INSTALLATION AND MAINTENANCE INSTRUCTIONS
3
2
1
3
2
1
3
2
1
(–)
(+)
+-
UL LISTED COMPATIBLE
CONTROL PANEL
CAUTION: DO NOT LOOP WIRE
UNDER TERMINAL 1 OR 2.
BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
CLASS A OPTIONAL WIRING
REMOTE
ANNUNCIATOR
(–)
(+)
TENS ONES
9
10
11
12
13
14
15
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
I56-3657-002R
H355, H355R, and H355HT
Intelligent Plug-In Temperature Sensors
SPECIFICATIONS
Diameter: 6.1˝ (155 mm) installed in B350LP
Height: 2.0˝ (51 mm)
Weight: 4.8 ounces (137 gm)
Installation Temperature: –4°F to 100°F (–20°C to 38°C), H355 and H355R; –4°F to 150°F (–20°C to 66°C), H355HT
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Mounting: B350LP flanged base
Voltage Range: 15 to 32 Volts DC Peak
Standby Current: 300 µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)
LED Current: 6.5 mA @ 24 VDC
Fixed Temperature Rating: 135°F (57°C) H355 and H355R; 190°F (88°C) H355HT
Rate of Rise Detection: Responds to greater than 15°F/minute; H355R
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with the National Fire Protection Association (NFPA);
see NFPA 72.
Before installing sensors, please read the system wiring and installation manual thoroughly. This manual provides detailed information on sensor spacing, placement, zoning, and special applications. Copies of these manuals are
available from Fire-Lite.
GENERAL DESCRIPTION
Models H355, H355R, and H355HT are intelligent sensors that utilize a stateof-the-art thermistor sensing circuit for fast response. These sensors are designed to provide open area protection with 50 foot spacing capability. For
installations which must comply with FM3210, see note below. Model H355 is
a fixed temperature sensor with 135° F fixed temperature alarm. Model H355R
is a rate-of-rise temperature sensor with 135° F fixed temperature alarm.
Model H355HT is a high temperature sensor with 190° F fixed temperature
alarm.
Two LEDs on each sensor light to provide a local, visible sensor indication.
Remote LED annunciator capability is available as an optional accessory (Part
No. RA400Z).
Models H355, H355R, and H355HT require compatible addressable communications to function properly. Connect these sensors to listed-compatible control panels only.
NOTE: Per FM3210
The H355 and H355HT are classified as fixed temperature thermal detectors:
A thermal detector that responds when the operating element of the detector
reaches a specified temperature. The actual temperature surrounding the sensing element is often much greater than the rated temperature due to the thermal lag.
The H355R is classified as a rate-compensated thermal detector: A thermal
detector that responds to a specified fixed temperature, regardless of the rate of
temperature rise.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes and the Authority Having Jurisdiction. Proper wire
gauges should be used. The installation wires should be color coded to limit
wiring mistakes and ease system troubleshooting. Improper connections will
prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram,
see Figure 1.
2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base
4. After all sensors have been installed, apply power to the control unit and
FL-400-001 1 I56-3657-002R
while turning it clockwise to secure it in place.
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
FIGURE 1. WIRING DIAGRAM:
C0129-00
FIGURE 2:
C0162-00
TAMPER RESISTANCE
The sensor base includes a tamper proof feature which when activated prevents removal of the sensor without the use of a tool. See the installation
instruction manual for the sensor base for details in using this feature.
TESTING SENSITIVITY
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors

offer maximum performance when tested and maintained in compliance with
LED
TEST MAGNET
MARKER
LED
TEST
MAGNET
MARKER
NFPA 72.
A. Test Magnet (p/n M02-04-01 or M02-09-00)
1. Place the optional test magnet against the cover in the magnet test
area, as shown in Figure 3, to activate the test feature.
2. The LEDs should latch on within 10 seconds, indicating alarm and
annunciating the panel.
3. Reset the detector at the system control panel.
B. Direct Heat Method (Hair dryer of 1000 – 1500 watts)
1. From the side of the detector, direct the heat toward the sensor. Hold
the heat source about 6 inches (15 cm) away to prevent damage to the
cover during testing.
2. The LEDs on the detector should light when the temperature at the
detector reaches the alarm set point. If the LEDs fail to light, check the
power to the detector and the wiring in the detector base.
3. Reset the detector at the system control panel.
Detectors that fail these tests should be cleaned as described under MAINTENANCE and retested. If the detectors still fail these tests, they should be
returned for repair.
FIGURE 3. VIEWS SHOWING POSITION OF TEST MAGNET:
C0152-00
MAINTENANCE
NOTE: Before cleaning notify the proper authorities that the system is undergoing maintenance, and therefore the system will temporarily be out of service. Disable the loop or system undergoing maintenance to prevent unwanted
alarms.
It is recommended that the sensor be removed from its mounting base for
easier cleaning and that sensors be cleaned at least once a year. Use a vacuum
cleaner to remove dust from the sensing chamber.
FIGURE 4:
Please refer to insert for the Limitations of Fire Alarm Systems
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
FL-400-001 2 I56-3657-002R
©2008 Fire-Lite
C0151-00
FCC STATEMENT