Fire-Lite Alarms MS-5UD, MS-10UD Series Series Manual

Fire Alarm Control Panels
MS-5UD Series
MS-10UD Series
Manual
Document 52626 6/30/2009 Rev:
P/N 52626:B1 ECN 09-432
B1
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull st ati ons, audib le warning devices, and a fire alarm control panel with remote notification capability—can provi de early warn ing of a develop ­ing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendati ons, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These documents can be found at http://www.systemsen­sor.com/html/applicat.html. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm sys­tem may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behi nd walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first­floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires d evelop in dif ferent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede ter­mined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over t ime. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building . Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilep sy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from st and by batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control panel. It is essential to use only equip­ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire al arm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A main­tenance agreement should be arranged through the local man­ufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addit ion, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to light ­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or out side aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect ele c tronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, opera ting, and pr o­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and rel iability depend upon prop er inst allatio n.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc.Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 3
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruit s radi­oelectriques depassant les limites applicables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact T echnical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
Table of Contents
Table of Contents
SECTION 1 Product Description............................................................................................11
1.1: Product Features ..........................................................................................................................................12
1.2: Specifications...............................................................................................................................................13
1.3: Controls and Indicators................................................................................................................................15
1.4: Digital Alarm Communicator/Transmitter ..................................................................................................16
1.5: Components.................................................................................................................................................17
1.6: Optional Modules and Accessories .............................................................................................................17
1.7: Telephone Requirements and Warnings.......................................................................................................19
1.7.1: Telephone Circuitry...........................................................................................................................19
1.7.2: Digital Communicator.......................................................................................................................19
1.7.3: Telephone Company Rights and Warnings.......................................................................................20
1.7.4: For Canadian Applications................................................................................................................21
SECTION 2 Installation...........................................................................................................22
2.1: Backbox Mounting ......................................................................................................................................22
2.2: Operating Power..........................................................................................................................................25
2.3: Input Circuits...............................................................................................................................................26
2.4: Output Circuits.............................................................................................................................................28
2.4.1: Notification Appliance Circuits.........................................................................................................28
2.4.2: Special Application DC Power Output Connections.........................................................................29
2.4.3: Relays - Programmable .....................................................................................................................29
2.4.4: Remote Synchronization Output .......................................................................................................30
2.5: Power-limited Wiring Requirements..................................................................................... ......................31
2.6: Digital Communicator .................................................................................................................................32
2.7: Installation of Optional Modules.................................................................................................................33
2.7.1: CAC-5X Class A Converter Module. ................................................................................................33
2.7.2: 4XTMF Option Module ....................................................................................................................35
2.8: ANN-BUS Devices......................................................................................................................................37
2.8.1: ANN-BUS Wiring.............................................................................................................................37
2.8.2: ANN-BUS Device Addressing ..........................................................................................................40
2.8.3: ANN-80 Remote Fire Annunciator ...................................................................................................41
2.8.4: Specifications.....................................................................................................................................41
2.8.5: Installation.........................................................................................................................................41
2.8.6: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................44
2.8.7: ANN-I/O LED Driver Module..........................................................................................................46
2.8.8: ANN-LED Annunciator Module.......................................................................................................49
2.8.9: ANN-RLY Relay Module .................................................................................................................51
2.9: ANN-BUS Audio Panel...............................................................................................................................53
SECTION 3 Programming ......................................................................................................55
3.1: User Programming.......................................................................................................................................55
3.2: Initial Power-up...........................................................................................................................................56
3.3: Programming Screens Description ..............................................................................................................56
3.4: Programming and Passwords.......................................................................................................................57
3.5: Master Programming Level.........................................................................................................................58
3.5.1: Input Zones........................................................................................................................................59
3.5.2: NAC (Notification Appliance Circuit) ..............................................................................................67
3.5.3: Relays ................................................................................................................................................71
3.5.4: System Setup .....................................................................................................................................73
3.5.5: Option Modules................................................................................................................................79
3.5.6: History.............................................................................................................................................100
3.5.7: Walktest...........................................................................................................................................102
3.5.8: Clear Program..................................................................................................................................103
3.5.9: Password Change.............................................................................................................................103
3.6: Maintenance Programming Level..............................................................................................................104
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 5
Table of Contents
3.6.1: Input Zones - Enable/Disable ..........................................................................................................105
3.6.2: History .............................................................................................................................................105
3.6.3: Walktest...........................................................................................................................................106
3.6.4: Time-Date........................................................................................................................................107
SECTION 4 Operating Instructions.....................................................................................109
4.1: Panel Control Buttons................................................................................................................................109
4.1.1: Acknowledge/Step...........................................................................................................................109
4.1.2: Alarm Silenced ................................................................................................................................109
4.1.3: Drill/Hold 2 Sec...............................................................................................................................109
4.1.4: Reset ................................................................................................................................................109
4.2: LED Indicators...........................................................................................................................................110
4.3: Normal Operation ......................................................................................................................................110
4.4: Trouble Operation......................................................................................................................................111
4.5: Alarm Operation ........................................................................................................................................112
4.6: Supervisory Operation ...............................................................................................................................113
4.7: Process Monitor Operation ........................................................................................................................114
4.8: Hazard/Tornado Condition Operation........................................................................................................114
4.9: Medical Alert Condition Operation ...........................................................................................................114
4.10: Disable/Enable Operation........................................................................................................................115
4.11: Waterflow Circuits Operation ..................................................................................................................115
4.12: Detector Functions................................................................................................ ...................................115
4.13: Time Functions: Real-Time Clock...........................................................................................................115
4.14: Coded Operation............................................................................... .......................................................115
4.15: Presignal..................................................... .................................... ..........................................................116
4.16: Positive Alarm Sequence.........................................................................................................................116
4.17: Special System Timers........................................................ ..................................... ................................117
4.17.1: Silence Inhibit Timer.......................................... ..................................... ......................................117
4.17.2: Autosilence Timer .............................................. ...........................................................................117
4.17.3: Trouble Reminder.................................................. ........................................................................117
4.17.4: Waterflow Retard Timer.......................................................................... ......................................117
4.17.5: Alarm Verification (None or One Minute)....................................................................................118
4.18: Walktest.................................................................................. ..................................................................118
4.19: Read Status..................................... ..........................................................................................................119
4.19.1: Input Zones................................................................................ ....................................................120
4.19.2: NAC................................................. ..............................................................................................120
4.19.3: Relays ............................................................................... .............................................................121
4.19.4: System Settings........................................................................................ ......................................121
4.19.5: Timers.................................................................... ..................................... ...................................122
4.19.6: Daylight Savings....................................................... ..................................... ................................122
4.19.7: History ............................ .................................... ...........................................................................123
4.19.8: Print......................................... ..................................... ..................................................................123
4.19.9: ANN-BUS.......................................... ...................................................................... ......................124
4.19.10: Central Station .............................................................................................................................125
4.19.11: Phone Line...................................................................................................................................126
4.19.12: Service Terminal..........................................................................................................................126
SECTION 5 Central Station Communications....................................................................127
5.1: Transmittal Priorities..................................................................................................................................128
SECTION 6 Local/Remote Site Upload/Download.............................................................130
6.1: Remote Download .....................................................................................................................................130
6.2: Transferring a Program..............................................................................................................................132
6.2.1: Security Features .............................................................................................................................132
SECTION 7 Power Supply Calculations..............................................................................134
7.1: Overview....................................................................................................................................................134
7.2: Calculating the AC Branch Circuit............................................................................................................134
6 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Table of Contents
7.3: Calculating the System Current Draw.......................................................................................................135
7.3.1: Overview .........................................................................................................................................135
7.3.2: How to Use Table 7-3 on page 136 to Calculate System Current Draw.........................................135
7.4: Calculating the Battery Size ......................................................................................................................137
7.4.1: NFPA Battery Requirements...........................................................................................................137
7.4.2: Selecting and Locating Batteries.....................................................................................................137
APPENDIX A Ademco Contact ID Format Event Code Descriptions...............................138
A.1: Transmission Format Between DACT and Receiver................................................................................138
A.2: Ademco Contact ID Typical Printout .......................................................................................................138
APPENDIX B NFPA Standard-Specific Requirements.......................................................143
B.1: Central Station/Remote Station Transmitter:................................... Connection to FACP Dry Contacts149
APPENDIX C FACP with Keltron .........................................................................................150
APPENDIX D Wire Requirements........................................................................................151
D.1: MS-5UD-3(E) & MS-10UD-3(E) NAC Wiring.......................................................................................152
D.2: MS-5UD-7(C/E) & MS-10UD-7(C/E) NAC Wiring................................................................................152
Index.......................................................................................................................................153
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 7
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
This Class (A) digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other: NEC Article 250 Grounding
NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384 411UD Manual Document #50759 411UDAC Manual Document #51073 ANN-80 Product Installation Doc. Document #52749 ANN-(R)LED Product Installation Doc. Document #53032 ANN-I/O Product Installation Doc. Document #151416 ANN-RLY Product Installation Doc. Document #53033 ANN-S/PG Product Installation Doc. Document #151417 ACC-25/50 Series Audio Panel Document #51889
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
8 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
MS-5UD Series Main Circuit Board
TB1
-
Style D (Class A) IDC
B B
+
11
TB4/
TB6
J2
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
+
Style Z (Class A) NAC
+
+
B
-
11 2
B
+
OUT1/3 OUT2/4
TB5/
TB7
OUT OUT
TB2
Class A Converter Module
USB Port for local programming using
a personal computer and PK-5X Utility
J11
NO NC C
A Fail Safe Trouble
relay switches to the
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
Contacts shown below in normal
NC position during
condition (AC power with no alarm,
trouble or supervisory activi ty).
Remote
Synchronization
Supervisory*
NO NC CNO NC C NO NC C
Trouble*
Alarm*
trouble conditions and
under loss of all power.
(* )Factory default relay programming
TB2
and power-limited.
Requires ELR.4.7K
0.040 amps maximum.
Special Application Power
24 VDC filtered, supervised
Output (see note 2)
Cut this jumper to
enable Supervisory
relay when 4XTM
module is installed
J5
J4
JP24
TB8
4XTM OPT BD
JP30
J7
Kiss-off LED
J6
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Secondary Phone
Primary Phone
J9
Active LED
Active LED
Secondary
(Nonpower-Limited)
J8
DACT Phone Line Jacks
Primary
ANN-BUS
A B
- +
- +
GND PWR
TB3
JP43
+
NAC #4
+
NAC #3
PN 71252
4.7K , ½ watt End-of-Line Resistor
Special App lic at io n Power
(See Style Z illustrated near right edge of board).
Notification Appliance Circuits (see note 1)
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
+
NAC #2
+
NAC #1
+
+
+
+
PN 71252
4.7K , ½ watt
Power Limited)
End-of-Line Resistor
(Class B) (Supervised,
(See Style D illustrated
IDCs 1 through 5, Style B
near right edge of board).
Initiating Device Circuits
+
+
+
+
B
-
B
+
22
B
-
B
+
11
OUT3 OUT4
+ - + -
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
FIRE ALARM
TB7
Class A Converter Module
AC POWER
J3
-
B
+ - + - + - + - + -
11
B
+
TB4
-
B
22
B
+
-
B
11
B
+
+ - + -
J2
321
JP31
RST AUX
OUT1 OUT2
TB5
PWR
RST/NONRST
AUXPWR
TB9
-
-
+
+
2
4
1
3
ALARM
TROUBLE
ST
1
DEF
3
ABC
2 1
ENTER
ESC
CLEAR
6
JKL
89
5
GHI
PRS TUV
7
4
RESET
DRILL
MODE
_/.
#
0
QZ_
*
- +
J12
BATTERY
nonpower-limited
24 VDC, supervised,
Battery (see note 3)
J15
5-Zone Panel
Removing Ground Fault
Basic System Connections
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited ci rcuits
Supervise with a power supervision relay EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Notes:
1. MS-5UD-3(E) = 2.5 amps max. per NAC
MS-5UD-7(C/E)= 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-5UD-3(E): refer to “Remote
Synchronization Output” on page 30
3. 18 Amp Hour max. for MS-5UD-3(E)
Important!
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
26 Amp Hour max. for MS-5UD-7(C/E)
(Authority Having Jurisdiction).
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Power Supply Connector J15
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 9
MS-10UD Series Main Circuit Board
-
Style D (Class A) IDC
B B
+
11
TB1
J2
TB4/
TB6
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resi stors
+
Style Z (Class A) NAC
+
+
-
B
11 2
B
+
OUT1/3 OUT2/4
TB5/
TB7
OUT OUT
TB2
Class A Converter Module
USB Port for local programming using
a personal computer and PK-5X Utility
J11
NO NC C
A Fail Safe Trouble
Contacts shown below in normal
End-of-Line Resistor
condition (AC power with no alarm,
trouble or supervisory activity).
PN 71252
relay switches to the
Remote
Synchronization
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
Power Limited)
4.7K , ½ watt
(Class B) (Supervised,
(See Style D illustrated
near right edge of board).
IDCs 6 through 10, Style B
Initiating Device Circuits
+
NAC #4
+
NAC #3
PN 71252
4.7K , ½ watt End-of-Line Resistor
Special Application Power
(See Style Z illustrated near right edge of board).
Notification Appliance Circuits (see note 1)
NAC #1, #2, #3 & #4, S ty le Y (Class B) (Supervised, Power Limited)
+
NAC #2
+
NAC #1
+
+
+
+
PN 71252
4.7K , ½ watt
Power Limited)
End-of-Line Resistor
(Class B) (Supervised,
(See Style D illustrated
IDCs 1 through 5, Style B
near right edge of board).
Initiating Device Circuits
+
+
+
+
Supervisory*
NO NC CNO NC C NO NC C
Trouble*
Alarm*
NC position during
trouble conditions and
under loss of all power.
(* )Factory default relay programming
TB2
Cut this jumper to
enable Supervisory
relay when 4XTM
module is installed
J5
J4
JP24
TB8
4XTM OPT BD
JP30
Kiss-off LED
J6
TB6
Cut this jumper to supervise
the 4XTMF module when
and power-limited.
Requires ELR.4.7K
0.040 amps maximum.
Special App lica tion Power
24 VDC filtered, supervised
Output (see note 2)
J7
installed (see J4 & J5)
J9
Secondary Phone
Active LED
Primary Phone
Active LED
Secondary
(Nonpower-Limited)
J8
DACT Phone Line Jacks
Primary
ANN-BUS
A B
- +
- +
GND PWR
TB3
-
B
+ - + - + - + - + -
B
+
66
-
B B
+
44
-
B
+ - + -
B
+
33
OUT3 OUT4
JP43
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of A HJ).
FIRE ALARM
ALARM
TROUBLE
RESET
ENTER
DRILL
TB7
ESC
ST
Class A Converter Module
AC POWER
J3
-
B
+ - + - + - + - + -
11
B
+
TB4
-
B
22
B
+
-
B
11
B
+
+ - + -
J2
321
JP31
RST AUX
OUT1 OUT2
TB5
PWR
RST/NONRST
AUXPWR
TB9
-
-
+
+
2
4
1
3
1
DEF
3
ABC
2 1
CLEAR
6
JKL
5
GHI
4
PRS TUV
MODE
_/.
#
89
0
QZ_
7
*
J12
J15
- +
BATTERY
nonpower-limited
24 VDC, supervised,
Battery (s ee n o te 3)
10-Zone Panel
Removing Ground Fault
Basic System Connections
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Notes:
1. MS-10UD-3(E) = 2.5 amps max. per NAC
MS-10UD-7(C/E) = 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-10UD-3(E): refer to “Remote
Synchronization Output” on page 30
3. 18 Amp Hour max. for MS-10UD-3(E)
26 Amp Hour max. for MS-10UD-7(C/E)
Important!
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Power Supply Connector J15
10 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009

SECTION 1 Product Description

The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone F ACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise specified. The combination control and digital communicator panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compatible with System Sensor’s i transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 45
o
F (refer to System Sensor i3 Installation and Maintenance Instructions). In addition, the control panel is compatible with conventional input devices such as two-wire smo ke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to Fire•Lite Device Compatibility Document for a complete listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery level and telephone line integrity. Available accessories include local and remote upload/download software, remote annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone network. Local programming interrogation is also possible using the PS-Tools and the USB port on the FACP. Any personal computer with Windows of 2400 baud and PS-Tools may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data and current status.
3
detectors which are conventional smoke detectors that can
XP or newer, compatible modem with a speed
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, display alarm information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.
11
Product Description Product Features
The following versions of the MS-5UD and MS-10UD are available:
FACP Version Description
MS-5UD-3 Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-5UD-7 Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-5UD-7C Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator. This panel is approved for Canadian applications
MS-5UD-3E Five Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-5UD-7E Five Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-10UD-3 Ten Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-10UD-7 Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-10UD-7C Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator. This panel is approved for Canadian applications.
MS-10UD-3E Ten Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-10UD-7E Ten Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
Note: Unless otherwise specified, the information in this manual applies to all versions of the panels.

1.1 Product Features

Built-in DACT (Digital Alarm Communicator/Transmitter)
Style B (Class B) IDC (Initiating Device Circuit)
MS-5UD - five programmable IDCsMS-10UD - ten programmable IDCs
Four Style Y (Class B) NAC (Notification Appliance Circuit)
- special application power
Three programmable Form-C relays
Built-in Programmer
Touchtone/Rotary dialing
Programmable Make/Break Ratio
Optional Dress Panel DP-51050
A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED Annunciator module
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
ANN-BUS for connection to optional:
ANN-80 Remote LCD AnnunciatorANN-I/O LED DriverANN-S/PG Printer ModuleANN-RLY Relay ModuleANN-LED Annunciator Module
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History log with 256 event storage
12 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Specifications Product Description
Control Buttons
ACK (Acknowledge)Alarm SilenceSystem Reset/Lamp TestDrill
LED Indicators
Fire AlarmSupervisoryTroubleAC PowerAlarm SilencePrimary and Secondary Phone Line Active LEDs
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Alarm Verification
NACs Programmable for:
Silence Inhibit Auto-Silence Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)Selective Silence (horn-strobe mute)Temporal or Steady SignalSilenceable or Nonsilenceable
Automatic battery charger with charger supervision
Silent or audible walktest capabilities
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/Download of program and data
Optional CAC-5X Class A Converter Module for NACs and IDCs
Optional 4XTMF Transmitter Module

1.2 Specifications

Note: For wiring specifications, refer to "Wire Requirements" on page 151.
AC Power
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps MS-5UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-5UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-10UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-10UD-7C (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-5UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps MS-10UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps Wire size: minimum #14 AWG (2.0 mm Supervised, nonpower-limited
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 13
2
) with 600V insulation
Product Description Specifications
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp Supervised, nonpower-limited Maximum Charger Capacity: 18 Amp Hour battery for MS-5UD-3(E), MS-10UD-3(E) and 26 Amp Hour battery for MS-5UD-7(E), MS-10UD-7(E) [two 18 Amp Hour batterie s can be housed in F ACP cabinet. Lar ger batteries require separate battery box such as BB-26 or BB-55] Minimum Battery Size: 7 Amp Hour (12 Amp Hour for MS-5UD-7C & MS-10UD-7C)
Initiating Device Circuits - TB4 (and TB6 on MS-10UD only)
Alarm Zones 1 - 5 on TB 4 (MS-5UD and MS-10UD) Alarm Zones 6 - 10 on TB6 (MS-10UD only) Supervised and power-limited circuitry Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA max. Maximum Loop Resistance: 100 ohms (2,000 ohms per zone for linear heat detection) End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #712 52) Standby Current: 2 mA Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB5 and TB7
1
Four NACs Operation: Style Y (Class B) Special Application power Supervised and power-limited circuitry Normal Operating Voltage: Nominal 24 VDC Maximum Signaling Current: 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) (2.5 amp maximum per NAC); 7.0 amps for MS-5UD-7(E), MS-10UD-7(E) (3.0 amps maximum per NAC) End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252) Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay) Relay 2 (factory default programmed as fail-safe Trouble Relay) Relay 3 (factory default programmed as Supervisory Relay) Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see note 1) Power-limited Circuitry Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA (see note 1) Power-limited Circuitry Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable powerJumper pins 2 & 3 on JP31 for resettable power
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
1. T otal current for resettable power, nonresettable power and Notification Appliance Circuits must not exceed 3.0 amps for the FACP versions which are powered by the FLPS-3 power supply or 7.0 amps for the FACP versions which are powered by the FLPS-7 power supply.
14 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Controls and Indicators Product Description
Remote Sync Output - TB2
Remote power supply synchronization output, only required for the MS -5UD-3(E), MS-10UD­3(E) [refer to "Remote Synchronization Output" on page 30] 24 VDC nominal special application power Maximum current is 40 mA End-of-Line Resistor: 4.7KΩ Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an external device for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector circuits. All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.

1.3 Controls and Indicators

LCD Display The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
SYSTEM ALL NORMAL
10:00A 012105
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Figure 1.1 Membrane/Display Panel
9050udkypd.cdr
Four cursor keys (up, down, left and right)
Enter key
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 15
Product Description Digital Alarm Communicator/Transmitter
LED Indicators
LEDs are provided to annunciate the following conditions:
Fire Alarm - red LED
Supervisory - yellow LED
AC Power - green LED
System Trouble - yellow LED
Alarm Silence - yellow LED
Primary Phone Line Active (on circuit board) - red LED
Secondary Phone Line Active (on circuit board) - red LED
Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process monitor and supervisory conditio ns as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse 1 second on and 1 second off
Supervisory - pulse ½ second on and ½ second off
Process Monitor - pulse ¼ second on and ¼ second off

1.4 Digital Alarm Communicator/Transmitter

T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the following functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact IDSIA-DCS-8SIA-DCS-20
®
, programmable to rotary
16 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Components Product Description

1.5 Components

Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)
FLPS-7 for the MS-5UD-7(C/E), MS-10UD-7(C/E)
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050) which mounts inside the cabinet and trim-ring (TR-CE). The Canadian version is supplied standard with a modified dress panel and one ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.

1.6 Optional Modules and Accessories

CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS­10UD. Note that two Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP LCD display.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory. ANN-LED module is installed in dress panel for Canadian version.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050 Dress Panel
A dress panel DP-51050 is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel. The Canadian version is supplied standard with a modified dress panel.
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 17
Product Description Optional Modules and Accessories
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flush mounting of the cabinet.
Battery Box
The BB-26 or BB-55 battery box may be used to house two batteries greater than 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly from most IBM compatible personal computers (PC), running Windows program files can also be created and stored on the PC and then downloaded later to the control
panel. The P/N: PK-CD includes the Windows-based Programming Utility software on CD-ROM with on-line help file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of the PC to the USB port J11 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to "Remote Download" on page 130). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.
XP (or newer). FACP
18 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Telephone Requirements and Warnings Product Description

1.7 Telephone Requirements and Warnings

1.7.1 Telephone Circuitry

Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.

1.7.2 Digital Communicator

Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer:Fire•Lite Alarms One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: MS-5UD/MS-10UD FCC Registration Number: 1W6AL00B10UD Ringer Equivalence: 0.0B
Important! The DACT must not
Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company .
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to "Digital Communicator" on page 32 for an illustration of the proper installation of this equipment.
be used to dial a phone number that is call-forwarded.
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 19
Product Description Telephone Requirements and Warnings

1.7.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same
telephone line. The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACT A. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
20 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Telephone Requirements and Warnings Product Description

1.7.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspections authority, or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
10 Whitmore Road Woodbridge, Ontario L4L7Z4 Phone: (905) 856-8733 FAX: (905) 856-9687
IC Certificate Number: 2132A-10UD Ringer Equivalence Number (REN): 0.0B Load Number: 2
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 21

SECTION 2 Installation

The cabinet can be surface mounted or semi-flush mounted. The door is removable during the installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left . Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.1 Backbox Mounting

The circuit board contains static-sensitive components. Always ground yourself with a pr oper wrist strap before handling any boards so that static charges are removed from the body. Use static
!
suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
See Page
grounding stud: attach solid earth ground wire (refer to Figure 2.4 on page 25)
Mark and predrill hole in the wall for the center top keyhole mounting bolt us ing the
dimensions illustrated in Figure 2.2 on page 23
Install center top fastener in the wall with the screw head protrudingPlace backbox over the top screw, level and secureMark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting
Install remaining fasteners and tighten
MS-5UD Board on Chassis
mounting holes
mounting slots mounting studs
mounting slots
mounting tabs
22
MS-5UD Backbox
Figure 2.1 Chassis Mounting in Backbox
5UDBRDINBOX.CDR
Backbox Mounting Installation
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to
Hinge Slot for optional Dress Panel
avoid covering venting holes on top of box.
Mounting slots for optional Trim Ring
Semi­Flush mounting hole
Hinge Slot for optional Dress Panel
9050UDencl.cdr
Figure 2.2 Cabinet Dimensions
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 23
Installation Backbox Mounting
Figure 2.3 Backbox and Battery Box
9050UDcab.cdr
24 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Operating Power Installation

2.2 Operating Power

WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconn ecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Refer to AC Power in the section titled "Specifications" on page 13, for power and current requirements for each FACP version. Run a pair of wires (with ground conductor) from the protected premises main breaker box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code, use 14 AWG (2.00 mm equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 A WG (2.00 mm in the backbox. Do not use conduit for the Earth Ground connection since this does not provide
reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
2
, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other
2
)] to the grounding stud
!
FLPS-7
Power Supply
AC Power
Hot (L1)
Earth
Neutral (L2)
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
MS-5UDC-7(C)(E)
MS-10UD-7(C)(E)
FLPS-3
Power Supply
AC Power
AC Hot
AC Neutral
Earth
MS-5UD-3(E)
MS-10UD-3(E)
-
Ground Wire
J12
+
Ground Wire
to batteries
5ud_10udacpowr.c
J12
-
+
to batteries
Figure 2.4 Operating Power Connections
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 25
Installation Input Circuits

2.3 Input Circuits

The MS-5UD has five IDCs (Initiating Device Circuits) and the MS-10UD has ten IDCs. Each circuit is compatible with System Sensor’s i
3
when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the detector rating of approximately 45
limit for each IDC is 100 ohms (2,000 ohms per zone for linear heat detection). The field wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to "CAC-5X Class A Converter Module" on page 33.
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC 4-wire smoke detector power (500 mA maximum)
UL listed Power Supervision Relay
UL listed compatible 4-wire smoke detector
manual pull stations
heat detectors
smoke detectors which generate a maintenance signal
o
F. The maximum loop resistance
3
smoke detectors, any
UL listed compatible 2-wire smoke detectors
Dummy load all unused circuits - 4.7 K resistor (P/N: 71245)
Ω, ½ watt
Figure 2.5 IDC Connections
26 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
ms-10UDidc.cdr
Input Circuits Installation
Combination Waterflow/Su pervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distin guish bet ween an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit .
Class B Initiating Device Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Supervisory Switch (tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch (waterflow)
Dummy load all unused circuits - 4.7 KΩ, ½ watt resistor (P/N: 71245)
Figure 2.6 Style B Combination Circuit on Zone 2
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circu it after the In-
Line Resistor as shown in Figure 2.6
ms10udcomboIDC.cdr
Program the FACP Initiating Device Circuit as a Combination circuit as described in
"Input Zones" on page 59. Note that since a Waterflow Supervisory Switch is included in
a Combination circuit, the waterflow delay must be taken into consideration. Refer to "Waterflow De lay" on pa ge 75.
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition is cleared) if the Combo Autoresettable Supervisory type code is selected
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 27
Installation Output Circuits

2.4 Output Circuits

2.4.1 Notification Appliance Circuits

T otal current drawn from the four Style Y (Class B) Notification Appliance Circuits as well as other DC power outputs cannot exceed 3.0 amps for the MS-5UD-3(E), MS-10UD-3(E) [2.5 amp maximum per NAC] powered by the FLPS-3 power supply or 7.0 amps for the MS-5UD-7(C/E), MS-10UD-7(C/E) [3.0 amps maximum per NAC] powered by the FLPS-7 power supply (refer to "Power Supply Calculations" on page 134). Each circuit is supervised, power-limited and provides special application power. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing the optional Class A Converter module. Refer to "CAC-5X Class A Converter Module" on page 33.
Class B Notification Appliance Circuits (supervised and power-limited)
Ω, ½ watt resistor P/N:71252
4.7 K
Polarized Bell
Polarized Strobe
Polarized Horn
Notification Appliance Circuit polarity shown in alarm condition
Polarized Bell
Polarized Horn-Strobe
Polarized Horn
Dummy load any unused circuits (P/N: 71245)
+ - + -
ms-10UDnac.cdr
Figure 2.7 NAC Connections
28 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Output Circuits Installation

2.4.2 Special Application DC Power Output Connections

Special Application Resettable and Nonresettable 24 VDC power is available on the MS-5UD and MS-10UD control panel.
Special Application 4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors can be obtained from these terminals (power-limited)
Special Application Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be obtained from these terminals (power-limited)
Jumper JP31 pins 1 & 2 for nonresettable power (as illustrated in figure to right)
-
4
+
3
-
2
+
1
ms-10UDtb9.cdr
Jumper JP31 pins 2 & 3 for resettable power
Figure 2.8 Special Application Auxiliary Power

2.4.3 Relays - Programmable

The MS-5UD and MS-10UD control panels provide a factory default programmed alarm relay, fail­safe trouble relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer to "Relays" on page 71). Each Form-C relay is rated for 2 amps @ 30VDC (resistive) and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
Note: Relay contacts are shown with power applied to the panel and no active troubles, alarms or supervisories. The Trouble Relay is a fail-safe relay which will transfer on any trouble or total power failure.
ms10udrelay.cdr
Figure 2.9 Relay Terminals
MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009 29
Installation Output Circuits

2.4.4 Remote Synchronization Output

Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard to individuals. Devices connected directly to the control panel’s NAC can be synchronized as described in "Synchronized NAC Operation" on page 69.
Notification appliances connected to remote power sources may require synchronization with the FACP’s devices. For the MS-5UD-3(E), MS-10UD-3(E), this can be accomplished by connecting the Remote Synchronization Output from TB2 of the FACP to a compatible sync input of a power supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics the signal on NAC 1 (Out 1). This allows the devices connected to the power supply to be synchronized with the devices connected to Out 1 on the FACP.
For the MS-5UD-7(C/E), MS-10UD-7(C/E), the Remote Sync Output is not
required. Synchronization for remote power supplies is provided directly from NAC1 (Out 1). Note that NAC 1 (Out 1) must be programmed for sync operation when used for this purpose.
The Remote Synchronization Output is power-limited and supervised and requires a 4.7KΩ ELR resistor at the remote power supply end of the wiring.
Remote Power Supply
Sync Input
4.7KΩ ELR
Remote Sync Output
FACP main circuit board
Figure 2.10 Remote Sync Output
30 MS-5UD and MS-10UD Series Manual — P/N 52626:B1 6/30/2009
Loading...
+ 130 hidden pages