Fire-Lite Alarms ES-200XC, ES-200X User Manual

Addressable Fire Alarm Control Panel
ES-200X
ES-200XC
Manual
Document LS10131-000FL-E Rev: C 7/25/2018 ECN:18-323
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifica­tion capability—can provide early warning of a d eveloping fire. Such a system, however, doe s not assure protection against property damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication methods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of Sys tem Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http:// www.systemsenso r.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warni ng or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chim­neys, even wet or humid areas may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where de t ec t ors are located.
• Smoke particles may be blown away fr om detectors by air out­lets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various level s of smoke density. If such density levels are not created by a devel­oping fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limita­tions. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate­of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signal­ing, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.
Audible warning devices such as bells, horns, strobes, speak­ers and displays may not alert people if these devices are located
on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert peo­ple with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:
• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.
• Voice messagi ng systems must be designed t o meet intelligibili ty requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly dis­seminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audib le devices, such as h orns and bell s, can hav e different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A life safety system will not operate without any e lectrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically c ompatible with the control panel. It is e ssential to use only equipment listed f or service with your control panel.
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backu
p radio transmission systems are recommended.
The most common cause of life safety system malfuncti on i s i na d­equate maintenance. To keep the entire life safety system in excel­lent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Envi­ronments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Mainte­nance should be scheduled as required by National and /or lo cal fire codes and should be performed by authorized professional life safety system installers only. Adequate written records of all inspec­tions should be kept.
Limit-D2-2016
2 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con­nected to the fire alarm control panel. Disconnect all sourc es of
power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be
tested in accordance with NFPA 72 after any programming opera­tion or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of syst em compo­nents, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be aff ected by a change must b e 100% tested. In addition, to ensure that other operations are not inadver­tently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/ 32-120º F and at a relative humidity . However, the useful life of the system's standby batteries and the electro nic compo nent s may be adversely affected by extreme temperature ranges and humidity . Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from light­ning transients and interference, pr oper grounding will reduce sus­ceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Con­sult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or pri nt ed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tighten­ing may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any cir­cuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interfer­ence to radio communications. It has been tested and foun d to comply with the limits for class A computing devices pur­suant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart­ment of Communications.
Le present appareil numerique n'emet pas de bruits radio­electriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LiteSpeed™ and Lite-Connect™ are trademarks; and Fire-Lite® Alarms, Honeywell®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about softwa re and the app rop riate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
Product name and version number (if applicable)
Printed manual or online Help
T opic Title (for online Help)
Page number (for printed manual)
Brief description of content you think should be improved or corrected
Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018

Table of Contents

Section 1: Product Description...................................................................................................................................... 13
1.1: Features and Options .......................................................................................................................................................................................13
1.2: Specifications...................................................................................................................................................................................................14
1.3: Controls and Indicators....................................................................................................................................................................................16
1.4: Components.....................................................................................................................................................................................................16
1.4.1: Intelligent Addressable Detectors.........................................................................................................................................................17
1.4.2: Intelligent Addressable Modules..........................................................................................................................................................17
1.4.3: Addressable Device Accessories..........................................................................................................................................................17
End-of-Line Resistor Assembly..............................................................................................................................................................17
Power Supervision Relay........................................................................................................................................................................17
EOL-C(R/W) Mounting Plate.................................................................................................................................................................17
1.5: Optional Modules ............................................................................................................................................................................................17
1.6: Accessories ......................................................................................................................................................................................................18
1.6.1: FS-Tools Programming Utility.............................................................................................................................................................18
1.6.2: Dress Panel ....................... ............................ ... ............................. ........................................................................................................18
1.6.3: Trim Ring............ ............................. ............................. .. ............................. ...........
1.6.4: Battery Box........... ... ............................. ............................. ............................ .......................................................................................18
BB-26......................................................................................................................................................................................................18
BB-55F....................................................................................................................................................................................................18
1.6.5: Battery Charger. .. ............................. .......................................................... ...........................................................................................18
CHG-75 Battery Charger........................................................................................................................................................................18
CHG-120F Battery Charger....................................................................................................................................................................19
1.6.6: ECC-50/100..........................................................................................................................................................................................19
1.6.7: ECC-FFT .................................................... ............................. ............................. ................................................................................19
1.6.8: W-GATE Wireless Gateway .......................................... ......................................................................................................................19
1.6.9: ANN-BUS Annunciators/Modules............................. .. .......................................................... .. ............................................................19
Guidelines...............................................................................................................................................................................................19
ANN-80/ANN-100 Remote Fire Annunciators......................................................................................................................................19
ANN-S/PG Serial/Parallel Interface Module..........................................................................................................................................19
ANN-I/O LED Driver Module ...............................................................................................................................................................20
ANN-LED Annunciator Module............................................................................................................................................................20
ANN-RLY Annunciator Module............................................................................................................................................................20
1.7: Getting Started.................................................................................................................................................................................................20
1.8: Telephone Requirements and Warnings...........................................................................................................................................................20
Telephone Circuitry..................................................................................... .. .......................................................................................20
1.8.1:
1.8.2: Telephone Company Rights and Warnings..........................................................................................................................................21
1.8.3: For Canadian Applications ...................................................................................................................................................................21
Section 2: Installation ....................................... ... .... ... ... ... ... .... ... ... ... .... ... ... ... .... ... ... ... ... ................................................. 22
2.1: Mounting the Backbox ....................................................................................................................................................................................22
2.2: Power...............................................................................................................................................................................................................25
2.2.1: AC Power and Earth Ground Connection ............................................................................................................................................25
2.2.2: Battery Power ..................... .. ............................. ............................. ......................................................................................................25
2.2.3: Special Application DC Power Output Connection ........................................... .. ................................................................................26
2.3: Relays ..............................................................................................................................................................................................................26
2.4: Notification Appliance Circuits.......................................................................................................................................................................26
2.4.1: Class B NAC Wiring .................................. .. ............................. ... ............................. ...........................................................................27
2.4.2: Class A NAC Wiring..... ....................................................................................... .. ..............................................................................27
2.5: Remote Synchronization Output......................................................................................................................................................................28
2.6: UL Power-limited Wiring Requirements.........................................................................................................................................................29
2.7: IPOTS-COM Communicator...........................................................................................................................................................................30
Wiring.....................................................................................................................................................................................................30
Dip Switches...........................................................................................................................................................................................30
2.8: Optional Module Installation...........................................................................................................................................................................31
2.8.1: CELL-CAB-FL/CELL-MOD................................................ .. .............................................................................................................31
Installation ..............................................................................................................................................................................................31
Wiring.....................................................................................................................................................................................................31
2.8.2: PWRMOD24 NAC Expander...............................................................................................................................................................31
Installation and Wiring ...........................................................................................................................................................................31
2.8.3: 4XTMF Transmitter Module Installation.............................................................................................................................................31
2.8.4: ANN-BUS Annunciators/Modules............................. .. .......................................................... .. ............................................................33
..............................................................................18
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 5
Table of Contents
ANN-BUS Wiring ..................................................................................................................................................................................33
ANN-BUS Device Addressing...............................................................................................................................................................36
ANN-80 Remote Fire Annunciator.........................................................................................................................................................36
ANN-100 Remote Fire Annunciator.......................................................................................................................................................38
ANN-S/PG Serial/Parallel Interface Module..........................................................................................................................................39
ANN-I/O LED Driver Module ...............................................................................................................................................................41
ANN-LED Annunciator Module............................................................................................................................................................43
ANN-RLY Annunciator Module............................................................................................................................................................45
2.8.5: Printer ............... ............................. ............................. ............................. .............................................................................................46
Printer Configuration..............................................................................................................................................................................46
2.8.6: ECC-FFT Firefighter Telephone ..........................................................................................................................................................47
W-GATE Wireless Gateway ................ .. ............................. .................................................................................................................47
2.8.7:
2.9: Automatic Audio Panel Control.......................................................................................................................................................................47
Section 3: Programming................................................................ ... .... ... ... ... .... ... ... ... ... .... ... .......................................... 49
3.1: Programming Data Entry.................................................................................................................................................................................49
3.2: User Programming...........................................................................................................................................................................................50
3.3: Initial Power-up ...............................................................................................................................................................................................51
3.4: Programming Screens Description ..................................................................................................................................................................51
3.5: Programming and Passwords...........................................................................................................................................................................51
3.6: Master Programming Level.............................................................................................................................................................................52
3.6.1: Autoprogram......... ................................................................................................................................................................................52
3.6.2: Point Program.......................................................................................................................................................................................53
Detector Programming............................................................................................................................................................................53
Module Programming.............................................................................................................................................................................60
3.6.3: Zone Setup................................ ............................. ............................. ..................................................................................................68
Enable .....................................................................................................................................................................................................68
Disable ....................................................................................................................................................................................................68
Special Purpose Zone..............................................................................................................................................................................69
s Installed........................................................................................................................................................................................69
Zone
Zones Enabled.........................................................................................................................................................................................69
Zones Disabled .......................................................................................................................................................................................69
Zone Type...............................................................................................................................................................................................70
Zones Available ......................................................................................................................................................................................70
Zone Message .........................................................................................................................................................................................70
3.6.4: Loop Setup............................................................................................................................................................................................71
Class........................................................................................................................................................................................................71
Loop Protocol .........................................................................................................................................................................................71
Device Addressing..................................................................................................................................................................................71
3.6.5: System Setup ........................................ ............................. ............................ .......................................................................................71
Function Keys............................................... ........................................................ ..................................................................................72
Banner.....................................................................................................................................................................................................73
Time-Date...............................................................................................................................................................................................73
Timers.....................................................................................................................................................................................................74
NAC (Notification Appliance Circuit) ........................... ............................. .. ............................. .. ..........................................................76
Relays......................................................................................................................................................................................................78
Canadian Option .....................................................................................................................................................................................79
Waterflow Silenceable..... ... ............................ ............................. ............................. ..............................................................................79
MNS Override................ ............................. .. ............................. .. ............................. ..............................................................................80
Auxiliary Power......................................................................................................................................................................................80
Trouble Reminder...................................................................................................................................................................................80
Language.................................................................................................................................................................................................80
Charger Enable ................ ... ............................ ............................. ............................. ..............................................................................80
4XTMF Supervision ...............................................................................................................................................................................80
Remote Sync Enable...............................................................................................................................................................................80
3.6.6: History ...................................................... ............................. ............................. ..................................................................................81
View Events............ ............................. ............................. ............................. .........................................................................................81
Erase History...........................................................................................................................................................................................81
3.6.7: Communicator ........................ ............................. .. ............................. ..................................................................................................81
Communicator Installed..........................................................................................................
POTS Settings..................... ............................ ............................. ...........................................................................................................82
IP Settings...............................................................................................................................................................................................83
................................................................81
6 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Table of Contents
Primary and Secondary Communication Paths ......................................................................................................................................84
Trouble Report Limit (Dialer Runaway Prevention)..............................................................................................................................86
Report Style ............................................................................................................................................................................................87
Event Codes...................................................................... ......................................................................................................................87
3.6.8: Annunciators................ ............................. .. ............................. .. ............................. ..............................................................................90
ANN-BUS Setup....................................................................................................................................................................................90
ANN-BUS Options.................................................................................................................................................................................97
3.6.9: Password Change..................................................................................................................................................................................99
Invalid Password..................... .. ............................. ............................. ............................. .......................................................................99
3.6.10: Clear Program...................................................................................................................................................................................100
3.6.11: Program Check .................................................................................................................................................................................100
3.7: Maintenance Programming Level..................................................................................................................................................................101
3.7.1: Disable Point. ............................ ... ............................. ..........................................................................................................................101
3.7.2: History ...................................................... ............................. ............................. ................................................................................102
3.7.3: Program Check .................................................... .. ............................. ... .............................................................................................102
3.7.4: Walktest......................................... ............................. ............................. .. .........................................................................................103
3.7.5: System............. ............................. ............................. ............................. .............................................................................................104
3.7.6: Zone Setup................................ ............................. ............................. ................................................................................................104
Section 4: Operating Instructions................................................................................................................................ 106
4.1: Panel Control Buttons....................................................................................................................................................................................106
4.1.1: Acknowledge......................................................................................................................................................................................106
4.1.2: Alarm Silence ............................................... ............................. ............................. ............................................................................106
4.1.3: Drill/Hold 2 Sec..................................................................................................................................................................................106
4.1.4: Reset ................. ............................. .. ............................. ............................. .........................................................................................106
4.1.5: Function Keys F1-F4..........................................................................................................................................................................106
4.2: LED Indicators...............................................................................................................................................................................................106
4.3: Normal Operation ..........................................................................................................................................................................................107
4.4: Trouble Operation..........................................................................................................................................................................................107
4.5: Alarm Operation ............................................................................................................................................................................................108
4.6: CO Alarm Operation......................................................................................................................................................................................109
4.7: Supervisory Operation...................................................................................................................................................................................109
4.8: Process Monitor Operation............................................................................................................................................................................110
4.9: Hazard/Tornado Condition Operation...........................................................................................................................................................110
4.10: Medical Alert Condition Operation.............................................................................................................................................................110
4.11: Mass Notification Operation... ... ............................ ... ......................................................... ..........................................................................111
4.12: NAC Operation............................................................................................................................................................................................111
4.13: Programmed Zone Operation ......................................................................................................................................................................111
4.14: Disable/Enable Operation............................................................................................................................................................................111
4.15: Waterflow Circuits Operation......................................................................................................................................................................111
4.16: Detector Functions.......................................................................................................................................................................................111
4.17: Time Functions: Real-Time Clock................... ............................. .. ............................. .. ..............................................................................112
4.18: Synchronized NAC Operation.....................................................................................................................................................................112
4.19: Coded Operation..........................................................................................................................................................................................112
4.20: Presignal ......................................................................................................................................................................................................112
4.21: Positive Alarm Sequence.............................................................................................................................................................................112
4.22: Special System Timers.................................................................................................................................................................................113
4.22.1: Silence Inhibit Timer........................................................................................................................................................................113
Autosilence Timer ............................................................................................................................................................................113
4.22.2:
4.22.3: Trouble Reminder.............................................................................................................................................................................113
4.22.4: Waterflow Retard Timer...................................................................................................................................................................113
4.22.5: Alarm Verification (None or One Minute). ... ............................... ....................................................................................................113
4.22.6: Control Module Delay Timer ...........................................................................................................................................................114
4.23: Walktest........................................................................................................................................................................................................114
4.24: Read Status ..................................................................................................................................................................................................114
4.24.1: System Point .....................................................................................................................................................................................114
4.24.2: Zones.................................................................................................................................................................................................115
4.24.3: Trouble Reminder.............................................................................................................................................................................116
4.24.4: Timers...............................................................................................................................................................................................116
4.24.5: NACs ................................................................................................................................................................................................116
4.24.6: Relays ...............................................................................................................................................................................................116
4.24.7: Program Check .................................................................................................................................................................................116
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 7
Table of Contents
4.24.8: History ..............................................................................................................................................................................................117
4.24.9: Annunciators.....................................................................................................................................................................................117
4.24.10: Communicator ................................................................................................................................................................................117
4.24.11: Print.................................................................................................................................................................................................118
Chamber Value .....................................................................................................................................................................................119
Drift Compensation...............................................................................................................................................................................119
Maintenance Alert.................................................................................................................................................................................119
4.24.12: Time-Date.......................................................................................................................................................................................120
4.24.13: Battery Charger...............................................................................................................................................................................120
4.24.14: 4XTM Supervision .........................................................................................................................................................................120
4.24.15: Remote Sync...................................................................................................................................................................................120
Section 5: Central Station Communications - POTS Transmission ......................................................................... 121
5.1: Transmittal Priorities .....................................................................................................................................................................................121
Section 6: FS-Tools Upload/Download........................................................................................................................ 123
6.1: FS-Tools Upload/Download..........................................................................................................................................................................123
6.2: Transferring a Program..................................................................................................................................................................................123
6.2.1: Security Features ................................................................... .............................................................................................................124
Secret Code Verification.................................................................................. .....................................................................................124
Time-out at Control Panel.....................................................................................................................................................................124
Error Checking......................................................................................................................................................................................124
Central Station Data Protection ............................................................................................................................................................124
Section 7: USB Upload/Download ............................................................................................................................... 125
7.1: USB Upload/Download.................................................................................................................................................................................125
Section 8: Firmware Upgrade....................................................................................................................................... 127
8.1: Firmware Upgrade.........................................................................................................................................................................................127
Section 9: Power Supply Calculations ........................................................................................................................ 128
9.1: Overview........................................................................................................................................................................................................128
9.2: Calculating the AC Branch Circuit................................................................................................................................................................128
9.3: Calculating the System Current Load............................................................................................................................................................128
9.3.1: Overview........................................ ............................. .. ............................. .........................................................................................128
9.3.2: How to Calculate System Current Load.............................................................................................................................................128
9.4: Calculating the Battery Size ..........................................................................................................................................................................130
9.4.1: NFPA Battery Requirements ................................................................. .. ............................ ...............................................................130
9.4.2: Selecting and Locating Batteries........................................................................................................................................................130
Appendix A: Software Zones........................................................................................................................................ 131
A.1: Correlations...................................................................................................................................................................................................131
Appendix B: Default Programming.............................................................................................................................. 138
Appendix C: NFPA Standard-Specific Requirements................................................................................................ 139
C.1: MBT-1 Municipal Box Trip - Silenceable ....................................................................................................................................................142
Appendix D: Wire Requirements.................................................................................................................................. 143
D.1: NAC Wiring..................................................................................................................................................................................................144
Appendix E: HVAC Control...........................................................................................................................................145
E.1: Control Module Operation............................................................................................................................................................................145
E.1.1: HVAC SHUTDOWN.........................................................................................................................................................................145
E.2: Monitor Module Operation ...........................................................................................................................................................................146
E.2.1: HVAC RESTART..............................................................................................................................................................................146
E.2.2: HVAC OVRRIDE..............................................................................................................................................................................146
Appendix F: Ademco Contact ID Format Event Code Descriptions.........................................................................147
F.1: Transmission Format Between DACT and Receiver.....................................................................................................................................147
F.2: Ademco Contact ID Typical Printout.............................................................................................................................................................147
8 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Table of Contents
Appendix G: Central Station Points............................................................................................................................. 152
Appendix H: NFPA Requirements................................................................................................................................ 154
Appendix I: Open/Short/Ground Trip Values.............................................................................................................. 155
Appendix J: Canadian Applications ............................................................................................................................ 156
Index............................................................................................................................................................................... 159
Slide-in Labels ...................................... ... .... ... ... ... .... ... ... ... ... .... ... ... ... .... ... ... .................................................................. 163
ES-200X and ES-200XC Fire Alarm Control Panels Operating Instructions............................................................ 165
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 9
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the stan­dards set forth by the following regulatory agencies:
Underwriters Laboratories/Underwriters Laboratories Canada
National Fire Protection Association
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code NFPA 720 Carbon Monoxide Detection and Warning Equipment
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems UL 2075 Standard for Gas and Vapor Detector and Sensors UL 2572 Communication and Control Units for Mass Notification Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems CAN/ULC - S561-03 Installation and Services for Fire Signal Receiving Centers and Systems CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems This Class (A) digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
Canadian Electrical Code, Part I EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 SLC Wiring Manual Document #51309 ECC-50/100 Manual Document #LS10001-000FL-E ECC-FFT Manual Document #LS10031-000FL-E Wireless Gateway Manual Document #LS10036-000FL-E CHG-120F Battery Charger Document #50888 CHG-75 Battery Charger Document #51315 IPOTS-COM POTS/IP Communicator Document #LS10184-000GE-E PWRMOD24 NAC Power Module Document #LS10185-000GE-E CELL-CAB-FL GSM Communicator Document #LS10186-000FL-E ANN-80 Product Installation Document Document #52749 ANN-100 Product Installation Document Document #LS10205-000FL-E ANN-(R)LED Product Installation Doc. Document #50055 ANN-I/O Product Installation Document Document #151416 ANN-RLY Product Installation Document Document #50055 ANN-S/PG Product Installation Document Document #151417
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Sys­tems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such oper­ation requires the approval of the local Authority Having Jurisdiction (AHJ).
10 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
RTN- OUT-
250
V
COMMUNI
CATOR
DISPLAY
PW
R
2
24V
2
A
NPM
RTN+OUT+
BATT
ERY
N/L2EARTHH/L1
USB-A
CNO NC
CNONC
CNCNO
SUPV
TRBL
ALRM
ANN-L
C
E
S200-PCAREVES50-PCARE
V
SLC
PWR1
RMT SYNC ANN-BUS PRI
ANN-BUS SEC
NAC4NAC3
NAC2
NAC1
+
+
+
+
+
+
+
+
+
+
+
+
SLC Loop
(supervised)
Secondary
ANN-BUS
to Annunciators
(power-limited,
supervised)
Primary
ANN-BUS
to Annunciators
(power-limited,
Remote
Synchronization
Output
Supervised, Power-
Limited circuits
24 VDC filtered (0.35
amp maximum),
Requires a 4.7 Kohm
End-of-Line Resistor
Supervisory*Alarm*
Trouble
2 Programmable Relays &
Fixed Trouble Relay
Non-supervised relay contacts
Contact rating:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in
normal condition (AC power
with no alarm, trouble, or
supervisory activity)
AC Fail Safe Trouble relay
switches to the NO position
during trouble conditions and
under loss of all power.
(*Factory default relay
programming)
NAC #1 NAC #2 NAC #4NAC #3
Notification Appliance Circuits
NAC #1, #2, #3, & #4 Class B or Class A
(Supervised, Power-Limited) (Special application) 2.5
amps max. per circuit
ELRs,
4.7K, 1/2W
(for Class
A wiring)
Auxiliary
Trouble
Input
C
A
U
T
I
O
N
!
H
I
G
H
V
O
L
T
A
G
E
AC Power
(Supervised,
Nonpower-Limited)
120 or 240 VAC, 50/60 Hz, 3.25 amps
Battery
24 VDC, supervised,
nonpower-limited,
18 AH maximum
USB Port J20
for firmware
updates, local
programming
using a
personal
computer and
FS-Tools
utility or a
thumb drive
To disable ground fault
detection, slide SW1 to the left.
Important! Disabling
Ground Fault Detection
voids UL/NFPA Class
identifications for circuits.
Disable Ground Fault only
with the approval of the
AHJ (Authority Having
Jurisdiction).
Special Application DC Power Outputs (24 VDC)
Nonsupervised, Power-Limited circuits
Nonresettable Power suitable for poweri ng
annunciators; Resettable Power suitable for
powering smoke detectors.
Aux Power 1: Resettable or Nonres ettable
Power, 24 VDC filtered, power-limited
(1.0 amp maximum). Class A or Class B
wiring possible. Supervision required for
Class B wiring. Supervise with a power
supervision relay EOLR-1
Aux Power 2: Nonresettable or Res ettable
Power, 24 VDC filtered, power-limited
(1.0 amp maximum). Supervision required.
Basic System Connections
Keypad
Connector
NPM Connector
Connection to the PWRMOD24
NAC power expander module
Connection to the IPOTS-
COM communicator card
for POTS and IP reporting
J12 & J13:
4XTMF
connection
SW2: 4XTMF
Supervisory Relay:
Slide switch to the
down position to
enable the relay
when the 4XTMF is
installed
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 11
Peripheral Devices and Their Documents:
SW2SW
3
S W 1
LED1LED2LED
3
L E D 4
L E D 5
L E D 6
L E D 7
L E D 8
J
3
J
5
J
4
ETH
L
I
N
E
2
L
I
N
E
1
Addressable Devices and SLC Wiring Doc. #51309
Wireless Gateway Doc. #LS10036-000FL-E
CHG-120F Charger
Doc. #50888
ANN-BUS - TB9/TB10
SLC Loop - TB12
Battery Connector - J15
es200annperi.wmf
ANN-80
LCD Text Annunciator
Doc. #52749
ANN-I/O
LED Driver
Doc. #151416
ANN-S/PG
Printer Driver
Doc. #151417
CHG-75 Charger
Doc. # 51315
ANN-(R)LED
LED Display
Doc. #53032
ANN-RLY
Relay Card
Doc. #53033
4XTMF
Reverse Polarity Module
J12 & J13
ANN Audio Control for ECC-50/100 Doc. #LS10001-000FL-E
IPOTS-COM POTS and IP Communicator Doc. #LS10184-000GE-E
J6
CELL-CAB-FL GSM Communicator Doc. #LS10186-000FL-E
PWRMOD24 NAC Power Expander
Doc. #LS10085-000GE-E
J16
J7
J15
ANN-100
LCD Text Annunciator
Doc. #LS10205-000FL-E
TB2
12 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
The Fire-Lite ES-200X is an addressable FACP (Fire Alarm Control Panel) with a pre-installed communicato r ca rd th at is compact, cost effective, intelligent, and has an extensive list of powerful features.The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the ES-200X FACP, offer the latest in fire protection technology. The power supply and all electronics are housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main circuit board, are available for special functions. Available accessories include multi-technology central station communicators, LED, graphic, and LCD annunciators, reverse polarity/city box transmitter, local and remote upload/download software, and remote power expansion.
The ES-200XC is a ULC-listed Canadian version of the FACP which offers the same features as the ES-200X, but is supplied standard with a dress panel. Refer to “Canadian Option” on page 79 for a full description.
NOTE: Unless otherwise specified, the term ES-200X is used to refer to all versions of the panel.
Inventory When ES-200X shipment is received, check that all parts have been included in shipment. The ES-200X shipment consists of one of
each of the following:
main circuit board with displaybackbox with doorplastic bag containing screws, cables, ELRs, terminal blocks, etc.

1.1 Features and Options

Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Telephone Service) Central Station Communicator
Optional CELL-MOD(C) or CELL-CAB-FL GSM Central Station Communicator over AlarmNet
Automated activation of the ECC-50/100 Emergency Command Center
ECC-FFT Firefighter Telephone option
Compatible with SWIFT® wireless devices
LiteSpeed™ polling protocol for faster SLC response time
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire (refer to “Wire Requirements” on page 143)
Single addressable SLC loop which meets NFPA Class A, Class B, and/or Class X requirements
198 addressable device capacity (99 detectors and 99 control/relay/monitor modules)
99 software zones
Four (4) Class B or four (4) Class A NAC (Notification Appliance Circuits) circuits - special application power
3.0 amps total 24 VDC output circuit current in alarm condition
NAC power expandable by 3.0 amps with optional PWRMOD24 module
Four programmable function keys for ease of maintenance
Two programmable relay outputs and one fixed trouble relay
Synchronization output for remote power supply applications (special application)
Built-in Programmer
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Addressable sounder base compatibility
Multi-criteria detector (smoke, heat, CO) with programmable response
Advanced fire technology features:
Automatic drift compensationMaintenance alertDetector sensitivity test capability (NFPA 72 compliant)Automatic device type-code verificationPoint trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or ANN-80/ANN-100 Remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad

Section 1: Product Description

ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 13
Product Description Specifications
Optional FS-Tools programming utility for local or remote Upload/Download of programming and data (available for download from www .firelite.com)
Compatible with Fire-Lite’s devices in Lite Spe ed a nd CL IP mode (refer to SLC Wiring Manual for a list of compatible addressable devices)
Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to the SLC Wiring Manual for a list of compatible addressable devices)
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
ANN-BUS for connection to following optional modules:
ANN-80 Remote Annunciator (UL applications only)ANN-100 (FM and Canadian applications only)ANN-I/O LED DriverANN-S/PG Printer ModuleANN-RLY Form-C Relay ModuleANN-LED Annunciator Module annunciates alarm, trouble and supervisory (required for Canada and emergency signaling)ANN-RLED Annunciator Module annunciates alarms only
Automated activation of the legacy ACC-25/50(ZS/T) Audio-Command-Center

1.2 Specifications

Refer to Illustration on page 10 for terminal locations and connections.
AC Power - TB13
Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 amps, auto-sensing. No switch or jumper required. Wire size: minimum 14 AWG (2.00 mm
Battery (Sealed Lead Acid Only) - J15
Maximum Charging Circuit: Normal Flat Charge – 27.6 VDC @ 1.5 amps Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of two 18 Amp Hour batteries. The BB-26 Battery Box holds two 26 Amp Hour batteries and the CHG-75. For greater than 26 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box). Minimum Battery Size: 7 Amp Hour Note: Refer to the programming section to disable the FACP battery charger when using an external battery charger.
Communication Loop - TB12
24 VDC nominal, 27.6 VDC maximum Maximum length - refer to “Wire Requirements” on page 143) Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit Refer to SLC Wiring manual for wiring information
Notification Appliance Circuits - TB4, TB5, TB6, & TB7
Four (4) Class B NAC circuits or four (4) Class A circuits Special Application, filtered power Power-limited circuitry NAC wiring requirements refer to “NAC Wiring” on page 144 Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps special application, 250 mA regulated (see Figure 1.1 on page 15) End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) required for each circuit; system capable of 1.9 kΩ - 22 kΩ ELR range. Refer to the Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB1, TB2, & TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.6 on page 26 for information on power-limited relay circuit wiring
Nonresettable or Resettable Special Application Power (24 VDC Nominal) - TB11, Terminals 1 (+), 2 (-), 3(+), & 4(-) (programmable)
Factory-set as nonresettable, suitable for powering annunciators Programmable Class A or Class B wiring Maximum ripple voltage: 20mV Total DC current available is up to 1.0 amp (see Figure 1.1 on page 15) Power-limited circuit Note: Refer to the programming section to configure power as resettable/non-resettable and for Class A or Class B wiring.
RMS
2
) with 600 V insulation
14 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Specifications Product Description
TB5
TB6
TB7
TB8
5 6
Figure 1.1 Current Availability without PWRMOD24 Option
Refer to the battery calculations section for additional information.
Standby
2.0 amps max
per panel
Special Application Nonresettable or Resettable Power
Special Application Resettable or Nonresettable Power
NAC #1
NAC #2
NAC #3
NAC #4
1.0 amp max
per circuit
2.5 amps max
per circuit
Alarm
3.0 amps max*
per panel
Remote
Synchronization
Output
*Note: When the option module PWRMOD24 is installed, an additional 3.0 amps of alarm power is available across NAC #1 through NAC #4 and the remote synchronization output expanding max power to 6.0 amps
1.0 amp max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
0.35 amp max
per circuit
Resettable or Nonresettable Special Application Power (24 VDC Nominal) - TB11, Terminals 5 (+) & 6 (-)
Factory-set as resettable, suitable for powering four-wire smoke detectors Class B wiring only Maximum ripple voltage: 20 mV Total DC current available is up to 1.0 amp (see Figure 1.1)
RMS
Power-limited circuit Refer to the Device Compatibility Document for listed compatible devices Note: Refer to the programming section to configure power as resettable/non-resettable.
Remote Sync Output - TB8
Remote power supply synchronization output 24 VDC nominal special application power Maximum current is 350 mA End-of-Line Resistor: 4.7KΩ Output linked to NAC 1 control Supervised and power-limited circuit Programmable Class A or Class B wiring
Secondary ANN-BUS - TB10
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B) Annunciators require non-resettable power
Primary ANN-BUS - TB9
Class A or Class B wiring ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B) Class A wiring uses Terminal 3 (+/A Return) and Terminal 4 (-/B Return) Annunciators require non-resettable power
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 15
Product Description Controls and Indicators
SYSTEM NORMAL
10:00A 010118
@
Figure 1.2 Membrane/Display Panel
es200kypd.wmf

1.3 Controls and Indicators

LCD Display
The F AC P uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed below. The key panel, which is visible with the cabinet door closed, has 30 keys, including a 16 key alpha­numeric pad similar to a telephone keypad.
LED Indicators
LED indicators are provided to annunciate the following conditions:
Fire Alarm (red)
CO Alarm (red)
AC Power (green)
Supervisory (yellow)
Trouble (yellow)
Ground fault (yellow)
Battery fault (yellow)
Disabled (yellow)
Maintenance (yellow)
Communication (yellow)
Alarm Silenced (yellow)
F1-F4 Function Keys (yellow)
Function keys:
Acknowledge
Alarm Silence
•Drill
Reset (lamp test)
four (4) programmable function keys
Service/program keys:
Keys labeled 1 to 9
•* key
•# key
0 (recall) key
First Event and scroll keys
Last Event and scroll keys
•Clear key
•Escape key
Two cursor keys (left and right)
Menu/Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.

1.4 Components

Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main circuit board.
IPOTS-COM Communicator Card
The pre-installed IP/POTS communica tor card transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the pub lic switched telephone network. It also allows remote programming or interrogation of the control panel using the FS-Tools Upload/Down­load utility and a hard-wired Ethernet IP connection. Any personal computer with Windows software may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages. Refer to Section 6 on page 123 for more information.
The IPOTS-COM digital communicator provides the following POTS functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
16 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
®
7 or greater, 32 or 64 bit, and FS-Tools
Optional Modules Product Description
Battery Cable P/N 75287
Dialing the Central Station(s) number: default is Touch-Tone®, programmable to rotary
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact IDSIA DCS 8SIA DCS 20
Cabinet
The ES-200X backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-ES-R), which mounts to the inside of the cabinet (required by ULC for Canadian installations).
Batteries
The ES-200X cabinet provides space for two batteries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour require an external charger such as the CHG-75 or CHG-120F and a UL listed battery box such as the BB-26 or BB-55F. Batteries must be ordered separately.

1.4.1 Intelligent Addressable Detectors

Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. The maximum address cannot exceed address 99. Note that a blink­ing LED on an intelligent detector indicates communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the same loop, the F A CP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible address­able detectors.

1.4.2 Intelligent Addressable Modules

Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. The maximum address cannot exceed address 99. Note that a blinking LED on an addressable module indicates communication between the module and the control panel.
These devices (i.e., MMF-300, MDF-300, MMF-301, MMF-302, CMF-300, CRF-300) can operate in CLIP mode (Classic Loop Inter­face Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC W iring Manual for a list of compatible addressable modules. Refer to the Device Compatibility Document for a list of approved conventional notification and initiating devices.

1.4.3 Addressable Device Accessories

End-of-Line Resistor Assembly
The End-of-Line resistors are included with each module. Refer to the specific module documentation for specific information.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is us ed to supervise the p ower to 4-wire smo ke detectors and notification appliances.
EOL-C(R/W) Mounting Plate
The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates which are required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the EOL-C(R/W) plate. Resistors mounted to the plate can be used for the supervision of a monitor and control module circuit.

1.5 Optional Modules

The ES-200X main circuit board includes option module connectors for the following modules:
CELL-MOD(C)/CELL-CAB-FL(C)
Optional GSM communicator card for central station reporting. It mounts in its own plastic or metal enclosure. Use of the CELL­MOD(C)/CELL-CAB-FL(C) requires the IPOTS-COM communicator. Connections are made from the CELL-MOD/CELL-CAB to the IPOTS-COM.
PWRMOD24 Power Expander Module
Optional power module. Increases NAC power output by 3 amps.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 17
Product Description Accessories
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the right edge the main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main circu it board, must be cut to allow supervision of the module.

1.6 Accessories

1.6.1 FS-Tools Programming Utility

The FS-Tools Programming Utility can be used to locally or remotely program the FACP from most Windows® compatible computers (PC), running Windows 7 or newer, 32 or 64 bit. The FACP program files can also be created and stored on the PC for future download to the control panel. FS-Tools can be downloaded from www.firelite.com. A standard USB cable with male-A to male-A connectors, which must be purchased separately, is required for local connection of the PC to the USB port J20 on the FACP main circuit board. Remote programming requires that the PC have a GSM or Ethernet connection.
FS-Tools also provides the ability to create panel program files on a USB flash drive. The drive can then be plugged into USB port J20 on the FACP main circuit board.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “FS-Tools Upload/Download” on page 123). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.

1.6.2 Dress Panel

An optional dress panel DP-ES-Ris available for the ES-200X (required by ULC for Canadian installations). The dress panel restricts access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of the dress panel and the ground stud in the backbox.The dress panel mounts to the backbox with two (2) #6-32 screws. The ES-200XC is supplied standard with a dress panel.

1.6.3 Trim Ring

An optional Trim Ring (P/N TR-CE) is ava ilable for the FACP backbox. The Trim Ring adds 1.5” of wall coverage around the backbox, concealing hardware and providing a finished appearance for a semi-flush mounted panel.

1.6.4 Battery Box

BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one 100 AH battery . When the CHG-120F is mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box.

1.6.5 Battery Charger

CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the ES-200X FACP. The FACP battery charger must be dis­abled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.
18 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Accessories Product Description
!
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the ES-200X FACP. The FACP battery charger must be dis­abled, by removing jumper JP5, when using the CHG-120F . The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the char ger and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.

1.6.6 ECC-50/100

The ECC-50/100 is a single channel, 50 watt, 25 V notification applications, or both. Automatic activation of the ECC-50/100 is possible via eight Command Input Circuits (CMD) or via the ANN BUS serial communications link from the ES-200X FACP.
, emergency voice evacuation panel that may be used for fire applications, mass
RMS

1.6.7 ECC-FFT

An ECC-FFT Fire Fighter Telephone provides supervision, annunciation, and control for local and remote telephone handsets. The ECC­FFT’s keypad provides indications of phone activation and corresponding trouble conditions. Not for use in Canadian applications.

1.6.8 W-GATE Wireless Gateway

The W - GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a LiteSpeed SLC loop on the ES-200X. It is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply evaluated for life safety. A vailable wireless devices include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, a monitor module, and a relay module. A maximum of 100 wireless devices can be used in the system. For details about wireless devices, system setup, and operation, see the SWIFT® Smart Wireless Integrated Fire Technolog y Instruction Manual #LS10036-000FL-E.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission (FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this product may be legally used outside the USA.

1.6.9 ANN-BUS Annunciators/Modules

WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR WIRING.
Guidelines
A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be connected to the primary communication circuit (EIA-485) terminals on TB9. A secondary communication circuit for these devices is available at TB8. Each ANN-BUS communication circuit supports up to eight (8) annunciators. Compatible devices include the following:
– ANN-80 LCD Annunciator (UL applications only) – ANN-100 LCD Annunciator (FM and Canadian applications only) – ANN-S/PG Serial/Parallel Printer Interface Module – ANN-I/O LED Driver Module – ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs) – ANN-RLED Annunciator Module (red alarm LEDs only) – ANN-RLY Relay Module (can be mounted in the supplied FACP chassis)
When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in the system.
The panel is capable of operating a primary ANN-BUS (TB9) and a secondary ANN-BUS (TB10) simultaneously.
Only one audio system (ECC-50/100 or ACC-25/50) may be connected to the ANN-BUS.
ANN-80/ANN-100 Remote Fire Annunciators
The ANN-80 and ANN-100 Annunciators are 80 charac ter, backlit LCD remote fire annunciators. They mimic the display on the control panel and will annunciate device type, point alarm, trouble or supervisory conditions, zone assignments plus any custom alpha labels programmed into the FACP. The annunciators also provide system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the annunciators are capable of remotely performing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication between the annunciators and the FACP is accomplished over a two wire RS­485 serial interface employing the ANN-BUS co mmunication format. The devices are powered, v ia two additio nal wires, from either the host F A CP or remote UL-listed, filtered, regulated, power supply.
The function buttons and piezo sounder may be individually enabled and disabled through the FACP software. Refer to “ANN-80/100 Options” on page 98 for a description of this feature and programming information.
ANN-S/PG Serial/Parallel Interface Module
The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel printer to the FACP for a real-time log of system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mounting.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 19
Product Description Getting Started
ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with mos t customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The module is provided with a plastic wall mount.
ANN-LED Annunciator Module
The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general system faults and input zones/points when used with a compatible F ACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. The ANN-RLED provides alarm (red) indication for up to 30 input zones or addressable points. Multiple ANN-(R)LED modules may be used for full system coverage.
ANN-RLY Annunciator Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP.

1.7 Getting Started

The following is a brief summary of the minimal steps involved in bringing an ES-200 on-line:
Install backbox and main circuit board (refer to “Mounting the Backbox” on page 22)
Address and install intelligent devices (refer to the SLC Wiring Manual)
Enter autoprogramming (refer to “Autoprogram” on page 52)
Resolve programming conflicts
Go to point program to enter specific data (refer to “Point Program” on page 53). Use the right and left arrow keys to navigate between devices.

1.8 Telephone Requirements and Warnings

1.8.1 Telephone Circuitry

Ringer Equivalence Number (REN) = 0.3A AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary . If tr ouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer: Honeywell International, Inc.
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: ES-200X FCC Registration Number: US:1W6AL03AEVOLX Ringer Equivalence: 0.3A
NOTE: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dial­ing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a quali­fied installer about installing the RJ31X jack and alarm dialing equipment. Refer to “IPOTS-COM Communicator” on page 30 for an illustration of the proper installation of this equipment.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
20 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Telephone Requirements and Warnings Product Description

1.8.2 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, ser­vices, equipment or procedures which may affect the operation of this control panel. However, the telephone company is re quired to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is neces­sary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES. When the control panel activates, premise phones will be disconnected. T wo separate phone lines are required. Do not connect both telephone interfaces to the same telephone line. The control panel must be connected to the public switched telephone netw ork upstream (as first device) of any private telephone system
at the protected premises. A plug and jack used to connect this equipment to the pr emises wiring and telephone ne twork must comp ly with the applicable FCC Part
68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.

1.8.3 For Canadian Applications

The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain tele-
communications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the users’ satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunica­tions company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier . Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION Users should not attempt to make such connections themselves, but should contact the appropria te electri c inspections author ity, or elec-
trician. “The Ringer Equivalence Number
allowed to be connected to a telephone interface. the termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
(REN) assigned to each terminal device provides an indication of the maximum number of terminals
10 Whitmore Road Woodbridge, Ontario L4L 7Z4 Phone: (905) 856-8733 F AX: (905) 856-9687
IC Certificate Number: 2132A-EVOLX Ringer Equivalence Number (REN): 0.3A Load Number: 2
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 21
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter
!
RTN-OUT-
COMMUNICATOR
DISPLAY
24V
RTN+OUT+
BATTERY
N/L2EARTHH/L1
USB-A
C
NO NC
CNO NC
CNCNO
SUPVTRBLALRM
ANN-LC
SLC
RMT SYNC
ANN-BUS PRI
ANN-BUS SEC
NAC4NAC3
NAC2
NAC1
@
Figure 2.1 ES-200X Chassis Removal and Installation
Backbox
Main Circuit Board on chassis
mounting studs
es200chassisinbox.wmf
grounding stud
mounting slots
holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme tem-
peratures are not encountered. The area should be readily accessible wit h sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conduc­tors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.1 Mounting the Backbox

CAUTION: STATIC SENSITIVE COMPONENTS
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Pla ce the chassis assembly in a safe location until it can be reinstalled in the backbox.
1. Mark and pre-drill hole in the wall for the center top keyhole mounting bolt using the dimensions illustrated in Figure 2.2 on page 23.
2. Install center top fastener in the wall with the screw head protruding.
3. Place backbox over the top screw, level and secure.
4. Mark and drill the left and right upper and lower mounting holes. Note: Outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
5. Install remaining fasteners and tighten.
6. When the location is dry and free of construction dust, install the chassis/circuit board assembly.
7. Mount the chassis to the backbox by aligning the two mounting tabs with the slots in the backbox, then position the two mounting hole tabs over the studs with nuts located in the upper portion of the backbox.
8. Slide the tabs located on the bottom of the chassis into the mounting slots in the backbox by pressing the chassis down.
9. Secure the chassis to the backbox by tightening the two mounting nuts (#10-32) at the top, and to ensure proper grounding, use a 3/8” nut driver or socket.
10. If the main circuit board is not already attached to the chassis, install it by positioning the ten mounting holes over the studs on the chassis and secure with the supplied screws.

Section 2: Installation

22 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Mounting the Backbox Installation
Figure 2.2 ES-200X Cabinet Mounting
9050udencl.wmf
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to avoid covering venting holes on top of box.
Hinge Slot for optional Dress Panel
Hinge Slot for optional Dress Panel
Semi-flush mounting hole
Mounting slots for optional Trim Ring
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 23
Installation Mounting the Backbox
6.537” (16.6cm)
5.207” (13.23cm)
16.822” (42.73 cm)
19.26” (48.92 cm)
Figure 2.3 Cabinet Dimensions
Height
Depth
Width
Left Side
Right Side
Top
Bottom
An optional Trim Ring (P/N TR-CE-) is also available for semi-flush mount installations.
24 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Power Installation
!
N/L2EARTHH/L1
Figure 2.4 Earth Ground Connection
9
2
0
0
g
r
n
d
.
w
m
f
grounding stud
keps nut
keps nut
Grounding Cable #71073
-
-
+
+
Interconnect Cable
!

2.2 Power

WARNING: RISK OF EQUIPMENT DAMAGE AND PERSONAL INJURY
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED T O THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.

2.2.1 AC Power and Earth Ground Connection

Primary power required for the FACP is 120 or 240 VAC, 50/60 Hz, 3.25 amps. The FACP will auto-detect the voltage used. No special switch or jumper is required to select AC power . Overcur­rent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG (2.00 mm certain that the AC mains circuit breaker is off and the control panel. Connect wiring from the AC mains to TB13 on the FACP, being careful to observe proper connections.
Remove the two keps nuts from the grounding stud in the backbox. Connect the incoming earth ground wire to supplied cable #71073 with a wire nut. Position the ring terminal end over the grounding stud. Secure with one of the keps nuts. Place the ring terminal from the other supplied ground cable #71073 over the ground stud and secure with the second keps nut. Wire the ground cable to the bottom posi­tion of TB11. Refer to Figure2.1 on page22 for location of the stud. Ensure that the ground for AC mains is the first cable installed, closest to the backbox. This connection is vital in reducing the panel’s susceptibility to transients generated by lightning an d electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be
applied to the panel before installing the battery interconnect cable (refer to the foll owing sec t ion).
2
) or larger wire with 600 volt insulation rating. Make
before wiring any connections between the mains

2.2.2 Battery Power

ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 25
The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not
connected. Do not con­nect the interconnect cable until the system is completely installed. Observe polarity when connecting the batteries. Connect the battery cable to J9 on the main circuit board. Refer to “Power Supply Calculations” on page 128, for calculation of the correct battery rating.
WARNING: RISK OF PERSONAL INJURY
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
Installation Relays
+ -
+ - + -
PWR2
24V
PWR1
Figure 2.5 Special Application Power Outputs - 24 VDC
Power-limited Non-resettable or Resettable Power
1.0 amperes max., 24 VDC nominal filtered, non­resettable or resettable power is programmable. PWR1 can be programmed as Class B or Class A.
Power-limited Resettable or Non-resettable Power
1.0 amperes max., 24 VDC nominal filtered, programmable resettable or non-resettable power can be drawn from TB11 Terminals 5(+) and 6(-)
e
s
2
0
0
t
b
1
1
.
w
m
f
TB11
Optional Class A wiring return
CNO NC
C
NONC
CNCNO
SUPV
TRBL
ALRM
Figure 2.6 Relay Terminals
Relay contacts shown with power applied to panel and no active troubles, alarms or supervisories
TB1
Note that the programmable relay labeled as Relay 1 is factory default programmed as Alarm and programmable Relay 3 is factory default programmed as Supervisory. The relay labeled Relay 2 is fixed as a Trouble relay and cannot be changed. It is a fail-safe relay which will transfer on any trouble or total power failure.
e
s
2
0
0
r
l
y
.
w
m
f
TB2 TB3
RELAY 1
RELAY 2 RELAY 3

2.2.3 Special Application DC Power Output Connection

All Special Application DC power outputs are power-limited (refer to “UL Power-limited Wiring Requirements” on page 29).

2.3 Relays

The F AC P provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay,Note that relay connections may be power-limited or nonpower-limited, provided that 0.25” spacing is maintained between conductors of power-limited and nonpower-lim­ited circuits. Refer “UL Power-limited Wiring Requirements” on page 29.

2.4 Notification Appliance Circuits

The control panel provides four Class B or four Class A NACs (Notification Appliance Circuits). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 6.0 amps (refer to “Calculating the System Current Load” on page 128). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Device Compati- bility Document for a listing of compatible notification appliances. The NACs, which are located on the main circuit board, may be expanded via the FCPS Series field charger/power supplies.
The following sections describe the configuration and wiring of Class B and Class A Notification Appliance Circuits on the ES-200X main circuit board.
26 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Notification Appliance Circuits Installation
NAC4NAC3
NAC2
NAC1
+
+
+
+
+
+
+
+
+
+
+
+
Figure 2.7 NAC Class B Wiring
4 Class B Notification Appliance Circuits, supervised and power-limited - 4.7 kΩ, ½ watt P/N:71252 UL listed
Polarized Bells
Polarized Bells
Polarized HornsPolarized Horns
Polarized Strobes
Notification Appliance Circuit polarity shown in alarm state
Dummy Load all unused circuit
TB5
e
s
2
0
0
n
a
c
y
.
w
m
f
Polarized Strobes
circuit number
NAC 1
NAC 2
NAC 3
NAC 4
TB4 TB6 TB7
NAC4NAC3
NAC2
NAC1
+
+
+
+
+
+
+
+
+
+
+
+
4 Class A Notification Appliance Circuits, supervised and power-limited
Polarized HornsPolarized Horns
Notification Appliance Circuit polarity shown in alarm state
Polarized Bells
Polarized Strobes Polarized Strobes
Figure 2.8 NAC Class A Wiring
NAC 1 NAC 4
TB5 TB7
NAC 2 N AC 3
Dummy Load all unused circuits
Polarized Bells
circuit number
e
s
2
0
0
c
n
a
c
z
.
w
m
f
TB7TB4

2.4.1 Class B NAC Wiring

2.4.2 Class A NAC Wiring

ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 27
Installation Remote Synchronization Output
RTN- OUT-
RTN+OUT+
CNO NC
SUPV
RMT SYNC NAC1
Figure 2.9 Remote Sync Output
Remote Power Supply
FACP main circuit board
Remote Sync Output
Sync Input
4.7 KΩ ELR
e
s
2
0
0
s
y
n
c
.
w
m
f
Optional Class A Return

2.5 Remote Synchronization Output

Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard to individuals. Devices connected directly to the control panel’s NACs can be synchronized as described in “Type” on page 76.
Notification appliances connected to FCPS NAC power supplies require synchronization with the FACP’s devices. This can be accom­plished by connecting the Remote Synchronization Output from TB8 of the ES-200X to the sync input of the FCPS-24FS6/8 Power Sup­ply. The 24 VDC signal from TB8 follows, that is mimics, the signal on NAC1. This allows the devices connected to the power supply to be synchronized with the devices connected to NAC1 on the FACP.
The Remote Synchronization Output is power-limited and supervised (refer to “UL Power-limited Wiring Requirements” on page 29) and can be wired in Class B or Class A. A 4.7 KΩ ELR resistor must be connected to the end of the wiring at the remote power supply for Class B wiring. Supervision of the remote synchronization is automatically enabled when the remote sync output is enabled. Supervi­sion will be disabled if the output is disabled. For more information on enabling the remote sync output, refer to page 104.
28 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
UL Power-limited Wiring Requirements Installation
RTN- OUT-
COMMUNICATOR
DISPLAY
24V
RTN+OUT+
BATTERY
N/L2EARTHH/L1
USB-A
CNO NC
CNO NC
CNCNO
SUPV
TRBL
ALRM
ANN-LC
SLC
RMT SYNC
ANN-BUS PRI
ANN-BUS SEC
NAC4NAC3
NAC2
NAC1
Figure 2.10 Typical UL Power-limited Wiring Requirements
Power-limited Circuits (Class 2)
Power­limited Circuits (Class 2)
AC
Power
Grounding Stud (see Figure 2.4)
n
f
w
1
0
0
x
u
l
w
i
r
e
.
w
m
f
To
Batteries
maintain minimum 0.25” between power-limited and nonpower-limited circuits wiring
Ground Cables (2) #71073
Wire Nut
Nonpower-limited Circuits
Power­limited Circuits (Class 2)
4XTMF
Power-limited (Class 2) Supervised Ethernet Circuit
Nonpower­limited (Class 1) Supervised Telephone Circuit
IPOTS-COM

2.6 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabi­net through different knockouts and/or conduits. When connecting the ground cables, be sure that the AC mains ground is the first one installed, closest to the backbox. A typical wiring diagram for the ES-200X is shown below.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018 29
Installation IPOTS-COM Communicator
Figure 2.11 Communicator Installation
Customer Premises Equipment and Wiring
Telephone
Line
FACP with IPOTS-COM
mounted internally
Network
Service
Provider’s
Facilities
Network
Demarcation
Point
RJ31X
Jack
Unused
RJ-11 Jack
Unused
RJ-11 Jack
Telephone
Telephone
Telephone
Answering
System
Fax Machine
Computer
e
s
2
0
0
d
a
c
t
.
w
m
f
123456778
123
4
56 8
LED4
LED5
LED6
LED7
LED8
J3
J5J4
ETHLINE2LINE1
Figure 2.12 Wiring Phone Jacks
Ring Tip
To premise phones
Ring
Tip
Green Wire
Red Wire
Rin
Ti
Green
Red Wire
(Secondary Lines) Incoming Telco Phone
Ring
Tip
To premise
(Primary Lines) Incoming Telco Phone
RJ31X
Jack
RJ31X
Jack
Note: Shorting
bars inside RJ31X
Jack removed
during installation.
7 foot Cable
MCBL-7
(ordered
separately)
Primary Phone Line
Secondary Phone Line
Module Female Connectors
Male Plug
Connectors
e
s
2
0
0
j
a
c
k
.
w
m
f
IPOTS-COM
SW2
SW3
Figure 2.13
IPOTS-COM Dip
Switches
S
W
2
S
W
3

2.7 IPOTS-COM Communicator

Two independent telephone lines can be connected to the control panel via the IPOTS-COM Phone/IP Communication Module. Tele­phone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is
critical that the IPOTS-COM Digital Communicator be located as the first device on the incoming t elephone circuit to properly function.
Important! The IPOTS-COM must not be used to dial a phone number that is call-forwarded.
30 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Wiring
Connection and wiring of two phone lines is required as shown below.
Dip Switches
There are two configurable dip switches on the IPOTS-COM communicator.
SW2: 6-position dip switch- FUTURE USE- No configuration necessary.
SW3: 2-position dip switch- Factory Settings- Do not change unless instructed to do
so by Honeywell.
Loading...
+ 138 hidden pages