While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power.
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.
Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LimWarLg.p65 01/10/2000
NFPA Standards
This control panel complies with the following NFPA standards:
• NFPA 72 - Central Station Signaling Systems (Automatic, Manual, and Waterflow) - Protected
Premises Unit
Requires NOTI-FIRE 911AC DACT or 411UDAC Universal Digital Alarm Communicator
• NFPA 72 - Local Fire Alarm Systems (Automatic, Manual, Waterflow and Sprinkler Supervisory)
• NFPA 72 - Auxiliary Fire Alarm Systems (Automatic, Manual, and Waterflow)
Requires 4XTMF
• NFPA 72 - Remote Station Fire Alarm Systems (Automatic, Manual, and Waterflow)
Requires 4XTMF or NOTI•FIRE 911AC DACT or 411UDAC
• NFPA 72 - Proprietary Fire Alarm Systems (Automatic, Manual, and Waterflow)
Requires Potter EFT-C McCulloh Transmitter.
Note: Applications which require the NOTI-FIRE 911AC, or the Potter EFT-C are not FM approved.
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
• NFPA 72 - Installation, Maintenance, and Use of Central Station Signaling Systems
• NFPA 72 - Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems
• NFPA 72 - Automatic Fire Detectors
• NFPA 72 - Installation, Maintenance, and Use of Notification Appliances for Protective Signaling
Systems
• NFPA 72 - Testing Procedures for Signaling Systems
NFPA Standards
Underwriters Laboratories Documents
• UL 38 - Manually Actuated Signaling Boxes
• UL 217 - Smoke Detectors, Single and Multiple Station
• UL 228 - Door Closers - Holders for Fire Alarm Systems
• UL 268 - Smoke Detectors for Fire Alarm Systems
• UL 268A - Smoke Detectors for Duct Applications
• UL 346 - Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 - Audible Signaling Appliances
• UL 521 - Heat Detectors for Fire Protective Signaling Systems
• UL 864 - Standard for Control Units for Fire Alarm Systems
• UL 1481 - Power Supplies for Fire Protective Signaling Systems
• UL 1638 - Visual Signaling Appliances
• UL 1971 - Signaling Devices for the Hearing Impaired
• CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems
• CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm System
Other
• NEC Article 300 - Wiring Methods
• NEC Article 760 - Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
The Fire•Lite MS-4412B or MS-4424B Fire Alarm Control Panel have been designed as a control center
for use in automatic fire detection systems. The panels are designed for maximum reliability with 100%
solid state circuitry and isolated relay contacts for outside interfacing and features programmable options
to allow on-site customization of the unit for various operating configurations.
An integral standby battery system, with charger, is provided. In case of commercial AC power
interruption, automatic switchover to the battery system will provide power to the panel for a minimum
of 24 hours.
The FACPs are supplied complete with backbox, hinged door, control switches, and indicator LEDs.
The units are housed in a standard sheet-metal enclosure with 1/2 in. (12.7 mm) and 3/4 in. (19.05 mm)
conduit knockouts available.
The MS-4412B is a 110/120 VAC, 12 VDC fire alarm control panel. The MS-4424B is a 110/120 VAC,
24 VDC fire alarm control panel. The MS-4424BE is an export version that uses 220/240 VAC, 24 VDC.
• Microprocessor-controlled
• Power-limited on all circuits except Municipal Box
Output
• Alarm and trouble resound
• Four Style B Initiating Device Circuits
• Two Style Y Notification Appliance Circuits
• General alarm and trouble relays
•One Man Walk Test
• Disable/enable controls per Initiating Device Circuit
• Last Event Recall
• Battery /Earth fault supervision
• Current protection on all notification circuits
• Unregulated output power, 2.25 amps
• 7 amp-hour (AH) to 18 AH battery options, up to 60
hours standby
• Resettable and nonresettable regulated power
outputs
• Extensive transient protection
• Watchdog timer to supervise microprocessor
• Output circuits protected against false activations
• Slide-in zone identification labels
• Steel cabinet 14.5” (36.83cm) wide by 14.00”
(35.56cm) high by 2.88” (7.32cm) deep
Options
• 4XZMF/4412ZM Module for 4 zone relays
• 4XTMF/4412TM Transmitter Module - Complies
with NFPA 72 Auxiliary and Remote Station
Protective Signaling systems
The table below describes the DIP switch functions. For a more detailed explaination see "Setting Mode
of Operation" on page 27.
Options
#1Alarm
Verification
#2WaterflowON Zone 3 configured for Waterflow.
#3SupervisoryON Zone 4 configured for Supervisory.
#4Silence
Inhibit
#5Disable
NACs
#6Walk TestON Places the panel into Walk Test Mode.
Note: See “Setting Mode of Operation” on page 27 for a more detailed explanation of DIP switch functions.
ON Alarm Verification enabled (two-minute period).
OFF No verification employed.
OFF Zone 3 functions as a normal Initiating Device Circuit.
OFF Zone 4 functions as a normal Initiating Device Circuit.
ON Alarm Silence will not function for 60 seconds after initiation of an alarm.
OFF Alarm Silence is possible at any time after initiation of an alarm.
ON Two Notification Appliance Circuits and the Alarm Relay are disabled.
OFF Two Notification Appliance Circuits and the Alarm Relay are enabled.
OFF Normal Operating Mode.
Three optional modules are available for use on the control panel. The control panel provides mounting
slots for two of these optional module boards.
Transmitter Module - 4XTMF (12V: 4412TM)
The Transmitter Module provides a supervised output for a Local Energy
Municipal Box transmitter and alarm and trouble reverse polarity circuits for
Remote Station Service. Also included is a DISABLE switch and disable
trouble LED.
Note: As a jumper option, the alarm reverse polarity circuit will open on trouble if no
alarm exists.
Specifications for Local Energy Municipal Box service (NFPA 72 Auxiliary
Fire Alarm System)
Supervisory current: 5.0 mA.
Trip current: 0.35 amps (subtracted from Notification Appliance power).
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms.
Municipal Box wiring can leave the building.
TBL
J1
J2
TB1
4XTMF.cdr
10
Specifications for Remote Station Service (NFPA 72 Remote Station Fire Alarm System)
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 12 or 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.
The Remote Annunciator mounts on a standard single-gang box, an d provides
LED indication of the following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• System Trouble LED (yellow)
A local trouble sounder and silence switch are also provided. All LED wiring
is supervised for open conditions. Any open condition will cause the System
Trouble LED to illuminate. Slide-in paper labels permit an easy change of
zone information.
Note: The Remote Annunciator requires the use of an LED Interface Module as described below.
FIRE ALARM ANNUNCIATOR
LATCH
SYSTEM TROUBLE
RE-SOUND
TONE
SILENCE
TB1
DISABLE
4XZMF.cdr
RXA-4XF.cdr
LED Interface Module - 4XLMF (12V: 4412LM)
The LED Interface Module supports the RZA-4XF Remote Annunciator
Module. Annunciator wiring is supervised for open conditions by this module.
The module mounts to the main board on the J8 option connector.
Specifications
Maximum voltage/current, each output: 27.6 V / 8 mA.
Outputs are power-limited.
Maximum Charging Circuit: MS-4412B = 13.8V, 1.5 amps; MS-4424B(E) = 27.6V, 1.5 amps
Maximum Battery Capacity: 18 AH.
Note: Batteries larger than 12 AH require Fire•Lite BB-17F or other UL-listed external battery cabinet.
Initiating Device Circuits
Power-limited circuitry
Operation: Style B (Class B)
Normal Operating Voltage: MS-4424B(E)= 24 VDC (ripple = 1.0V p-p)
MS-4412B= 12 VDC (ripple = 1.0V p-p)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: MS-4412B=100 ohms; MS-4424B(E)= 200 ohms
End-of-Line Resistor: MS-4412B= 2.2K, 1/2-watt (part # R2.2K UL listed)
MS-4424B(E)= 4.7K, 1/2-Watt (part # 71252 UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including End-of-Line Resistor)
Notification Appliance Circuits
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: MS-4412B= 12 VDC; MS-4424B(E)= 24 VDC
Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps
End-of-Line Resistor: MS-4412B= 2.2K, 1/2-watt (part # R2.2K UL listed)
MS-4424B(E)= 4.7K, 1/2-Watt (part # 71252 UL listed)
Note: Any power connected to these relay contacts must come from a power-limited supply. Fail-safe operation
ensures trouble relay functioning under loss of both primary power (AC) and secondary (battery power).
Resettable Power
Up to 200 mA is available for powering four-wire smoke detectors. Maximum ripple voltage: 1.0 V p-p.
Nonresettable Power
Total DC current available from this output is up to 200 mA (subtracted from four-wire smoke detector
power). Maximum ripple voltage: 1.0 V p-p.
RMS Rregulated Power
12
Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available
to Notification Appliance Circuits). Maximum ripple voltage: 100 mV p-p.
Carefully unpack the system and check for shipping damage.
Select a suitable location in a clean, dry, vibration-free environment that is not subject to extreme
temperatures. Locate the top of the cabinet approximately five feet above the floor with the hinge on the
left. The panel must be easily accessible for maintenance; the hinged door requires a minimum clearance
of 14 in. (35.56cm) to open.
Removal of Circuit Board
To prevent damage to the printed circuit board it should be removed prior to mounting of cabinet.
StepAction
1
Disconnect the transformer wires from the circuit board at the J1
connector.
2
Remove the four (4) phillips head screws securing circuit board to
backbox.
3
Carefully set board aside in a secure place.
2. Installation
Mounting of Cabinet
Securely mount the cabinet using the mounting holes provided.
StepAction
1Mark and predrill holes for the top two keyhole mounting screws using the
dimensions shown in Figure 2 on page 14.
2Install two upper screws in the wall with the heads protruding.
3Using the upper keyholes, mount the backbox over the two screws.
4Mark and drill the lower two holes.
5Secure backbox by installing the remaining fasteners and tightening all
screws.
6
If required, attach optional Trim Ring (TR-2-F) using the provided
instructions.
Attaching Conduit
Select and remove knockouts according to the number of conduits required.
Attach conduits to backbox as required.
Determine the number of conductors required for the devices to be employed. Pull required conductors
into the box through the knockouts provided.
Note: All wiring should be in accordance with the National and/or Local codes for fire alarm systems, including
"Power-limited Wiring Requirements" on page 16.
WARNING: Do not apply any type power to this control panel until all connections have been
!
made and verified.
AC Connections
Disconnect (open) the circuit breaker in the AC main breaker panel and tag it “Out of Service”.
Note: Refer to "Power-Up Procedure" on page 28 before closing AC breaker.
Primary power required for the MS-4412B and MS-4424B control panel is 110/120 VAC, 50/60 Hz, 1.2
amps and for the MS-4424BE is 220/240 VAC, 50/60 Hz, 0.6 amps.
Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC)
and/or local codes. Use #14 AWG (2.00 mm
A separately fused and protected power connection to the panel should be supplied to prevent voltage
fluctuation and interruption of power.
Ground
2
) or larger wire with 600V insulation rating.
Neutral
Hot
TB1
J9
MS44B-ACconn.cdr
Figure 3 AC Power Connections
Battery (DC) Connections
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
!
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
water for 15 minutes and seek immediate medical attention.
CAUTION: Do NOT connect the battery interconnect wire, or one battery lead in the case of the MS-
!
4412, at this time. Make this connection AFTER initial system primary power connection.
Place batteries into bottom of cabinet as shown below. See "Appendix A: Secondary Power Calculations"
on page 35 for calculation of correct battery rating.
Note: Batteries are shipped separately and should be mounted only after the cabinet has been installed, the conduit
connected, and all wiring pulled, tested, and made ready to be terminated.
Connect the battery cable (p/n 75202) to terminal J9 on the main circuit board using the plug-in connector
provided. Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing
batteries. Do NOT connect battery interconnect wire at this time.
12 Volt Connections
Connect the battery cable (p/n 75202) to terminal J9 on the main circuit board using the plug-in connector
provided. The short cable (battery interconnect) may be removed from bundle. Do NOT connect cables
to battery at this time.
12 Volt
Connections
TB1
J9
TB1
24 Volt
Connections
J9
Figure 4 Battery Installation and Connection
Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All powerlimited circuit wiring must remain at least 0.25 in (6.35 mm) away from any nonpower-limited circuit
wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must pass
through separate knockouts and/or conduits.
A maximum of 200mA is available from the 12 or 24VDC Resettable Power circuit on TB2 (VR terminals).
Any power that is drawn from the 12 or 24VDC N onresettable Power circuit on TB2 (VNR terminals) must
be subtracted from available resettable power. See "Specifications" on page 12 and "Powering External
Devices" on page 21.
Note: Refer to the Device Compatibility Document for suitable 4-wire smoke detectors.
Notes on Style B (Class B) field wiring:
1.The Power Supervision Relay coil leads must be connected to the last detector base 12 or 24VDC
screw terminals.
2.Calculation of the maximum allowable resistance in the 12 or 24VDC resettable power wiring:
Rmax =
(XX.x - Vom)
(N x Is) + (Na x Ia) + (Ir)
Where:
XX.x = 10.4 for 12VDC; 20.6 for 24VDC
Rmax = maximum resistance of the 12 or 24VDC wires
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N = total number of detectors on the 12 or 24VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 12 or 24VDC power circuit which must function at the same time in alarm
Ia = detector current in alarm
Ir = end-of-line relay current
4.7K, 1/2-Watt ELR
–
+
–
+
TB2
Control Panel
Power Circuit
TB4
IN #4
IN #3
IN #2
B+ B–
Class B
Initiating Device Circuit
B+ B–
B+ B–
Power
Supervision
Relay
(A77-716B)
–
+
–
+
12 or 24VDC Four-wire
Smoke Detectors
MS44B-4wiresd.cdr
18
Figure 7 Typical Connection for Four-Wire Smoke Detectors
The control panel provides two Notification Appliance Circuits (Style Y). Each circuit is capable of 1.5
amps of current. Total current drawn from all four circuits cannot exceed 2.25 amps. NACs are supervised
and power-limited.
Note: Refer to the Device Compatibility Document for suitable devices.
For details on how jumper configurations affect panel functions see "Supervisory Configuration" on page
20.
• For DIP switch configuration, see "Setting Mode of Operation" on page 27.
• For non-silenceable service on Initiating Zone #1, see "Non-Silenceable Service" on page 32.
• Unused circuits must be connected with a dummy load as shown.
If DIP switch #3 - “Supervisory on Zone 4” is selected (see "Setting Mode of Operation" on page 27) IDC
#4 will act as a supervisory circuit. Jumpers SUPV1 and SUPV2 control how the NACs respond.
1.No jumper is cut -
Both NACs activate for supervisory conditions on IDC #4.
2.SUPV1 jumper is cut -
NAC #1 activates with an alarm on IDC #1, IDC #2, or IDC #3.
NAC #2 activates with a supervisory condition on IDC #4 only.
3.SUPV2 jumper is cut -
NAC #1 and NAC #2 will not activate for supervisory conditions; panel piezo will sound.
Note: Do NOT cut both SUPV1 and SUPV2 jumpers.
Optional modules react to supervisory conditions as follows:
If a 4XZMF (4412ZM) Zone Relay Module is used, Relay 4 will activate for supervisory conditions.
If an RZA-4XF Remote Annunciator is used, the fourth LED (red) will annunciate supervisory
conditions.
To locate jumpers on the board, see Figure 1 on page 9.
SUPV 1
Figure 9 SUPV Jumper
SUPV 2
MS44B-jumper.cdr
Alarm Relay
One Form-C dry contact alarm relay is provided in the basic panel for controlling supplementary devices.
Contacts are rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and are non-silenceable when
an alarm occurs.
Trouble Relay
One Form-C dry contact trouble relay is provided in the basic panel for controlling supplementary devices.
It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and will restore to normal when the trouble
condition is cleared.
Note: Power connected to these relay contacts must come from a power-limited supply. Power may be obtained from
TB2 Terminals VU, VR or VNR, or a UL-listed power-limited power supply.
TB4
20
MS44B-relay.cdr
Figure 10 Schematic Representation of Alarm/Trouble Coils & Contacts
The control panel has two module connectors - J5 (upper position) and J8 (lower position). Three modules
are available for the panel and they can be used in any combination, including duplicate modules. The
corresponding option jumper must be cut before installation of an optional module, to enable module
supervision.
• The 4XTMF (4412TM) Transmitter and 4XZMF (4412ZM) Zone Relay Modules can be installed
in either position.
• The 4XLMF
Installation - Upper Position
To install either the 4XTMF (4412TM) or 4XZMF (4412ZM) module in the upper position follow these
instructions:
(4412LM) Interface Module must be installed in the lower position only.
StepAction
1Cut jumper ‘OPT1’ on main circuit board.
2Insert the two stand-offs into the holes located on the right-side edge of the
main board. Secure with nuts and tighten securely.
3Align the pins of J5 (and J4) connectors on the main board with the holes on
the underside of the J2 (and J1) connector on the optional board. Carefully
press down on the optional board until the pins are through the connectors
and it rests on the stand-offs.
4Secure optional board to stand-offs with screws. Tighten securely.
5Affix the terminal identification label (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module.
To install either the 4XTMF (4412TM), 4XZMF (4412ZM) or 4XLM (4412LM) module in the lower
position follow these instructions:
StepAction
1Cut jumper ‘OPT2’ on main circuit board.
2Remove the lower-right screw securing the main board to the backbox.
Replace with a stand-off and tighten securely.
3Insert one stand-off into the other hole located on the right-side edge of the
main board. Secure with nut and tighten securely.
4
Align the pins of J8 (and J7) connectors on the main board with the
holes on the underside of the J2 (and J1) connector on the optional
board. Carefully press down on the optional board until the pins are
through the connectors and it rests on the stand-offs.
5
Secure optional board to stand-offs with screws. Tighten securely.
6Affix the terminal identification label (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module.
Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module
as shown below. Polarities shown in activated positions.
Note: Dummy load terminals 6 and 7 (4.7K [2.2K for 12V], 1/4 W resistor) if Municipal Box is not connected.
Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.
Pushing the Disconnect Switch down will prevent unwanted acti vation of the Municipal Box during testing
of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the
Municipal Box.
Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring
Requirements" on page 16.
Relay #1 through #4 will activate with Input #1 through #4 and remain latched unless jumper “LATCH”
is cut. For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact,
the relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right.
Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label,
located on the door of the control panel.
TB1
J2
LATCH
DISABLE
4XZMF.cdr
Disable Switch“Latch” Jumper
Figure 15 Wiring the Zone Relay Module
The wiring of this module must follow the requirements specified under "Power-limited Wiring
Requirements" on page 16.
• If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of
dry contacts to maintain the required separation between circuit types.
• If this module is used to drive both nonpower-limited and power-limited relays that are next to each other, refer to the figure below which shows the one allowable arrangement.
Power-Limited
Circuit
Figure 16 Mixing Power-Limited and Nonpower-Limited Circuits
Select operating mode by setting the SW1 DIP switches as described below; basic programming options
are shown in this section.
After any changes are made to the configuration of the switches, the panel must be reset.
For Canadian use, refer to "Sprinkler Supervisory Tracking" on page 32.
SW1
MS44-dipsw.cdr
Switch 1: Alarm Verification
Switch 2: Waterflow on Zone 3
Switch 3: Supervisory on Zone 4
Switch 4: Silence Inhibit
Switch 5: Disable NACs
Switch 6: Walk Test
Figure 18 DIP Switch Settings
DIP Switch Functions
Switch 1: Alarm Verification - If selected (‘ON’), alarm signals that occur on any zone will be
subjected to a two-minute verification period to determine if the alarm is true. Note that the control panel
will distinguish if the alarm signal came from a shorting-type contact device (manual pull station, fourwire detector, or heat detector) or a two-wire smoke detector, and will not employ verification of alarm
signals from the contact devices.
Switch 2: Waterflow on Zone 3 - If set for Waterflow (‘ON’), Initiating Device Circuit #3 will
function as a waterflow circuit. If an alarm occurs on this zone, the ALARM SILENCE switch will not
silence any activated output circuits.
Switch 3: Supervisory on Zone 4 - If set for Supervisory (‘ON’), Initiating Device Circuit #4 will
function as a supervisory circuit. Activation of a tamper or other supervisory switch on this circuit will
result in a supervisory condition, but not an alarm condition, at the panel. All NACs will activate unless
SUPV1 or SUPV2 jumpers are cut (see "Supervisory Configuration" on page 20). The piezo will sound
a distinct pulsing tone and the yellow LED on zone 4 will flash along with the supervisory LED.
Switch 4: Silence Inhibit - If selected (‘ON’) and an alarm occurs, the ALARM SILENCE switch will
not function until 60 seconds have passed since initiation of the alarm. If another alarm occurs, the timer
will restart at 60 seconds.
Switch 5: Disable NACs - When this switch is set ‘ON’, the four Notification Appliance Circuits and
the System Alarm Relay will be disabled, and a local trouble signal will be generated.
Switch 6: Walk Test - Setting this switch to the ‘ON’ position places the control panel in Walk Test
Mode. The first alarm on the Initiating Circuit under test will ring associated Notification Appliance
Circuit(s) for 5 seconds. Zone Alarm LED will flash. The second alarm on Initiating Circuit under test
will ring associated Notification Circuit(s) for 1 second. Zone Alarm LED will illuminate steadily. A
Trouble condition on the Initiating Circuit under test will sound the control’s piezo and light the Zone
Trouble LED.
WARNING: Prior to energizing this panel, notify all personnel and authorities, including any
personnel who may be working on, around, or near this unit.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
!
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
water for 15 minutes and seek immediate medical attention.
CAUTION: Observe polarity of batteries. Improper connection will cause damage and VOID
WARRANTY.
!
Follow these steps to power-up the FACP:
1.Conduct Visual Inspection. A careful visual inspection should be made before applying power to
the system. See “Inspection” on page 43.
2.Notification. Notify personnel who may be working with the AC power circuits before removing
the “Out of Service” tag.
3.Apply Primary Power. Switch the circuit breaker to the ‘closed’ position, providing power to the
circuit.
• The green AC power LED will illuminate.
• The Trouble LED will illuminate until battery power is applied.
4.Connect Secondary Power. Connect battery interconnect wire (24 Volt), or battery cables
(12 Volt) as shown below.
• The trouble LED will clear. If the trouble light does not clear, refer to Table 3, “Troubleshooting
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged
(TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
3. System Operation
System
Status
LEDs
AC POWER
SYSTEM
ALARM TEST
SUPERVISORY
SYSTEM
TROUBLE
CIRCUIT
TROUBLE
SILENCED
TROUBLE
TONE
SILENCE
BATT EARTH
ALARM
ALARM
POWER
ALARM
SILENCE
ALARM
ACTIVATE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
SYSTEM
RESET
MS44-panel1.cdr
MICRO
FAIL
Figure 20 System Status LEDs
AC Power - Green LED that illuminates steadily to indicate presence of AC power.
System Alarm - Red LED that flashes when an alarm occurs.
Alarm Test - Red LED that illuminates during Walk Test.
Supervisory - Yellow LED that flashes upon activation of a supervisory device (such as tamper switch)
on Zone 4.
System Trouble - Yellow LED that flashes for any trouble condition, including those associated with
optional boards.
Circuit Trouble - Yellow LED that flashes for trouble conditions on output circuits.
Alarm Silenced - Yellow LED that illuminates steadily when the ALARM SILENCE switch has been
pushed after an alarm.
Power Trouble - Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
The following LEDs are located below the main panel and are visible only when the panel door is open.
Battery Fail (
BATT) - Yellow LED that illuminates steadily on motherboard when battery is low or not
detected.
Ground Fault (
EARTH) - Yellow LED that illuminates steadily on motherboard during a ground fault
condition.
Micro Fail - Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor
failure.
Tone Silence - Pressing this switch acknowledges alarms, troubles and supervisories. The panel has
alarm and trouble resound with LED flash of new conditions. The flashing trouble LED(s) illuminate
steadily and the piezo turns off. A second trouble will resound the piezo. Trouble conditions are selfrestoring. Alarms latch and require pressing SYSTEM RESET to clear. Unless the unit is set for nonlatching supervisory service, supervisories latch and require pressing SYSTEM RESET to clear. The piezo
has three tones for different conditions (see "Piezo" on page 31).
Alarm Silence - Pressing this switch acknowledges for alarms and supervisories. This switch will
silence the local piezo, change any flashing alarm LEDs to steady, and turn off the notification circuits.
The “Alarm Silenced” LED will illuminate. Alarm silence is a latching function and requires pressing
SYSTEM RESET to clear.
Note: If Silence Inhibit has been selected (SW1, DIP switch #4 set to “ON”), the Alarm Silence will not function until 60
seconds after the initiation of the alarm.
Alarm Activate - This switch may be used to activate Notification Appliance Circuits (NACs). It also
activates the System Alarm Relay. This is a latching function. Pressing ALARM SILENCE silences the
NACs and System Alarm Relay, and lights the Alarm Silenced LED. Pressing SYSTEM RESET returns
the system to normal.
System Reset - This switch breaks power to all initiating circuits, four-wire smoke detector power and
optional boards and will clear any activated output circuits. If any alarm or trouble still exists after reset,
they will reactivate the panel. Holding SYSTEM RESET down will perform a LAMP TEST function and
will activate the piezo sounder.
Zone Status LEDs
The alarm and/or trouble LED(s) will flash until the event(s) has been acknowledged (TONE or ALARM
SILENCE), at which point the LED(s) will illuminate steadily.
The piezo (local buzzer) generates different tone patterns for different event conditions:
• Alarm - Generates a steady tone, no pulse.
• Trouble - Pulses one second on, one second off. Repeats 30 pulses per minute.
• Supervisory - Pulses one-half second on, one-half second off. Repeats 60 pulses per minute.
Supervisory Service
Zone 4 is programmable for monitoring supervisory devices (such as valve tamper switches) by setting
SW1 DIP switch 3 to “ON” (see "Setting Mode of Operation" on page 27). A short circuit on this zone
(activation of a N.O. contact) will cause the supervisory LED and the zone 4 yellow LED to flash. The
piezo sounder will generate a unique sound. Pressing TONE SILENCE will silence the piezo and cause
the supervisory LED to illuminate steadily, but the Zone 4 Trouble LED will continue to flash. Supervisory
signals latch and require SYSTEM RESET to clear. The ALARM SILENCE switch will silence the piezo,
cause the supervisory LED to illuminate steadily and turn off the Supervisory Notification Circuit. An
open circuit on Zone 4 will be reported as a zone trouble.
Note: The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation; latching
operation is the default setting. Canadian regulations require latching operation; for programming instructions, See
“Sprinkler Supervisory Tracking” on page 32.
Zone Disable
If a zone has been disabled, an alarm that occurs on that zone will flash the red zone LED, but not the piezo
or any output circuit. If both power sources are removed from the system, all zones will be re-enabled upon
restoration of power. Disable status will be lost.
The Zone Disable routine makes use of the four panel
switches as follows:
1.Press and hold in the TONE SILENCE switch.
2.With the TONE SILENCE switch held in, press
3.The Zone 1 Alarm LED will flash.
4.To disable Zone 1, press the SYSTEM RESET switch. The Zone 1 yellow LED will light to show
Note: The SYSTEM RESET switch toggles disable status for the selected zone.
5.To select the next zone, press the ALARM SILENCE switch.
6.To select the previous zone, press the ALARM ACTIVATE switch.
7.When disable selections are complete, release the TONE SILENCE switch.
If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash.
(in sequence) the ALARM SILENCE switch, the
ALARM ACTIVATE switch, and then the
SYSTEM RESET switch.
Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes use
of the four panel switches as follows:
1.Press and hold in the TONE SILENCE switch.
2.With the TONE SILENCE switch held in, press (in sequence) the SYSTEM RESET switch, the
ALARM ACTIVATE switch, and then the ALARM SILENCE switch.
3.LEDs will light to indicate the last event recorded in the panel’s buffer.
4.Release the TONE SILENCE switch to return to normal operation.
To clear the Last Event buffer, press SYSTEM RESET twice.
Non-Silenceable Service
Initiating Zone #1 can be programmed as non-silenceable by following these steps:
1.Press and hold in the TONE SILENCE switch.
2.With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then
the ALARM ACTIVATE switch, and finally the ALARM SILENCE switch again.
3.Release the TONE SILENCE switch.
Note: If both primary and secondary power sources are removed from the system, these settings will be lost. When
power is restored, Initiating Zone #1 will default to silenceable operation.
Sprinkler Supervisory Tracking
The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation;
latching operation is the default setting. Canadian regulations require latching operation.
1.Press and hold in the TONE SILENCE switch.
2.With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then
the ALARM ACTIVATE switch, and finally the ALARM ACTIVATE switch again.
3.Release the TONE SILENCE switch.
Note: If both primary and secondary power sources are removed from the system, this setting will be lost. When
power is restored, supervisory will default to latching operation.
System Events
Standby Condition
Green LED (AC power on) will be illuminated. All other LEDs (trouble and alarm) are off.
System Trouble Condition
Interruption of any of the electrically supervised circuits will illuminate the System Trouble LED. The
Trouble RElay Contacts will transfer. The piezo (local buzzer) will sound one second on, one second off,
and repeating until silenced. Silence the piezo by pressing the TONE SILENCE switch. The panel will
remain in the trouble state until the trouble condition has been cleared and the panel reset.
32
Alarm Condition
Upon activation of an initiating device, a red alarm LED will illuminate for that zone. In add ition, the Alarm
Relay will activate, the piezo will sound, and Notification Appliance Circuit(s) will activate. (See “Output
Circuits” on page 19 for details).
The total power being provided to the system’s power supply should not exceed the current draw during
fully loaded panel operation. Brownout circuitry annunciates degradation of the incoming AC voltage
supply. A brownout condition is annunciated when the AC power decreases. When the brownout threshold
is reached, the system reacts as if AC power is totally lost:
• Battery backup begins supplying power to operate the control panel
• General Trouble Relay contact transfers
• Green AC Power LED turns off
• Yellow System Trouble LED illuminates
• The piezo will sound one second on, one second off, and repeat until the Trouble is cleared.
When the AC voltage returns or increases above the brownout threshold, the green AC Power LED will
illuminate. The power supply circuitry will return to primary power functions and begin to recharge the
backup battery supply.
The Standby Battery Current obtained in the table below represents the amount of current that must be
supplied by the secondary power source (batteries) to sustain control panel operation for one hour.
Note: The control panel will support the installation of one or two optional modules, including two of the same type of
module. Only one 4XLMF (4412LM) can be included in this count.
Device Type
Main Circuit Board1X0.088=
4XZMF/4412ZM
ZoneRelay Module
4XTMF/4412TM
Transmitter
•Reverse Polarity
Alarm output
•Reverse Polarity
Trouble output
RZA-4XF/4XLMF
(4412LM)
Remote Annunciator
4XMMF
Meter Module
2-wire
Detector Heads
4-wire
Detector Heads
End-of-line Relays
Module
2
# of
Devices
[ ]X0.008=
[ ]X0.011=
[ ]X0.005=
[ ]X0.005=
[ ]
(1 max)
[ ]X0.001=
[ ]X
[ ]X
[ ]X[ ]=
Current
(amps)
X0.019=
1
[ ]
1
[ ]
Total Current
(amps)
0.088
=
=
Current Draw from
TB2 (nonalarm)
1. Refer to the Device Compatibility Document for smoke detector standby current.
2. Must use compatible listed Power Supervision Relay.
3. The total standby current must include both the resettable (TB2 - VR terminals) and
nonresettable (TB2 - VNR terminals) power. Caution must be taken to ensure that current drawn
from these outputs during alarm does not exceed maximum ratings specified.
Appendix A: Secondary Power CalculationsCalculating the Battery Capacity
Calculating the Battery Capacity
Use this table to determine the battery capacity required by the system.
Standby Battery Current
(from Table 1)
[ ] ampsX
Required Standby Time in Hours
(typically 24
[ ] hrs
Enter:
0.25 for 5 minutes in alarm, or
0.50 for 10 minutes in alarm
1
or 602 hours)
Standby
=
Amp Hours
3
Alarm
Amp Hours
Total Standby and Alarm Load+
Multiply by derating factorX1.2
Battery size required in AH=
1. NFPA 72 Central Station and Local and Proprietary Fire Alarm Systems require 24 hours of standby time.
2. NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby time.
3. Alarm AH assumes a maximum system draw of 3.0 amps in alarm for 5 minutes (0.25 AH) or for
10 minutes (0.50 AH).
Table 2 Amp Hour Calculations
The battery charger in this panel will charge a maximum of 18 AH of batteries within 48 hours (7 AH
minimum). Batteries larger than 12 AH will require a UL-listed battery cabinet (e.g. Fire•Lite BB-17F).
Select a battery with an equal or greater AH rating than the value obtained in the table above.
The control panel has been designed for use in commercial, industrial, and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA) Standards
outlined in this appendix. The minimum system components required for compliance with the appropriate
NFPA standard are listed below.
• Fire Alarm Control Panel. Contains the main control board, cabinet (backbox and door), main
supply transformer and power supply.
• Batteries. Refer to "Appendix A: Secondary Power Calculations" on page 35.
• Initiating Devices. Connected to one of the control panel's Initiating Device Circuits.
• Notification Appliances. Connected to one of the control panel's Notification Appliance Circuits.
Additional Requirements
The following additional equipment is needed for compliance with the NFPA standards listed below. The
relay contacts of this control panel may be used to trip any dialer that is UL listed for Central St ation/Remote
Station services. The illustrations in this appendix provide examples of possible system configurations.
Note: Applications which require the the NOTI-FIRE 911AC or the Potter EFT-C are not FM approved.
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)
• NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter connected to a compatible
listed Central Station DACR or Protected Premises Receiving Unit. See "Digital Alarm
Communicator/Transmitter - Noti-Fire 911AC" on page 38 for installation instructions for this unit.
• 411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central
Station DACR or Protected Premises Receiving Unit. See "Universal Digital Alarm Communicator
- 411UDAC" on page 39 for installation instructions for this unit.
NFPA 72 - Auxiliary Fire Alarm System
• 4XTMF (4412TM) Transmitter Module for connection to a compatible listed Local Energy
Municipal Box. See "Local Energy Municipal Box" on page 40 for installation instructions for this
unit.
NFPA 72 - Remote Station Fire Alarm System
• Fire•Lite RS82-9 Remote Station Receiver connected to a 4XTMF (4412TM) Transmitter
Module. See "Remote Station Receiver - RS82-9" on page 41 for installation instructions for this
unit.
• NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter connected to a compatible
listed Central Station DACR. See "Digital Alarm Communicator/Transmitter - Noti-Fire 911AC"
on page 38 for installation instructions for this unit.
• 411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central
Station DACR. See "Universal Digital Alarm Communicator - 411UDAC" on page 39 for
installation instructions for this unit.
NFPA 72 - Proprietary Fire Alarm System
• Potter EFT-C McCulloh Transmitter. See "Potter EFT-C McCulloh Transmitter" on page 42 for
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
Note: This application is not FM approved
Using the Noti-Fire 911AC DACT for connection to a Central Station Receiver or Protected Premises
Receiving Unit.
• AC Wiring for DACT/FACP must be connected to the same circuit.
• If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less
than 20 ft. (609.6 cm) in length in the same room.
• For additional information refer to the Noti-Fire 911AC Instruction manual.
See Below for Terminal
Connections
To Central
Station
PS 1270
To AC Power
+
–
12Volt
7AH Battery
Control Panel
IN #2
IN #3
IN #4
B+ B–
B+ B–
TB4
SUPV 2
SUPV 1
STD DACT
B+ B–
JP1
J2
4XZMF Zone
Relay Module
LATCH
TB1
DISABLE
OPT1
Jumper
Place jumper over pins as shown when employing
a DACT. This directs the control panel to transmit
all trouble conditions except AC LOSS.
Universal Digital Alarm Communicator - 411UDACAppendix B: NFPA Standard-Specific Requirements
Universal Digital Alarm Communicator - 411UDAC
The following figure illustrates an example of Central Station/Remote Station Receiver or Protected
Premises Receiving Unit reporting using a 411UDAC. The relay contacts of the MS-4412B/MS-4424B
may be used to trip any dialer listed for Central Station/Remote Station services. For additional inform ation
refer to the Instruction Manual for the 411UDAC.
• All connections between the control panel and the 411UDAC must be in conduit, less than 20 feet
(6.1 meters) in length in the same room.
• Any zone of the 411UDAC can be wired to function as alarm, trouble or supervisory; the unit must
be programmed accordingly. In this example, Zone 1 is wired to the control panel’s alarm relay,
Zone2 is wired to the control panel’s trouble relay, and Zone 3 is wired to the optional module’s
supervisory relay.
• AC power is supplied directly to the 411UDAC, not through the control panel. AC wiring for both
the 411UDAC and the control panel must be connected to the same AC branch circuit.
• End-of-line Resistors must terminate all circuits. In this example, Zone 4 is unused and is terminated
at the board.
• When employing a DACT, place the JP1 jumper, on the control panel, as shown below. This directs
the panel to transmit all trouble conditions except AC LOSS. The DACT must be configured to
transmit AC power loss to the central station.
Appendix B: NFPA Standard-Specific RequirementsLocal Energy Municipal Box
Local Energy Municipal Box
Using the 4XTMF (4412TM) Transmitter Module for connection to a Local Energy Municipal Box.
• The Municipal Box circuit supervises for ground faults and opens (i.e. missing wire) but not for
direct short between two wires. It is not a power-limited circuit.
• This application is not suitable for separate transmission of sprinkler supervisory or trouble
conditions.
• Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.
Perform the following prior to applying power to the system.
• Check the actual wiring hookup with the wiring diagrams.
• Insure that no pieces of wire have fallen into the circuitry.
• Check for missing or damaged parts.
Alarm Test
An initial alarm test should be conducted following installation to determine that all parts of the system
are functioning properly.
To perform an alarm test on the panel, initiate an alarm condition by blowing smoke into a smoke detector.
This should cause the first zone alarm condition.
• The alarm relay will activate.
• The red zone alarm LED will be illuminated.
• Notification Appliance Circuits and the local piezo will start sounding.
Maintenance
A regular schedule of inspection, testing, and maintenance is vital to insure proper and reliable operation
of the control panel. The procedures should be performed as required by the local authority having
jurisdiction. Refer to NFPA for further details.
Troubleshooting
A troubleshooting table is included on the following page which provides for symptoms, problems and
their solutions.
2. Remove all field wiring and install dummy ELR at
output circuit. Check for supervisory voltage across it,
(Normal -2.3 V), if problem persists, replace circuit
board.
3. Removed dummy ELR, reconnect field wiring and
measure voltage across output; (trouble-5V, short 0V).
4. Check for ELR at last device.
5. Check field wiring.
1. Check TB4 for proper connections.
2. Remove field wiring for zone in trouble and install
dummy ELR (4.7K for 24V; 2.2K for 12V). If
problem persists, replace circuit board.
3. Check for ELR at last device.
4. Check field wiring.
1. Check installation manual.
1. Check battery connections.
1. Remove batteries, check voltage across charger
output (17 to 19V for 24V; 8-10V for 12V), otherwise
replace circuit board.
2. Reconnect batteries, measure battery voltage at
battery terminals. If voltage is less than 85% of rated
voltage, allow them to charge for 48 hours.
3. If problem persists, replace batteries.
1. Remove field wiring from main panel and optional
module(s) (if installed). Install dummy ELR (4.7K for
24V; 2.2K for 12V).
2. Remove both battery leads.
3. If trouble clears, connect one circuit at the time to
pin point the problem.
4. If trouble doesn’t clear, replace circuit board.
1. Move Municipal Box disconnect switch SW1 up.
1. Install optional module(s) or replace jumper if
module(s) is not used.
1. Install dummy load if Municipal Box option isn’t
used.
2. Check Municipal Box wiring.
1. Remove field wiring and install ELR. If trouble
clears, look for faulty or incorrectly wired devices.
1. Cut associated jumper OPT1 or OPT2.
1. Make sure module is properly installed.
2. Move disable switch SW1 on 4XZMF (4412ZM) to
the left.
1. Make sure that 4XLMF (4412LM) module is
installed on J8.
2. Check field wiring.
1. Replace circuit board.
1. Press system reset.
1. Check incoming power (TB1).
1. Replace circuit board.
1. Replace circuit board.
AC
Power
LED ON
AC
Power
LED OFF
Circuit trouble
LED ON
Any of the right
column yellow
LEDs flashing
Notification appliance circuit
trouble
Initiating zone open circuit
trouble
Any of the right
System trouble
LED ON
column yellow
LEDs steady
ON
Zone disable
Missing or
Disconnected
Battery trouble
Batt yellow
LED ON
Power trouble
Low or
damaged
battery
LED ON
Ground fault trouble
Earth yellow LED ON
Yellow LED on
4XTMF ON
4XTMF (4412TM)
OPT1, OPT2 jumper cut
Municipal Box open circuit
Any of the right column red LEDs
ON
Disconnecting Municipal Box
switch ON 4XTMF (4412TM)
does not create a trouble
Short on initiating circuit wiring
Jumper for optional modules
isn’t cut
4XZMF(4412ZM): associated
LED doesn’t activate for alarm,
Optional module trouble
trouble or supervisory conditions
RZA-4XF piezo doesn’t sound for
alarm, trouble or supervisory
4XLMF
(4412LM)
conditions
Micro Fail yellow LED ONMicroprocessor damaged
All RZA-4XF LEDs stay ON
System trouble LED ON
Power wasn’t removed prior to
installation
Loss of main power
Damaged circuit breaker
Micro Fail yellow LED ONMicroprocessor damaged
initial alarm test
initiating circuits
initiating device
Initiating Device Circuit
initiating devices
Initiating Zone 1
inspection
interconnect wire, battery
Interface Module
interruption of circuits
43
30
32
37
32
43
11
32
27, 32
28
45
Index
J
J1 connector
J9 Connector
JP1 jumper
jumper
LATCH
TBL
jumper configurations
jumpers, SUPV1/SUPV2
13, 14
16
39
20, 22, 23
25
24
19
27
K
keyhole
knockouts
13
13, 16
L
label
Protected Premises Unit
terminal identification
LAMP TEST function
31
latch
LATCH jumper
25
latched
latching operation
LED
Disconnect
System Trouble
LED Interface Module
LEDs
Alarm, Trouble and Supervisory
Local Energy Municipal Box
loop resistance
lower position
25
31, 32
24
24
40
22, 23
25
22, 23
30
11, 22
10
M
main breaker panel
maintenance
Manual Pull Stations
Maximum Battery Capacity
Maximum Charging Circuit
maximum resistance
microprocessor
minimum clearance
module connectors
motherboard
mounting hole locations
mounting holes
Municipal Box
15
43
17
12
12
18
29
13
22
29
14
13
24, 40
N
19, 20
NACs
National Electrical Code, Article 760
National Fire Protection Association
negative
NFPA
NFPA standards
16
43
37
29
15
37
non-latching
nonpower-limited
nonresettable power
non-silenceable
Notification Appliance Circuit
Notification Appliances
25, 30
16, 25
18, 21
19
27, 30, 32, 43
37
O
40
opens
operating mode
operating voltage
optional boards
optional modules
Out of Service
output circuits
overcurrent protection
27
18
29
10, 20
28
30
15
P
panel functions
paper labels
20, 27, 30, 31, 32, 33, 43
piezo
piezo tones
polarity
polarity reversal circuit
polarized devices
positive
Potter EFT-C McCulloh Transmitter
Potter Electric Signal Company
power connection
Power Supervision Relay
power-limited
power-limited power supply
previous panel status
primary power
programmed
Protected Premises Receiving Unit
19
11
30
17, 28
41
17, 19
16
42
15
18
16, 19, 25, 41
20
32
15, 28
39
R
red wire
regulated power
relay contacts
Relay, System Alarm
Remote Alarm circuit
Remote Annunciator
Remote Station
Remote Station Service
Remote Trouble circuit
resettable power
resistance, allowable
resistor
resound
reverse polarity
reverse polarity circuit
reverse polarity loop
ripple voltage
RS82-9 Remote Station Receiver
The manufacturer warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service. Products
are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer
is to repair or replace, at its option, free of charge for parts and labor, any part which is
defective in materials or workmanship under normal use and service. For products not under
the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of
original purchase by the manufacturer's distributor unless the installation instructions or catalog
sets forth a shorter period, in which case the shorter period shall apply. This warranty is void
if the product is altered, repaired, or serviced by anyone other than the manufacturer or its
authorized distributors, or if there is a failure to maintain the products and systems in which
they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our customer service department. Return product, transportation
prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its
products. The manufacturer does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they are
installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes
no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse,
abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER
NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S
PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR
AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the
manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.
LimWarLg.p65 01/10/2000
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.