While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power.
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.
Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
FIGURE 1-2: MS-5024 Control Panel.................................................................................................12
1.2: Controls and Indicators ...............................................................................................................................13
1.2.1: Front Panel Switches ........................................................................................................................13
FIGURE 1-3: Controls and Indicators .................................................................................................13
1.2.2: Display and Indicators ......................................................................................................................13
1.2.3: Local Sounder ...................................................................................................................................13
1.4: Digital Communicator.................................................................................................................................14
1.5.1: Main Circuit Board ...........................................................................................................................14
2.6: UL Power-limited Wiring Requirements ....................................................................................................26
Document 50066 Rev. D2 12/03/02 P/N: 50066:D25
Table of Contents
FIGURE 2-8: Typical Wiring Diagram for UL Power-limited Requirements ....................................26
2.7: Digital Communicator.................................................................................................................................27
3.1: Entering Program Mode ..............................................................................................................................31
4.1.5: Down Arrow......................................................................................................................................47
4.1.6: Up Arrow...........................................................................................................................................47
4.2: Display and LEDs........................................................................................................................................47
FIGURE 4-1: Phone Connectors and LEDs.........................................................................................48
4.3.7: Off Normal Reporting .......................................................................................................................51
4.3.8: Zone Disable/Enable .........................................................................................................................51
4.3.9: Fire Drill............................................................................................................................................52
4.3.10: No Battery/Low Battery..................................................................................................................52
4.4: Central Station Communications.................................................................................................................52
TABLE 4-1: Format Selection Addresses (16 & 42)...........................................................................53
TABLE 4-2: Format Selection Address Explanation...........................................................................54
5.2: History Mode...............................................................................................................................................58
5.3.2: AC Line.............................................................................................................................................59
5.4: Lamp Test ....................................................................................................................................................60
TABLE D-2: Function Modes ............................................................................................................73
Document 50066 Rev. D2 12/03/02 P/N: 50066:D27
Notes
8
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code for Local, Remote Station and Central Station Fire Alarm Systems
• CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code for Central Station Signaling Systems Protected Premises Unit
(Automatic, Manual and Waterflow), Local Fire Alarm Systems and Remote Station Fire Alarm
Systems.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524M Standard for Installation of Fire Alarm Systems
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
C22.1, Canadian Electrical Code, Part I
C22.2 No. 0, General Requirements - Canadian Electrical Code, Part II
C22.2 No. 0.4, Bonding and Grounding of Electrical Equipment (Protective Grounding) - Canadian
C282, Emergency Electrical Power Supply for Buildings - Canadian
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Note: When dressing wires, maintain a minimum of 0.25" distance between conductors to power-limited and
nonpower-limited circuits.
10
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Product Description
CHAPTER 1Product Description
The MS-5024 is a combination control panel and digital communicator all on one circuit board. It is a five-zone
panel which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, fourwire smoke detectors, pull stations and other normally open contact devices. Outputs include two NACs (Notification Appliance Circuits) and two programmable relays.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to UL listed Central Stations via
the public switched telephone network. The control panel has a built-in programmer and may also serve as a slave
communicator to a host control panel. It also supervises all wiring, AC voltage, telephone line input voltage and
battery level.
The MS-5024E offers the same features as the MS-5024 but allows connection to 220/240 VAC input. Note that
unless otherwise specified, the term MS-5024 shall be used in this manual to refer to both the MS-5024 and
MS-5024E Fire Control Communicators.
1.1Product Features
• Selectable as Fire Panel, Fire Panel/Communicator or Slave Communicator
• Programmable Zone ID:
✓2-wire smoke
✓Pull station
✓Normally open contact
✓Supervisory
✓Supervisory auto-resettable
✓Waterflow silenceable
✓Waterflow nonsilenceable
• One Style D (Class A) Initiating Zone
• Four Style B (Class B) Initiating Zones
• 3.6 amps usable power
• Two NFPA Style Y (Class B) Notification Appliance Circuits
• Small size - 14.5" (36.83 cm) X 12.5" (31.75 cm) X 2.875" (7.303 cm)
• History file with 32 event storage
• Silence inhibit per NAC
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
11
Product Features
• Auto-silence per NAC
• Touchtone/rotary dialing
• Programmable make/break ratio
• Fuseless design
• Number of dial attempts (5 minimum, 10 maximum)
• Programmable channel ID (slave)
• Programmable zone delay (waterflow only)
• Two Form-C programmable relays
• Low AC voltage sense
•One-man Walktest
• Optional Dead Front cover (DP-5024)
• CAC-5F Class A Converter module for Initiating Device Circuits
• NACA-2F Class A Converter module for Notification Appliance Circuits
FIGURE 1-2:
MS-5024 Control Panel
Notification
Appliance
Programmable
Relays
Circuits
FIGURE 1-1:
5 Input
Zones
DP-5024
Four
Character
7-Segment
LED Display
Piezo 85dB
BELLS
1 2
112234
TB5
24V NONRESETTABLE
1234
TB4
24V
RESETTABLE
NO NC C NO NC C
TB3
ZONE 4 ZONE 5
ZONE 3
ZONE 1 ZONE 2
B+ B- B+ B- B+ A+ A- B- B+ B- B+ B-
TB2
Annunciator
Driver Module
Interface
Connector
TB1
J1
TEST CONNECTOR
KISS OFF
/LOAD
LED 3
J3
PRIMARY SECONDARY
PRIMARY
ACTIVE
LED 1
SECONDARY
ACTIVE
LED 2
Primary &
Secondary
Phone Lines
Keypad
12
Holds up to 7 AH Batteries Up to 60 Hrs. of Standby
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Controls and Indicators
1.2Controls and Indicators
1.2.1 Front Panel Switches
RESETDigits 0 - 9
SILENCEA
MODEB
Up ArrowC
Down ArrowD
1st EVENTE
ENTER/STOREF
1.2.2 Display and Indicators
• Four 7-Segment Displays - red
• Alarm - red LED
• Trouble - yellow LED
• Supervisory - yellow LED
• Silence - yellow LED
• AC Power - green LED
• Primary Phone Line Active - red LED
• Secondary Phone Line Active - red LED
• 'Kissoff' Signal from Central Station - green LED
FIGURE 1-3:
Controls and Indicators
1.2.3 Local Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions.
1.3Circuits
1.3.1 Input Circuits
Five input circuits provide Style B configuration with one circuit also configurable for Style D. Input circuits may be
used as standard fire control panel zones or slave communicator input channels.
• Initiating Device Circuit 1 (Style B) accepts Normally Open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 2 (Style B) accepts Normally Open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 3 (Style B/D) accepts Normally Open contact devices, 2-wire smoke detectors and
waterflow devices
• Initiating Device Circuit 4 (Style B) accepts Normally Open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 5 (Style B) accepts Normally Open contact devices and 2-wire smoke detectors
1.3.2 Output Circuits
• 24 Volt Resettable Power Output
• 24 Volt Nonresettable Power Output
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
13
Digital Communicator
1.3.3 Notification Appliance Circuits
Two NACs (Notification Appliance Circuits) configurable for Style Y (Class B) with various programmable features.
1.3.4 Relays
Two dry Form-C relay contacts programmable for Alarm, Trouble, Supervisory and/or Communications Failure.
Contacts are rated 2 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive).
1.4Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the
Primary and Secondary phone lines. Telephone line active red LEDs are provided as well as a green 'Kissoff” LED.
The integral digital communicator provides the following functions:
• Line Seizure - takes control of the phone lines, disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) number - default is Touch-Tone
• For tone burst or touchtone type formats: discern proper 'Ack' and 'Kissoff' tone(s) - the frequency and time
duration of the tone(s) vary with the transmission format. The control panel will adjust accordingly
• Communicate in the following formats:
✓
12 Tone Burst Types: 20 pps
(3+1, 4+1 and 4+2 Standard, 3+1 Expanded, 4+1 Expanded, 4+2 Expanded)
✓
2 Touchtone Types:
4+1 Ademco Express and 4+2 Ademco Express
Refer to Table 4-3, “Compatible UL Listed Receivers,” on page 56 for a list of compatible receivers.
®
, programmable to rotary
1.5Components
1.5.1 Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface
connectors. Optional modules plug in and are mounted to the main circuit board. The main circuit board is delivered
premounted in the cabinet.
1.5.2 Cabinet
The cabinet is red with an attractive navy blue front overlay. The backbox measures 14.5" (36.83 cm) X 12.5" (31.75
cm) X 2.875" (7.303 cm) and provides space for two batteries (up to 7 Amp Hour). Also available is an optional
dress panel (DP-5024), which mounts inside the cabinet.
1.5.3 Transformer Assembly
One 100 VA transformer is provided standard with the panel.
14
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Optional Devices
1.5.4 Batteries
The cabinet provides space for 7 Amp Hour batteries (for 12 Amp Hour to 18 Amp Hour batteries use the UL listed
BB-17F battery box). Batteries must be ordered separately.
1.6Optional Devices
1.6.1 ADM-24
The ADM-24 Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is
supervised for open circuits by this module. The Annunciator Driver Module mounts to connector J3 in the upper
right corner of the main board. Refer to Figure 1-2 on page 12 and Figure 2-10 on page 28.
1.6.2 RZA-5F
The RZA-5F Remote Annunciator mounts on a standard single-gang box and provides LED indications of the
following:
✓
Alarm Zone 1 (red LED)
✓
Alarm Zone 2 (red LED)
✓
Alarm Zone 3 (red LED)
✓
Alarm Zone 4 (red LED)
✓
Alarm Zone 5 (red LED)
✓
System Trouble (yellow LED)
A Local Trouble Sounder and Tone Silence Switch are also provided. All LEDs and their wiring are supervised for
open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide in paper labels permit
an easy change of zone information (refer to Figure 2-11 on page 28). Note that the RZA-5F Remote Annunciator
requires the use of the ADM-24 Annunciator Driver Module. Only one ADM-24/RZA-5F combination is allowed per
system.
1.6.3 CAC-5F
The CAC-5F Class A Converter module converts the Style B (Class B) Initiating Device Circuits to Style D (Class
A). The CAC-5F mounts to terminal block TB2 located in the upper right corner of the main circuit board (refer to
Figure 1-2 on page 12 and Figure 2-15 on page 30). The removable terminal block on the CAC-5F module provides
for ease of wiring.
1.6.4 NACA-2F
The NACA-2F Notification Appliance Circuit Class A Converter module converts the two NAC circuits from Style
Y (Class B) to Style Z (Class A). The converter module mounts to terminal block TB5 located in the upper left corner of the main circuit board (refer to Figure 1-2 on page 12 and Figure 2-14 on page 30). The removable terminal
block on the NACA-2F module provides for ease of wiring.
1.6.5 DP-5024
The DP-5024 Dress Panel is red and is available as an option (required for Canadian installations). The dress panel
restricts access to the system wiring while allowing access to the membrane switch panel (refer to Figure 1-1 on page
12).
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
15
Specifications
1.6.6 BB-17F
The BB-17F Battery Box may be used to house two 12 Amp Hour or 18 AMP Hour batteries. The battery box
mounts directly below the control panel cabinet (refer to Figure 2-2 on page 21). The BB-17F is red and is provided
with knockouts.
1.7Specifications
AC Power - TB1
MS-5024: 120 VAC, 60 Hz, 1.2 amps
MS-5024E: 220/240 VAC, 50 Hz, 0.6 amps
Supervised for AC loss and brownout
Wire size: minimum 14 AWG (2.00 mm
Battery (lead acid only) - J1
Maximum charging circuit: Normal Flat Charge - 27.6V @ 0.8 amp
Maximum charger capacity: 17 Amp Hour battery (MS-5024 cabinet holds maximum 7 Amp Hour battery. Larger
batteries require Fire•Lite BB-17F or other UL listed battery cabinet).
Supervised for low and no battery
2
) with 600V insulation
Initiating Device Circuits - TB2
Detector zones 1, 2, 3, 4 and 5
Power-limited circuitry
Operation: All zones (NFPA Style B), Zone 3 (NFPA Style B or D). Use CAC-5F for Style D operation
Normal operating voltage: 24 VDC (ripple = 100mV maximum)
Alarm current: 26 mA Short circuit current: 42 mA maximum
Maximum loop resistance: 100 ohms
End-of-Line Resistor: 4.7K, ½ watt (P/N 27072 UL listed)
Detector loop current sufficient to ensure operation of one alarmed detector/zone
Standby current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuits - TB5
Nonregulated special purpose power, Style Y supported. Use NACA-2F for Style Z operation
Power-limited circuitry
Operating voltage nominal 24 volts
Current limit: PTC Maximum signaling current/circuit: 1.5 amps (3.0 amps max. for all external devices
End-of-Line Resistor: 4.7K, ½ watt (P/N 71252 UL listed) for Notification Appliance Circuits
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Four-Wire Smoke Detector Power - TB4, Terminals 3(+) & 4(-)
Maximum ripple voltage: 10 mV
Operating voltage: nominal 24 volts
RMS
Up to 300 mA is available for powering 4-wire smoke detectors
Power-limited circuitry Maximum standby current: 50 mA
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
16
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Telephone Requirements and Warnings
Nonresettable 24 VDC Power - TB4, Terminals 1(+) & 2(-)
Maximum ripple voltage: 10 mV
Operating voltage: nominal 24 volts
RMS
Total DC current available from this output is up to 300 mA
Power-limited circuitry Maximum standby current is 150 mA
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Notes:
For power supply calculations, refer to “Battery Calculations” on page 63
1.
Total current for nonresettable power, 4-wire smoke power and two NACs must not exceed 3.6 amps
2.
1.8Telephone Requirements and Warnings
1.8.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 1.3B
AC Impedance 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.
1.8.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Note: The FCC ID label is located on the inside of the control panel door.
1.8.3 Telephone Company Rights and Warnings
The telephone company under certain circumstances may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the
telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
17
Telephone Requirements and Warnings
When the control panel activates, premises phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone
system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
1.8.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the
appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the
equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The
customer should be aware that compliance with the above conditions may not prevent degradation of service in some
situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the
supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the
telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone
lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly
important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection
authority or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum
number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of
any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
Representative:NOTIFIER, CANADA
24 Viceroy Road
Concord, Ontario L4K2L9
IC Certificate Number: 21325785A
Ringer Equivalence Number (REN): 1.3B
Load Number: 2
18
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Installation
CHAPTER 2Installation
2.1Mounting Options
The cabinet may be either semi-flush or surface mounted. The
door is removable during the installation period by opening
and lifting off the hinges. The cabinet mounts using two key
slots and two additional 0.250" diameter holes located in the
backbox. The key slots are located at the top of the backbox
and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage.
Mount the cabinet in a clean, dry, vibration-free area where
extreme temperatures are not encountered. The area should be
readily accessible with sufficient room to easily install and
maintain the panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on
the left. Determine the number of conductors required for the
devices to be installed. Sufficient knockouts are provided for
wiring convenience. Select the appropriate knockout(s) and
pull the required conductors into the box. Note that there are
no knockouts located on the left (hinged) side of the cabinet.
All wiring should be in accordance with the National and/or
Local codes for fire alarm systems.
2.2Backbox Mounting
• Refer to Figure 2-1 on page 20 and Figure 2-2 on page 21
• Make certain there is no power (AC or DC) applied to the control panel
• Open the door and lift the door off the pin hinges
• Remove AC wiring
• Remove the main PC board assembly by unscrewing the five screws in the corners of the board. Two standoffs support the board in the center. Set the board aside in a safe, clean place. Avoid static discharge which
may damage the board
• Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown
• Install two upper fasteners in the wall with the screw heads protruding
• Using the upper 'keyholes', mount the backbox over the two screws
• Mark and drill the lower two holes
• Mount backbox, install remaining fasteners and tighten
• When the location is dry and free of construction dust, reinstall the main PC board
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
19
Backbox Mounting
(
)
(
)
(
)
(
)
Draw wires through the respective knockout locations.
2. Remove appropriate knockouts from the MS-5024 cabinet and BB-17F
3. Position the BB-17F near the MS-5024 cabinet and connect with conduit, making sure there is at least ½" of
clearance between the two cabinets
4. Anchor the BB-17F to the wall
Document #50066 Rev. D2 12/03/02 P/N 50066:D221
Operating Power
2.3Operating Power
CAUTION! Several different sources of power can be connected to this panel. Disconnect all sources of power
before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules
or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Primary power source for the MS-5024 is 120VAC,
60 Hz, 1.2 amps and for the MS-5024E is 220/240VAC, 50 Hz, 0.6 amps. Run a pair of wires (with ground
conductor) from the protected premises main breaker box to the orange and black primary leads of the MS-5024
transformer. As per the National Electric Code, use 14 AWG (2.00 mm
insulation. No other equipment may be connected to this circuit. In addition, this circuit must be provided with
overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must
be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire,
minimum 14 AWG (2.00 mm
2
), to the grounding stud indicated by the ground symbol label. Note that conduit must
not be used for an Earth Ground connection since this does not provide reliable protection.
Secondary Power Source (batteries)
Observe polarity when connecting the battery. Connect the battery cable to J1 on the main circuit board using the
plug-in connector provided. The battery charger is current-limited and capable of recharging sealed lead acid type
batteries. The charger shuts off when the system is in alarm or if the battery voltage drops too low (below 14.2VDC).
See Appendix A for calculations of the correct battery rating. WARNING! Battery contains sulfuric acid which can
cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately
flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
FIGURE 2-3:
Operating Power Connections
AC Feed
Neutral
Hot
Ground
2
) or heavier gauge wire with 600 V
Orange
Black
Connect Earth
Ground Wire
Red
Ground Stud
Brown
22
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Input Circuits
2.4Input Circuits
The control panel has five zone input circuits. The maximum loop resistance limit for each is 100 ohms. All field
wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated
as well as communicated to a Central Station.
Each zone is a Style B (Class B) Initiating Device Circuit designed to accept any Normally Open contact device and
conventional 2-wire, 24 volt smoke detectors. Each zone is power-limited to 7.26 mA in standby and 42 mA in
alarm. Zone 3 may also be configured as a Style D (Class A) Initiating Device Circuit. Figure 2-5 illustrates typical
circuit connections. Note that all five initiating zones may be converted to Style D (Class A) by using a CAC-5F Class
A Converter module (refer to Figure 2-15 on page 30).
Zones 1-5 may be programmed as shown below. The factory default is 2-wire smoke detector for all zones.
• 2-wire Smoke Detector (factory default)
• Pull Station
• Normally Open Contact Device
• Supervisory
• Supervisory, autoresettable
Zone 3 may also be programmed as:
• Waterflow silenceable
• Waterflow nonsilenceable
Note: A maximum of five waterflow devices may be used on Zone 3 per NFPA 72.
Four-wire smoke detectors may be connected to any zone. Resettable power is provided via TB4, Terminals 3 & 4.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any
zone. However, this is not recommended since specific and detailed reports will not be possible. For example, the
report of general fire alarm versus pull station fire alarm or smoke detector fire alarm.
FIGURE 2-4:
Typical Initiating Device Circuit Connections
Style B Initiating Device Circuit
(supervised and power-limited) 4.7K
ohm, ½ watt P/N 71252 UL listed
Manual Pull Station
Heat Detector
Style D Initiating Device Circuit
(supervised and power-limited)
*Nonresettable Power (300 mA)
24 VDC filtered, nonresettable power can be
obtained from TB4 Terminals 1(+) & 2(-)
Auxiliary Power Connections
+ - + -
1 2 3 4
*4-Wire Smoke Detector Power (300 mA)
24 VDC filtered, resettable power for 4-wire smoke
detectors can be obtained from TB4 Terminals 3(+) & 4(-)
* Refer to the Fire•Lite Device
Compatibility Document for a list of
compatible smoke detectors, notification
appliances and auxiliary devices
2.5.2 Telephone Circuits
Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 (Primary)
and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection (refer to Figure 2-9 on page 27).
The MS-5024 provides two Style Y NACs (Notification Appliance Circuits), each capable of 1.5 amps of current.
Total current drawn from these as well as other DC power outputs cannot exceed 3.6 amps. Circuits are supervised
and power-limited. Figure 2-6 illustrates a typical circuit connection. Refer to the Fire•Lite Device Compatibility
Document for a listing of compatible notification appliances.
Note that both NACs may be converted to Style Z (Class A) by using an NACA-2F Class A Converter module (refer to
Figure 2-14 on page 30).
24
FIGURE 2-6:
Typical NAC Connections
Style Y Notification Appliance
Circuit (supervised and powerlimited). 4.7K ohm, ½ watt
P/N 71252 UL listed
Note: Notification Appliance
Circuit polarity shown in
alarm
state.
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Polarized Bell
Polar ized Hor n
Polar ized Hor n
Dummy Load all unused circuits
P/N 71245
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.