While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
Fire Alarm.............................................................................................................................................. 46
Fire Alarm Restoral...............................................................................................................................46
General Page Using Optional Remote Microphone (ACC-25/50DA Only).......................................... 46
Emergency Page Using Optional Remote Microphone (ACC-25/50DA Only)..................................... 46
One Speaker Circuit...................................................................................................................................... 50
Single Channel....................................................................................................................................... 50
One Speaker Circuit With Backup................................................................................................................ 52
Single Channel....................................................................................................................................... 52
Two Speaker Circuits.................................................................................................................................... 54
Single Channel....................................................................................................................................... 54
How to use Table 6-2 to calculate system current draws...................................................................... 62
Calculating the Battery Size.......................................................................................................................... 63
Selecting and Locating Batteries........................................................................................................... 63
Digital Voice Messages ...........................................................................................................................................64
This audio panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Audio Distribution Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code
Note: Audible signal appliances used in public mode applications, are required to have minimum
sound levels of 75 dBA at 10 feet (3 meters) and a maximum level of 120 dBA at the minimum hearing distance from the audible appliance.
To ensure that the appliance is clearly heard, the audible appliance sound level must be at least 15
dBA above the average ambient sound level or 5 dBA above the maximum sound level with a duration of at least 60 seconds, depending on which level is greater, with the sound level being measured 5
feet (1.5 meters) above the floor.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1711 Amplifiers for Fire Protective Signaling Systems
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL
864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the
approval of the local Authority Having Jurisdiction (AHJ).
ACC-25/50DA 52265:B 1/30/08 7
25W Speaker Circuit
25W Speaker Circuit
25W Speaker Circuit
25W Speaker Circuit
To Additional ACC-25/50DA Panels
ACC-25/50DA
Audio Riser
Audio Command Center Distributed System
Audio Riser
25W Speaker Circuit
25W Speaker Circuit
Master Command Bus
ACC-25/50DA
FACP Control
Audio Riser
Master Command Bus
Master Command Bus
Audio Riser
FACP Control
ACC-25/50
CMD inputs on the ACC-25/50 and ACC-25/50DA(s)
1. The F ACP can automatically control the audio system via the
FACP Control
8 ACC-25/50DA 52265:B 1/30/08
2. The Audio Riser connects the audio output of the ACC-25/50
to each of the ACC-25/50DA(s).
the ACC-25/50 to the ACC-25/50DA(s).
configuration.
3. The Master Command Bus provides an All-Call trigger from
4. Maximum of 25 Distributed Audio panels may be used in this
accdadistsys.CDR
Speaker Circuit #9
Speaker Circuit #16
Speaker Circuit #17
Speaker Circuit #24
Audio Riser
Up to 24 Zones @ 150W (max.)
Audio Command Center Zone System
Audio Riser
Speaker Circuit #1
ACC-25/50DA
Speaker Circuit #8
ACC-25/50DA
ACC Control Serial Link (RS-485)
ACC Control Serial Link (RS-485)
ACC-25/50
Zone Split Configuration
CMD inputs on the ACC-25/50ZS.
50ZS to each of the ACC-25/50DAZS(s) to distribute alarm
or paging audio.
the routing of the alarm or paging audio.
survivability from attack by fire requirements in National
Fire Alarm Code, NFPA 72.
1. The FACP controls the audio system via the ACS Link or
2. The Audio Riser connects the audio output of the ACC-25/
Automatic Control via the
ACS Link or CMD Input
ACC-25/50DA 52265:B 1/30/08 9
3. The ACC-25/50ZS uses the Control Serial Link to control
4. Riser conductors must be installed in accordance with the
accdazsdistsys.CDR
Product Description
CHAPTER 1Pr oduct Description
The AUDIO•COMMAND•CENTER•25/50DA Distributed Panel (ACC-25/50DA) and AUDIO•COMMAND•CENTER•25/50DAZS Zone System Distributed Panel (ACC-25/50DAZS) are single channel, 25 watt, 25 V
gency voice evacuation panels which are designed to interface directly to the AUDIO•COMMAND•CENTER•25/50
(ACC-25/50) Series audio panels. The ACC-25/50DA Series, which supports up to eight speaker circuits, can be
used to distribute voice evacuation audio over a building’s speaker system. The audio riser input provides automatic
gain control (AGC) which compensates for any audio signal loss due to circuit loading or cable length, ensuring that
a full output signal is delivered to the speakers. An optional FC-MGM message generator is available with standard
pre-recorded message or programmable message capability (up to sixty seconds). An integral power supply with battery charger supplies operational power. An ACC-AAM25 audio amplifier is provided standard with each base unit.
An optional second ACC-AAM25 amplifier is also available for backup purposes or to provide an additional 25 watt
speaker circuit. Optional 70 V
conversion modules are also available for installations where 70 V
RMS
to be installed or already exist. The modular design allows for ease-of-serviceability.
The ACC-25/50DA can be automatically activated by the five CMD inputs from an FACP. The ACC-25/50DAZS
can be automatically activated via the Zone System serial communications link from the ACC-25/50ZS.
, emer-
RMS
speakers are
RMS
T wo Command Input Circuits can be independently field programmed for activation by an FACP Notification Appliance Circuit reverse polarity or by closure of a supervised normally open contact and three Command Input Circuits
activate on contact closure. CMD 1 and CMD 2 provide terminals for NAC input and output to allow instal lati on of
the audio panel anywhere along the NAC circuit being used to activate it.
The ACC-25/50DAZS includes an ACC-ZPM Zone Page Module and an ACC-ZSM Zone Splitter Module. These
modules provide up to eight speaker circuits that may be manually or automatically activated. Significant technological enhancements set the ACC-25/50DA Series apart from other voice panels. These enhancements include full supervision in both active (alarm or music) and standby conditions.
Note: Music cannot be used for ACC-25/50DAZS.
Supervision is provided for:
amplifier outputs
field wiring (shorts and opens)
optional message generator (FC-MGM)
all tone generators
optional remote microphone
If the audio riser input fails, the distributed audio panel can be programmed to switch to the built-in tone generator or
optional FC-MGM Message Generator. If the FC-MGM fails or is not installed, the tone generators on the main
circuit board can be automatically switched in as backups.
Power is fed independently
to each amplifier so that a short circuit in one amplifier will not shut down the other. Full
output power of 25 watts per amplifier is generated while in a low battery condition. Power is not diminished when
the optional 70 V
transformer module is installed. Audio is amplified utilizing modern integrated circuits as
RMS
opposed to transformer technology. This provides for very low signal distortion for crystal clear audio.
Primary applications for the audio panels include structures such as restaurants, schools, auditoriums, places of
worship, buildings with occupancies over 50, etc. The ACC-25/50DA Distributed Audio Series is designed to
interface directly to addressable or conventional fire alarm control panels or with the ACC-25/50 series audio control
panels to distribute audio in systems that require more than 50 watts.
10
ACC-25/50DA 52265:B 1/30/08
Product Features
1.1Product Features
• 25 watts of 25 V
audio power (expandable to 50 watts) per panel
RMS
• Automatic gain control (AGC) circuit ensures an unattenuated audio signal on the audio riser input
• Optional 70.7 V
conversion module available for each amplifier (note that speaker wiring continues to be
RMS
supervised in standby, alarm and when background music is playing with this option module installed)
• Modular design for maximum system flexibility
• Unobstructed module access and removable terminal blocks for ease of servicing and module replacement
• Designed to allow easy system expansion
• Five Command Input Circuits:
CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance
Circuits (reverse polarity) or contact closures
CMD3, CMD4 and CMD5 are activated by contact closures
• Speaker Circuits
single Style Y or Z speaker circuit (one ACC-AAM25 Audio Amplifier provided with base unit)
two Style Y or Style Z speaker circuits (with optional second ACC-AAM25 Audio Amplifier instal led)
eight Style Y or four Style Z speaker circuits using ACC-ZSM Zone Splitter Module
• ACC-25/50DAZS can be controlled by the ACC-25/50ZS via the Zone System serial link (EIA-485) to the
ACC-ZPM.
• Optional FC-MGM Message Generator Module with standard, prerecorded message:
“May I have your attention please. May I have your attention please. The signal you have just heard
indicates a report of a fire in this building. Please proceed to the nearest exit and leave the building.
Do not reenter the building unless directed to do so by the proper authorities.”
• Field selectable message capability and custom message field recording capability using optional FC-MGM
module’s audio input RCA jack or mini Audio jack for connection to a personal computer
• Record/playback control switches on optional FC-MGM
• One 60-second, two 30-second, three 20-second or four 15-second custom messages on optional FC-MGM
• Integral tone generators field selectable for steady, slow-whoop, high-low or chime tones
• Powered by integral AC power supply or batteries during AC fail
• T wo Form-C trouble relays:
System Trouble Relay - TB1
AC Power Loss Relay - TB11
• 35 mA Special Application auxiliary power output for addressable modules (when interfaced with the
Fire•Lite MS-9200(E), MS-9200UD or MS-9600 FACP or equivalent) and End-of-Line power supervision
relays
to the FC-RM Product Installation Document #51247 for additional information
• Optional local playback speaker (FC-LPS) for use with optional FC-MGM
• System Status LEDs (refer to Section 1.3 "Indicators" on page 17)
ACC-25/50DA 52265:B 1/30/08 11
Product Features
FIGURE 1-1:Distributed Audio Main Board
Specific
Application
Power
35 mA
nonsupervised
power-limited
Form-C AC
Loss Relay
nonsupervised
Input Triggersupervised
(activation by
reverse polarityactive polarity
shown)
use ELR specified
for triggering
source
nonsupervised
OUT IN
shield
shield
All CMD inputs and Trouble Contact Closure are supervised
and power-limited and require a 4.7KΩ ELR, P/N: 27072
CMD1 & CMD 2 Input
Trigger by contact
closure or NAC reverse
polarity - alarm polarity
shown
OUT IN
OUT IN
CMD3, CMD4 & CMD5 Input
Trigger by contact closure
alarm polarity shown (inputs only)
1 2
1 2
1 2
for monitoring
trouble contacts of
an external device
such as charger or
power supply
1 2
S3 Charger Enable/
Disable Switch
(shown in charger
enabled position)
Connector for
Transformer
Form-C Trouble Relay
(nonsupervised)
FC-MIM
AC25DAMNT1.CDR
12
HOT
(supervised,
nonpower-limited)
EARTH
NEUTRAL
AC Power Only (supervised,
nonpower-limited)
Refer to AC Power in Section
1.2 "Specifications" on page 15
ACC-25/50DA 52265:B 1/30/08
Battery
Product Features
FIGURE 1-2:
Distributed Audio Board With Amplifiers
CAUTION: Match proper polarity connections to field wiring and
speakers. Polarity shown is in the standby and alarm conditions.
Speaker Circuits are supervised
and power-limited
ELR Resistor required only for
Style Y (Class B) circuits.
4.75 KΩ, 1 watt P/N: 75470
+ - + -
ACC-25/50DA 52265:B 1/30/08 13
AC25DAMNT2.CDR
Product Features
ACC-ZSM and ACC-ZPM Modules for Distributed Audio with Zone Splitter Feature Only
FIGURE 1-3:Distributed Audio Board With ACC-ZPM & ACC-ZSM Modules
Circuits are supervised and
power-limited
ELRs 4.75KΩ P/N: 27589
Speaker Circuits are
supervised and power-limited
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
1 2 3 4 1 2 3 4
1 2 3 4
AC25DAZSMNT.CDR
(supervised)
1 2 3 4
14
ACC-25/50DA 52265:B 1/30/08
Specifications
1.2Specifications
AC Power - TB10
ACC-25/50DA(ZS):120 VAC, 50/60 Hz, 2.0 amp.
Supervised, nonpower-limited circuit
Wire size: minimum #14 AWG with 600 V insulation.
AC Loss Relay - TB11
Operation: normally energized fail-safe relay transfers on AC power loss for independent monitoring by DACT.
AC Loss relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.6 amps @ 30 VAC (resistive)
Nonsupervised circuit
Battery (lead acid only) - P11
Maximum Charging Circuit: Normal Flat Charge - 27.6V @ 0.800 amp
Maximum Charger Capacity: 18 Amp Hour battery (cabinet holds maximum 18 Amp Hour Battery.)
Supervised, nonpower-limited circuit
Command Input Circuits (alarm polarities shown)
• CMD1 - TB6 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals
which provide feed through of the NAC circuits to NAC devices down stream
• CMD2 - TB7 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals
which provide feed through of the NAC circuits to NAC devices down stream
• CMD3 - TB2 Terminals 1(+) & 2(-) are input terminals for contact closure only
• CMD4 - TB3 Terminals 1(+) & 2(-) are input terminals for contact closure only
• CMD5 - TB4 Terminals 1(+) & 2(-) are input terminals for contact closure only
Operation: CMD1 & CMD2 circuits are independently field programmable to activate amplifiers on NAC polarity reversal or contact-closure. IMPORTANT! When CMD1 and CMD2 are configured for reverse polarity, the
NAC cannot be Coded.
CMD3, CMD4 and CMD5 are fixed to activate on contact closure only
Power-limited and supervised circuitry
Normal Operating Voltage: 10.5 VDC - 29 VDC Maximum Voltage: 29 VDC
NAC Reverse Polarity Current (requires End-of-Line Resistor from NAC): 1.6 mA maximum.
Contact Closure Operation Current (requires 4.7K, ½ watt End-of-Line Resistor P/N 27072): 6.6 mA maximum
Maximum Wiring Impedance CMD1 - CMD5 (Contact Closure Operation): 200Ω
Maximum Input Impedance:
• CMD1 & CMD2 (Reverse Polarity Operation): 20KΩ
• CMD1 - CMD5 (Contact Closure Operation): 3.4KΩ
Audio Amplifier Module - Standard ACC-AAM25 Amplifier plugs into P1 of main circuit board, optional
ACC-AAM25 Amplifier plugs into P2 of main circuit board
Backup Audio In - TB2, Terminals 1(+) & 2(-) [Out Terminals 3(+) & 4(-)] on Amplifier Module
Operation: When TB2 is wired between the two amplifiers of a panel, the optional amplifier provides backup to
the standard amplifier. Switch S1 on the backup amplifier must be 'ON' and jumpers placed from backup amplifier TB2 Terminal 3 to standard amplifier TB2 Terminal 1 and from backup amplifier TB2 Terminal 4 to standard
amplifier TB2 Terminal 2. Refer to Section 5.4 "One Speaker Circuit With Backup" on page 52, for additional
information.
ACC-25/50DA 52265:B 1/30/08 15
Specifications
Speaker Circuit - TB1 Terminals 3(+) & 4(-) Style Y, 3(+), 4(-), 5(+) & 6(-) Style Z, 1 & 2 Shield (Standby and
Alarm Polarity Shown) on Amplifier Module
Power-limited, supervised circuitry
Operation: Circuit can be wired Style Y or Style Z
Normal Operating Voltage: 25 V
(70.7 V
@ 350 mA max. with maximum Load Impedance of 200Ω operation possible by plugging
RMS
@ 1 amp max. and maximum Load Impedance of 25Ω
RMS
optional FC-XRM70 conversion module into P1 of audio amplifier).
Circuit wiring is supervised during standby, alarm and when background music is playing
Output Power: 25 watts (20 watts when background music is employed). Frequency Range: 400Hz - 4,000Hz
Maximum total capacitance for each AAM-25/50: 250 uF.
End-of-Line Resistor required for Style Y circuit: 4.75 KΩ, 1 watt (P/N: 75470)
ACC-ZSM Zone Splitter Module and ACC-ZPM Zone Page Module
Power-limited circuitry
Operation: Circuits on ACC-ZSM can be wired as eight Style Y or four Style Z
Normal Operating Voltage for Speaker Circuits: 25 V
(70.0 V
@ 350 mA max. with maximum Load Impedance of 200Ω operation possible by plugging
RMS
@1 amp Max. and maximum Load Impedance of 25Ω
RMS
optional FC-XRM70 conversion module into P1 of audio amplifier).
Speaker circuit wiring is supervised during standby and alarm. (Note that background music is not permitted
in
Zone Splitter configuration since open-circuit fault detection is not possible)
Output Power: 25 watts total. Frequency Range: 400Hz - 4,000Hz
Maximum total capacitance for ACC-AAM25: 250 µF. (Note that the total
capacitance for the ACC-ZSM
speaker outputs must not exceed the maximum of 250 µF).
End-of-Line Resistor required for Style Y (Class B) speaker circuit: 4.75 KΩ, 1 watt (P/N: 75470)
TB1 on ACC-ZPM: ACS (EIA-485) electrically isolated link to FACP provides programmed speaker control
Provides reverse polarity trigger input from ACC-25/50 Series Master Command Bus Output.
Supervised and power-limited circuitry
Normal Operating Voltage: 24 VDC regulated, filtered. Maximum Voltage: 25.4 VDC
Reverse Polarity Current: 125 mA maximum.
Standby Voltage: -5 VDC. Short Circuit Current: 0.5 mA. Maximum Load Resistance: 200 ohms.
Wiring connections to Master CMD Bus Circuit:
End-of-Line Resistor required for Class B using Terminals 2(+) & 1(-): 4.7 KΩ, ½ watt (P/N: 27072)
Class A (no End-of-Line Resistor) requires the wiring of Terminal 2(+) and Terminal 1(-) to next
Distributed Audio Panel
Special Application Power (Aux. Power) - TB9 Terminals 1(+) & 2(-)
Up to 35 mA @ 24 VDC special application power is available for powering addressable modules and associated
End-of-Line power supervision relays. Output is unsupervised.
Power-limited circuitry. Refer to the Device Compatibility Document for a list of compatible devices.
Form-C Trouble Relay - TB1
Normally energized fail-safe relay transfers its contacts on any panel trouble condition.
TB1 Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.6 amps @ 30 VAC (resistive).
• RCA Audio Jack Input (female connector)
Input Impedance: 30KΩ maximum
Input Voltage: 700 mV
maximum
RMS
Input Current: 1 mA maximum @ 700 mV
Requires preamplifier output. Mates to an RCA phono 'plug' - 3mm diameter, 10mm length, 9mm
shell diameter.
• 3.5 mm PC Audio Jack Input (female connector)
Input Impedance: 150KΩ maximum
Input Voltage: 700 mV
maximum
RMS
Input Current: 1 mA maximum @ 700 mV
Requires preamplifier output
Interfaces to personal computer line output or headset output (Note: Some laptop personal computers
only provide an audio output for headphones. It may be necessary to adjust the headphone output
level for proper recording of voice messages.)
• Microphone Connector for optional standard microphone P/N: FC-MICROPHONE
• the optional FC-MIM Microphone Interface Module which is used to connect the FC-RM Remote Micro-
phone Module to provide remote microphone paging capabilities.
Audio Riser - TB5
Magnetically isolated input utilizes signals up to 70.7 V
with a frequency range of 400 Hz to 4 KHz.
RMS
Note: For ACC-25/50DA Only - If background music is enabled, the maximum input signal to the riser:
• with a 20 watt speaker load per amplifier cannot exceed 25 V
• with a 25 watt speaker load per amplifier cannot exceed 20 V
RMS
RMS
Trouble Contact Input - TB12
Non-supervised, non-isolated trouble input that can be used by chargers, power supplies, etc.
Contact Closure Operation Current: 1.2 mA maximum
Standby Current: n/a
1.3Indicators
1.3.1 LEDs Located on Main Circuit Board:
• Power ON (green)
• AC Power (green)
• Active (green)
• System Trouble (yellow)
• Tone Generator Trouble (yellow)
• Battery Trouble (yellow)
• Charger Trouble (yellow)
• Ground Fault (yellow)
1.3.2 ACC-ZPM Zone Page Module (ACC-25/50DAZS Only)
• ACC Comm (green LED) - indicates Communication is active on the serial link to the ACC-25/50ZS. Off
• Input circuits CMD1 and CMD2 are independently field programmable to accept Notification Appliance Cir-
cuits or normally open contacts. (IMPORTANT! When CMD1 and CMD2 are configured for reverse polarity, the NAC cannot be Coded). Terminals are provided to allow feed-through of the NACs, allowing
placement of the ACC-25/50 Series anywhere along a Notification Appliance Circuit. A trouble on the ACC25/50DA will cause relay contacts at the out terminals of CMD1 to open, causing an NAC circuit trouble at
the FACP. Note: The ACC-25/50DA will not open the out terminals while in alarm. Monitoring ACC-25/
50DA troubles while in alarm requires use of independent trouble relay at TB1.
• Programming CMD1 and/or CMD2 for activation on contact closure will allow activation of the amplifiers on
a normally open contact transfer to the closed condition. Contact wiring is supervised for open conditions. A
short will cause amplifier activation (contact closure).
• Input circuits CMD3, CMD4 and CMD5 will only activate on contact closure which will allow activation of
the amplifiers on a normally open contact transfer to the closed condition. Contact wiring is supervised for
open conditions.
• Contact Closure Trouble Input is used for identification of troubles on an optional external power supply or
charger.
Audio Input Jacks (located on optional FC-MGM Message Generator Module)
• RCA Jack provides convenient connection to an audio source such as a tape player for recording a new digital
message.
• PC Jack provides convenient connection to an audio source such as a personal computer for recording a new
digital message. The jack allows vertical plug-in of a standard mini-jack cable.
• Microphone Jack provides connection for a standard compatible microphone.
Output Circuits
• Specific Application Power Output, 35 mA @ 24 VDC.
• Main circuit provides a 24 Volt Battery Charger (up to 18 AH batteries) @ 800 mA maximum .
Master Command Bus
• Normal Operating Voltage: 24 VDC regulated, fil tered . Reverse Polarity Current 125 mA maximum.
• Control bus from the ACC-25/50 Series or other UL listed compatible audio products.
Notification Appliance Circuit
• One NAC Speaker Circuit Style Y or Style Z with each ACC-AAM25 amplif ier module.
• Four NAC Speaker Circuits Style Z or eight Style Y with ACC-ZSM.
Relays
• One Form-C Trouble Relay. TB1 Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.6 amps @ 30 VAC
(resistive).
• One Form-C AC Loss Relay. TB11 Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.6 amps 30 VAC
(resistive).
FC-MIM Microphone Interface Module
• Connector P7 provides a connection for the optional FC-MIM Microphone Interface Module which is used to
connect the FC-RM Remote Microphone Module to provide remote microphone paging capabilities (refer to
Remote Microphone Installation document #51247).
ACC-ZPM Zone Page Module
• Connector P3 provides a connection for the ACC-ZPM Zone Page Module which is used to annunciate and
control the selection of speaker circuits. Refer to Section 3.6.4 "ACC-ZPM Zone Page Module - Zone System
Serial Link" on page 36.
Local Speaker
• The removable local speaker P/N: FC-LPS can be mounted on the ACC-25/50DA main circuit board and connected to the FC-MGM module, to be used for reviewing the digital message without broadcasting over the
system speakers. The local speaker must be installed to take adva ntage of the playback feature. The FC-LPS
cannot be permanently installed and therefore must be removed after use.
18
ACC-25/50DA 52265:B 1/30/08
Components
1.5Components
Main Circuit Board
Audio Amplifier
FIGURE 1-4:Main Circuit Board
The Distributed Audio main circuit board contains
the system's CPU, tone generators, special application auxiliary 35 mA power output, DIP switches
for field programmable features, other primary
components and wiring interface components.
One amplifier module is supplied mounted to the
main circuit board along with one ACC-ZPM
Zone Page Module and one ACC-ZSM Zone
Splitter Module (refer to Figure 1-3 on page 14).
The main circuit board is delivered premounted in
the cabinet.
Audio Amplifier Module [ACC-AAM25]
A single Audio Amplifier Module is installed in the Distributed Audio Panel. The amplifier provides 25 watts of
power at 25 V
speaker power to 50 watts. An optional module, P/N: FC-XRM70, converts the 25 V
. A second optional ACC-AAM25 can be installed as a backup to the primary or to expand
RMS
output to 70.7 V
RMS
One fully supervised and power-limited speaker circuit is provided on the amplifier module. The circuit can be
wired for Style Y (Class B) or Style Z (Class A) operation.
LEDs are provided to indicate Amplifier Supervision (green indicates amplifier is functional) and Circuit Trouble
(yellow indicates field wiring fault or amplifier fault). The LEDs are only visible with the panel door open.
Cabinet
The cabinet is red with an attractive navy blue front overlay . The backbox measures 26.0" x 15.5" x 4.75" and
provides space for two batteries (up to 18 Amp Hours).
RMS
AC25DAMAST.CDR
.
FIGURE 1-5:Cabinet
ACC-2550DA.CDR
Batteries
The cabinet provides space for 18 Amp Hour batteries (charged by integral Power Supply/Battery Charger
module).
ACC-25/50DA 52265:B 1/30/08 19
Optional Modules
1.6 Optional Modules
ACC-AAM25 Audio Amplifier Module
An optional second identical audio amplifier can be plugged into connector P2 located in the lower center of the
main circuit board in the Distributed Audio Panel. This amplifier also provides 25 watts of power at 25 V
can therefore be used to expand system power to 50 watts (providing dual 25 watt speaker circuits) or it can be
used as a backup amplifier. An option module can also be used to convert the 25 V
Note: For ease of access, all wiring should be connected to the terminals on the main circuit board terminal blocks
prior to installing the secondary Audio Amplifier Module.
output to 70.7 V
RMS
RMS
RMS
and
.
FC-XRM70 Transformer Module 70.7 V
RMS
This optional module plugs into connector P1 of the Audio Amplifier Module and provides conversion from
25 V
to 70.7 V
RMS
at full rated 25 watts output power.
RMS
FC-MGM Message Generator Module
This optional module provides custom message recording capabilities and system audio backu p. The cust om
message may be recorded from an alternate audio source connected to the audio jack on the FC-MGM. In
addition, built-in tone generators, which are located on the main circuit board, provide tones before and after the
message as well as backup on message failure. The FACP can automatically control the ACC-25/50DA via
CMD2-CMD5 to generate voice messages over its local speaker circuits.
Note: The ACC-25/50DAZS uses the FC-MGM for backup purposes if the message from the ACC-25/50ZS is
lost or interrupted.
FC-LPS Local Playback Speaker
This optional speaker module is mounted on the Distributed Audio Panel main circuit board and connects to the
optional FC-MGM module. This unit allows reviewing of the digital messages locally without broadcasting over
the system speakers. The optional module must be installed in order to take advantage of the Playback feature. It
may be temporarily used to test recorded messages. A mounting kit is included for this purpose. The FC-LPS
cannot be permanently mounted in the enclosure and must be removed after use.
FC-RM Remote Microphone Module
The optional microphone module FC-RM, provides general paging capabilities through the remote microphone
from the ACC-25/50DA. Announcements can be broadcast over the speaker circuits by pressing the Remote
Microphone keyswitch. The FC-MIM Microphone Interface Module must be installed in the ACC-25/50DA for
connection to the FC-RM (refer to the FC-RM Product Installation Document #51247 for installation information).
Note: All-Call Paging operations initiated from the ACC-25/50 Series main panel will override the remote
microphone.
The ACC-25/50DAZS panel does not support the FC-RM. All remote microphone connections are
made on the ACC-25/50ZS main panel.
20
ACC-25/50DA 52265:B 1/30/08
Getting Started
1.7Getting Started
This section describes the basic guidelines for setting up the ACC-25/50DA Series, assuming that the speaker and
FACP cabling has been installed.
1.7.1 ACC-25/50 With ACC-25/50DA(s), System Requiring Greater Than 50 Watts of Audio Power
• Connect the Audio Riser and Master Command Bus (for All-Call) cabling between the ACC-25/50 and
ACC-25/50DA panels. Refer to Section 5, 'Application Examples' on page 49.
• Install backboxes and circuit boards as described in Section 3, 'Installation' on page 28.
• Configure the ACC-25/50 for Single Zone operation using DIP switch S3 switches 1, 2 and 3 on the
ACC-MCB motherboard. Refer to Section 2, ‘Field Programming’ in the ACC-25/50(ZS) Manual. The
ACC-25/50DA DIP switches can be left at the default settings.
• If the optional message generator is installed, record any new voice messages as described in Section 4,
'Operating Instructions' on page 43.
1.7.2 ACC-25/50ZS With ACC-25/50DAZS, System Requiring Greater Than 50 Watts of Audio
Power
• Connect the Audio Riser and EIA-485 cabling between the ACC-25/50ZS and ACC-25/50DAZS panels.
Refer to Section 5, 'Application Examples' on page 49.
• Install backboxes and circuit boards as described in Section 3, 'Installation' on page 28.
• Configure the ACC-ZPMK on the ACC-25/50ZS with the number of ACC-25/50DAZS panels connected on
the Zone System serial link.
• Configure the address wheel located on the ACC-ZPM in the ACC-25/50DAZS panel.
• If the optional message generator is installed, record any new voice messages as described in Section 4,
'Operating Instructions' on page 43.
ACC-25/50DA 52265:B 1/30/08 21
Field Programming
CHAPTER 2Field Pr ogramming
The ACC-25/50DA can be field programmed using option DIP switches S1 and S2 located in the upper right side of
the mother board. It is recommended that tone selection and background music options be reviewed and approved by
the local AHJ. Programming DIP switches are also located on the ACC-ZPM Zone Page Module. DIP switches are
also located on the optional Message Generator Module (FC-MGM). Refer to the following illustrations for details
on DIP switch placement in the ON and OFF positions.
CAUTION: In order to minimize risk of damage to any circuits, do not use conductive tools when configuring DIP
!
switches.
FIGURE 2-1:Field Programming DIP Switches
S3 shown in Charger
Enabled position
FIGURE 2-2:Field Programming DIP Switch for ACC-ZPM
Distributed Audio Panel Mother Board
Switches 1 through 7
shown in OFF position
AC25DAZSSWTC.CDR
Switch 8 shown
in ON position
AC25DASWTC.CDR
22
ACC-ZPM
Switches 1 through 7
shown in OFF position
EIA-485 Addressing Switches
ACC-25/50DA 52265:B 1/30/08
Switch 8 shown in
ON position
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.