Fire-Lite Alarms MMF-300 Series, MDF-300, MMF-300, MMF-301, MMF-302 Quick Start Manual

April 23, 2001
MMF-300 Series/MDF-300MMF-300 Series/MDF-300
MMF-300 Series/MDF-300
MMF-300 Series/MDF-300MMF-300 Series/MDF-300
Addressable Monitor ModulesAddressable Monitor Modules
Addressable Monitor Modules
Addressable Monitor ModulesAddressable Monitor Modules
www.firelite.com
GENERALGENERAL
GENERAL
GENERALGENERAL
Four different monitor modules are available for Fire•Lite Alarm’s MS-9200 and MS-9600 intelligent fire alarm control panels to suit a variety of applications. Monitor modules are used to supervise a circuit of dry-contact input devices, such as con­ventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (MMF-302).
MMF-300 (Replaces M300) — The MMF-300 Moni-
tor Module is a standard-sized module (typically mounts to a 4" [101.6 mm] square box) that supervises either a Class A (Style D) or Class B (Style B) circuit of dry-contact input de­vices.
MMF-301 (Replaces M301) — The MMF-301 is a Min-
iature Monitor Module (a mere 1.3" (33.02 mm) H x 2.75" (69.85 mm) W x 0.5" (12.70 mm) D) used to supervise a Class B (Style B) circuit. Its compact design allows the MMF­301 to be mounted in a single-gang box behind the device it is monitoring.
MMF-302 (Replaces M302) — The MMF-302 Inter-
face Module is a standard-sized module used to monitor and supervise compatible two-wire, 24 volt, smoke detectors on a Class A (Style D) or Class B (Style B) circuit.
MDF-300 (New) — The MDF-300 Dual Monitor Module
is a standard-sized module (typically mounts to a 4" [101.6 mm] square box) that supervises two Class B (Style B) cir­cuits of dry-contact input devices.
MMF-300 MONITOR MODULEMMF-300 MONITOR MODULE
MMF-300 MONITOR MODULE
MMF-300 MONITOR MODULEMMF-300 MONITOR MODULE
• Built-in type identification automatically identifies this de­vice as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional power required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct Decade 01 – 99 (MS-9200) and 01-159 (MS-9600) entry of address.
• LED flashes green during normal operation and latches on steady red to indicate alarm.
The MMF-300 Monitor Module is intended for use in intelli­gent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro­vides either a two-wire or four-wire Class A or Class B fault­tolerant Initiating Device Circuit (IDC) for normally-open-con­tact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The MMF-300 can be used to replace M300 modules in existing systems.
MMF-300 Applications — Use to monitor a zone of
four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact alarm activation devices. May also be used to monitor normally­open supervisory devices with special supervisory indica­tion at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class D) Initiating
terminates the Style B circuit. No resistor is required for su­pervision of the Style D circuit. Maximum IDC resistance is 1,500 ohms.
MMF-300 Operation — Each MMF-300 uses one of
99 (MS-9200) or 159 (MS-9600) available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limita­tions on the loop).
MMF-300 Specifications
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Average operating current: 400 µA (LED flashing).
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box.
Device Circuit. A 47K ohm End-of-Line Resistor (provided)
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applica­tions or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, Toll Free FAX: (877) 699-4105, FAX Back:(888) 388-3299.
MMF-300, MMF-302 and MDF-300
Section: Addressable Devices
7300-0075:185
9
9
7
7
6
6
5
5
4
4
8
3
3
8
2
2
1
1
0
0
TENS
TENS
7
7
7
7
6
6
5
5
4
4
6
6
3
3
2
2
1
1
0
0
5
5
ONES
LOOP ADDRESS
LOOP
ONES
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
8
8
9
9
ADDRESS
0
0
1
1
2
2
3
3
4
4
Made in the U.S.A.
DF-52121 — Page 1 of 3
DF-52121 E-325
52121m300.wmf
MMF-301 MINI MONITOR MODULEMMF-301 MINI MONITOR MODULE
MMF-301 MINI MONITOR MODULE
MMF-301 MINI MONITOR MODULEMMF-301 MINI MONITOR MODULE
• Built-in type identification automatically identifies this de­vice as a monitor module to the MS-9200.
• Powered directly by two-wire SLC Loop. No additional power required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct-dial entry of address (01-99).
The MMF-301 Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The MMF-301 is intended for use in intelligent, two-wire systems where the individual address of each mod­ule is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-contact fire alarm and security devices. The MMF-301 can be used to replace M301 module in existing systems.
1
2
3 4
5
6
ADDRESS
LOOP
9
8
ONES
0
1
2
3 4
5
6
7
MMF101-wired.wmf
12
11
13
10
14
9
0
15
7
8
TENS
MMF-301 Applications — Use to monitor a single de-
vice or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally­open supervisory devices with special supervisory indica­tion at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the circuit.
MMF-301 Operation — Each MMF-301 uses one of
159 (MS-9600 only) available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Ini­tiating Device Circuit (IDC).
MMF-301 Specifications
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 375 µA maximum.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3" (33.02 mm) high x 2.75" (69.85 mm) wide
x 0.5" (12.70 mm) deep.
Wire length: 6" (152.4 mm) minimum.
Page 2 of 3 — DF-52121
MMF-302 INTERFACE MODULEMMF-302 INTERFACE MODULE
MMF-302 INTERFACE MODULE
MMF-302 INTERFACE MODULEMMF-302 INTERFACE MODULE
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power source (resettable).
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address (01-99).
• LED flashes during normal operation (this is a program­mable option).
• LED latches steady to indicate alarm on command from control panel.
The MMF-302 Interface Module is intended for use in intel­ligent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two­wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional de­tectors back to the control panel. All two-wire detectors be­ing monitored must be UL compatible with the module.
MMF-302 Applications — Use the MMF-302 to moni-
tor a zone of two-wire smoke detectors. The monitored cir­cuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for Style D ap­plication.
MMF-302 Operation — Each MMF-302 uses one of
159 (MS-9600 only) available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Ini­tiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop).
MMF-302 Specifications
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Average operating current: 270 µA (LED flashing).
EOL resistance: 3.9K ohms.
External supply voltage
DC voltage:
18 to 28 volts power limited.
0.1 VRMS maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square
x 2.125" (53.975 mm) deep box.
MDF-300 DUAL MONITOR MODULEMDF-300 DUAL MONITOR MODULE
MDF-300 DUAL MONITOR MODULE
MDF-300 DUAL MONITOR MODULEMDF-300 DUAL MONITOR MODULE
Built-in type identification automatically identifies this de­vice as two monitor modules to the control panel.
Powered directly by the two-wire SLC loop. No additional power required.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address 01 159 on the MS-9600.
LED flashes green during normal operation and latches
on steady red to indicate alarm.
The MDF-300 Dual Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides two independant two-wire fault-tolerant Initiating Device Circuits (IDCs) at two separate, consecutive ad-
(between Terminals T3 and T4):
Ripple voltage:
Current:
90 mA per module maximum.