Fire-Lite Alarms MS-5024UD, MS-5024UDE User Manual

Page 1
PN: 15140:G ECN 01-685
Fire Alarm Control Panel
MS-5024UD/MS-5024UDE
Document #15140 01/02/02 Revision
G
Page 2
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warn­ing devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reach­ing the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede­termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power. If detectors are not so lo-
cated, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibil­ity to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized pro­fessional fire alarm installers only. Adequate written records of all inspections should be kept.
Precau-Lg.p65 01/18/2000
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, ad­dition or deletion of system components, or after any modifica­tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for operation at 0-49° C/32-120° F condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi­nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes. Consult with the Techni-
cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used
in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environ­ment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be re­quired to correct the interference at his own expense.
Precau-Lg.p65 01/18/2000
Page 4
Notes
4
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 5
Table of Contents
CHAPTER 1: Product Description .........................................................................................................................10
1.1: Product Features..........................................................................................................................................10
FIGURE 1-1: Optional DP-5024UD....................................................................................................11
FIGURE 1-2: MS-5024UD Panel........................................................................................................12
1.2: Controls and Indicators ...............................................................................................................................13
FIGURE 1-3: Controls and Indicators .................................................................................................13
1.3: Circuits ........................................................................................................................................................13
1.4: Digital Communicator.................................................................................................................................14
1.5: Components.................................................................................................................................................14
1.5.1: Main Circuit Board ...........................................................................................................................14
1.5.2: Cabinet ..............................................................................................................................................14
1.5.3: Transformer Assembly......................................................................................................................15
FIGURE 1-4: XRM-24(E) Transformer ..............................................................................................15
1.5.4: Batteries ............................................................................................................................................15
1.6: Optional Devices .........................................................................................................................................15
1.6.1: RM-5F Five-Zone Relay Module .....................................................................................................15
1.6.2: CAC-5F Class A Converter Module.................................................................................................15
1.6.3: ADM-24 Annunciator Driver Module ..............................................................................................15
1.6.4: RZA-5F Remote Annunciator...........................................................................................................15
1.6.5: PRT-24 Printer Interface Module......................................................................................................16
1.6.6: DP-5024UD Dress Panel ..................................................................................................................16
1.6.7: BB-17F Battery Box .........................................................................................................................16
1.6.8: PK-5024UD Programming Kit .........................................................................................................16
1.7: Specifications ..............................................................................................................................................16
1.8: Telephone Requirements and Warnings ......................................................................................................18
1.8.1: Telephone Circuitry...........................................................................................................................18
1.8.2: Digital Communicator.......................................................................................................................18
1.8.3: Telephone Company Rights and Warnings .......................................................................................18
CHAPTER 2: Installation.........................................................................................................................................19
2.1: Mounting Options ......................................................................................................................................19
FIGURE 2-1: MS-5024UD Cabinet ....................................................................................................19
2.2: Backbox Mounting......................................................................................................................................19
FIGURE 2-2: Cabinet Dimensions and Knockout Locations ..............................................................20
FIGURE 2-3: Backbox and Battery Box .............................................................................................21
2.3: Operating Power..........................................................................................................................................22
FIGURE 2-4: Operating Power Connections.......................................................................................22
2.4: Input Circuits...............................................................................................................................................23
FIGURE 2-5: Typical Initiating Device Circuit Connections .............................................................23
2.5: Output Circuits ............................................................................................................................................24
FIGURE 2-6: Auxiliary Power Connections .......................................................................................24
FIGURE 2-7: Notification Appliance Circuit Connections .................................................................24
FIGURE 2-8: Auxiliary Relay and Relay Driver Terminals ...............................................................25
2.6: UL Power-limited Wiring Requirements ....................................................................................................26
FIGURE 2-9: Typical Wiring Diagram for UL Power-limited Requirements ....................................26
2.7: Digital Communicator.................................................................................................................................27
FIGURE 2-10: Wiring Phone Jacks.....................................................................................................27
2.8: Optional Boards...........................................................................................................................................28
2.8.1: ADM-24 Annunciator Driver Module ..............................................................................................28
FIGURE 2-11: ADM-24 Annunciator Driver Module ........................................................................28
2.8.2: RZA-5F Remote Annunciator ..........................................................................................................28
FIGURE 2-12: RZA-5F .......................................................................................................................28
Document 15140 Rev. G 01/02/02 P/N: 15140:G 5
Page 6
Table of Contents
FIGURE 2-13: Wiring the RZA-5F/ADM-24 .....................................................................................29
FIGURE 2-14: Installing the Annunciator (Single-Gang Electrical Box) ...........................................29
2.8.3: PRT-24 Printer Interface Module......................................................................................................30
FIGURE 2-15: Remote Printer Connections........................................................................................30
2.8.4: RM-5F Five-Zone Relay Module......................................................................................................31
FIGURE 2-16: RM-5F Installation and Wiring ...................................................................................31
2.8.5: CAC-5F Class A Converter Module .................................................................................................32
FIGURE 2-17: CAC-5F Style D Converter .........................................................................................32
CHAPTER 3: Programming Instructions...............................................................................................................33
3.1: Entering Program Mode ..............................................................................................................................33
3.2: Switch Functions .........................................................................................................................................34
FIGURE 3-1: Control Panel Keypad ...................................................................................................34
3.3: Programming Options .................................................................................................................................34
TABLE 3-1: Primary Event Codes - 3+1, 4+1 Express, 4+1 Standard, Expanded & 4+2 Expanded .36
TABLE 3-2: Primary Event Codes - 4+2 Standard and 4+2 Express..................................................37
TABLE 3-3: Event Codes, Primary Central Station Number..............................................................38
TABLE 3-4: Secondary Event Codes-3+1, 4+1 Express, 4+1 Standard, Expanded & 4+2 Expanded41
TABLE 3-5: Secondary Event Codes - 4+2 Standard and 4+2 Express..............................................42
TABLE 3-6: Event Codes, Secondary Central Station Number ..........................................................43
FIGURE 3-2: Verification Timing Diagram........................................................................................44
TABLE 3-7: Zone Function Selection .................................................................................................45
3.4: Default Programming ..................................................................................................................................49
CHAPTER 4: Operating Instructions ....................................................................................................................50
4.1: Switches in Normal Mode...........................................................................................................................50
4.1.1: RESET...............................................................................................................................................50
4.2: Displays .......................................................................................................................................................51
FIGURE 4-1: Phone Connectors and LEDs.........................................................................................52
4.3: Operation .....................................................................................................................................................53
4.3.1: Alarm Response ................................................................................................................................53
4.3.2: Alarm Restoral ..................................................................................................................................54
4.3.3: System Supervisory Condition Response .........................................................................................54
4.3.4: System Supervisory Restoral Response ............................................................................................54
4.3.5: Trouble Condition Response .............................................................................................................55
4.3.6: Trouble Condition Restoral...............................................................................................................55
4.3.7: Off Normal Reporting .......................................................................................................................55
4.3.8: Zone Disable/Enable .........................................................................................................................56
4.3.9: Fire Drill............................................................................................................................................56
4.4: Central Station Communications.................................................................................................................57
TABLE 4-1: Format Selection Address (16 & 42) ..............................................................................58
TABLE 4-2: Format Selection Address Explanation...........................................................................59
4.4.1: Transmittal Priorities.........................................................................................................................60
TABLE 4-3: Compatible UL Listed Receivers....................................................................................61
CHAPTER 5: Servicing............................................................................................................................................62
5.1: Walktest Mode.............................................................................................................................................62
5.2: History Mode...............................................................................................................................................63
5.3: Troubleshoot Mode......................................................................................................................................64
5.3.1: Zone Voltages ....................................................................................................................................64
TABLE 5-1: Nominal Zone Voltages..................................................................................................64
5.3.2: AC Line Voltage................................................................................................................................65
5.3.3: Battery Voltage ..................................................................................................................................65
5.3.4: Telephone Lines ................................................................................................................................65
FIGURE 5-1: Phone Connectors and LEDs.........................................................................................65
TABLE 5-2: AC Line Voltage Range..................................................................................................65
6
Document 15140 Rev. G 01/02/02 P/N: 15140:G
Page 7
Table of Contents
TABLE 5-3: Battery Voltage...............................................................................................................65
5.3.5: NAC 1 & 2 ........................................................................................................................................66
5.3.6: Resettable Power...............................................................................................................................66
5.4: Lamp Test ....................................................................................................................................................66
5.5: Print Mode...................................................................................................................................................66
CHAPTER 6: Slave Communicator Configuration ...............................................................................................67
FIGURE 6-1: Slave Communicator Connections...............................................................................68
CHAPTER 7: Remote Site Upload/Download .......................................................................................................69
7.1: Downloading Program ................................................................................................................................69
7.1.1: Security Features...............................................................................................................................70
7.2: Downloading Initiated at Control Panel......................................................................................................71
7.3: Downloading Initiated at a Service Terminal..............................................................................................71
7.4: Uploading Initiated at a Service Terminal...................................................................................................72
Appendix A: Battery Calculations .......................................................................................................................73
TABLE A-1: Battery Calculations ......................................................................................................73
A.1: The Main Power Supply ............................................................................................................................74
TABLE A-2: Filtered Load in Standby - external devices connected to TB4 only ............................74
TABLE A-3: Filtered Load in Alarm .................................................................................................75
Appendix B: Programming Reference Sheets .....................................................................................................76
Appendix C: Operation and Function Modes .....................................................................................................82
C.1: Operation Modes .......................................................................................................................................82
C.2: Function Modes ........................................................................................................................................82
TABLE C-1: Operation Modes ...........................................................................................................82
TABLE C-2: Function Modes .............................................................................................................82
Appendix D: Ademco Contact ID Format Event Code Descriptions ...............................................................83
Document 15140 Rev. G 01/02/02 P/N: 15140:G 7
Page 8
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code for Local, Remote Station and Central Station Fire Alarm System
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Central Station Fire Alarm Systems Protected Premises Unit (Automatic, Manual and Waterflow), Local Fire Alarm Systems (Automatic, Manual, Waterflow and Sprinkler Supervisory), Auxiliary Protective Fire Alarm Systems (Automatic, Manual and Water­flow), Proprietary Protective Fire Alarm Systems (Automatic, Manual and Waterflow) and Remote Station Fire Alarm Systems (Automatic, Manual and Waterflow).
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384
8
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 9
MS-5024UD Main Circuit Board
Document #15140 Rev.G 01/02/02 P/N 15140:G
9
Page 10
Product Description
CHAPTER 1 Product Description
The MS-5024UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator Transmitter) all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally open contact devices. Outputs include two NACs (Notification Appliance Circuits), alarm and trouble relays, super­visory and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to UL-listed Central Stations via the public switched telephone network. The control panel has a built-in programmer and may also serve as a slave communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery level.
The control panel may be programmed or interrogated off-site via the public switched telephone network. Any IBM
compatible personal computer with DOS
4.01 or greater plus Windows™ 3.1 or greater, with a 1200 baud Hayes™ compatible modem and Fire•Lite Upload/Download software P/N PK-5024UD, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages. The MS-5024UDE offers the same features as the MS-5024UD but allows connection to 220/ 240 VAC input.
1.1 Product Features
• Selectable as Fire Panel, Fire Panel/Communicator or Slave Communicator
• Programmable Zone ID: 2-wire smoke, pull station, normally open contact device, supervisory, supervisory autosilence, waterflow silenceable or waterflow nonsilenceable
• One Style D (Class A) zone
• Four Style B (Class B) zones
• 3.6 amps usable power expandable to 5.6 amps
• Optional 5-zone Relay Module (RM-5F)
• CAC-5F Style D (Class A) Zone Converter Module
• Two NFPA Style Y (Class B) or Style Z (Class A) Notification Appliance (bell) Circuits
• Built-in programmer
• Built-in voltmeter
• Telephone Line Active LED indicators
• Communication confirmation (Kissoff) LED
• Disable report by event
• Programmable event codes
• 24 volt operation
• Real-Time clock and calendar
• Trouble reminder
• Alarm verification
• RZA-5F remote annunciator (requires ADM-24 Annunciator Driver Module)
• Small size - 15" (38.1 cm) x 14.5" (36.83 cm) x 2.75" (6.985 cm)
• History file with 32 event storage
• Silence inhibit per NAC (Notification Appliance Circuit)
• Autosilence per NAC
10
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 11
Product Features
A
• Touchtone/Rotary dialing
• Programmable make/break ratio
• Fuseless design
• PRT-24 (Printer Interface Module)
• Print real-time system status
• Print history and walktest files, program contents and troubleshoot mode voltages
• PK-5024UD Upload/Download Software Kit
• Number of dial attempts (minimum of 5 and maximum of 10)
• Programmable channel ID (slave)
• Programmable zone delay (waterflow only)
• Form-C alarm and trouble relays
• Supervisory and communication fail relay drivers
• Low AC voltage sense
•One-man walktest
• Optional Dress Panel cover (DP-5024UD)
Optional DP-5024UD
FIRE CONTROL/COMMUNICATOR
AC POWER
ALARM
RESET
1
4
7
A
Note: Unless otherwise specified
FIGURE 1-1:
, MS-5024UD shall be used in this manual to refer to both the MS-5024UD and
MS-5024UDE Fire Alarm Control Communicators.
n
SILENCE
2
3
5
6
8
9
0
B
TROUBLE
SUPERVISORY
MODE
F
E
1ST
D
EVENT
ENTER
C
STORE
Document #15140 Rev.G 01/02/02 P/N 15140:G
11
Page 12
Product Features
FIGURE 1-2:
MS-5024UD Panel
Notification Appliance Circuits
Standard Transformer
Four Character 7-Segment LED Display
Keypad
Optional Transformer
Alarm & Trouble Relays
5 Input Zones
Primary & Secondary Phone Lines
Annunciator Driver Module Interface Connector
Relay Module Interface Connector
PROM U23
Piezo 85dB
1
Printer Interface Module
Connector Holds up to 7 AH Batteries Up to 60 Hrs. of Standby
Software for the Fire Alarm Control Communicator is located in a PROM inserted in the IC socket labeled
1.
U23. The MS-5024UD and MS-5024UDE each contain unique software. For specific panel software infor­mation, refer to the MS-5024UD(E) Field Software Change Procedure Document #50125.
12
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 13
Controls and Indicators
1.2 Controls and Indicators
Front Panel Switches
RESET Digits 0-9
SILENCE A
MODE B
Up Arrow C
Down Arrow D
1st EVENT E
ENTER/STORE F
Displays
• Alarm - red LED
• Trouble - yellow LED
• Supervisory - yellow LED
• AC Power - green LED
• Four 7-Segment Displays - red
• Primary Phone Line Active - red LED
• Secondary Phone Line Active - red LED
• 'Kissoff' Signal from Central Station - green LED
• Silence - yellow LED
• Modem - green LED
FIGURE 1-3:
Controls and Indicators
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions.
1.3 Circuits
Input Circuits
Five input circuits provide Style B configuration with one circuit also configurable for Style D. Input circuits may be used as standard fire control panel zones or slave communicator input channels.
• Initiating Device Circuit 1 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 2 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 3 (Style B/D) accepts normally open contact devices, 2-wire smoke detectors and waterflow devices
• Initiating Device Circuit 4 (Style B) accepts normally open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 5 (Style B) accepts normally open contact devices and 2-wire smoke detectors
Output Circuits
• 24 Volt Resettable Power Output
• 24 Volt Nonresettable Power Output
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger
•Printer Port
Document #15140 Rev.G 01/02/02 P/N 15140:G
13
Page 14
Digital Communicator
Notification Appliance Circuits
Two Notification Appliance Circuits configurable for Style Y (Class B) or Style Z (Class A) with various program­mable features.
Relays
Two dry Form-C relay contacts for system alarm and system trouble are provided. Contacts are rated 2 amps @ 30 VDC and 0.5 amps @ 30 VAC resistive.
Relay Drivers
Two relay driver outputs for supervisory and communication failure are available.
1.4 Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the Primary and Secondary phone lines. Telephone line active red LEDs are provided as well as a green 'kissoff' LED. The integral digital communicator provides the following functions:
• Line Seizure - takes control of the phone lines disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone
• For tone burst or touchtone type formats: Discern proper 'Ack' and 'kissoff' tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
• Communicate in the following formats:
12 Tone Burst Types (20 pps):
(3+1, 4+1, 3+1 Expanded, 4+1 Expanded and 4+2 Expanded)
3 Touchtone Types:
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
(see Table 4-3 for a list of compatible receivers)
®
, programmable to rotary
1.5 Components
1.5.1 Main Circuit Board
The main circuit board contains the system's CPU, power supply, other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board. The main circuit board is delivered premounted in the cabinet.
1.5.2 Cabinet
The cabinet is red with an attractive navy blue front overlay. The backbox measures 15" (38.1 cm) x 14.5" (36.83 cm) x 2.75" (6.985 cm) and provides space for two batteries (up to 7 Amp Hours). Also available is an optional dress panel (DP-5024UD), which mounts inside the cabinet.
14
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 15
Optional Devices
1.5.3 Transformer Assembly
FIGURE 1-4:
XRM-24(E) Transformer
One 100VA transformer is provided standard with the panel (3.6 amps maximum). An optional 100VA transformer, XRM-24 (XRM-24E for MS-5024UDE), is available to provide maximum accessory power (6.6
Standard
Transformer
amps maximum).
1.5.4 Batteries
The cabinet provides space for 7 Amp Hour batteries (for 12 Amp Hour up to 18 Amp Hour batteries, use the listed BB-17F battery box). Batter­ies must be ordered separately.
Optional
Transformer
XRM-24(E)
1.6 Optional Devices
1.6.1 RM-5F Five-Zone Relay Module
The RM-5F option module provides five Form-C relays which track zones 1 through 5. The module mounts to con­nector J7 on the lower right side of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and Figure 2-16 on page 31.
1.6.2 CAC-5F Class A Converter Module
The CAC-5F Class A Converter module converts the Style B (Class B) Initiating Device Circuits to Style D (Class A). The CAC-5F mounts to terminal block TB2, located in the upper center of the main circuit board. The remov­able terminal block on the CAC-5F module provides for ease of wiring. Refer to Figure 2-17, “CAC-5F Style D Con­verter,” on page 32
1.6.3 ADM-24 Annunciator Driver Module
The ADM-24 Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is supervised for open circuits by this module. The Annunciator Driver Module mounts to connector J3 in the upper right corner of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and Figure 2-11 on page
28.
1.6.4 RZA-5F Remote Annunciator
The RZA-5F Remote Annunciator mounts on a standard single-gang box and provides LED indication of the following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• Alarm Zone 5 (red)
• System Trouble (yellow)
A Local Trouble Sounder and Tone Silence Switch are also provided. All LEDs and their wiring are supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit an easy change of zone information. Refer to Figure 2-12, “RZA-5F,” on page 28, Figure 2-13 on page 29 and Figure 2-14 on page 29. Note that the Remote Annunciator requires the use of the ADM-24 Annunciator Driver Module.
Document #15140 Rev.G 01/02/02 P/N 15140:G
15
Page 16
Specifications
1.6.5 PRT-24 Printer Interface Module
The Printer Interface Module may be used to connect a printer to the control panel for the purpose of printing a his­tory report, walktest file, troubleshoot report, program entries or current system status. Printers require separate external primary power. Connect the PRT-24 module (with cable) to the serial EIA-232 port on the printer. The module mounts to the J2 connector on the main circuit board. Note that an EDP listed printer must be used if the
printer will be permanently attached to the control panel. Refer to Figure 2-15, “Remote Printer Connections,” on page 30.
1.6.6 DP-5024UD Dress Panel
A red dress panel is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. Refer to Figure 1-1, “Optional DP-5024UD,” on page 11.
1.6.7 BB-17F Battery Box
The BB-17F battery box may be used to house two batteries, from 12 Amp Hour to 18 Amp Hour. The battery box mounts directly below the cabinet and main circuit board. Refer to Figure 2-3, “Backbox and Battery Box,” on page
21. The BB-17F is red and is provided with knockouts.
1.6.8 PK-5024UD Programming Kit
This kit includes one 3½" diskette plus Instruction Manual P/N 50041. When the software is loaded into an IBM compatible computer, it creates an off-line Service Terminal that allows any MS-5024UD panel to be uploaded or downloaded over standard telephone lines.
1.7 Specifications
AC Power - TB1
MS-5024UD: 120 VAC, 60 Hz, 2.3 amps MS-5024UDE: 220/240 VAC, 50 Hz, 1.2 amps Wire size: minimum #14 AWG (2 mm
Battery (lead acid only) - J1
Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.8 amp Maximum Charger Capacity: 17 Amp Hour battery. (MS-5024UD cabinet holds maximum 7 Amp Hour battery. Larger batteries require Fire•Lite BB-17F or other UL listed battery cabinet).
Initiating Device Circuits - TB2
Detector Zones 1, 2, 3, 4, 5 Power-limited Circuitry Operation: All zones are NFPA Style B, Zone 3 is NFPA Style B or Style D. Use CAC-5F module for Style D operations Normal Operating Voltage: 24 VDC (ripple = 100 mV maximum) Alarm Current: 26 mA Short Circuit Current: 42 mA maximum Maximum Loop Resistance: 100 ohms End-of-Line Resistor: 4.7K ohms, ½ watt (P/N 27072 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current) Smoke Detector Identifier A Refer to Fire•Lite Device Compatibility Document for listed compatible devices
2
) with 600V insulation
16
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 17
Specifications
Notification Appliance Circuits - TB5 & TB6
Nonregulated, special purpose power, Styles Y and Z supported Power-limited circuitry Operating Voltage: Nominal 24 volts Current for all external devices: 3.0 amps expandable to 5.6 amps Current-limit: PTC Maximum signaling current/circuit: 2.5 amps End-of-Line resistor: 4.7K ohms, ½ watt (P/N 71252 UL listed) for NACs Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Alarm and Trouble Relays - TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Alarm and Trouble: Form-C power-limited circuitry (see Figure 2-7 note for power-limited wiring application)
Auxiliary Outputs - TB4, Terminals 5 & 6
TB4-5 Supervisory Relay Driver: Normally high, active low, sinks up to 40 mA TB4-6 Communication Failure: Normally high, active low, sinks up to 40 mA Power-limited circuitry
Four-wire Smoke Detector Power - TB4, Terminals 3(+) & 4(-)
Maximum ripple voltage: 10 mV
RMS
Operating voltage: Nominal 24 volts Up to 300 mA is available for powering 4-wire smoke detectors Power-limited circuitry Recommended maximum standby current is 50 mA (see Battery Calculations in Appendix A) Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Nonresettable Filtered 24V Power - TB4 Terminals 1(+) & 2(-)
Maximum ripple voltage: 10 mV
RMS
Operating voltage: Nominal 24 volts Total DC current available from this output is up to 300 mA Power-limited circuitry Recommended maximum standby current is 150 mA (see Battery Calculations in Appendix A) Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Notes:
For power supply calculations, refer to Appendix A.
1.
Total current for nonresettable power, 4-wire smoke detector power and two Notification Appliance Circuits
2.
must not exceed 5.6 amps. Total external system current in excess of 3.6 amps requires the XRM-24 Trans­former (XRM-24E for 220/240 VAC applications) and 12 Amp Hour or 17 Amp Hour batteries.
Document #15140 Rev.G 01/02/02 P/N 15140:G
17
Page 18
Telephone Requirements and Warnings
1.8 Telephone Requirements and Warnings
1.8.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 1.3B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be con­nected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
1.8.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. The following information is provided if required by the local telephone company:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
Product Model Number: MS-5024UD
FCC Registration Number: 1W6USA-20004-AL-E
Ringer Equivalence 1.3B
Note: The FCC ID label is located on the inside of the control panel door
1.8.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone sys­tem at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
18
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 19
Installation
CHAPTER 2 Installation
2.1 Mounting Options
FIGURE 2-1:
MS-5024UD Cabinet
The cabinet may be either surface mounted or semi-flush mounted using the optional Trim Ring P/N: TR-1-R. The door is removable during the installation period by opening and lifting the door off the hinges. The cabinet mounts using two key slots and two additional 0.25" (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approxi­mately five feet above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the required conductors into the box. Note that there are no knockouts on the left (hinged) side of the cabinet. All wir­ing should be in accordance with the National and/or Local codes for fire alarm systems.
2.2 Backbox Mounting
Open the door and lift the door off the pin hinges
Remove the main PC board assembly by unscrewing the four screws in the corners of the board. Two standoffs support the board in the center. Set the board aside in a safe, clean place. Avoid static dis­charge which may damage the board.
Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown
Install two upper fasteners in the wall with the screw heads protruding
Using the proper 'keyholes', mount the backbox over the two screws
Mark and drill the lower two holes
Mount backbox, install remaining fasteners and tighten
When the location is dry and free of construction dust, reinstall the main PC board
Document #15140 Rev.G 01/02/02 P/N 15140:G
19
Page 20
Backbox Mounting
FIGURE 2-2:
Height=15.000”
(38.10 cm)
Cabinet Dimensions and Knockout Locations
2.875” (7.3 cm)
Draw wires through the respective knockout locations.
Backbox = 14.5”
(36.8 cm)
0.75”(1.9 cm)
9.1” (23.1 cm)
10.375”
(26.35 cm)
Top
Depth = 3.000”
(7.62 cm)
2.7”
(6.86cm)
Bottom
TR-1-R Trim Ring
Backbox Mounting Holes
ms2-4cab.cdr
1.125” (2.868 cm)
20
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 21
Backbox Mounting
FIGURE 2-3:
Door = 15.342“ (38.97 cm)
Backbox and Battery Box
To p
Door = 14.677 “ (37.28 cm)
Depth = 2.875" (7.3 cm)
Depth = 3.050“
(7.75 cm)
Bottom
Depth = 4.75 (12.065 cm)
Battery Box = 8.5“ (21.59 cm)
Battery Box = 14.5“ (37.384 cm)
Notes:
Mount the Fire Alarm Control Communicator cabinet to the wall
1.
Remove knockouts on bottom of FACP cabinet and top of BB-17F
2.
Using conduit, hang the BB-17F from the Fire Alarm Control Communicator cabinet, making sure there is at
3.
least ½" of clearance between the two cabinets
Anchor the BB-17F to the wall
4.
Document #15140 Rev.G 01/02/02 P/N 15140:G
21
Page 22
Operating Power
2.3 Operating Power
!
CAUTION: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the MS-5024UD is 120 VAC, 60 Hz, 2.3 amps and for the MS-5024UDE is 220/240 VAC, 50 HZ, 1.2 amps. Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB1 of the main circuit board. As per the National Electric Code, use 14 AWG (2.00 mm may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm one of the transformer mounting studs. Note: Do not use conduit for the Earth Ground connection since this does not
provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J1 on the main circuit board using the plug-in connector provided. The battery charger is current-limited and capable of recharging sealed lead acid type batteries. The charger shuts off when the system is in alarm or if the battery voltage drops too low (below 17.4 VDC). See Appendix A for calculation of the correct battery rating.
2
) or heavier gauge wire with 600V insulation. No other equipment
2
)] to
CAUTION: Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fab-
!
rics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
FIGURE 2-4:
Connect Earth Ground Wire
Operating Power Connections
22
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 23
Input Circuits
2.4 Input Circuits
The control panel has five zone input circuits. The maximum loop resistance limit for each is 100 ohms. All field wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated as well as communicated to a Central Station.
Each zone is a Style B Initiating Device Circuit (IDC) designed to accept any normally open contact device and con­ventional 2-wire, 24 volt smoke detectors. Each zone is power-limited to 7.26 mA in standby and 42 mA in alarm. Zone 3 may also be configured as a Style D Initiating Device Circuit.
Note: All five initiating zones may be converted to Style D (Class A) by using a CAC-5F Class A Converter module. Refer to Figure 2-17, “CAC-5F Style D Converter,” on page 32.
Zones 1-5 may be programmed as listed below. The factory default is 2-wire smoke detector for all zones:
• 2-wire smoke detector (factory default)
• Pull station
• Normally open contact device(s)
• Supervisory
• Supervisory, autoresettable
Zone 3 may also be programmed as:
• Waterflow, silenceable
• Waterflow, nonsilenceable
Note: A maximum of five waterflow devices may be used on zone 3 per NFPA 72.
Four-wire smoke detectors may be connected to any zone. Resettable power is provided via TB4, Terminals 3 and 4.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any zone. This is not recommended, however, since specific and detailed reports will not be possible. For example, the report of general fire alarm versus pull station fire alarm or smoke detector fire alarm.
Refer to the Fire•Lite Device Compatibility Document for a list of compatible smoke detectors.
FIGURE 2-5:
UL listed compatible 2-wire smoke detector
Typical Initiating Device Circuit Connections
Style B Initiating Device Circuit (supervised and power-limited)
4.7K ohm, ½ watt P/N 71252 UL listed
Manual Pull Station
Heat Detector
Style D Initiating Device Circuit (supervised and power-limited)
UL listed compatible 2-wire smoke detector
Manual Pull Station
Heat Detector
MS-5024UD
Dummy load all unused circuits with 4.7K ohm
Document #15140 Rev.G 01/02/02 P/N 15140:G
ELR P/N 71245, across B+ and B-.
23
Page 24
Output Circuits
2.5 Output Circuits
DC Power Output Connections
All DC power outputs are power-limited.
FIGURE 2-6:
Telephone Circuits
Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 (primary) and PH2 (secondary). Telephone line control/command is possible via double line seizure as well as usage of an RJ31X style interconnection. Refer to Figure 2-10, “Wiring Phone Jacks,” on page 27.
Auxiliary Power Connections
Nonresettable Power (300 mA)
24 VDC filtered, nonresettable
power can be obtained from TB4,
Terminals 1(+) and 2(-)
+ - + -
1 2 3 4 5 6
TB4
4-Wire Smoke Detector Power (300 mA)
24 VDC filtered, resettable power for 4-wire
smoke detectors can be obtained from TB4,
Terminals 3(+) and 4(-)
Notification Appliance Circuits
The MS-5024UD provides two NACs (Notification Appliance Circuits) which can be configured as Style Y or Style Z. Each circuit is capable of 2.5 amps of current. Total current drawn from these as will as other DC power outputs cannot exceed 3.6 amps with the standard transformer, 5.6 amps if an optional XRM-24 transformer (XRM-24E for the MS-5024UDE) is installed. Circuits are supervised and power-limited. Refer to the Fire•Lite Device Compatibil­ity Document for a listing of compatible notification appliances.
FIGURE 2-7:
Notification Appliance Circuit Connections
Style Y Notification Appliance Circuit (super-
vised and power-limited). 4.7K ohm, ½ watt
Polarized Bell
Polarized Strobe
Polarized Horn
P/N 71252 UL listed EOL resistor.
Polarized Bell
Polarized Horn
Polarized Horn
Note: Notification Appliance Circuit polarity shown in alarm
state.
Dummy Load all unused circuits P/N 71245
Both Notification Appliance Circuits may be programmed as follows:
• Silenceable
• Nonsilenceable
• Enabled/disabled
• Silence inhibited
• Autosilence, 5 to 30 minutes
• Coded (March Time, Temporal or California)
24
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 25
Output Circuits
Standard Relays
The control panel provides a set of Form-C alarm and a set of Form-C trouble contacts rated for 2.0 amps @ 30VDC (resistive).
Relay Drivers
Relay driver outputs are provided for supervisory and communicator failure. These outputs can be used to drive UL 864 listed remote relays such as the MR-101C and MR-201C.
The control panel's open collector outputs on TB4, terminals 5 and 6 can be used to activate UL 864 listed relays. Outputs are rated for 40 mA. The normal condition for each output is as shown below:
TB4-5 Supervisory Off (deenergized)
TB4-6 Communications Failure Off (deenergized)
Relays must be placed inside the cabinet or in a UL 864 recognized enclosure. Wiring from the control panel's termi­nals on TB4 to the relays must be less than 3 feet in length and enclosed in conduit. Wiring from the relay outputs must remain in the same room as the location of the enclosure and be enclosed in conduit.
FIGURE 2-8:
Auxiliary Relay and Relay Driver Terminals
Relay Connections
Alarm
NO NC C NC NO C
1 2 3 4 5 6
T B 3
Note: The alarm and trouble Form-C dry
contact relays must be power-limited cir­cuits. Any Form-C dry contact relay that
may be used must be wired from TB4 or a
UL listed power-limited power supply.
Trouble
All wiring to relay must
be in same room as panel and in conduit
Relay Driver Connections
Relay energized LED
MR-201/C*
Relay energized LED
DPDT Contacts
10 Amps @ 115 VAC
Connections must be in
the same room as the
panel
DPDT Contacts
10 Amps @ 115 VAC
* The MR-101C and MR-201C include an enclosure.
Document #15140 Rev.G 01/02/02 P/N 15140:G
MR-101/C*
25
Page 26
UL Power-limited Wiring Requirements
2.6 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-5024UD is shown below. Refer to Figure 2-16, “RM-5F Installation and Wiring,” on page 31 for additional information on wiring the RM-5F Relay module.
FIGURE 2-9:
Typical Wiring Diagram for UL Power-limited Requirements
Power-limited Circuits
Power-limited
Circuit
26
Nonpower-limited
Circuit
AC Power
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 27
Digital Communicator
2.7 Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the
panel's digital communicator be located as the first device on the incoming telephone circuit to properly function.
The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone lines is required as shown below.
FIGURE 2-10:
Wiring Phone Jacks
Document #15140 Rev.G 01/02/02 P/N 15140:G
27
Page 28
Optional Boards
2.8 Optional Boards
2.8.1 ADM-24 Annunciator Driver Module
The Annunciator Driver Module supports the RZA-5F Remote Annunciator. Annunciator wiring is supervised for open conditions by this module. The Annunciator Driver Module mounts to J3 in the upper right corner of the main circuit board.
FIGURE 2-11:
ADM-24 Annunciator Driver Module
Main Circuit Board
2.8.2 RZA-5F Remote Annunciator
The RZA-5F mounts on a standard single-gang electrical box and provides LED indication of the following:
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
Connector located on
Standoff
FIGURE 2-12:
back of board
ADM-24
RZA-5F
The remote annunciator provides individual zone alarm LEDs, a system trouble LED, a local piezo sounder and a remote sounder shut off switch. All LEDs and their wiring are supervised for open conditions. Any open condition will cause the System Trou­ble LED to turn on.
Note: The Remote Annunciator requires the use of an ADM-24 Annunciator Driver Module.
28
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 29
Optional Boards
FIGURE 2-13:
Wiring the RZA-5F/ADM-24
ADM-24
+24V
Note: Make wiring connections with system
power off. Maximum wire impedance is 100
ohms per wiring connection.
RZA-5F
FIGURE 2-14:
Installing the Annunciator (Single-Gang Electrical Box)
screw #6-32 x 1.00” LG
Single-gang Box
RZA-5F
Document #15140 Rev.G 01/02/02 P/N 15140:G
29
Page 30
Optional Boards
2.8.3 PRT-24 Printer Interface Module
A remote printer may be permanently or temporarily connected to provide a hardcopy printout of normal current sys­tem status and activity, program entries, history file, troubleshoot mode voltages and walktest data. The PRT-24 pro­vides an EIA-232 conversion to adapt to most 40 and 80 column printers.
CAUTION: DO NOT connect a printer to the Fire Alarm Control Communicator if a ground fault exists on the panel. Circuit damage may result.
!
Installation
Remote printers require separate external primary power. Also required is the PRT-24 which includes the Printer Interface Module and a 6 foot interface cable prewired to a DB25 connector. Connect the interface cable to the PRT­24 as shown in Figure 2-15. Insert the two supplied standoffs into mounting holes near the J2 connector on the main circuit board. Connect the Printer Interface board to J2 on the main circuit board, press onto standoffs and connect the attached cable to the serial EIA-232 port on the printer. The printer may be placed a maximum of 50 feet from the panel. Note that a ground fault may occur on the control panel when this connection is made. For this reason, it is important that there be no preexisting ground fault on the panel. For permanent printer connection, a ground fault is
not allowed.
Printer Configuration
The PRT-24 is required. Also refer to the documentation supplied with your printer. Set the printer's options as listed in the table below.
FIGURE 2-15:
YELLOW
Remote Printer Connections
J1 located on back of PRT-24 board
BLK
RED
GRN
Typical Printer Settings
Under the MENU area:
COMMUNICATION SETUP: DATA BITS: 7 PARITY: EVEN STOP BIT: 1 STOP BAUD RATE: 2400
30
PRT-24 connection to main circuit board
DB-25P Front View
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 31
Optional Boards
2.8.4 RM-5F Five-Zone Relay Module
The RM-5F option module provides five Form-C relays which track zones 1 through 5. The module mounts to con­nector J7 on the lower right side of the main circuit board as illustrated in Figure 2-16.
Nonpower-limited and power-limited wiring must have a minimum distance of 0.25" (6.35 mm) wire to wire. If this module is used to drive nonpower-limited and power-limited circuits:
Skip a set of dry contacts to maintain the 0.25" (6.35mm) required space between power-limited and non-
1.
power-limited circuits. The wiring of this module must follow the requirements as specified above - OR
If this module is needed to drive power-limited and nonpower-limited relays that are next to each other, one
2.
relay must be used as an open circuit and the other as a closed circuit as shown in Figure 2-16.
FIGURE 2-16:
RM-5F Installation and Wiring
Connector located
on back of board
Main Circuit Board
Note: If relays are used as power-limited
circuits, paste supplied label to terminal
block as indicated below.
Power
Limited
RM-5F
Standoffs
Power-limited
Power-limited
Power-limited
No connection No connection
Power-limited
Power-limited
Note: Zone Relay Contact Ratings - Maximum Switched Power is 150 watts or 1250 VA. Maximum Switched Current is 5 Amps UL Rating: 5 Amps @ 30 VDC or 125 VAC, resistive. Contact Material: Silver Alloy
Document #15140 Rev.G 01/02/02 P/N 15140:G
31
Page 32
Optional Boards
2.8.5 CAC-5F Class A Converter Module
The CAC-5F module converts the Style B (Class B) Initiating Device Circuits to Style D (Class A). The CAC-5F mounts to terminal block TB2 located in the upper center of the main circuit board. Refer to Figure 2-17, “CAC-5F Style D Converter,” on page 32. The removable terminal block on the CAC-5F module provides for ease of wiring.
FIGURE 2-17:
UL listed compatible 2-wire smoke detector
Insert two supplied standoffs into CAC-5F circuit board, remove protec­tive paper from self-adhesive base of standoff, install circuit board into TB2
of MS-5024UD and press to adhere
standoffs to cabinet.
CAC-5F Style D Converter
Manual Pull Station
Heat Detector
Waterflow Switch
Waterflow Switch
Waterflow Switch
Dummy load all unused circuits with 4.7K ohm
ELR P/N: 71245 across B+ and B-
CAC-5F Module
32
MS-5024UD Main Circuit Board
Notes:
Circuits 1 through 5 can accommodate 2-wire smoke detectors, plus any normally open contact device such as
1.
heat detectors or manual pull stations.
Only circuit 3 accommodates the nonsilenceable waterflow function.
2.
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 33
Programming Instructions
CHAPTER 3 Programming Instructions
This chapter describes programming the panel from the onboard keyboard. Chapter 7 describes remote site upload/ download which includes programming the control panel on premises. Programming of the control panel is possible at any time except when an alarm condition is present or during a fire drill.
The control panel has been designed for many different types of applications. After examining your specific applica­tion, review the programming options and choose the entries best suited for your system.
The control panel has a built-in intelligent programmer. All programming selections are stored in nonvolatile Electri­cally Erasable Programmable Read-Only Memory (EEPROM). This ensures that the control panel will remember all entries made in programming mode even if both AC and battery power are removed. Invalid entries cause a 'beep' from the onboard piezo sounder.
The user must program the primary and secondary phone numbers, account numbers and 24 hour test report times for each Central Station account and the current time and date. The control panel comes with factory chosen options/fea­tures already programmed. Other options/features may be programmed if desired. If all factory default settings are acceptable, programming is complete.
3.1 Entering Program Mode
To enter the Program Mode, press the MODE key once, (the display will go blank). You then have ten seconds to start entering the Program Mode code 7764.
7764 spells PROG on a Touch-Tone
If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key. Note that as information is entered into the control panel, the digits will scroll across the display from right to left:
___7
__77
_776
7764
A pause of up to 10 seconds is allowed between each number while entering the code. After pressing the [ENTER/ STORE] key, the control panel will be in Program Mode and display 00_F. A maximum of 10 minutes of idle time
is allowed at this point before starting program entries, otherwise, the control panel will return to Normal Mode. A maximum of 10 minutes is allowed between any key stroke. All entries made prior to the 10 minute time-out are valid and will be stored.
Once in Program Mode, the control panel will:
• Blink the trouble LED
• Activate the trouble relay
• Disable the NACs (Notification Appliance Circuits)
• Disable the alarm relay
•Display 00_F
• Ignore all other keys other than those mentioned in this section
• Continue to communicate any events not previously acknowledged at a Central Station prior to entering Program Mode
®
phone.
Document #15140 Rev.G 01/02/02 P/N 15140:G
33
Page 34
Switch Functions
Note that address location 56 is factory defaulted to '0' for 'control panel only.' This keeps the communicator off until location 56 is changed to '1' for 'slave communicator' or '2' for 'panel/communicator.' Once location 56 is set to '1' or '2' and a valid phone number is entered, entry into the Program Mode will cause transmission of the 'system off nor­mal' report.
When viewing any address in Program Mode, the first three digits on the left of the display represent the memory address which can be 00 to 374 (alpha-characters are not used). The last digit, farthest right, represents the contents of the memory address. The first address and contents displayed upon entering Program Mode are shown below:
00_F
(address)(data)
3.2 Switch Functions
The function of each keypad key in Program Mode is shown below.
FIGURE 3-1:
No function in
Program Mode
Control Panel Keypad
Address entry keys are 0 - 9
Data entry keys are 0 - 9 and
A - F
Select operating mode
Increment memory address
Decrement memory address
One press = first memory address
Two presses = type any address
Save data, go to next address
3.3 Programming Options
Primary Central Station Phone Number (00-15)
The first sixteen addresses (00-15) are factory set to 'F' (00_F to 15_F). Programming this feature is typically done as follows: If the phone number to be entered is 484-7161, press 4. The display will read 00_4. Press [ENTER/ STORE] to save the entry to memory and increment to the next address 01_F.
Enter the remaining numbers in their respective addresses as shown below:
Phone Number
Addresses
34
4847161FFFFFFFFF
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 35
Programming Options
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers and the alpha-characters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = 3-second pause
E = 5-second pause
F = end of phone number (Note: F must be entered)
Primary Central Station Number Communication Format (16)
One location is needed to select the Communication Format for the primary phone number. Address 16 is used for this purpose. The default (factory setting) for this address is 'E' for Ademco Contact ID format. '0' through 'E' may be entered in place of the default entry. After making the selection, press the [ENTER/STORE] key to store the selec­tion. The available format options are as follows:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Ademco Contact ID, DTMF, 1400/2300 ACK
F: Not Used
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format cho­sen, the control panel automatically programs all of the event codes. Refer to Table 3-1 through Table 3-5 .
Document #15140 Rev.G 01/02/02 P/N 15140:G
35
Page 36
Programming Options
3+1, 4+1 Express, 4+1 Standard and Expanded & 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 16, the following data is automatically programmed for the Pri­mary Central Station phone number event codes. Enter '0' for the Setting to disable the report.
TABLE 3-1:
Primary Event Codes - 3+1, 4+1 Express, 4+1 Standard, Expanded & 4+2 Expanded
Address Description Setting
127 Primary # Zone 1 Alarm Code 1 128 Primary # Zone 2 Alarm Code 1 129 Primary # Zone 3 Alarm Code 1 130 Primary # Zone 4 Alarm Code 1 131 Primary # Zone 5 Alarm Code 1 132 Primary # Zone 1 Disable Code F 133 Primary # Zone 2 Disable Code F 134 Primary # Zone 3 Disable Code F 135 Primary # Zone 4 Disable Code F 136 Primary # Zone 5 Disable Code F 137 Primary # Drill Code 9 138 Primary # AC Fault Code F 139 Primary # Zone 1 Fault Code F 140 Primary # Zone 2 Fault Code F 141 Primary # Zone 3 Fault Code F 142 Primary # Zone 4 Fault Code F 143 Primary # Zone 5 Fault Code F 144 Primary # Earth Fault Code F 145 Primary # Low Battery Fault Code F 146 Primary # No Battery Fault Code F 147 Primary # Telco Primary Line Fault Code F 148 Primary # Telco Secondary Line Fault Code F 149 Primary # NAC #1 Fault Code F 150 Primary # NAC #2 Fault Code F 151 Primary # Communication Trouble Primary # Code F 152 Primary # Communication Trouble Secondary # Code F 153 Primary # Annunciator Fault Code F 154 Primary # System Off Normal Code F 155 Primary # Zone 1 Alarm Restore Code E 156 Primary # Zone 2 Alarm Restore Code E 157 Primary # Zone 3 Alarm Restore Code E 158 Primary # Zone 4 Alarm Restore Code E 159 Primary # Zone 5 Alarm Restore Code E 160 Primary # Zone 1 Disable Restore Code E 161 Primary # Zone 2 Disable Restore Code E 162 Primary # Zone 3 Disable Restore Code E 163 Primary # Zone 4 Disable Restore Code E 164 Primary # Zone 5 Disable Restore Code E 165 Primary # Drill Restore Code 9 166 Primary # AC Fault Restore Code E 167 Primary # Zone 1 Fault Restore Code E 168 Primary # Zone 2 Fault Restore Code E 169 Primary # Zone 3 Fault Restore Code E 170 Primary # Zone 4 Fault Restore Code E 171 Primary # Zone 5 Fault Restore Code E 172 Primary # Earth Fault Restore Code E 173 Primary # Low Battery Fault Restore Code E 174 Primary # No Battery Fault Restore Code E 175 Primary # Telco Primary Line Fault Restore Code E 176 Primary # Telco Secondary Line Fault Restore Code E 177 Primary # NAC # 1 Fault Restore Code E 178 Primary # NAC # 2 Fault Restore Code E 179 Primary # Communication Trouble Primary # Restore Code E 180 Primary # Communication Trouble Secondary # Restore Code E 181 Primary # Annunciator Fault Restore Code E 182 Primary # System Off Normal Restore Code E 183 Primary # System Test Report 9 184 Primary # System Abnormal Test Report F 185 Primary # Request for Upload/Download 7 186 Primary # Successful Upload 7 187 Primary # Successful Download 7 188 Primary # Failed Upload/Download 7
36
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 37
Programming Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' is entered for address 16, the following data is automatically programmed for the Primary Central Sta­tion phone number event codes. Enter '00' for the Setting to disable the report.
TAB LE 3- 2:
Primary Event Codes - 4+2 Standard and 4+2 Express
Address Description Setting
127 - 128 Primary # Zone 1 Alarm Code 11 129 - 130 Primary # Zone 2 Alarm Code 12 131 - 132 Primary # Zone 3 Alarm Code 13 133 - 134 Primary # Zone 4 Alarm Code 14 135 - 136 Primary # Zone 5 Alarm Code 15 137 - 138 Primary # Zone 1 Disable Code F1 139 - 140 Primary # Zone 2 Disable Code F2 141 - 142 Primary # Zone 3 Disable Code F3 143 - 144 Primary # Zone 4 Disable Code F4 145 - 146 Primary # Zone 5 Disable Code F5 147 - 148 Primary # Drill Code 97 149 - 150 Primary # AC Fault Code F6 151 - 152 Primary # Zone 1 Fault Code F1 153 - 154 Primary # Zone 2 Fault Code F2 155 - 156 Primary # Zone 3 Fault Code F3 157 - 158 Primary # Zone 4 Fault Code F4 159 - 160 Primary # Zone 5 Fault Code F5 161 - 162 Primary # Earth Fault Code F7 163 - 164 Primary # Low Battery Fault Code F8 165 - 166 Primary # No Battery Fault Code F9 167 - 168 Primary # Telco Primary Line Fault Code FA 169 - 170 Primary # Telco Secondary Line Fault Code FB 171 - 172 Primary # NAC #1 Fault Code FC 173 - 174 Primary # NAC #2 Fault Code FC 175 - 176 Primary # Communication Trouble Primary # Code FD 177 - 178 Primary # Communication Trouble Secondary # Code FE 179 - 180 Primary # Annunciator Fault Code FC 181 - 182 Primary # System Off Normal Code FF 183 - 184 Primary # Zone 1 Alarm Restore Code E1 185 - 186 Primary # Zone 2 Alarm Restore Code E2 187 - 188 Primary # Zone 3 Alarm Restore Code E3 189 - 190 Primary # Zone 4 Alarm Restore Code E4 191 - 192 Primary # Zone 5 Alarm Restore Code E5 193 - 194 Primary # Zone 1 Disable Restore Code E1 195 - 196 Primary # Zone 2 Disable Restore Code E2 197 - 198 Primary # Zone 3 Disable Restore Code E3 199 - 200 Primary # Zone 4 Disable Restore Code E4 201 - 202 Primary # Zone 5 Disable Restore Code E5 203 - 204 Primary # Drill Restore Code 98 205 - 206 Primary # AC Fault Restore Code E6 207 - 208 Primary # Zone 1 Fault Restore Code E1 209 - 210 Primary # Zone 2 Fault Restore Code E2 211 - 212 Primary # Zone 3 Fault Restore Code E3 213 - 214 Primary # Zone 4 Fault Restore Code E4 215 - 216 Primary # Zone 5 Fault Restore Code E5 217 - 218 Primary # Earth Fault Restore Code E7 219 - 220 Primary # Low Battery Fault Restore Code E8 221 - 222 Primary # No Battery Fault Restore Code E9 223 - 224 Primary # Telco Primary Line Fault Restore Code EA 225 - 226 Primary # Telco Secondary Line Fault Restore Code EB 227 - 228 Primary # NAC # 1 Fault Restore Code EC 229 - 230 Primary # NAC # 2 Fault Restore Code EC 231 - 232 Primary # Communication Trouble Primary # Restore Code ED 233 - 234 Primary # Communication Trouble Secondary # Restore Code EE 235 - 236 Primary # Annunciator Fault Restore Code EC 237 - 238 Primary # System Off Normal Restore Code EF 239 - 240 Primary # System Test Report 99 241 - 242 Primary # System Abnormal Test Report 91 243 - 244 Primary # Request for Upload/Download 71 245 - 246 Primary # Successful Upload 72 247 - 248 Primary # Successful Download 73 249 - 250 Primary # Failed Upload/Download 74
Document #15140 Rev.G 01/02/02 P/N 15140:G
37
Page 38
Programming Options
Ademco Contact ID Format
If 'E' is entered for address 16 in Program Mode Level 1, the data shown in Table 3-3 is automatically pro­grammed for the Primary Central Station phone number event codes. Enter '000' for the setting to disable the report. The Setting entry is programmable, the Zone Number cannot be changed. Restoral code settings match the settings shown with the addition of an 'R' code transmitted. Refer to page 83 for additional information.
TABLE 3-3:
Address Description Setting Zone No.
Event Codes, Primary Central Station Number
127-129 Primary # Zone 1 Alarm Code 111 001 130-132 Primary # Zone 2 Alarm Code 111 002 133-135 Primary # Zone 3 Alarm Code 111 003 136-138 Primary # Zone 4 Alarm Code 111 004 139-141 Primary # Zone 5 Alarm Code 111 005 142-144 Primary # Zone 1 Disabled Code 570 001 145-147 Primary # Zone 2 Disabled Code 570 002 148-150 Primary # Zone 3 Disabled Code 570 003 151-153 Primary # Zone 4 Disabled Code 570 004 154-156 Primary # Zone 5 Disabled Code 570 005 157-159 Primary # Drill Code 604 000 160-162 Primary # AC Fault Code 301 000 163-165 Primary # Zone 1 Fault Code 380 001 166-168 Primary # Zone 2 Fault Code 380 002 169-171 Primary # Zone 3 Fault Code 380 003 172-174 Primary # Zone 4 Fault Code 380 004 175-177 Primary # Zone 5 Fault Code 380 005 178-180 Primary # Earth Fault Code 310 000 181-183 Primary # Low Battery Fault Code 302 000 184-186 Primary # No Battery Fault Code 311 000 187-189 Primary # Telco Primary Line Fault Code 351 000 190-192 Primary # Telco Secondary Line Fault Code 352 000 193-195 Primary # NAC #1 Fault Code 321 001 196-198 Primary # NAC #2 Fault Code 322 002 199-201 Primary # Comm Trouble Primary # Code 354 001 202-204 Primary # Comm Trouble Secondary # Code 354 002 205-207 Primary # Annunciator Fault Code 330 000 208-210 Primary # System Off Normal Code 308 000 211-213 Primary # System Test Message 602 000 214-216 Primary # System Abnormal Test Message 608 000 217-219 Primary # Upload/Download Request Code 411 000 220-222 Primary # Upload Successful Code 416 000 223-225 Primary # Download Successful Code 412 000 226-228 Primary # Upload/Download Failed Code 413 000
38
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 39
Programming Options
Primary Central Station Number Account Code (17-20)
A unique account code is provided by the Central Station. Four locations at addresses 17-20 (factory default settings of all '0s') are used to enter the account code. Valid entries are 0 to 9 and A to F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 16, enter the three digit account code supplied by the Central Station (location 20 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C or D' into address 16, enter the four digit account code supplied by the Central Station.
Primary Central Station Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four loca­tions, from addresses 21-24. The default is '2345' (11:45 PM). The limits for each address location are as follows:
21 - enter 0-2
22 - enter 0-9
23 - enter 0-5
24 - enter 0-9
Do not use 'A-F'
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (25)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter '1' for 12 hours, '2' for 8 hours or '3' for 6 hours.
Secondary Central Station Phone Number (26-41)
Addresses (26-41) are factory set to 'F' (26_F to 41_F). Programming this feature is typically done as follows: If the phone number to be entered is 484-7161, press 4. The display will read 26_4. Press [ENTER/STORE] to save the entry to memory and increment to the next address 27_F.
Enter the remaining numbers in their respective addresses as shown below:
Phone Number
Addresses
4847161FFFFFFFFF
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers and the alpha-characters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = 3-second pause
E = 5-second pause
F = end of phone number (Note: F must be entered)
Document #15140 Rev.G 01/02/02 P/N 15140:G
39
Page 40
Programming Options
Secondary Central Station Number Communication Format (42)
One location is needed to select the Communication Format for the secondary phone number. Address 42 is used for this purpose. The default (factory setting) for this address is 'E' for Ademco Contact ID format. Selections '0' through 'E' may be entered in place of the default entry. After making the selection, press the [ENTER/STORE] key to store the selection. The available format options are as follows:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Ademco Contact ID, DTMF, 1400/2300 ACK
F: Not Used
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format cho­sen, the control panel automatically programs all of the event codes. Refer to Table 3-1 through Table 3-5 .
40
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 41
Programming Options
3+1, 4+1 Express, 4+1 Standard and Expanded & 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 42, the following data is automatically programmed for the Secondary Central Station phone number event codes. Enter '0' for the Setting to disable the report.
TAB LE 3- 4:
Secondary Event Codes-3+1, 4+1 Express, 4+1 Standard, Expanded & 4+2 Expanded
Address Description Setting
251 Secondary # Zone 1 Alarm Code 1 252 Secondary # Zone 2 Alarm Code 1 253 Secondary # Zone 3 Alarm Code 1 254 Secondary # Zone 4 Alarm Code 1 255 Secondary # Zone 5 Alarm Code 1 256 Secondary # Zone 1 Disable Code F 257 Secondary # Zone 2 Disable Code F 258 Secondary # Zone 3 Disable Code F 259 Secondary # Zone 4 Disable Code F 260 Secondary # Zone 5 Disable Code F 261 Secondary # Drill Code 9 262 Secondary # AC Fault Code F 263 Secondary # Zone 1 Fault Code F 264 Secondary # Zone 2 Fault Code F 265 Secondary # Zone 3 Fault Code F 266 Secondary # Zone 4 Fault Code F 267 Secondary # Zone 5 Fault Code F 268 Secondary # Earth Fault Code F 269 Secondary # Low Battery Fault Code F 270 Secondary # No Battery Fault Code F 271 Secondary # Telco Primary Line Fault Code F 272 Secondary # Telco Secondary Line Fault Code F 273 Secondary # NAC #1 Fault Code F 274 Secondary # NAC #2 Fault Code F 275 Secondary # Communication Trouble Primary # Code F 276 Secondary # Communication Trouble Secondary # Code F 277 Secondary # Annunciator Fault Code F 278 Secondary # System Off Normal Code F 279 Secondary # Zone 1 Alarm Restore Code E 280 Secondary # Zone 2 Alarm Restore Code E 281 Secondary # Zone 3 Alarm Restore Code E 282 Secondary # Zone 4 Alarm Restore Code E 283 Secondary # Zone 5 Alarm Restore Code E 284 Secondary # Zone 1 Disable Restore Code E 285 Secondary # Zone 2 Disable Restore Code E 286 Secondary # Zone 3 Disable Restore Code E 287 Secondary # Zone 4 Disable Restore Code E 288 Secondary # Zone 5 Disable Restore Code E 289 Secondary # Drill Restore Code 9 290 Secondary # AC Fault Restore Code E 291 Secondary # Zone 1 Fault Restore Code E 292 Secondary # Zone 2 Fault Restore Code E 293 Secondary # Zone 3 Fault Restore Code E 294 Secondary # Zone 4 Fault Restore Code E 295 Secondary # Zone 5 Fault Restore Code E 296 Secondary # Earth Fault Restore Code E 297 Secondary # Low Battery Fault Restore Code E 298 Secondary # No Battery Fault Restore Code E 299 Secondary # Telco Primary Line Fault Restore Code E 300 Secondary # Telco Secondary Line Fault Restore Code E 301 Secondary # NAC # 1 Fault Restore Code E 302 Secondary # NAC # 2 Fault Restore Code E 303 Secondary # Communication Trouble Primary # Restore Code E 304 Secondary # Communication Trouble Secondary # Restore Code E 305 Secondary # Annunciator Fault Restore Code E 306 Secondary # System Off Normal Restore Code E 307 Secondary # System Test Report 9 308 Secondary # System Abnormal Test Report F 309 Secondary # Request for Upload/Download 7 310 Secondary # Successful Upload 7 311 Secondary # Successful Download 7 312 Secondary # Failed Upload/Download 7
Document #15140 Rev.G 01/02/02 P/N 15140:G
41
Page 42
Programming Options
4+2 Standard and 4+2 Express Formats
If '1, A or C' is entered for address 42, the following data is automatically programmed for the Secondary Central Sta­tion phone number event codes. Enter '00' for the Setting to disable the report.
TABLE 3-5:
Secondary Event Codes - 4+2 Standard and 4+2 Express
Address Description Setting
251 - 252 Secondary # Zone 1 Alarm Code 11 253 - 254 Secondary # Zone 2 Alarm Code 12 255 - 256 Secondary # Zone 3 Alarm Code 13 257 - 258 Secondary # Zone 4 Alarm Code 14 259 - 260 Secondary # Zone 5 Alarm Code 15 261 - 262 Secondary # Zone 1 Disable Code F1 263 - 264 Secondary # Zone 2 Disable Code F2 265 - 266 Secondary # Zone 3 Disable Code F3 267 - 268 Secondary # Zone 4 Disable Code F4 269 - 270 Secondary # Zone 5 Disable Code F5 271 - 272 Secondary # Drill Code 97 273 - 274 Secondary # AC Fault Code F6 275 - 276 Secondary # Zone 1 Fault Code F1 277 - 278 Secondary # Zone 2 Fault Code F2 279 - 280 Secondary # Zone 3 Fault Code F3 281 - 282 Secondary # Zone 4 Fault Code F4 283 - 284 Secondary # Zone 5 Fault Code F5 285 - 286 Secondary # Earth Fault Code F7 287 - 288 Secondary # Low Battery Fault Code F8 289 - 290 Secondary # No Battery Fault Code F9 291 - 292 Secondary # Telco Primary Line Fault Code FA 293 - 294 Secondary # Telco Secondary Line Fault Code FB 295 - 296 Secondary # NAC #1 Fault Code FC 297 - 298 Secondary # NAC #2 Fault Code FC 299 - 300 Secondary # Communication Trouble Primary # Code FD 301 - 302 Secondary # Communication Trouble Secondary # Code FE 303 - 304 Secondary # Annunciator Fault Code FC 305 - 306 Secondary # System Off Normal Code FF 307 - 308 Secondary # Zone 1 Alarm Restore Code E1 309 - 310 Secondary # Zone 2 Alarm Restore Code E2 311 - 312 Secondary # Zone 3 Alarm Restore Code E3 313 - 314 Secondary # Zone 4 Alarm Restore Code E4 315 - 316 Secondary # Zone 5 Alarm Restore Code E5 317 - 318 Secondary # Zone 1 Disable Restore Code E1 319 - 320 Secondary # Zone 2 Disable Restore Code E2 321 - 322 Secondary # Zone 3 Disable Restore Code E3 323 - 324 Secondary # Zone 4 Disable Restore Code E4 325 - 326 Secondary # Zone 5 Disable Restore Code E5 327 - 328 Secondary # Drill Restore Code 98 329 - 330 Secondary # AC Fault Restore Code E6 331 - 332 Secondary # Zone 1 Fault Restore Code E1 333 - 334 Secondary # Zone 2 Fault Restore Code E2 335 - 336 Secondary # Zone 3 Fault Restore Code E3 337 - 338 Secondary # Zone 4 Fault Restore Code E4 339 - 340 Secondary # Zone 5 Fault Restore Code E5 341 - 342 Secondary # Earth Fault Restore Code E7 343 - 344 Secondary # Low Battery Fault Restore Code E8 345 - 346 Secondary # No Battery Fault Restore Code E9 347 - 348 Secondary # Telco Primary Line Fault Restore Code EA 349 - 350 Secondary # Telco Secondary Line Fault Restore Code EB 351 - 352 Secondary # NAC # 1 Fault Restore Code EC 353 - 354 Secondary # NAC # 2 Fault Restore Code EC 355 - 356 Secondary # Communication Trouble Primary # Restore Code ED 357 - 358 Secondary # Communication Trouble Secondary # Restore Code EE 359 - 360 Secondary # Annunciator Fault Restore Code EC 361 - 362 Secondary # System Off Normal Restore Code EF 363 - 364 Secondary # System Test Report 99 365 - 366 Secondary # System Abnormal Test Report 91 367 - 368 Secondary # Request for Upload/Download 71 369 - 370 Secondary # Successful Upload 72 371 - 372 Secondary # Successful Download 73 373 - 374 Secondary # Failed Upload/Download 74
42
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 43
Programming Options
Ademco Contact ID Format
If 'E' is entered for address 42 in Program Mode Level 1, the data shown in Table 3-6 is automatically pro­grammed for the Secondary Central Station phone number event codes. Enter '000' for the setting to disable the report. The Setting entry is programmable, the Zone Number cannot be changed. Restoral code settings match the settings shown with the addition of an 'R' code transmitted. Refer to page 83 for additional information.
TAB LE 3- 6:
Address Description Setting Zone No.
Event Codes, Secondary Central Station Number
251-253 Secondary # Zone 1 Alarm Code 111 001 254-256 Secondary # Zone 2 Alarm Code 111 002 257-259 Secondary # Zone 3 Alarm Code 111 003 260-262 Secondary # Zone 4 Alarm Code 111 004 263-265 Secondary # Zone 5 Alarm Code 111 005 266-268 Secondary # Zone 1 Disabled Code 570 001 269-271 Secondary # Zone 2 Disabled Code 570 002 272-274 Secondary # Zone 3 Disabled Code 570 003 275-277 Secondary # Zone 4 Disabled Code 570 004 278-280 Secondary # Zone 5 Disabled Code 570 005 281-283 Secondary # Drill Code 604 000 284-286 Secondary # AC Fault Code 301 000 287-289 Secondary # Zone 1 Fault Code 380 001 290-292 Secondary # Zone 2 Fault Code 380 002 293-295 Secondary # Zone 3 Fault Code 380 003 296-298 Secondary # Zone 4 Fault Code 380 004 299-301 Secondary # Zone 5 Fault Code 380 005 302-304 Secondary # Earth Fault Code 310 000 305-307 Secondary # Low Battery Fault Code 302 000 308-310 Secondary # No Battery Fault Code 311 000 311-313 Secondary # Telco Primary Line Fault Code 351 000 314-316 Secondary # Telco Secondary Line Fault Code 352 000 317-319 Secondary # NAC #1 Fault Code 321 001 320-322 Secondary # NAC #2 Fault Code 322 002 323-325 Secondary # Comm Trouble Primary # Code 354 001 326-328 Secondary # Comm Trouble Secondary # Code 354 002 329-331 Secondary # Annunciator Fault Code 330 001 332-334 Secondary # System Off Normal Code 308 000 335-337 Secondary # System Test Message 602 000 338-340 Secondary # System Abnormal Test Message 608 000 341-343 Secondary # Upload/Download Request Code 411 000 344-346 Secondary # Upload Successful Code 416 000 347-349 Secondary # Download Successful Code 412 000 350-352 Secondary # Upload/Download Failed Code 413 000
Document #15140 Rev.G 01/02/02 P/N 15140:G
43
Page 44
Programming Options
Secondary Central Station Number Account Code (43-46)
A unique account code is provided by the Central Station. Four locations at addresses 43-46 (factory default settings of all '0s') are used to enter the account code. Valid entries are 0 to 9 and A to F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 42, enter the three digit account code supplied by the Central Station (location 46 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C or D' into address 42, enter the four digit account code supplied by the Central Station.
Secondary Central Station Number 24 Hour Test Time (47-50)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 2 takes up four loca­tions, from addresses 47-50. The default is '0000' (12:00 midnight). The limits for each location are as follows:
47 - enter 0-2
48 - enter 0-9
49 - enter 0-5
50 - enter 0-9
Do not use 'A-F'
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (51)
The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter '1' for 12 hours, '2' for 8 hours or '3' for 6 hours.
Alarm Verification (52)
Alarm verification works only on zones programmed as 2-wire smoke detector zones. After detecting an alarm, the panel removes power from all zones for six seconds, resetting all 2-wire smoke detectors. Power is reapplied and a 12 second retard period allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent alarms by the same initiating zone are ignored. An alarm detected on any other 2-wire detector zone during the retard period will cause immediate verified alarms. A subsequent alarm on the initiating zone occurring within the confirmation time will cause a verified alarm. Note: Mixing devices on zones designated as 2-wire smoke zones is not
recommended.
During the alarm verification period, access to other modes of operation is prevented.
FIGURE 3-2:
Detector Alarm Verification
Detector Zone Goes Into Alarm
Different Detector Zone Alarms
Verification Timing Diagram
0 Sec.
6 Sec.
RESET RETARD
Alarm Ignored
18 Sec.
0
ALARM VERIFICATION PERIOD
Control Panel Processes Alarm if Same Detector Zone if Still in Alarm
CONFIRMATION TIME
30
Control Panel Immediately Processes Alarm
9060
120 Sec.
120
Factory default selection is no verification which is a '0' entry. Entering a '1' enables alarm verification. Note: Con­sult local Authority Having Jurisdiction (AHJ) prior to altering this address.
Future Use (53-55)
Slave Communicator/Fire Panel Selection (56)
Leaving address 56 at '0' causes the control panel to operate as a fire panel only. Selecting '1' will make it operate as a slave communicator only. Selecting '2' will make it operate as a fire panel/communicator.
44
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 45
Programming Options
Zones 1-5 Function Selection (57-61)
The five zones on the control panel may be programmed as shown below. Program entries alter zone function and transmittal priority.
When using Ademco Contact ID format, Zone Alarm and Zone Restoral event codes change automatically as shown in Table 3-7 . Be certain to reprogram alarm event codes when selecting process monitoring functions. Zone fault and disable event codes may also be user reprogrammed (refer to “Ademco Contact ID Format Event Code Descrip­tions” on page 83).
TABLE 3-7:
Program Entry Function
1. Ademco Contact ID format selection causes Event Codes to automatically change to values shown in Table 3-7 .
Zone Function Selection
Zone Alarm/Restoral1
Event Code
0 Operates 2-wire smoke detectors 111 1 Pull station 115 2 Normally open contact device 110 3 Supervisory 200 4 Supervisory autoresettable - self restore function, is not latched by the
control panel 200
5 Waterflow silenceable - silencing of silenceable NACs allowed (affects
zone 3 only) 113
6 Waterflow nonsilenceable - silencing of silenceable NACs is not allowed.
Must clear waterflow alarm condition and press the reset key (affects zone 3 only) 113
Zone 1 Function Selection (57)
Factory default for zone 1 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 2 Function Selection (58)
Factory default for zone 2 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 3 Function Selection (59)
Factory default for zone 3 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact device; '3' for supervisory; '4' for supervisory autoresettable; '5' for waterflow silenceable; '6' for waterflow nonsilenceable.
Zone 4 Function Selection (60)
Factory default for zone 4 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 5 Function Selection (61)
Factory default for zone 5 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact device; '3' for supervisory; '4' for supervisory autoresettable.
Note: Programming any zone to function as supervisory or supervisory autoresettable will cause the defaulted event codes (see notes in Table 3-1 through Table 3-5 ) to be automatically changed. The defaulted code of '1' is changed to '8' for formats 3+1 and 4+1 Standard and Expanded, 4+2 Expanded and 4+1 Express. The defaulted codes of 11, 12, 13, 14 and 15 are changed to 81, 82, 83, 84 and 85 accordingly for formats 4+2 Standard and 4+2 Express.
Waterflow Retard Timer (62-63)
A delay may be added prior to declaring a waterflow type of alarm. Delays up to 89 seconds are allowed. The default for addresses 62 and 63 are '00' (no additional delay). Valid entries for address 62 are 0-8 and for address 63 are 0-9. Program entries into these addresses only if entering a '5' or '6' in address 59. Be careful to include any built-
in delays of the waterflow device.
Document #15140 Rev.G 01/02/02 P/N 15140:G
45
Page 46
Programming Options
AC Loss Reporting Delay (64)
Enter a digit of '1'-'F', corresponding to the number of hours to be delayed in reporting loss of AC power. The factory default setting is '0' for 6 hour delay. If 24 hour battery backup is being employed, select from choices '0' through '6'. If 60 hour backup is used, select from choices '7' through 'F'. Selections are: '0' for 6 hour delay; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10 hours; '5' for 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19 hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
Alarm Presignal (65)
Alarm Presignal is used to delay NAC (Notification Appliance Circuit) activation while allowing for visual verifica­tion by a person. Once a zone triggers an alarm, the main board piezo and the annunciator piezo sounders turn on steady, the display indicates the activated zone, the alarm LED blinks and the NACs are held off for 15 seconds. Dur­ing this time, if the silence switch is pressed, the notification appliances may be held off for up to three minutes (see Presignal Delay Timer Address 66-68). After the programmed delay period, the notification appliances will activate. Presignal does not function for zones defined as waterflow or supervisory. Factory default is '0' for no alarm presig­nal. Enter '1' to select alarm presignal. During alarm presignal, access to other modes is prevented.
Alarm Presignal Delay Timer (66-68)
The alarm presignal delay timer is factory set to 120 seconds (2 minutes), address 66=1, 67=2 and 68=0. The timer may be programmed from 0 to 179 seconds. Location 65 must be set to '1' for the delay timer to operate.
Notification Appliance Circuit #1 Enable (69)
NAC #1 may be programmed as '0' for silenceable, '1' for nonsilenceable or '2' for disabled (disabling will cause the display to indicate 'bEL1', system trouble light to turn on and onboard piezo to sound). Factory default is '0' for silenceable. Note: Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address.
Silence Inhibit Notification Appliance Circuit #1 (70)
Setting address 70 to '1' prohibits silencing of NAC #1 and the onboard piezo for one minute. Factory default is '0' for no silence inhibit of NAC #1.
Autosilence Notification Appliance Circuit #1 (71)
NAC #1 may be autosilenced after a programmed time interval between 5 and 30 minutes. Enter '1' for 5 minute autosilence, '2' for 10 minutes, '3' for 15 minutes, '4' for 20 minutes, '5' for 25 minutes or '6' for 30 minutes. The fac­tory default is '0' for no autosilence.
Coding Notification Appliance Circuit #1 (72)
Coding of NAC #1 is programmable by selecting '1' for March Time (120 ppm), '2' for California (10 seconds On, 5 seconds Off) or '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ seconds Off). Factory default is '0' for no coding (steady).
Notification Appliance Circuit #2 Enable (73)
NAC #2 may be programmed as '0' for silenceable, '1' for nonsilenceable or '2' for disabled (disabling will cause the display to indicate 'bEL2', system trouble light to turn on and onboard piezo to sound). Factory default is '0' for silenceable. Note: Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address.
Silence Inhibit Notification Appliance Circuit #2 (74)
Setting address 74 to '1' prohibits silencing of NAC #2 and the onboard piezo for one minute. Factory default is '0' for no silence inhibit of NAC #2.
Autosilence Notification Appliance Circuit #2 (75)
NAC #2 may be autosilenced after a programmed time interval between 5 and 30 minutes. Enter '1' for 5 minute autosilence, '2' for 10 minutes, '3' for 15 minutes, '4' for 20 minutes, '5' for 25 minutes or '6' for 30 minutes. The fac­tory default is '0' for no autosilence.
46
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 47
Programming Options
Coding Notification Appliance Circuit #2 (76)
Coding of NAC #2 is programmable by selecting '1' for March Time (120 ppm), '2' for California (10 seconds On, 5 seconds Off) or '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ seconds Off). Factory default is '0' for no coding (steady).
Trouble Reminder (77)
Factory default is '0' which disables the trouble reminder feature. Selecting '1' will cause a reminding beep (after the silence switch is pressed), every 15 seconds during an alarm and every two minutes during a trouble condition. The beeps from the onboard piezo sounder will continue until the alarm or fault is cleared.
Annunciator/Printer Supervision (78)
Factory default is '0' for no annunciator or printer present. Set address 78 to '1' if an annunciator is present, set to '2' if a printer is present or set to '3' if both an annunciator and a printer are present.
Backup Reporting (79)
Leaving the default setting of '0' programs the control panel to transmit reports to the Secondary Central Station phone number only if attempts to communicate to the Primary Central Station phone number are unsuccessful. Pro­gramming a '1' causes all reports to be transmitted to the Secondary Central Station Phone number.
Touchtone/Rotary Select (80)
A '0' programmed in this address by the factory triggers Touchtone dialing over both phone lines. Select '1' for rotary dialing.
Make/Break Ratio (81)
Use this address only if '1' (rotary dialing) has been selected for address 80. The make/break ratio is factory set to '0' for 67/33 ratio, but may be changed to '1' for 62/38 ratio.
Address (82)
Leave default of '0'.
Address (83)
Leave default of '0'.
Panel Identification Number (84-87)
The Panel Identification Number is a 4-digit code (valid digits are 0-F) that is used to identify the installed panel. This code is separate from the 8-digit secret code loaded in by the Service Terminal. It is important to program this 4­digit code at the jobsite the first time that downloading is performed so that the called Service Terminal can identify the control panel.
Service Terminal Number 1 Phone Number (88-103)
Addresses 88 through 103 are reserved for the Service Terminal phone number 1. Factory default is all 'Fs'. Valid entries are 0-9 plus A, B, C, D and E, similar to the primary and secondary Central Station phone number entries pro­grammed at addresses 00-15 and 26-41. Use 'F' to designate the end of the phone number.
Ring Count on Primary Phone Line (104-105)
Use this address to designate the number of rings allowed on the primary phone line prior to answering an incoming call from a Service Terminal. Factory default is '03' which means the panel will not answer an incoming call until 3 rings are detected. This entry may be programmed up to a maximum of 25 rings. A setting of '00' prevents the panel from answering incoming calls.
Document #15140 Rev.G 01/02/02 P/N 15140:G
47
Page 48
Programming Options
FAX/Answer Machine, Primary Phone Line (106)
This entry is used when the primary phone line is being shared with a FAX, answering machine or other device. Fac­tory default is '0' for no sharing of the primary phone line. An entry of '1' indicates sharing and allows the panel to wait for three consecutive calls from the Service Terminal, spaced 30 seconds apart, before responding.
Service Terminal Number 2 Phone Number (107-122)
Addresses 107 through 122 are reserved for the Service Terminal phone number 2. Factory default is all 'Fs'. Valid entries are 0-9 plus A, B, C, D and E, similar to the primary and secondary Central Station phone number entries pro­grammed at addresses 00-15 and 26-41. Use 'F' to designate the end of the phone number.
Ring Count on Secondary Phone Line (123-124)
Use this address to designate the number of rings allowed on the secondary phone line prior to answering an incom­ing call from a Service Terminal. Factory default is '03' which means the panel will not answer an incoming call until 3 rings are detected. This entry may be programmed up to a maximum of 25 rings. A setting of '00' prevents the panel from answering incoming calls.
FAX/Answer Machine, Secondary Phone Line (125)
This entry is used when the secondary phone line is being shared with a FAX, answering machine or other device. Factory default is '0' for no sharing of the secondary phone line. An entry of '1' indicates sharing and allows the panel to wait for three consecutive calls from the Service Terminal, spaced 30 seconds apart, before responding.
Upload/Download Reports Sent to Secondary Central Station Phone Number, Backup or Always (126)
Reports for request for 'upload/download', 'successful upload', 'successful download' and 'failed upload/download' are always sent to the primary Central Station phone number. This entry allows for the same reports to either always be sent to the secondary Central Station phone number or only if attempts to transmit to the primary Central Station phone number are unsuccessful. Factory default is '0' for backup only. Enter '1' for always.
Programming Event Codes (127-374)
The type of reports and event codes that are sent to the Central Station are in Table 3-1 through Table 3-5 . The selections made for the Primary Central Station Number Communication Format (address 16) and the Secondary Central Station Number Communication Format (address 42) automatically program addresses 127-374 with factory default selections.
Any of the event codes may be changed. Consult your Central Station prior to altering the event codes. Entering an event code of '0' will cause the communicator to NOT transmit the report. For the 3+1, 4+1 and 4+1 Express formats or the 4+2 Expanded format, enter '0'. For the 4+2 Standard or 4+2 Express formats, enter '00'. Transmission of reports to either or both Central Station phone numbers may be disabled.
Note the special 'System Abnormal Test Report' event code. This report was added per new UL DACT requirements. This report is generated in place of the normal test report when an alarm and/or trouble condition exists at the time the test report is due to be sent.
Programming the Real-Time Clock and Calendar
Entering an address greater than 374 will cause a display of the current time. On initial power-up, the clock will start running from the factory setting of 00:01 (military time). The far left digit will be flashing, indicating that this is the first digit to be programmed. It should be noted that setting the time and date may cause corruption of the History
File. For this reason, it is important that the History File be cleared after the time and date has been set. Refer to “History Mode” on page 63.
Hours/Minutes
Select a digit then press [ENTER/STORE]. The digit 2nd from the left will start flashing. Select a digit then press [ENTER/STORE]. Hours setting is complete. With the digit 2nd from the right flashing, select a digit then press [ENTER/STORE]. The digit on the far right will start flashing. Select a digit then press [ENTER/STORE]. Min-
utes setting is complete.
48
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 49
Default Programming
Ye a r
After entering the last digit corresponding to minutes (far right digit), the display will read 1994 with the digit 9 (sec­ond from the right) flashing. Press [ENTER/STORE] if the 9 is acceptable. The digit farthest right will begin flash­ing. Enter the appropriate digit corresponding to the last digit of the current year and press the [ENTER/STORE] key to complete programming of the year.
Note that changing to the year 2000
can be accomplished by entering ‘0’ while the second digit from the right is
flashing, followed by the [ENTER/STORE] key. The two digits to the left will change to ‘20’ and the digit farthest right will begin flashing. Enter the appropriate digit corresponding to the last digit of the year (i.e. ‘0’ for the year
2000
) and press the [ENTER/STORE] key to complete programming of the year.
Month/Day
After the year is entered, the display will show four digits representing the month and day of the software release date. The month is represented by the two digits on the left and the day by the two digits on the right. The digit on the far left will be flashing. The month and day are set the same way as the hours and minutes. Once the last digit corresponding to the day is entered, the display will show the contents of address '00'. The real-time clock/calendar keeps track of leap years automatically.
Note that the software for the MS-5024UD operates the internal clock based upon 60Hz. The software for the MS-5024UDE operates the internal clock based upon 50Hz.
End Programming
Exit Programming Mode by pressing MODE, followed by the 4-digit code corresponding to an alternate mode of operation, then press [ENTER/STORE].
During Program Mode, if no key is pressed within 10 minutes, the panel will return to Normal Mode.
3.4 Default Programming
To return all program entries to their factory original settings, perform the following steps only when the system is idle in Normal standby condition:
Press the MODE key followed by the four digit code 3337 and press the [ENTER/STORE] key.
3337 spells DEFP (DEFault Programming) on a Touch-Tone
®
phone
If an incorrect key is pressed, reenter the proper 4-digit code before pressing the [ENTER/STORE] key.
Within five seconds, repeat this entry by again pressing the MODE key followed by the 4-digit code 3337 and press­ing the [ENTER/STORE] key. The display will read 3337 while the E
2
nonvolatile memory (storage area for all programming options) is being reprogrammed with the original default settings. When reprogramming is complete, the display will be blank.
Document #15140 Rev.G 01/02/02 P/N 15140:G
49
Page 50
Operating Instructions
CHAPTER 4 Operating Instructions
The MS-5024UD has six modes of operation:
• Normal Mode
•Program Mode
• Walktest Mode
• Troubleshoot Mode
• History Mode
• Print Mode
Upon initial power-up, the system will be in Normal Mode. This chapter discusses operation of the control panel in the Normal Mode.
4.1 Switches in Normal Mode
4.1.1 RESET
The Reset Switch resets the system and any smoke detectors. If the Reset Switch is pressed, the control panel will:
Clear the display and status LEDs
Turn off the Notification Appliance Circuits Reset all zones by temporarily removing power
Silence the onboard piezo sounder
Store 'reset' message in the History file
Restore the alarm and trouble relays to normal
Clear the supervisory and communication fail relay driver outputs
Temporarily remove power from the resettable power output TB4 terminals 3 & 4
Restore to normal the RM-5F zone relays
Output 'reset' message to printer
Any alarm, supervisory or trouble condition that exists after a system reset, will resound the system, reactivating nor­mal system activity. Upon release of the Reset Switch, the display will read rES_ for six seconds.
50
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 51
Displays
SILENCE
If the Silence Switch is pressed:
The silenceable NACs will be turned Off
The silence LED will be turned Off
The piezo sounder will be shut Off
'System Silenced' message will be stored in the History file
'System Silenced' message will be sent to the printer
System Silence switch acts as acknowledge switch during alarm presignal
Upon the occurrence of a subsequent event (alarm or trouble), System Silence is overridden and the control panel will respond to the new event. The System Silence switch will be ignored for silenceable waterflow type alarms.
MODE
Pressing the MODE switch followed by a valid 4-digit numerical code and then the [ENTER/STORE] key selects one of the six modes of operation. To enter Normal Mode from any other mode, press MODE, then 6676 followed by the [ENTER/STORE] key.
6676 spells NORM on a Touchtone
®
phone.
1st EVENT
The 1st Event switch, along with the Up and Down arrow keys, is used to display any currently active alarm and/or fault conditions present in the system. Press the 1st Event switch at any time to display the first event (alarm and/or trouble) that occurred.
DOWN ARROW
The Down Arrow key is used to view other events (newer) that have occurred and are active (not yet cleared).
UP ARROW
The Up Arrow key is used to view other events (older) that have occurred and are active (not yet cleared).
[ENTER/STORE]
See individual mode descriptions in other sections of this manual.
4.2 Displays
Four 7-segment red LED characters provide visual annunciation of status, events and messages. A list of messages that may appear on the display in Normal Mode is shown below:
d__1 d__2 d__3 d__4 d__5 E__1 E__2 E__3 E__4 E__5 A__1 A__2 A__3 A__4 A__5
Zone 1 Disabled Zone 2 Disabled Zone 3 Disabled Zone 4 Disabled Zone 5 Disabled Zone 1 Enabled Zone 2 Enabled Zone 3 Enabled Zone 4 Enabled Zone 5 Enabled Alarm Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 4 Alarm Zone 5
F__1 F__2 F__3 F__4 F__5 F__A F__E Lo_b no_b PH_1 PH_2 bEL1 bEL2 no_1 no_2
Trouble Zone 1 Trouble Zone 2 Trouble Zone 3 Trouble Zone 4 Trouble Zone 5 Annunciator Fault Earth Fault Low Battery No Battery Primary C.S.# Comm. Fault Secondary C.S. # Comm. Fault Bell 1 Fault or Disabled Bell 2 Fault or Disabled Primary Phone Line Fault Secondary Phone Line Fault
SUP1 SUP2 SUP3 SUP4 SUP5 _AC_ rES_
Supv. Alarm Zone 1 Supv. Alarm Zone 2 Supv. Alarm Zone 3 Supv. Alarm Zone 4 Supv. Alarm Zone 5 AC Power Loss System Reset
Document #15140 Rev.G 01/02/02 P/N 15140:G
51
Page 52
Displays
Individual LEDs are provided for:
System Alarm
A red LED that turns on steady when an alarm condition is detected and blinks during the alarm presignal period.
System Trouble
This yellow LED blinks to indicate that a fault or abnormal condition exists and that the fire alarm system may be inoperative. It turns on steady when the silence switch is pressed.
AC Power On
A green LED that remains on while the AC power supply is within correct limits. If this indicator fails to light under normal conditions, service the system immediately.
Supervisory
A yellow LED that blinks to indicate the need for action in connection with the supervision or maintenance of sprin­klers, extinguishing systems or other protective systems.
System Silence
A yellow LED that turns on to indicate that an alarm or trouble condition exists in the system, but both NACs (if pro­grammed as silenceable) and local piezo have been silenced.
Primary Line Active
A red LED on the main circuit board that indicates the primary phone line is active.
Secondary Line Active
A red LED on the main circuit board that indicates the secondary phone line is active.
Kissoff
A green LED on the main circuit board that blinks when a Central Station has acknowledged receipt of each transmit­ted message or when a portion of upload or download data has been accepted from a Service Terminal.
Modem
A green LED on the main circuit board that stays on steady during modem types of communications.
FIGURE 4-1:
Phone Connectors and LEDs
Primary Line
Primary Active
Secondary Line
Secondary Active
52
Modem LED
Kissoff LED
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 53
Operation
4.3 Operation
Normal Mode is the standard mode of operation. In this mode, the control panel continuously monitors system status. When no alarm or trouble conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED). The Notifications Appliance Circuits will be off, all relays and relay drivers are normal and the onboard piezo sounder will be off. The communicator is not active, primary and secondary active LEDs are off.
All alarm and system trouble conditions are annunciated on the control panel's display. The control panel will main­tain an 'active event list' which will consist of all alarms, supervisory alarms and system troubles currently active and not cleared, requiring immediate service. When the system is cleared and restored to normal, the display will be blank. All alarms and troubles are stored in a history file and may be recalled at any time.
Higher priority events take precedence over lower priority events. Display and reporting of system status is done on a priority basis. Priorities are, from highest to lowest:
Alarms
1.
Supervisory Alarms
2.
System Troubles
3.
If the events to be displayed consist only of alarms and disabled zones (no troubles), the control panel will scroll them on the display. Pressing the 1st Event key will stop the scrolling and cause the display of the first alarm that occurred after the panel was last reset, cleared of all active events and placed into Normal Mode. Operation of the Up and Down arrow keys will display all remaining events in sequence.
If events to be displayed include system troubles, only one event is displayed at a time and there is no scrolling. The event displayed is the highest priority. Pressing the 1st Event key will cause the display of the first event that occurred after the panel was last reset, cleared of all active events and placed into Normal Mode. Operation of the Up and Down arrow keys will display all remaining events in order of their occurrences.
4.3.1 Alarm Response
Upon detection of an alarm condition, the control panel will:
Turn the alarm LED on
Activate the alarm relay
Display the alarm message (i.e. A__1 for alarm on zone 1)
Communicate the alarm to the Central Station
Store the alarm in the History file
Turn the NACs on
Turn the piezo sounder on
Turn on appropriate zone relay output
Output alarm message to printer
Terminate upload or download communications
Note that when any zone is programmed as a supervisory zone, it will not be processed in the same manner as a con­ventional alarm zone. See Supervisory Condition later in this section.
Document #15140 Rev.G 01/02/02 P/N 15140:G
53
Page 54
Operation
4.3.2 Alarm Restoral
The control panel returns to normal only after all alarms have been cleared and the Reset switch has been pressed (pull stations reset, smoke detectors reset and no smoke is present, waterflow has stopped, etc.). Upon restoral of all active alarms, the control panel will perform the following:
Turn off the alarm LED
Deactivate the alarm relay
Clear the 4-character display
Send all 'zone restoral' messages to the Central Station
Turn off the NACs
Turn off the piezo sounder
Turn off appropriate zone relay output
Output 'zone restoral' message to printer
Terminate upload or download communications
4.3.3 System Supervisory Condition Response
Program zones for supervisory in applications where a waterflow sensing device has been employed and the wiring to the waterflow valve and/or a tamper switch is to be monitored. If the tamper switch has been activated (normally open contacts close), a supervisory alarm condition will occur. When a supervisory condition occurs, the control panel will:
Blink the supervisory LED (½ second On, ½ second Off)
Activate the supervisory relay driver (TB4-5)
Display the following message: SUPX where X = the zone number
Communicate the supervisory condition to the Central Station
Store the 'supervisory' message in the History file
Pulse the piezo sounder at ½ second On and ½ second Off rate
Turn on appropriate zone relay output
Output system supervisory message to printer
Terminate upload or download communications
4.3.4 System Supervisory Restoral Response
When the supervisory condition has been cleared (condition is restored and the reset switch has been pressed), the control panel will perform the following:
Turn off the supervisory LED
Deactivate the supervisory relay driver (TB4-5)
Clear the display of the 'SUP' message
Communicate a supervisory restoral message to the Central Station
Shut off the piezo sounder
Turn off appropriate zone relay output
Output system supervisory restoral message to printer
Terminate upload or download communications
Note: For any zone programmed for supervisory autoresettable, the Reset switch does not need to be pressed to clear the zone (supervisory condition).
54
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 55
Operation
4.3.5 Trouble Condition Response
Upon detection of one or more trouble conditions, the control panel will perform the following:
Blink the trouble LED (1 second On and 1 second Off)
Activate the trouble relay
Display the appropriate trouble message(s) in priority fashion from the highest priority to the lowest.
Note that the Up Arrow, Down Arrow or 1st Event key must be pressed to view the messages
Communicate the trouble conditions to the Central Station
Store the trouble conditions in the History file
Sound the piezo sounder 1 second On and 1 second Off
Output the system trouble messages to the printer
Terminate upload or download communications
Note: When AC brownout occurs, the AC LED is turned off and the trouble LED blinks. Should the brownout con­dition remain, it will be transmitted to the Central Station after a delay (see program address 64).
Possible trouble messages that may appear on the display are as follows:
d__1 d__2 d__3 d__4 d__5 F__1 F__2 F__3 F__4 F__5 F__A F__E
Zone 1 Disabled Zone 2 Disabled Zone 3 Disabled Zone 4 Disabled Zone 5 Disabled Trouble Zone 1 Trouble Zone 2 Trouble Zone 3 Trouble Zone 4 Trouble Zone 5 Annunciator Fault Earth Fault
Lo_b no_b PH_1 PH_2 bEL1 bEL2 no_1 no_2 _AC_
Low Battery No Battery Primary C.S.# Comm. Fault Secondary C.S. # Comm. Fault Bell 1 Fault or Disabled Bell 2 Fault or Disabled Primary Phone Line Fault Secondary Phone Line Fault AC Power Loss (shown only when requested)
4.3.6 Trouble Condition Restoral
Upon restoral of all trouble conditions, the control panel performs the following:
Shut off the trouble LED
Deactivates the trouble relay
Turn off the AC Power LED if the trouble was loss of AC
Clear the display of all trouble messages
Communicate the restored trouble condition(s) to the Central Station
Output the system trouble restoral message to the printer
Terminate upload or download communications
4.3.7 Off Normal Reporting
Removing the control panel from Normal Mode and placing it into any other mode causes the transmission of an 'off normal' fault message to the Central Station. Returning the panel to Normal Mode causes the transmission of a 'return to normal' restoral message.
Document #15140 Rev.G 01/02/02 P/N 15140:G
55
Page 56
Operation
4.3.8 Zone Disable/Enable
The zone disable feature may be used to disable any zone in the system. Zones may be disabled if they are normal, in trouble or alarmed. Zones may be disabled only during the Normal Mode of operation, when the fire protection is
active. If the panel is in alarm, the silence switch must be pressed first, before the zone disable feature will function.
To disable a zone, press the MODE key once (the display will go blank). You then have 10 seconds to start entering the code 3472. Next press the [ENTER/STORE] key.
3472 spells DISA on a Touch-Tone
A flashing lower case d will appear on the far left of the display. Press the digit key corresponding to the zone num­ber to be disabled. The number will appear on the far right of the display. Press [ENTER/STORE] to disable the zone. Note that the trouble relay is activated and the trouble LED blinks.
The zone disable message will remain on the display until the zone is reenabled. To reenable a zone, press the
MODE key. The display will go blank. You then have 10 seconds to start entering the code 3622. Next, press the [ENTER/STORE] key.
3622 spells ENAB on a Touch-Tone
A flashing upper case E will appear on the left of the display. Press the digit key corresponding to the zone number to be enabled. The number will appear on the far right of the display. Press the [ENTER/STORE] key to reenable the zone. Not that the trouble relay is restored to normal and the trouble LED turns off (if no other troubles are on the system).
®
phone.
®
phone.
4.3.9 Fire Drill
The Drill (manual evacuate) feature turns on both Notification Appliance Circuits (if programmed as enabled) and turns off the silence LED. Tor perform a fire drill, press the MODE key followed by the code 3745 then the [ENTER/STORE] key. The display will indicate dril. The alarm relay is not activated for a fire drill. There is an option to transmit the fire drill report code to the Central Station.
3745 spells DRIL on a Touch-Tone
During a fire drill, the Silence key will silence both NACs and the Reset key restores the control panel to normal. All zones remain active during a fire drill.
®
phone.
56
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 57
Central Station Communications
4.4 Central Station Communications
The control panel transmits zone and system status reports to Central Stations via the public switched telephone net­work. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two optional 7 foot telephone cords are available for this purpose and can be purchased separately.
The control panel supervised both telephone lines for proper voltage. A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound, the yellow trouble LED will blink, the 4-character display will show either 'no 1' (primary line fault) or 'no 2' (secondary line fault) and the trouble condition will be reported to the Central Station over the remaining operational phone line.
The control panel comes with line seizure capability provided for both the primary and secondary telephone line interfaces. Any time that the control panel needs to make a call to a Central Station, line seizure will disconnect any local premises phones sharing the same telephone line.
All transmissions to the Central Stations will be sent over the primary phone line. In the event of noisy phone lines, transmissions will be sent over the backup secondary phone line.
Two phone numbers must be programmed, the primary Central Station phone number and the secondary Central Sta­tion phone number. All system reports will be transmitted to the primary Central Station phone number. Reports will automatically be sent to the secondary Central Station phone number if attempts to transmits to the primary Central Station phone number are unsuccessful. If 10 total attempts to communicate are unsuccessful, the Communicator Failure output will be turned on (TB4, Terminal 6). Note that as an option, all reports may also be sent to the second­ary Central Station phone number.
The MS-5024UD meets NFPA 72 National Fire Code reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting premises. The general priority reporting structure is:
Zone Alarms and Restores
1.
Zone Troubles and Restores
2.
System Troubles and Restores
3.
24-hour Test
4.
Document #15140 Rev.G 01/02/02 P/N 15140:G
57
Page 58
Central Station Communications
The control panel is capable of reporting detailed messages depending upon the format in use. Table 4-1 shows the reporting structure for all formats.
TABLE 4-1:
Zone Trouble Restore SSS(S) RTZ
System Trouble SSS(S) TS
System Trouble Restore SSS(S) RTS
Zone Disable Restore SSS(S) RDZ
Format Selection Address (16 & 42)
Format #
0, 2, 4, 6, 8
Report
Alarm SSS(S) A
Alarm Restore SSS(S) RA
Zone Trouble
(Zone Open)
Zone Disable SSS(S) DZ
3+1/4+1/Standard
4+1 Express
SSS(S) TZ
Format #
3, 5, 7, 9
3+1/4+1/Expanded
SSS(S) A
AAA(A) Z
SSS(S) RA
RARARA(RA) Z
SSS(S) TZ
TZTZTZ(TZ) Z
SSS(S) RTZ
RTZ RTZRTZ(RTZ ) Z
SSS(S) TS
TSTSTS(TS) Y
SSS(S) RTS
RTS RTSRTS(RTS ) Y
SSS(S) DZ
DZDZDZ(DZ) Z
SSS(S) RDZ
RDZRDZRDZ(RDZ) Z
Format #
1, A, C
4+2/Standard
4+2 Express
Format
B, D
4+2/Expanded
SSSS AA2 SSSS AZ
SSSS RARA2 SSSS RAZ
SSSS TZTZ2 SSSS TZZ
SSSS RTZRTZ2 SSSS RTZZ
SSSS TSTS2 SSSS TSY
SSSS RTSRTS2 SSSS RTSY
SSSS DZDZ2 SSSS DZZ
SSSS RDZRDZ2 SSSS RDZZ
Low Battery SSS(S) L SSS(S) L SSSS LL2 SSSS LL2
Low Battery Restore SSS(S) RL SSS(S) RL SSSS RLRL2 SSSS RLRL2
AC Loss SSS(S) P SSS(S) P SSSS PP2 SSSS PP2
AC Loss Restore SSS(S) RP SSS(S) RP SSSS RPRP2 SSSS RPRP2
Fire Drill SSS(S) Fd SSS(S) Fd SSSS FdFd2 SSSS FdFd2
Fire Drill Restore SSS(S) RFd SSS(S) RFd SSSS RFdRFd2 SSSS RFdRFd2
Supervisory Condition SSS(S) V
Supervisory Condition
Restore
SSS(S) RV
SSS(S) V
VVV(V) Z
SSS(S) RV
RVRVRV(RV ) Z
SSSS VV2 SSSS VZ
SSSS RVRV2 SSSS RVZ
Test Report SSS(S) X SSS(S) X SSSS XX2 SSSS XX2
Upload or Download SSS(S) UD SSS(S) UD SSS UDUD2 SSS UDUD2
Refer to Table 4-2 for an explanation of each letter code in Table 4-1 . Refer to Table 4-3 for a list of compatible receivers.
58
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 59
Central Station Communications
TAB LE 4- 2:
Format Selection Address Explanation
Where
SSS or SSSS = Subscriber ID A = Alarm (1st digit) A2 = Alarm (2nd digit) Z = Zone Number RA = Alarm Restore (1st digit) RA2 = Alarm Restore (2nd digit) TZ = Zone Trouble (1st digit) TZ2 = Zone Trouble (2nd digit) RTZ = Zone Trouble Restore (1st digit) RTZ2 = Zone Trouble Restore (2nd digit) TS = System Trouble (1st digit) TS2 = System Trouble (2nd digit) RTS = System Trouble Restore (1st digit) RTS2 = System Trouble Restore (2nd digit) DZ = Zone Disable (1st digit) DZ2 = Zone Disable (2nd digit) RDZ = Zone Disable Restore (1st digit) RDZ2 = Zone Disable Restore (2nd digit) L = Low Battery (1st digit) L2 = Low Battery (2nd digit) RL = Low Battery Restore (1st digit) RL2 = Low Battery Restore (2nd digit) P = AC Loss (1st digit) P2 = AC Loss (2nd digit) RP = AC Loss Restore (1st digit) RP2 = AC Loss Restore (2nd digit) FD = Fire Drill (1st digit) FD2 = Fire Drill (2nd digit) RFD = Fire Drill Restore (1st digit) RFD2 = Fire Drill Restore (2nd digit) V = Supervisory Condition (1st digit) V2 = Supervisory Condition (2nd digit) RV = Supervisory Condition Restore (1st digit) RV2 = Supervisory Condition Restore (2nd digit) X = Test Report (1st digit) X2 = Test Report (2nd digit) Y = A trouble corresponding to the following:
7 = Ground Fault 8 = Low Battery 9 = No Battery
A = Telco Primary Line Fault
B = Telco Secondary Line Fault C = Main Bell Fault, Annunciator Bell
D = Communication Fault to Primary Number
E = Communication Fault to Secondary Number
F = System Off Normal Fault/System Fault (Slave Operation, see Chapter 6) UD = Upload/download (1st digit) UD2 = Upload/download (2nd digit)
Note: For Expanded Reporting, the control panel automatically adds the digit corresponding to the zone number and the second digit corresponding to any system trouble condition. Only the first digit is programmable.
Document #15140 Rev.G 01/02/02 P/N 15140:G
59
Page 60
Central Station Communications
4.4.1 Transmittal Priorities
The integral communicator transmits highest priority events first. Events, in terms of priority, are listed below in descending order:
Alarms (highest priority level)
1.
Pull stations
Waterflow
Smoke detector
Other alarm types
Supervisory Zone
2.
System Troubles
3.
Zone disabled
Fire drill
AC fail (after delay)
Zonal faults
Earth fault
Low battery/no battery
Telephone line fault
Notification Appliance Circuits fault
Communication trouble
Annunciator trouble
System off normal
Restoral Reports
4.
Zone alarm
Supervisory
Zone(s) enabled
Fire drill
AC
Zone fault
Earth
Battery
Telephone line
Notification Appliance Circuits
Communication
Annunciator trouble
System off normal
24 Hour Test (lowest priority)
5.
Red LEDs are provided on the control panel circuit board to identify which telephone line is activated. Also, a green LED labeled 'kissoff' will turn on whenever the control panel has successfully transmitted reports to the Central Sta­tion. The 'kissoff' LED may turn on several times during communications with a Central Station.
60
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 61
Central Station Communications
The table below shows UL listed receivers which are compatible with the MS-5024UD.
TAB LE 4- 3:
0 4+1 Ademco Express
1 4+2 Ademco Express
2 3+1/Standard/1800/2300
3 3+1/Expanded/1800/2300
4 3+1/Standard/1900/1400
5 3+1/Expanded/1900/1400
6 4+1/Standard/1800/2300
7 4+1/Expanded/1800/2300
8 4+1/Standard/1900/1400
9 4+1/Expanded/1900/1400
A 4+2/Standard/1800/2300
B 4+2/Expanded/1800/2300
C 4+2/Standard/1900/1400
D 4+2/Expanded/1900/1400
E Ademco Contact ID
FNot Used
Compatible UL Listed Receivers
Format #
(Addresses 16 & 42)
Ademco
685 (1)
Silent Knight
9000 (2)
ITI
CS-4000 (3)
FBI
CP220FB
Osborne Hoffman
Models 1 & 2
Radionics
6000 (6)
Radionics
6500 (5)
Sescoa
3000R (7)
Surguard
MLR-2 (9)
✔✔
✔✔
✔✔ ✔✔
✔✔ ✔✔
✔✔
✔✔
✔✔ ✔✔
✔✔
✔✔
✔✔
✔✔ ✔✔
✔✔
✔✔
✔✔
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(8)
✔✔✔✔✔
✔✔
✔✔
✔✔
✔✔
✔✔
✔✔
✔✔
✔✔
✔✔
✔✔
✔✔
✔✔
With 685-8 Line Card with Rev. 4.4d software
1.
With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software
2.
Rev. 4.0 software
3.
FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8 software
4.
Model 6500 with Rev. 600 software
5.
Mode 6000 with Rev. 204 software
6.
With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software
7.
Model 2 only
8.
Version 1.62 software
9.
Document #15140 Rev.G 01/02/02 P/N 15140:G
61
Page 62
Servicing
CHAPTER 5 Servicing
5.1 Walktest Mode
The MS-5024UD provides the capability to perform a one-man walktest of the system without triggering the commu­nicator, the zone relays or the alarm output relay. Walktest allows for testing of the five zones (Initiating Device Cir­cuits). The first initiating device activated on a zone will cause the Notification Appliance Circuits to turn on for four seconds. Subsequent device activations on the same zone will cause the NACs to turn on for one second. Any smoke detectors that are activated will be reset. Zonal faults (open circuits) will cause the NAC to remain on steady. Prior to entering Walktest Mode, check to be certain that all system faults have been cleared. Note that the trouble relay
will be activated while the control panel is in Walktest Mode. Placing the control panel into this mode will only be possible if the system has no active alarms.
Pressing the MODE key followed by the 4-digit code 9255 and then the [ENTER/STORE] key will place the con­trol panel into Walktest Mode.
9255 spells WALK on a Touch-Tone
®
phone.
Once in Walktest Mode, the control panel will immediately:
Blink the trouble LED
Activate the trouble relay
Turn on the NACs for four seconds for the first alarm on a zone. Subsequent alarms on the same zone will sound for one second. Troubles cause the NACs to remain on
Disable the alarm relay
Display all alarm conditions as they occur
Display all zone troubles as they occur
Display ground faults as they occur
Transmit 'off normal' message to Central Station(s)
Continue to communicate any events not acknowledged at a Central Station prior to entering Walktest Mode
During Walktest Mode, zonal activity is displayed in real-time as it occurs. At the end of walktesting the system, the display will show the last event that occurred. To view all events stored during Walktest, use the Up arrow, Down arrow and 1st Event keys. The Down arrow key moves the Walktest list to show older (previous) events. The Up arrow key moves the Walktest list to show newer (more recent) events. Pressing the 1st Event key at any time will cause the display of the first event stored upon initial entry into Walktest Mode. While in Walktest Mode, the control panel will store up to 128 events in the Walktest File for later recall and display. A printer may be connected to the panel during Walktest. All Walktest events are printed in real-time as they occur.
To return the control panel to Normal Mode, press the MODE key followed by the code 6676 and then the [ENTER/ STORE] key. Any delay between key presses greater than 10 seconds causes the control panel to remain in Walktest Mode.
The control panel will automatically return to Normal Mode if no system activity has occurred for 60 minutes. This includes pressing any keys or activity on any zone. Exiting Walktest Mode leaves the Walktest file in memory such that it may be printed in Print Mode. Subsequent entries into Walktest Mode will delete the Walktest file.
Note that remote site upload or download is not possible while in Walktest Mode.
62
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 63
History Mode
5.2 History Mode
All Normal Mode events are stored in a History File list for future recall. Recall is possible via the 4-character dis­play or via an optional printer. The History File list is a first-in, first-out (FIFO) file. In this manner, only the most recent events may be called up from memory. Older events will be overwritten, that is, pushed out of the FIFO file. The number of stored events is 32 maximum. The History File is kept in E erase the list.
Pressing the MODE key followed by the code 4478 and then the [ENTER/STORE] key places the control panel into History Mode. This will not occur if there are any active alarm conditions present. The event displayed, is the most recent event.
4478 spells HIST on a Touch-Tone
®
phone.
Once in History Mode, the control panel will:
Blink the trouble LED
Activate the trouble relay
Disable the Notification Appliance Circuit(s)
Disable the alarm relay
Display all events as they occurred since the last time the History File list was cleared. The most recent
event will be displayed first
Ignore all other keys other than those mentioned in this section
Transmit the 'off normal' message to the Central Station(s)
Continue to communicate any events not previously acknowledged at the Central Station prior to enter-
ing History Mode
2
memory. Complete power loss will not
The Down Arrow key moves the History File to show older (previous) events. The Up Arrow key moves the History file to show newer (more recent) events. Following is a list of messages as they will appear on the display:
d__1 d__2 d__3 d__4 d__5 E__1 E__2 E__3 E__4 E__5 A__1 A__2 A__3 A__4 A__5
Zone 1 Disabled Zone 2 Disabled Zone 3 Disabled Zone 4 Disabled Zone 5 Disabled Zone 1 Enabled Zone 2 Enabled Zone 3 Enabled Zone 4 Enabled Zone 5 Enabled Alarm Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 4 Alarm Zone 5
F__1 F__2 F__3 F__4 F__5 F__A F__E Lo_b no_b PH_1 PH_2 bEL1 bEL2 no_1 no_2
Trouble Zone 1 Trouble Zone 2 Trouble Zone 3 Trouble Zone 4 Trouble Zone 5 Annunciator Fault Earth Fault Low Battery No Battery Primary C.S.# Comm. Fault Secondary C.S. # Comm. Fault Bell 1 Fault or Disabled Bell 2 Fault or Disabled Primary Phone Line Fault Secondary Phone Line Fault
SUP1 SUP2 SUP3 SUP4 SUP5 _AC_ SILE rES_
Supv. Alarm Zone 1 Supv. Alarm Zone 2 Supv. Alarm Zone 3 Supv. Alarm Zone 4 Supv. Alarm Zone 5 AC Power Loss Silence Switch Pressed Reset Switch Pressed
It should be noted that setting the time and date may cause corruption of the History File contents. The History File should therefore be cleared after the time and date are set. To clear the list from E
2
memory, press the SILENCE key
twice before exiting the History Mode.
A lack of keyboard activity for a period of 10 minutes will cause the control panel to return to Normal Mode. If a printer is connected to the control panel, the History File will be printed upon successful entry into History Mode and a list of the most recent 32 events, time and date stamped, will print out. Note that remote site upload or download is
not possible while the panel is in History Mode.
Document #15140 Rev.G 01/02/02 P/N 15140:G
63
Page 64
Troubleshoot Mode
5.3 Troubleshoot Mode
In Troubleshoot Mode, system voltages may be displayed on the 4-character display. An internal voltmeter measures the voltage present at:
• Zone inputs
• AC power input
• Battery terminal leads
•NAC #1
•NAC #2
• Resettable 24 volt power output
To enter Troubleshoot Mode, press the MODE key followed by the code
and then the [ENTER/STORE] key.
8768
A lack of keyboard activity for a period of 20 minutes will cause the control panel to return to Normal Mode.
8768 spells TROU on a Touch-Tone
®
phone.
Once in Troubleshoot Mode, the control panel will:
Blink the trouble LED
Activate the trouble relay
Disable the NACs
Disable the alarm relay
Transmit the 'off normal' message to the Central Station(s)
Continue to communicate any events not yet acknowledged at the Central Station prior to entering Troubleshoot Mode
Voltages can be viewed by performing the following steps:
• AC input voltage - press A and then the [ENTER/STORE] key
• Battery voltage - press B and then the [ENTER/STORE] key
• Zone 1 voltage - press 1 and then the [ENTER/STORE] key
• Zone 2 voltage - press 2 and then the [ENTER/STORE] key
• Zone 3 voltage - press 3 and then the [ENTER/STORE] key
• Zone 4 voltage - press 4 and then the [ENTER/STORE] key
• Zone 5 voltage - press 5 and then the [ENTER/STORE] key
• NAC #1 voltage - press b then 1 and then the [ENTER/STORE] key
• NAC #2 voltage - press b then 2 and then the [ENTER/STORE] key
• Resettable 24 volt power - press the RESET key and then the [ENTER/STORE] key
5.3.1 Zone Voltages
The nominal threshold voltages for each zone are listed below. Actual readings will vary depending upon system load and AC line voltage
TABLE 5-1:
Zone # Normal w/E.O.L. Shorted Open Circuit
1 23.5V 0.00V 25.4V
2 23.5V 0.00V 25.4V
3 23.5V 0.00V 25.4V
4 23.5V 0.00V 25.4V
5 23.5V 0.00V 25.4V
64
.
Nominal Zone Voltages
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 65
Troubleshoot Mode
5.3.2 AC Line Voltage
The following table lists the AC line voltage range. The AC On indicator will turn off when the AC line voltage drops below the Low Line threshold and the trouble LED will turn on.
TAB LE 5- 2:
AC Line Voltage Low Line Normal High Line
AC Line Voltage Range
MS-5024UD 102 VAC 115 VAC 132 VAC
MS-5024UDE 204 VAC 220 VAC 264 VAC
5.3.3 Battery Voltage
The following table lists the critical battery threshold conditions. Note that battery measurements should be made after allowing 48 hours to charge depleted batteries. If batteries do not show normal readings, replace them.
IMPORTANT
: The battery charger will turn off when the battery voltage drops to 17.4 VDC or less (No Battery
condition). A battery with a higher voltage must be installed to turn the charger back on.
TAB LE 5- 3:
Battery Voltage
Normal Low Battery No Battery
Battery Voltage: 27.6V 20.4V <17.4V
5.3.4 Telephone Lines
Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/STORE] causes seizure of the pri­mary phone line which in turn lights the red LED signifying primary phone line active. After a delay of three sec­onds, the control panel goes off-hook to acquire a dial tone.
The control panel keypad may be used as a telephone touchpad for number dialing. Once the first digit is pressed, the display will move the C or D character one position to the left, while placing the digit to be dialed on the farthest right display position. Continue to press the phone numbers to be dialed. Successive depressions of the [ENTER/ STORE] key hangs up and picks up the phone (places the phone on or off the hook).
The secondary phone line may be tested by pressing the E key for touchtone dialing or the F key for rotary dialing and then following the same procedure used for the primary phone line.
A handset may be temporarily connected across transformer T1 as indicated in Figure 5-1. The handset, when con­nected across T1, may be used only as an amplifier/speaker and telephone with the control panel used for number dialing.
FIGURE 5-1:
Phone Connectors and LEDs
Both Primary and Secondary Lines
Document #15140 Rev.G 01/02/02 P/N 15140:G
65
Page 66
Lamp Test
5.3.5 NAC 1 & 2
NAC voltage readings are nominally -2.32 volts when an EOL resistor of correct value is in place. A reading of 0.00 volts appears for shorts, -4.50 volts for opens. Intermediate readings are also available.
Note that remote site upload or download is not possible while the panel is in Troubleshoot or Lamp Test Mode.
5.3.6 Resettable Power
Resettable 24 volt power output must read 24 volts, + or - 10%.
5.4 Lamp Test
To perform a Lamp Test, press MODE then the code 5267 followed by the [ENTER/STORE] key. This will test all system LEDs. The LEDs will remain on for five seconds and then the control panel will return to Normal Mode.
5267 spells LAMP on a Touch-Tone
®
phone.
5.5 Print Mode
A printer may be temporarily or permanently connected to the control panel. Refer to Figure 2-15 on page 30, for proper PRT-24 Printer Interface module connection to the main circuit board before proceeding.
Programmable option address 78 must be programmed to a '2' if only a printer is connected to the control panel or '3' if both a printer and annunciator are connected to the control panel, to enable printer supervision. Once enabled, nor­mal system status as well as panel operations will be printed. If the printer connection is removed, the trouble LED will blink, the piezo sounder will pulse and the 4-character LED display will be blank.
Select Printer Mode by pressing the MODE key followed by the code 7746 and then the [ENTER/STORE] key. The display will read Prn and the following will be printed:
Entire program entries
1.
History file
2.
Walktest file
3.
Troubleshoot Mode voltages
4.
Current system status
5.
(Note that all activity is time and date stamped)
Upon entering the Print Mode, the control panel will transmit the 'system off normal' message to the Central Station. The panel will return to Normal Mode automatically after printing is completed. This will typically take three minutes.
Note that remote site upload or download is not possible while the panel is in Print Mode.
66
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 67
Slave Communicator Configuration
CHAPTER 6 Slave Communicator Configuration
The MS-5024UD may be used as a slave communicator to a host or master FACP (fire alarm control panel). All wir­ing between the master and the slave communicator is supervised. 4.7K ohm End-of-Line resistors should be connected.
In slave configuration, the five zones become five channels that may be triggered by the relay outputs of any host FACP. The five channels function as follows:
• Zone/Channel 1 - general alarm
• Zone/Channel 2 - general trouble
• Zone/Channel 3 - may be programmed to match the FACP relay function
• Zone/Channel 4 - supervisory
• Zone/Channel 5 - may be programmed to match the FACP relay function
The factory settings for Zone/Channel 2 alarm and restoral are altered as follows:
•If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, the report code for Zone 2 Alarm Code (address 128 & 252) is 'F' and the Zone 2 Restoral Code (address 156 & 280) is 'E'.
•If 1, A or C is entered for addresses 16 or 42, the report code for Zone 2 Alarm Code (addresses 129-130 & 253-254) is 'FF' and the Zone 2 Restoral Code (addresses 185-186 & 309-310) is 'EF.'
•If E is entered for addresses 16 or 42, the report code for Zone 2 Alarm Code and Restoral Code (addresses 130-132 & 254-256) is ‘300.’
The factory settings for Zone/Channel 4 alarm and restoral are altered as follows:
•If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, the report code for Zone 4 Alarm Code (address 130 & 254) is '8' and the Zone 4 Restoral Code (address 158 & 282) is 'E'.
•If 1, A or C is entered for addresses 16 or 42, the report code for Zone 4 Alarm Code (addresses 133-134 & 257-258) is '84' and the Zone 4 Restoral Code (addresses 189-190 & 313-314) is 'E4.'
•If E is entered for addresses 16 or 42, the report code for Zone 4 Alarm Code and Restoral Code (addresses 136-138 & 260-262) is ‘200.’
Location 56 must be programmed to a '1' to enable the control panel as a slave communicator.
Note that remote site upload or download is permitted in the Slave Communicator configuration, however, alarm presignal and verification do not function in Slave mode.
Be certain to connect the slave communicator's primary AC power to the same branch circuit as the host FACP.
Document #15140 Rev.G 01/02/02 P/N 15140:G
67
Page 68
Slave Communicator Configuration
FIGURE 6-1:
Slave Communicator Connections
Relays in the master FACP activate various input circuits on the slave communicator. Messages (event codes) pro­grammed for a particular input circuit (channel) will be transmitted to the Central Station upon relay activation.
68
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 69
Remote Site Upload/Download
CHAPTER 7 Remote Site Upload/Download
The control panel may be programmed or interrogated off-site via the public switched telephone network. Any per­sonal computer with DOS
4.01 or greater plus Windows™ 3.1 or greater, with a 1200 baud Hayes™ compatible modem and Fire•Lite Upload/Download software P/N PK-5024UD, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status, system voltages, time and date.
CAUTION: After successfully downloading a program, make certain to perform the following steps:
Print out all programmed data via Print Mode or manually view programmed entries and compare to intended
1.
program data
Test all affected panel operations
2.
Immediately correct any problems found
3.
7.1 Downloading Program
The first time that the control panel is downloaded (whether initiated at the jobsite or remotely), a secret code is loaded in by a Service Terminal. Future upload or download requests cause verification of the secret code by the con­trol panel before processing of data is allowed. If the secret code is not verified, the control panel will terminate the request.
While the control panel is communicating with the Service Terminal, the panel's green Modem LED and one of the red Line Seize LEDs will remain on steady. At the conclusion of a successful download, the green Kissoff LED will turn on steady for five seconds, the green Modem LED will turn off and the red Line Seize LED will turn off.
In order to download the panel (whether initiated at the jobsite or remotely), the following must be true:
The control panel must be in the Normal Mode of operation. Downloading is not possible if the panel is in any other mode
There cannot be any active communications ongoing with a Central Station receiver
All active events must be successfully 'kissed-off' by the Central Station(s). The communicator must be in a standby state with no new information waiting to be transmitted to a Central Station
With program address location 56 set to '1' or '2', anytime a download is initiated, the control panel will first contact the primary Central Station or both the primary and secondary Central Stations to report a 'request for upload/down­load' message. Once the request is 'kissed-off' by the Central Station(s), the control panel will then call the appropri­ate Service Terminal and begin the downloading process.
To prevent the 'request for upload/download' message(s) from being reported to the Central Station(s), make certain to leave address 56 set to '0' or disable all upload/download reports back to both Central Stations.
During the downloading process, the fire protection remains active
. Should a system trouble or alarm condition occur, the control panel immediately terminates downloading and processes the trouble or alarm locally and trans­mits the information to the Central Station(s).
Document #15140 Rev.G 01/02/02 P/N 15140:G
69
Page 70
Downloading Program
7.1.1 Security Features
Remote site upload and download with the control panel has been carefully designed to include key security features to ensure proper functionality. The key features are listed and explained below.
Secret Code Verification
A secret code is stored in the control panel by a Service Terminal to prevent unauthorized access. The secret code is created at the Service Terminal by the master user and cannot be viewed or changed by anyone other than a master user. Viewing of the secret code is prohibited at the control panel. Prior to allowing an upload or download of data, the control panel will verify the secret code transmitted by the Service Terminal.
Time-out at Control Panel
Upon answering an incoming call on either the primary or secondary Central Station phone line, the control panel will listen for a modem connection signal. If this signal is not received within 30 seconds, the control panel will dis­connect the call.
Callback to Service Terminal
Any time the control panel is requested to allow an upload or download, it will confirm the source of the incoming call, hang-up and call back the calling party (Service Terminal phone number).
Panel Identification Number
The panel identification number is typically used to identify the panel to the Service Terminal when the control panel calls the Service Terminal. If more than one call comes into the Service Terminal, the control panel ID number is used to sort out the calling parties.
Another use of this code allows for identical secret codes to be placed into multiple control panels at one jobsite, using the panel ID number to distinguish between the individual panels.
Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If an error is detected, the block is retransmitted until correct, up to a maximum of four times. If the Secret Code is not verified and four errors occur, the call is disconnected and the report that the upload/download was not successful is called to the Central Station(s).
Central Station Acknowledge
There is an option, referred to as the ‘callback’ option, whereby the control panel will report to one or both Central Stations that a request for uploading or downloading has been received prior to processing the call. If the Central Station(s) does not acknowledge receipt of this request, uploading or downloading is prohibited. If acknowledged by the Central Station(s), another message is transmitted, informing the Central Station(s) that:
• Downloading was successful
• Uploading was successful
• Uploading/downloading was not successful
Central Station Data Protection
Addresses '00' through '51' are assigned to the primary and secondary Central Station phone number, communication format, account code and test time. Addresses '127' through '374' are reserved for the programmable event codes. This block of addresses holds the entire vital Central Station information. These blocks are protected from partial programming due to faulty phone connections, line noise and other errors. This prevents the panel from being con­fused due to a wrong phone number, account code, test time and most critical formatting errors.
70
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 71
Downloading Initiated at Control Panel
7.2 Downloading Initiated at Control Panel
Before initiating the download procedure, make certain that the control panel is:
In Normal Mode
Central Station communications are off or location 56 is set to '0'
The communicator is in the standby state (red Line Seize LEDs are off, green Modem and Kissoff LEDs
are off)
Place the control panel into Program Mode and program one or both of the Service Terminal phone numbers. It is also advisable at this time to program the Panel Identification Number at addresses 84 - 87. This will allow the Ser­vice Terminal to easily identify incoming calls.
Exit the Program Mode and return the panel to Normal Mode. Press the MODE key followed by the 4-digit code
3696 and then the [ENTER/STORE] key.
3696 spells DOWN on a Touch-Tone
The display to the far left will flash the letter 'S'. Press the digit '1' for Service Terminal phone #1 or '2' for Service Terminal #2, followed by [ENTER/STORE]. The control panel will now call the appropriate Service Terminal phone number and the downloading process will begin.
®
phone.
Once the called Service Terminal identifies the incoming call (control panel), the downloading process is allowed to continue. Downloading progresses until all programmed information has been successfully loaded into the control panel. The programmed data may consist of addresses 00-374 plus the time and date.
7.3 Downloading Initiated at a Service Terminal
Before initiating the download procedure, make certain that the control panel is:
In Normal Mode
Central Station communications are off or location 56 is set to '0'
The communicator is in the standby state (red Line Seize LEDs are off, green Modem and Kissoff LEDs
are off)
Once the control panel accepts/answers an incoming call, the panel will:
Establish basic modem connection
1.
Verify secret code and panel identification number
2.
Verify callback vs. no callback request from the service terminal. If callback is requested, steps 4 through 9
3.
will occur. If no callback is requested, only steps 8 and 9 will occur
Identify the Service Terminal location
4.
Hang-up/disconnect call
5.
Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
6.
this message is accepted, the control panel will proceed to the next step
Return call to Service Terminal
7.
After security clearance, begin downloading
8.
Upon completion of download, call Central Station(s) back and report either a successful download or failed
9.
upload/download message (if programmed to do so)
Document #15140 Rev.G 01/02/02 P/N 15140:G
71
Page 72
Uploading Initiated at a Service Terminal
7.4 Uploading Initiated at a Service Terminal
Items that may be uploaded from the control panel to a Service Terminal are:
• All programmed data from addresses 00-374 plus the real-time clock, time and date
• Entire Walktest data file
• Troubleshoot Mode system voltages
• Entire 32 event History file
• Current system status
Uploading is possible at any time provided the following conditions are true:
The control panel must be in the Normal Mode of operation. Uploading is not possible if the panel is in
any other mode
There cannot be any active communications ongoing with a Central Station receiver
All active events must be successfully 'kissed-off' by the Central Station (the communicator must be in a standby state with no new information waiting to be transmitted to a Central Station)
Once an incoming call is accepted/answered by the control panel, the panel will:
Establish basic modem connection
1.
Verify secret code and panel identification number
2.
Verify callback vs. no callback request from the service terminal. If callback is requested, steps 4 through 9
3.
will occur. If no callback is requested, only steps 8 and 9 will occur
Identify the Service Terminal location
4.
Hang-up/disconnect call
5.
Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
6.
this message is accepted, the control panel will proceed to the next step
Return call to Service Terminal
7.
After security clearance, begin uploading
8.
Upon completion of upload, call Central Station(s) back and report either a successful upload or failed upload/
9.
download message (if programmed to do so).
During the uploading process, the fire protection remains active
. Should a system trouble or alarm condition occur, the control panel immediately terminates uploading and processes the trouble or alarm locally and trans­mits the information to the Central Station(s).
72
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 73
Battery Calculations
Appendix A Battery Calculations
Use the Total Standby and Alarm Load Currents calculated in Table A-2 and Table A-3 for the following battery calculation.
TAB LE A- 1:
Standby Load
Current (Amps)
Current (Amps)
Battery Calculations
[ ]
Alarm Load
[ }
Required Standby Time in Hours
X
(24 or 60 Hours)
[ ]
Required Alarm Time in Hours
X
(i.e. 5 minutes = 0.084)
[ ]
Add Standby and Alarm Load for Required Ampere Hour Battery = __________
Multiply by the Derating Factor of 1.2 X 1.2 __________
Total Ampere Hours (AH) Required = __________
Note:
7 Ampere Hour battery can be located in the backbox.
1.
12 Ampere Hour and 17 Ampere Hour batteries require the BB-17F battery box.
2.
= __________
= __________
Document #15140 Rev.G 01/02/02 P/N 15140:G
73
Page 74
Battery Calculations
A.1 The Main Power Supply
The MS-5024UD provides filtered power for operating the fire alarm control panel, external devices and the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or nonalarm) and Table A-3 (alarm) to determine if external loading is within the capabilities of the power supply.
Concerning 4-wire smoke detectors: Be sure to power smoke detectors from TB4, Terminals 3 and 4.
TABLE A-2:
Filtered Load in Standby - external devices connected to TB4 only
Device Type
# of
Devices
Current (Amps)
Total Current
(Amps)
Main Circuit Board 1 X 0.1 = 0.1
ADM-24 (1 max.) X 0.006 =
RZA-5F (1 max.) X 0 = 0
RM-5F (1 max.) X 0 = 0
CAC-5F (1 max.) X 0 = 0
2-wire Smoke Detector
Heads
[ ] X
[ ]
1
=
4-wire Smoke Detector
Heads
Power Supervision
2
Relays
Current Draw from
TB4 (nonalarm)
3
[ ] X
[ ] X 0.025 =
[ ]
1
=
=
Sum Column for Standby Load = Amps
1. Refer to the Device Compatibility Document for 2-wire smoke detector standby current.
2. Must use compatible listed power supervision relay.
3. The total standby current must include the sum of both the resettable (TB4, Terminals 3 & 4) and nonresettable (TB4, Terminals 5 & 6) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified (refer to Table A-3 )
74
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 75
Battery Calculations
TAB LE A- 3:
Filtered Load in Alarm
Device Type
# of
Devices
Current
(Amps)
Main Circuit Board 1 X 0.170 =
ADM-24 (1 max.) X 0.006 =
RZA-5F (1 max.) X
RM-5F (1 max.) X
0.046
0.080
2
2
CAC-5F (1 max.) X 0 = 0
4
4-wire Smoke Detector
Heads
Power Supervision Relays
[ ] X [ ] =
3
[ ] X 0.025 =
Total C urr ent
(Amps)
1
0.170
=
=
4
Notification Appliances
Notification Appliances
Current Draw from TB4
(alarm)
Sum Column for Standby Load
1. The current shown represents one zone on the main circuit board in alarm. For all five zones in alarm, the current draw increases to 0.36 amps.
2. The currents shown for the RZA-5F and RM-5F are for all five zones in alarm. For one zone in alarm, the RZA-5F cur­rent draw is 16 mA and the RM-5F current draw is 12 mA.
3. Must use compatible listed Power Supervision Relay.
4. Current limitations of terminals:
- TB4, Terminals 1 & 2 = 0.300 amp, filtered 24VDC +/- 5%, 120Hz ripple @ 10 mV ripple for MS-5024UDE).
- TB4, Terminals 3 & 4 = 0.300 amp, filtered 24VDC +/- 5%, 120Hz ripple @ 10 mV ple for MS-5024UDE)
- TB5, 2.5 amps.
- TB6, 2.5 amps.
5. Total Current draw listed above cannot exceed:
- 3.6 amps with only the standard transformer installed
- 5.6 amps with both the standard and optional transformer installed
[ ] X [ ] =
4
[ ] X [ ] =
4
5
=
=Amps
. Nonresettable power (100Hz
RMS
. Resettable power (100Hz rip-
RMS
Document #15140 Rev.G 01/02/02 P/N 15140:G
75
Page 76
Programming Reference Sheets
f
f
f f
Appendix B Programming Reference Sheets
...To enter Programming Mode, press the MODE key, the code 7764 and then the [ENTER/STORE] key...
❐00❐01❐02❐03❐04❐05❐06❐07❐08❐09❐10❐11❐12❐13❐14❐
Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.
Primary Central Station Communication Format: Enter '0 - F'.
16
❐17❐18❐19❐ ❐21❐22❐23❐ ❐
Primary Number Test Time Interval. Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
25
Primary Central Station Account Code: Valid entries are '0 - F'.
20
Primary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
24
❐26❐27❐28❐29❐30❐31❐32❐33❐34❐35❐36❐37❐38❐39❐40❐
Addresses 26 to 41 store the Secondary Central Station Phone Number. Enter 'F' to represent the end of the number.
Secondary Central Station Communication Format: Enter '0 - F'.
42
❐43❐44❐45❐ ❐47❐48❐49❐ ❐
Secondary Number Test Time Interval. Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
51
Alarm Verification. Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
52
❐53❐54❐ ❐
Slave Communicator/Fire Panel Selection. Enter '0' for fire panel only; '1' for slave communicator only; '2'
56
or fire panel/communicator operation.
55
Secondary Central Station Account Code: Valid entries are '0 - F'.
46
Secondary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
50
Future use.
15
41
Zone 1 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
57
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
Zone 2 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
58
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
Zone 3 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
59
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6'
or waterflow (nonsilenceable).
Zone 4 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
60
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
Zone 5 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
61
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐62❐ ❐
64
or 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19 hours; 'C' or 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
65
❐66❐67❐
Waterflow Retard timer. Enter 0 - 89 additional seconds.
63
AC Loss Delay. Enter '0' for 6 hour delay; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10 hours; '5'
Alarm Presignal. Enter '0' to disable alarm presignal; '1' to enable.
Alarm Presignal Delay Timer. Enter 0 - 179 additional seconds (default - 120 seconds).
68
69
able); '2' for disabled.
76
Notification Appliance Circuit #1 Selection. Enter '0' for enabled (silenceable); '1' for enabled (nonsilence-
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 77
Programming Reference Sheets
f
f
Silence Inhibit NAC #1. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #1 for one minute.
70
Autosilence NAC #1. Enter '0' for no autosilence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15 minutes; '4'
71
or 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
Coding NAC #1. Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds On, 5 sec-
72
onds Off); '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off).
Notification Appliance Circuit #2 Selection. Enter '0' for enabled (silenceable); '1' for enabled (nonsilence-
73
able); '2' for disabled.
Silence Inhibit NAC #2. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #2 for one minute.
74
Autosilence NAC #2. Enter '0' for no autosilence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15 minutes; '4'
75
or 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
Coding NAC #2. Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds On, 5 sec-
76
onds Off); '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off)
Trouble Reminder. Enter '0' to disable trouble reminder; '1' to enable.
77
Annunciator/Printer Supervision. Enter '0' for annunciator/printer not present; '1' for annunciator present;
78
'2' for printer present; '3' for annunciator and printer present.
Backup Reporting. Enter '0' to report to secondary phone number as backup only; '1' to report to secondary
79
phone number for all reports/messages. Does not affect upload/download messages.
Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.
80
Make/Break Ratio. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
81
Future use.
82
Future use.
83
❐84❐85❐86❐ ❐88❐89❐90❐91❐92❐93❐94❐95❐96❐97❐98❐99❐
Service Terminal #1 Phone Number. Addresses 88 - 103 store the phone number of Service Terminal #1. Enter 'F' to represent the end of the number.
104❐105
106
107❐108❐109❐110❐111❐112❐113❐114❐115❐116❐117❐118❐119❐120❐121❐122
Service Terminal #2 Phone Number. Addresses 107 - 122 store the phone number of Service Terminal #2. Enter 'F'
to represent the end of the number.
Ring Count on Primary Phone Line. Enter number of rings prior to panel answering call.
FAX/Answer Machine, Primary Phone Line. Enter '0' for no sharing of phone line; '1' for sharing.
Panel Identification Number. Valid entries are '0 - F'.
87
100❐101❐102❐103
123❐124
125
126
Station Phone Number on backup only; '1' for Upload/Download reports to always go to the Secondary Number.
Ring Count on Secondary Phone Line. Enter number of rings prior to panel answering call.
FAX/Answer Machine, Secondary Phone Line. Enter'0' for no sharing of phone line; '1' for sharing.
Upload/Download Backup Reporting. Enter '0' for Upload/Download reports to go to the Secondary Central
Document #15140 Rev.G 01/02/02 P/N 15140:G
77
Page 78
Programming Reference Sheets
Programming Reference Sheets
127
140
153
166
179
192
205
218
231
128
141
154
167
180
193
206
219
232
129
142
155
168
181
194
207
220
233
130
143
156
169
182
195
208
221
234
131
144
157
170
183
196
209
222
235
132
145
158
171
184
197
210
223
236
133
146
159
172
185
198
211
224
237
134
147
160
173
186
199
212
225
238
135
148
161
174
187
200
213
226
239
136
149
162
175
188
201
214
227
240
137
150
163
176
189
202
215
228
241
138
151
164
177
190
203
216
229
242
139
152
165
178
191
204
217
230
243
244
257
270
283
296
309
322
335
348
245
258
271
284
297
310
323
336
349
246
259
272
285
298
311
324
337
350
247
260
273
286
299
312
325
338
351
248
261
274
287
300
313
326
339
352
249
262
275
288
301
314
327
340
353
250
263
276
289
302
315
328
341
354
251
264
277
290
303
316
329
342
355
252
265
278
291
304
317
330
343
356
253
266
279
292
305
318
331
344
357
254
267
280
293
306
319
332
345
358
255
268
281
294
307
320
333
346
359
256
269
282
295
308
321
334
347
360
78
361
374
362
363
Document #15140 Rev.G 01/02/02 P/N 15140:G
364
365
366
367
368
369
370
371
372
373
Page 79
Programming Reference Sheets
Programming Reference Sheets - Factory Default Settings
...To enter Programming Mode, press the MODE key, the code 7764 and then the [ENTER/STORE] key...
FFFFFFFFFFFFFFFF
❐00❐01❐02❐03❐04❐05❐06❐07❐08❐09❐10❐11❐12❐13❐14❐
Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.
E
Primary Central Station Communication Format: 'E' for Ademco Contact ID.
16
0000
❐17❐18❐19❐
2345
❐21❐22❐23❐
0
Primary Number Test Time Interval. '0' for 24 hours.
25
FFFFFFFFFFFFFFFF
❐26❐27❐28❐29❐30❐31❐32❐33❐34❐35❐36❐37❐38❐39❐40❐
Addresses 26 to 41 store the Secondary Central Station Phone Number. Enter 'F' to represent the end of the number.
E
Secondary Central Station Communication Format: ‘E' for Ademco Contact ID.
42
0000
❐43❐44❐45❐
0000
❐47❐48❐49❐
0
Secondary Number Test Time Interval. 0' for 24 hours.
51
0
Alarm Verification. '0' for no verification.
52
000
❐53❐54❐
0
Slave Communicator/Fire Panel Selection. 0' for fire panel only operation.
56
0
Zone 1 Function Select. '0' for 2-wire smoke detectors.
57
0
Zone 2 Function Select. '0' for 2-wire smoke detectors.
58
0
Zone 3 Function Select. '0' for 2-wire smoke detectors.
59
0
Zone 4 Function Select. '0' for 2-wire smoke detectors.
60
0
Zone 5 Function Select. '0' for 2-wire smoke detectors.
61
00
❐62❐
0
AC Loss Delay. '0' for 6 hour delay.
64
0
Alarm Presignal. '0' for no alarm presignal.
65
120
❐66❐67❐
0
Notification Appliance Circuit #1 Selection. '0' for enabled (silenceable).
69
0
Silence Inhibit NAC #1. '0' for no silence inhibit.
70
0
Autosilence NAC #1. '0' for no autosilence.
71
0
Coding NAC #1. '0' for steady no coding.
72
0
Notification Appliance Circuit #2 Selection. '0' for enabled (silenceable).
73
55
Waterflow Retard timer. '00' for no delay.
63
68
Primary Central Station Account Code.
20
Primary Central Station 24-Hour Test Time. 2345 = 11:45 PM.
24
Secondary Central Station Account Code.
46
Secondary Central Station 24-Hour Test Time. 0000 = 12:00 midnight.
50
Future use.
Alarm Presignal Delay Timer. 120 second alarm presignal delay.
15
41
Document #15140 Rev.G 01/02/02 P/N 15140:G
79
Page 80
Programming Reference Sheets
0
Silence Inhibit NAC #2. '0' for no silence inhibit.
74
0
Autosilence NAC #2. '0' for no autosilence.
75
0
Coding NAC #2. '0' for steady no coding.
76
0
Trouble Reminder. '0' for no trouble reminder.
77
0
Annunciator/Printer Supervision. '0' for annunciator/printer not present.
78
0
Backup Reporting. '0' to report to secondary phone number as backup only.
79
0
Touchtone/Rotary Select. '0' for touchtone dialing.
80
0
Make/Break Ratio. '0' for 67/33 ratio.
81
0
Future use. Leave default of '0'.
82
0
Future use. Leave default of '0'.
83
0000
❐84❐85❐86❐
Panel Identification Number. Default is '0000'.
87
FFFFFF FFFFFFF FFF
❐88❐89❐90❐91❐92❐93❐94❐95❐96❐97❐98❐99❐
Service Terminal #1 Phone Number. Enter 'F' to represent the end of the number.
03
104❐105
0
106
FFFFFF FFFFFFF FFF
107❐108❐109❐110❐111❐112❐113❐114❐115❐116❐117❐118❐119❐120❐121❐122
Service Terminal #2 Phone Number. Enter 'F' to represent the end of the number.
03
123❐124
0
125
0
126
tion Phone Number on backup only.
Ring Count on Primary Phone Line. Default is '03' for do not answer until 3 rings are detected.
FAX/Answer Machine, Primary Phone Line. '0' for no sharing of phone line.
Ring Count on Secondary Phone Line. Default is '03' for do not answer until 3 rings are detected.
FAX/Answer Machine, Secondary Phone Line. '0' for no sharing of phone line.
Upload/Download Backup Reporting. '0' for Upload/Download reports to go to the Secondary Central Sta-
100❐101❐102❐103
80
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 81
Programming Reference Sheets
Programming Reference Sheets Factory Default
1111111111111
127
1157057057057
140
0570604301380
153
3803803803803
166
1030231135135
179
2321322354354
192
3303086026084
205
128
141
154
167
180
193
206
129
142
155
168
181
194
207
130
143
156
169
182
195
208
131
144
157
170
183
196
209
132
145
158
171
184
197
210
133
146
159
172
185
198
211
134
147
160
173
186
199
212
135
148
161
174
187
200
213
136
149
162
175
188
201
214
137
150
163
176
189
202
215
138
151
164
177
190
203
216
139
152
165
178
191
204
217
11416412413
218
219
220
221
222
223
224
225
226
227
228
Document #15140 Rev.G 01/02/02 P/N 15140:G
81
Page 82
Operation and Function Modes
Appendix C Operation and Function Modes
C.1 Operation Modes
TABLE C-1:
Operation Modes
CODE ACTIVITY NOTES
6676 (NORM) Returns to normal operation Fire protection is on
7764 (PROG) Enters Program Mode
9255 (WALK) Enters Walktest Mode
4478 (HIST) View History File
8768 (TROU)
Activates internal system voltmeter for trou­bleshooting and diagnosing problems
Sends status, history file, walktest file, trou-
7746 (PRIN)
bleshoot voltages and entire programming selections to printer
5267 (LAMP)
3696 (DOWN)
Turns on all LEDs on the main circuit board and all system annunciators for five seconds
Allows for downloading the entire program file to the panel
4 levels of programming may be entered. Fire protection is off
May select audible walktest function. Fire protection is off
Use display or printer to view History File. Fire protection is off
Fire protection is off while voltmeter function is enabled
Fire protection is off. Requires PRT-24 option module
Fire protection is on
Must have service terminal ready. Fire pro­tection remains on
C.2 Function Modes
TABLE C-2:
CODE ACTIVITY NOTES
3472 (DISA) Allows disabling of any input zone
3622 (ENAB)
3745 (DRIL)
3337 (DEFP)
Function Modes
Allows enabling (return to normal) of any zone
Performs drill function by turning on all NAC outputs
Reprograms all entries for programming back to the original factory settings
May only disable one zone at a time. Places system into trouble
May only enable one zone at a time
Transmission of drill function to Central Sta­tion is defaulted to ON
Entry of code must be performed two times in rapid succession as a safety feature. Use caution when using this feature
82
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 83
Ademco Contact ID Format Event Code Descriptions
Appendix D Ademco Contact ID Format Event
Code Descriptions
This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format.
The reporting structure for the Ademco Contact ID Format is as follows:
SSS 18 QXYZ GG CCC
where
SSSS = Four digit Subscriber ID Account Code (addresses 17 - 20 and 43 - 46)
18 = Identifies transmission as Contact ID to the receiver at the Central Station
Q = Event Qualifier where 1 = New Event and 3 = New Restore
XYZ = Event code (shown in Table 3-3 on page 38 and Table 3-6 on page 43)
GG = Group number
CCC = Zone number
Notes:
GG Group Number is fixed at '00' and cannot be changed.
1.
CCC Zone Number is transmitted as '001' for zone one up to '005' for zone five.
2.
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows:
Time Date Rcvr/Line ID SSSS QXYZ GG CCCC
11:28 03/25 11 7777 E110 00 C001 - general fire alarm on zone one
11:28 03/25 11 7777 E111 00 C002 - smoke detector alarm on zone two
11:28 03/25 11 7777 E380 00 C003 - fault on zone three
11:28 03/25 11 7777 E570 00 C004 - Zone four disabled
11:28 03/25 11 7777 R110 00 C001 - Zone one alarm restored
11:28 03/25 11 7777 R111 00 C002 - smoke detector zone two restored
11:28 03/25 11 7777 R380 00 C003 - zone three fault restored
11:28 03/25 11 7777 R570 00 C004 - zone four reenabled
11:28 03/25 11 7777 E158 00 C005 - high temperature, zone five
11:28 03/25 11 7777 E151 00 C003 - gas detected, zone three
Notes:
18
, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
1.
alarm and trouble report.
Q
, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or
2.
R
for New Restore.
Document #15140 Rev.G 01/02/02 P/N 15140:G
83
Page 84
Ademco Contact ID Format Event Code Descriptions
EVENT CODE CLASSIFICATIONS
1 0 0
ALARMS
Medical Fire Panic Burglary General 24 Hour
2 00
SUPERVISORY
Fire
3 00
TROUBLES
System Sounder/Relay System Peripheral Communication Protective Loop Sensor
400
OPEN/CLOSE
REMOTE ACCESS
Open/Close Remote Access Access Control
5 00
DISABLES/
BYPASSES
System Sounder/Relay System Peripheral Communication
EVENT MESSAGE
Medical Alarms - 100 100 Medical EMERG - Personal Emergency - # 101 Pendant transmitter EMERG - Personal Emergency - # 102 Fail to report in EMERG - Fail to Check-in - #
Fire Alarms - 110 110 Fire Alarm FIRE - Fire Alarm - # 111 Smoke FIRE - Smoke Detector - # 112 Combustion FIRE - Combustion - # 113 Waterflow FIRE - Waterflow - # 114 Heat FIRE - Heat Sensor - # 115 Pull station FIRE - Pull Station - # 116 Duct FIRE - Duct Sensor - # 117 Flame FIRE - Flame Sensor - # 118 Near Alarm FIRE - Near Alarm - #
600 TEST/ MISC.
Te st
Panic Alarms - 120 120 Panic Alarm PANIC - Panic - # 121 Duress PANIC - Duress 122 Silent PANIC - Silent Panic - # 123 Audible PANIC - Audible Panic - #
Burglar Alarms - 130 130 Burglary BURG - Burglary - # 131 Perimeter BURG - Perimeter - # 132 Interior BURG - Interior - # 133 24-Hour BURG - 24-Hour - # 134 Entry/Exit BURG - Entry/Exit - # 135 Day/Night BURG - Day/Night - # 136 Outdoor BURG - Outdoor - # 137 Tamper BURG - Tamper - # 138 Near Alarm BURG - Near Alarm - #
General Alarms - 140 140 General Alarm ALARM - General Alarm - # 141 Polling loop open ALARM - Polling Loop Open - # 142 Polling loop short ALARM - Polling Loop Short - # 143 Expansion module failure ALARM - Exp. Module Fail - # 144 Sensor tamper ALARM - Sensor Tamper - # 145 Expansion module tamper ALARM - Exp. Module Tamper - #
84
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 85
Ademco Contact ID Format Event Code Descriptions
EVENT MESSAGE
24 Hour Non-Burglary - 150 and 160 150 24-Hour Non-Burg ALARM - 24-Hr. Non-Burg - # 151 Gas detected ALARM - Gas Detected - # 152 Refrigeration ALARM - Refrigeration - # 153 Loss of heat ALARM - Heating System - # 154 Water leakage ALARM - Water Leakage - # 155 Foil break ALARM - Foil Break - # 156 Day trouble ALARM - Day Zone - # 157 Low bottled gas level ALARM - Low Gas Level - # 158 High temp ALARM - High Temperature - # 159 Low temp ALARM - Low Temperature - # 161 Loss of air flow ALARM - Air Flow - #
Fire Supervisory - 200 and 210 200 Fire supervisory SUPER. - Fire Supervisory - # 201 Low water pressure SUPER. - Low Water Pressure - # 202 Lox CO2 SUPER. - Low CO2 203 Gate valve sensor SUPER. - Gate Valve - # 204 Low water level SUPER. - Low Water Level - # 205 Pump activated SUPER. - Pump Activation - # 206 Pump failure SUPER. - Pump Failure - #
System Troubles - 300 and 310 300 System trouble TROUBLE - System Trouble 301 AC loss TROUBLE - AC Power 302 Low system battery TROUBLE - System Low Battery 303 RAM checksum bad TROUBLE - Bad RAM Checksum (Restore not applicable) 304 ROM checksum bad TROUBLE - Bad ROM Checksum (Restore not applicable) 305 System reset TROUBLE - System Reset (Restore not applicable) 306 Panel program changed TROUBLE - Programming Changed (Restore not applicable) 307 Self-test failure TROUBLE - Self Test Failure 308 System shutdown TROUBLE - System Shutdown 309 Battery test failure TROUBLE - Battery Test Failure 310 Ground fault TROUBLE - Ground Fault - # 311 No battery TROUBLE - No Battery
Sounder/Relay Troubles - 320 320 Sounder/Relay TROUBLE - Sounder Relay - # 321 Bell 1 TROUBLE - Bell/Siren #1 322 Bell 2 TROUBLE - Bell/Siren #2 323 Alarm relay TROUBLE - Alarm Relay 324 Trouble relay TROUBLE - Trouble Relay 325 Reversing TROUBLE - Reversing Relay 326 Bell 3 TROUBLE - Bell/Siren #3 327 Bell 4 TROUBLE - Bell/Siren #4
System Peripheral Troubles - 330 and 340 330 System peripheral TROUBLE - Sys. Peripheral - # 331 Polling loop open TROUBLE - Polling Loop Open 332 Polling loop short TROUBLE - Polling Loop Short 333 Expansion module failure TROUBLE - Exp. Module Fail - # 334 Repeater failure TROUBLE - Repeater Failure - # 335 Local printer paper out TROUBLE - Printer Paper Out 336 Local printer failure TROUBLE - Local Printer
Document #15140 Rev.G 01/02/02 P/N 15140:G
85
Page 86
Ademco Contact ID Format Event Code Descriptions
EVENT MESSAGE
Communication Troubles - 350 and 360 350 Communication TROUBLE - Communication Trouble 351 Telco 1 fault TROUBLE - Phone Line #1 352 Telco 2 fault TROUBLE - Phone Line #2 353 Long range radio xmitter fault TROUBLE - Radio Transmitter 354 Fail to communicate TROUBLE - Fail to Communicate 355 Loss of radio supervision TROUBLE - Radio Supervision 356 Loss of central polling TROUBLE - Central Radio Polling
Protection Loop Troubles - 370 370 Protection loop TROUBLE - Protection Loop - # 371 Protection loop open TROUBLE - Protection Loop Open - # 372 Protection loop short TROUBLE - Protection Loop Short - # 373 Fire Trouble TROUBLE - Fire Loop - #
Sensor Troubles - 380 380 Sensor trouble TROUBLE - Sensor Trouble - # 381 Loss of supervision - RF TROUBLE - RF Sensor Supervision - # 382 Loss of supervision - RPM TROUBLE - RPM Sensor Supervision - # 383 Sensor tamper TROUBLE - Sensor Tamper - # 384 RF transmitter low battery TROUBLE - RF Sensor Batt. - #
Open/Close - 400 400 Open/Close OPENING CLOSING 401 Open/Close by user OPENING - User # CLOSING - User # 402 Group Open/Close OPENING - Group User # CLOSING - Group User # 403 Automatic Open/Close OPENING - Automatic CLOSING - Automatic 404 Late Open/Close OPENING - Late CLOSING - Late 405 Deferred Open/Close Opening not used Closing not used 406 Cancel OPENING - Cancel Closing not used 407 Remote arm/disarm OPENING - Remote CLOSING - Remote 408 Quick arm Opening not applicable CLOSING - Quick arm 409 Keyswitch Open/Close OPENING - Keyswitch CLOSING - Keyswitch
Remote Access - 410 411 Callback request made REMOTE - Callback Requested Restore not applicable 412 Success - download/access REMOTE - Successful Access Restore not applicable 413 Unsuccessful access REMOTE - Unsuccessful Access Restore not applicable 414 System shutdown REMOTE - System Shutdown 415 Dialer shutdown REMOTE - Dialer Shutdown 416 Success - upload/access REMOTE - Successful Access Restore not applicable
Access Control - 420 421 Access denied ACCESS - Access Denied - User # Restore not used 422 Access report by user ACCESS - Access Gained - User # Restore not used
System Disables - 500 and 510
86
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 87
Ademco Contact ID Format Event Code Descriptions
EVENT MESSAGE
Sounder/Relay Disables - 520 520 Sounder/Relay disable DISABLE - Sounder/Relay - # 521 Bell 1 disable DISABLE - Bell/Siren - #1 522 Bell 2 disable DISABLE - Bell/Siren - #2 523 Alarm relay disable DISABLE - Alarm Relay 524 Trouble relay disable DISABLE - Trouble Relay 525 Reversing relay disable DISABLE - Reversing Relay 526 Bell 3 disable DISABLE - Bell/Siren - #3 527 Bell 4 disable DISABLE - Bell/Siren - #4
System Peripheral Disables - 530 and 540
Communication Disables - 550 and 560 551 Dialer disabled DISABLE - Dialer Disable 552 Radio transmitter disabled DISABLE - Radio Disable
Bypasses - 570 570 Zone bypass BYPASS - Zone Bypass - # 571 Fire bypass BYPASS - Fire Bypass - # 572 24-Hour zone bypass BYPASS - 24-Hour Bypass - # 573 Burglar bypass BYPASS - Burg. Bypass - # 574 Group bypass BYPASS - Group Bypass - #
Test Misc. - 600 601 Manual trigger test TEST - Manually Triggered Restore not applicable 602 Periodic test report TEST - Periodic Restore not applicable 603 Periodic RF transmission TEST - Periodic Radio Restore not applicable 604 Fire test TEST - Fire Test Restore not used 605 Status report to follow STATUS - Status Follows Restore not applicable 606 Listen-in to follow LISTEN - Listen-in Active Restore not applicable 607 Walk test mode TEST - Walk Test Mode 608 System abnormal test TEST - System Abnormal Test
Document #15140 Rev.G 01/02/02 P/N 15140:G
87
Page 88
Notes
88
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 89
Index
Numerics
1st EVENT 13, 51
A
AC Line Voltage 65 AC Loss Reporting Delay 46 AC Power 16 AC Power LED 13, 52 Ademco Contact ID format 83 Ademco Express 14 ADM-24 29 ADM-24 Annunciator Driver
Module 15, 28 Alarm LED 13, 52 Alarm Presignal 46 Alarm Presignal Delay Timer 46 Alarm Response 53 Alarm Restoral 54 Alarm Verification 44 Alarm verification 10 Annunciator/Printer Supervision 47 Autosilence 10 Autosilence Notification Appliance
Circuit #1 46 Autosilence Notification Appliance
Circuit #2 46 Auxiliary Output 17 Auxiliary Power 24
B
Backbox 19 backbox
see also cabinet 14 Backup Reporting 47 battery 15, 16
Charger Capacity 16
Charging Circuit 16 battery box 15, 16, 21 Battery Calculations 73 Battery Charger 13 Battery Voltage 65 BB-17F 16
see also battery box 15
C
cabinet 14 Cabinet Dimensions 20 CAC-5F Class A Converter
Module 10, 15, 32 Callback 70 Central Station 10, 70 Central Station Communications 57 Circuit
Input 13 Output 13
circuit
Input 23 output 24
Coding Notification Appliance Circuit
#1 46 Coding Notification Appliance Circuit
#2 47 Communication Failure 17 communication format 14 Controls 13
D
Default Programming 49
Digital Communicator 14, 18, 27 digital communicator 10 Display 51
see also Indicators 13 Downloading 69, 71 DP-5024UD 14
see also Dress Panel 11 Dress Panel 11, 16
E
Earth Ground 22 End Programming 49 ENTER/STORE 13, 51 Error Checking 70 event code classification 84
F
FAX/Answer Machine, Primary Phone
Line 48
FAX/Answer Machine, Secondary
Phone Line 48 Fire Drill 56 Fire Panel 10 Format Selection Address 58 Formats 38, 43 Form-C 25
see also relay 17 four-wire smoke detector 10 Four-Wire Smoke Detector Power 17
Current 17 Function Modes 82 Function Selection 45
H
History file 10 History Mode 50, 63
I
IDC
current 23
see also Initiating Device Circuit 23 Indicators 13 Initiating Device Circuit 16
Alarm Current 16
End-of-Line Resistor 16
Maximum Loop Resistance 16
Normal Operating Voltage 16
Short Circuit Current 16
Standby Current 16 Installation 19
K
Keypad 34 Kissoff 10 Kissoff LED 13, 52
L
Lamp Test 66 Line Seizure 14
M
Main Circuit Board 9, 14 Make/Break Ratio 47 MODE 13, 51 Modem LED 13, 52 Mounting 19 MS-5024UD 10
N
NAC 24, 66
current/circuit 17 End-of-Line Resistor 17 Maximum Current 17 Operating Voltage 17 see also Notification Appliance
Circuit 10
Nonresettable Filtered 24V Power 17
Current 17 Nonresettable Power 13 Normal Mode 50 Notification Appliance Circuit 10, 12,
14, 17, 24
Notification Appliance Circuit #1
Enable 46
Notification Appliance Circuit #2
Enable 46
O
Off Normal Reporting 55 Operating Instructions 50 Operation 53 Operation Modes 82
P
Panel Identification Number 47, 70 Piezo
see also Sounder 13 PK-5024UD 10, 16 Power 22 Primary Central Station Number 24
Hour Test Time 39
Primary Central Station Number 24/12/
8/6 Hour Test Time Interval 39
Primary Central Station Number
Account Code 39
Primary Central Station Number
Communication Format 35
Primary Central Station Phone
Number 34 Primary Line Active LED 52 Primary Phone Line 14 Primary Phone Line Active LED 13 primary phone number 33 Primary Power
see also AC Power 22 Primary Telephone Line 13 Print Mode 50, 66 Printer Configuration 30 Printer Port 13 Product Description 10 Product Features 10 Program Mode 33, 50 Programmable Zone ID 10 programmer 33 programmer, built-in 10 Programming 76 Programming Event Codes 48 Programming Instructions 33 Programming Options 34 PRT-24
Installation 30 PRT-24 Printer Interface Modul 16 PRT-24 Printer Interface Module 11,
30
pull station 10, 23
Document #15140 Rev.G 01/02/02 P/N 15140:G 89
Page 90
R
Real-Time Clock and Calendar 48 Real-Time clock and calendar 10 Receivers 61 Relay 14 relay 10, 11, 12, 17, 25
contact rating 14, 17, 25 driver 14, 17, 25
REN
see also Ringer Equivalence
Number 18 RESET 13, 50 Resettable Power 13, 66 Ring Count on Primary Phone Line 47 Ring Count on Secondary Phone
Line 48 Ringer Equivalence Number 18 RM-5F Five-Zone Relay Module 15,
31 RM-5F Relay Module 10 RZA-5F 29 RZA-5F Remote Annunciator 15, 28
S
Secondary Central Station Number 24
Hour Test Time 44 Secondary Central Station Number 24/
12/8/6 Hour Test Time
Interval 44 Secondary Central Station Number
Account Code 44 Secondary Central Station Number
Communication Format 40 Secondary Central Station Phone
Number 39 Secondary Line Active LED 52 Secondary Phone Line 14 Secondary Phone Line Active LED 13 secondary phone number 33 Secondary Power
see also battery 22 Secondary Telephone Line 13 Secret Code 70 Security Features 70 Service Terminal 10 Service Terminal Number 1 Phone
Number 47
Service Terminal Number 2 Phone
Number 48 Servicing 62 SILENCE 13, 51 Silence inhibit 10 Silence Inhibit Notification Appliance
Circuit #1 46 Silence Inhibit Notification Appliance
Circuit #2 46 Silence LED 13, 52 Slave Communicator 10 slave communicator 10, 67 Slave Communicator/Fire Panel
Selection 44 Sounder 13 sounder 15 Specifications 16 Style B 10, 13, 23, 32 Style D 10, 13, 23, 32 Style Y 10, 14 Style Z 10, 14 Supervisory Condition Response 54
Supervisory LED 13, 52 Supervisory Restoral Response 54 Switch Functions 34
T
Telephone Circuit 24 Telephone Circuitry 18 Telephone Company
Rights and Warnings 18 telephone line 27 Telephone Lines 65 Time-out 70 Tone Burst 14 Touchtone 14 Touchtone/Rotary Select 47 transformer 12, 15 Transmittal Priorities 60 Trouble Condition Response 55 Trouble Condition Restoral 55 Trouble LED 13, 52 Trouble Reminder 47 Trouble reminder 10 Troubleshoot Mode 50, 64 two-wire smoke detector 10, 23
U
UL Power-limited Wiring
Requirements 26 Upload/Download 69 Upload/Download Reports 48 Uploading 72
V
Vo l t a g e s 6 4 voltmeter, built-in 10
W
Walktest Mode 50, 62 waterflow 23 waterflow device 10 Waterflow Retard Timer 45
X
XRM-24
see also transformer 15
Z
Zone Disable/Enable 56 Zone Voltages 64
90
Document #15140 Rev.G 01/02/02 P/N 15140:G
Page 91
Limited Warranty
The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of original purchase by the manufacturer's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired, or serviced by anyone other than the manufacturer or its authorized distributors, or if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its products. The manufacturer does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
LimWarLg.p65 01/10/2000
Page 92
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...