While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power.
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.
Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
FIGURE 1-2: MS-5024 Control Panel.................................................................................................12
1.2: Controls and Indicators ...............................................................................................................................13
1.2.1: Front Panel Switches ........................................................................................................................13
FIGURE 1-3: Controls and Indicators .................................................................................................13
1.2.2: Display and Indicators ......................................................................................................................13
1.2.3: Local Sounder ...................................................................................................................................13
1.4: Digital Communicator.................................................................................................................................14
1.5.1: Main Circuit Board ...........................................................................................................................14
2.6: UL Power-limited Wiring Requirements ....................................................................................................26
Document 50066 Rev. D2 12/03/02 P/N: 50066:D25
Table of Contents
FIGURE 2-8: Typical Wiring Diagram for UL Power-limited Requirements ....................................26
2.7: Digital Communicator.................................................................................................................................27
3.1: Entering Program Mode ..............................................................................................................................31
4.1.5: Down Arrow......................................................................................................................................47
4.1.6: Up Arrow...........................................................................................................................................47
4.2: Display and LEDs........................................................................................................................................47
FIGURE 4-1: Phone Connectors and LEDs.........................................................................................48
4.3.7: Off Normal Reporting .......................................................................................................................51
4.3.8: Zone Disable/Enable .........................................................................................................................51
4.3.9: Fire Drill............................................................................................................................................52
4.3.10: No Battery/Low Battery..................................................................................................................52
4.4: Central Station Communications.................................................................................................................52
TABLE 4-1: Format Selection Addresses (16 & 42)...........................................................................53
TABLE 4-2: Format Selection Address Explanation...........................................................................54
TABLE 4-3: Compatible UL Listed Receivers....................................................................................56
6
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
Notes
8
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code for Local, Remote Station and Central Station Fire Alarm Systems
• CAN/ULC - S527M Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code for Central Station Signaling Systems Protected Premises Unit
(Automatic, Manual and Waterflow), Local Fire Alarm Systems and Remote Station Fire Alarm
Systems.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524M Standard for Installation of Fire Alarm Systems
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
C22.1, Canadian Electrical Code, Part I
C22.2 No. 0, General Requirements - Canadian Electrical Code, Part II
C22.2 No. 0.4, Bonding and Grounding of Electrical Equipment (Protective Grounding) - Canadian
C282, Emergency Electrical Power Supply for Buildings - Canadian
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Note: When dressing wires, maintain a minimum of 0.25" distance between conductors to power-limited and
nonpower-limited circuits.
10
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Product Description
CHAPTER 1Product Description
The MS-5024 is a combination control panel and digital communicator all on one circuit board. It is a five-zone
panel which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, fourwire smoke detectors, pull stations and other normally open contact devices. Outputs include two NACs (Notification Appliance Circuits) and two programmable relays.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to UL listed Central Stations via
the public switched telephone network. The control panel has a built-in programmer and may also serve as a slave
communicator to a host control panel. It also supervises all wiring, AC voltage, telephone line input voltage and
battery level.
The MS-5024E offers the same features as the MS-5024 but allows connection to 220/240 VAC input. Note that
unless otherwise specified, the term MS-5024 shall be used in this manual to refer to both the MS-5024 and
MS-5024E Fire Control Communicators.
1.1Product Features
• Selectable as Fire Panel, Fire Panel/Communicator or Slave Communicator
• Programmable Zone ID:
✓2-wire smoke
✓Pull station
✓Normally open contact
✓Supervisory
✓Supervisory auto-resettable
✓Waterflow silenceable
✓Waterflow nonsilenceable
• One Style D (Class A) Initiating Zone
• Four Style B (Class B) Initiating Zones
• 3.6 amps usable power
• Two NFPA Style Y (Class B) Notification Appliance Circuits
• Small size - 14.5" (36.83 cm) X 12.5" (31.75 cm) X 2.875" (7.303 cm)
• History file with 32 event storage
• Silence inhibit per NAC
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
11
Product Features
• Auto-silence per NAC
• Touchtone/rotary dialing
• Programmable make/break ratio
• Fuseless design
• Number of dial attempts (5 minimum, 10 maximum)
• Programmable channel ID (slave)
• Programmable zone delay (waterflow only)
• Two Form-C programmable relays
• Low AC voltage sense
•One-man Walktest
• Optional Dead Front cover (DP-5024)
• CAC-5F Class A Converter module for Initiating Device Circuits
• NACA-2F Class A Converter module for Notification Appliance Circuits
FIGURE 1-2:
MS-5024 Control Panel
Notification
Appliance
Programmable
Relays
Circuits
FIGURE 1-1:
5 Input
Zones
DP-5024
Four
Character
7-Segment
LED Display
Piezo 85dB
BELLS
1 2
112234
TB5
24V NONRESETTABLE
1234
TB4
24V
RESETTABLE
NO NC C NO NC C
TB3
ZONE 4 ZONE 5
ZONE 3
ZONE 1 ZONE 2
B+ B- B+ B- B+ A+ A- B- B+ B- B+ B-
TB2
Annunciator
Driver Module
Interface
Connector
TB1
J1
TEST CONNECTOR
KISS OFF
/LOAD
LED 3
J3
PRIMARY SECONDARY
PRIMARY
ACTIVE
LED 1
SECONDARY
ACTIVE
LED 2
Primary &
Secondary
Phone Lines
Keypad
12
Holds up to 7 AH Batteries Up to 60 Hrs. of Standby
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Controls and Indicators
1.2Controls and Indicators
1.2.1 Front Panel Switches
RESETDigits 0 - 9
SILENCEA
MODEB
Up ArrowC
Down ArrowD
1st EVENTE
ENTER/STOREF
1.2.2 Display and Indicators
• Four 7-Segment Displays - red
• Alarm - red LED
• Trouble - yellow LED
• Supervisory - yellow LED
• Silence - yellow LED
• AC Power - green LED
• Primary Phone Line Active - red LED
• Secondary Phone Line Active - red LED
• 'Kissoff' Signal from Central Station - green LED
FIGURE 1-3:
Controls and Indicators
1.2.3 Local Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions.
1.3Circuits
1.3.1 Input Circuits
Five input circuits provide Style B configuration with one circuit also configurable for Style D. Input circuits may be
used as standard fire control panel zones or slave communicator input channels.
• Initiating Device Circuit 1 (Style B) accepts Normally Open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 2 (Style B) accepts Normally Open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 3 (Style B/D) accepts Normally Open contact devices, 2-wire smoke detectors and
waterflow devices
• Initiating Device Circuit 4 (Style B) accepts Normally Open contact devices and 2-wire smoke detectors
• Initiating Device Circuit 5 (Style B) accepts Normally Open contact devices and 2-wire smoke detectors
1.3.2 Output Circuits
• 24 Volt Resettable Power Output
• 24 Volt Nonresettable Power Output
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
13
Digital Communicator
1.3.3 Notification Appliance Circuits
Two NACs (Notification Appliance Circuits) configurable for Style Y (Class B) with various programmable features.
1.3.4 Relays
Two dry Form-C relay contacts programmable for Alarm, Trouble, Supervisory and/or Communications Failure.
Contacts are rated 2 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive).
1.4Digital Communicator
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the
Primary and Secondary phone lines. Telephone line active red LEDs are provided as well as a green 'Kissoff” LED.
The integral digital communicator provides the following functions:
• Line Seizure - takes control of the phone lines, disconnecting any premises phones
• Off/On Hook - perform on and off-hook status to the phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) number - default is Touch-Tone
• For tone burst or touchtone type formats: discern proper 'Ack' and 'Kissoff' tone(s) - the frequency and time
duration of the tone(s) vary with the transmission format. The control panel will adjust accordingly
• Communicate in the following formats:
✓
12 Tone Burst Types: 20 pps
(3+1, 4+1 and 4+2 Standard, 3+1 Expanded, 4+1 Expanded, 4+2 Expanded)
✓
2 Touchtone Types:
4+1 Ademco Express and 4+2 Ademco Express
Refer to Table 4-3, “Compatible UL Listed Receivers,” on page 56 for a list of compatible receivers.
®
, programmable to rotary
1.5Components
1.5.1 Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface
connectors. Optional modules plug in and are mounted to the main circuit board. The main circuit board is delivered
premounted in the cabinet.
1.5.2 Cabinet
The cabinet is red with an attractive navy blue front overlay. The backbox measures 14.5" (36.83 cm) X 12.5" (31.75
cm) X 2.875" (7.303 cm) and provides space for two batteries (up to 7 Amp Hour). Also available is an optional
dress panel (DP-5024), which mounts inside the cabinet.
1.5.3 Transformer Assembly
One 100 VA transformer is provided standard with the panel.
14
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Optional Devices
1.5.4 Batteries
The cabinet provides space for 7 Amp Hour batteries (for 12 Amp Hour to 18 Amp Hour batteries use the UL listed
BB-17F battery box). Batteries must be ordered separately.
1.6Optional Devices
1.6.1 ADM-24
The ADM-24 Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is
supervised for open circuits by this module. The Annunciator Driver Module mounts to connector J3 in the upper
right corner of the main board. Refer to Figure 1-2 on page 12 and Figure 2-10 on page 28.
1.6.2 RZA-5F
The RZA-5F Remote Annunciator mounts on a standard single-gang box and provides LED indications of the
following:
✓
Alarm Zone 1 (red LED)
✓
Alarm Zone 2 (red LED)
✓
Alarm Zone 3 (red LED)
✓
Alarm Zone 4 (red LED)
✓
Alarm Zone 5 (red LED)
✓
System Trouble (yellow LED)
A Local Trouble Sounder and Tone Silence Switch are also provided. All LEDs and their wiring are supervised for
open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide in paper labels permit
an easy change of zone information (refer to Figure 2-11 on page 28). Note that the RZA-5F Remote Annunciator
requires the use of the ADM-24 Annunciator Driver Module. Only one ADM-24/RZA-5F combination is allowed per
system.
1.6.3 CAC-5F
The CAC-5F Class A Converter module converts the Style B (Class B) Initiating Device Circuits to Style D (Class
A). The CAC-5F mounts to terminal block TB2 located in the upper right corner of the main circuit board (refer to
Figure 1-2 on page 12 and Figure 2-15 on page 30). The removable terminal block on the CAC-5F module provides
for ease of wiring.
1.6.4 NACA-2F
The NACA-2F Notification Appliance Circuit Class A Converter module converts the two NAC circuits from Style
Y (Class B) to Style Z (Class A). The converter module mounts to terminal block TB5 located in the upper left corner of the main circuit board (refer to Figure 1-2 on page 12 and Figure 2-14 on page 30). The removable terminal
block on the NACA-2F module provides for ease of wiring.
1.6.5 DP-5024
The DP-5024 Dress Panel is red and is available as an option (required for Canadian installations). The dress panel
restricts access to the system wiring while allowing access to the membrane switch panel (refer to Figure 1-1 on page
12).
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
15
Specifications
1.6.6 BB-17F
The BB-17F Battery Box may be used to house two 12 Amp Hour or 18 AMP Hour batteries. The battery box
mounts directly below the control panel cabinet (refer to Figure 2-2 on page 21). The BB-17F is red and is provided
with knockouts.
1.7Specifications
AC Power - TB1
MS-5024: 120 VAC, 60 Hz, 1.2 amps
MS-5024E: 220/240 VAC, 50 Hz, 0.6 amps
Supervised for AC loss and brownout
Wire size: minimum 14 AWG (2.00 mm
Battery (lead acid only) - J1
Maximum charging circuit: Normal Flat Charge - 27.6V @ 0.8 amp
Maximum charger capacity: 17 Amp Hour battery (MS-5024 cabinet holds maximum 7 Amp Hour battery. Larger
batteries require Fire•Lite BB-17F or other UL listed battery cabinet).
Supervised for low and no battery
2
) with 600V insulation
Initiating Device Circuits - TB2
Detector zones 1, 2, 3, 4 and 5
Power-limited circuitry
Operation: All zones (NFPA Style B), Zone 3 (NFPA Style B or D). Use CAC-5F for Style D operation
Normal operating voltage: 24 VDC (ripple = 100mV maximum)
Alarm current: 26 mA Short circuit current: 42 mA maximum
Maximum loop resistance: 100 ohms
End-of-Line Resistor: 4.7K, ½ watt (P/N 27072 UL listed)
Detector loop current sufficient to ensure operation of one alarmed detector/zone
Standby current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuits - TB5
Nonregulated special purpose power, Style Y supported. Use NACA-2F for Style Z operation
Power-limited circuitry
Operating voltage nominal 24 volts
Current limit: PTC Maximum signaling current/circuit: 1.5 amps (3.0 amps max. for all external devices
End-of-Line Resistor: 4.7K, ½ watt (P/N 71252 UL listed) for Notification Appliance Circuits
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Four-Wire Smoke Detector Power - TB4, Terminals 3(+) & 4(-)
Maximum ripple voltage: 10 mV
Operating voltage: nominal 24 volts
RMS
Up to 300 mA is available for powering 4-wire smoke detectors
Power-limited circuitry Maximum standby current: 50 mA
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
16
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Telephone Requirements and Warnings
Nonresettable 24 VDC Power - TB4, Terminals 1(+) & 2(-)
Maximum ripple voltage: 10 mV
Operating voltage: nominal 24 volts
RMS
Total DC current available from this output is up to 300 mA
Power-limited circuitry Maximum standby current is 150 mA
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Notes:
For power supply calculations, refer to “Battery Calculations” on page 63
1.
Total current for nonresettable power, 4-wire smoke power and two NACs must not exceed 3.6 amps
2.
1.8Telephone Requirements and Warnings
1.8.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 1.3B
AC Impedance 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.
1.8.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Note: The FCC ID label is located on the inside of the control panel door.
1.8.3 Telephone Company Rights and Warnings
The telephone company under certain circumstances may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the
telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
17
Telephone Requirements and Warnings
When the control panel activates, premises phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone
system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
1.8.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the
appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the
equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The
customer should be aware that compliance with the above conditions may not prevent degradation of service in some
situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the
supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the
telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone
lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly
important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection
authority or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum
number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of
any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
Representative:NOTIFIER, CANADA
24 Viceroy Road
Concord, Ontario L4K2L9
IC Certificate Number: 21325785A
Ringer Equivalence Number (REN): 1.3B
Load Number: 2
18
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Installation
CHAPTER 2Installation
2.1Mounting Options
The cabinet may be either semi-flush or surface mounted. The
door is removable during the installation period by opening
and lifting off the hinges. The cabinet mounts using two key
slots and two additional 0.250" diameter holes located in the
backbox. The key slots are located at the top of the backbox
and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage.
Mount the cabinet in a clean, dry, vibration-free area where
extreme temperatures are not encountered. The area should be
readily accessible with sufficient room to easily install and
maintain the panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on
the left. Determine the number of conductors required for the
devices to be installed. Sufficient knockouts are provided for
wiring convenience. Select the appropriate knockout(s) and
pull the required conductors into the box. Note that there are
no knockouts located on the left (hinged) side of the cabinet.
All wiring should be in accordance with the National and/or
Local codes for fire alarm systems.
2.2Backbox Mounting
• Refer to Figure 2-1 on page 20 and Figure 2-2 on page 21
• Make certain there is no power (AC or DC) applied to the control panel
• Open the door and lift the door off the pin hinges
• Remove AC wiring
• Remove the main PC board assembly by unscrewing the five screws in the corners of the board. Two standoffs support the board in the center. Set the board aside in a safe, clean place. Avoid static discharge which
may damage the board
• Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown
• Install two upper fasteners in the wall with the screw heads protruding
• Using the upper 'keyholes', mount the backbox over the two screws
• Mark and drill the lower two holes
• Mount backbox, install remaining fasteners and tighten
• When the location is dry and free of construction dust, reinstall the main PC board
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
19
Backbox Mounting
(
)
(
)
(
)
(
)
Draw wires through the respective knockout locations.
2. Remove appropriate knockouts from the MS-5024 cabinet and BB-17F
3. Position the BB-17F near the MS-5024 cabinet and connect with conduit, making sure there is at least ½" of
clearance between the two cabinets
4. Anchor the BB-17F to the wall
Document #50066 Rev. D2 12/03/02 P/N 50066:D221
Operating Power
2.3Operating Power
CAUTION! Several different sources of power can be connected to this panel. Disconnect all sources of power
before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules
or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Primary power source for the MS-5024 is 120VAC,
60 Hz, 1.2 amps and for the MS-5024E is 220/240VAC, 50 Hz, 0.6 amps. Run a pair of wires (with ground
conductor) from the protected premises main breaker box to the orange and black primary leads of the MS-5024
transformer. As per the National Electric Code, use 14 AWG (2.00 mm
insulation. No other equipment may be connected to this circuit. In addition, this circuit must be provided with
overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must
be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire,
minimum 14 AWG (2.00 mm
2
), to the grounding stud indicated by the ground symbol label. Note that conduit must
not be used for an Earth Ground connection since this does not provide reliable protection.
Secondary Power Source (batteries)
Observe polarity when connecting the battery. Connect the battery cable to J1 on the main circuit board using the
plug-in connector provided. The battery charger is current-limited and capable of recharging sealed lead acid type
batteries. The charger shuts off when the system is in alarm or if the battery voltage drops too low (below 14.2VDC).
See Appendix A for calculations of the correct battery rating. WARNING! Battery contains sulfuric acid which can
cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately
flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
FIGURE 2-3:
Operating Power Connections
AC Feed
Neutral
Hot
Ground
2
) or heavier gauge wire with 600 V
Orange
Black
Connect Earth
Ground Wire
Red
Ground Stud
Brown
22
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Input Circuits
2.4Input Circuits
The control panel has five zone input circuits. The maximum loop resistance limit for each is 100 ohms. All field
wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated
as well as communicated to a Central Station.
Each zone is a Style B (Class B) Initiating Device Circuit designed to accept any Normally Open contact device and
conventional 2-wire, 24 volt smoke detectors. Each zone is power-limited to 7.26 mA in standby and 42 mA in
alarm. Zone 3 may also be configured as a Style D (Class A) Initiating Device Circuit. Figure 2-5 illustrates typical
circuit connections. Note that all five initiating zones may be converted to Style D (Class A) by using a CAC-5F Class
A Converter module (refer to Figure 2-15 on page 30).
Zones 1-5 may be programmed as shown below. The factory default is 2-wire smoke detector for all zones.
• 2-wire Smoke Detector (factory default)
• Pull Station
• Normally Open Contact Device
• Supervisory
• Supervisory, autoresettable
Zone 3 may also be programmed as:
• Waterflow silenceable
• Waterflow nonsilenceable
Note: A maximum of five waterflow devices may be used on Zone 3 per NFPA 72.
Four-wire smoke detectors may be connected to any zone. Resettable power is provided via TB4, Terminals 3 & 4.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any
zone. However, this is not recommended since specific and detailed reports will not be possible. For example, the
report of general fire alarm versus pull station fire alarm or smoke detector fire alarm.
FIGURE 2-4:
Typical Initiating Device Circuit Connections
Style B Initiating Device Circuit
(supervised and power-limited) 4.7K
ohm, ½ watt P/N 71252 UL listed
Manual Pull Station
Heat Detector
Style D Initiating Device Circuit
(supervised and power-limited)
*Nonresettable Power (300 mA)
24 VDC filtered, nonresettable power can be
obtained from TB4 Terminals 1(+) & 2(-)
Auxiliary Power Connections
+ - + -
1 2 3 4
*4-Wire Smoke Detector Power (300 mA)
24 VDC filtered, resettable power for 4-wire smoke
detectors can be obtained from TB4 Terminals 3(+) & 4(-)
* Refer to the Fire•Lite Device
Compatibility Document for a list of
compatible smoke detectors, notification
appliances and auxiliary devices
2.5.2 Telephone Circuits
Provision to connect to two independent telephone lines is available via two telephone jacks labeled PH1 (Primary)
and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection (refer to Figure 2-9 on page 27).
The MS-5024 provides two Style Y NACs (Notification Appliance Circuits), each capable of 1.5 amps of current.
Total current drawn from these as well as other DC power outputs cannot exceed 3.6 amps. Circuits are supervised
and power-limited. Figure 2-6 illustrates a typical circuit connection. Refer to the Fire•Lite Device Compatibility
Document for a listing of compatible notification appliances.
Note that both NACs may be converted to Style Z (Class A) by using an NACA-2F Class A Converter module (refer to
Figure 2-14 on page 30).
24
FIGURE 2-6:
Typical NAC Connections
Style Y Notification Appliance
Circuit (supervised and powerlimited). 4.7K ohm, ½ watt
P/N 71252 UL listed
Note: Notification Appliance
Circuit polarity shown in
alarm
state.
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Polarized Bell
Polar ized Hor n
Polar ized Hor n
Dummy Load all unused circuits
P/N 71245
Output Circuits
Note that both NACs may be programmed as follows:
• Silenceable
• Nonsilenceable
• Enabled/Disabled
• Silence Inhibited
• Autosilence, 5 to 30 minutes
• Coded (March Time, Temporal, California)
2.5.4 Programmable Relays
The control panel provides two sets of Form-C programmable relay contacts rated for 2.0 amps @ 30 VDC
(resistive). Each relay may be programmed for alarm, trouble, supervisory, communications failure or any combination of these. Refer to Figure 2-7 on page 25 for UL Power-limited wiring requirements.
Note that all relay connections must be power-limited or nonpower-limited. No mixing is permitted.
FIGURE 2-7:
Programmable Relay Terminals
Relay Connections
Relay 1Relay 2
Note: If relays are used as power-limited
circuits, paste supplied label to terminal
block as indicated below.
Power
Limited
Powe r
Limited
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
25
UL Power-limited Wiring Requirements
2.6UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited
circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or
conduits. A typical wiring diagram for the MS-5024 is shown below.
FIGURE 2-8:
Typical Wiring Diagram for UL Power-limited Requirements
Power-limited Circuits
Nonpower-limited Circuits
ZONE 1 ZONE 2
B+ B- B+ B- B+ A+ A- B- B+ B- B+ B-
TB3
J3
ZONE 4 ZONE 5
ZONE 3
TB2
ADM-24
TB1
AC Power
BELLS
1 2
112234
TB5
Earth
Ground
24V NONRESETTABLE
1234
TB4
24V
RESETTABLE
NO NC C NO NC C
Power-limited Circuits
Powe r- limited
Circuit
26
PRIMARY SECONDARY
PRIMARY
ACTIVE
LED 1
SECONDARY
ACTIVE
LED 2
J1
- +
TEST CO NNECTOR
KISS OFF
/LOAD
LED 3
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Digital Communicator
2.7Digital Communicator
Two independent telephone lines can be connected to the control panel. Telephone line control/command is made
possible via double line seizure as well as usage of an RJ31X style interconnection. The control panel’s digital communicator is built into the main circuit board. Connection and wiring of two phone lines is required as shown below.
Note that it is critical that the digital communicator be located as the first device on the incoming telephone circuit to
properly function.
FIGURE 2-9:
Wiring Phone Jacks
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
27
Optional Boards
2.8Optional Boards
2.8.1 ADM-24 Annunciator Driver Module
The ADM-24 supports the RZA-5F Remote Annunciator. The wiring is supervised for open conditions by this module. The Annunciator Driver Module mounts to J3 in the upper right corner of the main circuit board.
FIGURE 2-10:
ADM-24
Standoff
Main Board
2.8.2 RZA-5F Remote Annunciator
The RZA-5F mounts on a standard single-gang electrical box and provides LED indication of the following:
Connector located on back of board
FIGURE 2-11:
ADM-24
RZA-5F
• Alarm Zone 1 (red LED)
• Alarm Zone 2 (red LED)
• Alarm Zone 3 (red LED)
• Alarm Zone 4 (red LED)
• Alarm Zone 5 (red LED)
• System Trouble (yellow LED)
The remote annunciator provides individual zone
alarm LEDs, a system trouble LED, a piezo sounder
and a remote sounder shut off switch. All LEDs and
their wiring are supervised for open conditions. Any
open condition will cause the System Trouble LED to
illuminate.
Note that the RZA-5F requires the use of an ADM-24
Annunciator Drive Module. Only one RZA-5F/ADM24 combination is allowed per system.
28
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Optional Boards
FIGURE 2-12:
Wiring the RZA-5F/ADM-24
ADM-24
+24V
Note: Make wiring connections with
system power off. Maximum wire
impedance is 100 ohms per wiring
connection.
RZA-5F
FIGURE 2-13:
Installing Annunciator in Single-Gang Box
screw #6-32 x 1.00" LG
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
29
Optional Boards
2.8.3 NACA-2F and CAC-5F Class A Converter Modules
The NACA-2F module is used to convert the two Style Y (Class B) Notification Appliance Circuits to two Style Z
(Class A) NACs. The module connector J1 is inserted into the terminals of terminal block TB5 on the MS-5024 and
the terminal screws are tightened to secure the module. The NACs are wired as illustrated in Figure 2-14.
FIGURE 2-14:
NACA-2F Style Z Converter Module
Polarized bell
Polarized bell
Note: Notification Appliance Circuit
polarity is shown in alarm
Style Z Notification Appliance Circuits
are supervised and power-limited.
Insert two supplied standoffs into NACA-2F circuit
board, remove protective paper from self-adhesive
base of standoff, install circuit board into TB5 of
MS-5024 and press to adhere standoffs to cabinet.
state.
Polarized strobe
Polarized horn
Polarized strobe
Polarized horn
Dummy load any unused circuits
with 4.7K ohm ELR (P/N 71245)
across B+ and B-
NACA-2F Module
MS-5024 Main Board
The CAC-5F module is used to convert the Initiating Device Circuits to five Style D IDCs. The module connector J1
is inserted into the terminals of terminal block TB2 on the MS-5024 and the terminal screws are tightened to secure
the module. The IDCs are wired as illustrated in Figure 2-15.
FIGURE 2-15:
UL listed compatible 2-wire smoke detector
CAC-5F Style D Converter Module
Waterflow switch
Manual Pull Station
Heat Detector
Insert two supplied standoffs into CAC-5F
circuit board, remove protective paper
from self-adhesive base of standoff, install
circuit board into TB2 of MS-5024 and
press to adhere standoffs to cabinet.
Waterflow switch
Waterflow switch
Dummy load all unused circuits with
4.7K ELR (P/N 71245) across B+ and B-
CAC-5F Module
MS-5024 Main Board
Note:
Circuits 1 through 5 can accommodate 2-wire smoke detectors plus any normally open contact device such as
1.
heat detectors or manual pull stations
Only circuit 3 accommodates the nonsilenceable waterflow function
2.
30
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Instructions
CHAPTER 3Programming Instructions
This chapter describes programming the panel from the onboard keypad. Programming of the control panel is
possible at any time except when an alarm condition is present or during a fire drill.
The control panel has been designed for many different types of applications. After examining your specific
application, review the programming options and choose the entries best suited for your system.
The control panel has a built-in intelligent programmer. All programming selections are stored in nonvolatile
Electrically-Erasable Programmable Read-Only Memory (EEPROM). This ensures that the control panel will retain
all entries made in programming mode even if both AC and battery power are removed. Invalid entries cause a 'beep'
from the onboard piezo sounder.
The user must
program the primary and secondary phone numbers, account numbers and 24 hour test report times for
each Central Station account and the current time and date. The control panel comes with factory chosen options/
features already programmed. Other options/features may be programmed if desired. If all factory default settings
are acceptable, programming is complete.
Successful entry into Program Mode places the system into trouble. A 'system off-normal' message is transmitted to
the Central Station.
3.1Entering Program Mode
To enter Program Mode, press the MODE key once (the display will go blank). The user than has ten seconds to start
entering the code 7764.
7764 spells PROG on a Touch-Tone
☛
If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key. Note that as
the information is entered into the control panel, the digits will scroll across the display from right to left.
___7
__77
_776
7764
The user is allowed a pause of up to 10 seconds between each number while entering the code. After pressing the
[ENTER/STORE] key, the control panel will be in Program Mode and will display 00_F. A maximum of 10 min-
utes of idle time is allowed at this point before starting the programming, otherwise the control panel will return to
Normal Mode. A maximum of 10 minutes between key strokes is also allowed. All entries made prior to the 10
minute time-out are valid and are stored.
®
phone
Once in Programming Mode, the control panel will:
• Blink the trouble LED
• Activate the relay(s) if programmed for trouble
• Disable the Notification Appliance Circuit(s)
• Disable the relay(s) if programmed for alarm
•Display 00_F
• Ignore all other keys other than those mentioned in this section
• Continue to communicate any events not previously acknowledged at a Central Station prior to entering
Program Mode
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
31
Switch (Key) Functions
Note that location 56 is factory defaulted to '0' for control panel only. This keeps the communicator off until location
56 is changed to '1' for slave communicator or '2' for panel/communicator. Once location 56 is set to '1' or '2' and a
valid phone number is entered, entry into the Program Mode will cause transmission of the 'system off-normal' report.
Throughout Program Mode, the first three locations on the left of the display represent the memory address which can
range from 000 to 313 (alpha characters are not used). The last location (farthest right) represents the contents of the
memory address. The first address displayed is shown below:
00_F
(address)(data)
3.2Switch (Key) Functions
The function of each switch (key) in Program Mode is shown below.
FIGURE 3-1:
Control Panel Keypad
Address entry keys are 0 to 9
Data entry keys are 0 to 9 and A to F
No function in Program Mode
- Select operating mode
- Increment memory address
- Decrement memory address
- 1st press - first memory address
- 2nd press - type any address
- Save data, and increment address
3.3Programming Options
Primary Central Station Phone Number (00-15)
The first sixteen addresses, 00-15, are factory set to 'F' (from 00_F to 15_F). Programming is typically done as
follows: If the phone number to be entered is 484-7161, press the 4 key. The display will read 00_4. Press the
[ENTER/STORE] key to save the entry to memory and increment to the next address 01_F.
Enter the remaining numbers in their respective addresses as shown below:
48 47161FFFFFFFFF
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha characters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to 2 seconds (then dial anyway)
D = three second pause
E = five second pause
F = end of phone number ('F' must be entered)
32
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Options
Primary Central Station Number Communication Format (16)
One location is needed to select the Communication Format for the primary phone number. Address 16 is used for
this purpose. The default (factory setting) for this address is 'A' (16_A), which is 4+2 Standard, 1800 Hz 'Carrier',
2300 Hz 'ack'. You may enter 0 through D in place of the default, then press the [ENTER/STORE] key. Choose
from the list of formats below:
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes. See Table 3-1 , Table 3-2 , Table 3-3 and Table
3-4 .
CAUTION! Default entries for event codes (as shown in Table 3-1 through Table 3-4 ) are programmed into memory
each time address 16 is altered. Be certain to double check entries after programming the Zone Functions, addresses
57 - 61. Program the Format first then program the Zone(s) Function.
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 16, the data in Table 3-1 is automatically programmed for the
Primary Central Station phone number event codes. Enter '0' for the setting to disable the report.
TAB L E 3-1:
AddressDescriptionSetting
82Primary # Zone 1 Alarm Code1
83Primary # Zone 2 Alarm Code1
84Primary # Zone 3 Alarm Code1
85Primary # Zone 4 Alarm Code1
86Primary # Zone 5 Alarm Code1
87Primary # Zone 1 Disabled CodeF
88Primary # Zone 2 Disabled CodeF
89Primary # Zone 3 Disabled CodeF
90Primary # Zone 4 Disabled CodeF
91Primary # Zone 5 Disabled CodeF
92Primary # Drill Code9
93Primary # AC Fault CodeF
94Primary # Zone 1 Fault CodeF
95Primary # Zone 2 Fault CodeF
96Primary # Zone 3 Fault CodeF
97Primary # Zone 4 Fault CodeF
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded - Primary
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
33
Programming Options
TABLE 3-1:
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded - Primary
AddressDescriptionSetting
98Primary # Zone 5 Fault CodeF
99Primary # Earth Fault CodeF
100Primary # Low Battery Fault CodeF
101Primary # No Battery Fault CodeF
102Primary # Telco Primary Line Fault CodeF
103Primary # Telco Secondary Line Fault CodeF
104Primary # NAC #1 Fault CodeF
105Primary # NAC #2 Fault CodeF
106Primary # Communication Trouble Primary # Fault CodeF
107Primary # Communication Trouble Secondary # Fault CodeF
108Primary # Annunciator Fault CodeF
109Primary # System Off Normal CodeF
110Primary # Zone 1 Alarm Restore CodeE
111Primary # Zone 2 Alarm Restore CodeE
112Primary # Zone 3 Alarm Restore CodeE
113Primary # Zone 4 Alarm Restore CodeE
114Primary # Zone 5 Alarm Restore CodeE
115Primary # Zone 1 Disabled Restore CodeE
116Primary # Zone 2 Disabled Restore CodeE
117Primary # Zone 3 Disabled Restore CodeE
118Primary # Zone 4 Disabled Restore CodeE
119Primary # Zone 5 Disabled Restore CodeE
120Primary # Drill Restore Code9
121Primary # AC Fault Restore CodeE
122Primary # Zone 1 Fault Restore CodeE
123Primary # Zone 2 Fault Restore CodeE
124Primary # Zone 3 Fault Restore CodeE
125Primary # Zone 4 Fault Restore CodeE
126Primary # Zone 5 Fault Restore CodeE
127Primary # Earth Fault Restore CodeE
128Primary # Low Battery Fault Restore CodeE
129Primary # No Battery Fault Restore CodeE
130Primary # Telco Primary Line Fault Restore CodeE
131Primary # Telco Secondary Line Fault Restore CodeE
132Primary # NAC #1 Fault Restore CodeE
133Primary # NAC #2 Fault Restore CodeE
134Primary # Communication Trouble Primary # Restore CodeE
135Primary # Communication Trouble Secondary # Restore CodeE
136Primary # Annunciator Fault Restore CodeE
137Primary # System Off Normal Restore CodeE
138Primary # System Test Report9
139Primary # System Abnormal Test ReportF
34
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Options
4+2 Standard and 4+2 Express Format
If '1, A or C' is entered for address 16, the data in Table 3-2 is automatically programmed for the Primary Central
Station phone number event codes. Enter '00' for the setting to disable the report.
TAB L E 3-2:
AddressDescriptionSetting
82 - 83Primary # Zone 1 Alarm Code11
84 - 85Primary # Zone 2 Alarm Code12
86 - 87Primary # Zone 3 Alarm Code13
88 - 89Primary # Zone 4 Alarm Code14
90 - 91Primary # Zone 5 Alarm Code15
92 - 93Primary # Zone 1 Disabled CodeF1
94 - 95Primary # Zone 2 Disabled CodeF2
96 - 97Primary # Zone 3 Disabled CodeF3
98 - 99Primary # Zone 4 Disabled CodeF4
100 - 101Primary # Zone 5 Disabled CodeF5
102 - 103Primary # Drill Code97
104 - 105Primary # AC Fault CodeF6
106 - 107Primary # Zone 1 Fault CodeF1
108 - 109Primary # Zone 2 Fault CodeF2
110 - 111Primary # Zone 3 Fault CodeF3
112 - 113Primary # Zone 4 Fault CodeF4
114 - 115Primary # Zone 5 Fault CodeF5
116 - 117Primary # Earth Fault CodeF7
118 - 119Primary # Low Battery Fault CodeF8
120 - 121Primary # No Battery Fault CodeF9
122 - 123Primary # Telco Primary Line Fault CodeFA
124 - 125Primary # Telco Secondary Line Fault CodeFB
126 - 127Primary # NAC #1 Fault CodeFC
128 - 129Primary # NAC #2 Fault CodeFC
130 - 131Primary # Communication Trouble Primary # Fault CodeFD
132 - 133Primary # Communication Trouble Secondary # Fault CodeFE
134 - 135Primary # Annunciator Fault CodeFC
136 - 137Primary # System Off Normal CodeFF
138 - 139Primary # Zone 1 Alarm Restore CodeE1
140 - 141Primary # Zone 2 Alarm Restore CodeE2
142 - 143Primary # Zone 3 Alarm Restore CodeE3
144 - 145Primary # Zone 4 Alarm Restore CodeE4
146 - 147Primary # Zone 5 Alarm Restore CodeE5
148 - 149Primary # Zone 1 Disabled Restore CodeE1
150 - 151Primary # Zone 2 Disabled Restore CodeE2
152 - 153Primary # Zone 3 Disabled Restore CodeE3
154 - 155Primary # Zone 4 Disabled Restore CodeE4
156 - 157Primary # Zone 5 Disabled Restore CodeE5
158 - 159Primary # Drill Restore Code98
160 - 161Primary # AC Fault Restore CodeE6
162 - 163Primary # Zone 1 Fault Restore CodeE1
164 - 165Primary # Zone 2 Fault Restore CodeE2
166 - 167Primary # Zone 3 Fault Restore CodeE3
168 - 169Primary # Zone 4 Fault Restore CodeE4
170 - 171Primary # Zone 5 Fault Restore CodeE5
172 - 173Primary # Earth Fault Restore CodeE7
174 - 175Primary # Low Battery Fault Restore CodeE8
176 - 177Primary # No Battery Fault Restore CodeE9
178 - 179Primary # Telco Primary Line Fault Restore CodeEA
180 - 181Primary # Telco Secondary Line Fault Restore CodeEB
182 - 183Primary # NAC #1 Fault Restore CodeEC
184 - 185Primary # NAC #2 Fault Restore CodeEC
186 - 187Primary # Communication Trouble Primary # Restore CodeED
188 - 189Primary # Communication Trouble Secondary # Restore CodeEE
190 - 191Primary # Annunciator Fault Restore CodeEC
192 - 193Primary # System Off Normal Restore CodeEF
194 - 195Primary # System Test Report99
196 - 197Primary # System Abnormal Test Report91
4+2 Standard and 4+2 Express Format - Primary
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
35
Programming Options
Primary Central Station Number Account Code (17-20)
Four locations at addresses 17-20 default to all '0s.' Valid entries are '0-9' and 'A-F,' The number of digits entered
must match the format selection. If programming '2, 3, 4 or 5' into address 16, enter three digits (location 20 is not
used). If programming '0, 1, 6, 7, 8, 9, A, B, C or D' into address 16, enter four digits.
Primary Central Station Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four locations at addresses 21-24. The default is '0000' for 12:00 midnight. The limits for each location are as follows:
21 - enter 0, 1 or 2
22 - enter 0, 1, 2, 3, 4, 5, 6, 7, 8 or 9
23 - enter 0, 1, 2, 3, 4 or 5
24 - enter 0, 1, 2, 3, 4, 5, 6, 7, 8 or 9
Do not use 'A - F' as entries.
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (25)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be sent
every 24 hours, leave the factory default entry of '0.' If other test report times are needed, enter '1' for 12 hours, '2' for
8 hours or '3' for 6 hours.
Secondary Central Station Phone Number (26-41)
The sixteen addresses, 26-41, are factory set to 'F' (from 26_F to 41_F). Programming is typically done as follows: If
the phone number to be entered is 484-7161, press the 4 key. The display will read 26_4. Press the [ENTER/STORE] key to save the entry to memory and increment to the next address 27_F.
Enter the remaining numbers in their respective addresses as shown below:
48 47161FFFFFFFFF
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits a dialed numbers
and the alpha characters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to 2 seconds (then dial anyway)
D = three second pause
E = five second pause
F = end of phone number (F must be entered)
36
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Options
Secondary Central Station Number Communication Format (42)
One location is needed to select the Communication Format for the secondary phone number. Address 42 is used for
this purpose. The default (factory setting) for this address is 'A' (42_A), which is 4+2 Standard, 1800 Hz 'Carrier',
2300 Hz 'ack'. You may enter 0 through D in place of the default, then press the [ENTER/STORE] key. Choose
from the list of formats below:
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the event codes. See Table 3-1 , Table 3-2 , Table 3-3 and Table
3-4 .
CAUTION! Default entries for event codes (as shown in Table 3-1 through Table 3-4 ) are programmed into memory
each time address 42 is altered. Be certain to double check entries after programming the Zone Functions, addresses
57 - 61. Program the Format first then program the Zone(s) Function.
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 42, the data in Table 3-3 is automatically programmed for the
Secondary Central Station phone number event codes. Enter '0' for the setting to disable the report.
TAB L E 3-3:
AddressDescriptionSetting
198Secondary # Zone 1 Alarm Code1
199Secondary # Zone 2 Alarm Code1
200Secondary # Zone 3 Alarm Code1
201Secondary # Zone 4 Alarm Code1
202Secondary # Zone 5 Alarm Code1
203Secondary # Zone 1 Disabled CodeF
204Secondary # Zone 2 Disabled CodeF
205Secondary # Zone 3 Disabled CodeF
206Secondary # Zone 4 Disabled CodeF
207Secondary # Zone 5 Disabled CodeF
208Secondary # Drill Code9
209Secondary # AC Fault CodeF
210Secondary # Zone 1 Fault CodeF
211Secondary # Zone 2 Fault CodeF
212Secondary # Zone 3 Fault CodeF
213Secondary # Zone 4 Fault CodeF
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded - Secondary
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
37
Programming Options
TABLE 3-3:
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded - Secondary
AddressDescriptionSetting
214Secondary # Zone 5 Fault CodeF
215Secondary # Earth Fault CodeF
216Secondary # Low Battery Fault CodeF
217Secondary # No Battery Fault CodeF
218Secondary # Telco Primary Line Fault CodeF
219Secondary # Telco Secondary Line Fault CodeF
220Secondary # NAC #1 Fault CodeF
221Secondary # NAC #2 Fault CodeF
222Secondary # Communication Trouble Primary # Fault CodeF
223Secondary # Communication Trouble Secondary # Fault CodeF
224Secondary # Annunciator Fault CodeF
225Secondary # System Off Normal CodeF
226Secondary # Zone 1 Alarm Restore CodeE
227Secondary # Zone 2 Alarm Restore CodeE
228Secondary # Zone 3 Alarm Restore CodeE
229Secondary # Zone 4 Alarm Restore CodeE
230Secondary # Zone 5 Alarm Restore CodeE
231Secondary # Zone 1 Disabled Restore CodeE
232Secondary # Zone 2 Disabled Restore CodeE
233Secondary # Zone 3 Disabled Restore CodeE
234Secondary # Zone 4 Disabled Restore CodeE
235Secondary # Zone 5 Disabled Restore CodeE
236Secondary # Drill Restore Code9
237Secondary # AC Fault Restore CodeE
238Secondary # Zone 1 Fault Restore CodeE
239Secondary # Zone 2 Fault Restore CodeE
240Secondary # Zone 3 Fault Restore CodeE
241Secondary # Zone 4 Fault Restore CodeE
242Secondary # Zone 5 Fault Restore CodeE
243Secondary # Earth Fault Restore CodeE
244Secondary # Low Battery Fault Restore CodeE
245Secondary # No Battery Fault Restore CodeE
246Secondary # Telco Primary Line Fault Restore CodeE
247Secondary # Telco Secondary Line Fault Restore CodeE
248Secondary # NAC #1 Fault Restore CodeE
249Secondary # NAC #2 Fault Restore CodeE
250Secondary # Communication Trouble Primary # Restore CodeE
251Secondary # Communication Trouble Secondary # Restore CodeE
252Secondary # Annunciator Fault Restore CodeE
253Secondary # System Off Normal Restore CodeE
254Secondary # System Test Report9
255Secondary # System Abnormal Test ReportF
38
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Options
4+2 Standard and 4+2 Express Format
If '1, A or C' is entered for address 42, the data in Table 3-4 is automatically programmed for the Secondary Central
Station phone number event codes. Enter '00' for the setting to disable the report.
TAB L E 3-4:
AddressDescriptionSetting
198 - 199Secondary # Zone 1 Alarm Code11
200 - 201Secondary # Zone 2 Alarm Code12
202 - 203Secondary # Zone 3 Alarm Code13
204 - 205Secondary # Zone 4 Alarm Code14
206 - 207Secondary # Zone 5 Alarm Code15
208 - 209Secondary # Zone 1 Disabled CodeF1
210 - 211Secondary # Zone 2 Disabled CodeF2
212 - 213Secondary # Zone 3 Disabled CodeF3
214 - 215Secondary # Zone 4 Disabled CodeF4
216 - 217Secondary # Zone 5 Disabled CodeF5
218 - 219Secondary # Drill Code97
220 - 221Secondary # AC Fault CodeF6
222 - 223Secondary # Zone 1 Fault CodeF1
224 - 225Secondary # Zone 2 Fault CodeF2
226 - 227Secondary # Zone 3 Fault CodeF3
228 - 229Secondary # Zone 4 Fault CodeF4
230 - 231Secondary # Zone 5 Fault CodeF5
232 - 233Secondary # Earth Fault CodeF7
234 - 235Secondary # Low Battery Fault CodeF8
236 - 237Secondary # No Battery Fault CodeF9
238 - 239Secondary # Telco Primary Line Fault CodeFA
240 - 241Secondary # Telco Secondary Line Fault CodeFB
242 - 243Secondary # NAC #1 Fault CodeFC
244 - 245Secondary # NAC #2 Fault CodeFC
246 - 247Secondary # Communication Trouble Primary # Fault CodeFD
248 - 249Secondary # Communication Trouble Secondary # Fault CodeFE
250 - 251Secondary # Annunciator Fault CodeFC
252 - 253Secondary # System Off Normal CodeFF
254 - 255Secondary # Zone 1 Alarm Restore CodeE1
256 - 257Secondary # Zone 2 Alarm Restore CodeE2
258 - 259Secondary # Zone 3 Alarm Restore CodeE3
260 - 261Secondary # Zone 4 Alarm Restore CodeE4
262 - 263Secondary # Zone 5 Alarm Restore CodeE5
264 - 265Secondary # Zone 1 Disabled Restore CodeE1
266 - 267Secondary # Zone 2 Disabled Restore CodeE2
268 - 269Secondary # Zone 3 Disabled Restore CodeE3
270 - 271Secondary # Zone 4 Disabled Restore CodeE4
272 - 273Secondary # Zone 5 Disabled Restore CodeE5
274 - 275Secondary # Drill Restore Code98
276 - 277Secondary # AC Fault Restore CodeE6
278 - 279Secondary # Zone 1 Fault Restore CodeE1
280 - 281Secondary # Zone 2 Fault Restore CodeE2
282 - 283Secondary # Zone 3 Fault Restore CodeE3
284 - 285Secondary # Zone 4 Fault Restore CodeE4
286 - 287Secondary # Zone 5 Fault Restore CodeE5
288 - 289Secondary # Earth Fault Restore CodeE7
290 - 291Secondary # Low Battery Fault Restore CodeE8
292 - 293Secondary # No Battery Fault Restore CodeE9
294 - 295Secondary # Telco Primary Line Fault Restore CodeEA
296 - 297Secondary # Telco Secondary Line Fault Restore CodeEB
298 - 299Secondary # NAC #1 Fault Restore CodeEC
300 - 301Secondary # NAC #2 Fault Restore CodeEC
302 - 303Secondary # Communication Trouble Primary # Restore CodeED
304 - 305Secondary # Communication Trouble Secondary # Restore CodeEE
306 - 307Secondary # Annunciator Fault Restore CodeEC
308 - 309Secondary # System Off Normal Restore CodeEF
310 - 311Secondary # System Test Report99
312 - 313Secondary # System Abnormal Test Report91
4+2 Standard and 4+2 Express Format - Primary
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
39
Programming Options
Secondary Central Station Number Account Code (43-46)
Four locations at addresses 43-46 default to all '0s.' Valid entries are '0-9' and 'A-F,' The number of digits entered
must match the format selection. If programming '2, 3, 4 or 5' into address 42, enter three digits (location 46 is not
used). If programming '0, 1, 6, 7, 8, 9, A, B, C or D' into address 42, enter four digits.
Secondary Central Station Number 24 Hour Test Time (47-50)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 2 takes up four locations at addresses 47-50. The default is '0000' for 12:00 midnight. The limits for each location are as follows:
47 - enter 0, 1 or 2
48 - enter 0, 1, 2, 3, 4, 5, 6, 7, 8 or 9
49 - enter 0, 1, 2, 3, 4 or 5
50 - enter 0, 1, 2, 3, 4, 5, 6, 7, 8 or 9
Do not use 'A - F' as entries.
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (51)
The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0.' If other test report times are needed, enter '1' for 12 hours,
'2' for 8 hours or '3' for 6 hours.
Alarm Verification (52)
Alarm verification works only on zones programmed as 2-wire smoke detector zones. After detecting an alarm, the
control panel removes power from all zones for 6 seconds, resetting all 2-wire smoke detectors. Power is reapplied
and a 12 second retard period allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent
alarms by the same initiating zone are ignored. An alarm detected on any other 2-wire detector zone during the retard
period will cause immediate verified alarms. A subsequent alarm on the initiating zone occurring within the confirmation time will cause a verified alarm. Note that mixing devices on zones designated as 2-wire smoke zones is not
recommended.
During the alarm verification period, access to other modes of operation is prevented.
FIGURE 3-2:
Detector Alarm Verification
Detector Zone Goes Into Alarm
Verification Timing Diagram
0 Sec.
6 Sec.18 Sec.
RESET RETARD
ALARM VERIFICATION PERIOD
120 Sec.
CONFIRMATION TIME
Control Panel Processes Alarm if Same Detector is Still in AlarmAlarm Ignored
0
906030
120
Different Detector Zone Alarms
Control Panel Immediately Processes Alarm
Factory default selection is '0' for no verification. Entering a '1' enables alarm verification. Consult the local
Authority Having Jurisdiction (AHJ) prior to altering this address.
40
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Options
Programmable Relay #1 (53)
Programmable Relay #1 may be programmed to activate on alarm, trouble, supervisory, communication failure or
any combination of the four conditions. The default (factory) setting for this address is '1' for activation on alarm
only. Valid entries for address 53 are '0' through 'F' as listed below:
0 = Disable
1 = Alarm
2 = Supervisory
3 = Alarm or Supervisory
4 = Trouble
5 = Alarm or Trouble
6 = Supervisory or Trouble
7 = Alarm or Supervisory or Trouble
8 = Communication Failure
9 = Alarm or Communication Failure
A = Supervisory or Communication Failure
B = Alarm or Supervisory or Communication Failure
C = Trouble or Communication Failure
D = Alarm or Trouble or Communication Failure
E = Supervisory or Trouble or Communication Failure
F = Alarm or Supervisory or Trouble or Communication Failure
Programmable Relay #2 (54)
Programmable Relay #2 is programmed in address 54. The default (factory) setting for this address is '4' for activation on trouble only. Valid entries for address 54 are '0' through 'F' as listed above.
Future Use (55)
Slave Communicator/Fire Panel Selection (56)
Leaving address 56 at '0' causes the control panel to operate as a fire panel only. Selecting '1' will cause the panel to
operate as a slave communicator only. Selecting '2' will cause the panel to operate as a fire panel/communicator.
Zones 1-5 Function Selection (57-61)
The five zones on the control panel may be programmed as shown below. Program entries alter zone function and
transmittal priority.
TAB L E 3-5:
Program EntryFunction
0Operates 2-wire smoke detectors
1Pull station
2Normally open contact device
3Supervisory
4Supervisory autoresettable. Self-restore function, is not latched by the control panel
5
6
Waterflow silenceable. Silencing of silenceable Notification Appliance Circuits
allowed. Affects zone 3 only.
Waterflow nonsilenceable. Silencing of silenceable Notification Appliance Circuits
not allowed. Must clear waterflow alarm condition and press reset key. Affects zone 3
only
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
41
Programming Options
Zone 1 Function Selection (57)
Factory default for zone 1 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory or '4' for supervisory autoresettable.
Zone 2 Function Selection (58)
Factory default for zone 2 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory or '4' for supervisory autoresettable.
Zone 3 Function Selection (59)
Factory default for zone 3 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory, '4' for supervisory autoresettable, '5' for waterflow silenceable or '6' for waterflow
nonsilenceable.
Zone 4 Function Selection (60)
Factory default for zone 4 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory or '4' for supervisory autoresettable.
Zone 5 Function Selection (61)
Factory default for zone 5 is '0' for 2-wire smoke detector. Enter '1' for pull station, '2' for normally open contact
device, '3' for supervisory or '4' for supervisory autoresettable.
Note: Programming any zone to function as supervisory or supervisory autoresettable will cause the defaulted event
codes (note in Table 3-1 through Table 3-4 ) to be automatically changed. The defaulted code of '1' is changed to '8'
for Formats 3+1 and 4+1 Standard and Expanded, 4+2 Expanded and 4+1 Express. The defaulted codes of 11, 12,
13, 14 and 15 are changed to 81, 82, 83, 84 and 85 accordingly for Formats 4+2 Standard and 4+2 Express.
Waterflow Retard Timer (62-63)
A delay may be added prior to declaring a waterflow type of alarm. Delays up to 89 seconds are allowed. The
default for addresses 62 and 63 are '00' for no additional delay. Valid entries for address 62 are '0' to '8' and for
address 63 '0' to '9.' Program an entry into these addresses only if entering a '5' or '6' in address 59. Be careful to
include any built-in delays of the waterflow device.
AC Loss Reporting Delay (64)
Enter a digit of '1' to '9' or 'A' to 'F' corresponding to the number of hours to be delayed in reporting the loss of AC
power. The factory default setting is '0' for 6 hour delay. If 24 hour battery backup is being employed, select from
choices '0' to '6'. If 60 hour battery backup is used, select from choices '7' to 'F'. Selections are:
Positive Alarm Sequence is used to delay Notification Appliance Circuit(s) activation while allowing for visual verification by a person. Once a zone triggers an alarm, the mainboard piezo and the annunciator piezo turn on steady,
the display indicates the activated zone, the alarm LED blinks and the Notification Appliance Circuits are held off for
15 seconds. During this time, if the silence switch is pressed, the notification appliances may be held off for up to
three minutes (see Alarm Presignal Delay Timer Address 66-68). After the programmed delay period, the notification appliances will activate. Alarm Presignal does not function for zones defined as waterflow or supervisory. The
factory default is '0' for no Alarm Presignal. Enter '1' to select Alarm Presignal. During Alarm Presignal, access to
other modes is prevented and the communicator will not
transmit a signal to the Central Station signifying that the
Alarm Presignal has been initiated.
Alarm Presignal Delay Timer (66-68)
The Alarm Presignal timer is factory set to 120 seconds (two minutes), with address 66 set to '1', address 67 set to '2'
and address 68 set to '0'. The timer may be programmed from 0 to 179 seconds. Location 65 must be set to '1' to
enable Alarm Presignal.
Notification Appliance Circuit #1 Enable (69)
Notification Appliance Circuit #1 may be programmed to '0' for silenceable, '1' for nonsilenceable or '2' for disabled.
The factory default setting is '0' for silenceable. Consult the local Authority Having Jurisdiction (AHJ) prior to
Setting address 70 to '1' prevents silencing of Notification Appliance Circuit #1 and the on-board piezo sounder for
one minute after an alarm. The factory default setting is '0' for no silence inhibit of Notification Appliance Circuit #1.
Notification Appliance Circuit #1 may be autosilenced after a programmed time interval between 5 and 30 minutes.
Enter '1' for 5 minute autosilence, '2' for 10 minute autosilence, '3' for 15 minute autosilence, '4' for 20 minute autosilence, '5' for 25 minute autosilence or '6' for 30 minute autosilence. The factory default setting is '0' for no
autosilence.
Coding Notification Appliance Circuit #1 (72)
Coding of Notification Appliance Circuit #1 can be programmed by selecting '1' for March Time (120 ppm), '2' for
California (10 seconds On, 5 seconds Off) or '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second
Off, ½ second On, 1½ second Off). The factory default setting is '0' for steady (no coding).
Notification Appliance Circuit #2 Enable (73)
Notification Appliance Circuit #2 may be programmed to '0' for silenceable, '1' for nonsilenceable or '2' for disabled.
The factory default setting is '0' for silenceable. Consult the local Authority Having Jurisdiction (AHJ) prior to
Setting address 74 to '1' prevents silencing of Notification Appliance Circuit #2 and the on-board piezo sounder for
one minute after an alarm. The factory default setting is '0' for no silence inhibit of Notification Appliance Circuit #2.
Notification Appliance Circuit #2 may be autosilenced after a programmed time interval between 5 and 30 minutes.
Enter '1' for 5 minute autosilence, '2' for 10 minute autosilence, '3' for 15 minute autosilence, '4' for 20 minute autosilence, '5' for 25 minute autosilence or '6' for 30 minute autosilence. The factory default setting is '0' for no
autosilence.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
43
Programming Options
Coding Notification Appliance Circuit #2 (76)
Coding of Notification Appliance Circuit #2 can be programmed by selecting '1' for March Time (120 ppm), '2' for
California (10 seconds On, 5 seconds Off) or '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second
Off, ½ second On, 1½ second Off). The factory default setting is '0' for steady (no coding).
Trouble Reminder (77)
The factory default setting of '0' disables the trouble reminder feature. Selecting '1' will cause a reminding beep (after
the Silence switch is pressed) every 15 seconds during an alarm and every two minutes during a trouble condition.
The beeps from the on-board piezo sounder will occur until the alarm or fault is cleared.
Annunciator Supervision (78)
The factory default setting is '0' for no annunciator present. Set address 78 to '1' if an annunciator is present.
Backup Reporting (79)
Leaving address 79 at '0' means that reports will be transmitted to the secondary Central Station phone number only if
attempts to communicate to the primary Central Station phone number are unsuccessful. Programming a '1' causes
all reports to be transmitted to the secondary Central Station phone number.
Touchtone/Rotary Select (80)
A '0' programmed in this address by the factory triggers Touchtone dialing over both phone lines. Select '1' for rotary
dialing.
Make/Break Ratio (81)
Use this address only if you have chosen '1' for address 80. The make/break ratio is factory set to '0' which is 67/33,
but may be changed to '1' which is a 62/38 ratio.
Programming Event Codes (82-313)
The type of reports and 'event codes' that are sent to the Central Station are in the preceding Tables. The selections
made for the Primary Central Station Number Communication Format (address 16) and the Secondary Central Station Number Communication Format (address 42) automatically program addresses 82-313 with factory default
selections.
Any of the event codes may be changed. Consult your Central Station prior to altering the event codes. Entering an
event code of '0' will cause the communicator to not
transmit the report. For the 3+1, 4+1 and 4+2 Express formats or
the 4+2 Expanded format, enter a single zero. For the 4+2 Standard or 4+2 Express formats enter two zeros. Transmission of reports to either or both Central Station phone numbers may be disabled.
Note the special 'system abnormal test report' event code. This report was added per new UL DACT requirements.
This report is generated in place of the normal test report when an alarm and/or trouble condition exists at the time
the test report is due to be sent.
Programming the Real-Time Clock
Entering an address greater than 313 will cause a display of the current time. On initial power-up, the clock will start
running from the factory setting of 00:01 (military time). The far left digit will be flashing, indicating that this is the
first digit to be programmed.
44
Hours/Minutes Setting
Select a digit then press the [ENTER/STORE] key. The digit 2nd from the left will start flashing. Select a digit
then press the [ENTER/STORE] key. The hours setting is complete. With the digit 2nd from the right flashing,
select a digit then press the [ENTER/STORE] key. The digit on the far right will start flashing. Select a digit
then press the [ENTER/STORE] key. The minutes setting is complete. Once the last digit corresponding to the
minutes is entered, the display will show the contents of address '00'. Note that if an invalid digit is selected (i.e.
3 or higher for the first digit) the FACP piezo will beep and the digit will continue to blink until a valid entry is
made.
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Options
Note that the software for the MS-5024 operates the internal clock based upon 60 Hz. The software for the
MS-5024E operates the internal clock based upon 50 Hz.
End Programming
Exit Programming Mode by pressing the MODE key, followed by the 4-digit code corresponding to an alternate
mode of operation, then press the [ENTER/STORE] key.
During Program Mode, if no key is pressed within 10 minutes, the control panel will revert to Normal Mode.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
45
Operating Instructions
CHAPTER 4Operating Instructions
The MS-5024 has five modes of operation; Normal, Program, Walktest, Troubleshoot and History. Upon initial
power-up, the system will be in Normal Mode. This chapter discusses operation of the control panel in the Normal
Mode.
4.1Switches
This section describes the function switches in Normal Mode.
4.1.1 Reset
The Reset Switch resets the system and any smoke detectors. If the Reset Switch is pressed, the control panel will:
• Clear the display and status LEDs
• Turn off the Notification Appliance Circuits
• Reset all zones by temporarily removing power
• Silence the on-board piezo sounder
• Store 'reset' message in the History file
• Restore the programmable relays to normal
• Temporarily remove power from the resettable power output TB4 Terminals 3 & 4
Upon release of the Reset Switch, the display will read rES_ for six seconds. Any alarm, supervisory or trouble condition that exists after system reset will resound the system, reactivating normal system activity.
4.1.2 Silence
If the Silence Switch is pressed:
• The silenceable Notification Appliance Circuits will be turned Off
• The silence LED will be turned On
• The piezo sounder will be shut Off
• 'System Silenced' message will be stored in the History file
46
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Display and LEDs
Upon the occurrence of a subsequent event (alarm or trouble), System Silence is overridden and the control panel will
respond to the new event. The System Silence switch will be ignored for nonsilenceable waterflow type alarms.
4.1.3 Mode
Pressing the Mode Switch followed by a valid 4-digit numerical code and the [ENTER/STORE] key selects one of
the five modes of operation. To enter Normal Mode from any other mode, press the MODE key then 6676 followed
by the [ENTER/STORE] key.
6676 spells NORM on a Touch-Tone
☛
®
phone.
4.1.4 1st Event
This switch, along with the Up Arrow and Down Arrow keys, is used to display any presently active alarm and/or
fault conditions present in the system. Press the 1st Event switch at any time to display the first event (alarm and/or
trouble) that occurred.
4.1.5 Down Arrow
Use the Down Arrow key to view other events (older) that have occurred and are active (not yet cleared).
4.1.6 Up Arrow
Use the Up Arrow key to view other events (newer) that have occurred and are active (not yet cleared).
4.1.7 [ENTER/STORE]
See individual mode descriptions in other sections of this manual.
4.2Display and LEDs
Four 7-segment red LED characters provide visual annunciation of status, events and messages. A list of messages
that may appear on the display in Normal Mode is shown below:
d__1Zone 1 Disabled
d__2Zone 2 Disabled
d__3Zone 3 Disabled
d__4Zone 4 Disabled
d__5Zone 5 Disabled
E__1Zone 1 Enabled
E__2Zone 2 Enabled
E__3Zone 3 Enabled
E__4Zone 4 Enabled
E__5Zone 5 Enabled
A__1Alarm Zone 1
A__2Alarm Zone 2
A__3Alarm Zone 3
A__4Alarm Zone 4
A__5Alarm Zone 5
F__1Trouble Zone 1
F__2Trouble Zone 2
F__3Trouble Zone 3
F__4Trouble Zone 4
F__5Trouble Zone 5
rES_System Reset
F__AAnnunciator Fault
F__EEarth Fault
Lo_bLow Battery
no_bNo Battery
PH_1Primary Central Station Number Comm. Fault
PH_2Secondary Central Station Number Comm.
Fault
bEL1Bell 1 Fault
bEL2Bell 2 Fault
no_1Primary Phone Line Fault
no_2Secondary Phone Line Fault
SUP1Supervisory Alarm Zone 1
SUP2Supervisory Alarm Zone 2
SUP3Supervisory Alarm Zone 3
SUP4Supervisory Alarm Zone 4
SUP5Supervisory Alarm Zone 5
_AC_AC Power Loss
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
47
Display and LEDs
Individual LEDs are provided for:
System Alarm
A red LED that turns on steady when an alarm condition is detected and blinks during alarm Positive Alarm
Sequence period.
System Trouble
A yellow LED that blinks to indicate a fault or abnormal condition exists and that the fire alarm system may be
inoperative. It turns on steady when the silence switch is pressed.
AC Power On
A green LED that remains on while the AC power supply is within correct limits. If this indicator fails to light under
normal conditions, service the system immediately.
Supervisory
A yellow LED that blinks to indicate the need for action in connection with the supervision or maintenance of
sprinklers, extinguishing systems or other protective systems.
System Silence
A yellow LED that turns on to indicate that an alarm or trouble condition exists in the system, but both Notification
Appliance Circuits (if programmed as silenceable) and local piezo have been silenced.
Primary Line Active
A red LED that indicates the primary phone line is active.
Secondary Line Active
A red LED that indicates the secondary phone line is active.
Kissoff
A green LED that blinks when a Central Station has acknowledged receipt of each transmitted message.
FIGURE 4-1:
Phone Connectors and LEDs
Primary Phone Line
Primary
Secondary Phone Line
Kiss-off
Active
LED
LED
48
Secondary Active LED
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Operation
4.3Operation
Normal Mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When
no alarm or trouble conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED).
The Notification Appliance Circuits will be off, all relays are normal and the onboard piezo sounder will be off. The
communicator is not active, primary and secondary active LEDs are off.
All alarm and system trouble conditions are annunciated on the control panel’s display. The control panel will maintain an 'active event list' which will consist of all alarms, supervisory alarms and system troubles currently active and
not cleared, requiring immediate service. When the system is cleared and restored to normal, the display will be
blank. All alarms and troubles are stored in a history file and may be recalled at any time.
Higher priority events take precedence over lower priority events. Display and reporting of system status is done on
a priority basis. Priorities are, from highest to lowest:
Alarms
1.
Supervisory Alarms
2.
System Troubles
3.
If the events to be displayed consist of alarms and disabled zones only (no troubles), the control panel will scroll them
on the display. Pressing the 1st Event key will stop the scrolling and cause the display of the first alarm that occurred
after the panel was last reset, cleared of all active events and placed into Normal Mode. Operation of the Up and
Down arrow keys will display all remaining events in order of their occurrences.
4.3.1 Alarm Response
The control panel will, upon detection of an alarm condition:
• Turn on the alarm LED
• Activate relay(s) programmed for alarm
• Display the alarm message, for example A__1 for alarm on zone 1
• Communicate the alarm to the Central Station
• Store the alarm in the History file
• Turn on the Notification Appliance Circuits
• Turn on the piezo sounder
• Turn on the annunciator zone LED and annunciator piezo sounder
Note that when any zone is programmed as a supervisory zone, it will not be processed in the same manner as a conventional alarm zone. See “System Supervisory Condition Response” on page 50.
4.3.2 Alarm Restoral
The control panel returns to normal only after all alarms have been cleared and the Reset switch has been pressed
(pull stations reset, smoke detectors reset and no smoke present, waterflow has stopped). The control panel will
perform the following upon restoral of all active alarms:
• Turn off the alarm LED
• Deactivate the alarm relay(s) if programmed
• Clear the 4-character display
• Send all 'zone restoral' messages to the Central Station
• Turn off the Notification Appliance Circuits
• Turn off the piezo sounder
• Turn off the annunciator zone LED and annunciator piezo sounder
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
49
Operation
4.3.3 System Supervisory Condition Response
Program zones for supervisory in applications where a waterflow sensing device has been employed and the wiring to
the waterflow valve and/or tamper switch is to be monitored. If the wiring has been cut or the tamper switch has been
activated, a supervisory alarm condition will occur.
When a supervisory condition occurs, the control panel will:
• Blink the supervisory LED (½ second On, ½ second Off)
• Activate the supervisory relay(s) if programmed
• Display the following message: SUPX where X is the zone number
• Communicate the supervisory condition to the Central Station
• Store the 'supervisory' message in the History file
• Pulse the piezo sounder at ½ second on and ½ second off rate
• Turn on the annunciator zone LED and pulse the annunciator piezo
4.3.4 System Supervisory Restoral Response
When the supervisory condition has been cleared (condition is restored and the reset switch has been pressed), the
control panel will perform the following:
• Turn off the supervisory LED
• Deactivate the supervisory relay(s) if programmed
• Clear the display of the SUP message
• Communicate a supervisory restoral message to the Central Station
• Turn off the piezo sounder
• Turn off the annunciator zone LED and annunciator piezo sounder
Note that for any zone programmed for supervisory autoresettable, the Reset key does not need to be pressed to clear
the zone supervisory condition.
4.3.5 Trouble Condition Response
The control panel will perform the following upon detection of one or more trouble conditions:
• Blink the trouble LED (1 second on, 1 second off)
• Activate the trouble relay(s) if programmed
• Display the appropriate trouble message(s) in priority fashion from the highest priority to the lowest. Note
that the Up arrow, Down arrow or 1st Event key must be pressed to view the messages
• Communicate the trouble conditions to the Central Station
• Store the trouble conditions in the History file
• Sound the piezo sounder (1 second on, 1 second off)
• Blink the annunciator trouble LED and pulse the piezo sounder
Note that when AC brownout occurs, the AC LED is turned off and the trouble LED blinks. Should the brownout condition remain, it will be transmitted to the Central Station after a delay (see program address 64).
50
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Operation
Possible trouble messages that may appear on the display are as follows:
d__1Zone 1 Disabled
d__2Zone 2 Disabled
d__3Zone 3 Disabled
d__4Zone 4 Disabled
d__5Zone 5 Disabled
F__1Trouble Zone 1
F__2Trouble Zone 2
F__3Trouble Zone 3
F__4Trouble Zone 4
F__5Trouble Zone 5
F__AAnnunciator Fault
F__EEarth Fault
Lo_bLow Battery
no_bNo Battery
PH_1Primary Central Station Number Comm. Fault
PH_2Secondary Central Station Number Comm.
Fault
bEL1Bell 1 Fault
bEL2Bell 2 Fault
no_1Primary Phone Line Fault
no_2Secondary Phone Line Fault
4.3.6 Trouble Conditions Restoral
The control panel performs the following upon restoral of all trouble conditions:
• Turn off the trouble LED
• Deactivate the trouble relay(s) if programmed
• Turn on the AC Power LED if the trouble was loss of AC power
• Clear the display of the trouble message(s)
• Communicate the restored trouble condition(s) to the Central Station
4.3.7 Off Normal Reporting
Removing the panel from Normal Mode and placing it into any other mode causes a transmission of an 'off normal'
fault message. Returning the panel to Normal Mode causes a transmission of a 'return to normal' restoral message.
4.3.8 Zone Disable/Enable
The zone disable feature may be used to disable any zone in the system. Zones may be disabled if they are normal, in
trouble or in alarm. Zones may be disabled only during the Normal Mode of operation when the fire protection is
active. If the panel is in alarm, the silence switch must be pressed first before zone disable will function.
To disable a zone, press the MODE key once. The display will go blank. You then have 10 seconds to start entering
the code 3472. Next, press the [ENTER/STORE] key.
3472 spells DISA on a Touch-Tone
☛
A flashing lower case d will appear on the far left of the display. Press the zone number to be disabled. The number
will appear on the far right display character. Pressing the [ENTER/STORE] key will disable the selected zone.
Note that the relay (if programmed for trouble) is activated and the trouble LED will blink.
The zone disable message will remain on the display until the zone is enabled. To enable a zone, press the MODE
key once. The display will go blank. You then have 10 seconds to start entering the code 3622. Press the [ENTER/
STORE] key.
3622 spells ENAB on a Touch-Tone
☛
A flashing upper case E will appear on the left of the display. Press the zone number to be enabled. The number will
appear on the far right display character. Pressing the [ENTER/STORE] key will enable the selected zone. Note
that the relay (if programmed for trouble) is restored to normal and the trouble LED will turn off if no other troubles
exist on the system.
®
phone
®
phone
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
51
Central Station Communications
4.3.9 Fire Drill
The Drill (manual evacuate) feature turns on both Notification Appliance Circuits (if programmed as enabled) and
turns off the silence LED. To perform a fire drill, press the MODE key followed by the code 3745 and then the
[ENTER/STORE] key. The display will read dril. The relay (if programmed for alarm) is not activated. There is an
option to transmit the fire drill report code to the Central Station.
3745 spells DRIL on a Touch-Tone
☛
®
phone
During a fire drill, the Silence key will silence both Notification Appliance Circuits and the Reset key restores the
panel to normal. All zones remain active during a fire drill.
4.3.10 No Battery/Low Battery
This control panel detects two levels of battery fault conditions, low battery and no battery. The low battery condition is 20.4 volts per NFPA and UL requirements. The no battery condition can occur if a battery is not installed or if
the battery voltage drops below the 'no battery threshold' voltage limit. The no battery threshold voltage is the minimum voltage required to operate the system fully under loss of AC power. This voltage must be high enough to
power initiating devices, power notification appliances and provide internal power to system components including
the microprocessor. Both the no battery and low battery condition may be reported to the Central Station.
When AC power is lost and the system is running on battery, the panel will report 'loss of AC power' to the Central
Station after a programmed delay period. The panel will report 'low battery' when the low battery threshold is
reached. If AC power is not restored and the 'no battery' threshold is reached, the panel will power off. This prevents
false alarms, nuisance reports and incorrect panel operation when the battery falls to dangerous levels. After the AC
power is restored, the no battery (no_b) message will appear. The battery must be disconnected from the system and
either replaced or allowed to restore itself before being reinstalled.
CAUTION! Be certain to clear the no
the panel will not clear itself. The low
battery condition since the battery will not recharge from this condition and
battery condition will self-clear when the battery recharges, provided the
battery is good.
4.4Central Station Communications
The control panel transmits zone and system status reports to Central Station via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two
7-foot telephone cables are required for this purpose and must be ordered separately.
The control panel supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault
on either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will
sound, the yellow trouble LED will blink, the 4-character display will show either 'no_1' for Primary Line fault or
'no_2' for Secondary Line fault, and the trouble condition will be reported to the Central Station over the remaining
good phone line.
The control panel comes with line seizure capability provided for both the primary and secondary telephone line
interfaces. Any time that the control panel needs to make a call to a Central Station, line seizure will disconnect any
local premises phones sharing the same telephone line.
All transmissions to the Central Stations will be sent over the Primary Central Station phone line. In the event of
noisy phone lines, transmissions will be sent over the backup Secondary phone line.
Two phone numbers must be programmed, the Primary Central Station phone number and the Secondary Central Station phone number. All system reports will be transmitted to the Primary Central Station phone number. Reports will
automatically be sent to the Secondary Central Station phone number if attempts to transmit to the Primary Central
52
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Central Station Communications
Station phone number are unsuccessful. If 10 total attempts to communicate are unsuccessful, the relay(s) will activate if programmed for communications failure. Note that as an option, all reports may also be sent to the Secondary
Central Station phone number.
The MS-5024 meets NFPA 72 National Fire Alarm Code reporting requirements for (1) type of signal, (2) condition
and (3) location of the reporting premises. The general priority reporting structure is:
Zone Alarms and Restores
1.
Zone Troubles and Restores
2.
System Trouble and Restores
3.
24-hour test
4.
The control panel is capable of reporting detailed messages depending upon the format in use. Table 4-1 shows the
reporting structure for all formats.
AC Loss RestoreSSS(S) RPSSS(S) RPSSSS RPRP2SSSS RPRP2
Fire DrillSSS(S) FdSSS(S) FdSSSS FdFd2SSSS FdFd2
Fire Drill RestoreSSS(S) RFdSSS(S) RFdSSSS RFdRFd2SSSS RFdRFd2
Supervisory ConditionSSS(S) V
Supervisory Condition
Restore
Test ReportSSS(S) XSSS(S) XSSSS XX2SSSS XX2
3+1/4+1/Standard
4+1 Express
SSS(S) TZ
SSS(S) RV
Format #
3, 5, 7, 9
3+1/4+1/Expanded
SSS(S) A
AAA(A) Z
SSS(S) RA
RARARA(RA) Z
SSS(S) TZ
TZTZTZ(TZ) Z
SSS(S) RTZ
RTZ RTZRT Z(RTZ) Z
SSS(S) TS
TSTSTS(TS) Y
SSS(S) RTS
RTS RTSRT S(RTS ) Y
SSS(S) DZ
DZDZDZ(DZ) Z
SSS(S) RDZ
RDZRDZRDZ(RDZ) Z
SSS(S) V
VVV(V) Z
SSS(S) RV
RVRVRV( RV ) Z
Format #
1, A, C
4+2/Standard
4+2 Express
SSSS AA2SSSS AZ
SSSS RARA2SSSS RAZ
SSSS TZTZ2SSSS TZZ
SSSS RTZRTZ2SSSS RTZZ
SSSS TSTS2SSSS TSY
SSSS RTSRTS2SSSS RTSY
SSSS DZDZ2SSSS DZZ
SSSS RDZRDZ2SSSS RDZZ
SSSS VV2SSSS VZ
SSSS RVRV2SSSS RVZ
Format #
B, D
4+2/Expanded
Refer to Table 4-2 on page 54 for an explanation of each letter code in Table 4-1 .
Refer to Table 4-3 on page 56 for a list of compatible receivers.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
53
Central Station Communications
4.4.1 Transmittal Priorities
The integral communicator transmits highest priority events first. Events in terms of priority are listed below in
descending order:
1: Alarms (highest Priority Level)
Pull Stations
Waterfl ow
Smoke Detector
Other Alarm Types
2: Supervisory Zone
3: System Troubles
Zone Disabled
Fire Drill
AC Fail (after delay)
Zonal Faults
Earth Fault
Low Battery/No Battery
Telephone Line Fault
Notification Appliance Circuits Fault
Communication Trouble
Annunciator Trouble
System Off Normal
4: Restoral Reports
Zone Alarm
Supervisory
Zone(s) Enabled
Fire Drill
AC
Zone Fault
Earth
Battery
Telephone Line
Notification Appliance Circuits
Communication
Annunciator Trouble
System Off Normal
5: 24 Hour Test (Lowest Priority)
Red LEDs are provided on the control panel circuit board to identify which telephone line is activated. Also, a green
LED (labeled 'Kissoff') will turn on whenever the control panel has successfully transmitted reports to the Central
Station. The 'Kissoff' LED may turn on several times during communications with a Central Station.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
55
Servicing
CHAPTER 5Servicing
5.1Walktest Mode
The MS-5024 provides the capability to perform a one-man walktest of the system without triggering the communicator or the alarm relay (if programmed). Walktest allows for testing of the five zones (initiating circuits). The first
initiating device activated on a zone will cause the Notification Appliance Circuits to turn on for four seconds.
Subsequent device activations on the same zone will cause the Notification Appliance Circuits to turn on for one
second. Any smoke detectors that are activated will be reset. Zonal faults (open circuits) will cause the appliance
circuit to remain on steadily. Prior to entering Walktest Mode, check to be certain that all system faults have been
cleared. Note that the trouble relay will be activated (if programmed) while the control panel is in this mode. Placing
the control panel into Walktest Mode will be possible only if the system has no active alarms.
Pressing the MODE key followed by the 4-digit code 9255 and then the [ENTER/STORE] key will place the control panel into Walktest Mode.
9255 spells WALK on a Touch-Tone
☛
Once in Walktest Mode, the control panel will immediately:
®
phone.
• Blink the trouble LED
• Activate the trouble relay(s) if programmed
• Turn on the Notification Appliance Circuits for four seconds for the first alarm on a zone. Subsequent alarms
will sound for one second. Troubles cause the Notification Appliance Circuits to remain on
• Disable the alarm relay(s) if programmed
• Display all alarm conditions as they occur
• Display all zone troubles as they occur
• Display ground faults as they occur
• Transmit 'off normal' message to Central Station(s)
• Continue to communicate any events not acknowledged at a Central Station prior to entering Walktest Mode
During Walktest Mode, zonal activity is displayed in real time as it occurs. At the end of walktesting the system, the
display will show the last event that occurred. To view all events stored during the walktest, use the Up arrow, Down
arrow and 1st Event keys. The Down arrow key moves the walktest list to show older (previous) events. The Up
arrow key moves the walktest list to show newer (most recent) events. Pressing the 1st Event key at any time will
cause the display of the first event stored upon initial entry into Walktest Mode. While in Walktest Mode, the control
panel will store up to 128 events in the walktest file for future recall and display.
To return the control panel to Normal Mode, press the MODE key followed by the code 6676 and then the [ENTER/STORE] key. Any delay between key entries greater than 10 seconds causes the control panel to remain in Walktest
Mode.
The control panel will automatically revert back to Normal Mode if no system activity has occurred for 60 minutes.
This would include pressing any keys or activity on any zone.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
57
History Mode
5.2History Mode
All Normal Mode events are stored in a History file for future recall. Recall is possible via the 4-character display.
See the following page for a list and description of each event displayed.
The History file list is a first-in, first-out (FIFO). In this manner, only the most recent events may be called up from
memory. Old events will be overwritten (i.e. pushed out of the FIFO). The number of stored events is 32. This
History file is kept in E
Pressing the MODE key followed by 4478 and then the [ENTER/STORE] key places the control panel into History
Mode. This will not occur if there are any active alarm conditions present. The event displayed is the most recent
event.
☛
Once in History Mode, the control panel will:
• Blink the trouble LED
• Activate the trouble relay(s) if programmed
• Disable the Notification Appliance Circuit(s)
• Disable the alarm relay(s) if programmed
• Display all events as they occurred since the last time the History file list was cleared. The most recent event
will be displayed first
• Ignore all other keys other than those mentioned in this section
• Transmit the 'off normal' message to the Central Station(s)
• Continue to communicate any events not previously acknowledged at the Central Station prior to entering History Mode
2
memory. Complete power loss will not erase the list.
4478 spells HIST on a Touch-Tone
®
phone.
The Down arrow key moves the History file to show older (previous) events. The Up arrow key moves the History
file to show newer (most recent) events.
Shown below is the list of messages as they will appear on the display:
d__1Zone 1 Disabled
d__2Zone 2 Disabled
d__3Zone 3 Disabled
d__4Zone 4 Disabled
d__5Zone 5 Disabled
E__1Zone 1 Enabled
E__2Zone 2 Enabled
E__3Zone 3 Enabled
E__4Zone 4 Enabled
E__5Zone 5 Enabled
A__1Alarm Zone 1
A__2Alarm Zone 2
A__3Alarm Zone 3
A__4Alarm Zone 4
A__5Alarm Zone 5
F__1Trouble Zone 1
F__2Trouble Zone 2
F__3Trouble Zone 3
F__4Trouble Zone 4
F__5Trouble Zone 5
rES_System Reset
F__AAnnunciator Fault
F__EEarth Fault
Lo_bLow Battery
no_bNo Battery
PH_1Primary Central Station Number Comm. Fault
PH_2Secondary Central Station Number Comm.
Fault
bEL1Bell 1 Fault
bEL2Bell 2 Fault
no_1Primary Phone Line Fault
no_2Secondary Phone Line Fault
SUP1Supervisory Alarm Zone 1
SUP2Supervisory Alarm Zone 2
SUP3Supervisory Alarm Zone 3
SUP4Supervisory Alarm Zone 4
SUP5Supervisory Alarm Zone 5
_AC_AC Power Loss
To erase the list from E
2
memory, press the Silence key twice before exiting the History Mode. A lack of keyboard
activity for a period of 10 minutes will cause the control panel to return to Normal Mode.
58
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Troubleshoot Mode
5.3Troubleshoot Mode
In this mode, system voltages may be displayed on the 4-character display. An internal voltmeter measures the
voltage present at:
• zone inputs
• AC power input
• battery terminal leads
• NAC #1
• NAC #2
• resettable 24 volt power
A lack of keyboard activity for a period of 20 minutes will cause the control panel to return to Normal Mode.
To enter Troubleshoot Mode, press the MODE key followed by the code 8768 and then the [ENTER/STORE] key.
8768 spells TROU on a Touch-Tone
☛
Once in this mode, the control panel will:
• Blink the trouble LED
• Activate the trouble relay(s) if programmed
• Disable the Notification Appliance Circuits
• Disable the alarm relay(s) if programmed
• Transmit the 'off normal' message to the Central Station(s)
• Continue to communicate any events not yet acknowledged at the Central Station prior to entering Troubleshoot Mode
®
phone.
The Up arrow key, Down arrow key and 1st Event key do not function in this mode.
5.3.1 Zones
Pressing 01 through 05 followed by the [ENTER/STORE] key displays the zone voltage of the selected zone. Listed
below are the nominal threshold voltages for each zone:
Zone #Normal w/EOLShortedOpen Circuit
1 through 523.5V00.0V25.4V
5.3.2 AC Line
Pressing A followed by the [ENTER/STORE] key displays the AC input voltage as shown below. The following
lists the AC line voltage range. The AC On indicator will turn off and the trouble LED will turn on when the AC line
voltage drops below the Low Line threshold.
AC Line VoltageLow LineNormalHigh Line
MS-5024102VAC115VAC132VAC
MS-5024E204VAC220VAC264VAC
5.3.3 Battery
Pressing B followed by the [ENTER/STORE] key displays the Battery voltage. Shown below are the critical battery
threshold conditions:
Battery VoltageNormalLow BatteryNo Battery
27.6 VDC20.4 VDC<14.2 VDC
IMPORTANT
(No Battery condition). A battery with a higher voltage must be installed to turn the charger back on.
Note: Make measurements after allowing 48 hours to charge depleted batteries. If batteries do not
show normal readings, replace them.
The battery charger will turn off when the battery voltage drops to 14.2 VDC or less
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
59
Lamp Test
5.3.4 NAC 1 & 2
Pressing B1 followed by the [ENTER/STORE] key displays the voltage on NAC #1.
Pressing B2 followed by the [ENTER/STORE] key displays the voltage on NAC #2.
NAC voltage readings are nominally -2.32 volts when an EOL resistor of correct value is in place. A reading of 0.00
volts appears for shorts, -4.50 volts for opens. Intermediate readings are also possible.
5.3.5 Resettable Power
Pressing the Reset key followed by the [ENTER/STORE] key displays the resettable 24 volt power. The resettable
power must read 24 volts (+/- 10%).
5.3.6 Telephone Lines
Pressing C for touchtone dialing or D for rotary dialing, followed by the [ENTER/STORE] key causes seizure of the
Primary phone line which in turn lights the red LED signifying Primary phone line active. After a delay of three
seconds, the control panel goes off-hook to acquire a dial tone.
The control panel keypad may be used as a telephone touchpad for number dialing. Once the first digit is pressed, the
display will move the C or D character one position to the left, while placing the digit to be dialed on the farthest right
display position. Continue to press the phone numbers to be dialed. Successive depressions of the [ENTER/STORE] key hangs-up and picks-up the phone (places the phone on or off the hook).
The secondary phone line may be tested by pressing the E key for touchtone dialing or the F key for rotary dialing
and then following the same procedure used for the primary phone line.
A handset may be temporarily connected across transformer T1 as indicated in Figure 5-1. The handset, when
connected across T1, may be used only as an amplifier/speaker and telephone with the control panel used for number
dialing.
FIGURE 5-1:
Handset/Speaker Connection
Both Primary and Secondary Lines
5.4Lamp Test
To perform a Lamp Test, press the MODE key, then the code 5267 followed by the [ENTER/STORE] key. This will
test all system LEDs except the Primary Active LED, Secondary Active LED and Modem LED. The LEDs will stay
on for five seconds, then the control panel will return to Normal Mode.
®
phone
60
5267 spells LAMP on a Touch-Tone
☛
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Slave Communicator Configuration
CHAPTER 6Slave Communicator Configuration
The MS-5024 may be used as a slave communicator to a host or master FACP (fire alarm control panel). All wiring
between the master and the slave communicator is supervised. 4.7K ohm End-of-Line resistors should be connected.
In slave configuration, the five zones become five channels that may be triggered by the relay outputs of any host
FACP. The inputs have the following functions in the slave configuration:
• Zone 1/Channel 1 is used for general alarm
• Zone 2/Channel 2 is used for general trouble
• Zone 3/Channel 3 may be programmed to match the FACP relay function used as an input
• Zone 4/Channel 4 is used for supervisory
• Zone 5/Channel 5 may be programmed to match the FACP relay function used as an input
The factory settings for Zone 2/Channel 2 alarm and restoral are altered as follows:
❒
If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, the report code for Zone 2 Alarm Code
(address 83, 199) is 'F', Zone 2 Restoral Code (address 111, 227) is 'E'
❒
If 1, A or C is entered for address 16 or 42, the report code for Zone 2 Alarm Code (addresses 84-85, 200-
201) is 'FF', Zone 2 Restoral Code (addresses 140-141, 256-257) is 'EF.'
The factory settings for Zone 4/Channel 4 alarm and restoral are altered as follows:
❒
If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, report code for Zone 4/Channel 4 Alarm
Code (address 85, 201) is '8', Zone 4 Restoral Code (address 113, 229) is 'E.'
❒
If 1, A or C is entered for addresses 16 or 42, the report code for Zone 4 Alarm Code (addresses 88-89, 204-
205) is 84, Zone 4 Restoral Code (addresses 144-145, 260-261) is 'E4.'
Location 56 must be programmed to a '1' to enable the control panel as a slave communicator.
Be certain to connect the slave communicator’s primary AC power to the same branch circuit as the host FACP.
Note that Alarm Presignal and Alarm Verification do not function in Slave Communicator Mode.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
61
Slave Communicator Configuration
FIGURE 6-1:
Slave Communicator Connections
Relays in the master FACP activate various input circuits on the slave communicator. Messages (event codes) programmed for a particular input circuit (channel) will be transmitted to the Central Station upon relay activation.
62
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Battery Calculations
Appendix ABattery Calculations
Use the Total Standby and Alarm Load currents calculated in Table A-2 on page 64 and Table A-3 on page 65 for the
following battery calculation.
TAB L E A-1:
Standby Load
Current (amps)
[ ]
Alarm Load
Current (amps)
[ ]
Add Standby and Alarm Load for Required Ampere Hour Battery=__________
Battery Calculations
Required Standby Time in
X
X
Multiply by the Derating Factor of 1.2X 1.2__________
Total Ampere Hours (AH) Required=__________
Hours (24 or 60 Hours)
[ ]
Required Alarm Time in Hours
(i.e. 5 minutes = 0.084)
[ ]
=__________
=__________
Notes:
7 Ampere Hour battery can be located in the backbox
1.
12 Ampere Hour and 17 Ampere Hour batteries require the BB-17F battery box
2.
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
63
Battery Calculations
Main Power Supply
The MS-5024 provides filtered power for operating the fire alarm control panel, operating external devices and operating the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or nonalarm)
and Table A-3 on page 65 (alarm) to determine if external loading is within the capabilities of the power supply.
Concerning 4-wire smoke detectors: be sure to power detectors from TB4, Terminals 3 & 4.
Note that all external devices are connected to TB4 only
TABLE A-2:
Regulated Load in Standby
.
Current
Device Type# of Devices
(amps)
Main Circuit Board1X0.123=0.123
ADM-24(1 maximum)X0.006=
RZA-5F(1 maximum)X0=0
CAC-5F(1 maximum)X0=0
NACA-2F(1 maximum)X0=0
2-wire Detector Heads[ ]X
4-wire Detector Heads[ ]X
Power Supervision Relays
2
[ ]X0.025=
[ ]
[ ]
1
1
=
=
Tot a l Curr e nt
(amps)
Additional Current Draw
from TB4 (nonalarm)
X=
Sum Column for Standby Load=amps
Notes:
Refer to the Device Compatibility Document for 2-wire smoke detector standby current
1.
Must use compatible listed Power Supervision Relay
Total current draw listed above cannot exceed 3.6 amps
2.
Must use compatible listed Power Supervision Relay
3.
The current shown for the RZA-5F is for all five zones in alarm. For one zone in alarm, the RZA-5F current
4.
draw is 16 mA
The current shown represents one zone on the Main Circuit Board in alarm. For all five zones in alarm, the
5.
current draw increases to 0.39 amps
Relays may be programmed for alarm, trouble, supervisory, communications failure or any combination of
6.
these
RMS
RMS
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
65
Programming Reference Sheet
f
f
f
f
Appendix BProgramming Reference Sheet
...To enter Programming Mode, press the
MODE
key, the code
and then the
7764
[ENTER/STORE]
key...
❐00❐01❐02❐03❐04❐05❐06❐07❐08❐09❐10❐11❐12❐13❐14❐
Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.
❐
Primary Central Station Communication Format: Enter '0 - D'.
16
❐17❐18❐19❐
❐21❐22❐23❐
❐
Primary Number Test Time Interval. Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
25
Primary Central Station Account Code: Valid entries are '0 - F'.
20
Primary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
24
❐26❐27❐28❐29❐30❐31❐32❐33❐34❐35❐36❐37❐38❐39❐40❐
Addresses 26 to 41 store the Secondary Central Station Phone Number. Enter 'F' to represent the end of the number.
❐
Secondary Central Station Communication Format: Enter '0 - D'.
42
❐43❐44❐45❐
❐47❐48❐49❐
❐
Secondary Number Test Time Interval. Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
51
❐
Alarm Verification. Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
52
❐
Programmable Relay 1: Enter '0' to Disable; '1' for Alarm; '2' for Supervisory; '3' for Alarm or Supervisory;
53
'4' for Trouble; '5' for Alarm or Trouble; '6' for Supervisory or Trouble; '7' for Alarm or Supervisory or Trouble; '8'
or Communication Failure; '9' for Alarm or Communication Failure; 'A' for Supervisory or Communication Failure; 'B' for Alarm or Supervisory or Communication Failure; 'C' for Trouble or Communication Failure; 'D' for
Alarm or Trouble or Communication Failure; 'E' for Supervisory or Trouble or Communication Failure; 'F' for
Alarm or Supervisory or Trouble or Communication Failure.
Secondary Central Station Account Code: Valid entries are '0 - F'.
46
Secondary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
50
15
41
❐
Programmable Relay 1: Enter '0' to Disable; '1' for Alarm; '2' for Supervisory; '3' for Alarm or Supervisory;
54
'4' for Trouble; '5' for Alarm or Trouble; '6' for Supervisory or Trouble; '7' for Alarm or Supervisory or Trouble; '8'
or Communication Failure; '9' for Alarm or Communication Failure; 'A' for Supervisory or Communication Failure; 'B' for Alarm or Supervisory or Communication Failure; 'C' for Trouble or Communication Failure; 'D' for
Alarm or Trouble or Communication Failure; 'E' for Supervisory or Trouble or Communication Failure; 'F' for
Alarm or Supervisory or Trouble or Communication Failure.
❐
Future use.
55
❐
Slave Communicator/Fire Panel Selection. Enter '0' for fire panel only; '1' for slave communicator only; '2'
56
or fire panel/communicator operation.
❐
Zone 1 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
57
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
Zone 2 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
58
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
Zone 3 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
59
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6'
or waterflow (nonsilenceable).
66
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Reference Sheet
f
f
❐
Zone 4 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
60
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
Zone 5 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
61
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐62❐
❐
64
hours; '5' for 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19
hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
❐
65
❐66❐67❐
❐
69
(nonsilenceable); '2' for disabled.
❐
70
❐
71
or 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❐
72
onds Off); '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off).
❐
73
(nonsilenceable); '2' for disabled.
❐
74
Waterflow Retard Timer. Enter 0 - 89 additional seconds.
63
AC Loss Reporting Delay. Enter '0' for 6 hour delay; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10
Alarm Presignal. Enter '0' to disable alarm presignal; '1' to enable.
Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.
A
❐
Primary Central Station Communication Format: 'A' for 4+2 Standard, 1800/2300.
16
000 0
❐17❐18❐19❐
000 0
❐21❐22❐23❐
0
❐
Primary Number Test Time Interval. '0' for 24 hours.
25
FFFFFFFFFFFFFFFF
❐26❐27❐28❐29❐30❐31❐32❐33❐34❐35❐36❐37❐38❐39❐40❐
Addresses 26 to 41 store the Secondary Central Station Phone Number. Enter 'F' to represent the end of the number.
A
❐
Secondary Central Station Communication Format: 'A' for 4+2 Standard, 1800/2300.
42
000 0
❐43❐44❐45❐
000 0
❐47❐48❐49❐
0
❐
Secondary Number Test Time Interval. 0' for 24 hours.
51
0
❐
Alarm Verification. '0' for no verification.
52
1
❐
Programmable Relay #1. '1' for alarm only.
53
4
❐
Programmable Relay #2. '4' for trouble only.
54
0
❐
Future use.
55
0
❐
Slave Communicator/Fire Panel Selection. 0' for fire panel only operation.
56
0
❐
Zone 1 Function Select. '0' for 2-wire smoke detectors.
57
0
❐
Zone 2 Function Select. '0' for 2-wire smoke detectors.
58
0
❐
Zone 3 Function Select. '0' for 2-wire smoke detectors.
59
0
❐
Zone 4 Function Select. '0' for 2-wire smoke detectors.
60
0
❐
Zone 5 Function Select. '0' for 2-wire smoke detectors.
61
00
❐62❐
0
❐
64
0
❐
65
120
❐66❐67❐
0
❐
69
0
❐
70
0
❐
71
Waterflow Retard Timer. '00' for no delay.
63
AC Loss Reporting Delay. '0' for 6 hour delay.
Alarm Presignal. '0' for no Positive Alarm Sequence.
68
Notification Appliance Circuit #1 Selection. '0' for enabled (silenceable).
Silence Inhibit NAC #1. '0' for no silence inhibit.
Autosilence NAC #1. '0' for no autosilence.
Primary Central Station Account Code.
20
Primary Central Station 24-Hour Test Time. 0000 = 12:00 midnight.
24
Secondary Central Station Account Code.
46
Secondary Central Station 24-Hour Test Time. 0000 = 12:00 midnight.
50
Alarm Presignal Delay Time. 120 second Positive Alarm Sequence delay.
MODE
key, the code
and then the
7764
[ENTER/STORE]
key...
15
41
Document #50066 Rev. D2 12/03/02 P/N 50066:D2
69
Programming Reference Sheet
0
❐
Coding NAC #1. '0' for steady no coding.
72
0
❐
Notification Appliance Circuit #2 Selection. '0' for enabled (silenceable).
73
0
❐
Silence Inhibit NAC #2. '0' for no silence inhibit.
74
0
❐
Autosilence NAC #2. '0' for no autosilence.
75
0
❐
Coding NAC #2. '0' for steady no coding.
76
0
❐
Trouble Reminder. '0' for no trouble reminder.
77
0
❐
Annunciator/Printer Supervision. '0' for annunciator not present.
78
0
❐
Backup Reporting. '0' to report to secondary phone number as backup only.
79
0
❐
Touchtone/Rotary Select. '0' for touchtone dialing.
80
0
❐
Make/Break Ratio. '0' for 67/33 ratio.
81
70
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Programming Reference Sheets Factory Default
1112131415F1F
❐82❐83❐84❐85❐86❐87❐88❐89❐90❐91❐92❐93❐
2F3F4F597F6F1
❐95❐96❐97❐98❐99❐
F2F3F4F5F7F8F
❐
9 FAF BF CFCF DFE
❐
FCFFE1 E2E3 E4 E
❐
5E1E2E3E4E598
❐
E6E1 E2E3 E4 E5E
❐
7E8E9EAEBECEC
❐
108
121
134
147
160
173
❐
❐
❐
❐
❐
❐
109
122
135
148
161
174
❐
❐
❐
❐
❐
❐
110
123
136
149
162
175
❐
❐
❐
❐
❐
❐
111
124
137
150
163
176
❐
❐
❐
❐
❐
❐
112
125
138
151
164
177
❐
❐
❐
❐
❐
❐
100
113
126
139
152
165
178
❐
❐
❐
❐
❐
❐
❐
101
114
127
140
153
166
179
❐
❐
❐
❐
❐
❐
❐
102
115
128
141
154
167
180
❐
❐
❐
❐
❐
❐
❐
103
116
129
142
155
168
181
❐
❐
❐
❐
❐
❐
❐
104
117
130
143
156
169
182
❐
❐
❐
❐
❐
❐
❐
105
118
131
144
157
170
183
❐
❐
❐
❐
❐
❐
❐
106
119
132
145
158
171
184
❐
❐
❐
❐
❐
❐
❐
94
107
120
133
146
159
172
185
EDEEECEF99911
❐
112131415F1F2
❐
F3F4F597F6F1F
❐
2F3F4F5F7F8F9
❐
FAFBFCFCFDFEF
❐
CFFE1E2E3E4E5
❐
E1E2E3E4E598E
❐
6E1E2E3E4E5E7
❐
E8E9 EAEBECECE
❐
186
199
212
225
238
251
264
277
290
❐
❐
❐
❐
❐
❐
❐
❐
❐
187
200
213
226
239
252
265
278
291
❐
❐
❐
❐
❐
❐
❐
❐
❐
188
201
214
227
240
253
266
279
292
❐
❐
❐
❐
❐
❐
❐
❐
❐
189
202
215
228
241
254
267
280
293
❐
❐
❐
❐
❐
❐
❐
❐
❐
190
203
216
229
242
255
268
281
294
❐
❐
❐
❐
❐
❐
❐
❐
❐
191
204
217
230
243
256
269
282
295
❐
❐
❐
❐
❐
❐
❐
❐
❐
192
205
218
231
244
257
270
283
296
❐
❐
❐
❐
❐
❐
❐
❐
❐
193
206
219
232
245
258
271
284
297
❐
❐
❐
❐
❐
❐
❐
❐
❐
194
207
220
233
246
259
272
285
298
❐
❐
❐
❐
❐
❐
❐
❐
❐
195
208
221
234
247
260
273
286
299
❐
❐
❐
❐
❐
❐
❐
❐
❐
196
209
222
235
248
261
274
287
300
❐
❐
❐
❐
❐
❐
❐
❐
❐
197
210
223
236
249
262
275
288
301
❐
❐
❐
❐
❐
❐
❐
❐
❐
198
211
224
237
250
263
276
289
302
DEEECEF9991
❐
303
❐
304
❐
305
❐
306
❐
❐
307
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
308
❐
309
❐
310
❐
311
❐
312
❐
313
71
Wire Requirements
Appendix CWire Requirements
Connecting external system accessories to the MS-5024 main circuits must be carefully considered to ensure proper
operation. It is important to use the correct type of wire, wire gauge and wire run length per each MS-5024 circuit.
Reference the chart below to specify wire requirements and limitations for each MS-5024.
TABLE C-1:
Circuit TypeCircuit FunctionWire Type and Limitations
Fire Drill 52
fire panel 41
fire panel/communicator 11
format
communication 33, 37
formats
communication 14
function modes 73
H
history 58
history file 11
I
IDC 16, 23
see also Initiating Device Circuit 13
indicators 13
Initiating Device Circuit 16, 23
initiating device circuit 13
initiating zone 11
input
zones 23
input circuits 13, 23
installation 19
K
key functions 32
keys 46
Kissoff 48
C
cabinet 14
cabinet dimensions 20
CAC-5F 15, 30
see also Class A IDC converter module 12
Central Station Communications 52
central station phone 32, 36
circuit board 14
Class A converter modules 30
Class A IDC module 15
Class A NAC module 15
clock
real-time 44
coding
NAC 43
communication format 33, 37
communication formats 14
communicator 11
controls 13
current 11
D
description 11
dial tone 14
dialing 14
digital communicator 14, 17, 27
display 47
Down Arrow 47
E
ENTER/STORE 47
event codes
L
lamp test 60
LEDs 47
line seizure 14
local sounder 13
M
make/break ratio 44
Mode 47
mounting 19
N
NAC 16, 24
programming 43
see also Notification Appliance Circuit 11
see also notification appliance circuit 14
NACA-2F 15, 30
see also Class A NAC module 12
No Battery/Low Battery 52
nonresettable power 13, 17, 24
Notification Appliance Circuit 11, 16, 24
O
Off Normal Reporting 51
off/on hook 14
operating instructions 46
operation 49
operations modes 73
output circuits 13, 24
P
piezo
Document #50066 Rev.D2 12/03/02 P/N 50066:D275
see also local sounder 13
power
operating 22
power-limited wiring 26
presignal
alarm 43
Primary Line Active 48
program mode 31
programmer 11
programming 31
The manufacturer warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service. Products
are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer
is to repair or replace, at its option, free of charge for parts and labor, any part which is
defective in materials or workmanship under normal use and service. For products not under
the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of
original purchase by the manufacturer's distributor unless the installation instructions or catalog
sets forth a shorter period, in which case the shorter period shall apply. This warranty is void
if the product is altered, repaired, or serviced by anyone other than the manufacturer or its
authorized distributors, or if there is a failure to maintain the products and systems in which
they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our customer service department. Return product, transportation
prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its
products. The manufacturer does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they are
installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes
no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse,
abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER
NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S
PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR
AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the
manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.
LimWarLg.p65 01/10/2000