Process Alarm Zone 6d_b2Disable bell 2
PA_7Process Alarm Zone 7d_b3Disable bell 3
PA_8Process Alarm Zone 8d_b4Disable bell 4
PA_9Process Alarm Zone 9E_b1Enable bell 1
PA10Process Alarm Zone 10E_b2Enable bell 2
_AC_AC LossE_b3Enable bell 3
F__1Zone 1 FaultE_b4Enable bell 4
F__2Zone 2 FaultPH_1Primary C.S. Number Communication Fault
F__3Zone 3 FaultPH_2Secondary C.S. Number Communication Fault
F__4Zone 4 Faultno_bNo Battery
F__5Zone 5 FaultLo_bLow Battery
F__6Zone 6 FaultSILESilence Switch Pressed
F__7Zone 7 FaultSIL1NAC/Bell #1 Silenced
F__8Zone 8 FaultSIL2NAC/Bell #2 Silenced
F__9Zone 9 FaultSIL3NAC/Bell #3 Silenced
F_10Zone 10 FaultSIL4NAC/Bell #4 Silenced
bEL1Bell 1 Fault (open or short)no_1Primary Phone Line Fault
bEL2Bell 2 Fault (open or short)no_2Secondary Phone Line Fault
bEL3Bell 3 Fault (open or short)rES_Reset Switch Pressed
bEL4Bell 4 Fault (open or short)POr_Power On Reset (unit was powered off
History Mode Messages
completely, i.e. no AC and no battery)
To erase the list from E
2
memory, press the SILENCE key twice before exiting the History Mode. A lack of key-
board activity for a period of 10 minutes will cause the control panel to return to Normal Mode. If a printer is connected to the panel, the History File will be printed upon successful entry into History Mode and a list of the most
recent 256 events, time and date stamped, will print out.
Note that remote site upload or download is possible when the system is in History Mode.
Document #50193 Rev. E 01/30/02 P/N 50193:E
81
Troubleshoot Mode
5.3Troubleshoot Mode
In this mode, system voltages may be displayed on the 4-character display. An internal voltmeter measures the voltage present at:
✓zone inputs
✓
AC power input
✓
battery terminal leads
✓NAC #1
✓NAC #2
✓NAC #3
✓NAC #4
✓Resettable 24 volt power
A lack of keyboard activity for a period of 20 minutes will cause the control panel to return to Normal Mode.
To enter the Troubleshoot Mode, press the MODE key followed by the 4-digit code 8768 and then the [ENTER/
STORE] key.
8768 spells TROU on a Touch-Tone
☛
®
phone.
Once in Troubleshoot Mode, the control panel will:
• Blink the FACP trouble LED
• Blink all remote annunciator LEDs
• Activate the FACP trouble relays if programmed for trouble operation
• Disable the Notification Appliance Circuits
• Output all troubleshoot voltage readings to external printer
• Disable the alarm relay
• Transmit the 'off normal' message to the Central Station(s)
• Continue to communicate any events not yet acknowledged at the Central Station prior to entering Troubleshoot Mode.
The Up arrow, Down arrow and 1st Event keys do not function in Troubleshoot Mode.
5.3.1 Zones
Pressing 01 through 10, followed by [ENTER/STORE], displays the zone voltage of the selected zone. Listed
below are the nominal threshold voltages for each zone:
Zone #Normal w/EOLShortedOpen Circuit
1 through 1023.5V0.00V25.4V
Readings will vary proportionately, depending upon system load and AC line voltage.
82
Document #50193 Rev.E 01/30/02 P/N 50193:E
Troubleshoot Mode
5.3.2 AC Line
Pressing A, followed by [ENTER/STORE], displays the AC input voltage as shown below. The AC ON indicator will turn off when the AC line voltage drops below the Low Line threshold, and the trouble LED will turn on.
Following is a list of the AC line voltage range:
AC Line VoltageLow LineNormalHigh Line
MS-5210UD:102 VAC115 VAC132 VAC
MS-5210UDE:204 VAC220 VAC264 VAC
5.3.3 Battery
Pressing B, followed by [ENTER/STORE], will display the Battery Voltage. Listed below are the critical battery
threshold conditions:
NormalLow BatteryNo Battery
Battery Voltage:27.6V20.4V<17.4V
Note that voltage readings should be taken after allowing 48 hours to charge depleted batteries. If batteries do not
show normal readings, replace them.
IMPORTANT
condition). A battery with a higher voltage must be installed to turn the charger back on.
: The battery charger will turn off when the battery voltage drops to 17.4 VDC or less (No Battery
5.3.4 Telephone Lines
Pressing C for touchtone dialing or D for rotary dialing, followed by the [ENTER/STORE] key, causes seizure of
the Primary phone line, which in turn lights the red LED, signifying Primary phone line active. After a delay of
three seconds, the control panel goes off-hook to acquire a dial tone.
The control panel keypad may be used as a telephone touchpad for number dialing. Once the first digit is pressed,
the display will move the C or D character one position to the left, while placing the digit to be dialed on the farthest right display position. Continue to press the phone numbers to be dialed. Successive depressions of the
[ENTER/STORE] key hangs up and picks up the phone (places the phone on or off the hook).
The secondary phone line may be tested by pressing the E key for touchtone dialing or the F key for rotary dialing
and then following the same procedure used for the primary phone line.
A handset may be temporarily connected across transformer T1 as illustrated in Figure 5-1. The handset, when
connected across T1, may be used only as an amplifier/speaker and telephone with the control panel used for number dialing.
Note that remote site upload or download is not possible while testing the phone lines in this portion of Troubleshoot Mode.
FIGURE 5-1:
Handset/Speaker Connection
Document #50193 Rev. E 01/30/02 P/N 50193:E
Both Primary and
Secondary Lines
83
Lamp Test
5.3.5 NACs 1, 2, 3 and 4
• Pressing B1, followed by [ENTER/STORE], displays the voltage on NAC #1.
• Pressing B2, followed by [ENTER/STORE], displays the voltage on NAC #2.
• Pressing B3, followed by [ENTER/STORE], displays the voltage on NAC #3.
• Pressing B4, followed by [ENTER/STORE], displays the voltage on NAC #4.
NAC voltage readings are nominally -2.32 volts when an EOL resistor of correct value is in place. A reading of
0.00 volts will appear for a shorted output, -4.50 volts for an open output. Intermediate readings are also possible.
5.3.6 Resettable Power
Pressing the RESET key, followed by [ENTER/STORE], displays the resettable 24 volt power. Resettable 24
volt power must read 24 volts, + or - 10%.
5.4Lamp Test
To perform a Lamp Test, press the MODE key followed by the 4-digit code 5267 and then the [ENTER/STORE]
key. This will test all system LEDs on the FACP (except the Modem, Kissoff, Primary Active and Secondary Active
LEDs). The LEDs will stay on for five seconds, then the control panel will return to Normal Mode.
5267 spells LAMP on a Touch-Tone
☛
®
phone.
5.5Print Mode
Refer to Figure 2-13, “Remote Printer Connections,” on page 34 for proper PRT-24 Interface module connection to
the main circuit board before proceeding. A printer may be temporarily or permanently connected to the panel. Program address '4' in Program Mode Level 3 to a '1' to enable printer supervision. Once enabled, normal system status
as well as panel operations will be printed. If the printer connection is removed, the system trouble LEDs will blink,
the system piezo sounders will pulse and the 4-character system LED display will read F__P.
Select Printer Mode by pressing the MODE key followed by the code 7746 then pressing the [ENTER/STORE] key.
The display will read Prn and the following time and date stamped data will be printed:
✓Entire program entries
✓History File
✓Walktest File
✓Troubleshoot Mode voltages
✓Current System Status
The fire protection remains active while in print mode. Remote site upload or download is allowed while in Print
Mode. An alarm on any zone will take priority, causing the panel to exit Print Mode.
84
Document #50193 Rev.E 01/30/02 P/N 50193:E
Printer Output
5.6Printer Output
This section illustrates sample printouts for various panel modes.
Real Time Status
06-26-96 14:15:10
Zone 1 Verifying 2-Wire Smoke Detector Active 06-26-1996 14:15:20
Zone 2 2-Wire Smoke Detector Active06-26-1996 14:15:24
Zone 2 Pull Station Active06-26-1996 14:15:29
Zone 3 N.O. Contact Device Active06-26-1996 14:15:34
Zone 4 Supervisory Active06-26-1996 14:15:37
Zone 5 Waterflow, Silenceable Active06-26-1996 14:15:45
Zone 6 Process Monitoring Active06-26-1996 14:15:49
System Silenced06-26-1996 14:15:53
NAC 1 Silence06-26-1996 14:15:56
NAC 2 Silence06-26-1996 14:15:59
Zone 1 Alarm Cleared06-26-1996 14:16:03
Low Battery Detected06-26-1996 14:16:09
Normal Battery06-26-1996 14:16:15
Loss of AC Power06-26-1996 14:16:19
AC Power Restore06-26-1996 14:16:42
Drill Mode Entered06-26-1996 14:16:51
System Reset06-26-1996 14:17:25
Drill Mode Cleared06-26-1996 14:17:33
Entering Walktest Mode
06-26-96 14:32:15
Zone 2 Pull Station Active06-26-1996 14:33:20
Entering Trouble Shoot Mode 06-26-1996 14:47:12
Trouble Shoot Mode Data
06-26-96 14:47:12
Zone 1 Voltage=25.20
Zone 2 Voltage=25.18
Zone 3 Voltage=25.20
Zone 4 Voltage=25.20
Zone 5 Voltage=25.18
Zone 6 Voltage=25.18
Zone 7 Voltage=25.18
Zone 8 Voltage=25.20
Zone 9 Voltage=25.20
Zone 10 Voltage=25.20
AC Line Voltage=120.9
Battery Voltage=27.20
NAC 1 Voltage=-2.09
NAC 2 Voltage=-2.29
Resettable 24 Volts =26.03
Entering Lamp Test Mode
06-26-96 15:03:10
Entering Program Mode
06-26-96 15:08:13
Document #50193 Rev. E 01/30/02 P/N 50193:E
85
Remote Site Upload/Download
CHAPTER 6Remote Site Upload/Download
The control panel may be programmed or interrogated off site via the public switched telephone network. Any personal computer with Windows
®
3.1 or greater or Windows® 95, with a 1200 Baud Hayes™ compatible modem and
Fire•Lite Upload/Download software P/N PK-5210UD, may serve as a Service Terminal. For details on the remote
site upload/download software package, refer to the PK-5210UD manual. The Upload/Download software allows
the following:
• Download of the entire program
• Download of an individual program item at Levels 1 - 4
• Upload of the entire program
• Upload of an individual program item at Levels 1 - 4
• Download of a single program item (such as a Central Station phone number)
• Upload of the entire program plus History File, Walktest data, current status, system voltages or time & date
• Real-time upload, either continuous or 'snapshot' (one-time), of current status or system voltages
• Execution of control panel functions: Trouble Silence, Manual Evacuate, Manual Evacuate Restore, Zone/
NAC Disable, Zone/NAC Enable and Set Time & Date
CAUTION: Changes to program entries occur as a result of the downloading process. After successful downloading,
!
make certain to perform the following steps:
Print out all programmed data via Print Mode or manually view programmed entries and compare to intended
1.
program data.
Test all affected panel operations.
2.
Immediately correct any problems found.
3.
6.1Downloading Program: General
Any time that the control panel is downloaded, whether initiated at the jobsite or remotely, a secret code (factory
default 0000) is verified between the control panel and the Service Terminal. Changing the Secret Code may only be
accomplished at the Service Terminal and subsequently loaded into the control panel. Future upload or download
requests cause verification of the Secret Code by the control panel before processing of data is allowed. If the Secret
Code is not verified, the control panel will terminate the request immediately.
While the control panel is communicating with the Service Terminal, the panel's green Modem LED and one of the
red Line Seize LEDs will remain on steady. At the conclusion of a successful download transaction, the green
'Kissoff' LED will come on steady for one second. Upon termination of communication, the green Modem LED will
turn off and the red Line Seize LED will turn off.
In order to download the panel (whether initiated at the jobsite or remotely) the following must be true:
✓
The control panel may be in any mode of operation including Normal, Program, History, Walk Test,
Print, Troubleshoot or Lamp Test. It is also possible during any of the function modes including Disable, Enable and Drill. Downloading is not possible if the communicator is active during Central Station communications or while testing the phone lines while in Troubleshoot Mode.
✓
There cannot be any active communications ongoing with a Central Station receiver.
✓
All active events must be successfully 'Kissed-off' by the Central Station(s). The Communicator must
be in a standby state with no new information waiting to be transmitted to a central station.
86
Document #50193 Rev.E 01/30/02 P/N 50193:E
Downloading Program: General
Two basic communication mechanisms are supported as follows:
• Download with callback - The Service Terminal calls the control panel. The control panel answers the call,
confirms the calling party then hangs up. The Service Terminal then waits for a callback from the control
panel. After the control panel calls the Central Station and successfully reports that a request for downloading
has been received, the control panel calls the Service Terminal back. Upon secret code verification, data transfers occur. When the data transfers are completed and the Service Terminal disconnects from the control
panel, the panel calls the Central Station back to confirm either successful or nonsuccessful results.
• Download with callback disabled - The Service Terminal calls the control panel. No hang-up sequence occurs.
Data transfers proceed.
Note that Callback enable/disable is controlled by the master user at the Service Terminal on a per call basis.
With program address location 56 set to '1' in Program Mode Level 1, anytime a download with callback is initiated,
the first thing the control panel will do is one of the following:
• contact the primary Central Station
• contact both the primary and secondary Central Stations
• contact the first available Central Station phone number
Once contact has been established, the control panel will report a 'request for upload/download' message (depending
upon the program entry in Program Level 4 address location 42). Following 'kissoff' of the request by the Central
Station(s), the control panel will then call the appropriate Service Terminal and begin the downloading process.
With program address location 56 set to '1' in Program Mode Level 1, anytime a download with callback disabled is
initiated, the control panel and the Service Terminal will communicate and transfer data without first contacting a
Central Station. When the data transfers are completed and the control panel disconnects from the Service Terminal,
the control panel will call the Central Station and report one of the following conditions:
• Upload/download request received
• Upload and/or download successful
• Upload/download failed
To prevent the 'request for up/download' message(s) from being reported to the Central Station(s), make certain to
leave address 56 = 0 or disable all upload/download reports back to both Central Stations. Refer to Table 3-3 through
Table 3-8 for additional information.
During the downloading process, the fire protection remains active
. Should a system trouble or alarm condition
occur, the control panel immediately terminates downloading and processes the trouble or alarm locally and transmits the information to the Central Station(s).
6.1.1 Security Features
Remote site upload and download with the control panel has been carefully designed to include key security features
to ensure proper functionality. The key features are listed and explained below.
Secret Code Verification
A secret code is stored in the control panel by a Service Terminal to prevent unauthorized access. The secret code
is created at the Service Terminal by a Master user and cannot be viewed or changed by anyone other than a Master user. Viewing of the secret code is prohibited at the control panel. Prior to allowing an upload or download of
data, the control panel will verify the secret code transmitted by the Service Terminal.
Time-out at Control Panel
Upon answering an incoming call on either the primary or secondary Central Station phone line, the panel will listen for a modem connection signal. If this signal is not received within 30 seconds, the panel will disconnect the
call. Upon successful connection (i.e. secret code verified and callback completed, if applicable), if no communication occurs within two minutes, the panel will disconnect the call.
Document #50193 Rev. E 01/30/02 P/N 50193:E
87
Downloading Initiated at Control Panel
Callback to Service Terminal
Anytime that the panel is remotely requested to allow an upload or download with callback, it will confirm the
source of the incoming call, hang-up and call the calling party (Service Terminal phone number) back.
Panel Identification Number (future)
The panel identification number will be used in the future to identify the panel to the Service Terminal (when the
panel calls the Service Terminal) automatically.
Calls initiated at the FACP must be coordinated at the Service Terminal manually. Note that the Service Terminal
will not pickup the incoming call unless operating on the communications screen. The Service Terminal will not
recognize an FACP initiated call unless the secret code is at the factory default settings.
Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If an error is detected, the block
is retransmitted until correct, up to a maximum of four times. If the Secret Code is not verified and four errors
occur, the call is disconnected and the report that the upload/download was not successful is called to the Central
Station(s).
Central Station Acknowledge
There is an option whereby the control panel will report to one or both Central Station(s) that a request for uploading or downloading has been received prior to processing the call. This is called the 'callback' option. If the Central Station(s) does not acknowledge receipt of this request, up or downloading is prohibited. If acknowledged by
the Central Station(s), another message is transmitted informing the Central Station(s) of one of the following:
• downloading was successful
• uploading was successful
• uploading/downloading was not successful
Data Protection/Integrity
Options allow programming of single data entries, single programming levels (1 - 4) and the entire programming
of all four levels simultaneously. Use caution when selecting programming choices and verify all entries via an
upload or manual check at the FACP. Data blocks containing user programming options are protected from partial
programming due to faulty phone connections, line noise and other errors.
6.2Downloading Initiated at Control Panel
Before initiating the Download procedure, make certain that the following conditions exist:
control panel is in Normal Mode
✓
Central Station communications are off or Main Panel Options programming location 56 = 0
✓
the communicator is in the standby state (red Line Seize, green Modem and green Kissoff LEDs are off)
✓
Place the control panel into Program Mode and program one or both of the Service Terminal phone numbers. It is
also advisable at this time to coordinate this call with the Service Terminal operator to allow the Service Terminal
operator to easily identify the incoming call.
Exit the Program Mode and return the control panel to Normal Mode. Press the MODE key followed by the 4-digit
code 3696 and then the [ENTER/STORE] key.
3696 spells DOWN on a Touch-Tone
☛
The display to the far left will flash the letter S. Press the digit '1' for Service Terminal phone #1 or '2' for Service
Terminal phone #2, followed by the [ENTER/STORE] key. The control panel will now call the appropriate Service
Terminal phone number. With the Service Terminal set up with the correct download customer file and operating in
the communications window, the downloading process may begin.
®
phone.
88
Document #50193 Rev.E 01/30/02 P/N 50193:E
Downloading Initiated at a Service Terminal
Once the called Service Terminal accepts the incoming call (control panel) and verifies the secret code, the downloading process is allowed to continue. Downloading progresses until all programmed information has been successfully
loaded into the control panel. Communication terminates upon the Service Terminal hanging up or upon the FACP
hanging up after a two minute time-out following completion of data transfer.
6.3Downloading Initiated at a Service Terminal
Before initiating the Download procedure, make certain that the communicator is in the standby state; red Line Seize,
green Modem and green Kissoff LEDs are off.
Once an incoming call is accepted/answered by the control panel, the panel will:
Establish basic modem connection
1.
Verify secret code
2.
Verify callback vs. no callback request from the Service Terminal (if callback is requested, panel will perform
3.
steps 4 through 10; if no callback is requested, panel will perform only steps 9 and 10)
Identify the Service Terminal location
4.
Hang-up/disconnect call
5.
Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
6.
this message is accepted, the control panel will proceed to the next step
Return call to Service Terminal
7.
Verify secret code
8.
Begin downloading
9.
Upon completion of download, call-back Central Station(s) and report a successful download or failed upload/
10.
download status (if programmed to do so)
6.4Uploading Initiated at a Service Terminal
Items that may be uploaded from the control panel to a Service Terminal include:
• All or portions of programmed data plus the real-time clock, time and date
• Entire Walk Test data file in real-time continuous or as a 'snapshot'
• Troubleshoot system voltages in real-time continuous or as a 'snapshot'
• Entire 256 event History File
• Current system status in real-time continuous or as a 'snapshot'
Uploading is possible at any time provided the following conditions are true:
✓The control panel may be in any mode of operation. Uploading is not possible if the communicator is
active or while testing the phone lines while in Troubleshoot Mode
✓
There cannot be any active communications ongoing with the Central Station receiver
✓
All active events must be successfully 'kissed-off' by the Central Stations (communicator must be in a
standby state with no new information waiting to be transmitted to a Central Station).
Document #50193 Rev. E 01/30/02 P/N 50193:E
89
Simultaneous Data Transfers
Once an incoming call is accepted/answered by the control panel, the panel will:
Establish basic modem connection
1.
Verify secret code
2.
Verify callback vs. no callback request from the Service Terminal (if callback is requested, the panel performs
3.
steps 4 through 10; if no callback is requested, the panel performs only steps 9 and 10)
Identify the Service Terminal location
4.
Hang-up/disconnect call
5.
Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
6.
this message is accepted, the control panel will proceed to the next step
Return call to Service Terminal
7.
Verify secret code
8.
Begin uploading
9.
Upon completion of upload, call Central Station(s) back and report a successful upload or failed upload/down-
10.
load status (if programmed to do so)
During the uploading process, the fire protection remains active
. Should a system trouble or alarm condition
occur, the control panel immediately terminates uploading and processes the trouble or alarm locally and transmits the information to the Central Station(s).
6.5Simultaneous Data Transfers
Uploading and downloading may take place on a single telephone call. Control and selection of the data transaction
is coordinated at the Service Terminal. This eliminates multiple phone calls, allows instant verification of download
data files and simplifies the overall process.
90
Document #50193 Rev.E 01/30/02 P/N 50193:E
Battery Calculations
Appendix ABattery Calculations
Use the Total Standby and Alarm Load Currents calculated in Table A-2 and Table A-3 for the following battery
calculation.
TABLE A-1:
Battery Calculation
Standby Load
Current (amps)
[ ]
Al arm Loa d
Current (amps)
[ ]
Add Standby and Alarm Load for Required Ampere Hour Battery=_______________
X
X
Required Standby Time in Hours
(24 or 60 Hours)
[ ]
Required Alarm Time in Hours
(i.e. 5 min. = 0.084 hours)
[ ]
Multiply by derating factor of 1.2X 1.2_______________
=_______________
=_______________
Note:
12 Ampere Hour battery can be located in the backbox.
1.
Batteries larger than 12 Ampere Hour, up to 18 Ampere Hour, require the BB-17F battery box.
2.
Document #50193 Rev. E 01/30/02 P/N 50193:E
91
Battery Calculations
A.1Main Power Supply
The MS-5210UD provides regulated power for operating the fire alarm control panel, operating external devices and
operating the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or nonalarm) and Table A-3 (alarm) to determine if external loading is within the capabilities of the power supply.
Be certain to power 4-wire smoke detectors from TB2, Terminals 3 and 4. In Table A-2 , external devices are connected to TB2 only.
TAB LE A- 2:
Device Type
Regulated Load in Standby
# of
Devices
@24 VDC
.
Current
(amps)
Total Current
Main Circuit Board1X0.138=0.138
LED-10IM(1 max.)X0.017=
LED-10 Annunciator[ ]X0.023=
Misc. Annunciators[ ]X
[ ]
1
=
PRT-24(1 max.)X0=0
CAC-10F(1 max.)X0.004=
NAC-REM(1 max.)X0.002=
2-wire Detector Heads[ ]X
2-wire Detector Heads[ ]X
4-wire Detector Heads[ ]X
4-wire Detector Heads[ ]X
2
Power Supervision Relays
[ ]X0.025=
Current Draw from TB2
(nonalarm3)
[ ]
[ ]
[ ]
[ ]
1
1
1
1
=
=
=
=
=
Sum Column for Standby Load=amps
(amps)
92
1. Refer to the Device Compatibility Document for standby current.
2. Must use compatible listed Power Supervision Relay.
3. The total standby current must include both the resettable (TB2 Terminals 3 & 4) and nonresettable (TB2
Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these outputs during
alarm does not exceed maximum ratings specified (see Table A-2 ).
Document #50193 Rev.E 01/30/02 P/N 50193:E
Battery Calculations
TABLE A-3:
Device Type
Regulated Load in Alarm
# of
Devices
@24 VDC
.
Current
(amps)
Main Circuit Board1X0.245=
LED-10IM(1 max.)X0.017=
LED-10 Annunciator[ ]X
0.040
2
Misc. Annunciators[ ]X[ ]=
PRT-24(1 max.)X0=0
CAC-10F(1 max.)X0.020=
NAC-REM(1 max.)X0.075=
3
4-wire Smoke Detector
[ ]X[ ]=
4-wire Smoke Detector[ ]X[ ]=
4
Power Supervision Relay
Notification Appliances
Notification Appliances
Current Draw from TB2
[ ]X0.025=
5
[ ]X[ ]=
6
[ ]x[ ]=
3
(alarm current)
Sum Column for Alarm Load
7
Total Current
(amps)
1
0.245
=
=
=amps
1. The current shown represents one zone on the Main Circuit Board in alarm. For all ten zones in alarm,
the current draw increases to 0.590 amps with communicator off and 0.610 amps with communicator on.
2. The current shown represents all ten zones in alarm. One zone in alarm will draw 0.028 amps.
Backup Reporting. Enter '0' to report to secondary phone number as backup only; '1' to report to both primary
57
and secondary phone number for all reports/messages; '2' reports go to first available receiver.
❏
Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
58
❏
Make/Break Ratio for Primary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
59
❏
Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
60
❏
Make/Break Ratio for Secondary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
61
❏
Future use.
62
❏
Future use.
63
94
Document #50193 Rev.E 01/30/02 P/N 50193:E
Main Panel Options Program Sheets
❏
Zone 1 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
64
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
Zone 2 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
65
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
Zone 3 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
66
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
Zone 4 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
67
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
Zone 5 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
68
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
Zone 6 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
69
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
Zone 7 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
70
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
Zone 8 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
71
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
Zone 9 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
72
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
Document #50193 Rev. E 01/30/02 P/N 50193:E
95
Main Panel Options Program Sheets
❏
Zone 10 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open contact
73
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6' for
waterflow (nonsilenceable); '7' for process monitoring; '8' for autoresettable process monitoring; '9' for remote reset
switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual evacuate (drill)
switch.
❏
74 ❏75
❏
76
❏
77
hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19 hours; 'C' for 20
hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
❏
78
for trouble; '4' for communications fail; '5' for process monitoring; '6' for process monitoring autoresettable.
❏
79
for trouble; '4' for communications fail; '5' for process monitoring; '6' for process monitoring autoresettable.
❏
80
'2' for disable.
❏
81
❏
82
for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❏
83
onds Off); '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ seconds Off).
Waterflow Retard Timer. Enter 0 - 89 additional seconds.
Alarm Verification. Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
AC Loss Delay. Enter '0' for 6 hours; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10 hours; '5' for 11
Programmable Relay #1 Definition. Enter '0' for alarm; '1' for supervisory; '2' for supervisory autoresettable; '3'
Programmable Relay #2 Definition. Enter '0' for alarm; '1' for supervisory; '2' for supervisory autoresettable; '3'
Notification Appliance Circuit #1 Selection. Enter '0' for enabled (silenceable); '1' for enable (nonsilenceable);
Silence Inhibit NAC #1. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #1 for one minute.
Auto Silence NAC #1. Enter '0' for no auto silence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15 minutes; '4'
Coding NAC #1. Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds On, 5 sec-
❏
Notification Appliance Circuit #2 Selection. Enter '0' for enabled (silenceable); '1' for enable (nonsilenceable);
84
'2' for disable.
❏
Silence Inhibit NAC #2. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #2 for one minute.
85
❏
Auto Silence NAC #2. Enter '0' for no auto silence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15 minutes; '4'
86
for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❏
Coding NAC #2. Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds On, 5 sec-
87
onds Off); '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ seconds Off).
❏
Trouble Reminder. Enter '0' to disable; '1' to enable.
88
96
Document #50193 Rev.E 01/30/02 P/N 50193:E
Main Panel Options Program Sheets
Main Panel Options Programming Sheets (Factory Default Settings)
---To enter Programming Level 1, press the MODE key, 7764, '1', [ENTER/STORE]