Fire-Lite Alarms MS-2410B User Manual

PN: 51127:C ECN 00-506
Fire Alarm Control Panel
MS-2410B &
MS-2410BE
Document #51127 11/7/00 Rev.
© 2000 Fire•Lite
C
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warn­ing devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke detectors may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede­termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power.
cated, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibil­ity to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized pro­fessional fire alarm installers only. Adequate written records of all inspections should be kept.
If detectors are not so lo-
LimWarLg.p65 01/10/2000
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, ad­dition or deletion of system components, or after any modifica­tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for operation at 0-49° C/32-120° F condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi­nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LimWarLg.p65 01/10/2000
Notes
4
Document #51127 Rev.C 11/7/00 P/N 51127:C
Table of Contents
CHAPTER 1: Product Description .........................................................................................................................9
1.1: Product Features..........................................................................................................................................9
1.2: Specifications ..............................................................................................................................................11
1.3: Controls and Indicators ...............................................................................................................................12
1.4: Circuits ........................................................................................................................................................13
1.5: Components ................................................................................................................................................13
1.6: Optional Modules........................................................................................................................................14
1.7: Optional Accessories...................................................................................................................................14
CHAPTER 2: Installation.........................................................................................................................................19
2.1: Mounting Options .......................................................................................................................................19
2.2: Backbox Mounting......................................................................................................................................19
2.3: Transformer Installation ..............................................................................................................................22
2.4: Main Circuit Board Installation...................................................................................................................23
2.5: Operating Power..........................................................................................................................................24
2.6: Input Circuits...............................................................................................................................................25
2.7: Output Circuits ............................................................................................................................................26
2.8: Power-limited Wiring Requirements...........................................................................................................27
2.9: Installation of Optional Modules with Remote Accessories.......................................................................28
CHAPTER 3: Programming Instructions...............................................................................................................34
3.1: Switch Functions .........................................................................................................................................34
3.2: Programmable Features and Options ..........................................................................................................35
3.3: Entering Program Mode..............................................................................................................................36
3.4: Programming Function................................................................................................................................37
3.4.1: Program Feature Selection................................................................................................................37
3.4.2: Programming Options.......................................................................................................................37
3.4.3: Programming Example .....................................................................................................................37
3.5: Program Features and Options ....................................................................................................................41
3.5.1: Program Features ..............................................................................................................................41
3.5.2: Programming Options.......................................................................................................................41
3.6: Default Programming Mode........................................................................................................................46
CHAPTER 4: Operating Instructions..................................................................................................................... 47
4.1: Switch Functions in Normal Mode .............................................................................................................47
4.2: Status LEDs.................................................................................................................................................48
4.3: Operation.....................................................................................................................................................49
4.3.1: Fire Alarm Response.........................................................................................................................50
4.3.2: Fire Alarm Restoral...........................................................................................................................50
4.3.3: System Supervisory Condition Response .........................................................................................50
4.3.4: System Supervisory Restoral Response............................................................................................51
4.3.5: Trouble Condition Response.............................................................................................................51
4.3.6: Trouble Condition Restoral...............................................................................................................51
CHAPTER 5: Servicing ...........................................................................................................................................52
5.1: Walktest Mode.............................................................................................................................................52
5.2: Last Event/History Mode ............................................................................................................................53
5.3: Lamp Test ....................................................................................................................................................54
CHAPTER 6: Power Supply Calculations..............................................................................................................55
6.1: Overview .....................................................................................................................................................55
6.2: Calculating the AC Branch Circuit..............................................................................................................55
6.3: Calculating the System Current Draw.........................................................................................................56
Document 51127 Rev. C 11/7/00 P/N: 51127:C
5
Table of Contents
6.3.1: Overview ...........................................................................................................................................56
6.3.2: How to Use Table 6-3 on page 57 to Calculate System Current Draw .............................................56
6.4: Calculating the Battery Size ........................................................................................................................58
6.4.1: NFPA Battery Requirements .............................................................................................................58
6.4.2: Selecting and Locating Batteries.......................................................................................................58
Appendix A: NFPA Requirements ......................................................................................................................59
Appendix B: Wire Requirements .........................................................................................................................60
Appendix C: Slide-in Labels .................................................................................................................................61
6
Document #51127 Rev. C 11/7/00 P/N: 51127:C
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems (Automatic, Manual, Waterflow and Sprinkler Supervisory), Auxiliary Fire Alarm Systems (Automatic, Manual and Waterflow), Remote Station Fire Alarm Systems (Automatic, Manual and Waterflow) and Proprietary Fire Alarm Systems (Automatic, Manual and Waterflow).
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Inidicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Articla 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384
Annunciator Modules Document #15390
AFM-16ATF Annunciator Document #15970
AFM-16AF Annunciator Document #15210
FCPS-24F(E) Field Charger/Power Supply Document #50079
LDM Series Lamp Driver Modules Document #50055
LED-10 Annunciator Document #50361
ACM-8RF Annunciator Control Relay Module Document #50362
411 Digital Alarm Communicator/Transmitter Document #50921
411UD Digital Alarm Communicator/Transmitter Document #50759
Document #51127 Rev. C 11/7/00 P/N 51127:C
7
MS-2410B Main Circuit Board
24 V
24 V
NONR ESET
RESET
+ - + -
TB2
J3 PRIMARY TRANSFO RMER CONNECTOR
CAUTION! HIGH VOLTAGE
J2 OPTIONAL TRANSFO RMER CONNECTOR
BELL 1
+ - + -
TB3
24 V
RESET
NONRES ET
+ - + -
TB2
J3
J2
NC NO
TROUBLE RELAY
SUPV RELAY
NO
C
NC
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZON E 5
NO
ZO NE 6 ZON E 7 ZO NE 8 ZON E 9 ZO NE 10
BELL 2
REMOTE TRBL UNIT
AC TRBL BUZZ
GND
TB5
ALARM RELAY
C
TB4
TB6
SUPV
ALARM
24 V
BELL 1
BELL 2
REMOTE TRBL UNIT
AC TRBL BUZZ
GND
+ - + -
TB3
TB5
TB1
CB1
EARTH
HOT
NEUT
TROUBLE
RELAY
RELAY
NC NO
RELAY
CCC
ZONE 1 ZON E 2 Z ONE 3 ZO NE 4 ZO NE 5
NO
NCNCNC
C
NO
+ - + - + - + - + - + - + - + - + - + -
TB4
TB6
ZONE 6 ZONE 7 ZONE 8 ZO NE 9 ZO NE 10
J5
U3
LED-10IM MODULE
U6
TB7
SECURITY KEY
J4
TB7
J5
LED-10IM MODULE
J4
SECURITY KEY
J6
J6
MEMBRANE SW CONNECTOR
J1
BAT T - +
TON E/CITY BOX OPTIONS
J8
J7
JP1
OPTION
SUP ERVIS ION
TO NE/CIT Y BO X
J7
OPTIONS
TB1
H
N
O
E
T
U T
AC Pow er
J1
JP1
BATT - +
E A R T H
J8
MEMBRANE SW CO NNECTOR
OPTION
SUPERVISION
MS-2410B Terminals and Connectors
2410layo.cdr
8
Document #51127 Rev.C 11/7/00 P/N 51127:C
Product Description
CHAPTER 1 Product Description
The MS-2410B is a 10-zone FACP (Fire Alarm Control Panel), which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include two Notification Appliance Circuits (NACs), three standard Form-C relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad. It also supervises all wiring, AC voltage and battery level. The MS-2410BE offers the same features as the MS-2410B but allows connection to 220/ 240 VAC input.
1.1 Product Features
• 10 Class B Initiating Device Circuits (IDCs)
All zones accept smoke detectors and any normally open contact device
Zones 1 - 8 configured as general alarm zones
Zones 9 - 10 can be configured as smoke zones or supervisory alarm zones
• Two Class B Notification Appliance Circuits (NACs)
• Form-C Alarm Relay
• Form-C Trouble Relay
• Form-C Supervisory Relay
• 3.6 amps of system power expandable to 6.6 amps
• RTB Remote Trouble Buzzer
• Remote Relay Option Module (ACM-8RF) providing one 5.0 amp relay per zone
• Dress Panel coverplate (DP-2410B)
• Built-in keypad for panel control and programming
• 24 volt operation
• Trouble Reminder
• Alarm Verification (zones 1 through 3 only)
• Interfaces with Fire•Lite annunciators (requires LED-10IM Option Module)
LED-10 Series Remote Annunciators provide
red alarm and yellow trouble LEDs
LDM-32F Graphic Annunciator Driver
AFM Series LED Annunciators
• Small backbox size 16.9” (42.9 cm) X 14.5” (36.8 cm) X 4.5” (11.43 cm)
• Silence Inhibit Notification Appliance Circuits
• Auto-Silence Notification Appliance Circuits
• Fuseless design
• Low AC voltage sense
• Silent or audible Walktest
FIGURE 1-1:
DP-2410B
DP2410b.cdr
Note: Unless otherwise specified, the term MS-2410B shall be used in this manual to refer to both the MS-2410B and the MS-2410BE Fire Alarm Control Panels.
Document #51127 Rev. C 11/7/00 P/N 51127:C
9
Product Features
24 VDC Power
Keypad and LEDs
Standard Trans former
Notification Appliance Circuits
Remote Trouble Buzzer
AT
Zone 1 Zone 2
Zone 3 Zone 4
Zone 5 Zone 6
Zone 7 Zone 8
Zone 9 Zone 10
Trouble
Supervisory
Signal Silence
NAC Fault
Ground Fault
Battery Trouble
Zone Disabled
Annc. Trouble
Relays
10 Input Zones
Security Key
LED-10IM Interface Module Connector
Reverse Pol arity Module
Optional Trans former
Note: Transformers are mounted to the backbox, under the main circuit board.
Holds up to 12 AH Batteries,
FIGURE 1-2:
MS-2410B Panel
Reverse Polarity Module Supervision
m2410enc.cdr
10
Document #51127 Rev.C 11/7/00 P/N 51127:C
Specifications
1.2 Specifications
AC Power - TB1
MS-2410B: 120 VAC, 60 Hz, 2.3 amps MS-2410BE: 220/240 VAC, 50 Hz, 1.15 amps Wire size: minimum #14 AWG (2.0 mm
Battery (lead acid only) - J1
Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour battery (MS-2410B cabinet holds maximum 12 Amp Hour battery. Larger batteries require Fire•Lite BB-17F)
Initiating Device Circuits TB6 and TB7
General Alarm Zones 1 through 8
Smoke Zones or Supervisory Alarm Zones 9 and 10
Operation: All zones Class B
Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)
Alarm Current: 15 mA threshold
Short Circuit Current: 42 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K, ½ watt (Part #27072)
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Fire•Lite Device Compatibility Document for listed compatible devices.
2
) with 600V insulation
Notification Appliance Circuits - TB3
Class B wiring
Operating voltage nominal 24 volts
Current for all external devices: 3.0 amps expandable to 6.0 amps
1
Current Limit: TB3 via PTC
Maximum signaling current/circuit: TB3 = 1.25 amps expandable to 2.5 amps
End-of-Line resistor: 4.7K, ½ watt (Part #71252) for Notification Appliance Circuits
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Three Form-C Relays - TB4
TB4 relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)
Four-wire Smoke Detector Power - TB2 Terminals 3(-) & 4(+)
Maximum ripple voltage: 10 mV
Up to 300 mA is available for powering 4-wire smoke detectors
Recommended maximum Standby current is 50 mA
Operating Voltage nominal 24 volts
RMS
2
1
Refer to Fire•Lite Device Compatibility Document for compatible listed device
1. Total current for nonresettable power, four-wire smoke power, and two Notification Appliance Circuits
amps.
Total system current in excess of 3.6 amps requires the XRM-24 Transformer (XRM-24E for 220/240 VAC applications)
and 12 Amp Hour or 18 Amp Hour batteries.
2. For power supply and battery calculations, refer to “Power Supply Calculations” on page 55.
Document #51127 Rev. C 11/7/00 P/N 51127:C
must not exceed 6.0
11
Controls and Indicators
Nonresettable 24 VDC Power - TB2 Terminals 1(-) & 2(+)
Maximum ripple voltage: 10 mV
Total DC current available from this output is up to 500 mA
Operating Voltage nominal 24 volts
RMS
1
Recommended maximum Standby current is 150 mA
Refer to Fire•Lite Device Compatibility Chart for compatible listed devices
Remote Trouble Buzzer - TB5
Operating Voltage: nominal 24 VDC
DC current when RTB Remote Trouble Buzzer is in normal standby (AC Power LED on alone) is 20 mA.
Maximum DC current from this output when RTB Remote Trouble Buzzer is active is 50 mA.
1.3 Controls and Indicators
Front Panel Membrane Keys in Normal Mode
Acknowledge
Signal Silence
Drill
Disable/Enable
Reset/Lamp Test
Note that programming keys function slide-in-labels and option/feature slide-in labels are also provided and should be inserted while in Program Mode to view the altered key functions. Refer to Figure 4-1, “LED Indicators and Key­pad,” on page 47 and “Slide-in Labels” on page 61.
LEDs
AC Power - green LED
Alarm - red LED
Trouble - yellow LED
Supervisory - yellow LED
Signal Silence - yellow LED
NAC Fault - yellow LED
Ground Fault - yellow LED
Battery Trouble - yellow LED
Zone Disabled - yellow LED
Annunciator Trouble - yellow LED
Zone Fire Alarm - Zones 1 through 10 - red LEDs
Zone Supervisory Alarm - Zones 9 and 10 only - red LEDs
Zone Trouble - Zones 1 through 10 - yellow LEDs
AT
Zone 1 Zone 2
Zone 3 Zone 4
Zone 5 Zone 6
Zone 7 Zone 8
Zone 9 Zone 10
FIGURE 1-3:
Trouble
Supervisory
Signal Silence
NAC Fault
Ground Fault
Battery Trouble
Zone Disabled
Annunc. Trouble
LEDs and Keypad
2410disp.cdr
2410DISP
Note: A blank slide-in label is provided for circuits 1 through 10 which may be customized by the customer. In addition, slide-in-labels listing the programming features/options and programming key functions are provided and should be inserted while in Program Mode.
1. Total current for nonresettable power, four-wire smoke power, and two Notification Appliance Circuits
amps.
Total system current in excess of 3.6 amps requires the XRM-24 Transformer (XRM-24E for 220/240 VAC applica-
tions) and 12 Amp Hour or 18 Amp Hour batteries.
12
Document #51127 Rev.C 11/7/00 P/N 51127:C
must not exceed 6.0
Circuits
Local Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions:
• Alarm - on steady
• Alarm Verification - pulse 1 second On and 1 second Off
• Trouble - pulse 1 second On and 1 second Off
• Supervisory - pulse ½ second On and ½ second OFF
1.4 Circuits
Input Circuits
Ten input circuits provide Class B configuration. Input circuits 1 through 10 may be used as standard fire alarm control panel zones and circuits 9 and 10 may be used as supervisory alarm zones. All ten Initiating Device Cir­cuits accept normally-open contact devices and two-wire smoke detectors.
Output Circuits
• 24 Volt Resettable Power Output 300 mA
• 24 Volt Nonresettable Power Output 500 mA
• 24 Volt Remote Trouble Buzzer Output 50 mA maximum
• 24 Volt Battery Charger (up to 18 AH batteries)
• EIA-485 Port (interfaces to LED-10 Series Annunciators, AFM Series and LDM Graphic Series Annunciators and ACM-8RF Remote Relay Module)
Notification Appliance Circuits
Two Notification Appliance Circuits Class B.
Relays
Three dry Form-C relays for system alarm, system trouble and supervisory are provided standard. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 2.0 amps @ 30 VAC (resistive).
EIA-485 Port (Requires LED-10IM Module)
EIA-485 compatible port on the LED-10IM option module supports up to 10 different device addresses which can consist of LED-10 Series Remote Annunciators, ACM-8RF Relay Modules, AFM Series Annunciators or LDM Graphic Series Annunciators or any combination of the four modules.
Battery Charger
Battery Charger will charge up to 18 AH batteries. The MS-2410B cabinet holds a maximum of 12 AH batteries. The Fire•Lite BB-17F is required to hold 18 AH batteries. The charger is rated for 800 mA maximum current.
1.5 Components
Main Circuit Board
The main circuit board contains the system's CPU, power supply, other primary compo­nents and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board. The main circuit board is delivered premounted in the cabinet.
24 V
24 V
BELL 1 BELL 2
RESET
NONRESET
REMOTE TRBL BUZZER
GRD
+ - + -
+ - + -
TB2
TB3
J3
TB1
CB1
J2
HOT
AC TRBL BUZZ
TB5
EARTHNEUT
SUPV
TROUBLE
ALARM RELAY
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9 ZONE 10
RELAY
RELAY
NC
CCCNONONC NO
NC
+ - + - + - + - + - + - + - + - + - + -
TB6
TB4
MEMBRANE SW CONNECTOR
J1
BATT - +
SECURITY KEY
J4
TB7
J5
U3
LED-10IM MODULE
U6
J6
TONE/C ITY BOX OPTIONS
JP1
OPTION
SUPERVISION
J7
2410brd.cdr
J8
FIGURE 1-4:
Document #51127 Rev. C 11/7/00 P/N 51127:C
Main Circuit Board
13
Optional Modules
Cabinet
The cabinet is red and the backbox measures 16.90” (42.9 cm) long X 14.50” (36.8 cm) high X 4.5” (11.43 cm) deep and provides space for two batteries (up to 12 Amp Hours). Also available is an optional dress panel, DP-2410B, which mounts inside the cabinet.
ms2410bcdr
FIGURE 1-5:
MS-2410B Cabinet
Transformer Assembly
One 100VA transformer is provided standard with the panel. An optional 100VA transformer XRM-24 (XRM-24E for 220/240 VAC applications) is available to provide maximum accessory power.
Batteries
Standard XRM-24(E)
The cabinet provides space for 12 Amp Hour batteries (larger batteries up to 18 Amp Hour batteries, use the listed Fire•Lite BB-17F battery box). Batteries must be ordered separately.
Optional XRM-24(E)
FIGURE 1-6:
Transformer Assemblies
1.6 Optional Modules
LED-10IM
The LED-10IM Interface Module provides an EIA-485 port to support the LED-10 Series Remote Annunciator, LDM Series Annunciator, AFM Series Annunciator and ACM-8RF Relay Modules. EIA-485 wiring is supervised for short, open and grounded circuits by this module. The LED-10IM mounts to connector J5 on the main circuit board.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists.
1.7 Optional Accessories
Dress Panel
A dress panel (DP-2410B) is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. Refer to Figure 1-1, “DP-2410B,” on page 9.
14
Document #51127 Rev.C 11/7/00 P/N 51127:C
Optional Accessories
Battery Box
The Fire•Lite BB-17F battery box may be used to house two batteries greater than 12 Amp Hour to a maximum of 18 Amp Hour. The battery box mounts directly below the MS-2410B cabinet, centered to the main circuit board. The BB-17F is red and is provided with knockouts.
bb17.cdr
Remote Trouble Buzzer
One Remote Trouble Buzzer can be connected to the MS-2410B control panel using four wires. The remote unit includes an AC LED, System Trouble LED and piezo sounder which are controlled by the MS-2410B. It mounts to a single-gang electrical box.
ACM-8RF Relay Module
The ACM-8RF option module provides eight Form-C relays rated at 5.0 amps each. The Relay Module connects to the EIA-485 port off of the LED-10IM option module. Relays are assigned to each of the 10 Initiating Device Circuits.
411 and 411UD Digital Alarm Communicator/Transmitter
The three input/channel 411 and the four input/channel 411UD are dual line, digital alarm communicator transmitters which can be used as slave communicators with the MS-2410B. The inputs/channels are compatible with normally open relay con­tacts, require End-Of-Line (EOL) resistors, are supervised and are fully programmable. The communicators interface with the public switched telephone network and are compatible with most central station receivers. Power supplied must be 12 or 24 volts, filtered and nonresettable. The communicators are mounted in a small metal enclosure, providing a variety of mounting options. Refer to the 411 or 411UD manual for detailed information on installation, wiring and programming.
FIGURE 1-7:
FIGURE 1-8:
FIGURE 1-9:
BB-17F Battery Box
rtbbuzz.cdr
RTB Remote Trouble Buzzer
411udcvr.cdr
411UD Communicator
LED-10 Series Annunciator (LED Zone Type Annunciator)
The LED-10 Series is a 10 zone LED annunciator which mounts on a 3-gang electrical box and provides LED indication of the following:
• Alarm Zones 1 through 10
• Supervisory Zones 9 and 10 (LED-10LS2 only)
• Trouble Zones 1 through 10
FIRE ANNUNCIATOR
• AC Power (green)
• System Alarm (red)
• System Trouble (yellow)
FIGURE 1-10:
LED-10 Series Annunciator
• System Supervisory (yellow)
• Alarm Silence (yellow)
A local trouble sounder is standard and switches for remote Acknowledge, Silence, Drill and Reset are also pro­vided on the LED-10 only. Wiring is inherently supervised by the FACP. Slide-in paper labels permit an easy change of zone information. DIP switches allow the enabling and disabling of the local piezo sounder (with approval of local AHJ), enabling and disabling of the mechanical keyswitch which may be used to prevent unau­thorized use of the function switches and selection of annunciator receive/transmit mode.
Note that the LED-10 Series Remote Annunciators require the use of the LED-10IM Interface Module.
Document #51127 Rev. C 11/7/00 P/N 51127:C
led10.cdr
15
Optional Accessories
AFM Series Annunciators (LED Zone Type)
The AFM Series Annunciators remotely display system status. The AFM/AEM-16AT annunciators display zone alarm and trouble status. In addition, they provide remote Acknowledge, Silence, Reset and Drill functions. The AFM Series Annunciators require the use of the LED-10IM Interface Module. For more detailed information, refer to the appropriate AFM Annunciator manual.
AFM-16ATX - The Annunciator Fixed Module-16ATX contains
16 red alarm and 16 yellow trouble LEDs, a system trouble LED, an ON LINE/POWER LED and a local piezo sounder with switches for Acknowledge, Silence, Reset and Drill. The AFM-16ATX is fixed at address '1' and will accept up to 3 AEM-16ATF Expanders. The AFM-16ATX can be mounted in a Fire•Lite ABS-1F or ABF-1F backbox. Refer to the AFM-16ATX Manual for detailed information.
Note that only one AFM-16ATX is required to annunciate 10 zones of alarm and trouble, provided '8 Point Shift' function is selected. Refer to Annunciator Manual P/N 15390 for additional information.
AFM-16ATXCS4 - This module is the same as the AFM-16ATX
except with four yellow supervisory LEDs in place of the four red
FIGURE 1-11:
AFM-16ATX
LEDs at points 13 through 16.
AFM-16ATXCS8 - This module is the same as the AFM-16ATX except with eight yellow supervisory
LEDs in place of the eight red LEDs at points 9 through 16.
AFM-16ATXCS16 - This module is the same as the AFM-16ATX except with sixteen yellow
supervisory LEDs in place of the sixteen red LEDs at points 1 through 16.
AEM-16ATF - The Annunciator Expander Module-16ATF con-
nects to the AFM-16ATX and adds 16 sets of red alarm LEDs and yellow trouble LEDs. Up to three AEM-16ATFs may be added to an AFM-16ATX but only one is required.
Note that one AEM-16ATF is required with an AFM-16ATX to annunciate 10 zones of alarm and trouble as well as general system status pro­vided '8 Point Shift' function is not selected. Refer to Annuncia­tor Manual P/N 15390 for additional information.
AFM-16ATF - The Annunciator Fixed Module-16ATF contains
16 red alarm and 16 yellow trouble LEDs, a system trouble LED, an ON LINE/POWER LED and a local piezo sounder with switches for Acknowledge, Silence, Reset and Drill. The AFM-16ATF is fixed at address '1' and communication is via the EIA-485 data line. The AFM-16ATF can be mounted in a Fire•Lite ABS-1F or ABF-1F backbox. Refer to the AFM-16AT
FIGURE 1-12:
AFM-16ATF
Manual for detailed information.
AFM-16AF - The Annunciator Fixed Module-16AF has 16 red
alarm LEDs. Multiple annunciators may be used by setting all annunciators to Receive Only, except the last AFM-16AF in line. Each annunciator's address is internally fixed at '1' and communication is via the EIA-485 data line. The Local Silence/Acknowledge switch functions as local lamp test and silence for annunciator piezo. LEDs include On-Line and Sys­tem Trouble indicators. The AFM-16AF Annunciator can be mounted in a standard 4-gang electrical box. Refer to the AFM-16AF Manual for detailed information.
afm16atx.cdr
afm16atx.cdr
16
Document #51127 Rev.C 11/7/00 P/N 51127:C
FIGURE 1-13:
afm-16a.cdr
AFM-16AF
Optional Accessories
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander mod­ules, are used to provide an interface to a custom graphic LED annunciator. The master module provides power and control for a maximum of three expander modules (expander modules are not required when interfacing to the MS-2410B). The LDM-32F and LDM-E32F have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions. The LDM Series requires the use of the LED-10IM Interface Module. Refer to the LDM Series Lamp Driver Modules Manual for a complete description.
LDM-32F - The Lamp Driver Module has 32
alarm lamp/LED driver outputs which sink cur­rent to system common (-) on activation. A single positive (+) voltage is required to supply total operating power for all lamps or LEDs when all drivers are activated. The LDM-32F provides a separate driver for system trouble and inputs for a local lamp test switch. A maximum of 16 exter­nal control switches may be wired to the LDM-32F. DIP switch SW3 is used to enable or disable the onboard piezo sounder, enable remote switch functions, select a flashing LED function for new alarms and troubles and other functions. Switch SW4 is used to configure the module to annunciate 32 alarms or 16 alarms and 16 trou­bles. A green ON-LINE LED flashes to indicate ongoing communications with the host FACP. One LDM-32F supports up to three LDM-E32F modules. The LDM-32F is supplied with four standoffs and screws for mounting to a CHS-4L
FIGURE 1-14:
LDM-32F Module
ldm-32f.cdr
chassis or custom backbox.
FCPS-24F(E) Remote Power Supply (System Power Expansion)
The FCPS-24F(E) is a compact, remote power supply and battery charger. This remote power supply consists of a filtered 24 VDC output that may be configured to drive up to four Notification Appliance Circuits (four Class B or two Class A and two Class B). Alternately, the four Notification Appliance Circuits may be used as auxiliary power configured for resettable or nonresettable operation.
The FCPS-24F(E) may be used in a number of different applications. It may be used as a remotely mounted power supply and battery charger powering up to four, coded or noncoded, Notification Appliance Circuits. Alternately, any or all of these circuits may be used as 24 VDC output circuits capable of powering four-wire smoke detectors or any device that requires filtered power. These circuits may be configured as resettable or nonresettable outputs to expand FACP auxiliary system power.
Class B/Class A Notification Appli-
Notification Appliance Circuit Control Input #1 (from FACP)
Notification Appliance Circuit
Control Input #2 (from FACP)
FIGURE 1-15:
AC Power
FCPS-24F(E)
Specific Application
Power
FCPS Trouble
Contact Output
ance Circuit or 24 VDC Output #1
Class B Notification Appliance
Circuit or 24 VDC Output #2
Class B/Class A Notification Appli-
ance Circuit or 24 VDC Output #3
Class B Notification Appliance
Circuit or 24 VDC Output #4
Battery Charger
fcpsblok.cdr
Document #51127 Rev. C 11/7/00 P/N 51127:C
17
Optional Accessories
One of the most common applications for the FCPS-24F(E) remote power supply utilizes the NAC expander mode. In this application, one or two Notification Appliance Circuits (NACs) are connected from the main FACP NAC output(s) to the remote power supply Control Input circuits. When these Control Input circuits activate (due to reverse polarity of the NAC output), the power supply will activate its corresponding outputs. NAC Control Input #1 controls power supply output circuits #1 and #2. NAC Control Input #2 controls output circuits #3 and #4.
During the inactive state, the remote power supply supervises its NAC field wiring for short and open circuits. If a fault is detected, the supply will enter a trouble condition and illuminate the corresponding NAC trouble LED (Output Circuits 1-4), however, once the Notification Appliance Circuits are activated, the supervision is disabled and the circuits are no longer supervised. Supervision of other power supply faults such as low battery, Earth Fault, AC loss and battery charger failure will continue and may be monitored via the independent trouble relay contact.
If a specific application requires that all four outputs activate at the same time, only one NAC control input from the FACP is necessary. For this application, The Notification Appliance Circuit from the FACP is wired into NAC Control Input #1 of the remote supply and then a pair of wires are connected from NAC Control Output #1 to NAC Control Input #2. Refer to the FCPS-24F(E) Installation, Operation and Application Manual for a complete description and examples of applications.
18
Document #51127 Rev.C 11/7/00 P/N 51127:C
Installation
CHAPTER 2 Installation
2.1 Mounting Options
The cabinet may be either semi-flush or surface mounted. The door is removable during the installation period by opening and lifting off the hinges. The cabinet mounts using two key slots and two addi­tional 0.250" (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temper­atures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are pro­vided for wiring convenience. Select the appropriate knockout(s) and pull the required conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
FIGURE 2-1:
ms2410b.cdr
MS-2410B Mounting
2.2 Backbox Mounting
Open the door and lift the door off the pin hinges.
Remove the main PC board assembly and transformer(s) which are packaged with the backbox. Set the
board and transformer aside in a safe, clean place. Avoid static discharge which may damage the board.
Mark and predrill holes for the top two keyhole mounting bolts using the dimensions illustrated.
Install two upper fasteners in the wall with the screw heads protruding.
Using the upper 'keyholes', mount the backbox over the two screws.
Mark and drill the lower two holes.
Mount backbox, install remaining fasteners and tighten.
When the location is dry and free of construction dust, install the transformer and main circuit board as
described in the following sections.
Document #51127 Rev. C 11/7/00 P/N 51127:C
19
Backbox Mounting
Draw wires through the respective knockout locations.
To p
Left Side
1.5”
(3.81 cm)
1.55”
(3.94 cm)
14.5” (36.83 cm)
11.5” (29.21 cm)
Right Side
16.9””
(42.93 cm)
20
Bottom
FIGURE 2-2:
Document #51127 Rev.C 11/7/00 P/N 51127:C
Cabinet Dimensions and Knockout Locations
5210bkbx.cdr
Backbox Mounting
Depth = 4.5" (11.43 cm)
Left Side
Door = 17.114" (43.37 cm) Backbox = 16.9" (42.9 cm)
17.620"
(44.75 cm)
14.620"
(37.14 cm)
Bottom
Door = 14.714" (37.37 cm) Backbox = 14.5" (36.8 cm)
Depth =
4.695"
11.93 cm)
2410bcab.cdr
Right Side
Depth = 4.75" (12.07 cm)
17.020"
(43.23 cm)
TR-4-R Trim Ring
20.020"
50.85 cm) Battery Box=8.5"
(21.59 cm) (Optional BB-17F)
Battery Box=14.5" (36.8 cm) (Optional BB-17F)
When batteries larger than 12 Amp Hour are being used, the BB-17F battery box (or equivalent) must be installed. To install the BB-17F:
Mount the FACP cabinet to the wall.
1.
Remove knockouts on the bottom of the FACP cabinet and top of the BB-17F.
2.
Using conduit, hang the BB-17F from the FACP cabinet making sure there is at least ½" of
3.
clearance between the two cabinets.
Anchor the BB-17F to the wall.
4.
FIGURE 2-3:
FACP Backbox
Document #51127 Rev. C 11/7/00 P/N 51127:C
21
Loading...
+ 47 hidden pages