While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power.
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.
Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
1.3: Front Panel Switches...................................................................................................................................11
1.5: Digital Communicator.................................................................................................................................12
2.4: Digital Communicator.................................................................................................................................21
TABLE 2-1: Format Selection Addresses (16 & 42)...........................................................................22
TABLE 2-2: Compatible UL Listed Receivers....................................................................................25
FIGURE 3-4: Driving Relays From Open Collector Outputs..............................................................28
3.4: UL Power-limited Wiring Requirements ....................................................................................................29
FIGURE 3-5: Typical Wiring Diagram for UL Power-limited Requirements ....................................29
TABLE 3-1: Output Normal Conditions .............................................................................................29
3.5: Digital Communicator.................................................................................................................................30
4.1: Entering Program Mode ..............................................................................................................................35
FIGURE 4-1: First Address .................................................................................................................35
4.2: Switch Functions in Program Mode ...........................................................................................................36
Document 15465 Rev. F1 12/04/02 P/N: 15465:F15
Table of Contents
FIGURE 4-2: Switch Functions in Program Mode..............................................................................36
4.3.18: Auto Silence (60) ............................................................................................................................45
4.3.20: Bell Disable (62) .............................................................................................................................46
5.2: History Mode...............................................................................................................................................48
5.4: Lamp Test ....................................................................................................................................................50
Appendix A: Power Calculations .........................................................................................................................53
TABLE A-1: Total Ampere Hours .....................................................................................................53
TABLE A-2: Regulated Load in Standby ...........................................................................................54
TABLE A-3: Regulated Load in Alarm ..............................................................................................55
The MS-5012 is a combination FACP (Fire Alarm Control Panel) and digital communicator, all on one circuit board.
It is a five-zone panel which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke
detectors, four-wire smoke detectors, pull stations and other normally open contact devices. Outputs include NACs
(Notification Alarm Circuits), alarm relay, trouble relay, supervisory relay and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to a UL recognized Central Station via the public switched telephone network. The control panel has a built in programmer and may also serve as a
slave communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery level.
✓Initiating Device Circuit #4 (Style B) Normally Open contact devices only
✓Initiating Device Circuit #5 (Style B) Normally Open contact devices only
Output Circuits
✓Notification Appliance Circuit
✓Resettable Power Circuit
✓Nonresettable Power Circuit
✓Relay Driver Output - Alarm
✓Relay Driver Output - Trouble
✓Relay Driver Output - Supervisory
✓Relay Driver Output - Communicator Failure
✓Primary Telephone Line
✓Secondary Telephone Line
✓12 Volt Battery Charger
DP-5012 Cover
1.3Front Panel Switches
ResetDigits 0 - 9
SilenceA
ModeB
Up ArrowC
Down ArrowD
1st EventE
Enter/StoreF
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
u v w
123f q
456e r
789d s
a0bc t
11
Displays
1.4Displays
✓
Alarm - red LED
✓
Trouble - yellow LED
✓
Supervisory - yellow LED
✓
AC Power - green LED
✓
Four 7-Segment Displays - red
✓
Primary Phone Line Active - red LED
✓
Secondary Phone Line Active - red LED
✓
'Kissoff' signal from Central Station - green LED
✓
Silence - yellow LED
1.5Digital Communicator
The integral communicator provides the following functions:
✓Line Seizure - takes control of the phone lines disconnecting any premises phones
✓Off/On Hook - perform on and off-hook status to the phone lines
✓Listen for dial tone - 440 hertz tone typical in most networks
✓
Dialing the Central Station(s) number - default is Touch-Tone®, programmable to rotary
✓
Discern proper 'Ack' and 'Kiss-off' tone(s) - the frequency and time duration of the tone(s) varies with
the transmission format. The control panel will adjust accordingly
The ADM-12 Annunciator Driver Module permits connection of the RZA-5F Remote Annunciator module to the
MS-5012 and supervises annunciator wiring for open conditions. The ADM-12 mounts to the MS-5012 main circuit
board, occupying one of the two option connectors.
FIGURE 1-2:
12
ADM-12/MS-5012
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Connect ADM-12 to main circuit
board connector J3. Use the
supplied nylon spacer.
Make all connections with
power off.
RZA-5F Remote Annunciator
1.7RZA-5F Remote Annunciator
The RZA-5F Remote Annunciator mounts on a standard singlegang electrical box and provides LED indications for:
✓Alarm Zone 1 (red)
✓Alarm Zone 2 (red)
✓
Alarm Zone 3 (red)
✓
Alarm Zone 4 (red)
✓Alarm Zone 5 (red)
✓
System Trouble (yellow)
A local trouble sounder and tone silence switch are also provided.
All LED wiring is supervised for open conditions. Any open will
cause the System Trouble LED to turn on. Slide-in paper labels
permit an easy change of zone information. The RZA-5F requires
Total current available to external devices: 1 amp
End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed)
Auxiliary Outputs - TB3 Terminals 4-7
Power-limited Circuitry
Type: Open Collector
Rating: 40 mA each @ nominal 12 VDC
TB3 Terminal 4 Alarm Relay Driver - normally high, active low, sinks up to 40 mA
TB3 Terminal 5 Trouble Relay Driver - normally low, active high, sinks up to 40 mA
TB3 Terminal 6 Supervisory Relay Driver - normally high, active low, sinks up to 40 mA
TB3 Terminal 7 Communicator Failure - normally high, active low, sinks up to 40 mA
Four-wire Smoke Detector Power - TB2 Terminals 13 (+) and 14 (-)
Power-limited Circuitry
Up to 200 mA is available for powering 4-wire smoke detectors
Maximum ripple voltage: 100 mV maximum
Normal Operating Voltage: 13.8 VDC
Nonresettable Power - TB3 Terminal 3 (+) and TB2 Terminal 14 (-)
Power-limited Circuitry
Available Current: 185 mA
Maximum ripple voltage: 100 mV maximum
Normal Operating Voltage: 13.8 VDC
Telephone Circuitry:
Ringer Equivalence Number (REN) = 0.0B
AC Impedance 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most areas
(but not all), the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may
be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
14
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Specifications
Digital Communicator:
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks
is necessary. The following information is provided if required by the local telephone company:
Piezo Sounder
An on-board piezo sounder will emit three distinctly different audible tones depending on system activity:
✓
Steady on for alarms
✓
One second on and one second off for trouble
✓
½ second on and ½ second off for supervisory
NAC Fault
The NFPA Style Y circuit configuration allows for connection of polarized bells, strobes and horns. The wiring to
these notification appliances is monitored for opens and shorts.
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
Product Model Number: MS-5012
FCC Registration Number: 1W6USA-74525-AL-E
Ringer Equivalence 0.0B
Note: The FCC ID label is located on the inside of the control panel door.
Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue service and/or make changes
in its facilities, services, equipment or procedures which may affect the operation of this control panel. However,
the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any
problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone
system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected
to the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68
compliant.
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
15
Control Panel Operation
CHAPTER 2Control Panel Operation
The MS-5012 has six modes of operation:
✓
Normal Mode
✓
Program Mode
✓
Walktest Mode
✓
Lamp Test Mode
✓
Troubleshoot Mode
✓
History Mode
Upon initial power-up, the system will be in Normal Mode.
This section discusses operation of the control panel in the
Normal Mode. Programming is discussed in Chapter 4.
Walktest, History and Troubleshoot Modes are discussed in
“Servicing” on page 47.
FIGURE 2-1:
Display and Keypad
2.1Switch Functions in Normal Mode
u
The Reset Switch resets the system and any smoke detectors. Pressing the Reset Switch cause the control panel to:
✓
Clear the display and status LEDs
✓
Turn off the Notification Appliance Circuit
✓
Reset all zones by temporarily removing power
✓
Silence the on board piezo sounder
✓
Store 'Reset' message in the History file (see “History Mode” on page 48)
✓
Clear all relay driver outputs
✓
Temporarily remove power from the resettable power output (TB1 Terminals 13 & 14)
Any alarm, supervisory or trouble condition that exists after a system reset, will resound the system, reactivating normal system activity. Upon release of the Reset Switch, the display will
read for six seconds.
rES
v
If the Silence Switch is pressed:
✓
The Notification Appliance Circuit will be turned OFF
✓
The Silence LED will be turned ON
✓
The piezo sounder will be turned OFF
✓
'System Silenced' message will be stored in the History file
Upon the occurrence of a subsequent event (alarm or trouble), System Silence is overridden and the control panel will
respond to the new event. The System Silence switch will be ignored for waterflow type alarms.
16
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Displays
r
w
Pressing the Mode Switch followed by a valid 4-digit numerical code selects one of the five modes of operation.
☛
To enter Normal Mode from any other mode, press
followed by
t
.
6676
spells NORM on a Touch-Tone® phone.
w
then
6676
s
The 1st Event switch, along with the Up arrow and Down arrow switches, are used to display any currently active
alarm and/or fault conditions present in the system. Press the 1st Event switch at any time to display the 1st event
(alarm and/or trouble) that occurred.
Down arrow - use the Down arrow switch to view other events (older) that have occurred and
are active (not yet cleared).
Up arrow - use the Up arrow switch to view other events (newer) that have occurred and are
q
active (not yet cleared).
t
The
switch is not used in Normal Mode.
t
2.2Displays
Four 7-segment red LED characters provide visual annunciation of status, events and messages. The messages that
may appear on the display in Normal Mode are listed below:
A 1
A 2
A 3
A 4
A 5
F 1
F 2
F 3
F 4
F 5
F A
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
Alarm Zone 5
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
F E
Lo b
no b
PH 1
PH 2
bELL
no 1
no 2
SUP4
AC
rES
Earth Fault
Low Battery
No Battery
Primary Number Communication Fault
Secondary Number Communication Fault
Bell Fault
Primary Phone Line Fault
Secondary Phone Line Fault
Supervisory Alarm
AC Power Loss
Reset
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
17
Operation
Individual LEDs are provided for:
• System Alarm - red LED that lights when an alarm condition is detected
• System Trouble - yellow LED indicates that a fault or abnormal condition exists and that the fire alarm sys-
tem may be inoperative
• AC Power ON - green LED that remains on while the AC power supply is operating. If this indicator fails to
light under normal conditions, service the system immediately
• Supervisory - yellow LED that indicates need for action in connection with the supervision or maintenance of
sprinklers, extinguishing systems or other protective systems
• System Silence - yellow LED that indicates an Alarm or Trouble has been silenced
• Primary Line Active - red LED on the main circuit board that indicates the primary phone line is active
• Secondary Line Active - red LED on the main circuit board that indicates the secondary phone line is active
• Kiss-off - green LED on the main circuit board that indicates the Central Station has acknowledged receipt of
transmitted message
FIGURE 2-2:
Primary Active LED
Communicator Connections and LEDs
Primary LineSecondary Line
Secondary Active LED
Kiss-off LED
2.3Operation
Normal Mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When
no alarm or fault conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED).
The Notification Appliance Circuit will be off, all relay drivers are deactivated and the on-board piezo sounder will
be off. The communicator is not active, and the Primary and Secondary Active LEDs are off.
All alarm conditions and fault conditions are annunciated on the control panel's display. The control panel will maintain an 'active event list' as illustrated in “Displays” on page 17. The list will consist of all alarms, supervisory alarms
and faults currently active and not cleared, requiring immediate service. When the system is cleared and restored to
normal, the display will be blank. All alarms and faults are stored in a history file and may be recalled at any time.
Refer to “History Mode” on page 48.
18
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Operation
Higher priority events take precedence over lower priority events. Display of System Activity is accomplished on a
priority basis. Priorities are, from highest to lowest:
Alarms
1.
Supervisory alarms
2.
Faults (troubles)
3.
The highest priority event will be communicated to the Central Station first. It also is displayed, overriding any other
displayed event. Only one event is displayed at a time. Whenever multiple events occur, an authorized user may
view each event by pressing the Up and Down arrow switches on the keypad. At any time, the user may press the 1st
Event switch to display the first event that occurred (that is, the first event that occurred after the panel was last reset,
cleared of all active events and placed into Normal Mode).
If the events to be displayed are alarms only (no troubles), the control panel will scroll them on the display. Pressing
the 1st Event switch will stop the scrolling and cause the display of the first alarm that occurred. Operation of the Up
and Down arrow switches will display all remaining alarms in sequence.
Alarm Response
The MS-5012 will, upon detection of an alarm condition, perform the following functions:
✓
Turn the alarm LED on
✓
Activate the alarm relay driver (TB3-4)
✓
Display an alarm message as follows:
A 1
A 2
A 3
A 5
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 5
(Note that when Zone 4 is programmed as a supervisory zone, it will not be processed in the same
manner as a conventional alarm one. See 'System Supervisory Condition' later in this section.)
✓Communicate the alarm to the Central Station
✓Store the alarm in the History file
✓Turn the Notification Appliance Circuit on
✓Turn the piezo sounder on
Alarm Restoral
The control panel returns to normal only after all alarms have been cleared (pull stations reset, smoke detectors reset
and no smoke is present, waterflow has stopped) and the Reset switch has been pressed. The control panel will perform the following upon restoral of all active alarms:
✓
Turn off the alarm LED
✓
Deactivate the alarm relay driver (TB3-4)
✓
Clear the 4- character display
✓
Send all 'Zone Restoral' messages to the Central Station
✓
Turn off the Notification Appliance Circuit
✓
Turn off the piezo sounder
Document #15465 Rev. F1 12/04/02 P/N 15465:F1
19
Operation
System Supervisory Condition
Zone 4 is factory programmed as a supervisory zone. This zone is primarily used in applications where a waterflow
sensing device has been employed and the wiring to the waterflow valve and/or a tamper switch is monitored. If the
wiring is cut, a trouble condition will occur. If the Normally Open tamper switch is activated, a supervisory condition
will occur.
When a supervisory condition occurs, the control panel will:
✓
Turn on the supervisory LED
✓
Activate the supervisory relay driver (TB3-6)
✓
Display the following message -
SUP4
✓Communicate the supervisory condition to the Central Station
✓Store 'supervisory' message in the History file
✓Pulse the piezo sounder at ½ second On, ½ second Off rate
When the supervisory condition has been cleared (normal condition is restored and the Reset switch has been
pressed), the MS-5012 will perform the following:
✓Turn off the supervisory LED
✓Deactivate the supervisory relay driver (TB3-6)
✓Clear the display of the message -
SUP4
✓Communicate the 'supervisory restoral' message to the Central Station
✓Shut off the piezo sounder
Trouble Conditions
The control panel will perform the following upon detection of a trouble condition:
✓Turn on the trouble LED
✓Activate the trouble relay driver (TB3-5)
✓Display the appropriate trouble message. Following are the trouble messages shown in order of prior-
ity, from the highest priority to the lowest:
AC
F 1
F 3
F 2
F 5
F 4
F E
L b
no b
no 1
no 2
bELL
PH 1
PH 2
F A
rES
AC Loss (must press Up arrow, Down arrow or 1st Event to view)
Trouble on Zone 1
Trouble on Zone 3
Trouble on Zone 2
Trouble on Zone 5
Trouble on Zone 4
Ground Fault
Low battery
No battery
Primary Phone Line Fault
Secondary Phone Line Fault
Bell Circuit (NAC) Fault
Primary Number Communication Fault
Secondary Number Communication Fault
Annunciator Fault
Reset
20
Document #15465 Rev.F1 12/04/02 P/N 15465:F1
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.