Fire-Lite Alarms MS5012 User Manual

PN: 15465:F1 ECN 02-606
Control Communicator
MS-5012
Document #15465 12/04/02 Rev.
F
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede­termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power.
cated, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibil­ity to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized pro­fessional fire alarm installers only. Adequate written records of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, ad­dition or deletion of system components, or after any modifica­tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for operation at 0-49° C/32-120° F condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi­nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LimWarLg.p65 01/10/2000
Notes
4
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Table of Contents
CHAPTER 1: Product Description .........................................................................................................................10
1.1: Product Features..........................................................................................................................................10
FIGURE 1-1: DP-5012 Cover..............................................................................................................11
1.2: Circuits ........................................................................................................................................................11
1.3: Front Panel Switches...................................................................................................................................11
1.4: Displays.......................................................................................................................................................12
1.5: Digital Communicator.................................................................................................................................12
1.6: ADM-12 Annunciator Driver Module - Optional .......................................................................................12
FIGURE 1-2: ADM-12/MS-5012........................................................................................................12
1.7: RZA-5F Remote Annunciator.....................................................................................................................13
FIGURE 1-3: RZA-5F Annunciator ....................................................................................................13
1.8: Specifications ..............................................................................................................................................13
CHAPTER 2: Control Panel Operation ..................................................................................................................16
FIGURE 2-1: Display and Keypad ......................................................................................................16
2.1: Switch Functions in Normal Mode .............................................................................................................16
2.2: Displays.......................................................................................................................................................17
FIGURE 2-2: Communicator Connections and LEDs.........................................................................18
2.3: Operation.....................................................................................................................................................18
2.4: Digital Communicator.................................................................................................................................21
TABLE 2-1: Format Selection Addresses (16 & 42)...........................................................................22
TABLE 2-2: Compatible UL Listed Receivers....................................................................................25
CHAPTER 3: Installation.........................................................................................................................................26
3.1: Cabinet Mounting Options ..........................................................................................................................26
FIGURE 3-1: Cabinet Dimensions and Knockout Locations ..............................................................26
3.2: Input Circuits...............................................................................................................................................27
FIGURE 3-2: Initiating Device Circuits - TB2....................................................................................27
3.3: Output Circuits ............................................................................................................................................28
FIGURE 3-3: Output Circuits - TB3....................................................................................................28
FIGURE 3-4: Driving Relays From Open Collector Outputs..............................................................28
3.4: UL Power-limited Wiring Requirements ....................................................................................................29
FIGURE 3-5: Typical Wiring Diagram for UL Power-limited Requirements ....................................29
TABLE 3-1: Output Normal Conditions .............................................................................................29
3.5: Digital Communicator.................................................................................................................................30
FIGURE 3-6: Wiring Phone Jacks.......................................................................................................30
3.6: Operating Power..........................................................................................................................................31
3.6.1: Primary Power Source (AC) and Earth Ground Connections...........................................................31
3.6.2: Secondary Power Source (batteries) .................................................................................................31
FIGURE 3-7: MS-5012 Power Connections .......................................................................................31
3.6.3: Optional AC Terminal Block ............................................................................................................32
FIGURE 3-8: Optional AC Terminal Block Installation .....................................................................32
3.7: Optional Boards...........................................................................................................................................33
3.7.1: ADM-12 Annunciator Driver Module ..............................................................................................33
FIGURE 3-9: ADM-12 Module...........................................................................................................33
3.7.2: RZA-5F Remote Annunciator...........................................................................................................33
FIGURE 3-10: RZA-5F Remote Annunciator.....................................................................................33
FIGURE 3-11: Mounting the RZA-5F to Single-Gang Electrical Box ...............................................33
FIGURE 3-12: Wiring the RZA-5F to the ADM-12 ...........................................................................34
CHAPTER 4: Programming Instructions...............................................................................................................35
4.1: Entering Program Mode ..............................................................................................................................35
FIGURE 4-1: First Address .................................................................................................................35
4.2: Switch Functions in Program Mode ...........................................................................................................36
Document 15465 Rev. F1 12/04/02 P/N: 15465:F1 5
Table of Contents
FIGURE 4-2: Switch Functions in Program Mode..............................................................................36
4.3: Programming ...............................................................................................................................................36
4.3.1: Programming the Primary Phone Number (00 - 15).........................................................................36
4.3.2: Programming Primary Number Communication Format (16) ..........................................................37
TABLE 4-1: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats ......................................37
4.3.3: Programming the Primary Number Account Code (17-20) ..............................................................38
TABLE 4-2: 4+2 Standard Formats.....................................................................................................39
4.3.4: Programming the Primary Number 24 Hour Test Time (21-24).......................................................40
4.3.5: Programming Primary Number 24/12 Hour Test Time (25).............................................................40
4.3.6: Programming the Secondary Phone Number (26-41) .......................................................................40
4.3.7: Programming Secondary Number Communication Format (42)......................................................41
TABLE 4-3: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats ......................................41
4.3.8: Programming the Secondary Number Account Code (43-46) ..........................................................42
TABLE 4-4: 4+2 Standard Formats.....................................................................................................43
4.3.9: Programming the Secondary Number 24 Hour Test Time (47-50)...................................................44
4.3.10: Programming Secondary Number 24/12 Hour Test Time (51).......................................................44
4.3.11: Programming Zone 3 Functionality (52).........................................................................................44
4.3.12: Programming Waterflow Retard Timer (53-54)..............................................................................44
4.3.13: Programming AC Loss Reporting Delay (55).................................................................................45
4.3.14: Programming Slave Communicator/Fire Panel Selection (56) .......................................................45
4.3.15: Secondary Phone Number Reporting (57) ......................................................................................45
4.3.16: Alarm Verification on Detector Zones 2 and 3 (58) ........................................................................45
4.3.17: Silence Inhibit (59)..........................................................................................................................45
4.3.18: Auto Silence (60) ............................................................................................................................45
4.3.19: Trouble Reminder (61)....................................................................................................................45
4.3.20: Bell Disable (62) .............................................................................................................................46
4.3.21: Annunciator Present (63) ................................................................................................................46
4.3.22: Programming Zone 4 Functionality (64).........................................................................................46
4.3.23: Address (65) - Not used ..................................................................................................................46
4.3.24: Touchtone/Rotary Select (66)..........................................................................................................46
4.3.25: Make/Break Ratio (67)....................................................................................................................46
4.3.26: Programming Event Codes (68-243)...............................................................................................46
4.3.27: End Programming ...........................................................................................................................46
4.3.28: Programming the Real-Time Clock ................................................................................................46
CHAPTER 5: Servicing............................................................................................................................................47
5.1: Walktest Mode.............................................................................................................................................47
5.2: History Mode...............................................................................................................................................48
5.3: Troubleshoot Mode......................................................................................................................................49
FIGURE 5-1: Handset Connection ......................................................................................................50
5.4: Lamp Test ....................................................................................................................................................50
CHAPTER 6: Slave Communicator Configuration ...............................................................................................51
Appendix A: Power Calculations .........................................................................................................................53
TABLE A-1: Total Ampere Hours .....................................................................................................53
TABLE A-2: Regulated Load in Standby ...........................................................................................54
TABLE A-3: Regulated Load in Alarm ..............................................................................................55
Appendix B: Programming Reference Sheets .....................................................................................................56
B.1: Blank System Programming Reference Sheets ........................................................................................56
B.2: Blank Format Programming Reference Sheet ...........................................................................................57
B.3: Programming Reference Sheet Factory Default Settings ..........................................................................58
B.4: Format Programming Reference Sheet Factory Default Sheet ..................................................................59
6
Document 15465 Rev. F1 12/04/02 P/N: 15465:F1
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code for Local, Remote Station Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
Intallation, Maintenance and Use of Central Station Fire Alarm Systems
Local Fire Alarm Systems
Use of Proprietary Fire Alarm Systems
Automatic Fire Detectors
Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems
Testing Procedures for Fire Alarm Systems.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
ADA American with Disabilities Act
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
7
8
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
The MS-5012 Panel
Primary & Secondary Phone Lines
Connector for Annunciator Driver Module
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
9
Product Description
CHAPTER 1 Product Description
The MS-5012 is a combination FACP (Fire Alarm Control Panel) and digital communicator, all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally open contact devices. Outputs include NACs (Notification Alarm Circuits), alarm relay, trouble relay, supervisory relay and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to a UL recognized Central Sta­tion via the public switched telephone network. The control panel has a built in programmer and may also serve as a slave communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and bat­tery level.
1.1 Product Features
• FACP (Fire Alarm Control Panel)
• Slave Fire Communicator
• 12 volt operation
• Real time clock
• Telephone line active indicators
• Trouble reminder
• One Style D (Class A) zone
• Four Style B (Class B) zones
• Programmable zone ID
• Alarm verification
• Optional annunciators
RZA-5F remote annunciator (requires ADM-12 Annunciator Driver Module)
LED type annunciators
• Small size [14.5" (36.83 cm) x 12.5" (31.75 cm) x 2.875" (7.303 cm)]
• Event history storage
• Silence inhibit
• Auto-silence
• Programmable event codes (all formats)
• Touchtone/rotary dialing
• Programmable make/break ratio
• Communication confirmation (kissoff) LED
• Fuseless
• AC loss report meets UL 864 requirements
• Number of dial attempts (5 minimum, 10 maximum)
• Programmable channel ID (slave)
• Programmable zone delay (waterflow only)
• Four open collector outputs
• Disable report by event
• Low AC voltage sense
• Walktest
10
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Circuits
• Built-in voltmeter
• Built-in programmer
• One NFPA Style Y NAC (Notification Appliance Circuit)
• Optional Dead Panel cover available
FIGURE 1-1:
1.2 Circuits
Input Circuits
Initiating Device Circuit #1 (Style B) Normally Open contact devices only
Initiating Device Circuit #2 (Style B) Normally Open contact devices and 2-wire smoke detectors
Initiating Device Circuit #3 (Style B/D) Normally Open contact devices, 2-wire smoke detectors (Style
B only), waterflow devices
Initiating Device Circuit #4 (Style B) Normally Open contact devices only
Initiating Device Circuit #5 (Style B) Normally Open contact devices only
Output Circuits
Notification Appliance Circuit
Resettable Power Circuit
Nonresettable Power Circuit
Relay Driver Output - Alarm
Relay Driver Output - Trouble
Relay Driver Output - Supervisory
Relay Driver Output - Communicator Failure
Primary Telephone Line
Secondary Telephone Line
12 Volt Battery Charger
DP-5012 Cover
1.3 Front Panel Switches
Reset Digits 0 - 9
Silence A
Mode B
Up Arrow C
Down Arrow D
1st Event E
Enter/Store F
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
u v w 123f q 456e r 789d s a0bc t
11
Displays
1.4 Displays
Alarm - red LED
Trouble - yellow LED
Supervisory - yellow LED
AC Power - green LED
Four 7-Segment Displays - red
Primary Phone Line Active - red LED
Secondary Phone Line Active - red LED
'Kissoff' signal from Central Station - green LED
Silence - yellow LED
1.5 Digital Communicator
The integral communicator provides the following functions:
Line Seizure - takes control of the phone lines disconnecting any premises phones
Off/On Hook - perform on and off-hook status to the phone lines
Listen for dial tone - 440 hertz tone typical in most networks
Dialing the Central Station(s) number - default is Touch-Tone®, programmable to rotary
Discern proper 'Ack' and 'Kiss-off' tone(s) - the frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly
Communicate in the following formats:
12 Tone Burst Types: 20 pps
(3+1, 4+1, 4+2, 3+1 Expanded, 4+1 Expanded, 4+2 Expanded)
1.6 ADM-12 Annunciator Driver Module - Optional
The ADM-12 Annunciator Driver Module permits connection of the RZA-5F Remote Annunciator module to the MS-5012 and supervises annunciator wiring for open conditions. The ADM-12 mounts to the MS-5012 main circuit board, occupying one of the two option connectors.
FIGURE 1-2:
12
ADM-12/MS-5012
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Connect ADM-12 to main circuit board connector J3. Use the supplied nylon spacer.
Make all connections with power off.
RZA-5F Remote Annunciator
1.7 RZA-5F Remote Annunciator
The RZA-5F Remote Annunciator mounts on a standard single­gang electrical box and provides LED indications for:
Alarm Zone 1 (red) Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
A local trouble sounder and tone silence switch are also provided. All LED wiring is supervised for open conditions. Any open will cause the System Trouble LED to turn on. Slide-in paper labels permit an easy change of zone information. The RZA-5F requires
the use of the ADM-12 Annunciator Driver Module.
1.8 Specifications
AC Power Primary - TB1 Terminals 1 & 2
120 VAC, 50,60 Hz, 0.32 amps
15.0 VAC, 50/60 Hz, 2.0 amps, 25 VA
Battery (sealed lead acid only) - Connector J1
Maximum Charging Capacity: 14.3 volts, 0.08 amps
Maximum Battery Capacity: 7 AH
FIGURE 1-3:
RZA-5F Annunciator
Initiating Device Circuits - TB2 Terminals 1-2, 9-10, 11-12
Normally Open Contact Zones 1, 4, 5
Power-limited Circuitry
Operation: NFPA Style B
Normal Operating Voltage: 13.8 VDC (ripple = 100 mV maximum)
Short Circuit Current: 4.46 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed)
Standby Current: 2.66 mA
Initiating Device Circuits - TB2 Terminals 3-4, 5-8
Detector Zones 2, 3
Power-limited Circuitry
Operation: Zone 2 (NFPA Style B), Zone 3 (NFPA Style B, D)
Connecting 2-wire detectors on Zone 3 requires NFPA Style B only
Normal Operating Voltage: 13.8 VDC (ripple = 100 mV maximum)
Alarm Current: 12 mA
Short Circuit Current: 24 mA maximum
Maximum Detector Current in Standby: 2 mA
Maximum Loop Resistance: 30 ohms
End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone
Standby Current: 5.17 mA (including ELR)
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
13
Specifications
Notification Appliance Circuit - TB3 Terminals 1 & 2
Power-limited Circuitry
Nominal Operating Voltage: 12 VDC
Requires minimum of 300 mA load
Total current available to external devices: 1 amp
End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed)
Auxiliary Outputs - TB3 Terminals 4-7
Power-limited Circuitry
Type: Open Collector
Rating: 40 mA each @ nominal 12 VDC
TB3 Terminal 4 Alarm Relay Driver - normally high, active low, sinks up to 40 mA
TB3 Terminal 5 Trouble Relay Driver - normally low, active high, sinks up to 40 mA
TB3 Terminal 6 Supervisory Relay Driver - normally high, active low, sinks up to 40 mA
TB3 Terminal 7 Communicator Failure - normally high, active low, sinks up to 40 mA
Four-wire Smoke Detector Power - TB2 Terminals 13 (+) and 14 (-)
Power-limited Circuitry
Up to 200 mA is available for powering 4-wire smoke detectors
Maximum ripple voltage: 100 mV maximum
Normal Operating Voltage: 13.8 VDC
Nonresettable Power - TB3 Terminal 3 (+) and TB2 Terminal 14 (-)
Power-limited Circuitry
Available Current: 185 mA
Maximum ripple voltage: 100 mV maximum
Normal Operating Voltage: 13.8 VDC
Telephone Circuitry:
Ringer Equivalence Number (REN) = 0.0B
AC Impedance 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most areas (but not all), the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maxi­mum REN for the calling area.
14
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Specifications
Digital Communicator:
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. The following information is provided if required by the local telephone company:
Piezo Sounder
An on-board piezo sounder will emit three distinctly different audible tones depending on system activity:
Steady on for alarms
One second on and one second off for trouble
½ second on and ½ second off for supervisory
NAC Fault
The NFPA Style Y circuit configuration allows for connection of polarized bells, strobes and horns. The wiring to these notification appliances is monitored for opens and shorts.
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
Product Model Number: MS-5012
FCC Registration Number: 1W6USA-74525-AL-E
Ringer Equivalence 0.0B
Note: The FCC ID label is located on the inside of the control panel door.
Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue service and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to tempo­rarily discontinue service. Advance notification will be provided except in cases when advance notice is not prac­tical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
15
Control Panel Operation
CHAPTER 2 Control Panel Operation
The MS-5012 has six modes of operation:
Normal Mode
Program Mode
Walktest Mode
Lamp Test Mode
Troubleshoot Mode
History Mode
Upon initial power-up, the system will be in Normal Mode. This section discusses operation of the control panel in the Normal Mode. Programming is discussed in Chapter 4. Walktest, History and Troubleshoot Modes are discussed in “Servicing” on page 47.
FIGURE 2-1:
Display and Keypad
2.1 Switch Functions in Normal Mode
u
The Reset Switch resets the system and any smoke detectors. Pressing the Reset Switch cause the control panel to:
Clear the display and status LEDs
Turn off the Notification Appliance Circuit
Reset all zones by temporarily removing power
Silence the on board piezo sounder
Store 'Reset' message in the History file (see “History Mode” on page 48)
Clear all relay driver outputs
Temporarily remove power from the resettable power output (TB1 Terminals 13 & 14)
Any alarm, supervisory or trouble condition that exists after a system reset, will resound the system, reactivating nor­mal system activity. Upon release of the Reset Switch, the display will
read for six seconds.
rES
v
If the Silence Switch is pressed:
The Notification Appliance Circuit will be turned OFF
The Silence LED will be turned ON
The piezo sounder will be turned OFF
'System Silenced' message will be stored in the History file
Upon the occurrence of a subsequent event (alarm or trouble), System Silence is overridden and the control panel will respond to the new event. The System Silence switch will be ignored for waterflow type alarms.
16
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Displays
r
w
Pressing the Mode Switch followed by a valid 4-digit numerical code selects one of the five modes of operation.
To enter Normal Mode from any other mode, press
followed by
t
.
6676
spells NORM on a Touch-Tone® phone.
w
then
6676
s
The 1st Event switch, along with the Up arrow and Down arrow switches, are used to display any currently active alarm and/or fault conditions present in the system. Press the 1st Event switch at any time to display the 1st event (alarm and/or trouble) that occurred.
Down arrow - use the Down arrow switch to view other events (older) that have occurred and are active (not yet cleared).
Up arrow - use the Up arrow switch to view other events (newer) that have occurred and are
q
active (not yet cleared).
t
The
switch is not used in Normal Mode.
t
2.2 Displays
Four 7-segment red LED characters provide visual annunciation of status, events and messages. The messages that may appear on the display in Normal Mode are listed below:
A 1 A 2 A 3 A 4 A 5 F 1 F 2 F 3 F 4 F 5 F A
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
Alarm Zone 5
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
F E Lo b no b PH 1 PH 2 bELL no 1 no 2 SUP4 AC rES
Earth Fault
Low Battery
No Battery
Primary Number Communication Fault
Secondary Number Communication Fault
Bell Fault
Primary Phone Line Fault
Secondary Phone Line Fault
Supervisory Alarm
AC Power Loss
Reset
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
17
Operation
Individual LEDs are provided for:
System Alarm - red LED that lights when an alarm condition is detected
System Trouble - yellow LED indicates that a fault or abnormal condition exists and that the fire alarm sys-
tem may be inoperative
AC Power ON - green LED that remains on while the AC power supply is operating. If this indicator fails to
light under normal conditions, service the system immediately
Supervisory - yellow LED that indicates need for action in connection with the supervision or maintenance of
sprinklers, extinguishing systems or other protective systems
System Silence - yellow LED that indicates an Alarm or Trouble has been silenced
Primary Line Active - red LED on the main circuit board that indicates the primary phone line is active
Secondary Line Active - red LED on the main circuit board that indicates the secondary phone line is active
Kiss-off - green LED on the main circuit board that indicates the Central Station has acknowledged receipt of
transmitted message
FIGURE 2-2:
Primary Active LED
Communicator Connections and LEDs
Primary Line Secondary Line
Secondary Active LED
Kiss-off LED
2.3 Operation
Normal Mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When no alarm or fault conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED). The Notification Appliance Circuit will be off, all relay drivers are deactivated and the on-board piezo sounder will be off. The communicator is not active, and the Primary and Secondary Active LEDs are off.
All alarm conditions and fault conditions are annunciated on the control panel's display. The control panel will main­tain an 'active event list' as illustrated in “Displays” on page 17. The list will consist of all alarms, supervisory alarms and faults currently active and not cleared, requiring immediate service. When the system is cleared and restored to normal, the display will be blank. All alarms and faults are stored in a history file and may be recalled at any time. Refer to “History Mode” on page 48.
18
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Operation
Higher priority events take precedence over lower priority events. Display of System Activity is accomplished on a priority basis. Priorities are, from highest to lowest:
Alarms
1.
Supervisory alarms
2.
Faults (troubles)
3.
The highest priority event will be communicated to the Central Station first. It also is displayed, overriding any other displayed event. Only one event is displayed at a time. Whenever multiple events occur, an authorized user may view each event by pressing the Up and Down arrow switches on the keypad. At any time, the user may press the 1st Event switch to display the first event that occurred (that is, the first event that occurred after the panel was last reset, cleared of all active events and placed into Normal Mode).
If the events to be displayed are alarms only (no troubles), the control panel will scroll them on the display. Pressing the 1st Event switch will stop the scrolling and cause the display of the first alarm that occurred. Operation of the Up and Down arrow switches will display all remaining alarms in sequence.
Alarm Response
The MS-5012 will, upon detection of an alarm condition, perform the following functions:
Turn the alarm LED on
Activate the alarm relay driver (TB3-4)
Display an alarm message as follows:
A 1 A 2 A 3 A 5
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 5
(Note that when Zone 4 is programmed as a supervisory zone, it will not be processed in the same manner as a conventional alarm one. See 'System Supervisory Condition' later in this section.)
Communicate the alarm to the Central Station
Store the alarm in the History file
Turn the Notification Appliance Circuit on
Turn the piezo sounder on
Alarm Restoral
The control panel returns to normal only after all alarms have been cleared (pull stations reset, smoke detectors reset and no smoke is present, waterflow has stopped) and the Reset switch has been pressed. The control panel will per­form the following upon restoral of all active alarms:
Turn off the alarm LED
Deactivate the alarm relay driver (TB3-4)
Clear the 4- character display
Send all 'Zone Restoral' messages to the Central Station
Turn off the Notification Appliance Circuit
Turn off the piezo sounder
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
19
Operation
System Supervisory Condition
Zone 4 is factory programmed as a supervisory zone. This zone is primarily used in applications where a waterflow sensing device has been employed and the wiring to the waterflow valve and/or a tamper switch is monitored. If the wiring is cut, a trouble condition will occur. If the Normally Open tamper switch is activated, a supervisory condition will occur.
When a supervisory condition occurs, the control panel will:
Turn on the supervisory LED
Activate the supervisory relay driver (TB3-6)
Display the following message -
SUP4
Communicate the supervisory condition to the Central Station
Store 'supervisory' message in the History file
Pulse the piezo sounder at ½ second On, ½ second Off rate
When the supervisory condition has been cleared (normal condition is restored and the Reset switch has been pressed), the MS-5012 will perform the following:
Turn off the supervisory LED
Deactivate the supervisory relay driver (TB3-6)
Clear the display of the message -
SUP4
Communicate the 'supervisory restoral' message to the Central Station
Shut off the piezo sounder
Trouble Conditions
The control panel will perform the following upon detection of a trouble condition:
Turn on the trouble LED
Activate the trouble relay driver (TB3-5)
Display the appropriate trouble message. Following are the trouble messages shown in order of prior-
ity, from the highest priority to the lowest:
AC F 1 F 3 F 2 F 5 F 4 F E L b no b no 1 no 2 bELL PH 1 PH 2 F A rES
AC Loss (must press Up arrow, Down arrow or 1st Event to view)
Trouble on Zone 1
Trouble on Zone 3
Trouble on Zone 2
Trouble on Zone 5
Trouble on Zone 4
Ground Fault
Low battery
No battery
Primary Phone Line Fault
Secondary Phone Line Fault
Bell Circuit (NAC) Fault
Primary Number Communication Fault
Secondary Number Communication Fault
Annunciator Fault
Reset
20
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Loading...
+ 44 hidden pages