Fire-Lite Alarms I300-6 Installation And Maintenance Instructions Manual

TO BACK OF CABINET
INSTALLATION AND MAINTENANCE INSTRUCTIONS
I300-6 Six Fault Isolator Module
SPECIFICATIONS
Normal Operating Voltage: 15-32VDC Stand-By Current: 2.7 mA Maximum Current Draw: 102 mA Temperature Range: 32°F to 120°F (0°C to 49°C) Humidity: 10 to 93% Non-condensing Dimensions: 6.8˝H × 5.8˝W × 1.0˝D Accessories: CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-3 Series Cabinets; CAB-4 Series Cabinets Wire Gauge: 12-18 AWG
I56-4097-000
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect the power to the control panel before installing the modules. This system contains static sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. The housing cabinet should be metallic and suitably grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The I300-6 Six Fault Isolator Module provides six equivalent circuits that will allow a portion of the communications loop to continue operating when a short circuit occurs on that loop. An amber LED indicator will blink in the noromal state for each of the six inputs and will latch on during a short circuit condition. The module will automatically restore the communications loop to normal condition when the short circuit is removed.
CONTENTS INCLUDE:
(6) 1 × 4 Terminal Blocks (2) 1¼˝ (32mm) Stand offs (4) Machine Screws (2) Nuts
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible FireLite system control panel.
COMPONENTS
Following are descriptions of the I300-6 mounting frameworks. There are two mounting options for I300-6 modules:
• Up to six I300-6 modules can be installed on a CHS-6 in a CAB-3, CAB-4 or BB-25 cabinet
• One or two I300-6 modules can be installed in a BB-XP cabinet
Chassis
The CHS-6 chassis is used to mount I300-6 modules in a BB-25, CAB-3 or CAB-4 Series cabinet. It accommodates up to six I300-6 modules in a single cabinet row three modules wide and two modules deep.
FIGURE 1. CHS-6 CHASSIS:
MOUNT WITH
SELF-THREADING SCREWS
The BB-XP cabinet has a built-in chassis that will accommodate one or two I300-6 modules.
FIGURE 2. BB-XP CABINET:
C0236-01
C0234-06
1 I56-4097-000
The front I300-6 module positions of each chassis are offset below the rear I300-6 module positions so that all of the status indicators are visible.
Cabinets
A BB-25, CAB-3 or CAB-4 Series cabinet will house the CHS-6 chassis with up to six I300-6 modules installed on it. Refer to cabinet installation documents for dimensions.
The BB-XP cabinet houses one or two I300-6 modules on the internal chassis that is part of the cabinet. Refer to cabinet installation documents for dimen­sions.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes provided in the back surface of the cabinet.
FIGURE 3. TYPICAL MOUNTING HOLE LOCATIONS:
BACKBOX MOUNTING HOLES
C0235-00
2. Chassis Installation
The CHS-6 chassis is mounted in the BB-25, CAB-3 or CAB-4 Series cabinets. It is shipped with two self-threading screws, which are used to fasten the chassis to the back wall of the cabinet (see Figure 4).
FIGURE 4: MOUNTING THE CHS-6 CHASSIS
Step 1: Insert the bottom of the I300-6 module down into a rear slot on the
chassis.
Step 2: Carefully pivot the upper edge of the board back towards the back of
the chassis until it touches the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Wire the modules according to the instructions in this manual.
The steps in Figures 6A – 6C describe and illustrate module installation when the rear chassis position and the position in front of it will be filled. Front position installation is possible only if the rear position is filled with a module.
FIGURE 6A. INSTALLATION OF I300-6 MODULE IN A REAR CHASSIS POSITION, METHOD TWO:
1
C0225-01
Step 1: Install two long standoffs in the lower mounting holes using two 4-40
nuts as shown.
FIGURE 6B.
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
C0236-00
The BB-XP cabinet comes with the chassis already installed, so no mounting is necessary.
3. Module Installation
There are two methods for installing a module in the rear position of a chas­sis. Method one is for installation of a rear module only, when no module will be installed in front of it. Refer to Figure 5 for instructions. Method two is for installation of a rear module when another module will be installed in the chassis position in front of it. Refer to Figures 6a and 6b for method two. All necessary screws and standoffs are supplied with the modules.
FIGURE 5. INSTALLATION OF REAR MODULE ONLY, METHOD ONE:
2
3
1
3
4
2
C0249-01
Step 2: Insert the bottom of the I300-6 module down into a rear slot on the
chassis.
Step 3: Carefully pivot the upper edge of the board back towards the back of
the chassis until it touches the two standoffs on the board.
Step 4: Align two 4-40 screws with the two standoffs on the chassis and
tighten.
Step 5: Wire the modules according to the instructions in this manual.
FIGURE 6C. INSTALLATION OF I300-6 MODULE IN FRONT CHASSIS