While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke detectors may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power.
cated, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F
condensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.
Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
1.3: Controls and Indicators ...............................................................................................................................12
2.4: Main Circuit Board Installation...................................................................................................................23
3.2: Programmable Features and Options ..........................................................................................................35
3.3: Entering Program Mode..............................................................................................................................36
3.4.3: Programming Example .....................................................................................................................37
3.5: Program Features and Options ....................................................................................................................41
3.5.1: Program Features ..............................................................................................................................41
4.1: Switch Functions in Normal Mode .............................................................................................................47
4.2: Status LEDs.................................................................................................................................................48
4.3.1: Fire Alarm Response.........................................................................................................................50
4.3.2: Fire Alarm Restoral...........................................................................................................................50
4.3.3: System Supervisory Condition Response .........................................................................................50
4.3.4: System Supervisory Restoral Response............................................................................................51
5.2: Last Event/History Mode ............................................................................................................................53
5.3: Lamp Test ....................................................................................................................................................54
CHAPTER 6: Power Supply Calculations..............................................................................................................55
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems (Automatic, Manual, Waterflow
and Sprinkler Supervisory), Auxiliary Fire Alarm Systems (Automatic, Manual and Waterflow),
Remote Station Fire Alarm Systems (Automatic, Manual and Waterflow) and Proprietary Fire Alarm
Systems (Automatic, Manual and Waterflow).
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Inidicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Articla 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
FCPS-24F(E) Field Charger/Power SupplyDocument #50079
LDM Series Lamp Driver ModulesDocument #50055
LED-10 AnnunciatorDocument #50361
ACM-8RF Annunciator Control Relay ModuleDocument #50362
411 Digital Alarm Communicator/TransmitterDocument #50921
411UD Digital Alarm Communicator/Transmitter Document #50759
Document #51127 Rev. C 11/7/00 P/N 51127:C
7
MS-2410B Main Circuit Board
24 V
24 V
NONR ESET
RESET
+ - + -
TB2
J3
PRIMARY
TRANSFO RMER
CONNECTOR
CAUTION!
HIGH VOLTAGE
J2
OPTIONAL
TRANSFO RMER
CONNECTOR
BELL 1
+ - + -
TB3
24 V
RESET
NONRES ET
+ - + -
TB2
J3
J2
NC NO
TROUBLE
RELAY
SUPV
RELAY
NO
C
NC
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZON E 5
NO
ZO NE 6 ZON E 7 ZO NE 8 ZON E 9 ZO NE 10
BELL 2
REMOTE TRBL UNIT
AC TRBL BUZZ
GND
TB5
ALARM
RELAY
C
TB4
TB6
SUPV
ALARM
24 V
BELL 1
BELL 2
REMOTE TRBL UNIT
AC TRBL BUZZ
GND
+ - + -
TB3
TB5
TB1
CB1
EARTH
HOT
NEUT
TROUBLE
RELAY
RELAY
NC NO
RELAY
CCC
ZONE 1 ZON E 2 Z ONE 3 ZO NE 4 ZO NE 5
NO
NCNCNC
C
NO
+ - + - + - + - + - + - + - + - + - + -
TB4
TB6
ZONE 6 ZONE 7 ZONE 8 ZO NE 9 ZO NE 10
J5
U3
LED-10IM
MODULE
U6
TB7
SECURITY KEY
J4
TB7
J5
LED-10IM
MODULE
J4
SECURITY KEY
J6
J6
MEMBRANE SW CONNECTOR
J1
BAT T - +
TON E/CITY BOX
OPTIONS
J8
J7
JP1
OPTION
SUP ERVIS ION
TO NE/CIT Y BO X
J7
OPTIONS
TB1
H
N
O
E
T
U
T
AC Pow er
J1
JP1
BATT - +
E
A
R
T
H
J8
MEMBRANE SW CO NNECTOR
OPTION
SUPERVISION
MS-2410B Terminals and Connectors
2410layo.cdr
8
Document #51127 Rev.C 11/7/00 P/N 51127:C
Product Description
CHAPTER 1Product Description
The MS-2410B is a 10-zone FACP (Fire Alarm Control Panel), which uses conventional input devices. The panel
accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other
normally-open contact devices. Outputs include two Notification Appliance Circuits (NACs), three standard Form-C
relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional
remote relay modules. The FACP is field programmable via the panel keypad. It also supervises all wiring, AC
voltage and battery level. The MS-2410BE offers the same features as the MS-2410B but allows connection to 220/
240 VAC input.
1.1Product Features
• 10 Class B Initiating Device Circuits (IDCs)
✓All zones accept smoke detectors and any normally open contact device
✓Zones 1 - 8 configured as general alarm zones
✓Zones 9 - 10 can be configured as smoke zones or supervisory alarm zones
• Two Class B Notification Appliance Circuits (NACs)
• Form-C Alarm Relay
• Form-C Trouble Relay
• Form-C Supervisory Relay
• 3.6 amps of system power expandable to 6.6 amps
• RTB Remote Trouble Buzzer
• Remote Relay Option Module (ACM-8RF) providing one 5.0 amp relay per zone
• Dress Panel coverplate (DP-2410B)
• Built-in keypad for panel control and programming
• 24 volt operation
• Trouble Reminder
• Alarm Verification (zones 1 through 3 only)
• Interfaces with Fire•Lite annunciators (requires
LED-10IM Option Module)
✓LED-10 Series Remote Annunciators provide
red alarm and yellow trouble LEDs
✓LDM-32F Graphic Annunciator Driver
✓AFM Series LED Annunciators
• Small backbox size 16.9” (42.9 cm) X 14.5” (36.8
cm) X 4.5” (11.43 cm)
• Silence Inhibit Notification Appliance Circuits
• Auto-Silence Notification Appliance Circuits
• Fuseless design
• Low AC voltage sense
• Silent or audible Walktest
FIGURE 1-1:
DP-2410B
DP2410b.cdr
Note: Unless otherwise specified, the term MS-2410B shall be used in this manual to refer to both the MS-2410B and
the MS-2410BE Fire Alarm Control Panels.
Document #51127 Rev. C 11/7/00 P/N 51127:C
9
Product Features
24 VDC
Power
Keypad and
LEDs
Standard
Trans former
Notification
Appliance
Circuits
Remote
Trouble
Buzzer
AT
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Trouble
Supervisory
Signal Silence
NAC Fault
Ground Fault
Battery Trouble
Zone Disabled
Annc. Trouble
Relays
10 Input
Zones
Security Key
LED-10IM
Interface
Module
Connector
Reverse
Pol arity
Module
Optional
Trans former
Note: Transformers
are mounted to the
backbox, under the
main circuit board.
Four-wire Smoke Detector Power - TB2 Terminals 3(-) & 4(+)
Maximum ripple voltage: 10 mV
Up to 300 mA is available for powering 4-wire smoke detectors
Recommended maximum Standby current is 50 mA
Operating Voltage nominal 24 volts
RMS
2
1
Refer to Fire•Lite Device Compatibility Document for compatible listed device
1. Total current for nonresettable power, four-wire smoke power, and two Notification Appliance Circuits
amps.
Total system current in excess of 3.6 amps requires the XRM-24 Transformer (XRM-24E for 220/240 VAC applications)
and 12 Amp Hour or 18 Amp Hour batteries.
2. For power supply and battery calculations, refer to “Power Supply Calculations” on page 55.
Document #51127 Rev. C 11/7/00 P/N 51127:C
must not exceed 6.0
11
Controls and Indicators
Nonresettable 24 VDC Power - TB2 Terminals 1(-) & 2(+)
Maximum ripple voltage: 10 mV
Total DC current available from this output is up to 500 mA
Operating Voltage nominal 24 volts
RMS
1
Recommended maximum Standby current is 150 mA
Refer to Fire•Lite Device Compatibility Chart for compatible listed devices
Remote Trouble Buzzer - TB5
Operating Voltage: nominal 24 VDC
DC current when RTB Remote Trouble Buzzer is in normal standby (AC Power LED on alone) is 20 mA.
Maximum DC current from this output when RTB Remote Trouble Buzzer is active is 50 mA.
1.3Controls and Indicators
Front Panel Membrane Keys in Normal Mode
Acknowledge
Signal Silence
Drill
Disable/Enable
Reset/Lamp Test
Note that programming keys function slide-in-labels and
option/feature slide-in labels are also provided and should
be inserted while in Program Mode to view the altered key
functions. Refer to Figure 4-1, “LED Indicators and Keypad,” on page 47 and “Slide-in Labels” on page 61.
LEDs
AC Power - green LED
Alarm - red LED
Trouble - yellow LED
Supervisory - yellow LED
Signal Silence - yellow LED
NAC Fault - yellow LED
Ground Fault - yellow LED
Battery Trouble - yellow LED
Zone Disabled - yellow LED
Annunciator Trouble - yellow LED
Zone Fire Alarm - Zones 1 through 10 - red LEDs
Zone Supervisory Alarm - Zones 9 and 10 only - red LEDs
Zone Trouble - Zones 1 through 10 - yellow LEDs
AT
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
FIGURE 1-3:
Trouble
Supervisory
Signal Silence
NAC Fault
Ground Fault
Battery Trouble
Zone Disabled
Annunc. Trouble
LEDs and Keypad
2410disp.cdr
2410DISP
Note: A blank slide-in label is provided for circuits 1 through 10 which may be customized by the customer. In
addition, slide-in-labels listing the programming features/options and programming key functions are provided and
should be inserted while in Program Mode.
1. Total current for nonresettable power, four-wire smoke power, and two Notification Appliance Circuits
amps.
Total system current in excess of 3.6 amps requires the XRM-24 Transformer (XRM-24E for 220/240 VAC applica-
tions) and 12 Amp Hour or 18 Amp Hour batteries.
12
Document #51127 Rev.C 11/7/00 P/N 51127:C
must not exceed 6.0
Circuits
Local Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions:
• Alarm - on steady
• Alarm Verification - pulse 1 second On and 1 second Off
• Trouble - pulse 1 second On and 1 second Off
• Supervisory - pulse ½ second On and ½ second OFF
1.4Circuits
Input Circuits
Ten input circuits provide Class B configuration. Input circuits 1 through 10 may be used as standard fire alarm
control panel zones and circuits 9 and 10 may be used as supervisory alarm zones. All ten Initiating Device Circuits accept normally-open contact devices and two-wire smoke detectors.
Output Circuits
• 24 Volt Resettable Power Output 300 mA
• 24 Volt Nonresettable Power Output 500 mA
• 24 Volt Remote Trouble Buzzer Output 50 mA maximum
• 24 Volt Battery Charger (up to 18 AH batteries)
• EIA-485 Port (interfaces to LED-10 Series Annunciators, AFM Series and LDM Graphic Series Annunciators
and ACM-8RF Remote Relay Module)
Notification Appliance Circuits
Two Notification Appliance Circuits Class B.
Relays
Three dry Form-C relays for system alarm, system trouble and supervisory are provided standard. Contacts are
rated 2.0 amps @ 30 VDC (resistive) and 2.0 amps @ 30 VAC (resistive).
EIA-485 Port (Requires LED-10IM Module)
EIA-485 compatible port on the LED-10IM option module supports up to 10 different device addresses which can
consist of LED-10 Series Remote Annunciators, ACM-8RF Relay Modules, AFM Series Annunciators or LDM
Graphic Series Annunciators or any combination of the four modules.
Battery Charger
Battery Charger will charge up to 18 AH batteries. The MS-2410B cabinet holds a maximum of 12 AH batteries.
The Fire•Lite BB-17F is required to hold 18 AH batteries. The charger is rated for 800 mA maximum current.
1.5Components
Main Circuit Board
The main circuit board contains the system's
CPU, power supply, other primary components and wiring interface connectors.
Optional modules plug in and are mounted to
the main circuit board. The main circuit board
is delivered premounted in the cabinet.
24 V
24 V
BELL 1 BELL 2
RESET
NONRESET
REMOTE TRBL BUZZER
GRD
+ - + -
+ - + -
TB2
TB3
J3
TB1
CB1
J2
HOT
AC TRBL BUZZ
TB5
EARTHNEUT
SUPV
TROUBLE
ALARM
RELAY
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10
RELAY
RELAY
NC
CCCNONONC NO
NC
+ - + - + - + - + - + - + - + - + - + -
TB6
TB4
MEMBRANE SW CONNECTOR
J1
BATT - +
SECURITY KEY
J4
TB7
J5
U3
LED-10IM
MODULE
U6
J6
TONE/C ITY BOX
OPTIONS
JP1
OPTION
SUPERVISION
J7
2410brd.cdr
J8
FIGURE 1-4:
Document #51127 Rev. C 11/7/00 P/N 51127:C
Main Circuit Board
13
Optional Modules
Cabinet
The cabinet is red and the backbox measures 16.90” (42.9 cm) long X 14.50” (36.8 cm) high X 4.5” (11.43 cm)
deep and provides space for two batteries (up to 12 Amp Hours). Also available is an optional dress panel,
DP-2410B, which mounts inside the cabinet.
ms2410bcdr
FIGURE 1-5:
MS-2410B Cabinet
Transformer Assembly
One 100VA transformer is provided standard with the panel.
An optional 100VA transformer XRM-24 (XRM-24E for
220/240 VAC applications) is available to provide maximum
accessory power.
Batteries
Standard XRM-24(E)
The cabinet provides space for 12 Amp Hour batteries (larger
batteries up to 18 Amp Hour batteries, use the listed Fire•Lite
BB-17F battery box). Batteries must be ordered separately.
Optional XRM-24(E)
FIGURE 1-6:
Transformer Assemblies
1.6Optional Modules
LED-10IM
The LED-10IM Interface Module provides an EIA-485 port to support the LED-10 Series Remote Annunciator,
LDM Series Annunciator, AFM Series Annunciator and ACM-8RF Relay Modules. EIA-485 wiring is
supervised for short, open and grounded circuits by this module. The LED-10IM mounts to connector J5 on the
main circuit board.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble
reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse
polarity circuit to open with a system trouble condition if no alarm condition exists.
1.7Optional Accessories
Dress Panel
A dress panel (DP-2410B) is available as an option. The dress panel restricts access to the system wiring while
allowing access to the membrane switch panel. Refer to Figure 1-1, “DP-2410B,” on page 9.
14
Document #51127 Rev.C 11/7/00 P/N 51127:C
Optional Accessories
Battery Box
The Fire•Lite BB-17F battery box may be used to house
two batteries greater than 12 Amp Hour to a maximum of
18 Amp Hour. The battery box mounts directly below the
MS-2410B cabinet, centered to the main circuit board. The
BB-17F is red and is provided with knockouts.
bb17.cdr
Remote Trouble Buzzer
One Remote Trouble Buzzer can be connected to the
MS-2410B control panel using four wires. The remote unit
includes an AC LED, System Trouble LED and piezo
sounder which are controlled by the MS-2410B. It mounts
to a single-gang electrical box.
ACM-8RF Relay Module
The ACM-8RF option module provides eight Form-C relays
rated at 5.0 amps each. The Relay Module connects to the
EIA-485 port off of the LED-10IM option module. Relays
are assigned to each of the 10 Initiating Device Circuits.
411 and 411UD Digital Alarm Communicator/Transmitter
The three input/channel 411 and the four input/channel 411UD
are dual line, digital alarm communicator transmitters which
can be used as slave communicators with the MS-2410B. The
inputs/channels are compatible with normally open relay contacts, require End-Of-Line (EOL) resistors, are supervised and
are fully programmable. The communicators interface with
the public switched telephone network and are compatible
with most central station receivers. Power supplied must be 12
or 24 volts, filtered and nonresettable. The communicators are
mounted in a small metal enclosure, providing a variety of
mounting options. Refer to the 411 or 411UD manual for
detailed information on installation, wiring and programming.
FIGURE 1-7:
FIGURE 1-8:
FIGURE 1-9:
BB-17F Battery Box
rtbbuzz.cdr
RTB Remote Trouble Buzzer
411udcvr.cdr
411UD Communicator
LED-10 Series Annunciator (LED Zone Type Annunciator)
The LED-10 Series is a 10 zone LED annunciator which
mounts on a 3-gang electrical box and provides LED
indication of the following:
• Alarm Zones 1 through 10
• Supervisory Zones 9 and 10 (LED-10LS2 only)
• Trouble Zones 1 through 10
FIRE ANNUNCIATOR
• AC Power (green)
• System Alarm (red)
• System Trouble (yellow)
FIGURE 1-10:
LED-10 Series Annunciator
• System Supervisory (yellow)
• Alarm Silence (yellow)
A local trouble sounder is standard and switches for remote Acknowledge, Silence, Drill and Reset are also provided on the LED-10 only. Wiring is inherently supervised by the FACP. Slide-in paper labels permit an easy
change of zone information. DIP switches allow the enabling and disabling of the local piezo sounder (with
approval of local AHJ), enabling and disabling of the mechanical keyswitch which may be used to prevent unauthorized use of the function switches and selection of annunciator receive/transmit mode.
Note that the LED-10 Series Remote Annunciators require the use of the LED-10IM Interface Module.
Document #51127 Rev. C 11/7/00 P/N 51127:C
led10.cdr
15
Optional Accessories
AFM Series Annunciators (LED Zone Type)
The AFM Series Annunciators remotely display system status. The AFM/AEM-16AT annunciators display zone
alarm and trouble status. In addition, they provide remote Acknowledge, Silence, Reset and Drill functions. The
AFM Series Annunciators require the use of the LED-10IM Interface Module. For more detailed information,
refer to the appropriate AFM Annunciator manual.
✓AFM-16ATX - The Annunciator Fixed Module-16ATX contains
16 red alarm and 16 yellow trouble LEDs, a system trouble LED,
an ON LINE/POWER LED and a local piezo sounder with
switches for Acknowledge, Silence, Reset and Drill. The
AFM-16ATX is fixed at address '1' and will accept up to 3
AEM-16ATF Expanders. The AFM-16ATX can be mounted in a
Fire•Lite ABS-1F or ABF-1F backbox. Refer to the AFM-16ATX
Manual for detailed information.
Note that only one AFM-16ATX
is required to annunciate 10 zones of alarm and trouble, provided '8
Point Shift' function is selected. Refer to Annunciator Manual P/N
15390 for additional information.
✓AFM-16ATXCS4 - This module is the same as the AFM-16ATX
except with four yellow supervisory LEDs in place of the four red
FIGURE 1-11:
AFM-16ATX
LEDs at points 13 through 16.
✓AFM-16ATXCS8 - This module is the same as the AFM-16ATX except with eight yellow supervisory
LEDs in place of the eight red LEDs at points 9 through 16.
✓AFM-16ATXCS16 - This module is the same as the AFM-16ATX except with sixteen yellow
supervisory LEDs in place of the sixteen red LEDs at points 1 through 16.
✓AEM-16ATF - The Annunciator Expander Module-16ATF con-
nects to the AFM-16ATX and adds 16 sets of red alarm LEDs
and yellow trouble LEDs. Up to three AEM-16ATFs may be
added to an AFM-16ATX but only one is required.
Note that one
AEM-16ATF is required with an AFM-16ATX to annunciate 10
zones of alarm and trouble as well as general system status provided '8 Point Shift' function is not selected. Refer to Annunciator Manual P/N 15390 for additional information.
✓AFM-16ATF - The Annunciator Fixed Module-16ATF contains
16 red alarm and 16 yellow trouble LEDs, a system trouble LED,
an ON LINE/POWER LED and a local piezo sounder with
switches for Acknowledge, Silence, Reset and Drill. The
AFM-16ATF is fixed at address '1' and communication is via the
EIA-485 data line. The AFM-16ATF can be mounted in a
Fire•Lite ABS-1F or ABF-1F backbox. Refer to the AFM-16AT
FIGURE 1-12:
AFM-16ATF
Manual for detailed information.
✓AFM-16AF - The Annunciator Fixed Module-16AF has 16 red
alarm LEDs. Multiple annunciators may be used by setting all
annunciators to Receive Only, except the last AFM-16AF in
line. Each annunciator's address is internally fixed at '1' and
communication is via the EIA-485 data line. The Local
Silence/Acknowledge switch functions as local lamp test and
silence for annunciator piezo. LEDs include On-Line and System Trouble indicators. The AFM-16AF Annunciator can be
mounted in a standard 4-gang electrical box. Refer to the
AFM-16AF Manual for detailed information.
afm16atx.cdr
afm16atx.cdr
16
Document #51127 Rev.C 11/7/00 P/N 51127:C
FIGURE 1-13:
afm-16a.cdr
AFM-16AF
Optional Accessories
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power
and control for a maximum of three expander modules (expander modules are not required when interfacing to the
MS-2410B). The LDM-32F and LDM-E32F have output connectors which are used to drive lamps or LEDs and
input connectors which are used for remote switch functions. The LDM Series requires the use of the LED-10IM
Interface Module. Refer to the LDM Series Lamp Driver Modules Manual for a complete description.
✓LDM-32F - The Lamp Driver Module has 32
alarm lamp/LED driver outputs which sink current to system common (-) on activation. A single
positive (+) voltage is required to supply total
operating power for all lamps or LEDs when all
drivers are activated. The LDM-32F provides a
separate driver for system trouble and inputs for a
local lamp test switch. A maximum of 16 external control switches may be wired to the
LDM-32F. DIP switch SW3 is used to enable or
disable the onboard piezo sounder, enable remote
switch functions, select a flashing LED function
for new alarms and troubles and other functions.
Switch SW4 is used to configure the module to
annunciate 32 alarms or 16 alarms and 16 troubles. A green ON-LINE LED flashes to indicate
ongoing communications with the host FACP.
One LDM-32F supports up to three LDM-E32F
modules. The LDM-32F is supplied with four
standoffs and screws for mounting to a CHS-4L
FIGURE 1-14:
LDM-32F Module
ldm-32f.cdr
chassis or custom backbox.
FCPS-24F(E) Remote Power Supply (System Power Expansion)
The FCPS-24F(E) is a compact, remote power supply and battery charger. This remote power supply consists of a
filtered 24 VDC output that may be configured to drive up to four Notification Appliance Circuits (four Class B or
two Class A and two Class B). Alternately, the four Notification Appliance Circuits may be used as auxiliary
power configured for resettable or nonresettable operation.
The FCPS-24F(E) may be used in a number of different applications. It may be used as a remotely mounted power
supply and battery charger powering up to four, coded or noncoded, Notification Appliance Circuits. Alternately,
any or all of these circuits may be used as 24 VDC output circuits capable of powering four-wire smoke detectors
or any device that requires filtered power. These circuits may be configured as resettable or nonresettable outputs
to expand FACP auxiliary system power.
Class B/Class A Notification Appli-
Notification Appliance Circuit
Control Input #1 (from FACP)
Notification Appliance Circuit
Control Input #2 (from FACP)
FIGURE 1-15:
AC Power
FCPS-24F(E)
Specific Application
Power
FCPS Trouble
Contact Output
ance Circuit or 24 VDC Output #1
Class B Notification Appliance
Circuit or 24 VDC Output #2
Class B/Class A Notification Appli-
ance Circuit or 24 VDC Output #3
Class B Notification Appliance
Circuit or 24 VDC Output #4
Battery Charger
fcpsblok.cdr
Document #51127 Rev. C 11/7/00 P/N 51127:C
17
Optional Accessories
One of the most common applications for the FCPS-24F(E) remote power supply utilizes the NAC expander
mode. In this application, one or two Notification Appliance Circuits (NACs) are connected from the main FACP
NAC output(s) to the remote power supply Control Input circuits. When these Control Input circuits activate (due
to reverse polarity of the NAC output), the power supply will activate its corresponding outputs. NAC Control
Input #1 controls power supply output circuits #1 and #2. NAC Control Input #2 controls output circuits #3 and
#4.
During the inactive state, the remote power supply supervises its NAC field wiring for short and open circuits. If
a fault is detected, the supply will enter a trouble condition and illuminate the corresponding NAC trouble LED
(Output Circuits 1-4), however, once the Notification Appliance Circuits are activated, the supervision is disabled
and the circuits are no longer supervised. Supervision of other power supply faults such as low battery, Earth
Fault, AC loss and battery charger failure will continue and may be monitored via the independent trouble relay
contact.
If a specific application requires that all four outputs activate at the same time, only one NAC control input from
the FACP is necessary. For this application, The Notification Appliance Circuit from the FACP is wired into NAC
Control Input #1 of the remote supply and then a pair of wires are connected from NAC Control Output #1 to
NAC Control Input #2. Refer to the FCPS-24F(E) Installation, Operation and Application Manual for a complete
description and examples of applications.
18
Document #51127 Rev.C 11/7/00 P/N 51127:C
Installation
CHAPTER 2Installation
2.1Mounting Options
The cabinet may be either semi-flush or surface mounted. The door
is removable during the installation period by opening and lifting off
the hinges. The cabinet mounts using two key slots and two additional 0.250" (6.35 mm) diameter holes located in the backbox. The
key slots are located at the top of the backbox and the two securing
holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount
the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible
with sufficient room to easily install and maintain the panel. Locate
the top of the cabinet approximately five feet above the floor with the
hinge mounting on the left. Determine the number of conductors
required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s)
and pull the required conductors into the box. All wiring should be
in accordance with the National and/or Local codes for fire alarm
systems.
FIGURE 2-1:
ms2410b.cdr
MS-2410B Mounting
2.2Backbox Mounting
✓Open the door and lift the door off the pin hinges.
✓Remove the main PC board assembly and transformer(s) which are packaged with the backbox. Set the
board and transformer aside in a safe, clean place. Avoid static discharge which may damage the board.
✓Mark and predrill holes for the top two keyhole mounting bolts using the dimensions illustrated.
✓Install two upper fasteners in the wall with the screw heads protruding.
✓Using the upper 'keyholes', mount the backbox over the two screws.
✓Mark and drill the lower two holes.
✓Mount backbox, install remaining fasteners and tighten.
✓When the location is dry and free of construction dust, install the transformer and main circuit board as
described in the following sections.
Document #51127 Rev. C 11/7/00 P/N 51127:C
19
Backbox Mounting
Draw wires through the respective knockout locations.
To p
Left Side
1.5”
(3.81 cm)
1.55”
(3.94 cm)
14.5” (36.83 cm)
11.5” (29.21 cm)
Right Side
16.9””
(42.93 cm)
20
Bottom
FIGURE 2-2:
Document #51127 Rev.C 11/7/00 P/N 51127:C
Cabinet Dimensions and Knockout Locations
5210bkbx.cdr
Backbox Mounting
Depth = 4.5" (11.43 cm)
Left Side
Door = 17.114" (43.37 cm)
Backbox = 16.9" (42.9 cm)
17.620"
(44.75 cm)
14.620"
(37.14 cm)
Bottom
Door = 14.714" (37.37 cm)
Backbox = 14.5" (36.8 cm)
Depth =
4.695"
11.93 cm)
2410bcab.cdr
Right Side
Depth = 4.75"
(12.07 cm)
17.020"
(43.23 cm)
TR-4-R Trim Ring
20.020"
50.85 cm)
Battery Box=8.5"
(21.59 cm)
(Optional BB-17F)
Battery Box=14.5" (36.8 cm)
(Optional BB-17F)
When batteries larger than 12 Amp Hour are being used, the BB-17F battery box (or equivalent) must be
installed. To install the BB-17F:
Mount the FACP cabinet to the wall.
1.
Remove knockouts on the bottom of the FACP cabinet and top of the BB-17F.
2.
Using conduit, hang the BB-17F from the FACP cabinet making sure there is at least ½" of
3.
clearance between the two cabinets.
Anchor the BB-17F to the wall.
4.
FIGURE 2-3:
FACP Backbox
Document #51127 Rev. C 11/7/00 P/N 51127:C
21
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.