While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so lo-
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
Precau-Lg.p65 01/18/2000
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used
in accordance with the instruction manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which
is designed to provide reasonable protection against such interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
1.2: Controls and Indicators ...............................................................................................................................13
FIGURE 1-3: Controls and Indicators .................................................................................................13
1.4: Digital Communicator.................................................................................................................................14
1.5.1: Main Circuit Board ...........................................................................................................................14
FIGURE 2-8: Auxiliary Relay and Relay Driver Terminals ...............................................................25
2.6: UL Power-limited Wiring Requirements ....................................................................................................26
FIGURE 2-9: Typical Wiring Diagram for UL Power-limited Requirements ....................................26
2.7: Digital Communicator.................................................................................................................................27
3.1: Entering Program Mode ..............................................................................................................................33
4.1: Switches in Normal Mode...........................................................................................................................50
4.3.7: Off Normal Reporting .......................................................................................................................55
4.3.8: Zone Disable/Enable .........................................................................................................................56
4.3.9: Fire Drill............................................................................................................................................56
4.4: Central Station Communications.................................................................................................................57
TABLE 4-1: Format Selection Address (16 & 42) ..............................................................................58
TABLE 4-2: Format Selection Address Explanation...........................................................................59
5.2: History Mode...............................................................................................................................................63
5.3.1: Zone Voltages ....................................................................................................................................64
TABLE 5-1: Nominal Zone Voltages..................................................................................................64
5.3.2: AC Line Voltage................................................................................................................................65
5.3.3: Battery Voltage ..................................................................................................................................65
5.4: Lamp Test ....................................................................................................................................................66
CHAPTER 7: Remote Site Upload/Download .......................................................................................................69
7.1: Downloading Program ................................................................................................................................69
A.1: The Main Power Supply ............................................................................................................................74
TABLE A-2: Filtered Load in Standby - external devices connected to TB4 only ............................74
TABLE A-3: Filtered Load in Alarm .................................................................................................75
C.2: Function Modes ........................................................................................................................................82
TABLE C-2: Function Modes .............................................................................................................82
Appendix D: Ademco Contact ID Format Event Code Descriptions ...............................................................83
Document 15140 Rev. G 01/02/02 P/N: 15140:G7
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code for Local, Remote Station and Central Station Fire Alarm System
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Central Station Fire Alarm Systems Protected Premises Unit
(Automatic, Manual and Waterflow), Local Fire Alarm Systems (Automatic, Manual, Waterflow and
Sprinkler Supervisory), Auxiliary Protective Fire Alarm Systems (Automatic, Manual and Waterflow), Proprietary Protective Fire Alarm Systems (Automatic, Manual and Waterflow) and Remote
Station Fire Alarm Systems (Automatic, Manual and Waterflow).
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
The MS-5024UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator
Transmitter) all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel
accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally
open contact devices. Outputs include two NACs (Notification Appliance Circuits), alarm and trouble relays, supervisory and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to UL-listed Central Stations via
the public switched telephone network. The control panel has a built-in programmer and may also serve as a slave
communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery
level.
The control panel may be programmed or interrogated off-site via the public switched telephone network. Any IBM
™
compatible personal computer with DOS
4.01 or greater plus Windows™ 3.1 or greater, with a 1200 baud Hayes™
compatible modem and Fire•Lite Upload/Download software P/N PK-5024UD, may serve as a Service Terminal.
This allows download of the entire program or upload of the entire program, history file, walktest data, current status
and system voltages. The MS-5024UDE offers the same features as the MS-5024UD but allows connection to 220/
240 VAC input.
1.1Product Features
• Selectable as Fire Panel, Fire Panel/Communicator or Slave Communicator
• Programmable Zone ID: 2-wire smoke, pull station, normally open contact device, supervisory, supervisory
autosilence, waterflow silenceable or waterflow nonsilenceable
• One Style D (Class A) zone
• Four Style B (Class B) zones
• 3.6 amps usable power expandable to 5.6 amps
• Optional 5-zone Relay Module (RM-5F)
• CAC-5F Style D (Class A) Zone Converter Module
• Two NFPA Style Y (Class B) or Style Z (Class A) Notification Appliance (bell) Circuits
• Small size - 15" (38.1 cm) x 14.5" (36.83 cm) x 2.75" (6.985 cm)
• History file with 32 event storage
• Silence inhibit per NAC (Notification Appliance Circuit)
• Autosilence per NAC
10
Document #15140 Rev.G 01/02/02 P/N 15140:G
Product Features
A
• Touchtone/Rotary dialing
• Programmable make/break ratio
• Fuseless design
• PRT-24 (Printer Interface Module)
• Print real-time system status
• Print history and walktest files, program contents and troubleshoot mode voltages
• PK-5024UD Upload/Download Software Kit
• Number of dial attempts (minimum of 5 and maximum of 10)
• Programmable channel ID (slave)
• Programmable zone delay (waterflow only)
• Form-C alarm and trouble relays
• Supervisory and communication fail relay drivers
• Low AC voltage sense
•One-man walktest
• Optional Dress Panel cover (DP-5024UD)
Optional DP-5024UD
FIRE CONTROL/COMMUNICATOR
AC POWER
ALARM
RESET
1
4
7
A
Note: Unless otherwise specified
FIGURE 1-1:
, MS-5024UD shall be used in this manual to refer to both the MS-5024UD and
MS-5024UDE Fire Alarm Control Communicators.
n
SILENCE
2
3
5
6
8
9
0
B
TROUBLE
SUPERVISORY
MODE
F
E
1ST
D
EVENT
ENTER
C
STORE
Document #15140 Rev.G 01/02/02 P/N 15140:G
11
Product Features
FIGURE 1-2:
MS-5024UD Panel
Notification Appliance
Circuits
Standard
Transformer
Four Character
7-Segment LED
Display
Keypad
Optional
Transformer
Alarm &
Trouble
Relays
5 Input
Zones
Primary & Secondary Phone Lines
Annunciator
Driver Module
Interface
Connector
Relay Module
Interface
Connector
PROM U23
Piezo 85dB
1
Printer
Interface
Module
Connector
Holds up to 7 AH Batteries
Up to 60 Hrs. of Standby
Software for the Fire Alarm Control Communicator is located in a PROM inserted in the IC socket labeled
1.
U23. The MS-5024UD and MS-5024UDE each contain unique software. For specific panel software information, refer to the MS-5024UD(E) Field Software Change Procedure Document #50125.
12
Document #15140 Rev.G 01/02/02 P/N 15140:G
Controls and Indicators
1.2Controls and Indicators
Front Panel Switches
RESETDigits 0-9
SILENCEA
MODEB
Up ArrowC
Down ArrowD
1st EVENTE
ENTER/STOREF
Displays
• Alarm - red LED
• Trouble - yellow LED
• Supervisory - yellow LED
• AC Power - green LED
• Four 7-Segment Displays - red
• Primary Phone Line Active - red LED
• Secondary Phone Line Active - red LED
• 'Kissoff' Signal from Central Station - green LED
• Silence - yellow LED
• Modem - green LED
FIGURE 1-3:
Controls and Indicators
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions.
1.3Circuits
Input Circuits
Five input circuits provide Style B configuration with one circuit also configurable for Style D. Input circuits may be
used as standard fire control panel zones or slave communicator input channels.
• Initiating Device Circuit 1 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 2 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 3 (Style B/D) accepts normally open contact devices, 2-wire smoke detectors and
waterflow devices
• Initiating Device Circuit 4 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 5 (Style B) accepts normally open contact devices and 2-wire smoke detectors
Output Circuits
• 24 Volt Resettable Power Output
• 24 Volt Nonresettable Power Output
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger
•Printer Port
Document #15140 Rev.G 01/02/02 P/N 15140:G
13
Digital Communicator
Notification Appliance Circuits
Two Notification Appliance Circuits configurable for Style Y (Class B) or Style Z (Class A) with various programmable features.
Relays
Two dry Form-C relay contacts for system alarm and system trouble are provided. Contacts are rated 2 amps @ 30
VDC and 0.5 amps @ 30 VAC resistive.
Relay Drivers
Two relay driver outputs for supervisory and communication failure are available.
1.4Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the
Primary and Secondary phone lines. Telephone line active red LEDs are provided as well as a green 'kissoff' LED.
The integral digital communicator provides the following functions:
• Line Seizure - takes control of the phone lines disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone
• For tone burst or touchtone type formats: Discern proper 'Ack' and 'kissoff' tone(s). The frequency and time
duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
• Communicate in the following formats:
✓
12 Tone Burst Types (20 pps):
(3+1, 4+1, 3+1 Expanded, 4+1 Expanded and 4+2 Expanded)
✓
3 Touchtone Types:
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
(see Table 4-3 for a list of compatible receivers)
®
, programmable to rotary
1.5Components
1.5.1 Main Circuit Board
The main circuit board contains the system's CPU, power supply, other primary components and wiring interface
connectors. Optional modules plug in and are mounted to the main circuit board. The main circuit board is delivered
premounted in the cabinet.
1.5.2 Cabinet
The cabinet is red with an attractive navy blue front overlay. The backbox measures 15" (38.1 cm) x 14.5" (36.83
cm) x 2.75" (6.985 cm) and provides space for two batteries (up to 7 Amp Hours). Also available is an optional dress
panel (DP-5024UD), which mounts inside the cabinet.
14
Document #15140 Rev.G 01/02/02 P/N 15140:G
Optional Devices
1.5.3 Transformer Assembly
FIGURE 1-4:
XRM-24(E) Transformer
One 100VA transformer is provided standard with the panel (3.6 amps
maximum). An optional 100VA transformer, XRM-24 (XRM-24E for
MS-5024UDE), is available to provide maximum accessory power (6.6
Standard
Transformer
amps maximum).
1.5.4 Batteries
The cabinet provides space for 7 Amp Hour batteries (for 12 Amp Hour
up to 18 Amp Hour batteries, use the listed BB-17F battery box). Batteries must be ordered separately.
Optional
Transformer
XRM-24(E)
1.6Optional Devices
1.6.1 RM-5F Five-Zone Relay Module
The RM-5F option module provides five Form-C relays which track zones 1 through 5. The module mounts to connector J7 on the lower right side of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and
Figure 2-16 on page 31.
1.6.2 CAC-5F Class A Converter Module
The CAC-5F Class A Converter module converts the Style B (Class B) Initiating Device Circuits to Style D (Class
A). The CAC-5F mounts to terminal block TB2, located in the upper center of the main circuit board. The removable terminal block on the CAC-5F module provides for ease of wiring. Refer to Figure 2-17, “CAC-5F Style D Converter,” on page 32
1.6.3 ADM-24 Annunciator Driver Module
The ADM-24 Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is
supervised for open circuits by this module. The Annunciator Driver Module mounts to connector J3 in the upper
right corner of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and Figure 2-11 on page
28.
1.6.4 RZA-5F Remote Annunciator
The RZA-5F Remote Annunciator mounts on a standard single-gang box and provides LED indication of the
following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• Alarm Zone 5 (red)
• System Trouble (yellow)
A Local Trouble Sounder and Tone Silence Switch are also provided. All LEDs and their wiring are supervised for
open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit
an easy change of zone information. Refer to Figure 2-12, “RZA-5F,” on page 28, Figure 2-13 on page 29 and Figure
2-14 on page 29. Note that the Remote Annunciator requires the use of the ADM-24 Annunciator Driver Module.
Document #15140 Rev.G 01/02/02 P/N 15140:G
15
Specifications
1.6.5 PRT-24 Printer Interface Module
The Printer Interface Module may be used to connect a printer to the control panel for the purpose of printing a history report, walktest file, troubleshoot report, program entries or current system status. Printers require separate
external primary power. Connect the PRT-24 module (with cable) to the serial EIA-232 port on the printer. The
module mounts to the J2 connector on the main circuit board. Note that an EDP listed printer must be used if the
printer will be permanently attached to the control panel. Refer to Figure 2-15, “Remote Printer Connections,” on
page 30.
1.6.6 DP-5024UD Dress Panel
A red dress panel is available as an option. The dress panel restricts access to the system wiring while allowing
access to the membrane switch panel. Refer to Figure 1-1, “Optional DP-5024UD,” on page 11.
1.6.7 BB-17F Battery Box
The BB-17F battery box may be used to house two batteries, from 12 Amp Hour to 18 Amp Hour. The battery box
mounts directly below the cabinet and main circuit board. Refer to Figure 2-3, “Backbox and Battery Box,” on page
21. The BB-17F is red and is provided with knockouts.
1.6.8 PK-5024UD Programming Kit
This kit includes one 3½" diskette plus Instruction Manual P/N 50041. When the software is loaded into an IBM
compatible computer, it creates an off-line Service Terminal that allows any MS-5024UD panel to be uploaded or
downloaded over standard telephone lines.
Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.8 amp
Maximum Charger Capacity: 17 Amp Hour battery. (MS-5024UD cabinet holds maximum 7 Amp Hour battery.
Larger batteries require Fire•Lite BB-17F or other UL listed battery cabinet).
Initiating Device Circuits - TB2
Detector Zones 1, 2, 3, 4, 5Power-limited Circuitry
Operation: All zones are NFPA Style B, Zone 3 is NFPA Style B or Style D. Use CAC-5F module for Style D
operations
Normal Operating Voltage: 24 VDC (ripple = 100 mV maximum)
Alarm Current: 26 mAShort Circuit Current: 42 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K ohms, ½ watt (P/N 27072 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
2
) with 600V insulation
16
Document #15140 Rev.G 01/02/02 P/N 15140:G
Specifications
Notification Appliance Circuits - TB5 & TB6
Nonregulated, special purpose power, Styles Y and Z supported
Power-limited circuitry
Operating Voltage: Nominal 24 volts
Current for all external devices: 3.0 amps expandable to 5.6 amps
Current-limit: PTC
Maximum signaling current/circuit: 2.5 amps
End-of-Line resistor: 4.7K ohms, ½ watt (P/N 71252 UL listed) for NACs
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Alarm and Trouble Relays - TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Alarm and Trouble: Form-C power-limited circuitry (see Figure 2-7 note for power-limited wiring application)
Auxiliary Outputs - TB4, Terminals 5 & 6
TB4-5 Supervisory Relay Driver: Normally high, active low, sinks up to 40 mA
TB4-6 Communication Failure: Normally high, active low, sinks up to 40 mA
Power-limited circuitry
Four-wire Smoke Detector Power - TB4, Terminals 3(+) & 4(-)
Maximum ripple voltage: 10 mV
RMS
Operating voltage: Nominal 24 volts
Up to 300 mA is available for powering 4-wire smoke detectors
Power-limited circuitry
Recommended maximum standby current is 50 mA (see Battery Calculations in Appendix A)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Nonresettable Filtered 24V Power - TB4 Terminals 1(+) & 2(-)
Maximum ripple voltage: 10 mV
RMS
Operating voltage: Nominal 24 volts
Total DC current available from this output is up to 300 mA
Power-limited circuitry
Recommended maximum standby current is 150 mA (see Battery Calculations in Appendix A)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Notes:
For power supply calculations, refer to Appendix A.
1.
Total current for nonresettable power, 4-wire smoke detector power and two Notification Appliance Circuits
2.
must not exceed 5.6 amps. Total external system current in excess of 3.6 amps requires the XRM-24 Transformer (XRM-24E for 220/240 VAC applications) and 12 Amp Hour or 17 Amp Hour batteries.
Document #15140 Rev.G 01/02/02 P/N 15140:G
17
Telephone Requirements and Warnings
1.8Telephone Requirements and Warnings
1.8.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 1.3B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.
1.8.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Manufacturer:Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
Product Model Number: MS-5024UD
FCC Registration Number: 1W6USA-20004-AL-E
Ringer Equivalence 1.3B
Note: The FCC ID label is located on the inside of the control panel door
1.8.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the
telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
18
Document #15140 Rev.G 01/02/02 P/N 15140:G
Installation
CHAPTER 2Installation
2.1Mounting Options
FIGURE 2-1:
MS-5024UD Cabinet
The cabinet may be either surface mounted or semi-flush
mounted using the optional Trim Ring P/N: TR-1-R. The
door is removable during the installation period by opening
and lifting the door off the hinges. The cabinet mounts using
two key slots and two additional 0.25" (6.35 mm) diameter
holes located in the backbox. The key slots are located at the
top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage.
Mount the cabinet in a clean, dry, vibration-free area where
extreme temperatures are not encountered. The area should
be readily accessible with sufficient room to easily install and
maintain the panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on
the left. Determine the number of conductors required for the
devices to be installed. Sufficient knockouts are provided for
wiring convenience. Select the appropriate knockout(s) and
pull the required conductors into the box. Note that there are
no knockouts on the left (hinged) side of the cabinet. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.2Backbox Mounting
✓
Open the door and lift the door off the pin hinges
✓
Remove the main PC board assembly by unscrewing the four screws in the corners of the board. Two
standoffs support the board in the center. Set the board aside in a safe, clean place. Avoid static discharge which may damage the board.
✓
Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown
✓
Install two upper fasteners in the wall with the screw heads protruding
✓
Using the proper 'keyholes', mount the backbox over the two screws
✓
Mark and drill the lower two holes
✓
Mount backbox, install remaining fasteners and tighten
✓
When the location is dry and free of construction dust, reinstall the main PC board
Document #15140 Rev.G 01/02/02 P/N 15140:G
19
Backbox Mounting
FIGURE 2-2:
Height=15.000”
(38.10 cm)
Cabinet Dimensions and Knockout Locations
2.875” (7.3 cm)
Draw wires through the respective knockout locations.
Backbox = 14.5”
(36.8 cm)
0.75”(1.9 cm)
9.1” (23.1 cm)
10.375”
(26.35 cm)
Top
Depth = 3.000”
(7.62 cm)
2.7”
(6.86cm)
Bottom
TR-1-R Trim Ring
Backbox Mounting Holes
ms2-4cab.cdr
1.125” (2.868 cm)
20
Document #15140 Rev.G 01/02/02 P/N 15140:G
Backbox Mounting
FIGURE 2-3:
Door = 15.342“ (38.97 cm)
Backbox and Battery Box
To p
Door = 14.677 “ (37.28 cm)
Depth = 2.875" (7.3 cm)
Depth = 3.050“
(7.75 cm)
Bottom
Depth = 4.75
(12.065 cm)
Battery Box = 8.5“ (21.59 cm)
Battery Box = 14.5“
(37.384 cm)
Notes:
Mount the Fire Alarm Control Communicator cabinet to the wall
1.
Remove knockouts on bottom of FACP cabinet and top of BB-17F
2.
Using conduit, hang the BB-17F from the Fire Alarm Control Communicator cabinet, making sure there is at
3.
least ½" of clearance between the two cabinets
Anchor the BB-17F to the wall
4.
Document #15140 Rev.G 01/02/02 P/N 15140:G
21
Operating Power
2.3Operating Power
!
CAUTION: Several different sources of power can be connected to this panel. Disconnect all sources of power
before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules
or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the MS-5024UD is
120 VAC, 60 Hz, 2.3 amps and for the MS-5024UDE is 220/240 VAC, 50 HZ, 1.2 amps. Run a pair of wires (with
ground conductor) from the protected premises main breaker box to TB1 of the main circuit board. As per the
National Electric Code, use 14 AWG (2.00 mm
may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not
contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel
operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm
one of the transformer mounting studs. Note: Do not use conduit for the Earth Ground connection since this does not
provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J1 on the main circuit board using the
plug-in connector provided. The battery charger is current-limited and capable of recharging sealed lead acid type
batteries. The charger shuts off when the system is in alarm or if the battery voltage drops too low (below 17.4
VDC). See Appendix A for calculation of the correct battery rating.
2
) or heavier gauge wire with 600V insulation. No other equipment
2
)] to
CAUTION: Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fab-
!
rics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek
immediate medical attention.
FIGURE 2-4:
Connect Earth Ground Wire
Operating Power Connections
22
Document #15140 Rev.G 01/02/02 P/N 15140:G
Input Circuits
2.4Input Circuits
The control panel has five zone input circuits. The maximum loop resistance limit for each is 100 ohms. All field
wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated
as well as communicated to a Central Station.
Each zone is a Style B Initiating Device Circuit (IDC) designed to accept any normally open contact device and conventional 2-wire, 24 volt smoke detectors. Each zone is power-limited to 7.26 mA in standby and 42 mA in alarm.
Zone 3 may also be configured as a Style D Initiating Device Circuit.
Note: All five initiating zones may be converted to Style D (Class A) by using a CAC-5F Class A Converter module.
Refer to Figure 2-17, “CAC-5F Style D Converter,” on page 32.
Zones 1-5 may be programmed as listed below. The factory default is 2-wire smoke detector for all zones:
• 2-wire smoke detector (factory default)
• Pull station
• Normally open contact device(s)
• Supervisory
• Supervisory, autoresettable
Zone 3 may also be programmed as:
• Waterflow, silenceable
• Waterflow, nonsilenceable
Note: A maximum of five waterflow devices may be used on zone 3 per NFPA 72.
Four-wire smoke detectors may be connected to any zone. Resettable power is provided via TB4, Terminals 3 and 4.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any
zone. This is not recommended, however, since specific and detailed reports will not be possible. For example, the
report of general fire alarm versus pull station fire alarm or smoke detector fire alarm.
Refer to the Fire•Lite Device Compatibility Document for a list of compatible smoke detectors.
FIGURE 2-5:
UL listed compatible 2-wire smoke detector
Typical Initiating Device Circuit Connections
Style B Initiating Device Circuit
(supervised and power-limited)
4.7K ohm, ½ watt P/N 71252 UL listed
Manual Pull Station
Heat Detector
Style D Initiating Device Circuit
(supervised and power-limited)
UL listed compatible 2-wire smoke detector
Manual Pull Station
Heat Detector
MS-5024UD
Dummy load all unused circuits with 4.7K ohm
Document #15140 Rev.G 01/02/02 P/N 15140:G
ELR P/N 71245, across B+ and B-.
23
Output Circuits
2.5Output Circuits
DC Power Output Connections
All DC power outputs are power-limited.
FIGURE 2-6:
Telephone Circuits
Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 (primary)
and PH2 (secondary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection. Refer to Figure 2-10, “Wiring Phone Jacks,” on page 27.
Auxiliary Power Connections
Nonresettable Power (300 mA)
24 VDC filtered, nonresettable
power can be obtained from TB4,
Terminals 1(+) and 2(-)
+ - + -
1 2 3 4 5 6
TB4
4-Wire Smoke Detector Power (300 mA)
24 VDC filtered, resettable power for 4-wire
smoke detectors can be obtained from TB4,
Terminals 3(+) and 4(-)
Notification Appliance Circuits
The MS-5024UD provides two NACs (Notification Appliance Circuits) which can be configured as Style Y or Style
Z. Each circuit is capable of 2.5 amps of current. Total current drawn from these as will as other DC power outputs
cannot exceed 3.6 amps with the standard transformer, 5.6 amps if an optional XRM-24 transformer (XRM-24E for
the MS-5024UDE) is installed. Circuits are supervised and power-limited. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.
FIGURE 2-7:
Notification Appliance Circuit Connections
Style Y Notification Appliance Circuit (super-
vised and power-limited). 4.7K ohm, ½ watt
Polarized Bell
Polarized Strobe
Polarized Horn
P/N 71252 UL listed EOL resistor.
Polarized Bell
Polarized Horn
Polarized Horn
Note: Notification
Appliance Circuit
polarity shown in
alarm
state.
Dummy Load all
unused circuits
P/N 71245
Both Notification Appliance Circuits may be programmed as follows:
• Silenceable
• Nonsilenceable
• Enabled/disabled
• Silence inhibited
• Autosilence, 5 to 30 minutes
• Coded (March Time, Temporal or California)
24
Document #15140 Rev.G 01/02/02 P/N 15140:G
Output Circuits
Standard Relays
The control panel provides a set of Form-C alarm and a set of Form-C trouble contacts rated for 2.0 amps @ 30VDC
(resistive).
Relay Drivers
Relay driver outputs are provided for supervisory and communicator failure. These outputs can be used to drive UL
864 listed remote relays such as the MR-101C and MR-201C.
The control panel's open collector outputs on TB4, terminals 5 and 6 can be used to activate UL 864 listed relays.
Outputs are rated for 40 mA. The normal condition for each output is as shown below:
TB4-5 SupervisoryOff (deenergized)
TB4-6 Communications FailureOff (deenergized)
Relays must be placed inside the cabinet or in a UL 864 recognized enclosure. Wiring from the control panel's terminals on TB4 to the relays must be less than 3 feet in length and enclosed in conduit. Wiring from the relay outputs
must remain in the same room as the location of the enclosure and be enclosed in conduit.
FIGURE 2-8:
Auxiliary Relay and Relay Driver Terminals
Relay Connections
Alarm
NO NC C NC NO C
1 2 3 4 5 6
T
B
3
Note: The alarm and trouble Form-C dry
contact relays must be power-limited circuits. Any Form-C dry contact relay that
may be used must be wired from TB4 or a
UL listed power-limited power supply.
Trouble
All wiring to relay must
be in same room as
panel and in conduit
Relay Driver Connections
Relay energized LED
MR-201/C*
Relay energized LED
DPDT Contacts
10 Amps @ 115 VAC
Connections must be in
the same room as the
panel
DPDT Contacts
10 Amps @ 115 VAC
* The MR-101C and MR-201C include an enclosure.
Document #15140 Rev.G 01/02/02 P/N 15140:G
MR-101/C*
25
UL Power-limited Wiring Requirements
2.6UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all
power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or
conduits. A typical wiring diagram for the MS-5024UD is shown below. Refer to Figure 2-16, “RM-5F Installation
and Wiring,” on page 31 for additional information on wiring the RM-5F Relay module.
FIGURE 2-9:
Typical Wiring Diagram for UL Power-limited Requirements
Power-limited Circuits
Power-limited
Circuit
26
Nonpower-limited
Circuit
AC Power
Document #15140 Rev.G 01/02/02 P/N 15140:G
Digital Communicator
2.7Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line control/command is made
possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the
panel's digital communicator be located as the first device on the incoming telephone circuit to properly function.
The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone
lines is required as shown below.
FIGURE 2-10:
Wiring Phone Jacks
Document #15140 Rev.G 01/02/02 P/N 15140:G
27
Optional Boards
2.8Optional Boards
2.8.1 ADM-24 Annunciator Driver Module
The Annunciator Driver Module supports the RZA-5F Remote Annunciator. Annunciator wiring is supervised for
open conditions by this module. The Annunciator Driver Module mounts to J3 in the upper right corner of the main
circuit board.
FIGURE 2-11:
ADM-24 Annunciator Driver Module
Main Circuit Board
2.8.2 RZA-5F Remote Annunciator
The RZA-5F mounts on a standard single-gang electrical box and
provides LED indication of the following:
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
Connector located on
Standoff
FIGURE 2-12:
back of board
ADM-24
RZA-5F
The remote annunciator provides individual zone alarm LEDs, a
system trouble LED, a local piezo sounder and a remote sounder
shut off switch. All LEDs and their wiring are supervised for
open conditions. Any open condition will cause the System Trouble LED to turn on.
Note: The Remote Annunciator requires the use of an ADM-24
Annunciator Driver Module.
28
Document #15140 Rev.G 01/02/02 P/N 15140:G
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.