While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so lo-
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
Precau-Lg.p65 01/18/2000
Page 3
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be con-
nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used
in accordance with the instruction manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which
is designed to provide reasonable protection against such interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
1.2: Controls and Indicators ...............................................................................................................................13
FIGURE 1-3: Controls and Indicators .................................................................................................13
1.4: Digital Communicator.................................................................................................................................14
1.5.1: Main Circuit Board ...........................................................................................................................14
FIGURE 2-8: Auxiliary Relay and Relay Driver Terminals ...............................................................25
2.6: UL Power-limited Wiring Requirements ....................................................................................................26
FIGURE 2-9: Typical Wiring Diagram for UL Power-limited Requirements ....................................26
2.7: Digital Communicator.................................................................................................................................27
3.1: Entering Program Mode ..............................................................................................................................33
4.1: Switches in Normal Mode...........................................................................................................................50
4.3.7: Off Normal Reporting .......................................................................................................................55
4.3.8: Zone Disable/Enable .........................................................................................................................56
4.3.9: Fire Drill............................................................................................................................................56
4.4: Central Station Communications.................................................................................................................57
TABLE 4-1: Format Selection Address (16 & 42) ..............................................................................58
TABLE 4-2: Format Selection Address Explanation...........................................................................59
5.2: History Mode...............................................................................................................................................63
5.3.1: Zone Voltages ....................................................................................................................................64
TABLE 5-1: Nominal Zone Voltages..................................................................................................64
5.3.2: AC Line Voltage................................................................................................................................65
5.3.3: Battery Voltage ..................................................................................................................................65
5.4: Lamp Test ....................................................................................................................................................66
CHAPTER 7: Remote Site Upload/Download .......................................................................................................69
7.1: Downloading Program ................................................................................................................................69
A.1: The Main Power Supply ............................................................................................................................74
TABLE A-2: Filtered Load in Standby - external devices connected to TB4 only ............................74
TABLE A-3: Filtered Load in Alarm .................................................................................................75
C.2: Function Modes ........................................................................................................................................82
TABLE C-2: Function Modes .............................................................................................................82
Appendix D: Ademco Contact ID Format Event Code Descriptions ...............................................................83
Document 15140 Rev. G 01/02/02 P/N: 15140:G7
Page 8
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code for Local, Remote Station and Central Station Fire Alarm System
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Central Station Fire Alarm Systems Protected Premises Unit
(Automatic, Manual and Waterflow), Local Fire Alarm Systems (Automatic, Manual, Waterflow and
Sprinkler Supervisory), Auxiliary Protective Fire Alarm Systems (Automatic, Manual and Waterflow), Proprietary Protective Fire Alarm Systems (Automatic, Manual and Waterflow) and Remote
Station Fire Alarm Systems (Automatic, Manual and Waterflow).
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
The MS-5024UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator
Transmitter) all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel
accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally
open contact devices. Outputs include two NACs (Notification Appliance Circuits), alarm and trouble relays, supervisory and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to UL-listed Central Stations via
the public switched telephone network. The control panel has a built-in programmer and may also serve as a slave
communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery
level.
The control panel may be programmed or interrogated off-site via the public switched telephone network. Any IBM
™
compatible personal computer with DOS
4.01 or greater plus Windows™ 3.1 or greater, with a 1200 baud Hayes™
compatible modem and Fire•Lite Upload/Download software P/N PK-5024UD, may serve as a Service Terminal.
This allows download of the entire program or upload of the entire program, history file, walktest data, current status
and system voltages. The MS-5024UDE offers the same features as the MS-5024UD but allows connection to 220/
240 VAC input.
1.1Product Features
• Selectable as Fire Panel, Fire Panel/Communicator or Slave Communicator
• Programmable Zone ID: 2-wire smoke, pull station, normally open contact device, supervisory, supervisory
autosilence, waterflow silenceable or waterflow nonsilenceable
• One Style D (Class A) zone
• Four Style B (Class B) zones
• 3.6 amps usable power expandable to 5.6 amps
• Optional 5-zone Relay Module (RM-5F)
• CAC-5F Style D (Class A) Zone Converter Module
• Two NFPA Style Y (Class B) or Style Z (Class A) Notification Appliance (bell) Circuits
• Small size - 15" (38.1 cm) x 14.5" (36.83 cm) x 2.75" (6.985 cm)
• History file with 32 event storage
• Silence inhibit per NAC (Notification Appliance Circuit)
• Autosilence per NAC
10
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 11
Product Features
A
• Touchtone/Rotary dialing
• Programmable make/break ratio
• Fuseless design
• PRT-24 (Printer Interface Module)
• Print real-time system status
• Print history and walktest files, program contents and troubleshoot mode voltages
• PK-5024UD Upload/Download Software Kit
• Number of dial attempts (minimum of 5 and maximum of 10)
• Programmable channel ID (slave)
• Programmable zone delay (waterflow only)
• Form-C alarm and trouble relays
• Supervisory and communication fail relay drivers
• Low AC voltage sense
•One-man walktest
• Optional Dress Panel cover (DP-5024UD)
Optional DP-5024UD
FIRE CONTROL/COMMUNICATOR
AC POWER
ALARM
RESET
1
4
7
A
Note: Unless otherwise specified
FIGURE 1-1:
, MS-5024UD shall be used in this manual to refer to both the MS-5024UD and
MS-5024UDE Fire Alarm Control Communicators.
n
SILENCE
2
3
5
6
8
9
0
B
TROUBLE
SUPERVISORY
MODE
F
E
1ST
D
EVENT
ENTER
C
STORE
Document #15140 Rev.G 01/02/02 P/N 15140:G
11
Page 12
Product Features
FIGURE 1-2:
MS-5024UD Panel
Notification Appliance
Circuits
Standard
Transformer
Four Character
7-Segment LED
Display
Keypad
Optional
Transformer
Alarm &
Trouble
Relays
5 Input
Zones
Primary & Secondary Phone Lines
Annunciator
Driver Module
Interface
Connector
Relay Module
Interface
Connector
PROM U23
Piezo 85dB
1
Printer
Interface
Module
Connector
Holds up to 7 AH Batteries
Up to 60 Hrs. of Standby
Software for the Fire Alarm Control Communicator is located in a PROM inserted in the IC socket labeled
1.
U23. The MS-5024UD and MS-5024UDE each contain unique software. For specific panel software information, refer to the MS-5024UD(E) Field Software Change Procedure Document #50125.
12
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 13
Controls and Indicators
1.2Controls and Indicators
Front Panel Switches
RESETDigits 0-9
SILENCEA
MODEB
Up ArrowC
Down ArrowD
1st EVENTE
ENTER/STOREF
Displays
• Alarm - red LED
• Trouble - yellow LED
• Supervisory - yellow LED
• AC Power - green LED
• Four 7-Segment Displays - red
• Primary Phone Line Active - red LED
• Secondary Phone Line Active - red LED
• 'Kissoff' Signal from Central Station - green LED
• Silence - yellow LED
• Modem - green LED
FIGURE 1-3:
Controls and Indicators
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions.
1.3Circuits
Input Circuits
Five input circuits provide Style B configuration with one circuit also configurable for Style D. Input circuits may be
used as standard fire control panel zones or slave communicator input channels.
• Initiating Device Circuit 1 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 2 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 3 (Style B/D) accepts normally open contact devices, 2-wire smoke detectors and
waterflow devices
• Initiating Device Circuit 4 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 5 (Style B) accepts normally open contact devices and 2-wire smoke detectors
Output Circuits
• 24 Volt Resettable Power Output
• 24 Volt Nonresettable Power Output
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger
•Printer Port
Document #15140 Rev.G 01/02/02 P/N 15140:G
13
Page 14
Digital Communicator
Notification Appliance Circuits
Two Notification Appliance Circuits configurable for Style Y (Class B) or Style Z (Class A) with various programmable features.
Relays
Two dry Form-C relay contacts for system alarm and system trouble are provided. Contacts are rated 2 amps @ 30
VDC and 0.5 amps @ 30 VAC resistive.
Relay Drivers
Two relay driver outputs for supervisory and communication failure are available.
1.4Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the
Primary and Secondary phone lines. Telephone line active red LEDs are provided as well as a green 'kissoff' LED.
The integral digital communicator provides the following functions:
• Line Seizure - takes control of the phone lines disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone
• For tone burst or touchtone type formats: Discern proper 'Ack' and 'kissoff' tone(s). The frequency and time
duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
• Communicate in the following formats:
✓
12 Tone Burst Types (20 pps):
(3+1, 4+1, 3+1 Expanded, 4+1 Expanded and 4+2 Expanded)
✓
3 Touchtone Types:
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
(see Table 4-3 for a list of compatible receivers)
®
, programmable to rotary
1.5Components
1.5.1 Main Circuit Board
The main circuit board contains the system's CPU, power supply, other primary components and wiring interface
connectors. Optional modules plug in and are mounted to the main circuit board. The main circuit board is delivered
premounted in the cabinet.
1.5.2 Cabinet
The cabinet is red with an attractive navy blue front overlay. The backbox measures 15" (38.1 cm) x 14.5" (36.83
cm) x 2.75" (6.985 cm) and provides space for two batteries (up to 7 Amp Hours). Also available is an optional dress
panel (DP-5024UD), which mounts inside the cabinet.
14
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 15
Optional Devices
1.5.3 Transformer Assembly
FIGURE 1-4:
XRM-24(E) Transformer
One 100VA transformer is provided standard with the panel (3.6 amps
maximum). An optional 100VA transformer, XRM-24 (XRM-24E for
MS-5024UDE), is available to provide maximum accessory power (6.6
Standard
Transformer
amps maximum).
1.5.4 Batteries
The cabinet provides space for 7 Amp Hour batteries (for 12 Amp Hour
up to 18 Amp Hour batteries, use the listed BB-17F battery box). Batteries must be ordered separately.
Optional
Transformer
XRM-24(E)
1.6Optional Devices
1.6.1 RM-5F Five-Zone Relay Module
The RM-5F option module provides five Form-C relays which track zones 1 through 5. The module mounts to connector J7 on the lower right side of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and
Figure 2-16 on page 31.
1.6.2 CAC-5F Class A Converter Module
The CAC-5F Class A Converter module converts the Style B (Class B) Initiating Device Circuits to Style D (Class
A). The CAC-5F mounts to terminal block TB2, located in the upper center of the main circuit board. The removable terminal block on the CAC-5F module provides for ease of wiring. Refer to Figure 2-17, “CAC-5F Style D Converter,” on page 32
1.6.3 ADM-24 Annunciator Driver Module
The ADM-24 Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is
supervised for open circuits by this module. The Annunciator Driver Module mounts to connector J3 in the upper
right corner of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and Figure 2-11 on page
28.
1.6.4 RZA-5F Remote Annunciator
The RZA-5F Remote Annunciator mounts on a standard single-gang box and provides LED indication of the
following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• Alarm Zone 5 (red)
• System Trouble (yellow)
A Local Trouble Sounder and Tone Silence Switch are also provided. All LEDs and their wiring are supervised for
open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit
an easy change of zone information. Refer to Figure 2-12, “RZA-5F,” on page 28, Figure 2-13 on page 29 and Figure
2-14 on page 29. Note that the Remote Annunciator requires the use of the ADM-24 Annunciator Driver Module.
Document #15140 Rev.G 01/02/02 P/N 15140:G
15
Page 16
Specifications
1.6.5 PRT-24 Printer Interface Module
The Printer Interface Module may be used to connect a printer to the control panel for the purpose of printing a history report, walktest file, troubleshoot report, program entries or current system status. Printers require separate
external primary power. Connect the PRT-24 module (with cable) to the serial EIA-232 port on the printer. The
module mounts to the J2 connector on the main circuit board. Note that an EDP listed printer must be used if the
printer will be permanently attached to the control panel. Refer to Figure 2-15, “Remote Printer Connections,” on
page 30.
1.6.6 DP-5024UD Dress Panel
A red dress panel is available as an option. The dress panel restricts access to the system wiring while allowing
access to the membrane switch panel. Refer to Figure 1-1, “Optional DP-5024UD,” on page 11.
1.6.7 BB-17F Battery Box
The BB-17F battery box may be used to house two batteries, from 12 Amp Hour to 18 Amp Hour. The battery box
mounts directly below the cabinet and main circuit board. Refer to Figure 2-3, “Backbox and Battery Box,” on page
21. The BB-17F is red and is provided with knockouts.
1.6.8 PK-5024UD Programming Kit
This kit includes one 3½" diskette plus Instruction Manual P/N 50041. When the software is loaded into an IBM
compatible computer, it creates an off-line Service Terminal that allows any MS-5024UD panel to be uploaded or
downloaded over standard telephone lines.
Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.8 amp
Maximum Charger Capacity: 17 Amp Hour battery. (MS-5024UD cabinet holds maximum 7 Amp Hour battery.
Larger batteries require Fire•Lite BB-17F or other UL listed battery cabinet).
Initiating Device Circuits - TB2
Detector Zones 1, 2, 3, 4, 5Power-limited Circuitry
Operation: All zones are NFPA Style B, Zone 3 is NFPA Style B or Style D. Use CAC-5F module for Style D
operations
Normal Operating Voltage: 24 VDC (ripple = 100 mV maximum)
Alarm Current: 26 mAShort Circuit Current: 42 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K ohms, ½ watt (P/N 27072 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
2
) with 600V insulation
16
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 17
Specifications
Notification Appliance Circuits - TB5 & TB6
Nonregulated, special purpose power, Styles Y and Z supported
Power-limited circuitry
Operating Voltage: Nominal 24 volts
Current for all external devices: 3.0 amps expandable to 5.6 amps
Current-limit: PTC
Maximum signaling current/circuit: 2.5 amps
End-of-Line resistor: 4.7K ohms, ½ watt (P/N 71252 UL listed) for NACs
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Alarm and Trouble Relays - TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Alarm and Trouble: Form-C power-limited circuitry (see Figure 2-7 note for power-limited wiring application)
Auxiliary Outputs - TB4, Terminals 5 & 6
TB4-5 Supervisory Relay Driver: Normally high, active low, sinks up to 40 mA
TB4-6 Communication Failure: Normally high, active low, sinks up to 40 mA
Power-limited circuitry
Four-wire Smoke Detector Power - TB4, Terminals 3(+) & 4(-)
Maximum ripple voltage: 10 mV
RMS
Operating voltage: Nominal 24 volts
Up to 300 mA is available for powering 4-wire smoke detectors
Power-limited circuitry
Recommended maximum standby current is 50 mA (see Battery Calculations in Appendix A)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Nonresettable Filtered 24V Power - TB4 Terminals 1(+) & 2(-)
Maximum ripple voltage: 10 mV
RMS
Operating voltage: Nominal 24 volts
Total DC current available from this output is up to 300 mA
Power-limited circuitry
Recommended maximum standby current is 150 mA (see Battery Calculations in Appendix A)
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Notes:
For power supply calculations, refer to Appendix A.
1.
Total current for nonresettable power, 4-wire smoke detector power and two Notification Appliance Circuits
2.
must not exceed 5.6 amps. Total external system current in excess of 3.6 amps requires the XRM-24 Transformer (XRM-24E for 220/240 VAC applications) and 12 Amp Hour or 17 Amp Hour batteries.
Document #15140 Rev.G 01/02/02 P/N 15140:G
17
Page 18
Telephone Requirements and Warnings
1.8Telephone Requirements and Warnings
1.8.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 1.3B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.
1.8.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Manufacturer:Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
Product Model Number: MS-5024UD
FCC Registration Number: 1W6USA-20004-AL-E
Ringer Equivalence 1.3B
Note: The FCC ID label is located on the inside of the control panel door
1.8.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the
telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
18
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 19
Installation
CHAPTER 2Installation
2.1Mounting Options
FIGURE 2-1:
MS-5024UD Cabinet
The cabinet may be either surface mounted or semi-flush
mounted using the optional Trim Ring P/N: TR-1-R. The
door is removable during the installation period by opening
and lifting the door off the hinges. The cabinet mounts using
two key slots and two additional 0.25" (6.35 mm) diameter
holes located in the backbox. The key slots are located at the
top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage.
Mount the cabinet in a clean, dry, vibration-free area where
extreme temperatures are not encountered. The area should
be readily accessible with sufficient room to easily install and
maintain the panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on
the left. Determine the number of conductors required for the
devices to be installed. Sufficient knockouts are provided for
wiring convenience. Select the appropriate knockout(s) and
pull the required conductors into the box. Note that there are
no knockouts on the left (hinged) side of the cabinet. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.2Backbox Mounting
✓
Open the door and lift the door off the pin hinges
✓
Remove the main PC board assembly by unscrewing the four screws in the corners of the board. Two
standoffs support the board in the center. Set the board aside in a safe, clean place. Avoid static discharge which may damage the board.
✓
Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown
✓
Install two upper fasteners in the wall with the screw heads protruding
✓
Using the proper 'keyholes', mount the backbox over the two screws
✓
Mark and drill the lower two holes
✓
Mount backbox, install remaining fasteners and tighten
✓
When the location is dry and free of construction dust, reinstall the main PC board
Document #15140 Rev.G 01/02/02 P/N 15140:G
19
Page 20
Backbox Mounting
FIGURE 2-2:
Height=15.000”
(38.10 cm)
Cabinet Dimensions and Knockout Locations
2.875” (7.3 cm)
Draw wires through the respective knockout locations.
Backbox = 14.5”
(36.8 cm)
0.75”(1.9 cm)
9.1” (23.1 cm)
10.375”
(26.35 cm)
Top
Depth = 3.000”
(7.62 cm)
2.7”
(6.86cm)
Bottom
TR-1-R Trim Ring
Backbox Mounting Holes
ms2-4cab.cdr
1.125” (2.868 cm)
20
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 21
Backbox Mounting
FIGURE 2-3:
Door = 15.342“ (38.97 cm)
Backbox and Battery Box
To p
Door = 14.677 “ (37.28 cm)
Depth = 2.875" (7.3 cm)
Depth = 3.050“
(7.75 cm)
Bottom
Depth = 4.75
(12.065 cm)
Battery Box = 8.5“ (21.59 cm)
Battery Box = 14.5“
(37.384 cm)
Notes:
Mount the Fire Alarm Control Communicator cabinet to the wall
1.
Remove knockouts on bottom of FACP cabinet and top of BB-17F
2.
Using conduit, hang the BB-17F from the Fire Alarm Control Communicator cabinet, making sure there is at
3.
least ½" of clearance between the two cabinets
Anchor the BB-17F to the wall
4.
Document #15140 Rev.G 01/02/02 P/N 15140:G
21
Page 22
Operating Power
2.3Operating Power
!
CAUTION: Several different sources of power can be connected to this panel. Disconnect all sources of power
before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules
or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the MS-5024UD is
120 VAC, 60 Hz, 2.3 amps and for the MS-5024UDE is 220/240 VAC, 50 HZ, 1.2 amps. Run a pair of wires (with
ground conductor) from the protected premises main breaker box to TB1 of the main circuit board. As per the
National Electric Code, use 14 AWG (2.00 mm
may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not
contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel
operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm
one of the transformer mounting studs. Note: Do not use conduit for the Earth Ground connection since this does not
provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J1 on the main circuit board using the
plug-in connector provided. The battery charger is current-limited and capable of recharging sealed lead acid type
batteries. The charger shuts off when the system is in alarm or if the battery voltage drops too low (below 17.4
VDC). See Appendix A for calculation of the correct battery rating.
2
) or heavier gauge wire with 600V insulation. No other equipment
2
)] to
CAUTION: Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fab-
!
rics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek
immediate medical attention.
FIGURE 2-4:
Connect Earth Ground Wire
Operating Power Connections
22
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 23
Input Circuits
2.4Input Circuits
The control panel has five zone input circuits. The maximum loop resistance limit for each is 100 ohms. All field
wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated
as well as communicated to a Central Station.
Each zone is a Style B Initiating Device Circuit (IDC) designed to accept any normally open contact device and conventional 2-wire, 24 volt smoke detectors. Each zone is power-limited to 7.26 mA in standby and 42 mA in alarm.
Zone 3 may also be configured as a Style D Initiating Device Circuit.
Note: All five initiating zones may be converted to Style D (Class A) by using a CAC-5F Class A Converter module.
Refer to Figure 2-17, “CAC-5F Style D Converter,” on page 32.
Zones 1-5 may be programmed as listed below. The factory default is 2-wire smoke detector for all zones:
• 2-wire smoke detector (factory default)
• Pull station
• Normally open contact device(s)
• Supervisory
• Supervisory, autoresettable
Zone 3 may also be programmed as:
• Waterflow, silenceable
• Waterflow, nonsilenceable
Note: A maximum of five waterflow devices may be used on zone 3 per NFPA 72.
Four-wire smoke detectors may be connected to any zone. Resettable power is provided via TB4, Terminals 3 and 4.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any
zone. This is not recommended, however, since specific and detailed reports will not be possible. For example, the
report of general fire alarm versus pull station fire alarm or smoke detector fire alarm.
Refer to the Fire•Lite Device Compatibility Document for a list of compatible smoke detectors.
FIGURE 2-5:
UL listed compatible 2-wire smoke detector
Typical Initiating Device Circuit Connections
Style B Initiating Device Circuit
(supervised and power-limited)
4.7K ohm, ½ watt P/N 71252 UL listed
Manual Pull Station
Heat Detector
Style D Initiating Device Circuit
(supervised and power-limited)
UL listed compatible 2-wire smoke detector
Manual Pull Station
Heat Detector
MS-5024UD
Dummy load all unused circuits with 4.7K ohm
Document #15140 Rev.G 01/02/02 P/N 15140:G
ELR P/N 71245, across B+ and B-.
23
Page 24
Output Circuits
2.5Output Circuits
DC Power Output Connections
All DC power outputs are power-limited.
FIGURE 2-6:
Telephone Circuits
Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 (primary)
and PH2 (secondary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection. Refer to Figure 2-10, “Wiring Phone Jacks,” on page 27.
Auxiliary Power Connections
Nonresettable Power (300 mA)
24 VDC filtered, nonresettable
power can be obtained from TB4,
Terminals 1(+) and 2(-)
+ - + -
1 2 3 4 5 6
TB4
4-Wire Smoke Detector Power (300 mA)
24 VDC filtered, resettable power for 4-wire
smoke detectors can be obtained from TB4,
Terminals 3(+) and 4(-)
Notification Appliance Circuits
The MS-5024UD provides two NACs (Notification Appliance Circuits) which can be configured as Style Y or Style
Z. Each circuit is capable of 2.5 amps of current. Total current drawn from these as will as other DC power outputs
cannot exceed 3.6 amps with the standard transformer, 5.6 amps if an optional XRM-24 transformer (XRM-24E for
the MS-5024UDE) is installed. Circuits are supervised and power-limited. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.
FIGURE 2-7:
Notification Appliance Circuit Connections
Style Y Notification Appliance Circuit (super-
vised and power-limited). 4.7K ohm, ½ watt
Polarized Bell
Polarized Strobe
Polarized Horn
P/N 71252 UL listed EOL resistor.
Polarized Bell
Polarized Horn
Polarized Horn
Note: Notification
Appliance Circuit
polarity shown in
alarm
state.
Dummy Load all
unused circuits
P/N 71245
Both Notification Appliance Circuits may be programmed as follows:
• Silenceable
• Nonsilenceable
• Enabled/disabled
• Silence inhibited
• Autosilence, 5 to 30 minutes
• Coded (March Time, Temporal or California)
24
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 25
Output Circuits
Standard Relays
The control panel provides a set of Form-C alarm and a set of Form-C trouble contacts rated for 2.0 amps @ 30VDC
(resistive).
Relay Drivers
Relay driver outputs are provided for supervisory and communicator failure. These outputs can be used to drive UL
864 listed remote relays such as the MR-101C and MR-201C.
The control panel's open collector outputs on TB4, terminals 5 and 6 can be used to activate UL 864 listed relays.
Outputs are rated for 40 mA. The normal condition for each output is as shown below:
TB4-5 SupervisoryOff (deenergized)
TB4-6 Communications FailureOff (deenergized)
Relays must be placed inside the cabinet or in a UL 864 recognized enclosure. Wiring from the control panel's terminals on TB4 to the relays must be less than 3 feet in length and enclosed in conduit. Wiring from the relay outputs
must remain in the same room as the location of the enclosure and be enclosed in conduit.
FIGURE 2-8:
Auxiliary Relay and Relay Driver Terminals
Relay Connections
Alarm
NO NC C NC NO C
1 2 3 4 5 6
T
B
3
Note: The alarm and trouble Form-C dry
contact relays must be power-limited circuits. Any Form-C dry contact relay that
may be used must be wired from TB4 or a
UL listed power-limited power supply.
Trouble
All wiring to relay must
be in same room as
panel and in conduit
Relay Driver Connections
Relay energized LED
MR-201/C*
Relay energized LED
DPDT Contacts
10 Amps @ 115 VAC
Connections must be in
the same room as the
panel
DPDT Contacts
10 Amps @ 115 VAC
* The MR-101C and MR-201C include an enclosure.
Document #15140 Rev.G 01/02/02 P/N 15140:G
MR-101/C*
25
Page 26
UL Power-limited Wiring Requirements
2.6UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all
power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or
conduits. A typical wiring diagram for the MS-5024UD is shown below. Refer to Figure 2-16, “RM-5F Installation
and Wiring,” on page 31 for additional information on wiring the RM-5F Relay module.
FIGURE 2-9:
Typical Wiring Diagram for UL Power-limited Requirements
Power-limited Circuits
Power-limited
Circuit
26
Nonpower-limited
Circuit
AC Power
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 27
Digital Communicator
2.7Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line control/command is made
possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the
panel's digital communicator be located as the first device on the incoming telephone circuit to properly function.
The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone
lines is required as shown below.
FIGURE 2-10:
Wiring Phone Jacks
Document #15140 Rev.G 01/02/02 P/N 15140:G
27
Page 28
Optional Boards
2.8Optional Boards
2.8.1 ADM-24 Annunciator Driver Module
The Annunciator Driver Module supports the RZA-5F Remote Annunciator. Annunciator wiring is supervised for
open conditions by this module. The Annunciator Driver Module mounts to J3 in the upper right corner of the main
circuit board.
FIGURE 2-11:
ADM-24 Annunciator Driver Module
Main Circuit Board
2.8.2 RZA-5F Remote Annunciator
The RZA-5F mounts on a standard single-gang electrical box and
provides LED indication of the following:
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
Connector located on
Standoff
FIGURE 2-12:
back of board
ADM-24
RZA-5F
The remote annunciator provides individual zone alarm LEDs, a
system trouble LED, a local piezo sounder and a remote sounder
shut off switch. All LEDs and their wiring are supervised for
open conditions. Any open condition will cause the System Trouble LED to turn on.
Note: The Remote Annunciator requires the use of an ADM-24
Annunciator Driver Module.
28
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 29
Optional Boards
FIGURE 2-13:
Wiring the RZA-5F/ADM-24
ADM-24
+24V
Note: Make wiring connections with system
power off. Maximum wire impedance is 100
ohms per wiring connection.
RZA-5F
FIGURE 2-14:
Installing the Annunciator (Single-Gang Electrical Box)
screw #6-32 x 1.00” LG
Single-gang Box
RZA-5F
Document #15140 Rev.G 01/02/02 P/N 15140:G
29
Page 30
Optional Boards
2.8.3 PRT-24 Printer Interface Module
A remote printer may be permanently or temporarily connected to provide a hardcopy printout of normal current system status and activity, program entries, history file, troubleshoot mode voltages and walktest data. The PRT-24 provides an EIA-232 conversion to adapt to most 40 and 80 column printers.
CAUTION: DO NOT connect a printer to the Fire Alarm Control Communicator if a ground fault exists on the panel.
Circuit damage may result.
!
Installation
Remote printers require separate external primary power. Also required is the PRT-24 which includes the Printer
Interface Module and a 6 foot interface cable prewired to a DB25 connector. Connect the interface cable to the PRT24 as shown in Figure 2-15. Insert the two supplied standoffs into mounting holes near the J2 connector on the main
circuit board. Connect the Printer Interface board to J2 on the main circuit board, press onto standoffs and connect
the attached cable to the serial EIA-232 port on the printer. The printer may be placed a maximum of 50 feet from the
panel. Note that a ground fault may occur on the control panel when this connection is made. For this reason, it is
important that there be no preexisting ground fault on the panel. For permanent printer connection, a ground fault is
not allowed.
Printer Configuration
The PRT-24 is required. Also refer to the documentation supplied with your printer. Set the printer's options as listed
in the table below.
FIGURE 2-15:
YELLOW
Remote Printer Connections
J1 located on back
of PRT-24 board
BLK
RED
GRN
Typical Printer Settings
Under the MENU area:
COMMUNICATION SETUP:
DATA BITS:7
PARITY:EVEN
STOP BIT:1 STOP
BAUD RATE:2400
30
PRT-24 connection to main circuit board
DB-25P Front View
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 31
Optional Boards
2.8.4 RM-5F Five-Zone Relay Module
The RM-5F option module provides five Form-C relays which track zones 1 through 5. The module mounts to connector J7 on the lower right side of the main circuit board as illustrated in Figure 2-16.
Nonpower-limited and power-limited wiring must have a minimum distance of 0.25" (6.35 mm) wire to wire. If this
module is used to drive nonpower-limited and power-limited circuits:
Skip a set of dry contacts to maintain the 0.25" (6.35mm) required space between power-limited and non-
1.
power-limited circuits. The wiring of this module must follow the requirements as specified above - OR
If this module is needed to drive power-limited and nonpower-limited relays that are next to each other, one
2.
relay must be used as an open circuit and the other as a closed circuit as shown in Figure 2-16.
FIGURE 2-16:
RM-5F Installation and Wiring
Connector located
on back of board
Main Circuit Board
Note: If relays are used as power-limited
circuits, paste supplied label to terminal
block as indicated below.
Power
Limited
RM-5F
Standoffs
Power-limited
Power-limited
Power-limited
No connection
No connection
Power-limited
Power-limited
Note: Zone Relay Contact Ratings - Maximum Switched Power is 150 watts or 1250 VA. Maximum Switched Current is 5 Amps
UL Rating: 5 Amps @ 30 VDC or 125 VAC, resistive. Contact Material: Silver Alloy
Document #15140 Rev.G 01/02/02 P/N 15140:G
31
Page 32
Optional Boards
2.8.5 CAC-5F Class A Converter Module
The CAC-5F module converts the Style B (Class B) Initiating Device Circuits to Style D (Class A). The CAC-5F
mounts to terminal block TB2 located in the upper center of the main circuit board. Refer to Figure 2-17, “CAC-5F
Style D Converter,” on page 32. The removable terminal block on the CAC-5F module provides for ease of wiring.
FIGURE 2-17:
UL listed compatible 2-wire smoke detector
Insert two supplied standoffs into
CAC-5F circuit board, remove protective paper from self-adhesive base of
standoff, install circuit board into TB2
of MS-5024UD and press to adhere
standoffs to cabinet.
CAC-5F Style D Converter
Manual Pull Station
Heat Detector
Waterflow Switch
Waterflow Switch
Waterflow Switch
Dummy load all unused circuits with 4.7K ohm
ELR P/N: 71245 across B+ and B-
CAC-5F Module
32
MS-5024UD Main Circuit Board
Notes:
Circuits 1 through 5 can accommodate 2-wire smoke detectors, plus any normally open contact device such as
1.
heat detectors or manual pull stations.
Only circuit 3 accommodates the nonsilenceable waterflow function.
2.
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 33
Programming Instructions
CHAPTER 3Programming Instructions
This chapter describes programming the panel from the onboard keyboard. Chapter 7 describes remote site upload/
download which includes programming the control panel on premises. Programming of the control panel is possible
at any time except when an alarm condition is present or during a fire drill.
The control panel has been designed for many different types of applications. After examining your specific application, review the programming options and choose the entries best suited for your system.
The control panel has a built-in intelligent programmer. All programming selections are stored in nonvolatile Electrically Erasable Programmable Read-Only Memory (EEPROM). This ensures that the control panel will remember all
entries made in programming mode even if both AC and battery power are removed. Invalid entries cause a 'beep'
from the onboard piezo sounder.
The user must program the primary and secondary phone numbers, account numbers and 24 hour test report times for
each Central Station account and the current time and date. The control panel comes with factory chosen options/features already programmed. Other options/features may be programmed if desired. If all factory default settings are
acceptable, programming is complete.
3.1Entering Program Mode
To enter the Program Mode, press the MODE key once, (the display will go blank). You then have ten seconds to
start entering the Program Mode code 7764.
7764 spells PROG on a Touch-Tone
☛
If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key. Note that as
information is entered into the control panel, the digits will scroll across the display from right to left:
___7
__77
_776
7764
A pause of up to 10 seconds is allowed between each number while entering the code. After pressing the [ENTER/
STORE] key, the control panel will be in Program Mode and display 00_F. A maximum of 10 minutes of idle time
is allowed at this point before starting program entries, otherwise, the control panel will return to Normal Mode. A
maximum of 10 minutes is allowed between any key stroke. All entries made prior to the 10 minute time-out are
valid and will be stored.
Once in Program Mode, the control panel will:
• Blink the trouble LED
• Activate the trouble relay
• Disable the NACs (Notification Appliance Circuits)
• Disable the alarm relay
•Display 00_F
• Ignore all other keys other than those mentioned in this section
• Continue to communicate any events not previously acknowledged at a Central Station prior to entering
Program Mode
®
phone.
Document #15140 Rev.G 01/02/02 P/N 15140:G
33
Page 34
Switch Functions
Note that address location 56 is factory defaulted to '0' for 'control panel only.' This keeps the communicator off until
location 56 is changed to '1' for 'slave communicator' or '2' for 'panel/communicator.' Once location 56 is set to '1' or
'2' and a valid phone number is entered, entry into the Program Mode will cause transmission of the 'system off normal' report.
When viewing any address in Program Mode, the first three digits on the left of the display represent the memory
address which can be 00 to 374 (alpha-characters are not used). The last digit, farthest right, represents the contents
of the memory address. The first address and contents displayed upon entering Program Mode are shown below:
00_F
(address)(data)
3.2Switch Functions
The function of each keypad key in Program Mode is shown below.
FIGURE 3-1:
No function in
Program Mode
Control Panel Keypad
Address entry keys are 0 - 9
Data entry keys are 0 - 9 and
A - F
Select operating mode
Increment memory address
Decrement memory address
One press = first memory address
Two presses = type any address
Save data, go to next address
3.3Programming Options
Primary Central Station Phone Number (00-15)
The first sixteen addresses (00-15) are factory set to 'F' (00_F to 15_F). Programming this feature is typically done as
follows: If the phone number to be entered is 484-7161, press 4. The display will read 00_4. Press [ENTER/STORE] to save the entry to memory and increment to the next address 01_F.
Enter the remaining numbers in their respective addresses as shown below:
Phone Number
Addresses
34
4847161FFFFFFFFF
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 35
Programming Options
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha-characters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = 3-second pause
E = 5-second pause
F = end of phone number (Note: F must be entered)
Primary Central Station Number Communication Format (16)
One location is needed to select the Communication Format for the primary phone number. Address 16 is used for
this purpose. The default (factory setting) for this address is 'E' for Ademco Contact ID format. '0' through 'E' may be
entered in place of the default entry. After making the selection, press the [ENTER/STORE] key to store the selection. The available format options are as follows:
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes. Refer to Table 3-1 through Table 3-5 .
Document #15140 Rev.G 01/02/02 P/N 15140:G
35
Page 36
Programming Options
3+1, 4+1 Express, 4+1 Standard and Expanded & 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 16, the following data is automatically programmed for the Primary Central Station phone number event codes. Enter '0' for the Setting to disable the report.
127Primary # Zone 1 Alarm Code1
128Primary # Zone 2 Alarm Code1
129Primary # Zone 3 Alarm Code1
130Primary # Zone 4 Alarm Code1
131Primary # Zone 5 Alarm Code1
132Primary # Zone 1 Disable CodeF
133Primary # Zone 2 Disable CodeF
134Primary # Zone 3 Disable CodeF
135Primary # Zone 4 Disable CodeF
136Primary # Zone 5 Disable CodeF
137Primary # Drill Code9
138Primary # AC Fault CodeF
139Primary # Zone 1 Fault CodeF
140Primary # Zone 2 Fault CodeF
141Primary # Zone 3 Fault CodeF
142Primary # Zone 4 Fault CodeF
143Primary # Zone 5 Fault CodeF
144Primary # Earth Fault CodeF
145Primary # Low Battery Fault CodeF
146Primary # No Battery Fault CodeF
147Primary # Telco Primary Line Fault CodeF
148Primary # Telco Secondary Line Fault CodeF
149Primary # NAC #1 Fault CodeF
150Primary # NAC #2 Fault CodeF
151Primary # Communication Trouble Primary # CodeF
152Primary # Communication Trouble Secondary # CodeF
153Primary # Annunciator Fault CodeF
154Primary # System Off Normal CodeF
155Primary # Zone 1 Alarm Restore CodeE
156Primary # Zone 2 Alarm Restore CodeE
157Primary # Zone 3 Alarm Restore CodeE
158Primary # Zone 4 Alarm Restore CodeE
159Primary # Zone 5 Alarm Restore CodeE
160Primary # Zone 1 Disable Restore CodeE
161Primary # Zone 2 Disable Restore CodeE
162Primary # Zone 3 Disable Restore CodeE
163Primary # Zone 4 Disable Restore CodeE
164Primary # Zone 5 Disable Restore CodeE
165Primary # Drill Restore Code9
166Primary # AC Fault Restore CodeE
167Primary # Zone 1 Fault Restore CodeE
168Primary # Zone 2 Fault Restore CodeE
169Primary # Zone 3 Fault Restore CodeE
170Primary # Zone 4 Fault Restore CodeE
171Primary # Zone 5 Fault Restore CodeE
172Primary # Earth Fault Restore CodeE
173Primary # Low Battery Fault Restore CodeE
174Primary # No Battery Fault Restore CodeE
175Primary # Telco Primary Line Fault Restore CodeE
176Primary # Telco Secondary Line Fault Restore CodeE
177Primary # NAC # 1 Fault Restore CodeE
178Primary # NAC # 2 Fault Restore CodeE
179Primary # Communication Trouble Primary # Restore CodeE
180Primary # Communication Trouble Secondary # Restore CodeE
181Primary # Annunciator Fault Restore CodeE
182Primary # System Off Normal Restore CodeE
183Primary # System Test Report9
184Primary # System Abnormal Test ReportF
185Primary # Request for Upload/Download7
186Primary # Successful Upload7
187Primary # Successful Download7
188Primary # Failed Upload/Download7
36
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 37
Programming Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' is entered for address 16, the following data is automatically programmed for the Primary Central Station phone number event codes. Enter '00' for the Setting to disable the report.
TAB LE 3- 2:
Primary Event Codes - 4+2 Standard and 4+2 Express
AddressDescriptionSetting
127 - 128Primary # Zone 1 Alarm Code11
129 - 130Primary # Zone 2 Alarm Code12
131 - 132Primary # Zone 3 Alarm Code13
133 - 134Primary # Zone 4 Alarm Code14
135 - 136Primary # Zone 5 Alarm Code15
137 - 138Primary # Zone 1 Disable CodeF1
139 - 140Primary # Zone 2 Disable CodeF2
141 - 142Primary # Zone 3 Disable CodeF3
143 - 144Primary # Zone 4 Disable CodeF4
145 - 146Primary # Zone 5 Disable CodeF5
147 - 148Primary # Drill Code97
149 - 150Primary # AC Fault CodeF6
151 - 152Primary # Zone 1 Fault CodeF1
153 - 154Primary # Zone 2 Fault CodeF2
155 - 156Primary # Zone 3 Fault CodeF3
157 - 158Primary # Zone 4 Fault CodeF4
159 - 160Primary # Zone 5 Fault CodeF5
161 - 162Primary # Earth Fault CodeF7
163 - 164Primary # Low Battery Fault CodeF8
165 - 166Primary # No Battery Fault CodeF9
167 - 168Primary # Telco Primary Line Fault CodeFA
169 - 170Primary # Telco Secondary Line Fault CodeFB
171 - 172Primary # NAC #1 Fault CodeFC
173 - 174Primary # NAC #2 Fault CodeFC
175 - 176Primary # Communication Trouble Primary # CodeFD
177 - 178Primary # Communication Trouble Secondary # CodeFE
179 - 180Primary # Annunciator Fault CodeFC
181 - 182Primary # System Off Normal CodeFF
183 - 184Primary # Zone 1 Alarm Restore CodeE1
185 - 186Primary # Zone 2 Alarm Restore CodeE2
187 - 188Primary # Zone 3 Alarm Restore CodeE3
189 - 190Primary # Zone 4 Alarm Restore CodeE4
191 - 192Primary # Zone 5 Alarm Restore CodeE5
193 - 194Primary # Zone 1 Disable Restore CodeE1
195 - 196Primary # Zone 2 Disable Restore CodeE2
197 - 198Primary # Zone 3 Disable Restore CodeE3
199 - 200Primary # Zone 4 Disable Restore CodeE4
201 - 202Primary # Zone 5 Disable Restore CodeE5
203 - 204Primary # Drill Restore Code98
205 - 206Primary # AC Fault Restore CodeE6
207 - 208Primary # Zone 1 Fault Restore CodeE1
209 - 210Primary # Zone 2 Fault Restore CodeE2
211 - 212Primary # Zone 3 Fault Restore CodeE3
213 - 214Primary # Zone 4 Fault Restore CodeE4
215 - 216Primary # Zone 5 Fault Restore CodeE5
217 - 218Primary # Earth Fault Restore CodeE7
219 - 220Primary # Low Battery Fault Restore CodeE8
221 - 222Primary # No Battery Fault Restore CodeE9
223 - 224Primary # Telco Primary Line Fault Restore CodeEA
225 - 226Primary # Telco Secondary Line Fault Restore CodeEB
227 - 228Primary # NAC # 1 Fault Restore CodeEC
229 - 230Primary # NAC # 2 Fault Restore CodeEC
231 - 232Primary # Communication Trouble Primary # Restore CodeED
233 - 234Primary # Communication Trouble Secondary # Restore CodeEE
235 - 236Primary # Annunciator Fault Restore CodeEC
237 - 238Primary # System Off Normal Restore CodeEF
239 - 240Primary # System Test Report99
241 - 242Primary # System Abnormal Test Report91
243 - 244Primary # Request for Upload/Download71
245 - 246Primary # Successful Upload72
247 - 248Primary # Successful Download73
249 - 250Primary # Failed Upload/Download74
Document #15140 Rev.G 01/02/02 P/N 15140:G
37
Page 38
Programming Options
Ademco Contact ID Format
If 'E' is entered for address 16 in Program Mode Level 1, the data shown in Table 3-3 is automatically programmed for the Primary Central Station phone number event codes. Enter '000' for the setting to disable the
report. The Setting entry is programmable, the Zone Number cannot be changed. Restoral code settings match
the settings shown with the addition of an 'R' code transmitted. Refer to page 83 for additional information.
TABLE 3-3:
AddressDescriptionSettingZone No.
Event Codes, Primary Central Station Number
127-129Primary # Zone 1 Alarm Code111001
130-132Primary # Zone 2 Alarm Code111002
133-135Primary # Zone 3 Alarm Code111003
136-138Primary # Zone 4 Alarm Code111004
139-141Primary # Zone 5 Alarm Code111005
142-144Primary # Zone 1 Disabled Code570001
145-147Primary # Zone 2 Disabled Code570002
148-150Primary # Zone 3 Disabled Code570003
151-153Primary # Zone 4 Disabled Code570004
154-156Primary # Zone 5 Disabled Code570005
157-159Primary # Drill Code604000
160-162Primary # AC Fault Code301000
163-165Primary # Zone 1 Fault Code380001
166-168Primary # Zone 2 Fault Code380002
169-171Primary # Zone 3 Fault Code380003
172-174Primary # Zone 4 Fault Code380004
175-177Primary # Zone 5 Fault Code380005
178-180Primary # Earth Fault Code310000
181-183Primary # Low Battery Fault Code302000
184-186Primary # No Battery Fault Code311000
187-189Primary # Telco Primary Line Fault Code351000
190-192Primary # Telco Secondary Line Fault Code352000
193-195Primary # NAC #1 Fault Code321001
196-198Primary # NAC #2 Fault Code322002
199-201Primary # Comm Trouble Primary # Code354001
202-204Primary # Comm Trouble Secondary # Code354002
205-207Primary # Annunciator Fault Code330000
208-210Primary # System Off Normal Code308000
211-213Primary # System Test Message602000
214-216Primary # System Abnormal Test Message608000
217-219Primary # Upload/Download Request Code411000
220-222Primary # Upload Successful Code416000
223-225Primary # Download Successful Code412000
226-228Primary # Upload/Download Failed Code413000
38
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 39
Programming Options
Primary Central Station Number Account Code (17-20)
A unique account code is provided by the Central Station. Four locations at addresses 17-20 (factory default settings
of all '0s') are used to enter the account code. Valid entries are 0 to 9 and A to F. The number of digits entered must
match the format selection. If programming '2, 3, 4 or 5' into address 16, enter the three digit account code supplied
by the Central Station (location 20 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C or D' into address 16, enter
the four digit account code supplied by the Central Station.
Primary Central Station Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four locations, from addresses 21-24. The default is '2345' (11:45 PM). The limits for each address location are as follows:
21 - enter 0-2
22 - enter 0-9
23 - enter 0-5
24 - enter 0-9
Do not use 'A-F'
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (25)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be sent
every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter '1' for 12 hours, '2' for
8 hours or '3' for 6 hours.
Secondary Central Station Phone Number (26-41)
Addresses (26-41) are factory set to 'F' (26_F to 41_F). Programming this feature is typically done as follows: If the
phone number to be entered is 484-7161, press 4. The display will read 26_4. Press [ENTER/STORE] to save the
entry to memory and increment to the next address 27_F.
Enter the remaining numbers in their respective addresses as shown below:
Phone Number
Addresses
4847161FFFFFFFFF
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha-characters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = 3-second pause
E = 5-second pause
F = end of phone number (Note: F must be entered)
Document #15140 Rev.G 01/02/02 P/N 15140:G
39
Page 40
Programming Options
Secondary Central Station Number Communication Format (42)
One location is needed to select the Communication Format for the secondary phone number. Address 42 is used for
this purpose. The default (factory setting) for this address is 'E' for Ademco Contact ID format. Selections '0'
through 'E' may be entered in place of the default entry. After making the selection, press the [ENTER/STORE] key
to store the selection. The available format options are as follows:
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes. Refer to Table 3-1 through Table 3-5 .
40
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 41
Programming Options
3+1, 4+1 Express, 4+1 Standard and Expanded & 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 42, the following data is automatically programmed for the
Secondary Central Station phone number event codes. Enter '0' for the Setting to disable the report.
251Secondary # Zone 1 Alarm Code1
252Secondary # Zone 2 Alarm Code1
253Secondary # Zone 3 Alarm Code1
254Secondary # Zone 4 Alarm Code1
255Secondary # Zone 5 Alarm Code1
256Secondary # Zone 1 Disable CodeF
257Secondary # Zone 2 Disable CodeF
258Secondary # Zone 3 Disable CodeF
259Secondary # Zone 4 Disable CodeF
260Secondary # Zone 5 Disable CodeF
261Secondary # Drill Code9
262Secondary # AC Fault CodeF
263Secondary # Zone 1 Fault CodeF
264Secondary # Zone 2 Fault CodeF
265Secondary # Zone 3 Fault CodeF
266Secondary # Zone 4 Fault CodeF
267Secondary # Zone 5 Fault CodeF
268Secondary # Earth Fault CodeF
269Secondary # Low Battery Fault CodeF
270Secondary # No Battery Fault CodeF
271Secondary # Telco Primary Line Fault CodeF
272Secondary # Telco Secondary Line Fault CodeF
273Secondary # NAC #1 Fault CodeF
274Secondary # NAC #2 Fault CodeF
275Secondary # Communication Trouble Primary # CodeF
276Secondary # Communication Trouble Secondary # CodeF
277Secondary # Annunciator Fault CodeF
278Secondary # System Off Normal CodeF
279Secondary # Zone 1 Alarm Restore CodeE
280Secondary # Zone 2 Alarm Restore CodeE
281Secondary # Zone 3 Alarm Restore CodeE
282Secondary # Zone 4 Alarm Restore CodeE
283Secondary # Zone 5 Alarm Restore CodeE
284Secondary # Zone 1 Disable Restore CodeE
285Secondary # Zone 2 Disable Restore CodeE
286Secondary # Zone 3 Disable Restore CodeE
287Secondary # Zone 4 Disable Restore CodeE
288Secondary # Zone 5 Disable Restore CodeE
289Secondary # Drill Restore Code9
290Secondary # AC Fault Restore CodeE
291Secondary # Zone 1 Fault Restore CodeE
292Secondary # Zone 2 Fault Restore CodeE
293Secondary # Zone 3 Fault Restore CodeE
294Secondary # Zone 4 Fault Restore CodeE
295Secondary # Zone 5 Fault Restore CodeE
296Secondary # Earth Fault Restore CodeE
297Secondary # Low Battery Fault Restore CodeE
298Secondary # No Battery Fault Restore CodeE
299Secondary # Telco Primary Line Fault Restore CodeE
300Secondary # Telco Secondary Line Fault Restore CodeE
301Secondary # NAC # 1 Fault Restore CodeE
302Secondary # NAC # 2 Fault Restore CodeE
303Secondary # Communication Trouble Primary # Restore CodeE
304Secondary # Communication Trouble Secondary # Restore CodeE
305Secondary # Annunciator Fault Restore CodeE
306Secondary # System Off Normal Restore CodeE
307Secondary # System Test Report9
308Secondary # System Abnormal Test ReportF
309Secondary # Request for Upload/Download7
310Secondary # Successful Upload7
311Secondary # Successful Download7
312Secondary # Failed Upload/Download7
Document #15140 Rev.G 01/02/02 P/N 15140:G
41
Page 42
Programming Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' is entered for address 42, the following data is automatically programmed for the Secondary Central Station phone number event codes. Enter '00' for the Setting to disable the report.
TABLE 3-5:
Secondary Event Codes - 4+2 Standard and 4+2 Express
AddressDescriptionSetting
251 - 252Secondary # Zone 1 Alarm Code11
253 - 254Secondary # Zone 2 Alarm Code12
255 - 256Secondary # Zone 3 Alarm Code13
257 - 258Secondary # Zone 4 Alarm Code14
259 - 260Secondary # Zone 5 Alarm Code15
261 - 262Secondary # Zone 1 Disable CodeF1
263 - 264Secondary # Zone 2 Disable CodeF2
265 - 266Secondary # Zone 3 Disable CodeF3
267 - 268Secondary # Zone 4 Disable CodeF4
269 - 270Secondary # Zone 5 Disable CodeF5
271 - 272Secondary # Drill Code97
273 - 274Secondary # AC Fault CodeF6
275 - 276Secondary # Zone 1 Fault CodeF1
277 - 278Secondary # Zone 2 Fault CodeF2
279 - 280Secondary # Zone 3 Fault CodeF3
281 - 282Secondary # Zone 4 Fault CodeF4
283 - 284Secondary # Zone 5 Fault CodeF5
285 - 286Secondary # Earth Fault CodeF7
287 - 288Secondary # Low Battery Fault CodeF8
289 - 290Secondary # No Battery Fault CodeF9
291 - 292Secondary # Telco Primary Line Fault CodeFA
293 - 294Secondary # Telco Secondary Line Fault CodeFB
295 - 296Secondary # NAC #1 Fault CodeFC
297 - 298Secondary # NAC #2 Fault CodeFC
299 - 300Secondary # Communication Trouble Primary # CodeFD
301 - 302Secondary # Communication Trouble Secondary # CodeFE
303 - 304Secondary # Annunciator Fault CodeFC
305 - 306Secondary # System Off Normal CodeFF
307 - 308Secondary # Zone 1 Alarm Restore CodeE1
309 - 310Secondary # Zone 2 Alarm Restore CodeE2
311 - 312Secondary # Zone 3 Alarm Restore CodeE3
313 - 314Secondary # Zone 4 Alarm Restore CodeE4
315 - 316Secondary # Zone 5 Alarm Restore CodeE5
317 - 318Secondary # Zone 1 Disable Restore CodeE1
319 - 320Secondary # Zone 2 Disable Restore CodeE2
321 - 322Secondary # Zone 3 Disable Restore CodeE3
323 - 324Secondary # Zone 4 Disable Restore CodeE4
325 - 326Secondary # Zone 5 Disable Restore CodeE5
327 - 328Secondary # Drill Restore Code98
329 - 330Secondary # AC Fault Restore CodeE6
331 - 332Secondary # Zone 1 Fault Restore CodeE1
333 - 334Secondary # Zone 2 Fault Restore CodeE2
335 - 336Secondary # Zone 3 Fault Restore CodeE3
337 - 338Secondary # Zone 4 Fault Restore CodeE4
339 - 340Secondary # Zone 5 Fault Restore CodeE5
341 - 342Secondary # Earth Fault Restore CodeE7
343 - 344Secondary # Low Battery Fault Restore CodeE8
345 - 346Secondary # No Battery Fault Restore CodeE9
347 - 348Secondary # Telco Primary Line Fault Restore CodeEA
349 - 350Secondary # Telco Secondary Line Fault Restore CodeEB
351 - 352Secondary # NAC # 1 Fault Restore CodeEC
353 - 354Secondary # NAC # 2 Fault Restore CodeEC
355 - 356Secondary # Communication Trouble Primary # Restore CodeED
357 - 358Secondary # Communication Trouble Secondary # Restore CodeEE
359 - 360Secondary # Annunciator Fault Restore CodeEC
361 - 362Secondary # System Off Normal Restore CodeEF
363 - 364Secondary # System Test Report99
365 - 366Secondary # System Abnormal Test Report91
367 - 368Secondary # Request for Upload/Download71
369 - 370Secondary # Successful Upload72
371 - 372Secondary # Successful Download73
373 - 374Secondary # Failed Upload/Download74
42
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 43
Programming Options
Ademco Contact ID Format
If 'E' is entered for address 42 in Program Mode Level 1, the data shown in Table 3-6 is automatically programmed for the Secondary Central Station phone number event codes. Enter '000' for the setting to disable the
report. The Setting entry is programmable, the Zone Number cannot be changed. Restoral code settings match
the settings shown with the addition of an 'R' code transmitted. Refer to page 83 for additional information.
TAB LE 3- 6:
AddressDescriptionSettingZone No.
Event Codes, Secondary Central Station Number
251-253Secondary # Zone 1 Alarm Code111001
254-256Secondary # Zone 2 Alarm Code111002
257-259Secondary # Zone 3 Alarm Code111003
260-262Secondary # Zone 4 Alarm Code111004
263-265Secondary # Zone 5 Alarm Code111005
266-268Secondary # Zone 1 Disabled Code570001
269-271Secondary # Zone 2 Disabled Code570002
272-274Secondary # Zone 3 Disabled Code570003
275-277Secondary # Zone 4 Disabled Code570004
278-280Secondary # Zone 5 Disabled Code570005
281-283Secondary # Drill Code604000
284-286Secondary # AC Fault Code301000
287-289Secondary # Zone 1 Fault Code380001
290-292Secondary # Zone 2 Fault Code380002
293-295Secondary # Zone 3 Fault Code380003
296-298Secondary # Zone 4 Fault Code380004
299-301Secondary # Zone 5 Fault Code380005
302-304Secondary # Earth Fault Code310000
305-307Secondary # Low Battery Fault Code302000
308-310Secondary # No Battery Fault Code311000
311-313Secondary # Telco Primary Line Fault Code351000
314-316Secondary # Telco Secondary Line Fault Code352000
317-319Secondary # NAC #1 Fault Code321001
320-322Secondary # NAC #2 Fault Code322002
323-325Secondary # Comm Trouble Primary # Code354001
326-328Secondary # Comm Trouble Secondary # Code354002
329-331Secondary # Annunciator Fault Code330001
332-334Secondary # System Off Normal Code308000
335-337Secondary # System Test Message602000
338-340Secondary # System Abnormal Test Message608000
341-343Secondary # Upload/Download Request Code411000
344-346Secondary # Upload Successful Code416000
347-349Secondary # Download Successful Code412000
350-352Secondary # Upload/Download Failed Code413000
Document #15140 Rev.G 01/02/02 P/N 15140:G
43
Page 44
Programming Options
Secondary Central Station Number Account Code (43-46)
A unique account code is provided by the Central Station. Four locations at addresses 43-46 (factory default settings
of all '0s') are used to enter the account code. Valid entries are 0 to 9 and A to F. The number of digits entered must
match the format selection. If programming '2, 3, 4 or 5' into address 42, enter the three digit account code supplied
by the Central Station (location 46 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C or D' into address 42, enter
the four digit account code supplied by the Central Station.
Secondary Central Station Number 24 Hour Test Time (47-50)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 2 takes up four locations, from addresses 47-50. The default is '0000' (12:00 midnight). The limits for each location are as follows:
47 - enter 0-2
48 - enter 0-9
49 - enter 0-5
50 - enter 0-9
Do not use 'A-F'
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (51)
The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter '1' for 12 hours,
'2' for 8 hours or '3' for 6 hours.
Alarm Verification (52)
Alarm verification works only on zones programmed as 2-wire smoke detector zones. After detecting an alarm, the
panel removes power from all zones for six seconds, resetting all 2-wire smoke detectors. Power is reapplied and a
12 second retard period allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent alarms
by the same initiating zone are ignored. An alarm detected on any other 2-wire detector zone during the retard period
will cause immediate verified alarms. A subsequent alarm on the initiating zone occurring within the confirmation
time will cause a verified alarm. Note: Mixing devices on zones designated as 2-wire smoke zones is not
recommended.
During the alarm verification period, access to other modes of operation is prevented.
FIGURE 3-2:
Detector Alarm Verification
Detector Zone Goes Into Alarm
Different Detector Zone Alarms
Verification Timing Diagram
0 Sec.
6 Sec.
RESET RETARD
Alarm Ignored
18 Sec.
0
ALARM VERIFICATION PERIOD
Control Panel Processes Alarm if Same Detector Zone if Still in Alarm
CONFIRMATION TIME
30
Control Panel Immediately Processes Alarm
9060
120 Sec.
120
Factory default selection is no verification which is a '0' entry. Entering a '1' enables alarm verification. Note: Consult local Authority Having Jurisdiction (AHJ) prior to altering this address.
Future Use (53-55)
Slave Communicator/Fire Panel Selection (56)
Leaving address 56 at '0' causes the control panel to operate as a fire panel only. Selecting '1' will make it operate as
a slave communicator only. Selecting '2' will make it operate as a fire panel/communicator.
44
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 45
Programming Options
Zones 1-5 Function Selection (57-61)
The five zones on the control panel may be programmed as shown below. Program entries alter zone function and
transmittal priority.
When using Ademco Contact ID format, Zone Alarm and Zone Restoral event codes change automatically as shown
in Table 3-7 . Be certain to reprogram alarm event codes when selecting process monitoring functions. Zone fault
and disable event codes may also be user reprogrammed (refer to “Ademco Contact ID Format Event Code Descriptions” on page 83).
TABLE 3-7:
Program EntryFunction
1. Ademco Contact ID format selection causes Event Codes to automatically change to values shown in Table 3-7 .
Zone Function Selection
Zone Alarm/Restoral1
Event Code
0Operates 2-wire smoke detectors111
1Pull station115
2Normally open contact device110
3Supervisory200
4Supervisory autoresettable - self restore function, is not latched by the
control panel200
5Waterflow silenceable - silencing of silenceable NACs allowed (affects
zone 3 only)113
6Waterflow nonsilenceable - silencing of silenceable NACs is not allowed.
Must clear waterflow alarm condition and press the reset key (affects zone
3 only)113
Zone 1 Function Selection (57)
Factory default for zone 1 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 2 Function Selection (58)
Factory default for zone 2 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 3 Function Selection (59)
Factory default for zone 3 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable; '5' for waterflow silenceable; '6' for waterflow
nonsilenceable.
Zone 4 Function Selection (60)
Factory default for zone 4 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 5 Function Selection (61)
Factory default for zone 5 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable.
Note: Programming any zone to function as supervisory or supervisory autoresettable will cause the defaulted event
codes (see notes in Table 3-1 through Table 3-5 ) to be automatically changed. The defaulted code of '1' is changed
to '8' for formats 3+1 and 4+1 Standard and Expanded, 4+2 Expanded and 4+1 Express. The defaulted codes of 11,
12, 13, 14 and 15 are changed to 81, 82, 83, 84 and 85 accordingly for formats 4+2 Standard and 4+2 Express.
Waterflow Retard Timer (62-63)
A delay may be added prior to declaring a waterflow type of alarm. Delays up to 89 seconds are allowed. The
default for addresses 62 and 63 are '00' (no additional delay). Valid entries for address 62 are 0-8 and for address 63
are 0-9. Program entries into these addresses only if entering a '5' or '6' in address 59. Be careful to include any built-
in delays of the waterflow device.
Document #15140 Rev.G 01/02/02 P/N 15140:G
45
Page 46
Programming Options
AC Loss Reporting Delay (64)
Enter a digit of '1'-'F', corresponding to the number of hours to be delayed in reporting loss of AC power. The factory
default setting is '0' for 6 hour delay. If 24 hour battery backup is being employed, select from choices '0' through '6'.
If 60 hour backup is used, select from choices '7' through 'F'. Selections are: '0' for 6 hour delay; '1' for 7 hours; '2' for
8 hours; '3' for 9 hours; '4' for 10 hours; '5' for 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17
hours; 'A' for 18 hours; 'B' for 19 hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
Alarm Presignal (65)
Alarm Presignal is used to delay NAC (Notification Appliance Circuit) activation while allowing for visual verification by a person. Once a zone triggers an alarm, the main board piezo and the annunciator piezo sounders turn on
steady, the display indicates the activated zone, the alarm LED blinks and the NACs are held off for 15 seconds. During this time, if the silence switch is pressed, the notification appliances may be held off for up to three minutes (see
Presignal Delay Timer Address 66-68). After the programmed delay period, the notification appliances will activate.
Presignal does not function for zones defined as waterflow or supervisory. Factory default is '0' for no alarm presignal. Enter '1' to select alarm presignal. During alarm presignal, access to other modes is prevented.
Alarm Presignal Delay Timer (66-68)
The alarm presignal delay timer is factory set to 120 seconds (2 minutes), address 66=1, 67=2 and 68=0. The timer
may be programmed from 0 to 179 seconds. Location 65 must be set to '1' for the delay timer to operate.
Notification Appliance Circuit #1 Enable (69)
NAC #1 may be programmed as '0' for silenceable, '1' for nonsilenceable or '2' for disabled (disabling will cause the
display to indicate 'bEL1', system trouble light to turn on and onboard piezo to sound). Factory default is '0' for
silenceable. Note: Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address.
NAC #1 may be autosilenced after a programmed time interval between 5 and 30 minutes. Enter '1' for 5 minute
autosilence, '2' for 10 minutes, '3' for 15 minutes, '4' for 20 minutes, '5' for 25 minutes or '6' for 30 minutes. The factory default is '0' for no autosilence.
Coding Notification Appliance Circuit #1 (72)
Coding of NAC #1 is programmable by selecting '1' for March Time (120 ppm), '2' for California (10 seconds On, 5
seconds Off) or '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ seconds
Off). Factory default is '0' for no coding (steady).
Notification Appliance Circuit #2 Enable (73)
NAC #2 may be programmed as '0' for silenceable, '1' for nonsilenceable or '2' for disabled (disabling will cause the
display to indicate 'bEL2', system trouble light to turn on and onboard piezo to sound). Factory default is '0' for
silenceable. Note: Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address.
NAC #2 may be autosilenced after a programmed time interval between 5 and 30 minutes. Enter '1' for 5 minute
autosilence, '2' for 10 minutes, '3' for 15 minutes, '4' for 20 minutes, '5' for 25 minutes or '6' for 30 minutes. The factory default is '0' for no autosilence.
46
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 47
Programming Options
Coding Notification Appliance Circuit #2 (76)
Coding of NAC #2 is programmable by selecting '1' for March Time (120 ppm), '2' for California (10 seconds On, 5
seconds Off) or '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ seconds
Off). Factory default is '0' for no coding (steady).
Trouble Reminder (77)
Factory default is '0' which disables the trouble reminder feature. Selecting '1' will cause a reminding beep (after the
silence switch is pressed), every 15 seconds during an alarm and every two minutes during a trouble condition. The
beeps from the onboard piezo sounder will continue until the alarm or fault is cleared.
Annunciator/Printer Supervision (78)
Factory default is '0' for no annunciator or printer present. Set address 78 to '1' if an annunciator is present, set to '2'
if a printer is present or set to '3' if both an annunciator and a printer are present.
Backup Reporting (79)
Leaving the default setting of '0' programs the control panel to transmit reports to the Secondary Central Station
phone number only if attempts to communicate to the Primary Central Station phone number are unsuccessful. Programming a '1' causes all reports to be transmitted to the Secondary Central Station Phone number.
Touchtone/Rotary Select (80)
A '0' programmed in this address by the factory triggers Touchtone dialing over both phone lines. Select '1' for rotary
dialing.
Make/Break Ratio (81)
Use this address only if '1' (rotary dialing) has been selected for address 80. The make/break ratio is factory set to '0'
for 67/33 ratio, but may be changed to '1' for 62/38 ratio.
Address (82)
Leave default of '0'.
Address (83)
Leave default of '0'.
Panel Identification Number (84-87)
The Panel Identification Number is a 4-digit code (valid digits are 0-F) that is used to identify the installed panel.
This code is separate from the 8-digit secret code loaded in by the Service Terminal. It is important to program this 4digit code at the jobsite the first time that downloading is performed so that the called Service Terminal can identify
the control panel.
Service Terminal Number 1 Phone Number (88-103)
Addresses 88 through 103 are reserved for the Service Terminal phone number 1. Factory default is all 'Fs'. Valid
entries are 0-9 plus A, B, C, D and E, similar to the primary and secondary Central Station phone number entries programmed at addresses 00-15 and 26-41. Use 'F' to designate the end of the phone number.
Ring Count on Primary Phone Line (104-105)
Use this address to designate the number of rings allowed on the primary phone line prior to answering an incoming
call from a Service Terminal. Factory default is '03' which means the panel will not answer an incoming call until 3
rings are detected. This entry may be programmed up to a maximum of 25 rings. A setting of '00' prevents the panel
from answering incoming calls.
Document #15140 Rev.G 01/02/02 P/N 15140:G
47
Page 48
Programming Options
FAX/Answer Machine, Primary Phone Line (106)
This entry is used when the primary phone line is being shared with a FAX, answering machine or other device. Factory default is '0' for no sharing of the primary phone line. An entry of '1' indicates sharing and allows the panel to
wait for three consecutive calls from the Service Terminal, spaced 30 seconds apart, before responding.
Service Terminal Number 2 Phone Number (107-122)
Addresses 107 through 122 are reserved for the Service Terminal phone number 2. Factory default is all 'Fs'. Valid
entries are 0-9 plus A, B, C, D and E, similar to the primary and secondary Central Station phone number entries programmed at addresses 00-15 and 26-41. Use 'F' to designate the end of the phone number.
Ring Count on Secondary Phone Line (123-124)
Use this address to designate the number of rings allowed on the secondary phone line prior to answering an incoming call from a Service Terminal. Factory default is '03' which means the panel will not answer an incoming call until
3 rings are detected. This entry may be programmed up to a maximum of 25 rings. A setting of '00' prevents the
panel from answering incoming calls.
FAX/Answer Machine, Secondary Phone Line (125)
This entry is used when the secondary phone line is being shared with a FAX, answering machine or other device.
Factory default is '0' for no sharing of the secondary phone line. An entry of '1' indicates sharing and allows the panel
to wait for three consecutive calls from the Service Terminal, spaced 30 seconds apart, before responding.
Upload/Download Reports Sent to Secondary Central Station Phone Number, Backup or Always (126)
Reports for request for 'upload/download', 'successful upload', 'successful download' and 'failed upload/download' are
always sent to the primary Central Station phone number. This entry allows for the same reports to either always be
sent to the secondary Central Station phone number or only if attempts to transmit to the primary Central Station
phone number are unsuccessful. Factory default is '0' for backup only. Enter '1' for always.
Programming Event Codes (127-374)
The type of reports and event codes that are sent to the Central Station are in Table 3-1 through Table 3-5 . The
selections made for the Primary Central Station Number Communication Format (address 16) and the Secondary
Central Station Number Communication Format (address 42) automatically program addresses 127-374 with factory
default selections.
Any of the event codes may be changed. Consult your Central Station prior to altering the event codes. Entering an
event code of '0' will cause the communicator to NOT transmit the report. For the 3+1, 4+1 and 4+1 Express formats
or the 4+2 Expanded format, enter '0'. For the 4+2 Standard or 4+2 Express formats, enter '00'. Transmission of
reports to either or both Central Station phone numbers may be disabled.
Note the special 'System Abnormal Test Report' event code. This report was added per new UL DACT requirements.
This report is generated in place of the normal test report when an alarm and/or trouble condition exists at the time
the test report is due to be sent.
Programming the Real-Time Clock and Calendar
Entering an address greater than 374 will cause a display of the current time. On initial power-up, the clock will start
running from the factory setting of 00:01 (military time). The far left digit will be flashing, indicating that this is the
first digit to be programmed. It should be noted that setting the time and date may cause corruption of the History
File. For this reason, it is important that the History File be cleared after the time and date has been set. Refer to
“History Mode” on page 63.
Hours/Minutes
Select a digit then press [ENTER/STORE]. The digit 2nd from the left will start flashing. Select a digit then press
[ENTER/STORE]. Hours setting is complete. With the digit 2nd from the right flashing, select a digit then press
[ENTER/STORE]. The digit on the far right will start flashing. Select a digit then press [ENTER/STORE]. Min-
utes setting is complete.
48
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 49
Default Programming
Ye a r
After entering the last digit corresponding to minutes (far right digit), the display will read 1994 with the digit 9 (second from the right) flashing. Press [ENTER/STORE] if the 9 is acceptable. The digit farthest right will begin flashing. Enter the appropriate digit corresponding to the last digit of the current year and press the [ENTER/STORE]
key to complete programming of the year.
Note that changing to the year 2000
can be accomplished by entering ‘0’ while the second digit from the right is
flashing, followed by the [ENTER/STORE] key. The two digits to the left will change to ‘20’ and the digit farthest
right will begin flashing. Enter the appropriate digit corresponding to the last digit of the year (i.e. ‘0’ for the year
2000
) and press the [ENTER/STORE] key to complete programming of the year.
Month/Day
After the year is entered, the display will show four digits representing the month and day of the software release
date. The month is represented by the two digits on the left and the day by the two digits on the right. The digit on
the far left will be flashing. The month and day are set the same way as the hours and minutes. Once the last digit
corresponding to the day is entered, the display will show the contents of address '00'. The real-time clock/calendar
keeps track of leap years automatically.
Note that the software for the MS-5024UD operates the internal clock based upon 60Hz. The software for the
MS-5024UDE operates the internal clock based upon 50Hz.
End Programming
Exit Programming Mode by pressing MODE, followed by the 4-digit code corresponding to an alternate mode of
operation, then press [ENTER/STORE].
During Program Mode, if no key is pressed within 10 minutes, the panel will return to Normal Mode.
3.4Default Programming
To return all program entries to their factory original settings, perform the following steps only when the system is
idle in Normal standby condition:
Press the MODE key followed by the four digit code 3337 and press the [ENTER/STORE] key.
3337 spells DEFP (DEFault Programming) on a Touch-Tone
☛
®
phone
If an incorrect key is pressed, reenter the proper 4-digit code before pressing the [ENTER/STORE] key.
Within five seconds, repeat this entry by again pressing the MODE key followed by the 4-digit code 3337 and pressing the [ENTER/STORE] key. The display will read 3337 while the E
2
nonvolatile memory (storage area for all
programming options) is being reprogrammed with the original default settings. When reprogramming is complete,
the display will be blank.
Document #15140 Rev.G 01/02/02 P/N 15140:G
49
Page 50
Operating Instructions
CHAPTER 4Operating Instructions
The MS-5024UD has six modes of operation:
• Normal Mode
•Program Mode
• Walktest Mode
• Troubleshoot Mode
• History Mode
• Print Mode
Upon initial power-up, the system will be in Normal Mode. This chapter discusses operation of the control panel in
the Normal Mode.
4.1Switches in Normal Mode
4.1.1 RESET
The Reset Switch resets the system and any smoke detectors. If the Reset Switch is pressed, the control panel will:
✓
Clear the display and status LEDs
✓Turn off the Notification Appliance Circuits
✓Reset all zones by temporarily removing power
✓
Silence the onboard piezo sounder
✓
Store 'reset' message in the History file
✓
Restore the alarm and trouble relays to normal
✓
Clear the supervisory and communication fail relay driver outputs
✓
Temporarily remove power from the resettable power output TB4 terminals 3 & 4
✓
Restore to normal the RM-5F zone relays
✓
Output 'reset' message to printer
Any alarm, supervisory or trouble condition that exists after a system reset, will resound the system, reactivating normal system activity. Upon release of the Reset Switch, the display will read rES_ for six seconds.
50
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 51
Displays
SILENCE
If the Silence Switch is pressed:
✓The silenceable NACs will be turned Off
✓The silence LED will be turned Off
✓The piezo sounder will be shut Off
✓'System Silenced' message will be stored in the History file
✓
'System Silenced' message will be sent to the printer
✓System Silence switch acts as acknowledge switch during alarm presignal
Upon the occurrence of a subsequent event (alarm or trouble), System Silence is overridden and the control panel will
respond to the new event. The System Silence switch will be ignored for silenceable waterflow type alarms.
MODE
Pressing the MODE switch followed by a valid 4-digit numerical code and then the [ENTER/STORE] key selects
one of the six modes of operation. To enter Normal Mode from any other mode, press MODE, then 6676 followed
by the [ENTER/STORE] key.
6676 spells NORM on a Touchtone
☛
®
phone.
1st EVENT
The 1st Event switch, along with the Up and Down arrow keys, is used to display any currently active alarm and/or
fault conditions present in the system. Press the 1st Event switch at any time to display the first event (alarm and/or
trouble) that occurred.
DOWN ARROW
The Down Arrow key is used to view other events (newer) that have occurred and are active (not yet cleared).
UP ARROW
The Up Arrow key is used to view other events (older) that have occurred and are active (not yet cleared).
[ENTER/STORE]
See individual mode descriptions in other sections of this manual.
4.2Displays
Four 7-segment red LED characters provide visual annunciation of status, events and messages. A list of messages
that may appear on the display in Normal Mode is shown below:
Zone 1 Disabled
Zone 2 Disabled
Zone 3 Disabled
Zone 4 Disabled
Zone 5 Disabled
Zone 1 Enabled
Zone 2 Enabled
Zone 3 Enabled
Zone 4 Enabled
Zone 5 Enabled
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
Alarm Zone 5
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
Earth Fault
Low Battery
No Battery
Primary C.S.# Comm. Fault
Secondary C.S. # Comm. Fault
Bell 1 Fault or Disabled
Bell 2 Fault or Disabled
Primary Phone Line Fault
Secondary Phone Line Fault
SUP1
SUP2
SUP3
SUP4
SUP5
_AC_
rES_
Supv. Alarm Zone 1
Supv. Alarm Zone 2
Supv. Alarm Zone 3
Supv. Alarm Zone 4
Supv. Alarm Zone 5
AC Power Loss
System Reset
Document #15140 Rev.G 01/02/02 P/N 15140:G
51
Page 52
Displays
Individual LEDs are provided for:
System Alarm
A red LED that turns on steady when an alarm condition is detected and blinks during the alarm presignal period.
System Trouble
This yellow LED blinks to indicate that a fault or abnormal condition exists and that the fire alarm system may be
inoperative. It turns on steady when the silence switch is pressed.
AC Power On
A green LED that remains on while the AC power supply is within correct limits. If this indicator fails to light under
normal conditions, service the system immediately.
Supervisory
A yellow LED that blinks to indicate the need for action in connection with the supervision or maintenance of sprinklers, extinguishing systems or other protective systems.
System Silence
A yellow LED that turns on to indicate that an alarm or trouble condition exists in the system, but both NACs (if programmed as silenceable) and local piezo have been silenced.
Primary Line Active
A red LED on the main circuit board that indicates the primary phone line is active.
Secondary Line Active
A red LED on the main circuit board that indicates the secondary phone line is active.
Kissoff
A green LED on the main circuit board that blinks when a Central Station has acknowledged receipt of each transmitted message or when a portion of upload or download data has been accepted from a Service Terminal.
Modem
A green LED on the main circuit board that stays on steady during modem types of communications.
FIGURE 4-1:
Phone Connectors and LEDs
Primary Line
Primary Active
Secondary Line
Secondary Active
52
Modem LED
Kissoff LED
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 53
Operation
4.3Operation
Normal Mode is the standard mode of operation. In this mode, the control panel continuously monitors system status.
When no alarm or trouble conditions exist, the display will be blank and all LEDs will be off (except the AC Power
LED). The Notifications Appliance Circuits will be off, all relays and relay drivers are normal and the onboard piezo
sounder will be off. The communicator is not active, primary and secondary active LEDs are off.
All alarm and system trouble conditions are annunciated on the control panel's display. The control panel will maintain an 'active event list' which will consist of all alarms, supervisory alarms and system troubles currently active and
not cleared, requiring immediate service. When the system is cleared and restored to normal, the display will be
blank. All alarms and troubles are stored in a history file and may be recalled at any time.
Higher priority events take precedence over lower priority events. Display and reporting of system status is done on
a priority basis. Priorities are, from highest to lowest:
Alarms
1.
Supervisory Alarms
2.
System Troubles
3.
If the events to be displayed consist only of alarms and disabled zones (no troubles), the control panel will scroll them
on the display. Pressing the 1st Event key will stop the scrolling and cause the display of the first alarm that occurred
after the panel was last reset, cleared of all active events and placed into Normal Mode. Operation of the Up and
Down arrow keys will display all remaining events in sequence.
If events to be displayed include system troubles, only one event is displayed at a time and there is no scrolling. The
event displayed is the highest priority. Pressing the 1st Event key will cause the display of the first event that
occurred after the panel was last reset, cleared of all active events and placed into Normal Mode. Operation of the Up
and Down arrow keys will display all remaining events in order of their occurrences.
4.3.1 Alarm Response
Upon detection of an alarm condition, the control panel will:
✓Turn the alarm LED on
✓Activate the alarm relay
✓
Display the alarm message (i.e. A__1 for alarm on zone 1)
✓
Communicate the alarm to the Central Station
✓Store the alarm in the History file
✓Turn the NACs on
✓Turn the piezo sounder on
✓Turn on appropriate zone relay output
✓Output alarm message to printer
✓Terminate upload or download communications
Note that when any zone is programmed as a supervisory zone, it will not be processed in the same manner as a conventional alarm zone. See Supervisory Condition later in this section.
Document #15140 Rev.G 01/02/02 P/N 15140:G
53
Page 54
Operation
4.3.2 Alarm Restoral
The control panel returns to normal only after all alarms have been cleared and the Reset switch has been pressed
(pull stations reset, smoke detectors reset and no smoke is present, waterflow has stopped, etc.). Upon restoral of all
active alarms, the control panel will perform the following:
✓Turn off the alarm LED
✓Deactivate the alarm relay
✓Clear the 4-character display
✓Send all 'zone restoral' messages to the Central Station
✓Turn off the NACs
✓Turn off the piezo sounder
✓Turn off appropriate zone relay output
✓Output 'zone restoral' message to printer
✓Terminate upload or download communications
4.3.3 System Supervisory Condition Response
Program zones for supervisory in applications where a waterflow sensing device has been employed and the wiring to
the waterflow valve and/or a tamper switch is to be monitored. If the tamper switch has been activated (normally
open contacts close), a supervisory alarm condition will occur. When a supervisory condition occurs, the control
panel will:
✓
Blink the supervisory LED (½ second On, ½ second Off)
✓
Activate the supervisory relay driver (TB4-5)
✓
Display the following message: SUPX where X = the zone number
✓
Communicate the supervisory condition to the Central Station
✓
Store the 'supervisory' message in the History file
✓
Pulse the piezo sounder at ½ second On and ½ second Off rate
✓
Turn on appropriate zone relay output
✓
Output system supervisory message to printer
✓
Terminate upload or download communications
4.3.4 System Supervisory Restoral Response
When the supervisory condition has been cleared (condition is restored and the reset switch has been pressed), the
control panel will perform the following:
✓Turn off the supervisory LED
✓Deactivate the supervisory relay driver (TB4-5)
✓Clear the display of the 'SUP' message
✓
Communicate a supervisory restoral message to the Central Station
✓
Shut off the piezo sounder
✓
Turn off appropriate zone relay output
✓
Output system supervisory restoral message to printer
✓
Terminate upload or download communications
Note: For any zone programmed for supervisory autoresettable, the Reset switch does not need to be pressed to clear
the zone (supervisory condition).
54
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 55
Operation
4.3.5 Trouble Condition Response
Upon detection of one or more trouble conditions, the control panel will perform the following:
✓Blink the trouble LED (1 second On and 1 second Off)
✓Activate the trouble relay
✓Display the appropriate trouble message(s) in priority fashion from the highest priority to the lowest.
Note that the Up Arrow, Down Arrow or 1st Event key must be pressed to view the messages
✓Communicate the trouble conditions to the Central Station
✓Store the trouble conditions in the History file
✓Sound the piezo sounder 1 second On and 1 second Off
✓Output the system trouble messages to the printer
✓Terminate upload or download communications
Note: When AC brownout occurs, the AC LED is turned off and the trouble LED blinks. Should the brownout condition remain, it will be transmitted to the Central Station after a delay (see program address 64).
Possible trouble messages that may appear on the display are as follows:
Zone 1 Disabled
Zone 2 Disabled
Zone 3 Disabled
Zone 4 Disabled
Zone 5 Disabled
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
Earth Fault
Lo_b
no_b
PH_1
PH_2
bEL1
bEL2
no_1
no_2
_AC_
Low Battery
No Battery
Primary C.S.# Comm. Fault
Secondary C.S. # Comm. Fault
Bell 1 Fault or Disabled
Bell 2 Fault or Disabled
Primary Phone Line Fault
Secondary Phone Line Fault
AC Power Loss (shown only when requested)
4.3.6 Trouble Condition Restoral
Upon restoral of all trouble conditions, the control panel performs the following:
✓Shut off the trouble LED
✓Deactivates the trouble relay
✓Turn off the AC Power LED if the trouble was loss of AC
✓
Clear the display of all trouble messages
✓
Communicate the restored trouble condition(s) to the Central Station
✓
Output the system trouble restoral message to the printer
✓
Terminate upload or download communications
4.3.7 Off Normal Reporting
Removing the control panel from Normal Mode and placing it into any other mode causes the transmission of an 'off
normal' fault message to the Central Station. Returning the panel to Normal Mode causes the transmission of a
'return to normal' restoral message.
Document #15140 Rev.G 01/02/02 P/N 15140:G
55
Page 56
Operation
4.3.8 Zone Disable/Enable
The zone disable feature may be used to disable any zone in the system. Zones may be disabled if they are normal, in
trouble or alarmed. Zones may be disabled only during the Normal Mode of operation, when the fire protection is
active. If the panel is in alarm, the silence switch must be pressed first, before the zone disable feature will function.
To disable a zone, press the MODE key once (the display will go blank). You then have 10 seconds to start entering
the code 3472. Next press the [ENTER/STORE] key.
3472 spells DISA on a Touch-Tone
☛
A flashing lower case d will appear on the far left of the display. Press the digit key corresponding to the zone number to be disabled. The number will appear on the far right of the display. Press [ENTER/STORE] to disable the
zone. Note that the trouble relay is activated and the trouble LED blinks.
The zone disable message will remain on the display until the zone is reenabled. To reenable a zone, press the
MODE key. The display will go blank. You then have 10 seconds to start entering the code 3622. Next, press the
[ENTER/STORE] key.
3622 spells ENAB on a Touch-Tone
☛
A flashing upper case E will appear on the left of the display. Press the digit key corresponding to the zone number to
be enabled. The number will appear on the far right of the display. Press the [ENTER/STORE] key to reenable the
zone. Not that the trouble relay is restored to normal and the trouble LED turns off (if no other troubles are on the
system).
®
phone.
®
phone.
4.3.9 Fire Drill
The Drill (manual evacuate) feature turns on both Notification Appliance Circuits (if programmed as enabled) and
turns off the silence LED. Tor perform a fire drill, press the MODE key followed by the code 3745 then the
[ENTER/STORE] key. The display will indicate dril. The alarm relay is not activated for a fire drill. There is an
option to transmit the fire drill report code to the Central Station.
3745 spells DRIL on a Touch-Tone
☛
During a fire drill, the Silence key will silence both NACs and the Reset key restores the control panel to normal. All
zones remain active during a fire drill.
®
phone.
56
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 57
Central Station Communications
4.4Central Station Communications
The control panel transmits zone and system status reports to Central Stations via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two
optional 7 foot telephone cords are available for this purpose and can be purchased separately.
The control panel supervised both telephone lines for proper voltage. A delay of two minutes will occur before a
fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will
sound, the yellow trouble LED will blink, the 4-character display will show either 'no 1' (primary line fault) or 'no 2'
(secondary line fault) and the trouble condition will be reported to the Central Station over the remaining operational
phone line.
The control panel comes with line seizure capability provided for both the primary and secondary telephone line
interfaces. Any time that the control panel needs to make a call to a Central Station, line seizure will disconnect any
local premises phones sharing the same telephone line.
All transmissions to the Central Stations will be sent over the primary phone line. In the event of noisy phone lines,
transmissions will be sent over the backup secondary phone line.
Two phone numbers must be programmed, the primary Central Station phone number and the secondary Central Station phone number. All system reports will be transmitted to the primary Central Station phone number. Reports will
automatically be sent to the secondary Central Station phone number if attempts to transmits to the primary Central
Station phone number are unsuccessful. If 10 total attempts to communicate are unsuccessful, the Communicator
Failure output will be turned on (TB4, Terminal 6). Note that as an option, all reports may also be sent to the secondary Central Station phone number.
The MS-5024UD meets NFPA 72 National Fire Code reporting requirements for: (a) the type of signal, (b) condition
and (c) location of the reporting premises. The general priority reporting structure is:
Zone Alarms and Restores
1.
Zone Troubles and Restores
2.
System Troubles and Restores
3.
24-hour Test
4.
Document #15140 Rev.G 01/02/02 P/N 15140:G
57
Page 58
Central Station Communications
The control panel is capable of reporting detailed messages depending upon the format in use. Table 4-1 shows the
reporting structure for all formats.
B =Telco Secondary Line Fault
C =Main Bell Fault, Annunciator Bell
D =Communication Fault to Primary Number
E =Communication Fault to Secondary Number
F =System Off Normal Fault/System Fault (Slave Operation, see Chapter 6)
UD=Upload/download (1st digit)
UD2=Upload/download (2nd digit)
Note: For Expanded Reporting, the control panel automatically adds the digit corresponding to the zone number and
the second digit corresponding to any system trouble condition. Only the first digit is programmable.
Document #15140 Rev.G 01/02/02 P/N 15140:G
59
Page 60
Central Station Communications
4.4.1 Transmittal Priorities
The integral communicator transmits highest priority events first. Events, in terms of priority, are listed below in
descending order:
Alarms (highest priority level)
1.
✓Pull stations
✓Waterflow
✓Smoke detector
✓Other alarm types
Supervisory Zone
2.
System Troubles
3.
✓Zone disabled
✓Fire drill
✓AC fail (after delay)
✓Zonal faults
✓Earth fault
✓Low battery/no battery
✓Telephone line fault
✓Notification Appliance Circuits fault
✓Communication trouble
✓Annunciator trouble
✓System off normal
Restoral Reports
4.
✓Zone alarm
✓Supervisory
✓Zone(s) enabled
✓Fire drill
✓AC
✓
Zone fault
✓
Earth
✓Battery
✓Telephone line
✓Notification Appliance Circuits
✓Communication
✓Annunciator trouble
✓System off normal
24 Hour Test (lowest priority)
5.
Red LEDs are provided on the control panel circuit board to identify which telephone line is activated. Also, a green
LED labeled 'kissoff' will turn on whenever the control panel has successfully transmitted reports to the Central Station. The 'kissoff' LED may turn on several times during communications with a Central Station.
60
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 61
Central Station Communications
The table below shows UL listed receivers which are compatible with the MS-5024UD.
TAB LE 4- 3:
04+1 Ademco Express
14+2 Ademco Express
23+1/Standard/1800/2300
33+1/Expanded/1800/2300
43+1/Standard/1900/1400
53+1/Expanded/1900/1400
64+1/Standard/1800/2300
74+1/Expanded/1800/2300
84+1/Standard/1900/1400
94+1/Expanded/1900/1400
A4+2/Standard/1800/2300
B4+2/Expanded/1800/2300
C4+2/Standard/1900/1400
D4+2/Expanded/1900/1400
EAdemco Contact ID
FNot Used
Compatible UL Listed Receivers
Format #
(Addresses 16 & 42)
Ademco
685 (1)
Silent Knight
9000 (2)
ITI
CS-4000 (3)
FBI
CP220FB
Osborne Hoffman
Models 1 & 2
Radionics
6000 (6)
Radionics
6500 (5)
Sescoa
3000R (7)
Surguard
MLR-2 (9)
✔✔✔
✔✔✔
✔✔ ✔✔
✔✔ ✔✔
✔✔✔
✔✔✔
✔✔ ✔✔
✔✔✔
✔✔✔
✔✔✔
✔✔ ✔✔
✔✔✔
✔✔✔
✔✔✔
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(8)
✔
✔✔✔✔✔
✔✔✔
✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
✔✔✔
✔✔✔
✔✔✔✔
✔✔✔
✔✔✔
✔✔✔
✔✔✔✔
With 685-8 Line Card with Rev. 4.4d software
1.
With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software
2.
Rev. 4.0 software
3.
FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8 software
4.
Model 6500 with Rev. 600 software
5.
Mode 6000 with Rev. 204 software
6.
With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software
7.
Model 2 only
8.
Version 1.62 software
9.
Document #15140 Rev.G 01/02/02 P/N 15140:G
61
Page 62
Servicing
CHAPTER 5Servicing
5.1Walktest Mode
The MS-5024UD provides the capability to perform a one-man walktest of the system without triggering the communicator, the zone relays or the alarm output relay. Walktest allows for testing of the five zones (Initiating Device Circuits). The first initiating device activated on a zone will cause the Notification Appliance Circuits to turn on for four
seconds. Subsequent device activations on the same zone will cause the NACs to turn on for one second. Any smoke
detectors that are activated will be reset. Zonal faults (open circuits) will cause the NAC to remain on steady. Prior
to entering Walktest Mode, check to be certain that all system faults have been cleared. Note that the trouble relay
will be activated while the control panel is in Walktest Mode. Placing the control panel into this mode will only be
possible if the system has no active alarms.
Pressing the MODE key followed by the 4-digit code 9255 and then the [ENTER/STORE] key will place the control panel into Walktest Mode.
9255 spells WALK on a Touch-Tone
☛
®
phone.
Once in Walktest Mode, the control panel will immediately:
✓
Blink the trouble LED
✓
Activate the trouble relay
✓
Turn on the NACs for four seconds for the first alarm on a zone. Subsequent alarms on the same zone
will sound for one second. Troubles cause the NACs to remain on
✓
Disable the alarm relay
✓
Display all alarm conditions as they occur
✓
Display all zone troubles as they occur
✓
Display ground faults as they occur
✓
Transmit 'off normal' message to Central Station(s)
✓
Continue to communicate any events not acknowledged at a Central Station prior to entering Walktest
Mode
During Walktest Mode, zonal activity is displayed in real-time as it occurs. At the end of walktesting the system, the
display will show the last event that occurred. To view all events stored during Walktest, use the Up arrow, Down
arrow and 1st Event keys. The Down arrow key moves the Walktest list to show older (previous) events. The Up
arrow key moves the Walktest list to show newer (more recent) events. Pressing the 1st Event key at any time will
cause the display of the first event stored upon initial entry into Walktest Mode. While in Walktest Mode, the control
panel will store up to 128 events in the Walktest File for later recall and display. A printer may be connected to the
panel during Walktest. All Walktest events are printed in real-time as they occur.
To return the control panel to Normal Mode, press the MODE key followed by the code 6676 and then the [ENTER/STORE] key. Any delay between key presses greater than 10 seconds causes the control panel to remain in Walktest
Mode.
The control panel will automatically return to Normal Mode if no system activity has occurred for 60 minutes. This
includes pressing any keys or activity on any zone. Exiting Walktest Mode leaves the Walktest file in memory such
that it may be printed in Print Mode. Subsequent entries into Walktest Mode will delete the Walktest file.
Note that remote site upload or download is not possible while in Walktest Mode.
62
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 63
History Mode
5.2History Mode
All Normal Mode events are stored in a History File list for future recall. Recall is possible via the 4-character display or via an optional printer. The History File list is a first-in, first-out (FIFO) file. In this manner, only the most
recent events may be called up from memory. Older events will be overwritten, that is, pushed out of the FIFO file.
The number of stored events is 32 maximum. The History File is kept in E
erase the list.
Pressing the MODE key followed by the code 4478 and then the [ENTER/STORE] key places the control panel into
History Mode. This will not occur if there are any active alarm conditions present. The event displayed, is the most
recent event.
4478 spells HIST on a Touch-Tone
☛
®
phone.
Once in History Mode, the control panel will:
✓
Blink the trouble LED
✓
Activate the trouble relay
✓Disable the Notification Appliance Circuit(s)
✓Disable the alarm relay
✓Display all events as they occurred since the last time the History File list was cleared. The most recent
event will be displayed first
✓Ignore all other keys other than those mentioned in this section
✓Transmit the 'off normal' message to the Central Station(s)
✓Continue to communicate any events not previously acknowledged at the Central Station prior to enter-
ing History Mode
2
memory. Complete power loss will not
The Down Arrow key moves the History File to show older (previous) events. The Up Arrow key moves the History
file to show newer (more recent) events. Following is a list of messages as they will appear on the display:
Zone 1 Disabled
Zone 2 Disabled
Zone 3 Disabled
Zone 4 Disabled
Zone 5 Disabled
Zone 1 Enabled
Zone 2 Enabled
Zone 3 Enabled
Zone 4 Enabled
Zone 5 Enabled
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
Alarm Zone 5
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
Earth Fault
Low Battery
No Battery
Primary C.S.# Comm. Fault
Secondary C.S. # Comm. Fault
Bell 1 Fault or Disabled
Bell 2 Fault or Disabled
Primary Phone Line Fault
Secondary Phone Line Fault
SUP1
SUP2
SUP3
SUP4
SUP5
_AC_
SILE
rES_
Supv. Alarm Zone 1
Supv. Alarm Zone 2
Supv. Alarm Zone 3
Supv. Alarm Zone 4
Supv. Alarm Zone 5
AC Power Loss
Silence Switch Pressed
Reset Switch Pressed
It should be noted that setting the time and date may cause corruption of the History File contents. The History File
should therefore be cleared after the time and date are set. To clear the list from E
2
memory, press the SILENCE key
twice before exiting the History Mode.
A lack of keyboard activity for a period of 10 minutes will cause the control panel to return to Normal Mode. If a
printer is connected to the control panel, the History File will be printed upon successful entry into History Mode and
a list of the most recent 32 events, time and date stamped, will print out. Note that remote site upload or download is
not possible while the panel is in History Mode.
Document #15140 Rev.G 01/02/02 P/N 15140:G
63
Page 64
Troubleshoot Mode
5.3Troubleshoot Mode
In Troubleshoot Mode, system voltages may be displayed on the 4-character display. An internal voltmeter measures
the voltage present at:
• Zone inputs
• AC power input
• Battery terminal leads
•NAC #1
•NAC #2
• Resettable 24 volt power output
To enter Troubleshoot Mode, press the MODE key followed by the code
and then the [ENTER/STORE] key.
8768
A lack of keyboard activity for a period of 20 minutes will cause the control panel to return to Normal Mode.
8768 spells TROU on a Touch-Tone
☛
®
phone.
Once in Troubleshoot Mode, the control panel will:
✓
Blink the trouble LED
✓
Activate the trouble relay
✓
Disable the NACs
✓
Disable the alarm relay
✓
Transmit the 'off normal' message to the Central Station(s)
✓
Continue to communicate any events not yet acknowledged at the Central Station prior to entering
Troubleshoot Mode
Voltages can be viewed by performing the following steps:
• AC input voltage - press A and then the [ENTER/STORE] key
• Battery voltage - press B and then the [ENTER/STORE] key
• Zone 1 voltage - press 1 and then the [ENTER/STORE] key
• Zone 2 voltage - press 2 and then the [ENTER/STORE] key
• Zone 3 voltage - press 3 and then the [ENTER/STORE] key
• Zone 4 voltage - press 4 and then the [ENTER/STORE] key
• Zone 5 voltage - press 5 and then the [ENTER/STORE] key
• NAC #1 voltage - press b then 1 and then the [ENTER/STORE] key
• NAC #2 voltage - press b then 2 and then the [ENTER/STORE] key
• Resettable 24 volt power - press the RESET key and then the [ENTER/STORE] key
5.3.1 Zone Voltages
The nominal threshold voltages for each zone are listed below. Actual readings will vary depending upon system load
and AC line voltage
TABLE 5-1:
Zone #Normal w/E.O.L.ShortedOpen Circuit
123.5V0.00V25.4V
223.5V0.00V25.4V
323.5V0.00V25.4V
423.5V0.00V25.4V
523.5V0.00V25.4V
64
.
Nominal Zone Voltages
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 65
Troubleshoot Mode
5.3.2 AC Line Voltage
The following table lists the AC line voltage range. The AC On indicator will turn off when the AC line voltage
drops below the Low Line threshold and the trouble LED will turn on.
TAB LE 5- 2:
AC Line VoltageLow LineNormalHigh Line
AC Line Voltage Range
MS-5024UD102 VAC115 VAC132 VAC
MS-5024UDE204 VAC220 VAC264 VAC
5.3.3 Battery Voltage
The following table lists the critical battery threshold conditions. Note that battery measurements should be made
after allowing 48 hours to charge depleted batteries. If batteries do not show normal readings, replace them.
IMPORTANT
: The battery charger will turn off when the battery voltage drops to 17.4 VDC or less (No Battery
condition). A battery with a higher voltage must be installed to turn the charger back on.
TAB LE 5- 3:
Battery Voltage
NormalLow BatteryNo Battery
Battery Voltage:27.6V20.4V<17.4V
5.3.4 Telephone Lines
Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/STORE] causes seizure of the primary phone line which in turn lights the red LED signifying primary phone line active. After a delay of three seconds, the control panel goes off-hook to acquire a dial tone.
The control panel keypad may be used as a telephone touchpad for number dialing. Once the first digit is pressed, the
display will move the C or D character one position to the left, while placing the digit to be dialed on the farthest right
display position. Continue to press the phone numbers to be dialed. Successive depressions of the [ENTER/STORE] key hangs up and picks up the phone (places the phone on or off the hook).
The secondary phone line may be tested by pressing the E key for touchtone dialing or the F key for rotary dialing
and then following the same procedure used for the primary phone line.
A handset may be temporarily connected across transformer T1 as indicated in Figure 5-1. The handset, when connected across T1, may be used only as an amplifier/speaker and telephone with the control panel used for number
dialing.
FIGURE 5-1:
Phone Connectors and LEDs
Both Primary and Secondary Lines
Document #15140 Rev.G 01/02/02 P/N 15140:G
65
Page 66
Lamp Test
5.3.5 NAC 1 & 2
NAC voltage readings are nominally -2.32 volts when an EOL resistor of correct value is in place. A reading of 0.00
volts appears for shorts, -4.50 volts for opens. Intermediate readings are also available.
Note that remote site upload or download is not possible while the panel is in Troubleshoot or Lamp Test Mode.
5.3.6 Resettable Power
Resettable 24 volt power output must read 24 volts, + or - 10%.
5.4Lamp Test
To perform a Lamp Test, press MODE then the code 5267 followed by the [ENTER/STORE] key. This will test all
system LEDs. The LEDs will remain on for five seconds and then the control panel will return to Normal Mode.
5267 spells LAMP on a Touch-Tone
☛
®
phone.
5.5Print Mode
A printer may be temporarily or permanently connected to the control panel. Refer to Figure 2-15 on page 30, for
proper PRT-24 Printer Interface module connection to the main circuit board before proceeding.
Programmable option address 78 must be programmed to a '2' if only a printer is connected to the control panel or '3'
if both a printer and annunciator are connected to the control panel, to enable printer supervision. Once enabled, normal system status as well as panel operations will be printed. If the printer connection is removed, the trouble LED
will blink, the piezo sounder will pulse and the 4-character LED display will be blank.
Select Printer Mode by pressing the MODE key followed by the code 7746 and then the [ENTER/STORE] key.
The display will read Prn and the following will be printed:
Entire program entries
1.
History file
2.
Walktest file
3.
Troubleshoot Mode voltages
4.
Current system status
5.
(Note that all activity is time and date stamped)
Upon entering the Print Mode, the control panel will transmit the 'system off normal' message to the Central Station.
The panel will return to Normal Mode automatically after printing is completed. This will typically take three
minutes.
Note that remote site upload or download is not possible while the panel is in Print Mode.
66
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 67
Slave Communicator Configuration
CHAPTER 6Slave Communicator Configuration
The MS-5024UD may be used as a slave communicator to a host or master FACP (fire alarm control panel). All wiring between the master and the slave communicator is supervised. 4.7K ohm End-of-Line resistors should be
connected.
In slave configuration, the five zones become five channels that may be triggered by the relay outputs of any host
FACP. The five channels function as follows:
• Zone/Channel 1 - general alarm
• Zone/Channel 2 - general trouble
• Zone/Channel 3 - may be programmed to match the FACP relay function
• Zone/Channel 4 - supervisory
• Zone/Channel 5 - may be programmed to match the FACP relay function
The factory settings for Zone/Channel 2 alarm and restoral are altered as follows:
•If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, the report code for Zone 2 Alarm Code
(address 128 & 252) is 'F' and the Zone 2 Restoral Code (address 156 & 280) is 'E'.
•If 1, A or C is entered for addresses 16 or 42, the report code for Zone 2 Alarm Code (addresses 129-130 &
253-254) is 'FF' and the Zone 2 Restoral Code (addresses 185-186 & 309-310) is 'EF.'
•If E is entered for addresses 16 or 42, the report code for Zone 2 Alarm Code and Restoral Code (addresses
130-132 & 254-256) is ‘300.’
The factory settings for Zone/Channel 4 alarm and restoral are altered as follows:
•If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, the report code for Zone 4 Alarm Code
(address 130 & 254) is '8' and the Zone 4 Restoral Code (address 158 & 282) is 'E'.
•If 1, A or C is entered for addresses 16 or 42, the report code for Zone 4 Alarm Code (addresses 133-134 &
257-258) is '84' and the Zone 4 Restoral Code (addresses 189-190 & 313-314) is 'E4.'
•If E is entered for addresses 16 or 42, the report code for Zone 4 Alarm Code and Restoral Code (addresses
136-138 & 260-262) is ‘200.’
Location 56 must be programmed to a '1' to enable the control panel as a slave communicator.
Note that remote site upload or download is permitted in the Slave Communicator configuration, however, alarm
presignal and verification do not function in Slave mode.
Be certain to connect the slave communicator's primary AC power to the same branch circuit as the host FACP.
Document #15140 Rev.G 01/02/02 P/N 15140:G
67
Page 68
Slave Communicator Configuration
FIGURE 6-1:
Slave Communicator Connections
Relays in the master FACP activate various input circuits on the slave communicator. Messages (event codes) programmed for a particular input circuit (channel) will be transmitted to the Central Station upon relay activation.
68
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 69
Remote Site Upload/Download
CHAPTER 7Remote Site Upload/Download
The control panel may be programmed or interrogated off-site via the public switched telephone network. Any personal computer with DOS
™
4.01 or greater plus Windows™ 3.1 or greater, with a 1200 baud Hayes™ compatible
modem and Fire•Lite Upload/Download software P/N PK-5024UD, may serve as a Service Terminal. This allows
download of the entire program or upload of the entire program, history file, walktest data, current status, system
voltages, time and date.
CAUTION: After successfully downloading a program, make certain to perform the following steps:
Print out all programmed data via Print Mode or manually view programmed entries and compare to intended
1.
program data
Test all affected panel operations
2.
Immediately correct any problems found
3.
7.1Downloading Program
The first time that the control panel is downloaded (whether initiated at the jobsite or remotely), a secret code is
loaded in by a Service Terminal. Future upload or download requests cause verification of the secret code by the control panel before processing of data is allowed. If the secret code is not verified, the control panel will terminate the
request.
While the control panel is communicating with the Service Terminal, the panel's green Modem LED and one of the
red Line Seize LEDs will remain on steady. At the conclusion of a successful download, the green Kissoff LED will
turn on steady for five seconds, the green Modem LED will turn off and the red Line Seize LED will turn off.
In order to download the panel (whether initiated at the jobsite or remotely), the following must be true:
✓
The control panel must be in the Normal Mode of operation. Downloading is not possible if the panel is
in any other mode
✓
There cannot be any active communications ongoing with a Central Station receiver
✓
All active events must be successfully 'kissed-off' by the Central Station(s). The communicator must be
in a standby state with no new information waiting to be transmitted to a Central Station
With program address location 56 set to '1' or '2', anytime a download is initiated, the control panel will first contact
the primary Central Station or both the primary and secondary Central Stations to report a 'request for upload/download' message. Once the request is 'kissed-off' by the Central Station(s), the control panel will then call the appropriate Service Terminal and begin the downloading process.
To prevent the 'request for upload/download' message(s) from being reported to the Central Station(s), make certain
to leave address 56 set to '0' or disable all upload/download reports back to both Central Stations.
During the downloading process, the fire protection remains active
. Should a system trouble or alarm condition
occur, the control panel immediately terminates downloading and processes the trouble or alarm locally and transmits the information to the Central Station(s).
Document #15140 Rev.G 01/02/02 P/N 15140:G
69
Page 70
Downloading Program
7.1.1 Security Features
Remote site upload and download with the control panel has been carefully designed to include key security features
to ensure proper functionality. The key features are listed and explained below.
Secret Code Verification
A secret code is stored in the control panel by a Service Terminal to prevent unauthorized access. The secret code is
created at the Service Terminal by the master user and cannot be viewed or changed by anyone other than a master
user. Viewing of the secret code is prohibited at the control panel. Prior to allowing an upload or download of data,
the control panel will verify the secret code transmitted by the Service Terminal.
Time-out at Control Panel
Upon answering an incoming call on either the primary or secondary Central Station phone line, the control panel
will listen for a modem connection signal. If this signal is not received within 30 seconds, the control panel will disconnect the call.
Callback to Service Terminal
Any time the control panel is requested to allow an upload or download, it will confirm the source of the incoming
call, hang-up and call back the calling party (Service Terminal phone number).
Panel Identification Number
The panel identification number is typically used to identify the panel to the Service Terminal when the control panel
calls the Service Terminal. If more than one call comes into the Service Terminal, the control panel ID number is
used to sort out the calling parties.
Another use of this code allows for identical secret codes to be placed into multiple control panels at one jobsite,
using the panel ID number to distinguish between the individual panels.
Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If an error is detected, the block is
retransmitted until correct, up to a maximum of four times. If the Secret Code is not verified and four errors occur,
the call is disconnected and the report that the upload/download was not successful is called to the Central Station(s).
Central Station Acknowledge
There is an option, referred to as the ‘callback’ option, whereby the control panel will report to one or both Central
Stations that a request for uploading or downloading has been received prior to processing the call. If the Central
Station(s) does not acknowledge receipt of this request, uploading or downloading is prohibited. If acknowledged by
the Central Station(s), another message is transmitted, informing the Central Station(s) that:
• Downloading was successful
• Uploading was successful
• Uploading/downloading was not successful
Central Station Data Protection
Addresses '00' through '51' are assigned to the primary and secondary Central Station phone number, communication
format, account code and test time. Addresses '127' through '374' are reserved for the programmable event codes.
This block of addresses holds the entire vital Central Station information. These blocks are protected from partial
programming due to faulty phone connections, line noise and other errors. This prevents the panel from being confused due to a wrong phone number, account code, test time and most critical formatting errors.
70
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 71
Downloading Initiated at Control Panel
7.2Downloading Initiated at Control Panel
Before initiating the download procedure, make certain that the control panel is:
In Normal Mode
✓
Central Station communications are off or location 56 is set to '0'
✓
The communicator is in the standby state (red Line Seize LEDs are off, green Modem and Kissoff LEDs
✓
are off)
Place the control panel into Program Mode and program one or both of the Service Terminal phone numbers. It is
also advisable at this time to program the Panel Identification Number at addresses 84 - 87. This will allow the Service Terminal to easily identify incoming calls.
Exit the Program Mode and return the panel to Normal Mode. Press the MODE key followed by the 4-digit code
3696 and then the [ENTER/STORE] key.
3696 spells DOWN on a Touch-Tone
☛
The display to the far left will flash the letter 'S'. Press the digit '1' for Service Terminal phone #1 or '2' for Service
Terminal #2, followed by [ENTER/STORE]. The control panel will now call the appropriate Service Terminal
phone number and the downloading process will begin.
®
phone.
Once the called Service Terminal identifies the incoming call (control panel), the downloading process is allowed to
continue. Downloading progresses until all programmed information has been successfully loaded into the control
panel. The programmed data may consist of addresses 00-374 plus the time and date.
7.3Downloading Initiated at a Service Terminal
Before initiating the download procedure, make certain that the control panel is:
In Normal Mode
✓
Central Station communications are off or location 56 is set to '0'
✓
The communicator is in the standby state (red Line Seize LEDs are off, green Modem and Kissoff LEDs
✓
are off)
Once the control panel accepts/answers an incoming call, the panel will:
Establish basic modem connection
1.
Verify secret code and panel identification number
2.
Verify callback vs. no callback request from the service terminal. If callback is requested, steps 4 through 9
3.
will occur. If no callback is requested, only steps 8 and 9 will occur
Identify the Service Terminal location
4.
Hang-up/disconnect call
5.
Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
6.
this message is accepted, the control panel will proceed to the next step
Return call to Service Terminal
7.
After security clearance, begin downloading
8.
Upon completion of download, call Central Station(s) back and report either a successful download or failed
9.
upload/download message (if programmed to do so)
Document #15140 Rev.G 01/02/02 P/N 15140:G
71
Page 72
Uploading Initiated at a Service Terminal
7.4Uploading Initiated at a Service Terminal
Items that may be uploaded from the control panel to a Service Terminal are:
• All programmed data from addresses 00-374 plus the real-time clock, time and date
• Entire Walktest data file
• Troubleshoot Mode system voltages
• Entire 32 event History file
• Current system status
Uploading is possible at any time provided the following conditions are true:
✓The control panel must be in the Normal Mode of operation. Uploading is not possible if the panel is in
any other mode
✓There cannot be any active communications ongoing with a Central Station receiver
✓
All active events must be successfully 'kissed-off' by the Central Station (the communicator must be in
a standby state with no new information waiting to be transmitted to a Central Station)
Once an incoming call is accepted/answered by the control panel, the panel will:
Establish basic modem connection
1.
Verify secret code and panel identification number
2.
Verify callback vs. no callback request from the service terminal. If callback is requested, steps 4 through 9
3.
will occur. If no callback is requested, only steps 8 and 9 will occur
Identify the Service Terminal location
4.
Hang-up/disconnect call
5.
Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
6.
this message is accepted, the control panel will proceed to the next step
Return call to Service Terminal
7.
After security clearance, begin uploading
8.
Upon completion of upload, call Central Station(s) back and report either a successful upload or failed upload/
9.
download message (if programmed to do so).
During the uploading process, the fire protection remains active
. Should a system trouble or alarm condition
occur, the control panel immediately terminates uploading and processes the trouble or alarm locally and transmits the information to the Central Station(s).
72
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 73
Battery Calculations
Appendix ABattery Calculations
Use the Total Standby and Alarm Load Currents calculated in Table A-2 and Table A-3 for the following battery
calculation.
TAB LE A- 1:
Standby Load
Current (Amps)
Current (Amps)
Battery Calculations
[ ]
Alarm Load
[ }
Required Standby Time in Hours
X
(24 or 60 Hours)
[ ]
Required Alarm Time in Hours
X
(i.e. 5 minutes = 0.084)
[ ]
Add Standby and Alarm Load for Required Ampere Hour Battery=__________
Multiply by the Derating Factor of 1.2X 1.2__________
Total Ampere Hours (AH) Required=__________
Note:
7 Ampere Hour battery can be located in the backbox.
1.
12 Ampere Hour and 17 Ampere Hour batteries require the BB-17F battery box.
2.
=__________
=__________
Document #15140 Rev.G 01/02/02 P/N 15140:G
73
Page 74
Battery Calculations
A.1The Main Power Supply
The MS-5024UD provides filtered power for operating the fire alarm control panel, external devices and the standby
battery. The power for operating external devices is limited. Use Table A-2 (standby or nonalarm) and Table A-3
(alarm) to determine if external loading is within the capabilities of the power supply.
Concerning 4-wire smoke detectors: Be sure to power smoke detectors from TB4, Terminals 3 and 4.
TABLE A-2:
Filtered Load in Standby - external devices connected to TB4 only
Device Type
# of
Devices
Current
(Amps)
Total Current
(Amps)
Main Circuit Board1X0.1=0.1
ADM-24(1 max.)X0.006=
RZA-5F(1 max.)X0=0
RM-5F(1 max.)X0=0
CAC-5F(1 max.)X0=0
2-wire Smoke Detector
Heads
[ ]X
[ ]
1
=
4-wire Smoke Detector
Heads
Power Supervision
2
Relays
Current Draw from
TB4 (nonalarm)
3
[ ]X
[ ]X0.025=
[ ]
1
=
=
Sum Column for Standby Load=Amps
1. Refer to the Device Compatibility Document for 2-wire smoke detector standby current.
2. Must use compatible listed power supervision relay.
3. The total standby current must include the sum of both the resettable (TB4, Terminals 3 & 4) and nonresettable (TB4,
Terminals 5 & 6) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not
exceed maximum ratings specified (refer to Table A-3 )
74
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 75
Battery Calculations
TAB LE A- 3:
Filtered Load in Alarm
Device Type
# of
Devices
Current
(Amps)
Main Circuit Board1X0.170=
ADM-24(1 max.)X0.006=
RZA-5F(1 max.)X
RM-5F(1 max.)X
0.046
0.080
2
2
CAC-5F(1 max.)X0=0
4
4-wire Smoke Detector
Heads
Power Supervision Relays
[ ]X[ ]=
3
[ ]X0.025=
Total C urr ent
(Amps)
1
0.170
=
=
4
Notification Appliances
Notification Appliances
Current Draw from TB4
(alarm)
Sum Column for Standby Load
1. The current shown represents one zone on the main circuit board in alarm. For all five zones in alarm, the current draw
increases to 0.36 amps.
2. The currents shown for the RZA-5F and RM-5F are for all five zones in alarm. For one zone in alarm, the RZA-5F current draw is 16 mA and the RM-5F current draw is 12 mA.
3. Must use compatible listed Power Supervision Relay.
- 3.6 amps with only the standard transformer installed
- 5.6 amps with both the standard and optional transformer installed
[ ]X[ ]=
4
[ ]X[ ]=
4
5
=
=Amps
. Nonresettable power (100Hz
RMS
. Resettable power (100Hz rip-
RMS
Document #15140 Rev.G 01/02/02 P/N 15140:G
75
Page 76
Programming Reference Sheets
f
f
f
f
Appendix BProgramming Reference Sheets
...To enter Programming Mode, press the MODE key, the code 7764 and then the [ENTER/STORE] key...
❐00❐01❐02❐03❐04❐05❐06❐07❐08❐09❐10❐11❐12❐13❐14❐
Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.
❐
Primary Central Station Communication Format: Enter '0 - F'.
16
❐17❐18❐19❐
❐21❐22❐23❐
❐
Primary Number Test Time Interval. Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
25
Primary Central Station Account Code: Valid entries are '0 - F'.
20
Primary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
24
❐26❐27❐28❐29❐30❐31❐32❐33❐34❐35❐36❐37❐38❐39❐40❐
Addresses 26 to 41 store the Secondary Central Station Phone Number. Enter 'F' to represent the end of the number.
❐
Secondary Central Station Communication Format: Enter '0 - F'.
42
❐43❐44❐45❐
❐47❐48❐49❐
❐
Secondary Number Test Time Interval. Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
51
❐
Alarm Verification. Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
52
❐53❐54❐
❐
Slave Communicator/Fire Panel Selection. Enter '0' for fire panel only; '1' for slave communicator only; '2'
56
or fire panel/communicator operation.
55
Secondary Central Station Account Code: Valid entries are '0 - F'.
46
Secondary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
50
Future use.
15
41
❐
Zone 1 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
57
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
Zone 2 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
58
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
Zone 3 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
59
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6'
or waterflow (nonsilenceable).
❐
Zone 4 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
60
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
Zone 5 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
61
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐62❐
❐
64
or 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19 hours; 'C'
or 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
❐
65
❐66❐67❐
Waterflow Retard timer. Enter 0 - 89 additional seconds.
63
AC Loss Delay. Enter '0' for 6 hour delay; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10 hours; '5'
Alarm Presignal. Enter '0' to disable alarm presignal; '1' to enable.
Service Terminal #2 Phone Number. Enter 'F' to represent the end of the number.
03
❐
123❐124
0
❐
125
0
❐
126
tion Phone Number on backup only.
Ring Count on Primary Phone Line. Default is '03' for do not answer until 3 rings are detected.
FAX/Answer Machine, Primary Phone Line. '0' for no sharing of phone line.
Ring Count on Secondary Phone Line. Default is '03' for do not answer until 3 rings are detected.
FAX/Answer Machine, Secondary Phone Line. '0' for no sharing of phone line.
Upload/Download Backup Reporting. '0' for Upload/Download reports to go to the Secondary Central Sta-
100❐101❐102❐103
80
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 81
Programming Reference Sheets
Programming Reference Sheets Factory Default
1111111111111
❐
❐
❐
❐
❐
❐
❐
❐
127
1157057057057
❐
140
0570604301380
❐
153
3803803803803
❐
166
1030231135135
❐
179
2321322354354
❐
192
3303086026084
❐
205
128
141
154
167
180
193
206
❐
❐
❐
❐
❐
❐
❐
129
142
155
168
181
194
207
❐
❐
❐
❐
❐
❐
❐
130
143
156
169
182
195
208
❐
❐
❐
❐
❐
❐
❐
131
144
157
170
183
196
209
❐
❐
❐
❐
❐
❐
❐
132
145
158
171
184
197
210
❐
❐
❐
❐
❐
❐
❐
133
146
159
172
185
198
211
❐
❐
❐
❐
❐
❐
❐
134
147
160
173
186
199
212
❐
❐
❐
❐
❐
❐
❐
135
148
161
174
187
200
213
❐
❐
❐
❐
❐
❐
❐
136
149
162
175
188
201
214
❐
❐
❐
❐
❐
❐
❐
137
150
163
176
189
202
215
❐
❐
❐
❐
❐
❐
❐
138
151
164
177
190
203
216
❐
❐
❐
❐
❐
❐
❐
139
152
165
178
191
204
217
11416412413
❐
218
❐
219
❐
220
❐
221
❐
222
❐
223
❐
224
❐
225
❐
226
❐
227
❐
228
Document #15140 Rev.G 01/02/02 P/N 15140:G
81
Page 82
Operation and Function Modes
Appendix COperation and Function Modes
C.1Operation Modes
TABLE C-1:
Operation Modes
CODEACTIVITYNOTES
6676 (NORM)Returns to normal operationFire protection is on
7764 (PROG)Enters Program Mode
9255 (WALK)Enters Walktest Mode
4478 (HIST)View History File
8768 (TROU)
Activates internal system voltmeter for troubleshooting and diagnosing problems
Sends status, history file, walktest file, trou-
7746 (PRIN)
bleshoot voltages and entire programming
selections to printer
5267 (LAMP)
3696 (DOWN)
Turns on all LEDs on the main circuit board
and all system annunciators for five seconds
Allows for downloading the entire program
file to the panel
4 levels of programming may be entered.
Fire protection is off
May select audible walktest function. Fire
protection is off
Use display or printer to view History File.
Fire protection is off
Fire protection is off while voltmeter function
is enabled
Fire protection is off. Requires PRT-24
option module
Fire protection is on
Must have service terminal ready. Fire protection remains on
C.2Function Modes
TABLE C-2:
CODEACTIVITYNOTES
3472 (DISA)Allows disabling of any input zone
3622 (ENAB)
3745 (DRIL)
3337 (DEFP)
Function Modes
Allows enabling (return to normal) of any
zone
Performs drill function by turning on all
NAC outputs
Reprograms all entries for programming
back to the original factory settings
May only disable one zone at a time. Places
system into trouble
May only enable one zone at a time
Transmission of drill function to Central Station is defaulted to ON
Entry of code must be performed two times in
rapid succession as a safety feature. Use
caution when using this feature
82
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 83
Ademco Contact ID Format Event Code Descriptions
Appendix DAdemco Contact ID Format Event
Code Descriptions
This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID
Format.
The reporting structure for the Ademco Contact ID Format is as follows:
SSS 18 QXYZ GG CCC
where
SSSS= Four digit Subscriber ID Account Code (addresses 17 - 20 and 43 - 46)
18= Identifies transmission as Contact ID to the receiver at the Central Station
Q= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ= Event code (shown in Table 3-3 on page 38 and Table 3-6 on page 43)
GG= Group number
CCC= Zone number
Notes:
GG Group Number is fixed at '00' and cannot be changed.
1.
CCC Zone Number is transmitted as '001' for zone one up to '005' for zone five.
2.
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the
Ademco Contact ID Reporting Structure follows:
TimeDateRcvr/Line IDSSSSQXYZGGCCCC
11:2803/25117777E11000C001 - general fire alarm on zone one
11:2803/25117777E11100C002 - smoke detector alarm on zone two
11:2803/25117777E38000C003 - fault on zone three
11:2803/25117777E57000C004 - Zone four disabled
11:2803/25117777R11000C001 - Zone one alarm restored
11:2803/25117777R11100C002 - smoke detector zone two restored
11:2803/25117777R38000C003 - zone three fault restored
11:2803/25117777R57000C004 - zone four reenabled
11:2803/25117777E15800C005 - high temperature, zone five
11:2803/25117777E15100C003 - gas detected, zone three
Notes:
18
, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
1.
alarm and trouble report.
Q
, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or
2.
R
for New Restore.
Document #15140 Rev.G 01/02/02 P/N 15140:G
83
Page 84
Ademco Contact ID Format Event Code Descriptions
EVENT CODE CLASSIFICATIONS
1 0 0
ALARMS
Medical
Fire
Panic
Burglary
General
24 Hour
2 00
SUPERVISORY
Fire
3 00
TROUBLES
System
Sounder/Relay
System Peripheral
Communication
Protective Loop
Sensor
400
OPEN/CLOSE
REMOTE ACCESS
Open/Close
Remote Access
Access Control
5 00
DISABLES/
BYPASSES
System
Sounder/Relay
System Peripheral
Communication
EVENTMESSAGE
Medical Alarms - 100
100 MedicalEMERG - Personal Emergency - #
101 Pendant transmitterEMERG - Personal Emergency - #
102 Fail to report inEMERG - Fail to Check-in - #
24 Hour Non-Burglary - 150 and 160
150 24-Hour Non-BurgALARM - 24-Hr. Non-Burg - #
151 Gas detectedALARM - Gas Detected - #
152 RefrigerationALARM - Refrigeration - #
153 Loss of heatALARM - Heating System - #
154 Water leakageALARM - Water Leakage - #
155 Foil breakALARM - Foil Break - #
156 Day trouble ALARM - Day Zone - #
157 Low bottled gas levelALARM - Low Gas Level - #
158 High tempALARM - High Temperature - #
159 Low tempALARM - Low Temperature - #
161 Loss of air flowALARM - Air Flow - #
Fire Supervisory - 200 and 210
200 Fire supervisorySUPER. - Fire Supervisory - #
201 Low water pressureSUPER. - Low Water Pressure - #
202 Lox CO2SUPER. - Low CO2
203 Gate valve sensorSUPER. - Gate Valve - #
204 Low water levelSUPER. - Low Water Level - #
205 Pump activatedSUPER. - Pump Activation - #
206 Pump failureSUPER. - Pump Failure - #
System Troubles - 300 and 310
300 System troubleTROUBLE - System Trouble
301 AC lossTROUBLE - AC Power
302 Low system batteryTROUBLE - System Low Battery
303 RAM checksum badTROUBLE - Bad RAM Checksum (Restore not applicable)
304 ROM checksum badTROUBLE - Bad ROM Checksum (Restore not applicable)
305 System resetTROUBLE - System Reset (Restore not applicable)
306 Panel program changedTROUBLE - Programming Changed (Restore not applicable)
307 Self-test failureTROUBLE - Self Test Failure
308 System shutdownTROUBLE - System Shutdown
309 Battery test failureTROUBLE - Battery Test Failure
310 Ground faultTROUBLE - Ground Fault - #
311 No batteryTROUBLE - No Battery
System Peripheral Troubles - 330 and 340
330 System peripheralTROUBLE - Sys. Peripheral - #
331 Polling loop openTROUBLE - Polling Loop Open
332 Polling loop shortTROUBLE - Polling Loop Short
333 Expansion module failureTROUBLE - Exp. Module Fail - #
334 Repeater failureTROUBLE - Repeater Failure - #
335 Local printer paper outTROUBLE - Printer Paper Out
336 Local printer failureTROUBLE - Local Printer
Document #15140 Rev.G 01/02/02 P/N 15140:G
85
Page 86
Ademco Contact ID Format Event Code Descriptions
EVENTMESSAGE
Communication Troubles - 350 and 360
350 CommunicationTROUBLE - Communication Trouble
351 Telco 1 faultTROUBLE - Phone Line #1
352 Telco 2 faultTROUBLE - Phone Line #2
353 Long range radio xmitter faultTROUBLE - Radio Transmitter
354 Fail to communicateTROUBLE - Fail to Communicate
355 Loss of radio supervisionTROUBLE - Radio Supervision
356 Loss of central pollingTROUBLE - Central Radio Polling
Open/Close - 400
400 Open/CloseOPENINGCLOSING
401 Open/Close by userOPENING - User #CLOSING - User #
402 Group Open/CloseOPENING - Group User # CLOSING - Group User #
403 Automatic Open/CloseOPENING - AutomaticCLOSING - Automatic
404 Late Open/CloseOPENING - LateCLOSING - Late
405 Deferred Open/CloseOpening not usedClosing not used
406 CancelOPENING - CancelClosing not used
407 Remote arm/disarmOPENING - RemoteCLOSING - Remote
408 Quick armOpening not applicableCLOSING - Quick arm
409 Keyswitch Open/CloseOPENING - KeyswitchCLOSING - Keyswitch
Remote Access - 410
411 Callback request madeREMOTE - Callback RequestedRestore not applicable
412 Success - download/accessREMOTE - Successful AccessRestore not applicable
413 Unsuccessful accessREMOTE - Unsuccessful AccessRestore not applicable
414 System shutdownREMOTE - System Shutdown
415 Dialer shutdownREMOTE - Dialer Shutdown
416 Success - upload/accessREMOTE - Successful AccessRestore not applicable
Access Control - 420
421 Access deniedACCESS - Access Denied - User # Restore not used
422 Access report by userACCESS - Access Gained - User # Restore not used
Communication Disables - 550 and 560
551 Dialer disabledDISABLE - Dialer Disable
552 Radio transmitter disabledDISABLE - Radio Disable
Bypasses - 570
570 Zone bypassBYPASS - Zone Bypass - #
571 Fire bypassBYPASS - Fire Bypass - #
572 24-Hour zone bypassBYPASS - 24-Hour Bypass - #
573 Burglar bypassBYPASS - Burg. Bypass - #
574 Group bypassBYPASS - Group Bypass - #
Test Misc. - 600
601 Manual trigger testTEST - Manually TriggeredRestore not applicable
602 Periodic test reportTEST - PeriodicRestore not applicable
603 Periodic RF transmissionTEST - Periodic RadioRestore not applicable
604 Fire testTEST - Fire TestRestore not used
605 Status report to followSTATUS - Status FollowsRestore not applicable
606 Listen-in to followLISTEN - Listen-in ActiveRestore not applicable
607 Walk test modeTEST - Walk Test Mode
608 System abnormal testTEST - System Abnormal Test
Document #15140 Rev.G 01/02/02 P/N 15140:G
87
Page 88
Notes
88
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 89
Index
Numerics
1st EVENT 13, 51
A
AC Line Voltage 65
AC Loss Reporting Delay 46
AC Power 16
AC Power LED 13, 52
Ademco Contact ID format 83
Ademco Express 14
ADM-24 29
ADM-24 Annunciator Driver
The manufacturer warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service. Products
are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer
is to repair or replace, at its option, free of charge for parts and labor, any part which is
defective in materials or workmanship under normal use and service. For products not under
the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of
original purchase by the manufacturer's distributor unless the installation instructions or catalog
sets forth a shorter period, in which case the shorter period shall apply. This warranty is void
if the product is altered, repaired, or serviced by anyone other than the manufacturer or its
authorized distributors, or if there is a failure to maintain the products and systems in which
they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our customer service department. Return product, transportation
prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its
products. The manufacturer does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they are
installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes
no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse,
abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER
NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S
PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR
AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the
manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.
LimWarLg.p65 01/10/2000
Page 92
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.