Document LS10131-000FL-E Rev: C
7/25/2018 ECN:18-323
Fire Alarm & Emergency Communication System Limitations
While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!
An automatic fire alarm system—typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning
devices, and a fire alarm control panel (FACP) with remote notification capability—can provide early warning of a d eveloping fire. Such
a system, however, doe s not assure protection against property
damage or loss of life resulting from a fire.
An emergency communication system—typically made up of an
automatic fire alarm system (as described above) and a life safety
communication system that may include an autonomous control
unit (ACU), local operating console (LOC), voice communication,
and other various interoperable communication methods—can
broadcast a mass notification message. Such a system, however,
does not assure protection against property damage or loss of life
resulting from a fire or life safety event.
The Manufacturer recommends that smoke and/or heat detectors
be located throughout a protected premises following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the
recommendations contained in the Guide for Proper Use of Sys tem
Smoke Detectors, which is made available at no charge to all
installing dealers. This document can be found at http://
www.systemsenso r.com/appguides/. A study by the Federal
Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in as
many as 35% of all fires. While fire alarm systems are designed to
provide early warning against fire, they do not guarantee warni ng or
protection against fire. A fire alarm system may not provide timely or
adequate warning, or simply may not function, for a variety of
reasons:
Smoke detectors may not sense fire where smoke cannot reach
the detectors such as in chimneys, in or behind walls, on roofs, or
on the other side of closed doors. Smoke detectors also may not
sense a fire on another level or floor of a building. A second-floor
detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may
not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, chimneys, even wet or humid areas may inhibit particle or smoke
flow.
• Smoke particles may become “cold,” stratify, and not reach the
ceiling or upper walls where de t ec t ors are located.
• Smoke particles may be blown away fr om detectors by air outlets, such as air conditioning vents.
• Smoke particles may be drawn into air returns before reaching
the detector.
The amount of “smoke” present may be insufficient to alarm smoke
detectors. Smoke detectors are designed to alarm at various level s
of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into
alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend
to detect smoldering fires better than flaming fires, which have little
visible smoke. Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering fires.
Because fires develop in different ways and are often unpredictable
in their growth, neither type of detector is necessarily best and a
given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning
of fires caused by arson, children playing with matches (especially
in bedrooms), smoking in bed, and violent explosions (caused by
escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined rate
or reaches a predetermined level. Rate-of-rise heat detectors may
be subject to reduced sensitivity over time. For this reason, the rateof-rise feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Heat detectors are
designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same
room as the control panel and in rooms used by the system for the
connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire
may damage the alarm system, compromising its ability to report a
fire.
Audible warning devices such as bells, horns, strobes, speakers and displays may not alert people if these devices are located
on the other side of closed or partly open doors or are located on
another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs,
alcohol, or medication. Please note that:
• An emergency communication system may take priority over a
fire alarm system in the event of a life safety emergency.
• Voice messagi ng systems must be designed t o meet intelligibili ty
requirements as defined by NFPA, local codes, and Authorities
Having Jurisdiction (AHJ).
• Language and instructional requirements must be clearly disseminated on any local displays.
• Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a
fire alarm signal, do not respond to or comprehend the meaning
of the signal. Audib le devices, such as h orns and bell s, can hav e
different tonal patterns and frequencies. It is the property
owner's responsibility to conduct fire drills and other training
exercises to make people aware of fire alarm signals and
instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause
temporary or permanent hearing loss.
A life safety system will not operate without any e lectrical power. If
AC power fails, the system will operate from standby batteries only
for a specified time and only if the batteries have been properly
maintained and replaced regularly.
Equipment used in the system may not be technically c ompatible
with the control panel. It is e ssential to use only equipment listed f or
service with your control panel.
Telephone lines needed to transmit alarm signals from a premises
to a central monitoring station may be out of service or temporarily
disabled. For added protection against telephone line failure,
backu
p radio transmission systems are recommended.
The most common cause of life safety system malfuncti on i s i na dequate maintenance. To keep the entire life safety system in excellent working order, ongoing maintenance is required per the
manufacturer's recommendations, and UL and NFPA standards. At
a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt, or high air velocity require
more frequent maintenance. A maintenance agreement should be
arranged through the local manufacturer's representative. Maintenance should be scheduled as required by National and /or lo cal fire
codes and should be performed by authorized professional life
safety system installers only. Adequate written records of all inspections should be kept.
Limit-D2-2016
2 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sourc es of
power before servicing. Control unit and associated equipment
may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt
to install, service, or operate this unit until manuals are read and
understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product must be
tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Re-acceptance testing is
required after any change, addition or deletion of syst em components, or after any modification, repair or adjustment to system
hardware or wiring. All components, circuits, system operations, or
software functions known to be aff ected by a change must b e 100%
tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must also
be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/
32-120º F and at a relative humidity . However, the useful life of
the system's standby batteries and the electro nic compo nent s may
be adversely affected by extreme temperature ranges and humidity .
Therefore, it is recommended that this system and its peripherals
be installed in an environment with a normal room temperature of
15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from lightning transients and interference, pr oper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are
anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make all
cable entries from the sides or rear. Before making modifications,
verify that they will not interfere with battery, transformer, or pri nt ed
circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact
pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static
suppressive packaging to protect electronic assemblies removed
from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual may cause interference to radio communications. It has been tested and foun d
to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such
interference when devices are operated in a commercial
environment. Operation of this equipment in a residential
area is likely to cause interference, in which case the user
will be required to correct the interference at his or her own
expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for
radiation noise emissions from digital apparatus set out in
the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des
Communications du Canada.
LiteSpeed™ and Lite-Connect™ are trademarks; and Fire-Lite® Alarms, Honeywell®, and SWIFT® are registered trademarks of Honeywell International Inc.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registeredtrademark of The Mozilla Foundation.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/20183
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent
upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we
strongly recommend that you download the most current version of software for each product prior to commissioning any system.
Contact Technical Support with any questions about softwa re and the app rop riate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•T opic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
4 ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
1.1: Features and Options .......................................................................................................................................................................................13
1.3: Controls and Indicators....................................................................................................................................................................................16
Power Supervision Relay........................................................................................................................................................................17
ANN-80/ANN-100 Remote Fire Annunciators......................................................................................................................................19
ANN-I/O LED Driver Module ...............................................................................................................................................................20
1.8: Telephone Requirements and Warnings...........................................................................................................................................................20
1.8.2: Telephone Company Rights and Warnings..........................................................................................................................................21
1.8.3: For Canadian Applications ...................................................................................................................................................................21
2.1: Mounting the Backbox ....................................................................................................................................................................................22
2.2.1: AC Power and Earth Ground Connection ............................................................................................................................................25
2.2.2: Battery Power ..................... .. ............................. ............................. ......................................................................................................25
2.2.3: Special Application DC Power Output Connection ........................................... .. ................................................................................26
2.4.1: Class B NAC Wiring .................................. .. ............................. ... ............................. ...........................................................................27
2.4.2: Class A NAC Wiring..... ....................................................................................... .. ..............................................................................27
2.6: UL Power-limited Wiring Requirements.........................................................................................................................................................29
Installation and Wiring ...........................................................................................................................................................................31
ANN-80 Remote Fire Annunciator.........................................................................................................................................................36
ANN-100 Remote Fire Annunciator.......................................................................................................................................................38
ANN-I/O LED Driver Module ...............................................................................................................................................................41
3.1: Programming Data Entry.................................................................................................................................................................................49
3.2: User Programming...........................................................................................................................................................................................50
3.5: Programming and Passwords...........................................................................................................................................................................51
3.6.2: Point Program.......................................................................................................................................................................................53
Special Purpose Zone..............................................................................................................................................................................69
s Installed........................................................................................................................................................................................69
Zone
Zones Enabled.........................................................................................................................................................................................69
Zones Disabled .......................................................................................................................................................................................69
Zone Type...............................................................................................................................................................................................70
Zones Available ......................................................................................................................................................................................70
Zone Message .........................................................................................................................................................................................70
3.6.5: System Setup ........................................ ............................. ............................ .......................................................................................71
Function Keys............................................... ........................................................ ..................................................................................72
Canadian Option .....................................................................................................................................................................................79
IP Settings...............................................................................................................................................................................................83
6ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Table of Contents
Primary and Secondary Communication Paths ......................................................................................................................................84
3.6.11: Program Check .................................................................................................................................................................................100
4.1: Panel Control Buttons....................................................................................................................................................................................106
4.1.5: Function Keys F1-F4..........................................................................................................................................................................106
4.2: LED Indicators...............................................................................................................................................................................................106
4.3: Normal Operation ..........................................................................................................................................................................................107
4.6: CO Alarm Operation......................................................................................................................................................................................109
4.8: Process Monitor Operation............................................................................................................................................................................110
4.10: Medical Alert Condition Operation.............................................................................................................................................................110
4.11: Mass Notification Operation... ... ............................ ... ......................................................... ..........................................................................111
4.13: Programmed Zone Operation ......................................................................................................................................................................111
4.22: Special System Timers.................................................................................................................................................................................113
4.22.5: Alarm Verification (None or One Minute). ... ............................... ....................................................................................................113
4.22.6: Control Module Delay Timer ...........................................................................................................................................................114
4.24: Read Status ..................................................................................................................................................................................................114
4.24.1: System Point .....................................................................................................................................................................................114
4.24.7: Program Check .................................................................................................................................................................................116
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/20187
Table of Contents
4.24.8: History ..............................................................................................................................................................................................117
Chamber Value .....................................................................................................................................................................................119
6.2: Transferring a Program..................................................................................................................................................................................123
6.2.1: Security Features ................................................................... .............................................................................................................124
Time-out at Control Panel.....................................................................................................................................................................124
Central Station Data Protection ............................................................................................................................................................124
Section 7: USB Upload/Download ............................................................................................................................... 125
7.1: USB Upload/Download.................................................................................................................................................................................125
9.2: Calculating the AC Branch Circuit................................................................................................................................................................128
9.3: Calculating the System Current Load............................................................................................................................................................128
9.3.2: How to Calculate System Current Load.............................................................................................................................................128
9.4: Calculating the Battery Size ..........................................................................................................................................................................130
9.4.2: Selecting and Locating Batteries........................................................................................................................................................130
E.1: Control Module Operation............................................................................................................................................................................145
Appendix F: Ademco Contact ID Format Event Code Descriptions.........................................................................147
F.1: Transmission Format Between DACT and Receiver.....................................................................................................................................147
F.2: Ademco Contact ID Typical Printout.............................................................................................................................................................147
8ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Table of Contents
Appendix G: Central Station Points............................................................................................................................. 152
ES-200X and ES-200XC Fire Alarm Control Panels Operating Instructions............................................................ 165
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/20189
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
NFPA 720 Carbon Monoxide Detection and Warning Equipment
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2017 General-Purpose Signaling Devices and Systems
UL 2075 Standard for Gas and Vapor Detector and Sensors
UL 2572 Communication and Control Units for Mass Notification Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
CAN/ULC - S561-03 Installation and Services for Fire Signal Receiving Centers and Systems
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
Canadian Electrical Code, Part I
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
10ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
12ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
The Fire-Lite ES-200X is an addressable FACP (Fire Alarm Control Panel) with a pre-installed communicato r ca rd th at is compact, cost
effective, intelligent, and has an extensive list of powerful features.The combination of Fire-Lite’s newer series devices and legacy 300
Series devices, along with the ES-200X FACP, offer the latest in fire protection technology. The power supply and all electronics are
housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main
circuit board, are available for special functions. Available accessories include multi-technology central station communicators, LED,
graphic, and LCD annunciators, reverse polarity/city box transmitter, local and remote upload/download software, and remote power
expansion.
The ES-200XC is a ULC-listed Canadian version of the FACP which offers the same features as the ES-200X, but is supplied standard
with a dress panel. Refer to “Canadian Option” on page 79 for a full description.
NOTE: Unless otherwise specified, the term ES-200X is used to refer to all versions of the panel.
Inventory
When ES-200X shipment is received, check that all parts have been included in shipment. The ES-200X shipment consists of one of
each of the following:
main circuit board with display
backbox with door
plastic bag containing screws, cables, ELRs, terminal blocks, etc.
1.1 Features and Options
•Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Telephone Service) Central Station Communicator
•Optional CELL-MOD(C) or CELL-CAB-FL GSM Central Station Communicator over AlarmNet
•Automated activation of the ECC-50/100 Emergency Command Center
•ECC-FFT Firefighter Telephone option
•Compatible with SWIFT® wireless devices
•LiteSpeed™ polling protocol for faster SLC response time
•SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire (refer to “Wire Requirements” on
page 143)
•Single addressable SLC loop which meets NFPA Class A, Class B, and/or Class X requirements
•198 addressable device capacity (99 detectors and 99 control/relay/monitor modules)
•99 software zones
•Four (4) Class B or four (4) Class A NAC (Notification Appliance Circuits) circuits - special application power
•3.0 amps total 24 VDC output circuit current in alarm condition
•NAC power expandable by 3.0 amps with optional PWRMOD24 module
•Four programmable function keys for ease of maintenance
•Two programmable relay outputs and one fixed trouble relay
•Synchronization output for remote power supply applications (special application)
•Built-in Programmer
•80-character LCD display (backlit)
•Real-time clock/calendar with daylight savings time control
•History file with 1,000 event capacity
•Addressable sounder base compatibility
•Multi-criteria detector (smoke, heat, CO) with programmable response
•ANN-BUS for connection to following optional modules:
ANN-80 Remote Annunciator (UL applications only)
ANN-100 (FM and Canadian applications only)
ANN-I/O LED Driver
ANN-S/PG Printer Module
ANN-RLY Form-C Relay Module
ANN-LED Annunciator Module annunciates alarm, trouble and supervisory (required for Canada and emergency signaling)
ANN-RLED Annunciator Module annunciates alarms only
•Automated activation of the legacy ACC-25/50(ZS/T) Audio-Command-Center
1.2 Specifications
Refer to Illustration on page 10 for terminal locations and connections.
AC Power - TB13
Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 amps, auto-sensing. No switch or jumper required.
Wire size: minimum 14 AWG (2.00 mm
Battery (Sealed Lead Acid Only) - J15
Maximum Charging Circuit: Normal Flat Charge – 27.6 VDC @ 1.5 amps
Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of two 18 Amp Hour batteries. The BB-26 Battery
Box holds two 26 Amp Hour batteries and the CHG-75. For greater than 26 Amp Hour up to 120 Amp Hour batteries, use the CHG-75
or CHG-120F Battery Charger and BB-55F Battery Box).
Minimum Battery Size: 7 Amp Hour
Note: Refer to the programming section to disable the FACP battery charger when using an external battery charger.
Communication Loop - TB12
24 VDC nominal, 27.6 VDC maximum
Maximum length - refer to “Wire Requirements” on page 143)
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited circuit
Refer to SLC Wiring manual for wiring information
Four (4) Class B NAC circuits or four (4) Class A circuits
Special Application, filtered power
Power-limited circuitry
NAC wiring requirements refer to “NAC Wiring” on page 144
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 2.5 amps special application, 250 mA regulated (see Figure 1.1 on page 15)
End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) required for each circuit; system capable of 1.9 kΩ - 22 kΩ ELR range.
Refer to the Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB1, TB2, & TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.6 on page 26 for information on power-limited relay circuit wiring
Nonresettable or Resettable Special Application Power (24 VDC Nominal) - TB11, Terminals 1 (+), 2 (-), 3(+), & 4(-)
(programmable)
Factory-set as nonresettable, suitable for powering annunciators
Programmable Class A or Class B wiring
Maximum ripple voltage: 20mV
Total DC current available is up to 1.0 amp (see Figure 1.1 on page 15)
Power-limited circuit
Note: Refer to the programming section to configure power as resettable/non-resettable and for Class A or Class B wiring.
RMS
2
) with 600 V insulation
14ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
SpecificationsProduct Description
TB5
TB6
TB7
TB8
5
6
Figure 1.1 Current Availability without PWRMOD24 Option
Refer to the battery calculations section for additional information.
Standby
2.0 amps max
per panel
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable or
Nonresettable Power
NAC #1
NAC #2
NAC #3
NAC #4
1.0 amp max
per circuit
2.5 amps max
per circuit
Alarm
3.0 amps max*
per panel
Remote
Synchronization
Output
*Note: When the option module
PWRMOD24 is installed, an
additional 3.0 amps of alarm power is
available across NAC #1 through
NAC #4 and the remote
synchronization output expanding
max power to 6.0 amps
1.0 amp max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
0.35 amp max
per circuit
Resettable or Nonresettable Special Application Power (24 VDC Nominal) - TB11, Terminals 5 (+) & 6 (-)
Factory-set as resettable, suitable for powering four-wire smoke detectors
Class B wiring only
Maximum ripple voltage: 20 mV
Total DC current available is up to 1.0 amp (see Figure 1.1)
RMS
Power-limited circuit
Refer to the Device Compatibility Document for listed compatible devices
Note: Refer to the programming section to configure power as resettable/non-resettable.
Remote Sync Output - TB8
Remote power supply synchronization output
24 VDC nominal special application power
Maximum current is 350 mA
End-of-Line Resistor: 4.7KΩ
Output linked to NAC 1 control
Supervised and power-limited circuit
Programmable Class A or Class B wiring
Secondary ANN-BUS - TB10
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
Annunciators require non-resettable power
Primary ANN-BUS - TB9
Class A or Class B wiring
ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
Class A wiring uses Terminal 3 (+/A Return) and Terminal 4 (-/B Return)
Annunciators require non-resettable power
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available
from the FACP.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/201815
Product DescriptionControls and Indicators
SYSTEM NORMAL
10:00A 010118
@
Figure 1.2 Membrane/Display Panel
es200kypd.wmf
1.3 Controls and Indicators
LCD Display
The F AC P uses an 80-character
(4 lines X 20 characters) high viewing angle LCD display. The display includes a long life
LED backlight that remains illuminated. If AC power is lost and the system is not in alarm,
the LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display
and LED indicators as listed below. The key panel, which is visible with the cabinet door closed, has 30 keys, including a 16 key alphanumeric pad similar to a telephone keypad.
LED Indicators
LED indicators are provided to annunciate the following conditions:
•Fire Alarm (red)
•CO Alarm (red)
•AC Power (green)
•Supervisory (yellow)
•Trouble (yellow)
•Ground fault (yellow)
•Battery fault (yellow)
•Disabled (yellow)
•Maintenance (yellow)
•Communication (yellow)
•Alarm Silenced (yellow)
•F1-F4 Function Keys (yellow)
Function keys:
•Acknowledge
•Alarm Silence
•Drill
•Reset (lamp test)
•four (4) programmable function keys
Service/program keys:
•Keys labeled 1 to 9
•* key
•# key
•0 (recall) key
•First Event and scroll keys
•Last Event and scroll keys
•Clear key
•Escape key
•Two cursor keys (left and right)
•Menu/Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
1.4 Components
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The
4XTMF option module plugs in and is mounted to the main circuit board.
IPOTS-COM Communicator Card
The pre-installed IP/POTS communica tor card transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the pub lic
switched telephone network. It also allows remote programming or interrogation of the control panel using the FS-Tools Upload/Download utility and a hard-wired Ethernet IP connection. Any personal computer with Windows
software may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file,
walktest data, current status and system voltages. Refer to Section 6 on page 123 for more information.
The IPOTS-COM digital communicator provides the following POTS functions:
•Line Seizure: takes control of the phone lines disconnecting any premises phones
•Off/On Hook: performs on and off-hook status to the phone lines
•Listen for dial tone: 440 Hz tone typical in most networks
16ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
®
7 or greater, 32 or 64 bit, and FS-Tools
Optional ModulesProduct Description
Battery Cable P/N 75287
•Dialing the Central Station(s) number: default is Touch-Tone®, programmable to rotary
•For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s)
varies with the transmission format. The control panel will adjust accordingly.
•Communicate in the following formats:
Ademco Contact ID
SIA DCS 8
SIA DCS 20
Cabinet
The ES-200X backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also
available is an optional dress panel (DP-ES-R), which mounts to the inside of the cabinet (required by ULC for Canadian installations).
Batteries
The ES-200X cabinet provides space for two batteries (up to 18 Amp Hour). Batteries larger
than 18 Amp Hour require an external charger such as the CHG-75 or CHG-120F and a UL
listed battery box such as the BB-26 or BB-55F. Batteries must be ordered separately.
1.4.1 Intelligent Addressable Detectors
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring
Manual for detailed information on device installation, wiring and operation). This allows the control panel to continually process the
information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address
that is set in the detector head using built-in rotary decimal switches. The maximum address cannot exceed address 99. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a
quicker response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the
same loop, the F A CP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable detectors.
1.4.2 Intelligent Addressable Modules
Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating
devices. Each module can be set to respond to an address with built-in rotary switches. The maximum address cannot exceed address 99.
Note that a blinking LED on an addressable module indicates communication between the module and the control panel.
These devices (i.e., MMF-300, MDF-300, MMF-301, MMF-302, CMF-300, CRF-300) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 series devices. If a mix of old
and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC W iring Manual for a list of compatible addressable modules. Refer to the Device Compatibility Document for a list of approved conventional
notification and initiating devices.
1.4.3 Addressable Device Accessories
End-of-Line Resistor Assembly
The End-of-Line resistors are included with each module. Refer to the specific module documentation for specific information.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is us ed to supervise the p ower to 4-wire smo ke detectors and notification appliances.
EOL-C(R/W) Mounting Plate
The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates which are required for use in Canada. An ELR, which is
supplied with each module and fire alarm control panel, is mounted to the EOL-C(R/W) plate. Resistors mounted to the plate can be used
for the supervision of a monitor and control module circuit.
1.5 Optional Modules
The ES-200X main circuit board includes option module connectors for the following modules:
CELL-MOD(C)/CELL-CAB-FL(C)
Optional GSM communicator card for central station reporting. It mounts in its own plastic or metal enclosure. Use of the CELLMOD(C)/CELL-CAB-FL(C) requires the IPOTS-COM communicator. Connections are made from the CELL-MOD/CELL-CAB to the
IPOTS-COM.
PWRMOD24 Power Expander Module
Optional power module. Increases NAC power output by 3 amps.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/201817
Product DescriptionAccessories
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a
disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to
open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the
right edge the main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main circu it board, must be cut to allow
supervision of the module.
1.6 Accessories
1.6.1 FS-Tools Programming Utility
The FS-Tools Programming Utility can be used to locally or remotely program the FACP from most Windows® compatible computers
(PC), running Windows 7 or newer, 32 or 64 bit. The FACP program files can also be created and stored on the PC for future download
to the control panel. FS-Tools can be downloaded from www.firelite.com. A standard USB cable with male-A to male-A connectors,
which must be purchased separately, is required for local connection of the PC to the USB port J20 on the FACP main circuit board.
Remote programming requires that the PC have a GSM or Ethernet connection.
FS-Tools also provides the ability to create panel program files on a USB flash drive. The drive can then be plugged into USB port J20
on the FACP main circuit board.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “FS-Tools
Upload/Download” on page 123). Remote interrogation of panel programming, history logs, detector status, etc., is possible without
enabling the remote download option.
1.6.2 Dress Panel
An optional dress panel DP-ES-Ris available for the ES-200X (required by ULC for Canadian installations). The dress panel restricts
access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of
the dress panel and the ground stud in the backbox.The dress panel mounts to the backbox with two (2) #6-32 screws. The ES-200XC is
supplied standard with a dress panel.
1.6.3 Trim Ring
An optional Trim Ring (P/N TR-CE) is ava ilable for the FACP backbox. The Trim Ring adds 1.5” of wall coverage around the backbox,
concealing hardware and providing a finished appearance for a semi-flush mounted panel.
1.6.4 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one 100 AH battery . When the CHG-120F is
mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box.
1.6.5 Battery Charger
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the ES-200X FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box.
Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Refer to the CHG-75 Manual for additional information.
18ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
AccessoriesProduct Description
!
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the ES-200X FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-120F . The batteries and charger can be housed in the BB-55F battery box which
can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the char ger and batteries greater
than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.
1.6.6 ECC-50/100
The ECC-50/100 is a single channel, 50 watt, 25 V
notification applications, or both. Automatic activation of the ECC-50/100 is possible via eight Command Input Circuits (CMD) or via
the ANN BUS serial communications link from the ES-200X FACP.
, emergency voice evacuation panel that may be used for fire applications, mass
RMS
1.6.7 ECC-FFT
An ECC-FFT Fire Fighter Telephone provides supervision, annunciation, and control for local and remote telephone handsets. The ECCFFT’s keypad provides indications of phone activation and corresponding trouble conditions. Not for use in Canadian applications.
1.6.8 W-GATE Wireless Gateway
The W - GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a LiteSpeed SLC loop on the ES-200X. It
is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply evaluated for life safety. A vailable wireless
devices include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, a monitor module,
and a relay module. A maximum of 100 wireless devices can be used in the system. For details about wireless devices, system setup, and
operation, see the SWIFT® Smart Wireless Integrated Fire Technolog y Instruction Manual #LS10036-000FL-E.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission
(FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the
USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this
product may be legally used outside the USA.
1.6.9 ANN-BUS Annunciators/Modules
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR
WIRING.
Guidelines
•A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be
connected to the primary communication circuit (EIA-485) terminals on TB9. A secondary communication circuit for these devices
is available at TB8. Each ANN-BUS communication circuit supports up to eight (8) annunciators. Compatible devices include the
following:
– ANN-80 LCD Annunciator (UL applications only)
– ANN-100 LCD Annunciator (FM and Canadian applications only)
– ANN-S/PG Serial/Parallel Printer Interface Module
– ANN-I/O LED Driver Module
– ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)
– ANN-RLED Annunciator Module (red alarm LEDs only)
– ANN-RLY Relay Module (can be mounted in the supplied FACP chassis)
•When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in the system.
•The panel is capable of operating a primary ANN-BUS (TB9) and a secondary ANN-BUS (TB10) simultaneously.
•Only one audio system (ECC-50/100 or ACC-25/50) may be connected to the ANN-BUS.
ANN-80/ANN-100 Remote Fire Annunciators
The ANN-80 and ANN-100 Annunciators are 80 charac ter, backlit LCD remote fire annunciators. They mimic the display on the control
panel and will annunciate device type, point alarm, trouble or supervisory conditions, zone assignments plus any custom alpha labels
programmed into the FACP. The annunciators also provide system status LEDs to display AC Power, Alarm, Trouble, Supervisory and
Alarm Silenced conditions. Additionally, the annunciators are capable of remotely performing critical system functions such as
Acknowledge, Silence, Reset and Drill. Communication between the annunciators and the FACP is accomplished over a two wire RS485 serial interface employing the ANN-BUS co mmunication format. The devices are powered, v ia two additio nal wires, from either the
host F A CP or remote UL-listed, filtered, regulated, power supply.
The function buttons and piezo sounder may be individually enabled and disabled through the FACP software. Refer to “ANN-80/100 Options” on page 98 for a description of this feature and programming information.
ANN-S/PG Serial/Parallel Interface Module
The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel printer to the FACP for a real-time
log of system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mounting.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/201819
Product DescriptionGetting Started
ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with mos t customized
graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The module is provided with a plastic wall mount.
ANN-LED Annunciator Module
The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general system faults and input zones/points when
used with a compatible F ACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up
to ten input zones or addressable points. The ANN-RLED provides alarm (red) indication for up to 30 input zones or addressable points.
Multiple ANN-(R)LED modules may be used for full system coverage.
ANN-RLY Annunciator Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP.
1.7 Getting Started
The following is a brief summary of the minimal steps involved in bringing an ES-200 on-line:
•Install backbox and main circuit board (refer to “Mounting the Backbox” on page 22)
•Address and install intelligent devices (refer to the SLC Wiring Manual)
•Enter autoprogramming (refer to “Autoprogram” on page 52)
•Resolve programming conflicts
•Go to point program to enter specific data (refer to “Point Program” on page 53). Use the right and left arrow keys to navigate
between devices.
1.8 Telephone Requirements and Warnings
1.8.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.3A
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone
line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not
exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the
telephone company to determine the maximum REN for the calling area.
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary . If tr ouble
is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer:Honeywell International, Inc.
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
NOTE: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP
door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number
must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this
even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment
attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to “IPOTS-COM Communicator” on page 30 for an
illustration of the proper installation of this equipment.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
20ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Telephone Requirements and WarningsProduct Description
1.8.2 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is re quired to give
advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service.
Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided
as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
T wo separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone netw ork upstream (as first device) of any private telephone system
at the protected premises.
A plug and jack used to connect this equipment to the pr emises wiring and telephone ne twork must comp ly with the applicable FCC Part
68 rules and requirements adopted by ACTA. This equipment is designed to be connected to the telephone network or premises wiring
using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
1.8.3 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equipment meets certain tele-
communications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical
Requirements document(s). The Department does not guarantee the equipment will operate to the users’ satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that
compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier . Any repairs or
alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request
the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal
metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropria te electri c inspections author ity, or elec-
trician.
“The Ringer Equivalence Number
allowed to be connected to a telephone interface. the termination of an interface may consist of any combination of devices subject only
to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in
the Radio Interference Regulations of the Canadian Department of Communications.”
Representative:NOTIFIER/FIRE•LITE, CANADA
(REN) assigned to each terminal device provides an indication of the maximum number of terminals
IC Certificate Number: 2132A-EVOLX
Ringer Equivalence Number (REN): 0.3A
Load Number: 2
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/201821
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter
!
RTN-OUT-
COMMUNICATOR
DISPLAY
24V
RTN+OUT+
BATTERY
N/L2EARTHH/L1
USB-A
C
NO NC
CNO NC
CNCNO
SUPVTRBLALRM
ANN-LC
SLC
RMT SYNC
ANN-BUS PRI
ANN-BUS SEC
NAC4NAC3
NAC2
NAC1
@
Figure 2.1 ES-200X Chassis Removal and Installation
Backbox
Main Circuit Board on chassis
mounting studs
es200chassisinbox.wmf
grounding stud
mounting slots
holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme tem-
peratures are not encountered. The area should be readily accessible wit h sufficient room to easily install and maintain the panel. Locate
the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s)
and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.1 Mounting the Backbox
CAUTION: STATIC SENSITIVE COMPONENTS
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS. ALWAYS GROUND YOURSELF WITH A
PROPER WRIST STRAP BEFORE HANDLING ANY BOARDS SO THAT STATIC CHARGES ARE REMOVED FROM THE
BODY. USE STATIC SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board can be easily removed.
Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Pla ce the chassis
assembly in a safe location until it can be reinstalled in the backbox.
1.Mark and pre-drill hole in the wall for the center top keyhole mounting bolt using the dimensions illustrated in Figure 2.2 on
page 23.
2.Install center top fastener in the wall with the screw head protruding.
3.Place backbox over the top screw, level and secure.
4.Mark and drill the left and right upper and lower mounting holes.
Note: Outer holes (closest to sidewall) are used for 16” O.C. stud mounting.
5.Install remaining fasteners and tighten.
6.When the location is dry and free of construction dust, install the chassis/circuit board assembly.
7.Mount the chassis to the backbox by aligning the two mounting tabs with the slots in the backbox, then position the two mounting
hole tabs over the studs with nuts located in the upper portion of the backbox.
8.Slide the tabs located on the bottom of the chassis into the mounting slots in the backbox by pressing the chassis down.
9.Secure the chassis to the backbox by tightening the two mounting nuts (#10-32) at the top, and to ensure proper grounding, use a
3/8” nut driver or socket.
10. If the main circuit board is not already attached to the chassis, install it by positioning the ten mounting holes over the studs on the
chassis and secure with the supplied screws.
Section 2: Installation
22ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Mounting the BackboxInstallation
Figure 2.2 ES-200X Cabinet Mounting
9050udencl.wmf
Semi-Flush
Mounting
Do not recess box more
than 3.875” into wall to
avoid covering venting
holes on top of box.
Hinge Slot for optional
Dress Panel
Hinge Slot for optional
Dress Panel
Semi-flush
mounting hole
Mounting
slots for
optional
Trim Ring
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/201823
InstallationMounting the Backbox
6.537” (16.6cm)
5.207” (13.23cm)
16.822” (42.73 cm)
19.26” (48.92 cm)
Figure 2.3 Cabinet Dimensions
Height
Depth
Width
Left Side
Right Side
Top
Bottom
An optional Trim Ring (P/N TR-CE-) is also available for semi-flush mount installations.
24ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
PowerInstallation
!
N/L2EARTHH/L1
Figure 2.4 Earth Ground Connection
9
2
0
0
g
r
n
d
.
w
m
f
grounding stud
keps nut
keps nut
Grounding
Cable #71073
-
-
+
+
Interconnect
Cable
!
2.2 Power
WARNING: RISK OF EQUIPMENT DAMAGE AND PERSONAL INJURY
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED T O THIS PANEL. DISCONNECT ALL SOURCES
OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING
AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
2.2.1 AC Power and Earth Ground Connection
Primary power required for the FACP is 120 or 240 VAC, 50/60 Hz, 3.25 amps. The FACP will
auto-detect the voltage used. No special switch or jumper is required to select AC power . Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC)
and/or local codes. Use 14 AWG (2.00 mm
certain that the AC mains circuit breaker is off
and the control panel. Connect wiring from the AC mains to TB13 on the FACP, being careful to
observe proper connections.
Remove the two keps nuts from the grounding stud in the backbox. Connect the incoming earth ground wire to supplied cable #71073
with a wire nut. Position the ring terminal end over the grounding stud. Secure with one of the keps nuts. Place the ring terminal from the
other supplied ground cable #71073 over the ground stud and secure with the second keps nut. Wire the ground cable to the bottom position of TB11. Refer to Figure2.1 on page22 for location of the stud. Ensure that the ground for AC mains is the first cable installed,
closest to the backbox. This connection is vital in reducing the panel’s susceptibility to transients generated by lightning an d electrostatic
discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be
applied to the panel before installing the battery interconnect cable (refer to the foll owing sec t ion).
2
) or larger wire with 600 volt insulation rating. Make
before wiring any connections between the mains
2.2.2 Battery Power
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/201825
The batteries must be sealed lead acid type. Before connecting the batteries to the FACP,
make certain that the interconnect cable between the batteries is not
connected. Do not connect the interconnect cable until the system is completely installed. Observe polarity when
connecting the batteries. Connect the battery cable to J9 on the main circuit board. Refer to
“Power Supply Calculations” on page 128, for calculation of the correct battery rating.
WARNING: RISK OF PERSONAL INJURY
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN
DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH
WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
InstallationRelays
+ -
+ - + -
PWR2
24V
PWR1
Figure 2.5 Special Application Power Outputs - 24 VDC
Power-limited Non-resettable or Resettable Power
1.0 amperes max., 24 VDC nominal filtered, nonresettable or resettable power is programmable. PWR1
can be programmed as Class B or Class A.
Power-limited Resettable or Non-resettable Power
1.0 amperes max., 24 VDC nominal filtered, programmable
resettable or non-resettable power can be drawn from TB11
Terminals 5(+) and 6(-)
e
s
2
0
0
t
b
1
1
.
w
m
f
TB11
Optional Class A
wiring return
CNO NC
C
NONC
CNCNO
SUPV
TRBL
ALRM
Figure 2.6 Relay Terminals
Relay contacts shown with power
applied to panel and no active
troubles, alarms or supervisories
TB1
Note that the programmable relay
labeled as Relay 1 is factory default
programmed as Alarm and
programmable Relay 3 is factory default
programmed as Supervisory.
The relay labeled Relay 2 is fixed as a
Trouble relay and cannot be changed. It
is a fail-safe relay which will transfer on
any trouble or total power failure.
e
s
2
0
0
r
l
y
.
w
m
f
TB2TB3
RELAY 1
RELAY 2RELAY 3
2.2.3 Special Application DC Power Output Connection
All Special Application DC power outputs are power-limited (refer to “UL Power-limited Wiring Requirements” on page 29).
2.3 Relays
The F AC P provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay,Note that relay connections may be
power-limited or nonpower-limited, provided that 0.25” spacing is maintained between conductors of power-limited and nonpower-limited circuits. Refer “UL Power-limited Wiring Requirements” on page 29.
2.4 Notification Appliance Circuits
The control panel provides four Class B or four Class A NACs (Notification Appliance Circuits). Each circuit is capable of 2.5 amps of
current. Total current in alarm for all external devices cannot exceed 6.0 amps (refer to “Calculating the System Current Load” on
page 128). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Device Compati-bility Document for a listing of compatible notification appliances. The NACs, which are located on the main circuit board, may be
expanded via the FCPS Series field charger/power supplies.
The following sections describe the configuration and wiring of Class B and Class A Notification Appliance Circuits on the ES-200X
main circuit board.
26ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Notification Appliance CircuitsInstallation
NAC4NAC3
NAC2
NAC1
+
+
+
+
+
+
+
+
+
+
+
+
Figure 2.7 NAC Class B Wiring
4 Class B Notification Appliance Circuits, supervised and power-limited - 4.7 kΩ, ½ watt P/N:71252 UL listed
Polarized Bells
Polarized Bells
Polarized HornsPolarized Horns
Polarized Strobes
Notification Appliance Circuit
polarity shown in alarm state
Dummy Load all unused circuit
TB5
e
s
2
0
0
n
a
c
y
.
w
m
f
Polarized Strobes
circuit number
NAC 1
NAC 2
NAC 3
NAC 4
TB4TB6TB7
NAC4NAC3
NAC2
NAC1
+
+
+
+
+
+
+
+
+
+
+
+
4 Class A Notification Appliance Circuits, supervised and power-limited
Polarized HornsPolarized Horns
Notification Appliance Circuit
polarity shown in alarm state
Polarized Bells
Polarized StrobesPolarized Strobes
Figure 2.8 NAC Class A Wiring
NAC 1NAC 4
TB5TB7
NAC 2N AC 3
Dummy Load all unused circuits
Polarized Bells
circuit number
e
s
2
0
0
c
n
a
c
z
.
w
m
f
TB7TB4
2.4.1 Class B NAC Wiring
2.4.2 Class A NAC Wiring
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/201827
InstallationRemote Synchronization Output
RTN- OUT-
RTN+OUT+
CNO NC
SUPV
RMT SYNCNAC1
Figure 2.9 Remote Sync Output
Remote
Power
Supply
FACP main
circuit board
Remote Sync Output
Sync Input
4.7 KΩ ELR
e
s
2
0
0
s
y
n
c
.
w
m
f
Optional Class A Return
2.5 Remote Synchronization Output
Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at
exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a
potential hazard to individuals. Devices connected directly to the control panel’s NACs can be synchronized as described in “Type” on
page 76.
Notification appliances connected to FCPS NAC power supplies require synchronization with the FACP’s devices. This can be accomplished by connecting the Remote Synchronization Output from TB8 of the ES-200X to the sync input of the FCPS-24FS6/8 Power Supply. The 24 VDC signal from TB8 follows, that is mimics, the signal on NAC1. This allows the devices connected to the power supply to
be synchronized with the devices connected to NAC1 on the FACP.
The Remote Synchronization Output is power-limited and supervised (refer to “UL Power-limited Wiring Requirements” on page 29)
and can be wired in Class B or Class A. A 4.7 KΩ ELR resistor must be connected to the end of the wiring at the remote power supply
for Class B wiring. Supervision of the remote synchronization is automatically enabled when the remote sync output is enabled. Supervision will be disabled if the output is disabled. For more information on enabling the remote sync output, refer to page 104.
28ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
UL Power-limited Wiring RequirementsInstallation
RTN- OUT-
COMMUNICATOR
DISPLAY
24V
RTN+OUT+
BATTERY
N/L2EARTHH/L1
USB-A
CNO NC
CNO NC
CNCNO
SUPV
TRBL
ALRM
ANN-LC
SLC
RMT SYNC
ANN-BUS PRI
ANN-BUS SEC
NAC4NAC3
NAC2
NAC1
Figure 2.10 Typical UL Power-limited Wiring Requirements
Power-limited Circuits (Class 2)
Powerlimited
Circuits
(Class 2)
AC
Power
Grounding
Stud (see
Figure 2.4)
n
f
w
1
0
0
x
u
l
w
i
r
e
.
w
m
f
To
Batteries
maintain minimum 0.25” between
power-limited and nonpower-limited
circuits wiring
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at
least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. When connecting the ground cables, be sure that the AC mains ground is the first one
installed, closest to the backbox. A typical wiring diagram for the ES-200X is shown below.
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/201829
InstallationIPOTS-COM Communicator
Figure 2.11 Communicator Installation
Customer Premises Equipment and Wiring
Telephone
Line
FACP with IPOTS-COM
mounted internally
Network
Service
Provider’s
Facilities
Network
Demarcation
Point
RJ31X
Jack
Unused
RJ-11 Jack
Unused
RJ-11 Jack
Telephone
Telephone
Telephone
Answering
System
Fax Machine
Computer
e
s
2
0
0
d
a
c
t
.
w
m
f
123456778
123
4
56 8
LED4
LED5
LED6
LED7
LED8
J3
J5J4
ETHLINE2LINE1
Figure 2.12 Wiring Phone Jacks
Ring
Tip
To premise phones
Ring
Tip
Green Wire
Red Wire
Rin
Ti
Green
Red Wire
(Secondary Lines)
Incoming Telco Phone
Ring
Tip
To premise
(Primary Lines)
Incoming Telco Phone
RJ31X
Jack
RJ31X
Jack
Note: Shorting
bars inside RJ31X
Jack removed
during installation.
7 foot Cable
MCBL-7
(ordered
separately)
Primary Phone Line
Secondary
Phone Line
Module Female
Connectors
Male Plug
Connectors
e
s
2
0
0
j
a
c
k
.
w
m
f
IPOTS-COM
SW2
SW3
Figure 2.13
IPOTS-COM Dip
Switches
S
W
2
S
W
3
2.7 IPOTS-COM Communicator
Two independent telephone lines can be connected to the control panel via the IPOTS-COM Phone/IP Communication Module. Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is
critical that the IPOTS-COM Digital Communicator be located as the first device on the incoming t elephone circuit to properly function.
Important! The IPOTS-COM must not be used to dial a phone number that is call-forwarded.
30ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Wiring
Connection and wiring of two phone lines is required as shown below.
Dip Switches
There are two configurable dip switches on the IPOTS-COM communicator.
•SW2: 6-position dip switch- FUTURE USE- No configuration necessary.
•SW3: 2-position dip switch- Factory Settings- Do not change unless instructed to do
so by Honeywell.
Loading...
+ 138 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.