In order to function properly, this detector must be installed according to the instructions. Do not exceed the electrical or ambient specifications or the
detector will not function properly. This detector must be protected from the elements.
INSTALLATION SEQUENCE
Step 1. Verify duct air flow direction and velocity .....................................................................................................................................................2
Step 2. Drill the mounting holes ...............................................................................................................................................................................2
Step 2.1 Install the sampling tube for ducts less than 11⁄2 feet (0.46m) wide .............................................................................................................2
Step 3. Secure the detector housing to the duct ......................................................................................................................................................3
Step 4. Install the sampling tube for ducts greater than 11⁄2 feet (0.46m) wide .......................................................................................................3
Step 4.1 Installation for ducts greater than 11⁄2 feet (0.46m) but less than 8 feet (2.4m) wide ................................................................................3
Step 4.2 Installation for ducts more than 8 feet (2.4m) wide ....................................................................................................................................4
Step 5. Install the filters ............................................................................................................................................................................................4
Step 6. Field wiring ...................................................................................................................................................................................................4
Step 7. Perform detector check ................................................................................................................................................................................5
Step 8. Install the cover ............................................................................................................................................................................................5
Step 9. Detector Maintenance and Test Procedures ................................................................................................................................................5
[1] Verify Duct Air Flow Direction And Velocity
The D350PL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute (0.5 to 20.32m/s).
Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If necessary, use a velocity meter
to check the air velocity in the duct.
[2] Drill The Mounting Holes
Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indicated on the template.
[2.1] Sampling Tube Installation for Ducts Less Than 11⁄2 Feet (0.46m) Wide (see Figur e 2)
1. Remove the front cover.
2. Slide the plastic sampling tube into the housing bushing and extend it the full width of
the duct.
3. Align the holes in the bushing with the holes in the sampling tube. Secure with the #8
self-tapping screw into the bottom of the permanent tube.
NOTE: For ducts greater than 11⁄2 feet (0.46m) in width, refer to sections [4], [4.1] and
[4.2].
[3] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in Figure 3. Use the two 11⁄4″ long
sheet metal screws to screw the detector housing to the duct.
CAUTION: Do not overtighten the screws.
Figure 2. Plastic sampling tube
connected to duct smoke detector
F300-27-00 7 I56-1975-003R
[9.2.2] Alarm Tests
[9.2.2.1] M02-04-00 Magnet Test
1. Place the painted surface of the magnet onto the TEST locator
on the bottom of the detector housing (Figure 12).
2. Verify system control panel alarm status and control panel execution of
all intended auxiliary functions (i.e. fan shutdown, damper control, etc.)
3. The detector is self-restoring when the magnet is removed.
Verify that the system control panel has reset.
[9.2.2.2] RTS451/RTS451KEY Remote Station Test
The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm
capability of the duct smoke detector. These accessories provide the
stimulus to initiate an alarm condition at the detector. The detector is
self-restoring when the accessory test stimulus is removed.
Verify that the system control panel has reset.
[9.2.3] Sensitivity Tests
Notify the proper authorities that the smoke detector system is undergoing maintenance, and that the system will temporarily be out of service. Disable
the device or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department.
[9.3] Maintenance of Duct Smoke Detectors
[9.3.1] Air Filters
1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with new filters (p/n F36-09-11). If they are not heavily coated,
use a vacuum cleaner or compressed air nozzle to remove dust, then reinstall the filters.
[9.3.2] Photo Detector Boards
1. Remove the screen by gently grasping on each side and pulling straight off
2. Lift the photo chamber in the same fashion. Vacuum the screen and cover. Use clean, compressed air to loosen and
blow out any remaining debris. Replacement screens (p/n S08-39-01) are available.
3. Vacuum photo chamber, then use clean compressed air to blow area clean.
4. Replace the chamber by pressing it onto the base. Press the screen into place. It should fit tightly on the chamber.
Figure 12. Testing detector alarm:
H0137-00
Figure 10. Wiring Diagram for D350PL Duct Detector
with optional RA400Z
Figure 11. System Wiring Diagram for D350PL Duct
Smoke Detector with RTS451/RTS451KEY