Fire-Lite Alarms MS4424 User Manual

Page 1
PN 15153:G1 ECN 02-539
Fire Alarm Control Panel
MS-4424
Instruction Manual
Document 15153 10/22/2002 Rev:
G
Page 2
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warn­ing devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede­termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power.
cated, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibil­ity to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized pro­fessional fire alarm installers only. Adequate written records of all inspections should be kept.
If detectors are not so lo-
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, ad­dition or deletion of system components, or after any modifica­tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for operation at 0-49° C/32-120° F condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi­nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Page 4
NFPA Standards
This control panel complies with the following NFPA standards:
NFPA 72 - Central Station Signaling Systems (Automatic, Manual, and Waterflow) - Protected Premises Unit Requires NOTI-FIRE 911AC DACT or 411UDAC Universal Digital Alarm Communicator
NFPA 72 - Local Fire Alarm Systems (Automatic, Manual, Waterflow and Sprinkler Supervisory)
NFPA 72 - Auxiliary Fire Alarm Systems (Automatic, Manual, and Waterflow) Requires 4XTMF
NFPA 72 - Remote Station Fire Alarm Systems (Automatic, Manual, and Waterflow) Requires 4XTMF or NOTI•FIRE 911AC DACT or 411UDAC
NFPA 72 - Proprietary Fire Alarm Systems (Automatic, Manual, and Waterflow) Requires Potter EFT-C McCulloh Transmitter.
Note: Applications which require the NOTI-FIRE 911AC, or the Potter EFT-C are not FM approved.
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
• NFPA 72 - Installation, Maintenance, and Use of Central Station Signaling Systems
• NFPA 72 - Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems
• NFPA 72 - Automatic Fire Detectors
• NFPA 72 - Installation, Maintenance, and Use of Notification Appliances for Protective Signaling Systems
• NFPA 72 - Testing Procedures for Signaling Systems
NFPA Standards
Underwriters Laboratories Documents
• UL 38 - Manually Actuated Signaling Boxes
• UL 217 - Smoke Detectors, Single and Multiple Station
• UL 228 - Door Closers - Holders for Fire Alarm Systems
• UL 268 - Smoke Detectors for Fire Alarm Systems
• UL 268A - Smoke Detectors for Duct Applications
• UL 346 - Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 - Audible Signaling Appliances
• UL 521 - Heat Detectors for Fire Protective Signaling Systems
• UL 864 - Standard for Control Units for Fire Alarm Systems
• UL 1481 - Power Supplies for Fire Protective Signaling Systems
• UL 1638 - Visual Signaling Appliances
• UL 1971 - Signaling Devices for the Hearing Impaired
• CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems
• CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm System
Other
• NEC Article 300 - Wiring Methods
• NEC Article 760 - Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
• Fire•Lite Device Compatibility Document, 15384.
• ADA - Americans with Disabilities Act
4
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 5
NFPA Standards.......................................................................................................... 4
NFPA Standards .................................................................................................... 4
Underwriters Laboratories Documents ................................................................. 4
Other....................................................................................................................... 4
1. Product Description
Overview ...................................................................................................................... 7
Features .......................................................................................................................7
Options ........................................................................................................................7
Circuits ......................................................................................................................... 8
Input Circuits.......................................................................................................... 8
Output circuits........................................................................................................ 8
Front Panel Control Switches ................................................................................ 8
Suplemental Documentation ...................................................................................... 8
Control Panel............................................................................................................... 9
DIP Switch Functions................................................................................................ 10
Options ....................................................................................................................... 10
Transmitter Module - 4XTMF ............................................................................ 10
Zone Relay Module - 4XZMF ............................................................................ 11
Remote Annunciator - RZA-4XF ....................................................................... 11
LED Interface Module - 4XLMF ........................................................................ 11
Meter Module (Volts-Amps) - 4XMMF ............................................................. 12
Specifications ............................................................................................................. 13
AC Power............................................................................................................. 13
Battery (lead acid only)........................................................................................ 13
Initiating Device Circuits ..................................................................................... 13
Notification Appliance Circuits ........................................................................... 13
Alarm and Trouble Relays ................................................................................... 13
Resettable Power.................................................................................................. 13
Nonresettable Power ............................................................................................ 13
RMS Regulated Power......................................................................................... 13
Table of Contents
Table of Contents
2. Installation
Cabinet Mounting ..................................................................................................... 15
Removal of Circuit Board.................................................................................... 15
Mounting of Cabinet ............................................................................................ 15
Attaching Conduit ................................................................................................ 15
Reinstallation of Circuit Board ............................................................................ 16
Installing Optional Voltmeter/Ammeter................................................................. 17
Power Connections.................................................................................................... 18
AC Connections ................................................................................................... 18
Battery (DC) Connections.................................................................................... 18
Power-limited Wiring Requirements ...................................................................... 19
Initiating Device Circuits.......................................................................................... 20
Four-Wire Smoke Detector Connections............................................................. 21
Output Circuits.......................................................................................................... 22
Notification Appliance Circuits ........................................................................... 22
General Alarm Configuration ....................................................................... 23
Supervisory Configuration............................................................................ 23
Ring-by-Zone Feature................................................................................... 23
Jumper Location ........................................................................................... 24
Jumper Configuration ................................................................................... 24
Alarm Relay Circuit............................................................................................. 25
MS-4424 Instruction Manual PN 15153:G1 10/22/02
5
Page 6
Table of Contents
Trouble Relay Circuit........................................................................................... 25
Powering External Devices ....................................................................................... 25
Optional Modules ...................................................................................................... 26
Overview .............................................................................................................. 26
Installation - Upper Position ................................................................................ 26
Installation - Lower Position................................................................................ 27
Setup and Configuration....................................................................................... 28
Setting Mode of Operation ....................................................................................... 31
DIP Switch Functions........................................................................................... 31
Power-Up Procedure................................................................................................. 32
3. System Operation
System Status LEDs .................................................................................................. 33
Control Switches........................................................................................................ 34
Zone Status LEDs...................................................................................................... 34
Piezo ............................................................................................................................ 35
Supervisory Service................................................................................................... 35
Zone Disable............................................................................................................... 35
Last Event Recall....................................................................................................... 36
Non-Silenceable Service ............................................................................................ 36
Sprinkler Supervisory Tracking .............................................................................. 36
System Events ............................................................................................................ 36
Standby Condition................................................................................................ 36
System Trouble Condition ................................................................................... 36
Alarm Condition................................................................................................... 36
Brownout Condition............................................................................................. 37
Transmitter Module - 4XTMF ...................................................................... 28
Zone Relay Module - 4XZMF ...................................................................... 29
LED Interface Module - 4XLMF.................................................................. 30
Appendix A: Secondary Power Calculations
Standby Battery Requirements................................................................................ 39
Calculating the Battery Capacity............................................................................. 40
Appendix B: NFPA Standard-Specific Requirements
Minimum System Requirements.......................................................................... 41
Additional Requirements...................................................................................... 41
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)41
NFPA 72 - Auxiliary Fire Alarm System ..................................................... 41
NFPA 72 - Remote Station Fire Alarm System ............................................ 41
NFPA 72 - Proprietary Fire Alarm System................................................... 41
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC............................. 42
Universal Digital Alarm Communicator - 411UDAC ............................................ 43
Local Energy Municipal Box.................................................................................... 44
Remote Station Receiver - RS82-9 ........................................................................... 45
Potter EFT-C McCulloh Transmitter ..................................................................... 46
Appendix C: Testing & Maintenance
Testing ........................................................................................................................ 47
Inspection ............................................................................................................. 47
Alarm Test............................................................................................................ 47
Maintenance............................................................................................................... 47
Troubleshooting......................................................................................................... 47
6
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 7
Overview
Features
1. Product Description
The Fire•Lite MS-4424 Fire Alarm Control Panel has been designed as a control center for use in automatic fire detection systems. The panel is designed for maximum reliability with 100% solid state circuitry and isolated relay contacts for outside interfacing and features programmable options to allow on-site customization of the unit for various operating configurations.
An integral standby battery system, with charger, is provided. In case of commercial AC power interruption, automatic switchover to the battery system will provide power to the panel for a minimum of 24 hours.
The FACP is supplied complete with backbox, hinged door, control switches, and indicator LEDs.
The entire unit is housed in a standard sheet-metal enclosure with 1/2 in. (12.7 mm) and 3/4 in. (19.05 mm) conduit knockouts available.
The MS-4424 is a 110/120 VAC fire alarm control panel. The MS-4424C is a 110/120 VAC panel that functions according to the requirements of Underwriters Laboratories of Canada (ULC). The MS-4424E is an export version that uses 220/240 VAC.
• Microprocessor-controlled
• Power-limited on all circuits except Municipal Box
Output
• Alarm and trouble resound
• Four Style B/D Initiating Device Circuits
• Two Style Y/Z Notification Appliance Circuits
• Two Style Y only Notification Appliance Circuits
• General alarm and trouble relays
•One Man Walk Test
• Ring-by-Zone
• Disable/enable controls per Initiating Device Circuit
• Last Event Recall
• Battery /Earth fault supervision
• Current protection on all notification circuits
• RMS regulated output power, 2.25 amps
• 7 amp-hour (AH) to 18 AH battery options, up to 60 hours standby
• Resettable and nonresettable regulated power outputs
• Extensive transient protection
• Watchdog timer to supervise microprocessor
• Output circuits protected against false activations
• Slide-in zone identification labels
• Steel cabinet 14.5” (36.83cm) wide by 16.00” (40.64cm) high by 4.75” (12.07cm) deep
Options
• 4XZMF Module for 4 zone relays
• 4XTMF Transmitter Module - Complies with NFPA 72 Auxiliary and Remote Station Protective Signaling systems
• 4XMMF Volt/Amp Meter Module
• RZA-4XF Supervised remote annunciator (requires 4XLMF Interface Module)
• 411UDAC or NOTI•FIRE 911AC Digital Communicator - Complies with NFPA 72 Central Station and Remote Station Protective Signaling systems
Note: Applications which require the 411UDAC, the NOTI-FIRE 911AC, or the Potter EFT-C are not FM approved.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
• Potter EFT-C McCulloh Transmitter - Complies with NFPA 72 Proprietary Fire Alarm Systems
• Waterflow Input option
• Supervisory Input option
• Alarm Verification option
• Dead-front dress panel option (DP-4XF) (Required for Canadian applications)
• Trim ring for flush mount between 16 in. (40.64 cm) center studs (TR-4XRF)
7
Page 8
1. Product Description Circuits
Circuits
Input Circuits
Initiating Device Circuit 1 (Style B/D)
Initiating Device Circuit 2 (Style B/D)
Initiating Device Circuit 3 (Style B/D)
Initiating Device Circuit 4 (Style B/D)
Note: Optional auxiliary relay module 4XZMF tracks these four circuits.
Output circuits
Notification Appliance Circuit 1 (Style Y/Z)
Notification Appliance Circuit 2 (Style Y/Z)
Notification Appliance Circuit 3 (Style Y)
Notification Appliance Circuit 4 (Style Y)
Front Panel Control Switches
Switch 1 - Tone Silence
Switch 2 - Alarm Silence
Switch 3 - Alarm Activate
Switch 4 - System Reset
Suplemental Documentation
The table below lists document sources containing additional information regarding the MS-4424:
For information on... Refer to... Part Number
All Features MS-4424 Data Sheet DF-51069
Compatable Devices Fire•Lite Device Compatability Document 15384
Digital Alarm Communicator/Transmitters
Remote Station Receiver Fire•Lite RS82-9 Instruction Manual 15400
Voltmeter/Ampmeter 4X Series Power Meter PID 15396
NOTI-FIRE 911AC Instruction Manual
411UDAC Instruction Manual
74-06200-005
51073
8
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 9
Control Panel 1. Product Description
Control Panel
Notification Appliance Circuits
24VDC
Regulated Nonresettable
Regulated Resettable
RMS-Regulated
B+ A+ A– B–
TB1
#1 - Style Z (Class A) / Style Y (Class B) #2 - Style Z (Class A) / Style Y (Class B) #3 - Style Y (Class B) #4 - Style Y (Class B)
OUT#1
OUT#2
B+ A+ A– B–
OUT#3 B+ B–
OUT#4 B+ B–
TB2
TB3
Relays
Alarm Contacts Trouble Contacts
Initiating Device Circuits
Style D (Class A) / Style B (Class B)
IN #2
B+ A+ A– B–
JP1
IN #1
B+ A+ A– B–
IN #3
B+ A+ A– B–
IN #4
B+ A+ A– B–
TB4
GEN ALM1
GEN ALM2
J1
AC POWER
SYSTEM
ALARM
ALARM TEST
SUPERVISORY
TB5
J2
AMP
J9
J3
SYSTEM
TROUBLE
CIRCUIT
TROUBLE
ALARM
SILENCED
POWER
TROUBLE
TONE
SILENCE
ALARM
SILENCE
ALARM
ACTIVATE
ZONE 1
ZONE 3
ZONE 4
SYSTEM
RESET
SUPV 1
SUPV 2
Jumpers for configuring Output Circuits
J4
J5
OPT1
J10
OPT2
J7
J8
Battery Fail LED
Ground Fault LED
MS-4424 Instruction Manual PN 15153:G1 10/22/02
SW1 - DIP Switch
Micro Fail LED
Figure 1 Control Panel
SW1
J4 - J5 - J7 - J8
Optional Module
Connectors
MS4424-board.cdr
9
Page 10
1. Product Description DIP Switch Functions
DIP Switch Functions
The table below describes the DIP switch functions. For a more detailed explaination see "Setting Mode of Operation" on page 31.
Options
#1 Alarm
Verification
#2 Waterflow ON Zone 3 configured for Waterflow.
#3 Supervisory ON Zone 4 configured for Supervisory.
#4 Silence
Inhibit
#5 Disable
NACs
#6 Walk Test ON Places the panel into Walk Test Mode.
Note: See “Setting Mode of Operation” on page 31 for a more detailed explanation of DIP switch functions.
ON Alarm Verification enabled (two-minute period). OFF No verification employed.
OFF Zone 3 functions as a normal Initiating Device Circuit.
OFF Zone 4 functions as a normal Initiating Device Circuit.
ON Alarm Silence will not function for 60 seconds after initiation of an alarm. OFF Alarm Silence is possible at any time after initiation of an alarm.
ON Four Notification Appliance Circuits and the Alarm Relay are disabled. OFF Four Notification Appliance Circuits and the Alarm Relay are enabled.
OFF Normal Operating Mode.
Three optional modules are available for use on the control panel. The control panel provides mounting slots for two of these optional module boards.
Transmitter Module - 4XTMF
The Transmitter Module provides a supervised output for a Local Energy Municipal Box transmitter and alarm and trouble reverse polarity circuits for Remote Station Service. Also included is a DISABLE switch and disable trouble LED.
Note: As a jumper option, the alarm reverse polarity circuit will open on trouble if no alarm exists.
Specifications for Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System)
Supervisory current: 5.0 mA. Trip current: 0.35 amps (subtracted from Notification Appliance power). Coil Voltage: 3.65 VDC. Coil resistance: 14.6 ohms. Maximum allowable wire resistance between panel and trip coil: 3 ohms. Municipal Box wiring can leave the building.
TBL
J1
J2
TB1
4XTMF.cdr
10
Specifications for Remote Station Service (NFPA 72 Remote Station Fire Alarm System)
Maximum load for each circuit: 10 mA. Reverse polarity output voltage: 24 VDC. Remote Alarm and Remote Trouble wiring can leave the building.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 11
Options 1. Product Description
Zone Relay Module - 4XZMF
The Zone Relay Module provides Form-C contacts for the following:
• Relay #1 - Alarm Zone 1
• Relay #2 - Alarm Zone 2
• Relay #3- Alarm Zone 3
• Relay #4 - Alarm Zone 4
• Relay #5 - System Alarm
• Relay #6 - System Trouble
Note: As a jumper option, Alarm Zone 1, 2, 3 & 4 can be made Silenceable.
J2
Specifications
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
Remote Annunciator - RZA-4XF
The Remote Annunciator mounts on a standard single-gang box, an d provides LED indication of the following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• System Trouble LED (yellow)
A local trouble sounder and silence switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit an easy change of zone information.
Note: The Remote Annunciator requires the use of an LED Interface Module as described below.
FIRE ALARM ANNUNCIATOR
LATCH
SYSTEM TROUBLE
RE-SOUND
TONE
SILENCE
TB1
DISABLE
4XZMF.cdr
RXA-4XF.cdr
LED Interface Module - 4XLMF
The LED Interface Module supports the RZA-4XF Remote Annunciator Module. Annunciator wiring is supervised for open conditions by this module. The module mounts to the main board on the J8 option connector.
Specifications
Maximum voltage/current, each output: 27.6 V / 8 mA. Outputs are power-limited.
TB1
J2
4XLMF.cdr
MS-4424 Instruction Manual PN 15153:G1 10/22/02
11
Page 12
1. Product Description Options
Meter Module (Volts-Amps) - 4XMMF
The Meter Module provides a voltmeter to measure the voltage across the batteries and an ammeter to measure the charging current to the batteries. The meters are provided as an assembly that mounts to the lower left-hand corner of the cabinet.
0
10 20
DC VOLTS
30
3
0
DC AMPERES
3
4XMMF.cdr
12
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 13
Specifications 1. Product Description
Specifications
AC Power
MS-4424, MS-4424C: 110/120 VAC, 50/60 Hz, 1.2 amps MS-4424E: 220/240 VAC, 50/60 Hz, 0.6 amps
Wire size: minimum #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps Maximum Battery Capacity: 18 AH.
Note: Batteries larger than 12 AH require Fire•Lite BB-17F or other UL-listed external battery cabinet.
Initiating Device Circuits
Power-limited circuitry
Operation: Style B (Class B) or Style D (Class A) Normal Operating Voltage: 24 VDC (ripple = 1.0V p-p) Alarm current: 15 mA minimum Short circuit current: 40 mA maximum Maximum detector current in standby: 2 mA (max) per zone Maximum loop resistance: 100 ohms End-of-Line Resistor: 4.7K, 1/2-Watt (part # 71252 UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including End-of-Line Resistor)
Notification Appliance Circuits
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC Normal Operating Voltage: 24 VDC Total current available to all external devices: 2.25 amps Maximum signaling current per circuit: 1.5 amps End-of-Line Resistor: 4.7K, 1/2-Watt (part # 71252 UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
Note: Any power connected to these relay contacts must come from a power-limited supply. Fail-safe operation ensures trouble relay functioning under loss of both primary power (AC) and secondary (battery power).
Resettable Power
Up to 200 mA is available for powering four-wire smoke detectors. Maximum ripple voltage: 1.0 V p-p.
Nonresettable Power
Total DC current available from this output is up to 200 mA (subtracted from four-wire smoke detector power). Maximum ripple voltage: 1.0 V p-p.
RMS Regulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available to Notification Appliance Circuits). Maximum ripple voltage: 100 mV p-p.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
13
Page 14
1. Product Description Specifications
Notes
14
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 15
Cabinet Mounting
Carefully unpack the system and check for shipping damage.
Select a suitable location in a clean, dry, vibration-free environment that is not subject to extreme temperatures. Locate the top of the cabinet approximately five feet above the floor with the hinge on the left. The panel must be easily accessible for maintenance; the hinged door requires a minimum clearance of 14 in. (35.56cm) to open.
Removal of Circuit Board
To prevent damage to the printed circuit board it should be removed prior to mounting of cabinet.
Step Action
1
Disconnect the transformer wires from the circuit board at the J1 connector.
2
Remove the four (4) phillips head screws securing circuit board to backbox rails.
3
Carefully set board aside in a secure place.
2. Installation
Mounting of Cabinet
Securely mount the cabinet using the mounting holes provided.
Step Action
1 Mark and predrill holes for the top two keyhole mounting screws using the
dimensions shown in Figure 2 on page 16.
2 Install two upper screws in the wall with the heads protruding.
3 Using the upper keyholes, mount the backbox over the two screws.
4 Mark and drill the lower two holes.
5 Secure backbox by installing the remaining fasteners and tightening all
screws.
6
If required, attach optional Trim Ring (TR-4XRF) using the provided instructions.
Attaching Conduit
Select and remove knockouts according to the number of conduits required.
Attach conduits to backbox as required.
Determine the number of conductors required for the devices to be employed. Pull required conductors into the box through the knockouts provided.
Note: All wiring should be in accordance with the National and/or Local codes for fire alarm systems, including "Power-limited Wiring Requirements" on page 19.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
15
Page 16
2. Installation Cabinet Mounting
(
)
(
)
(
)
(
)
(
)
The figure below shows the exterior dimensions and mounting hole locations for the cabinet backbox and dimensions of the optional trim ring:
16.125”
(40.96cm)
1.00” (2.54cm)
1.00” (2.54cm)
9.50”
(24.13cm)
14.50”
(36.83cm)
14.625”
37.15cm
12.50”
31.75cm
5.375”
13.65cm
4.75”
12.07cm
16.00”
40.64cm
MS44-cabdim.cdr
Figure 2 Cabinet Mounting Dimensions
Reinstallation of Circuit Board
Reinstall the printed circuit board as follows:
Step Action
1 Position circuit board over stand-offs on backbox rail and secure with four
(4) phillips screws. Tighten securely.
14.625”
(37.15cm)
16.125”
(40.96cm)
1.5”
(3.81cm)
MS44-trimring.cdr
2 Connect transformer wires to J1 connector on circuit board.
16
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 17
Installing Optional Voltmeter/Ammeter 2. Installation
Installing Optional Voltmeter/Ammeter
To monitor battery voltage and battery charging current, a 4XMMF Meter Module is required. To install the power meter module follow the steps below:
Step Action
1
Cut the jumper wire labeled “AMP”.
2 Secure the module to the backbox with the hardware provided. Refer to
Product Installation Drawing (PID) for detailed instructions.
3
Connect meter cable P2 to connector J2 on the main circuit board.
4
Connect meter cable P3 to connector J3 on the main circuit board.
The figure below shows the mounting location and connections for the Voltmeter/Ammeter.
TB5
‘AMP’ Jumper
J2
AMP
J9
J3
10 20
DC VOLTS
0
30
3
0
3
DC AMPERES
Figure 3 Mounting and Connecting the Meters
MS44-mminst.cdr
MS-4424 Instruction Manual PN 15153:G1 10/22/02
17
Page 18
2. Installation Power Connections
Power Connections
WARNING: Do not apply any type power to this control panel until all connections have been
!
made and verified.
AC Connections
Disconnect (open) the circuit breaker in the AC main breaker panel and tag it “Out of Service”.
Note: Refer to "Power-Up Procedure" on page 32 before closing AC breaker.
Primary power required for the MS-4424 and MS-4424C control panel is 110/120 VAC, 50/60 Hz, 1.2 amps and for the MS-4424E is 220/240 VAC, 50/60 Hz, 0.6 amps. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use #14 AWG (2.00 mm
A separately fused and protected power connection to the panel should be supplied to prevent voltage fluctuation and interruption of power.
Ground
2
) or larger wire with 600V insulation rating.
Neutral
Hot
TB5
J2
AMP
J9
J3
MS44-ACconn.cdr
Figure 4 AC Power Connections
Battery (DC) Connections
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
!
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
CAUTION: Do NOT connect the battery interconnect wire at this time. Make this connection AFTER
!
initial system primary power connection.
Place batteries into bottom of cabinet as shown below. See "Appendix A: Secondary Power Calculations" on page 39 for calculation of correct battery rating.
Note: Batteries are shipped separately and should be mounted only after the cabinet has been installed, the conduit connected, and all wiring pulled, tested, and made ready to be terminated.
18
Continued on the next page...
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 19
Power-limited Wiring Requirements 2. Installation
Observe polarity when connecting the batteries. Connect the battery cable (p/n 75203 or 75202, depending on terminal size of battery) to terminal J9 on the main circuit board using the plug-in connector provided. Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing batteries. Do NOT connect battery interconnect wire at this time.
TB5
J2
AMP
J9
J3
Figure 5 Battery Installation and Connection
Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power­limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must pass through separate knockouts and/or conduits.
B+ A+ A– B–
TB1
J1
TB5
J2
AMP
J9
J3
MS44-BATconn.cdr
All upper terminals are power-limited circuits
OUT#4
AC POWER
SYSTEM
ALARM
ALARM TEST
SYSTEM TROUBLE
CIRCUIT TROUBLE
ALARM
SILENCED
POWER TROUBLE
TONE
SILENCE
ALARM
OUT#3
B+ B–
NO NC C
B+ B–
TB3
TB2
GEN ALM1
GEN ALM2
ALARM
ALARM
SILENCE
ACTIVATE
OUT#1
OUT#2
B+ A+ A– B–
SUPERVISORY
ZONE 1
ZONE 2
ZONE 3
ZONE 4
SYSTEM
RESET
IN #2
IN #3
IN #1
B+ A+ A– B–
JP1
SUPV 1
SUPR 2
B+ A+ A– B–
IN #4
B+ A+ A– B–
B+ A+ A– B–
TB4
TB1
POWER LIMITED
J4
TBL
J1
J5
J2
7 6 5 1
OPT1
TB1
Power-limited Circuit
J10
OPT2
J7
J8
J2
DISABLE
SW1
LATCH
Nonpower-limited Circuit
AC Power
MS-4424 Instruction Manual PN 15153:G1 10/22/02
MS44-plwiring.cdr
Figure 6 Power-limited Wiring Requirements
19
Page 20
2. Installation Initiating Device Circuits
Initiating Device Circuits
The control panel provides four Initiating Device Circuits and they may be configured as either Style D (Class A) or Style B (Class B).
Circuit #4 may be converted to a Supervisory Circuit by setting DIP switch #3 to the ‘on’ position (see "Setting Mode of Operation" on page 31).
Initiating devices include: Heat, Photoelectric and Ionization type detectors, Manual Pull Stations and Waterflow alarm devices.
Note: Refer to the Device Compatibility Document for compatible devices.
• Wire all alarm initiating devices sequentially for proper supervision.
• Observe polarity when connecting polarized devices.
• All circuits are supervised and power-limited.
• Leave dummy load resistor (provided) on all unused circuits.
Style D (Class A)
Initiating Device
Circuit
Heat Detector
Two-wir e Smoke Detector
Manual Pull Station
Style B (Class B)
Initiating Device
Circuit
Style B (Class B)
Initiating Device
Note: Silk screen printing on circuit board moved to bottom for clarity
4.7K, 1/2-Watt resistor PN 71252 (UL listed)
Supervisory Circuit
(If DIP switch SW1-3
Circuit
Style B (Class B)
is “ON”)
Normally Open Tam p e r S w i t ch
MS44-idc.cdr
20
Figure 7 Initiating Device Circuits
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 21
Initiating Device Circuits 2. Installation
Four-Wire Smoke Detector Connections
A maximum of 200mA is available from the 24VDC Resettable Power circuit on TB1 (+24VR terminals). Any power that is drawn from the 24VDC Nonresettable Power on TB2 (+24VNR terminal) must be subtracted from available resettable power. See "Specifications" on page 13 and "Powering External Devices" on page 25.
Note: Refer to the Device Compatibility Document for suitable 4-wire smoke detectors.
Notes on Style D (Class A) and Style B (Class B) field wiring:
1. The Power Supervision Relay coil leads must be connected to the last detector base 24V screw terminals.
2. Calculation of the maximum allowable resistance in the 24VDC resettable power wiring:
Rmax =
(20.6 - Vom)
(N x Is) + (Na x Ia) + (Ir)
Where:
Rmax = maximum resistance of the 24 VDC wires Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts N = total number of detectors on the 24 VDC supply circuit Is = detector current in standby Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia = detector current in alarm Ir = end-of-line relay current
4.7K, 1/2-Watt ELR
+
+
TB1
Control Panel Power Circuit
IN #1
B+ A+ A– B–
Initiating Device Circuit
Style B
IN B+ A+
TB4
Power Supervision Relay (A77-716B)
+
+
24 VDC Four-wire
Smoke Detectors
MS44-4wiresd.cdr
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Figure 8 Typical Connection for Four-Wire Smoke Detectors
21
Page 22
2. Installation Output Circuits
Output Circuits
Notification Appliance Circuits
The control panel provides four Notification Appliance Circuits (two Style Y or Z and two Style Y only). Each circuit is capable of 1.5 amps of current. Total current drawn from all four circuits cannot exceed
2.25 amps. NACs are supervised and power-limited.
Note: Refer to the Device Compatibility Document for suitable devices.
For details on how jumper configurations affect panel functions see Table 1, “Jumper Configuration Table” on page 24.
• For DIP switch configuration, see "Setting Mode of Operation" on page 31.
• For non-silenceable service on Initiating Zone #1, see "Non-Silenceable Service" on page 36.
• Unused circuits must be connected with a dummy load as shown.
Style Y
(Class B)
Style Z
(Class A)
Polarized Bell
4.7K, 1/2-Watt ELR (PN 71252)
Polarized Strobe
Polarized Horn
Unused Style Y Circuit
(4.7K, 1/4-Watt ELR)
TB2
MS44-nac.cdr
Figure 9 Notification Appliance Circuits
22
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 23
Output Circuits 2. Installation
General Alarm Configuration
NACs can be configured in two different ways, other than the default, to sound a General Alarm (see Table 1 on page 24):
• If ‘GEN ALM 1’ jumper is cut (see Figure 10 on page 24 for location): IDC #1 will activate
NAC #1; IDC #2, #3 or
• If ‘GEN ALM 2’ jumper is cut (see Figure 10 on page 24 for location): IDC #1 or
NACs #1 and
Note: Default = If any IDC is activated all NACs will sound.
#2; IDC #3 or #4 will activate NACs #3 and #4.
#4 will activate NACs #2, 3, and 4.
#2 will activate
Supervisory Configuration
If DIP switch #3 - “Supervisory on Zone 4” is selected (see "Setting Mode of Operation" on page 31) IDC #4 will act as a supervisory circuit and NAC #4 will not activate unless SUPV1 jumper is cut (see Table 1 on page 24).
• To activate only the #4 NAC, cut the SUPV1 jumper (see Figure 10 on page 24 for location).
• To disable all NACs for supervisory conditions, cut the SUPV2 jumper (see Figure 10 on page 24
for location).
Note: If a 4XZMF Zone Relay Module is used, Relay 4 will activate for supervisory conditions.
Note: If an RZA-4XF Remote Annunciator is used, the fourth LED (red) will annunciate supervisory conditions.
Ring-by-Zone Feature
This feature, if enabled, will allow NAC #1 to sound if IDC #1 is activated; NAC#2 to sound if IDC#2 is activated; etc. (see Table 1 on page 24). NACs will function as General Alarm (all four NACs will be activated when any IDC zone goes into alarm) unless the Ring-by-Zone feature is enabled.
• To enable Ring-by-Zone feature, cut the following jumpers (see Figure 10 on page 24 for location):
GEN ALM1, GEN ALM2, and SUPV1
MS-4424 Instruction Manual PN 15153:G1 10/22/02
23
Page 24
2. Installation Output Circuits
Jumper Location
To locate jumpers on the circuit board, see Figure 1 on page 9.
GEN
SUPV 1
ALM1
SUPV 2
GEN ALM2
Figure 10 Jumpers
Jumper Configuration
The table below lists the various configurations for the NACs:
and this
Notification Appliance
will be activated
(x = output activated)
1234
If this jumper has been cut...
Gen Alm #1
Gen Alm #2
Supv #1
Supv #2
Gen Alm #1 & #2 and Supv #1 (Ring-by-Zone)
None
Initiating
Device
Circuit
has
activated...
1x 2 xxx 3 xxx 4 xxx 1xx 2xx 3xx 4xx 1 xxx 2 xxx 3 xxx 4x 1 xxxx 2 xxxx 3 xxxx 4 1x 2x 3x 4x 1 xxxx 2 xxxx 3 xxxx 4 xxxx
MS44-jumper.cdr
then this
Circuit
24
Table 1 Jumper Configuration Table
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 25
Powering External Devices 2. Installation
Alarm Relay Circuit
One Form-C dry contact alarm relay is provided in the basic panel for controlling supplementary devices. Contacts are rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and are non-silenceable when an alarm occurs.
Trouble Relay Circuit
One Form-C dry contact trouble relay is provided in the basic panel for controlling supplementary devices. It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive) and will restore to normal when the trouble condition is cleared.
Note: Power connected to these relay contacts must come from a power-limited supply. Power may be obtained from TB1 Terminals 24VU or 24VR and TB2 Terminals 24VNR, or a UL-listed power-limited power supply.
TB3
Figure 11 Schematic Representation of Alarm/Trouble Coils & Contacts
Powering External Devices
CAUTION: Several different sources of power can be connected to this panel. Disconnect all sources
!
of power before servicing. The panel and associated equipment may be damaged by removing and/or
!
!
inserting cards, modules, or interconnecting cables while this unit is energized.
DC power connections are available from TB1 and TB2 on the control panel as shown below:
RMS-Regulated Power - 24 VDC power for inductive-type devices such as door holders can be connected to these terminals.
This output is not suitable for powering devices requiring filtered DC power.
TB1
MS44-relay.cdr
TB2
MS44-dcpower.cdr
Nonresettable Power -
24 VDC filtered, nonresettable power can be drawn from these terminals.
The combined current draws from the Resettable and Nonresettable outputs cannot exceed 200 mA.
Resettable Power -
24 VDC filtered, resettable power for four-wire smoke detectors can be obtained from these terminals.
The combined current draws from the Resettable and Nonresettable outputs cannot exceed 200 mA.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Figure 12 Power Terminals
25
Page 26
2. Installation Optional Modules
Optional Modules
Overview
The control panel has two module connectors - J5 (upper position) and J8 (lower position). Three modules are available for the panel and they can be used in any combination, including duplicate modules. The corresponding option jumper must be cut before installation of an optional module, to enable module supervision.
• The 4XTMF Transmitter and 4XZMF Zone Relay Modules can be installed in either position.
• The 4XLMF LED Interface Module must be installed in the lower position only.
Installation - Upper Position
To install either the 4XTMF or 4XZMF module in the upper position follow these instructions:
Step Action
1 Cut jumper ‘OPT1’ on main circuit board.
2 Insert the two stand-offs into the holes located on the right-side edge of the
main board. Secure with nuts and tighten securely.
3 Align the pins of J5 (and J4) connectors on the main board with the holes on
the underside of the J2 (and J1) connector on the optional board. Carefully press down on the optional board until the pins are through the connectors and it rests on the stand-offs.
4 Secure optional board to stand-offs with screws. Tighten securely.
5 Affix the terminal identification label (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module.
Install Stand-offs here
B–
IN #2
B+ A+ A– B–
B+ A+ A– B–
J4
J5
J10
J7
J8
IN #3
IN #4
B+ A+ A– B–
TB4
J2
OPT1
LATCH
TB1
DISABLE
OPT1 - Cut prior to installation of module
OPT2
26
MS44-instmod1.cdr
Figure 13 Module Installation - Upper Position
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 27
Optional Modules 2. Installation
Installation - Lower Position
To install either the 4XTMF, 4XZMF or 4XLMF module in the lower position follow these instructions:
Step Action
1 Cut jumper ‘OPT2’ on main circuit board.
2 Remove the lower-right screw securing the main board to the lower rail.
Replace with a stand-off and tighten securely.
3 Insert one stand-off into the other hole located on the right-side edge of the
main board. Secure with nut and tighten securely.
4
Align the pins of J8 (and J7) connectors on the main board with the holes on the underside of the J2 (and J1) connector on the optional board. Carefully press down on the optional board until the pins are through the connectors and it rests on the stand-offs.
5
Secure optional board to stand-offs with screws. Tighten securely.
6 Affix the terminal identification label (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module.
IN #2
IN #3
B–
B+ A+ A– B–
B+ A+ A– B–
IN #4
B+ A+ A– B–
TB4
J4
J5
TB1
OPT1
OPT2 - Cut prior to installation of module
Install Stand-offs here
J10
J7
J8
OPT2
J2
Figure 14 Module Installation - Lower Position
MS44-instmod2.cdr
MS-4424 Instruction Manual PN 15153:G1 10/22/02
27
Page 28
2. Installation Optional Modules
Setup and Configuration
Transmitter Module - 4XTMF
Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module as shown below. Polarities shown in activated positions.
Note: Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected.
Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.
Pushing the Disconnect Switch down will prevent unwanted acti vation of the Municipal Box during testing of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the Municipal Box.
Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring Requirements" on page 19.
TB1
+
Remote Alarm (Power-limited)
– +
Remote Trouble (Power-limited)
No Connection
+
Municipal Box (Nonpower-limited)
TBL Jumper
TBL
Disconnect Switch
J1
J2
Figure 15 4XTMF Configuration
Disconnect LED
4XTMF.cdr
28
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 29
Optional Modules 2. Installation
Zone Relay Module - 4XZMF
Relay #1 through #4 will activate with Input #1 through #4 and remain latched unless jumper “LATCH” is cut. For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact, the relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right.
Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label, located on the door of the control panel.
TB1
J2
LATCH
DISABLE
4XZMF.cdr
Disable Switch“Latch” Jumper
Figure 16 Wiring the Zone Relay Module
The wiring of this module must follow the requirements specified under "Power-limited Wiring Requirements" on page 19.
• If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of
dry contacts to maintain the required separation between circuit types.
• If this module is used to drive both nonpower-limited and power-limited relays that are next to each
other, refer to the figure below which shows the one allowable arrangement.
Power-Limited Circuit
MS-4424 Instruction Manual PN 15153:G1 10/22/02
No Connection
Nonpower-Limited Circuit
MS44--4xzmf1.cdr
Figure 17 Mixing Power-Limited and Nonpower-Limited Circuits
29
Page 30
2. Installation Optional Modules
LED Interface Module - 4XLMF
Connect the terminals on TB1 of the LED Interface Module to the corresponding terminals of the RZA­4XF Remote Annunciator.
Make wiring connections with system power off.
Maximum wire impedance is 50 ohm per wiring connection.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring Requirements" on page 19.
TB1
+24V Out #1 Out #2 Out #3 Out #4 Sysyem Trouble Sound Resound
J2
Connect to corresponding terminals of the RZA-4XF Remote Annunciator.
SYSTEM TROUBLE
RE-SOUND
TONE
SILENCE
FIRE ALAR M ANNUNCIATOR
Front View
Side View
Figure 18 Connection of 4XLMF to RZA-4XF
Single-gang Box
MS44--4xlmfconn.cdr
30
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 31
Setting Mode of Operation 2. Installation
Setting Mode of Operation
Select operating mode by setting the SW1 DIP switches as described below; basic programming options are shown in this section.
After any changes are made to the configuration of the switches, the panel must be reset.
For Canadian use, refer to "Sprinkler Supervisory Tracking" on page 36.
SW1
MS44-dipsw.cdr
Switch 1: Alarm Verification Switch 2: Waterflow on Zone 3 Switch 3: Supervisory on Zone 4
Switch 4: Silence Inhibit Switch 5: Disable NACs Switch 6: Walk Test
Figure 19 DIP Switch Settings
DIP Switch Functions
Switch 1: Alarm Verification - If selected (‘ON’), alarm signals that occur on any zone will be
subjected to a two-minute verification period to determine if the alarm is true. Note that the control panel will distinguish if the alarm signal came from a shorting-type contact device (manual pull station, four­wire detector, or heat detector) or a two-wire smoke detector, and will not employ verification of alarm signals from the contact devices.
Switch 2: Waterflow on Zone 3 - If set for Waterflow (‘ON’), Initiating Device Circuit #3 will function as a waterflow circuit. If an alarm occurs on this zone, the ALARM SILENCE switch will not silence any activated output circuits.
Switch 3: Supervisory on Zone 4 - If set for Supervisory (‘ON’), Initiating Device Circuit #4 will function as a supervisory circuit. Activation of a tamper or other supervisory switch on this circuit will result in a supervisory condition, but not an alarm condition, at the panel. All NACs will activate unless SUPV1 or SUPV2 jumpers are cut (see Table 1 on page 24 for jumper configuration table). The piezo will sound a distinct pulsing tone and the yellow LED on zone 4 will flash along with the supervisory LED.
Switch 4: Silence Inhibit - If selected (‘ON’) and an alarm occurs, the ALARM SILENCE switch will not function until 60 seconds have passed since initiation of the alarm. If another alarm occurs, the timer will restart at 60 seconds.
Switch 5: Disable NACs - When this switch is set ‘ON’, the four Notification Appliance Circuits and the System Alarm Relay will be disabled, and a local trouble signal will be generated.
Switch 6: Walk Test - Setting this switch to the ‘ON’ position places the control panel in Walk Test Mode. The first alarm on the Initiating Circuit under test will ring associated Notification Appliance Circuit(s) for 5 seconds. Zone Alarm LED will flash. The second alarm on Initiating Circuit under test will ring associated Notification Circuit(s) for 1 second. Zone Alarm LED will illuminate steadily. A Trouble condition on the Initiating Circuit under test will sound the control’s piezo and light the Zone Trouble LED.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
31
Page 32
2. Installation Power-Up Procedure
Power-Up Procedure
WARNING: Prior to energizing this panel, notify all personnel and authorities, including any personnel who may be working on, around, or near this unit.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
!
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
CAUTION: Observe polarity of batteries. Improper connection will cause damage and VOID
WARRANTY.
!
Follow these steps to power-up the FACP:
1. Conduct Visual Inspection. A careful visual inspection should be made before applying power to the system. See “Inspection” on page 47.
2. Notification. Notify personnel who may be working with the AC power circuits before removing the “Out of Service” tag.
3. Apply Primary Power. Switch the circuit breaker to the ‘closed’ position, providing power to the circuit.
• The green AC power LED will illuminate.
• The Trouble LED will illuminate until battery power is applied.
4. Connect Secondary Power. Connect battery interconnect wire as shown below.
• The trouble LED will clear. If the trouble light does not clear, refer to "Troubleshooting Table" on
page 48.
Battery Interconnect Wire
MS44-batcable.cdr
Figure 20 Battery Connections
32
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 33
System Status LEDs
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
3. System Operation
System Status LEDs
AC POWER
SYSTEM
ALARM TEST
SUPERVISORY
SYSTEM
TROUBLE
CIRCUIT
TROUBLE
SILENCED
TROUBLE
TONE
SILENCE
BATT EARTH
ALARM
ALARM
POWER
ALARM
SILENCE
ALARM
ACTIVATE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
SYSTEM
RESET
MS44-panel1.cdr
MICRO FAIL
Figure 21 System Status LEDs
AC Power - Green LED that illuminates steadily to indicate presence of AC power.
System Alarm - Red LED that flashes when an alarm occurs.
Alarm Test - Red LED that illuminates during Walk Test.
Supervisory - Yellow LED that flashes upon activation of a supervisory device (such as tamper switch)
on Zone 4.
System Trouble - Yellow LED that flashes for any trouble condition, including those associated with optional boards.
Circuit Trouble - Yellow LED that flashes for trouble conditions on output circuits.
Alarm Silenced - Yellow LED that illuminates steadily when the ALARM SILENCE switch has been
pushed after an alarm.
Power Trouble - Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
The following LEDs are located below the main panel and are visible only when the panel door is open.
Battery Fail (
detected.
Ground Fault (
condition.
Micro Fail - Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor failure.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
) - Yellow LED that illuminates steadily on motherboard when battery is low or not
BATT
) - Yellow LED that illuminates steadily on motherboard during a ground fault
EARTH
33
Page 34
3. System Operation Control Switches
Control Switches
TONE
SILENCE
ALARM
SILENCE
ALARM
AC TIVATE
SYSTEM
RESET
MS44-panel2.cdr
Figure 22 Control Panel Switches
Tone Silence - Pressing this switch acknowledges alarms, troubles and supervisories. The panel has
alarm and trouble resound with LED flash of new conditions. The flashing trouble LED(s) illuminate steadily and the piezo turns off. A second trouble will resound the piezo. Trouble conditions are self­restoring. Alarms latch and require pressing SYSTEM RESET to clear. Unless the unit is set for non­latching supervisory service, supervisories latch and require pressing SYSTEM RESET to clear. The piezo has three tones for different conditions (see "Piezo" on page 35).
Alarm Silence - Pressing this switch acknowledges for alarms and supervisories. This switch will silence the local piezo, change any flashing alarm LEDs to steady, and turn off the notification circuits. The “Alarm Silenced” LED will illuminate. Alarm silence is a latching function and requires pressing SYSTEM RESET to clear.
If Silence Inhibit has been selected (SW1, DIP switch #4 set to “ON”), the Alarm Silence will not function until 60
Note:
seconds after the initiation of the alarm.
Alarm Activate - This switch may be used to activate Notification Appliance Circuits (NACs). It also activates the System Alarm Relay. This is a latching function. Pressing ALARM SILENCE silences the NACs and System Alarm Relay, and lights the Alarm Silenced LED. Pressing SYSTEM RESET returns the system to normal.
System Reset - This switch breaks power to all initiating circuits, four-wire smoke detector power and optional boards and will clear any activated output circuits. If any alarm or trouble still exists after reset, they will reactivate the panel. Holding SYSTEM RESET down will perform a LAMP TEST function and will activate the piezo sounder.
Zone Status LEDs
The alarm and/or trouble LED(s) will flash until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED(s) will illuminate steadily.
ZONE 1
Alarm LED
ZONE 2
Trouble LED
ZONE 3
ZONE 4
MS44-panel3.cdr
34
Figure 23 Zone Status LEDs
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 35
Piezo 3. System Operation
Piezo
The piezo (local buzzer) generates different tone patterns for different event conditions:
Alarm - Generates a steady tone, no pulse.
Trouble - Pulses one second on, one second off. Repeats 30 pulses per minute.
Supervisory - Pulses one-half second on, one-half second off. Repeats 60 pulses per minute.
Supervisory Service
Zone 4 is programmable for monitoring supervisory devices (such as valve tamper switches) by setting SW1 DIP switch 3 to “ON” (see "Setting Mode of Operation" on page 31). A short circuit on this zone (activation of a N.O. contact) will cause the supervisory LED and the zone 4 yellow LED to flash. The piezo sounder will generate a unique sound. Pressing TONE SILENCE will silence the piezo and cause the supervisory LED to illuminate steadily, but the Zone 4 Trouble LED will continue to flash. Supervisory signals latch and require SYSTEM RESET to clear. The ALARM SILENCE switch will silence the piezo, cause the supervisory LED to illuminate steadily and turn off the Supervisory Notification Circuit. An open circuit on Zone 4 will be reported as a zone trouble.
The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation; latching
Note:
operation is the default setting. Canadian regulations require latching operation; for programming instructions, See “Sprinkler Supervisory Tracking” on page 36.
Zone Disable
If a zone has been disabled, an alarm that occurs on that zone will flash the red zone LED, but not the piezo or any output circuit. If both power sources are removed from the system, all zones will be re-enabled upon
restoration of power. Disable status will be lost.
The Zone Disable routine makes use of the four panel switches as follows: I
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press
3. The Zone 1 Alarm LED will flash.
4. To disable Zone 1, press the SYSTEM RESET switch. The Zone 1 yellow LED will light to show
Note:
5. To select the next zone, press the ALARM SILENCE switch.
6. To select the previous zone, press the ALARM ACTIVATE switch.
7. When disable selections are complete, release the TONE SILENCE switch.
If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash.
TONE
SILENCE
(in sequence) the ALARM SILENCE switch, the ALARM ACTIVATE switch, and then the SYSTEM RESET switch.
Press
&
Hold
that the zone is disabled.
The SYSTEM RESET switch toggles disable status for the selected zone.
ALARM
SILENCE
Press ---> Press ---> Press
ALARM
ACTIVATE
SYSTEM
RESET
MS-4424 Instruction Manual PN 15153:G1 10/22/02
35
Page 36
3. System Operation Last Event Recall
Last Event Recall
Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes use of the four panel switches as follows:
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press (in sequence) the SYSTEM RESET switch, the ALARM ACTIVATE switch, and then the ALARM SILENCE switch.
3. LEDs will light to indicate the last event recorded in the panel’s buffer.
4. Release the TONE SILENCE switch to return to normal operation.
To clear the Last Event buffer, press SYSTEM RESET twice.
Non-Silenceable Service
Initiating Zone #1 can be programmed as non-silenceable by following these steps:
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then the ALARM ACTIVATE switch, and finally the ALARM SILENCE switch again.
3. Release the TONE SILENCE switch.
If both primary and secondary power sources are removed from the system, these settings will be lost. When
Note:
power is restored, Initiating Zone #1 will default to silenceable operation.
Sprinkler Supervisory Tracking
The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation; latching operation is the default setting. Canadian regulations require latching operation.
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch, then the ALARM ACTIVATE switch, and finally the ALARM ACTIVATE switch again.
3. Release the TONE SILENCE switch.
If both primary and secondary power sources are removed from the system, this setting will be lost. When
Note:
power is restored, supervisory will default to latching operation.
System Events
Standby Condition
Green LED (AC power on) will be illuminated. All other LEDs (trouble and alarm) are off.
System Trouble Condition
Interruption of any of the electrically supervised circuits will illuminate the System Trouble LED. The Trouble Relay Contacts will transfer. The piezo (local buzzer) will sound one second on, one second off, and repeating until silenced. Silence the piezo by pressing the TONE SILENCE switch. The panel will remain in the trouble state until the trouble condition has been cleared and the panel reset.
36
Alarm Condition
Upon activation of an initiating device, a red alarm LED will illuminate for that zone. In add ition, the Alarm Relay will activate, the piezo will sound, and Notification Appliance Circuit(s) will activate. (See “Output Circuits” on page 22 for details).
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 37
System Events 3. System Operation
Brownout Condition
The total power being provided to the system’s power supply should not exceed the current draw during fully loaded panel operation. Brownout circuitry annunciates degradation of the incoming AC voltage supply. A brownout condition is annunciated when the AC power decreases. When the brownout threshold is reached, the system reacts as if AC power is totally lost:
• Battery backup begins supplying power to operate the control panel
• General Trouble Relay contact transfers
• Green AC Power LED turns off
• Yellow System Trouble LED illuminates
• The piezo will sound one second on, one second off, and repeat until the Trouble is cleared.
When the AC voltage returns or increases above the brownout threshold, the green AC Power LED will illuminate. The power supply circuitry will return to primary power functions and begin to recharge the backup battery supply.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
37
Page 38
3. System Operation System Events
Notes
38
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 39
Appendix A: Secondary Power Calculations
Standby Battery Requirements
The Standby Battery Current obtained in the table below represents the amount of current that must be supplied by the secondary power source (batteries) to sustain control panel operation for one hour.
The control panel will support the installation of one or two optional modules, including two of the same type of
Note:
module. Only one 4XLMF can be included in this count.
Device Type
Main Circuit Board 1 X 0.088 =
4XZMF ZoneRelay Module
4XTMF Transmitter
•Reverse Polarity Alarm output
•Reverse Polarity Trouble output
RZA-4XF/4XLMF Remote Annunciator
4XMMF Meter Module
2-wire Detector Heads
4-wire Detector Heads
End-of-line Relays
Current Draw from
TB2 (nonalarm)
Module
2
3
# of
Devices
[ ] X 0.008 =
[ ] X 0.011 =
[ ] X 0.005 =
[ ] X 0.005 =
[ ]
(1 max)
[ ] X 0.001 =
[ ] X
[ ] X
[ ] X [ ] =
[ ] X [ ] =
Current
(amps)
X 0.019 =
1
[ ]
1
[ ]
Total Current
(amps)
0.088
=
=
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Standby Battery Current = amps
1. Refer to the Device Compatibility Document for smoke detector standby current.
2. Must use compatible listed Power Supervision Relay.
3. The total standby current must include both the resettable (TB1 - +24VR terminals) and nonresettable (TB2 - +24VNR terminals) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified.
Table 2 Standby Battery Current
39
Page 40
Appendix A: Secondary Power Calculations Calculating the Battery Capacity
Calculating the Battery Capacity
Use this table to determine the battery capacity required by the system.
Standby Battery Current (from Table 2) [ ] amps X
Required Standby Time in Hours
(typically 24 [ ] hrs
Enter:
0.25 for 5 minutes in alarm, or
0.50 for 10 minutes in alarm
1
or 602 hours)
Standby
=
Amp Hours
3
Alarm Amp Hours
Total Standby and Alarm Load +
Multiply by derating factor X 1.2
Battery size required in AH =
1. NFPA 72 Central Station and Local and Proprietary Fire Alarm Systems require 24 hours of standby time.
2. NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby time.
3. Alarm AH assumes a maximum system draw of 3 amps in alarm for 5 minutes (0.25 AH) or for 10 minutes (0.5AH).
Table 3 Amp Hour Calculations
The battery charger in this panel will charge a maximum of 18 AH of batteries within 48 hours (7 AH minimum). Batteries larger than 12 AH will require a UL-listed battery cabinet (e.g. Fire•Lite BB-17F).
Select a battery with an equal or greater AH rating than the value obtained in the table above.
Batteries must be lead-acid type.
Note:
40
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 41
Appendix B: NFPA Standard-Specific Requirements
Minimum System Requirements
The control panel has been designed for use in commercial, industrial, and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this appendix. The minimum system components required for compliance with the appropriate NFPA standard are listed below.
Fire Alarm Control Panel. Contains the main control board, cabinet (backbox and door), main supply transformer and power supply.
Batteries. Refer to "Appendix A: Secondary Power Calculations" on page 39
Initiating Devices. Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances. Connected to one of the control panel's Notification Appliance Circuits.
Additional Requirements
The following additional equipment is needed for compliance with the NFPA standards listed below. The relay contacts of this control panel may be used to trip any dialer that is UL listed for Central St ation/Remote Station services. The illustrations in this appendix provide examples of possible system configurations.
Applications which require the the NOTI-FIRE 911AC or the Potter EFT-C are not FM approved.
Note:
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)
NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter (DACT) connected to a compatible listed Central Station DACR or Protected Premises Receiving Unit. See "Digital Alarm Communicator/Transmitter - Noti-Fire 911AC" on page 42 for installation instructions for this unit.
411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central Station DACR or Protected Premises Receiving Unit. See "Universal Digital Alarm Communicator
- 411UDAC" on page 43 for installation instructions for this unit.
NFPA 72 - Auxiliary Fire Alarm System
4XTMF Transmitter Module for connection to a compatible listed Local Energy Municipal Box. See "Local Energy Municipal Box" on page 44 for installation instructions for this unit.
NFPA 72 - Remote Station Fire Alarm System
Fire•Lite RS82-9 Remote Station Receiver connected to a 4XTMF Transmitter Module. See "Remote Station Receiver - RS82-9" on page 45 for installation instructions for this unit.
NOTI-FIRE 911AC DACT connected to a compatible listed Central Station DACR. See "Digital Alarm Communicator/Transmitter - Noti-Fire 911AC" on page 42 for installation instructions for this unit
411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central Station DACR. See "Universal Digital Alarm Communicator - 411UDAC" on page 43 for installation instructions for this unit.
NFPA 72 - Proprietary Fire Alarm System
Potter EFT-C McCulloh Transmitter. See "Potter EFT-C McCulloh Transmitter" on page 46 for installation instructions for this unit.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
41
Page 42
Appendix B: NFPA Standard-Specific Requirements Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
This application is not FM approved
Note:
Using the Noti-Fire 911AC DACT for connection to a Central Station Receiver or Protected Premises Receiving Unit.
• AC Wiring for DACT/FACP must be connected to the same circuit.
• If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less than 20 feet (6.1 meters) in length in the same room.
• For additional information refer to the Noti-Fire 911AC Instruction manual.
See Below for Terminal Connections
To Central Station
To AC Power
MS-4424 Control Panel
IN #1
IN #2
IN #3
IN #4
B+ A+ A– B–
TB4
TB3
B+ A+ A– B–
B+ A+ A– B–
B+ A+ A– B–
4XZMF Zone
JP1
GEN
SUPV 1
ALM1
GEN ALM2
STD DACT
Relay Module
SUPR 2
J2
LATCH
TB1
DISABL E
OPT1
Jumper
Place jumper over pins as shown when employing a DACT. This directs the control panel to transmit all trouble conditions except AC LOSS.
Figure 24 DACT Connections
+
PS 1270
12Volt
7AH Battery
TB3
To Common Terminal of Relay
MS44-911ac.cdr
42
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 43
Universal Digital Alarm Communicator - 411UDAC Appendix B: NFPA Standard-Specific Requirements
Universal Digital Alarm Communicator - 411UDAC
The following figure illustrates an example of Central Station/Remote Station Receiver or Protected Premises Receiving Unit reporting using a 411UDAC. The relay contacts of the MS-4424 may be used to trip any dialer listed for Central Station/Remote Station services. For additional information refer to the Instruction Manual for the 411UDAC.
• All connections between the control panel and the 411UDAC must be in conduit, less than 20 feet (6.1 meters) in length in the same room.
• Any zone of the 411UDAC can be wired to function as alarm, trouble or supervisory; the unit must be programmed accordingly. In this example, Zone 1 is wired to the control panel’s alarm relay, Zone2 is wired to the control panel’s trouble relay, and Zone 3 is wired to the optional module’s supervisory relay.
• AC power is supplied directly to the 411UDAC, not through the control panel. AC wiring for both the 411UDAC and the control panel must be connected to the same AC branch circuit.
• End-of-Line Resistors must terminate all circuits. In this example, Zone 4 is unused and is terminated at the board.
• When employing a DACT, place the JP1 jumper, on the control panel, as shown below. This directs the panel to transmit all trouble conditions except AC LOSS. The DACT must be configured to transmit AC power loss to the central station.
Zone 1 Zone 2 Zone 3
Alarm
Secondary Phone Line Primary Phone Line
Trouble
Jumper
Control Panel
Figure 25 411UDAC Connections
Supervisory
4XZMF Zone Relay Module
RELAY 1 NO NC C
RELAY 2 NO NC C
TB1
NAC B+ B-
+12V PWR + -
ZONE 1 B+ B-
TB4
411 UDAC
ZONE 2 B+ B-
ZONE 3 B+ A+ A- B-
ZONE 4 B+ B-
TB2
PH1
PH2
Modular Cable P/N MCBL-6
MS44-411.cdr
MS-4424 Instruction Manual PN 15153:G1 10/22/02
43
Page 44
Appendix B: NFPA Standard-Specific Requirements Local Energy Municipal Box
Local Energy Municipal Box
Using the 4XTMF Transmitter Module for connection to a Local Energy Municipal Box.
• The Municipal Box circuit supervises for ground faults and opens (i.e. missing wire) but not for direct short between two wires. It is not a power-limited circuit.
• This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.
• Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.
FIRE
TBL
Municipal Box Circuit
+
TB1
Local Energy
Municipal Box
J1
J2
4XTMF Transmitter Module (activated polarities shown)
Figure 26 Municipal Box Connection
MS44-4xtmfmb.cdr
44
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 45
Remote Station Receiver - RS82-9 Appendix B: NFPA Standard-Specific Requirements
Remote Station Receiver - RS82-9
Using the 4XTMF Transmitter Module for connection to a Fire•Lite RS82-9 Remote Station Receiver.
• Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings.
• All connections are power-limited and supervised with the exception of the reverse polarity loop.
• Supervision of the loop is the responsibility of the receiver.
Fire•Lite RS82-9 Remote Station Receiver
4XTMF Transmitter Module
Figure 27 RS82-9 Connections
+ –
+ –
Remote
Alarm
TB1
Remote Trouble
TBL
J1
J2
MS44-rs82.cdr
MS-4424 Instruction Manual PN 15153:G1 10/22/02
45
Page 46
Appendix B: NFPA Standard-Specific Requirements Potter EFT-C McCulloh Transmitter
Potter EFT-C McCulloh Transmitter
This application is not FM approved.
Note:
• Connections between control panel and the transmitter are supervised by the transmitter.
• Use transformer model ULT STK. NO. 1000391 (listed, Class 2, 12 V, 10 VA.). See Potter Electric Signal Company Bulletin # 748.
• Form-C Trouble relay which will automatically activate on any trouble condition.
• Form-C Alarm relay programmed to activate on General Alarm.
TB3
Potter EFT-C
MS-4424 Terminal Blocks
IN #1
B+ A+ A– B–
IN #2
B+ A+ A– B–
IN #3
B+ A+ A– B–
IN #4
B+ A+ A– B–
TB4
Figure 28 Potter EFT-C Connections
MS44-potter.cdr
46
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 47
Testi ng
Appendix C: Testing & Maintenance
Inspection
Perform the following prior to applying power to the system.
• Check the actual wiring hookup with the wiring diagrams.
• Insure that no pieces of wire have fallen into the circuitry.
• Check for missing or damaged parts.
Alarm Test
An initial alarm test should be conducted following installation to determine that all parts of the system are functioning properly.
To perform an alarm test on the panel, initiate an alarm condition by blowing smoke into a smoke detector. This should cause the first zone alarm condition.
• The alarm relay will activate.
• The red zone alarm LED will be illuminated.
• Notification Appliance Circuits and the local piezo will start sounding.
Maintenance
A regular schedule of inspection, testing, and maintenance is vital to insure proper and reliable operation of the control panel. The procedures should be performed as required by the local authority having jurisdiction. Refer to NFPA for further details.
Troubleshooting
A troubleshooting table is included on the following page which provides for symptoms, problems and their solutions.
MS-4424 Instruction Manual PN 15153:G1 10/22/02
47
Page 48
Appendix C: Testing & Maintenance Troubleshooting
Table 4 Troubleshooting Table
Symptom Problem Solution
1. Check TB2 for proper connections.
2. Remove all field wiring and install dummy ELR at output circuit. Check for supervisory voltage across it, (Normal -2.3 V), if problem persists, replace circuit board.
3. Removed dummy ELR, reconnect field wiring and measure voltage across output; (trouble-5V, short 0V).
4. Check for ELR at last device.
5. Check field wiring.
1. Check TB4 for proper connections.
2. Remove field wiring for zone in trouble and install dummy ELR (4.7K). If problem persists, replace circuit board.
3. Check for ELR at last device.
4. Check field wiring.
1. Check installation manual.
1. Check battery connections.
1. Remove batteries, check voltage across charger output (17 to 19V), otherwise replace circuit board.
2. Reconnect batteries, measure battery voltage at battery terminals. If voltage is less than 85% of rated voltage, allow them to charge for 48 hours.
3. If problem persists, replace batteries.
1. Remove field wiring from main panel and optional module(s) (if installed). Install dummy ELR (4.7K).
2. Remove both battery leads.
3. If trouble clears, connect one circuit at the time to pin point the problem.
4. If trouble doesn’t clear, replace circuit board.
1. Move Municipal Box disconnect switch SW1 up.
1. Install optional module(s) or replace jumper if module(s) is not used.
1. Install dummy load if Municipal Box option isn’t used.
2. Check Municipal Box wiring.
1. Remove field wiring and install ELR. If trouble clears, look for faulty or incorrectly wired devices.
1. Cut associated jumper OPT1 or OPT2.
1. Make sure module is properly installed.
2. Move disable switch SW1 on 4XZMF to the left.
1. Make sure that 4XLMF module is installed on J8.
2. Check field wiring.
1. Replace circuit board.
1. Press system reset.
1. Check incoming power (TB5).
1. Replace circuit board.
1. Replace circuit board.
AC Power LED ON
AC Power LED OFF
Circuit trouble LED ON
Any of the right column yellow LEDs flashing
Notification appliance circuit trouble
Initiating zone open circuit trouble
Any of the right
System trouble LED ON
column yellow LEDs steady ON
Zone disable
Missing or Disconnected
Battery trouble Batt yellow LED ON
Power trouble
Low or damaged battery
LED ON
Ground fault trouble Earth yellow LED ON
Yellow LED on 4XTMF ON
4XTMF
OPT1, OPT2 jumper cut
Municipal Box open circuit
Any of the right column red LEDs ON Disconnecting Municipal Box switch ON 4XTMF does not create a trouble
Short on initiating circuit wiring
Jumper for optional modules isn’t cut
4XZMF: associated LED doesn’t activate for alarm, trouble or
Optional module trouble supervisory conditions RZA-4XF piezo doesn’t sound for alarm, trouble or supervisory
4XLMF conditions Micro Fail yellow LED ON Microprocessor damaged
All RZA-4XF LEDs stay ON
System trouble LED ON
Power wasn’t removed prior to
installation
Loss of main power
Damaged circuit breaker Micro Fail yellow LED ON Microprocessor damaged
48
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 49
Numerics
110/120 VAC 220/240 VAC 411UDAC 4XLMF LED Interface Module 4XMMF Meter Module 4XTMF Transmitter Module 4XZMF Zone Relay Module 911AC DACT
13 13
41, 43
12, 17
10, 26, 41, 44, 45
11, 23, 26
41, 42
A
AC branch circuit AC power acknowledge additional equipment alarm alarm relay alarm signals ALARM SILENCE switch Alarm Verification allowable resistance ammeter annunciator wiring authority having jurisdiction
33, 43
33, 43
12
43
34
41
25, 47
31
31
31
21
11
47
B
backbox backbox rail Batteries battery
BB-17F black wire Brownout circuitry buffer
15
15, 16
18, 41
19
cable capacity charger interconnect wire
40
40
13, 40
19
37
36
18, 19
C
Canadian Central Station charging current circuit
circuit board circuit breaker conductors conduit contact device Control Panel
31, 35, 36
41, 42, 43
17
Remote Alarm Remote Trouble reverse polarity
15, 16
18, 32
15
15, 43
31
9
28
28
10
11, 26
Index
current current draw
D
DC power connections detector, four-wire smoke detectors, type of devices, supplementary dialer DIP switch DIP switch functions direct short Disable NACs disable switch disabled zone Disconnect LED Disconnect Switch dry contacts dummy load dummy load resistor duplicate modules
E
earth fault ELR End-of-Line Resistor event exterior dimensions external battery cabinet external devices
F
Fire Alarm Control Panel FM approved Form-C Form-C contacts four-wire smoke detector
G
General Alarm ground fault
I
initial alarm test initiating circuits initiating device Initiating Device Circuit initiating devices Initiating Zone 1 inspection interconnect wire, battery Interface Module interruption of circuits
Index
13
37
25
34
20
25
41, 43
20, 22, 23, 31, 35
10
44
31 29
35
28
28
29
22
20
26
33
21, 22
13, 43
33
16
13
13
41
41, 42, 46
46
11, 13
13, 34
23, 46
33, 44
47
34
36
31, 36
41
36
47
32
11
36
MS-4424 Instruction Manual PN 15153:G1 10/22/02
49
Page 50
Index
J
J1 connector J2 Connector J3 Connector J9 Connector JP1 jumper jumper
LATCH
TBL jumper configurations jumpers, SUPV1/SUPV2
15, 16
17 17 19
43
23, 26, 27
29
28
22
31
K
keyhole knockouts
15
15, 19
L
label
Protected Premises Unit
terminal identification LAMP TEST function
34, 35
latch LATCH jumper
29
latched latching operation LED
Disconnect
System Trouble LED Interface Module LEDs
Alarm, Trouble and Supervisory Local Energy Municipal Box loop resistance lower position
29
35, 36
28
28
44
26, 27
29
26, 27
34
11, 26
10
M
main breaker panel maintenance Manual Pull Stations Maximum Battery Capacity Maximum Charging Circuit maximum resistance Meter Module microprocessor minimum clearance module connectors motherboard mounting hole locations mounting holes Municipal Box
18
47
20
13 13
21
12, 17
33
15
26
33
16
15
28, 44
N
22, 23
NACs National Electrical Code, Article 760 National Fire Protection Association
33
18
41
negative NFPA NFPA standards non-latching nonpower-limited nonresettable power non-silenceable
non-silenceable service Notification Appliance Circuit Notification Appliances
19
47
41
29, 34
19, 29
Initiating Zone 1
21, 25
36
22
31, 34, 36, 47
41
O
44
opens operating mode operating voltage optional boards optional modules Out of Service output circuits overcurrent protection
31
21
34
10
32
34
18
P
panel functions paper labels
31, 34, 35, 36, 37, 47
piezo piezo tones polarity polarity reversal circuit polarized devices positive Potter EFT-C McCulloh Transmitter Potter Electric Signal Company power connection Power Supervision Relay power-limited power-limited circuits power-limited power supply previous panel status primary power programmed Protected Premises Receiving Unit
19, 20, 32
22
11
34
45
20, 22
19
46
18
21
19, 22, 45
29
25
36
18, 32
43
R
27
rail rail, backbox red wire regulated power relay contacts Relay, System Alarm Remote Alarm circuit Remote Annunciator Remote Station Remote Station Service Remote Trouble circuit resettable power
15, 16
19
25
43
31, 34
28
11
41, 43
10
28
21, 25
41
41, 42, 43
50
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 51
Index
resistance, allowable
43
resistor
resound
reverse polarity
reverse polarity circuit
reverse polarity loop
ripple voltage
RS82-9 Remote Station Receiver
RZA-4XF Remote Annunciator
34
21
28
10
45
13
S
Secondary Power
secondary power source
self-restoring
separate transmission
short circuit
Silence Inhibit
silence switch
Slide-in paper labels
sprinkler
sprinkler supervisory
Standby Battery Current
stand-off
Style B (Class B)
Style D (Class A)
Style Y
Style Z
sulfuric acid
supervised
supervisory
Supervisory on Zone 4
supplementary devices
switch
System Alarm Relay
System Trouble LED
35, 36
16, 26, 27
22
22
circuit device switch
ALARM SILENCE disable supervisory/tamper
32
39
34
44
35
31, 34
11
11
44
39
20
20
32
22
43
20, 23, 31
33, 35 31
31 25
31
29
31
31, 34
28
41, 45
11, 23
Transmitter Module trim ring trouble
troubleshooting
16
43
condition
25
relay sounder
33, 36, 44, 46
11
47
U
UL listed unused circuits upper position
41
22
26
V
verification period visual inspection
17
voltage voltage drop voltmeter
12
31
32
13
W
Walk Test watchdog timer Waterflow Waterflow on Zone 3 wire, primary power wires, transformer
31, 33
33
20
15
Z
43
zone Zone Relay Module
10, 26, 44, 45
31
18
11, 26
T
tag, “Out of Service”
tamper switch
TBL Jumper
terminal identification label
testing
timer
timer, watchdog
tone patterns
tones, piezo
tracking operation
transformer
transformer wires
transmitter
MS-4424 Instruction Manual PN 15153:G1 10/22/02
28
47
31
35
34
46
46
32
20, 31
26, 27
33
35, 36
15, 16
51
Page 52
52
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 53
MS-4424 Instruction Manual PN 15153:G1 10/22/02
53
Page 54
54
MS-4424 Instruction Manual PN 15153:G1 10/22/02
Page 55
Limited Warranty
The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of original purchase by the manufacturer's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired, or serviced by anyone other than the manufacturer or its authorized distributors, or if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its products. The manufacturer does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
Page 56
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...