Fire-Lite 411UDAC User Manual

Fire Alarm Communicator
411UDAC
Manual
Document 51073 9/20/2013 Rev:
P/N 51073:E ECN 13-786
E
2 411UDAC Manual — P/N 51073:E 9/20/2013
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity . However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi­oelectriques depassant les limites applicables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, ECLIPSE®, Filtrex®, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, Pinnacle®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2013. All rights reserved. Unauthorized use of this document is strictly prohibited.
411UDAC Manual — P/N 51073:E 9/20/2013 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 411UDAC Manual — P/N 51073:E 9/20/2013

Table of Contents

Section 1: Product Description .............................................................................................10
1.1: Product Features ..........................................................................................................................................10
1.2: Specifications...............................................................................................................................................12
1.3: Circuits.........................................................................................................................................................13
1.3.1: Channels/Inputs .................................................................................................................................13
1.3.2: Notification Appliance Circuit ..........................................................................................................13
1.3.3: Output Circuits ..................................................................................................................................13
1.3.4: Auxiliary Relays................................................................................................................................13
1.3.5: Earth Ground .....................................................................................................................................13
1.4: Controls and Indicators................................................................................................................................14
1.5: Components and Accessories ......................................................................................................................15
1.6: Digital Communicator Operation ................................................................................................................15
1.7: Panel Configuration .....................................................................................................................................16
1.8: Operational Modes.......................................................................................................................................16
1.8.1: Normal Mode.....................................................................................................................................16
1.8.2: Real Time Clock Mode......................................................................................................................16
1.8.3: Program Mode ...................................................................................................................................16
1.8.4: Troubleshoot Mode............................................................................................................................16
1.8.5: Default Mode.....................................................................................................................................16
1.9: Telephone Requirements and Warnings.......................................................................................................17
1.9.1: Telephone Circuitry - PH1 & PH2 ....................................................................................................17
1.9.2: Digital Alarm Communicator:...........................................................................................................17
1.9.3: Telephone Company Rights and Warnings .......................................................................................17
Section 2: Installation.............................................................................................................18
2.1: Mounting Options........................................................................................................................................18
2.2: Mounting......................................................................................................................................................18
2.3: Operating Power ..........................................................................................................................................20
Primary Power Source (AC) and Earth Ground Connections ..............................................................20
Secondary Power Source (batteries).....................................................................................................21
2.4: Input Channels .............................................................................................................................................22
2.5: Output Circuits.............................................................................................................................................25
Notification Appliance Circuit .............................................................................................................25
Relay Programming..............................................................................................................................26
2.6: Telephone Circuits .......................................................................................................................................27
2.7: Optional Programmer ..................................................................................................................................28
2.8: UL Power-limited Wiring Requirements.....................................................................................................29
Section 3: Modes of Operation.............................................................................................. 30
3.1: Normal Mode...............................................................................................................................................30
3.1.1: Programmer Key Functions...............................................................................................................31
MODE KEY .........................................................................................................................................31
LAMP TEST KEY ...............................................................................................................................31
1st EVENT KEY ..................................................................................................................................32
DOWN ARROW..................................................................................................................................32
UP ARROW .........................................................................................................................................32
ENTER/STORE ...................................................................................................................................32
3.1.2: Programmer Display..........................................................................................................................32
3.2: Password Creation and Entry.......................................................................................................................32
3.3: Real Time Clock Mode................................................................................................................................33
3.4: Program Mode .............................................................................................................................................34
3.4.1: DACT Programming .........................................................................................................................36
Primary Central Station Phone Number (00 - 19)................................................................................36
Primary Central Station Number Communication Format (20) ...........................................................36
Event Codes - Setting Entries...............................................................................................................37
411UDAC Manual — P/N 51073:E 9/20/2013 5
Table of Contents
Ademco Contact ID Format Primary Central Station Event Codes .....................................................37
4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes...................................38
All 3+1, 4+1 and 4+2 Expanded Formats Primary Central Station Event Codes ................................39
Primary Central Station Number Account Code (21 - 24) ...................................................................40
Primary Central Station Number 24 Hour Test Time (25 - 28)............................................................40
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (29) ..........................................40
Secondary Central Station Phone Number (30 - 49) ............................................................................40
Secondary Central Station Number Communication Format (50) .......................................................41
Ademco Contact ID Format Secondary Central Station Event Codes .................................................42
4+2 Standard and 4+2 Express Formats Secondary Central Station Event Codes...............................43
All 3+1, 4+1 and 4+2 Expanded Formats Secondary Central Station Event Codes ............................44
Secondary Central Station Number Account Code (51 - 54) ...............................................................45
Secondary Central Station Number 24 Hour Test Time (55 - 58)........................................................45
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (59) ......................................45
AC Loss Reporting Delay (60).............................................................................................................45
Backup Reporting (61) .........................................................................................................................45
Reserved for Future Use (62) ...............................................................................................................45
DACT Trouble Reminder (63) .............................................................................................................45
Operational Mode Selection (64)..........................................................................................................45
Input Channel 1 Function Selection (65)..............................................................................................46
Input Channel 2 Function Selection (66) Input Channel 3 Function Selection (67) Input Channel 4 Function Selection (68)
Input Channel 1 Delay Timer (69 - 71) ................................................................................................46
Input Channel 2 Delay Timer (72 - 74)
Input Channel 3 Delay Timer (75 - 77) ................................................................................................47
Input Channel 4 Delay Timer (78 - 80)
1
............................................................................................46
1
............................................................................................46
1
............................................................................................46
2
...............................................................................................46
1
...............................................................................................47
Touchtone/Rotary Select for Primary Phone (81) ................................................................................47
Make/Break Ratio for Primary Phone (82)...........................................................................................47
Touchtone/Rotary Select for Secondary Phone (83) ............................................................................47
Make/Break Ratio for Secondary Phone (84).......................................................................................47
Output Relay #1 Enable (85) ................................................................................................................47
Output Relay #1 Function Selections (86)............................................................................................47
Output Relay #2 Enable (87) ................................................................................................................47
Output Relay #2 Function Selections (88)............................................................................................47
Reserved for Future Use (89) ...............................................................................................................48
Panel Unlock (90).................................................................................................................................48
Alarm Verification Enable (91)............................................................................................................48
Silence Inhibit Notification Appliance Circuit (92) .............................................................................48
Autosilence Notification Appliance Circuit (93)..................................................................................48
Restoral Method (94)............................................................................................................................49
Coding, Notification Appliance Circuit (95)........................................................................................50
Trouble Call Limit - Dialer Runaway Prevention (96).........................................................................50
Panel Identification Number (97 - 100)................................................................................................50
Service Terminal 1 Phone Number (101 - 120)....................................................................................51
Ring Count on Primary Phone Line (121 - 122)...................................................................................51
FAX/Answer Machine, Primary Phone Line (123)..............................................................................51
Service Terminal 2 Phone Number (124 - 143)....................................................................................51
Upload/Download Reports Sent to Secondary Central Station Phone #, Backup or Always (144).....51
Programming Event Code Settings (145 - 312)....................................................................................51
3.5: Default Mode ...............................................................................................................................................51
3.6: Troubleshoot Mode......................................................................................................................................52
Channel/Inputs......................................................................................................................................52
AC Line ................................................................................................................................................52
Notification Appliance Circuit .............................................................................................................52
Telephone Line Testing ........................................................................................................................53
6 411UDAC Manual — P/N 51073:E 9/20/2013
Table of Contents
Section 4: Central Station Communications........................................................................ 54
4.1: Transmittal Priorities ...................................................................................................................................57
4.2: Ademco Contact ID Format Event Code Description .................................................................................57
Section 5: Remote Site Upload/Download............................................................................60
5.1: General.........................................................................................................................................................60
5.1.1: Security Features ...............................................................................................................................61
Secret Code Verification ......................................................................................................................61
Panel Unlock ........................................................................................................................................61
Time-out at 411UDAC.........................................................................................................................61
Callback to Service Terminal ...............................................................................................................62
Error Checking .....................................................................................................................................62
Central Station Acknowledge...............................................................................................................62
Data Protection/Integrity ......................................................................................................................62
5.2: Downloading to the Communicator.............................................................................................................62
5.3: Uploading From the Communicator ............................................................................................................62
5.4: Simultaneous Data Transfers.......................................................................................................................63
Section 6: Battery Calculations............................................................................................. 64
6.1: 411UDAC Power Supply.............................................................................................................................65
Appendix A: Programming Sheets........................................................................................66
A.1: Digital Communicator Options Program Sheets ........................................................................................66
A.2: Digital Communicator Options Program Sheet (Factory Defaults)............................................................68
Appendix B: Event Codes/Transmission Format Programming Sheets ........................... 70
B.1: 4+2 Standard & 4+2 Express Formats Primary Central Station .................................................................70
B.2: 4+2 Standard & 4+2 Express Formats Secondary B.3: 4+2 Standard & 4+2 Express Formats Primary B.4: 4+2 Standard & 4+2 Express Formats Secondary B.5: All 3+1, All 4+1 and 4+2 Expanded Formats for Primary B.6: All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary B.7: All 3+1, All 4+1 and 4+2 Expanded Formats for Primary B.8: All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary B.9: Ademco Contact ID Format Primary B.10: Ademco Contact ID Format Secondary B.11: Ademco Contact ID Format Primary B.12: Ademco Contact ID Format Secondary
Central Station.................................................................................73
Central Station...........................................................................73
Central Station (Factory Defaults).................................................74
Central Station (Factory Defaults).............................................74
Central Station .............................................................70
Central Station .................................................................71
Central Station .............................................................71
Central Station ................................................72
Central Station ............................................72
Central Station (Factory Defaults)..................72
Central Station (Factory Defaults).............72
Appendix C: Ademco Contact ID Format Event Code Description.................................... 75
Appendix D: Events and Default Event Codes.....................................................................79
Appendix E: Operational Modes............................................................................................80
Index......................................................................................................................................... 81
411UDAC Manual — P/N 51073:E 9/20/2013 7
This digital communicator/transmitter has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories
• NFPA National Fire Protection Association
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
Central Station Signaling Systems Protected Premises Unit (Automatic, Manual and Waterflow)
Proprietary Fire Alarm Systems (Protected Premises Unit)
Remote Station Fire Alarm Systems
Automatic Fire Detectors
Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems
Inspection, Testing and Maintenance for Fire Alarm Systems
Underwriters Laboratories Documents:
UL 217 Smoke Detectors, Single and Multiple Station
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1635 Digital Alarm Communicator System Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with prod­ucts not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
8 411UDAC Manual — P/N 51073:E 9/20/2013
CAUTION!
GND FAULT
411UDAC-PCB Rev
Relay 2
(nonsupervised)
Common NC Contact NO Contact
Relay 1
(nonsupervised)
Common NC Contact NO Contact
NAC B+ NAC B­+12 VDC Resettable
- Resettable (common) Zone 1 B+ Zone 1 B­Zone 2 B+ Zone 2 B­Zone 3 B+ Zone 3 A+ Zone 3 A­Zone 3 B­Zone 4 B+ Zone 4 B-
Phone Line 1 Phone Line 2
PRO-411 DACT Programmer
Battery Connector (supervised, nonpower-limited)
AC Power Connector*
(supervised, nonpower-limited)
HOT NEU
EARTH
411udab2.wmf
411anac.wmf
411arel.wmf
- +
HIGH VOLTAGE
CAUTION!
Transformer Connection
All Circuits on TB2 and TB4 are
supervised and power-limited
hinged cover must be
closed after wiring
411UDAC Board Revision Level
!
411UDAC Manual — P/N 51073:E 9/20/2013 9
CAUTION: AC POWER TERMINAL LAYOUT CHANGE
USE CAUTION WHEN WIRING AC POWER TO THE 411UDAC AS TERMINAL LAYOUT HAS CHANGED ON TB3!!

Section 1: Product Description

Figure 1.1 411UDAC Digital
Communicator
411udacv.wmf
The 411UDAC is a fire alarm communicator with four input/channels and dual telephone lines. The four inputs use conventional input devices. The 411UDAC accepts waterflow devices, four­wire smoke detectors, pull stations and other normally-open contact devices. The unit also super­vises AC voltage, telephone line input voltage/current, battery level and battery charger operation.
Outputs include one supplementary NAC (Notification Appliance Circuit), two programmable Form-C relays and 12 VDC resettable special application power. The 411UDAC interfaces with the public switched telephone network and is compatible with most central station receivers. A total of fifteen popular communications formats are supported, including the industry standard Ademco Contact ID. The communicator also contains a unique DACT option that eliminates
'dialer runaway'. It restricts the transmission of any intermittent nuisance fault to 10 attempts in a 24 hour period.
Accessories include the Fire-Watch 411 Series DACT Programmer (Model PRO-411) as well as the PK-411UD Windows
®
-based remote site programming software. The 411UDAC is supplied with
a compact metal cabinet.
The digital communicator can be programmed or interrogated off-site via the public switched tele­phone network. Any IBM compatible personal computer with Windows 1200 baud Hayes
®
compatible modem and Upload/Download software P/N PK-411UD, may serve
®
XP or greater, with a
as a service terminal.

1.1 Product Features

Four input/channels - three fixed Style B (Class B) and one Style A (Class A) or Style B (Class B)
Programmable input channels
4-wire smoke (Inputs 1 & 3 only)
pull station
normally-open contact
host panel trouble (Slave Mode)
supervisory
supervisory autoresettable
waterflow (silenceable)
waterflow (nonsilenceable)
One Style Y (Class B) NAC (supplementary application)
Dual telephone lines
Dual telephone line voltage detect
Alternating phone lines for 24 hour test messages
12 VDC operation
Alarm Verification
Signal Silence Inhibit
Autosilence
Trouble Reminder
Trouble Resound - troubles will resound the buzzer every 24 hours at midnight until the trouble is cleared
Optional TR-6 Series Trim Ring
20-digit central station and service terminal telephone numbers
NAC coding per ANSI S-3.41 (Temporal Coding)
10 411UDAC Manual — P/N 51073:E 9/20/2013
Product Features Product Description
Separate external keypad and display
provides means of programming 411UDAC in program mode
provides means of testing input/output circuits (including telephone connections) in
Troubleshoot Mode
Compact in size 14.5" (36.83 cm) high X 12.875" (32.7 cm) wide X 4.5" (11.43 cm) deep metal cabinet
Communicates vital status of monitored control panel (Slave Mode):
fire alarm
host control panel trouble
fire supervisory
AC (mains) power loss (programmable)
other
Communicates vital status of 411UDAC:
digital communicator troubles
telephone Line 1 and 2 voltage fault
Primary Central Station number communication fault
Secondary Central Station number communication fault
system off-normal (local Program Mode entered)
24 Hour normal test
24 Hour abnormal test (24 hour test message with previously reported alarm or trouble still
active)
Individual LEDs for:
AC Power
System Trouble
Input Active
Supervisory
Communication Fail
Battery Trouble
Earth Fault
Local piezo sounder with separate and distinct sounds for the various conditions
Acknowledge/System Silence switch - 1st press silences local piezo sounder, 2nd press silences NAC
Reset switch
Real time clock
Two Form-C relays, fully programmable to activate for the following conditions:
fire alarm total communication failurehost control panel trouble DACT trouble (factory default for relay)fire supervisory (latching)fire supervisory (autoresettable)
Optional PK-411UD Remote Upload/Download Kit
'Dialer runaway' feature
User selectable restoral methods
411UDAC Manual — P/N 51073:E 9/20/2013 11
Product Description Specifications

1.2 Specifications

AC Power - TB3
120 VAC, 60 Hz, 0.7 amps Wire size: minimum 14 AWG (2.00 mm Supervised, nonpower-limited
Battery (lead acid only) - J3
Maximum Charging Circuit: Float charge - 13.6V @ 3.15 amps Maximum Charger Capacity: 14 Amp Hour battery Supervised, nonpower-limited
Channels/Inputs - TB2 Terminals 1 through 10
Programmable Channels 1 through 4 Power-limited circuitry Fully supervised (monitored for opens, shorts and earth fault) Normal Operating Voltage: 12.0 VDC (ripple = 100 mV maximum) End-of-Line Resistor: 2.2K ohms, ½ watt (P/N 27070 UL listed) Operation for each channel:
Channel/Input 1, Style B (Class B) 4-wire smoke detector input and Channel/Input 3, Style B (Class B) 4-wire smoke detectors or waterflows or Style D (Class A) waterflow input:
Connecting 4-wire detectors on Channel/Input 3 requires NFPA Style B (Class B) only.
Alarm Current: 11 mA Short Circuit Current: 24 mA maximum Maximum Detector Current in Standby: 1.8 mA Maximum Loop Resistance: 30 ohms
Detector Loop Current is sufficient to ensure operation of a minimum of one alarmed detector per zone
Standby Current: 5.17 mA (including End-of-Line Resistor)
• Channel/Input 2 and Channel/Input 4 - Style B (Class B) contact closure input:
Short Circuit Current: 4.46 mA maximum Maximum Loop Resistance: 100 ohms Standby Current: 2.66 mA Refer to the Device Compatibility Document for listed compatible devices.
Notification Appliance Circuit - TB4 Terminals 1(+) & 2(-)
The 411UDAC Notification Appliance Circuit may only be used to supplement host panel NACs Style Y (Class B) power-limited and supervised circuit (monitored for opens, shorts, and earth fault) Maximum voltage drop in wiring: 2.0 VDC Operating voltage nominal 13.8 VDC Current for all external devices: 1.0 amp End-of-line resistor: 2.2K ohms, ½ watt (P/N 27070) Refer to the Device Compatibility Document for listed compatible devices
Two Form-C Relays - TB1 Terminals 1 through 6
2
) with 600V insulation
Operating voltage nominal 12 VDC Contact rating: 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive) Non-supervised
12 VDC Resettable Special Application Power - TB4 Terminals 3(+) and 4(-)
Operating voltage nominal 12 volts Maximum ripple voltage: 10 mV
RMS
Up to 200 mA is available for powering 4-wire smoke detectors Power-limited and supervised with a UL-listed power supervision relay
For power supply and battery calculations, refer to Section 6.
12 411UDAC Manual — P/N 51073:E 9/20/2013
Circuits Product Description

1.3 Circuits

The 411UDAC circuit board contains a MicroController Unit (MCU), dual modular phone line jacks, piezo sounder, and connectors for input, output and power wiring. A piezo silence switch and reset switch are provided on the membrane panel which plugs into connector J7 on the main circuit board.

1.3.1 Channels/Inputs

Four input channels are provided on the 411UDAC. The 411UDAC can be used to monitor a host FACP (Fire Alarm Control Panel) in Slave Mode or as a stand-alone FAC (Fire Alarm Communica­tor). Each input can be programmed to monitor the following conditions:
fire alarm activation
4-wire smoke (channels 1 & 3 only)
pull station
normally open contact device
waterflow
trouble activation
fire supervisory activation

1.3.2 Notification Appliance Circuit

One Style B NAC (Notification Appliance Circuit) requiring a 2.2K ohm End-of-Line resistor. This NAC can only be used to supplement host panel NACs.

1.3.3 Output Circuits

Modular jacks are used to interface the primary and secondary phone lines to the public telephone network. Phone lines are fully supervised at all times (if communication is enabled).
12 volt resettable special application power output (200 mA)
12 volt battery charger will charge up to 14 AH batteries

1.3.4 Auxiliary Relays

Two dry Form-C relays (P/N: 411RK), with contacts rated for 2.0 amps @ 30 VDC (resistive) or
0.5 amps @ 30 VAC (resistive), are installed on the main circuit board. Each relay is programma-
ble for:
Alarm
Fire supervisory - latching
Fire supervisory - autoresettable
Host panel trouble
DACT trouble
Total communications failure

1.3.5 Earth Ground

Connect a separate earth ground wire to ground stud in backbox for transient protection (refer to Figure 2.3 on page 21 for location of stud).
411UDAC Manual — P/N 51073:E 9/20/2013 13
Product Description Controls and Indicators
Figure 1.2 411UDAC Controls and Indicators
411udacdsp.wmf

1.4 Controls and Indicators

Front Panel Switch
Reset Switch - to reset 411UDAC circuits
Acknowledge/System Silence Switch
– press once to acknowledge alarm or trouble (silence local 411UDAC piezo sounder and
change all flashing LEDs to steady on)
– press a second time and hold for minimum of two seconds to perform a System Signal
Silence (silence Notification Appliance Circuit)
411UDAC Piezo Sounder
The 411UDAC piezo sounder is used to locally annunciate DACT alarms and troubles. DACT troubles include input channel open circuit, NAC fault, phone line 1 or 2 voltage fault, phone number 1 or 2 communication fault and total communication failure. Separate and distinct sounds are provided for the following conditions:
alarm - steady On
trouble - 1 second On and 1 second Off
supervisory - ½ second On and ½ second Off
Front Panel Indicator
AC Power - green LED
Input Active - red LED
Communication Fail - yellow LED
System Trouble - yellow LED
Supervisory - yellow LED
Battery Trouble - yellow LED
Circuit Board Indicator
Earth Fault - yellow LED (indicates zero impedance between panel and earth ground)
14 411UDAC Manual — P/N 51073:E 9/20/2013
Components and Accessories Product Description

1.5 Components and Accessories

Main Circuit Board
The main circuit board contains the system’s MCU (microcontroller unit), power supply, other pri­mary components and wiring interface connectors. The main circuit board is shipped in the same carton as the cabinet but is not mounted in the cabinet. The circuit board should be installed only after the cabinet is mounted to the wall and the area is clean and free of potential contaminants.
Cabinet
The cabinet is red and measures 14.5" (36.83 cm) high X 12.875" (32.7 cm) wide X 4.5" (11.43 cm) deep. It provides space for up to two 7 Amp Hour batteries which must be ordered separately. A supplied bezel must be installed in the door opening.
Trim Ring
An optional Trim Ring (P/N TR-6-R) is available for the backbox. The Trim Ring provides a fin­ished appearance for a semi-flush mounted panel.
Transformer Assembly
One transformer is shipped in the same carton as the cabinet and main circuit board but not mounted in the cabinet. The transformer should be installed before the cabinet is mounted to the wall.
Fire•Watch 411 Series DACT Programmer (Model PRO-411)
The PRO-411 is an optional DACT programmer which can be used to troubleshoot and program the 411UDAC, as well as access the various modes of operation. The PRO-411 must be ordered separately.
PK-411UD Upload/Download Software Kit
The optional PK-411UD Kit consists of the PK-411UD Upload/Download software on CD and the PK-411UD Program Manual. The PK-411UD enables a user to program the 411UDAC off site via the public switched telephone network using any personal computer with Windows and a 1200 baud Hayes
®
compatible modem.

1.6 Digital Communicator Operation

The 411UDAC has been designed to be compatible with a wide variety of fire alarm, nonfire and combination control panels (Slave Mode operation). Numerous formats are also available for com­munication to a central station. Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the Primary and Secondary phone lines. The digital communicator provides the following functions:
• Line Seizure- takes control phone lines, disconnecting any premise phones which may be
using the same lines
• Off/On-Hook - perform on and off-hook status to phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone®, programmable to
rotary
• Discern proper Central Station 'ACK' and 'Kiss-off' tone(s)
• Transmit data to the Central Station(s)
• Verify data has been accepted by the Central Station(s)
• Hang-up and release phone lines
• Communicate in a variety of formats (Table 4.1, “Format Selection Addresses (20 and 50)
Programming,” on page 55).
®
XP or greater
411UDAC Manual — P/N 51073:E 9/20/2013 15
Product Description Panel Configuration

1.7 Panel Configuration

The 411UDAC can be configured, through programming, for the following modes of operation:
• Stand-alone Mode With Communicator Enabled - the 411UDAC functions as a latching
digital alarm communicator in which all input circuit activations latch (except those programmed as autoresettable) and are restored only by pressing the local reset switch. The onboard communicator will attempt to transmit events to a Central Station
• Slave Mode With Communicator Enabled - the 411UDAC functions as a nonlatching slave
to a host control panel and the onboard digital alarm communicator will attempt to transmit events to a Central Station
• Slave Mode With Communicator Disabled - the 411UDAC functions only as a nonlatching
slave to a host control panel. The digital alarm communicator will not transmit to a Central Station

1.8 Operational Modes

1.8.1 Normal Mode

Normal Mode is the standard mode of operation in which the 411UDAC monitors the channel/input circuits as well as telephone line voltage and other internal circuits. In addition to locally annunci­ating system trouble, active channel/input and communication fail, the onboard communicator transmits system status information to UL listed central station receivers if programmed to do so. Transmitted data includes fire alarm, fire alarm trouble, supervisory alarm and AC loss informa­tion. Specific digital communicator troubles are also transmitted.

1.8.2 Real Time Clock Mode

Real Time Clock Mode allows the user to change the digital alarm communicator’s internal 24 hour clock. Connecting an external Programmer allows access to the various Modes of operation. While the 411UDAC is in Real Time Clock Mode, it does not monitor channel inputs. Use of this mode requires a valid password.

1.8.3 Program Mode

Program Mode is used to change the programmed functions of the 411UDAC. While the 411UDAC is in Program Mode, it does not monitor channel inputs. In addition, some program items will be locked, which will prevent editing while the communicator is active (dialing, trans­mitting, etc.). Use of this mode requires a valid password.

1.8.4 Troubleshoot Mode

Troubleshoot Mode may be used to sample and display status for all channel/input circuits, Notifi­cation Appliance Circuit, AC power, battery, charger and 12 volt resettable power. In addition, Troubleshoot Mode may be used for testing the telephone line interconnect wiring. Connection from the 411UDAC’s modular jacks, through the RJ31X jacks and into the telephone network may be easily checked. In this mode, the Programmer keypad acts similar to a telephone touchpad. While the 411UDAC is in Troubleshoot Mode, it does not monitor channel inputs.

1.8.5 Default Mode

Default Mode may be used to return all 411UDAC programming back to the factory default set­tings and to reset the Real-Time Clock to ‘00:01’ midnight. See “Default Mode” on page 51.
16 411UDAC Manual — P/N 51073:E 9/20/2013
Telephone Requirements and Warnings Product Description

1.9 Telephone Requirements and Warnings

1.9.1 Telephone Circuitry - PH1 & PH2

AC Ringer Equivalence Number (REN) = 0.4B
Mates with RJ31X Male Connector
Supervision Threshold: less than 5.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.

1.9.2 Digital Alarm Communicator:

Before connecting the 411UDAC to the public switched telephone network, the installation of two RJ31X jacks is necessary. The following information is provided if required by the local telephone company:
Manufacturer: Fire•Lite Alarms Inc./Notifier
One Fire-Lite Place
Northford, CT 06472
Product Model Number: 411UDAC
FCC Registration Number: 1W6AL04B411UDAC
AC Ringer Equivalence: 0.4B
FCC ID label is located on the inside cover.
Important! The DACT must not ments of UL 864 9th Edition.
be used to dial a phone number that is call-forwarded per require-

1.9.3 Telephone Company Rights and Warnings

The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this digital communicator. However, the telephone company is required to give advance notice of such changes or interruptions. If the digital communicator causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the digital communicator activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same tele­phone line.
The digital communicator must be connected to the public switched telephone network upstream of any private telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
411UDAC Manual — P/N 51073:E 9/20/2013 17

Section 2: Installation

CAUTION!
Transformer
flanges
Transformer mounting studs
411xfmrmn2t.wmf
Ground Stud
Figure 2.1 Transformer Mounting

2.1 Mounting Options

The cabinet may be either semi-flush or surface mounted. The door is removable during the instal­lation period by opening and lifting it off the hinges. The cabinet mounts using two key slots and two additional 0.25" diameter holes located in the backbox. The keyslots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabi­net approximately five feet above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the required conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

2.2 Mounting

Backbox Mounting
1. Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown in Figure 2.1.
2. Install two upper fasteners in the wall with the screw heads protruding.
3. Using the upper 'keyholes', temporarily mount the backbox over the two screws.
4. Mark the lower two holes, remove the backbox from the wall and drill the lower two holes in the wall.
5. Before mounting the backbox to the wall, install the supplied transformer in the backbox. Position the holes in the transformer flanges over the trans­former mounting studs. Refer to Figure 2.1.
6. Secure the transformer with the supplied nuts and attached washers.
18 411UDAC Manual — P/N 51073:E 9/20/2013
Mounting Installation
Figure 2.1 Cabinet Dimensions and Knockout Locations
411udaccab.wmf
Ground Stud
Top
Right side
Mounting Keyholes
10.0” (25.4cm)
Main Circuit Board
Mounting Studs
Transformer
Mounting Studs
Left side
Mounting Holes
Bottom
7. Mount the backbox to the keyhole mounting bolts, install and tighten the remaining fastener.
Main Circuit Board Mounting
1. When the location is clean and free of construction dust or other contaminants, install the main PC board by installing the four supplied standoffs on the four main circuit board mounting studs located in the backbox. Refer to Figure 2.1 for locations.
2. Position the main circuit board’s four corner mounting holes over the four standoffs just installed. Be certain to observe the proper ESD (Electro Static Discharge) precautions to
prevent damage to the static sensitive circuits. This includes, but is not limited to, use of a wrist strap.
3. Secure the main circuit board to the standoffs with the four supplied screws and attached washers.
4. Plug the transformer connector into the main circuit board connector J4. The connector is keyed and can only be plugged-in one way. Refer to Figure 2.3 on page 21 and Figure 2.11 on page 29 for transformer connector location and AC power connections.
411UDAC Manual — P/N 51073:E 9/20/2013 19
Installation Operating Power
!
Figure 2.2 411UDAC Backbox
411accab2.wmf
Top
Door = 13.047” (33.14cm) Backbox = 12.875” (32.7cm)
Door = 14.760” (37.49cm) Backbox = 14.5” (36.83cm)
Depth=4.533”
(11.51cm)
Bottom
Right Side
Left Side
5. When wiring is completed, re-install the door.

2.3 Operating Power

CAUTION: DISCONNECT POWER BEFORE SERVICING
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THE 411UDAC. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING THIS UNIT. THE COMMUNICATOR AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING MODULES OR CABLES WITH POWER APPLIED.

Primary Power Source (AC) and Earth Ground Connections

AC power connections are made inside the 411UDAC cabinet. The primary power source is 120 VAC, 60 Hz, 0.7 amps. Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB3 of the main circuit board. As per the National Electric Code, use 14 AWG (2.00 mm nected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices.
2
) or heavier gauge wire with 600V insulation. No other equipment may be con-
20 411UDAC Manual — P/N 51073:E 9/20/2013
Operating Power Installation
CAUTION!
HIGH VOLTAGE
CAUTION!
GND FAULT
Figure 2.3 Operating Power Connections
Connect Earth Ground Wire to earth ground stud
Earth
Red
Black
12 VDC Battery
Neutral
Hot
411udacinbox.wmf
A separate earth ground connection must be made to ensure proper panel operation and lightning and transient protection. Remove the two keps nuts from the grounding stud in the backbox. Con­nect the incoming earth ground wire to supplied cable #71073 with a wire nut. Position the ring ter­minal end over the grounding stud. Secure with one of the keps nuts. Place the ring terminal from the other supplied ground cable #71073 over the ground stud and secure with the second keps nut. Wire the ground cable to the bottom position of TB3. Refer to the figure below for location of the stud. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be applied to the panel before installing the battery interconnect cable.

Secondary Power Source (batteries)

Observe polarity while connecting the battery. When installing one 12 volt battery for up to 12 Amp Hour applications, connect the supplied battery cable (P/N 75516) by sliding the connector attached to the long red wire onto the positive (+) battery terminal and the connector attached to the long black wire onto the negative (-) battery terminal. Tie-wrap or tape the two unused short wires to the long wires.
When installing two 12 volt, 7 Amp Hour batteries (in parallel) for up to 14 Amp Hour applica­tions, follow the same procedure as described for one battery except connect the unused short wires to the second battery. Slide the connector attached to the short red wire onto the positive (+) termi­nal of the second battery and the connector attached to the short black wire onto the negative (-) battery terminal of the second battery.
411UDAC Manual — P/N 51073:E 9/20/2013 21
Installation Input Channels
!
Figure 2.4 Battery Cable Connections
Two 12 Volt Batteries - Up to 14 Amp Hour Applications
One 12 Volt Battery - Up to 12 Amp Hour Applications
Black Wire
Red Wire
Negative (-) Terminal
Positive (+) Terminal
Unused wire - tie-wrap or tape to long wires
Unused wire - tie-wrap or tape to long wires
Connect to J3 on 411UDAC main circuit board
Connect to J3 on 411UDAC main circuit board
Black Wire
Red Wire
Negative (-) Terminal
Negative (-) Terminal
Positive (+) Terminals
411batt2.wmf
411batt.wmf
When the panel is ready to have power applied, connect the battery cable plug to connector J3 on the 411UDAC main circuit board. The battery charger is capable of recharging sealed lead acid type batteries. Refer to the battery calculations table to determine the correct battery rating.
CAUTION: BATTERY CONTAINS SULFURIC ACID
THE BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES, AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.

2.4 Input Channels

The 411UDAC has four channel inputs. Channel/input field wiring is supervised for opens (trou­ble), shorts (alarm) and ground faults (zero ohms impedance between panel and earth ground) by the 411UDAC. All conditions are visually and audibly annunciated and, if programmed, communi­cated to a Central Station.
Each channel is a Style B (Class B) Initiating Device Circuit with the exception of channel/input 3 which can be configured for Style B or Style D (Class A). All inputs can be connected to normally­open contact type devices. In addition, inputs 1 and 3 can be connected to conventional 4-wire smoke detectors. Figure 2.5, “Wiring Initiating Device Circuits” on page 23 for information on wiring Style B and Style D circuits.
22 411UDAC Manual — P/N 51073:E 9/20/2013
Input Channels Installation
UL-listed power supervision relay*
Manual Pull Stations (Class A)
Manual Pull Stations (Class B)
Waterflow Devices (Class B)
411UDAC Main Circuit Board
Zone 1/Channel 1
Zone 2/Channel 2
Zone 3/Channel 3
Zone 4/Channel 4
Figure 2.5 Wiring Initiating Device Circuits
411udain3.wmf
4-Wire Smoke Detector
*Refer to the Device Compatibility Document for a list of compatible relays.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 K, ½ watt resistor P/N:71252
The channel/inputs may be programmed as shown below:
• 4-wire smoke detector (inputs 1 & 3 only) • Supervisory
• Pull station • Supervisory autoresettable
• Normally-open contact device • Waterflow silenceable
• Host panel trouble • Waterflow nonsilenceable
A maximum of five waterflow devices may be used on any circuit programmed as a waterflow zone per NFPA 72.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull sta­tions, etc.) on any zone. This is not recommended, however, since specific and detailed reports will not be possible (particularly critical when using Contact ID format). For example, the report of general fire alarm versus pull station fire alarm or smoke detector fire alarm could not be distin­guished.
The factory default programming for each channel is as follows:
Channel 1 - fire alarm (4-wire smoke)
Channel 2 - pull station
Channel 3 - fire alarm (4-wire smoke)
Channel 4 - pull station
The following illustration shows Channel 1 connected to 4-wire smoke detectors, and UL-listed power supervision relay; Channel 2 connected to manual pull stations; Channel 3 connected to manual pull stations; and Channel 4 connected to waterflow devices. In this example, the factory default programming for Channel 4 must be changed from pull station to waterflow device.
411UDAC Manual — P/N 51073:E 9/20/2013 23
Installation Input Channels
CAUTION!
HIGH VOLTAGE
COMM. FAIL
BATT FAULT
SYSTEM
TROUBLE
SUPV.
AC PWR
ACTIVE
GND FAULT
B+ A+ B- A- A B Slc Slc Slc Slc Shield
NO NC C NO NC C NC NO C
411UDAC
Note: The addressable monitor module input, which is being used to monitor the 411UDAC Relay Output programmed for DACT Trouble must be programmed as 'DACT Trouble' at the FACP. The 411UDAC must be programmed as a Slave Communicator (programming address 64 set to ‘2’)
Addressable FACP (must be UL-listed for Central Station Service and Remote Signaling Service)
411UDAC Relay 2 Output (DACT Trouble)
Channel 2/Zone 2
Channel 1/Zone 1
Channel 3/Zone 3
2.2K ELR Channel 4
2.2K ELR
Monitor Circuit Input
SLC Loop
Trouble Relay
Alarm Relay
Supervisory Relay
UL listed
2.2K ELRs P/N 27070
Program the 411UDAC as follows: Channel 1 - Normally Open Contact Device (alarm) Channel 2 - Host Panel Trouble Channel 3 - Supervisory
9200udlsc411a.wmf
Monitor Module*
ELR supplied with Monitor Module
*If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion charts for legacy and newer versions of the modules.
Figure 2.6 Typical Addressable FACP Connection to 411UDAC
24 411UDAC Manual — P/N 51073:E 9/20/2013
Output Circuits Installation
Figure 2.7 Notification Appliance Circuit Connections
Style Y (Class B) Notification Appliance Circuit
(supervised and power-limited).
2.2K ohms, ½ watt P/N 27070
Polarized Bell
Polarized Horn
Polarized Horn
Dummy Load NAC circuit with 2.2K ohm, ½ watt End-of-Line resistor if not being used.
Note: Notification Appliance Circuit polarity shown in alarm state
411anac.wmf
NAC +12V Power

2.5 Output Circuits

Notification Appliance Circuit

The 411UDAC provides one Style Y (Class B) NAC (Notification Appliance Circuit). The NAC is supervised and power-limited and is capable of 1.0 amp of current. Refer to the Device Compati-
bility Document for a listing of compatible notification appliances.
Notes:
1. The 411UDAC can only be used to supplement host panel NACs.
2. Do not connect strobes to the 411UDAC Notification Appliance Circuit.
The NAC may be programmed as follows:
Silenceable
Nonsilenceable (waterflow)
Silence Inhibited (one minute)
Autosilence (5 to 30 minutes)
411UDAC Manual — P/N 51073:E 9/20/2013 25
Installation Output Circuits
RELAY 1 RELAY 2
TB1
NO NONC NCCC
Figure 2.8 Programmable Relay
Note: Relay connections may be power-limited or nonpower-limited. However, connecting one type next to the other type is not allowed. Both circuits must be either power-limited or nonpower-limited.
Relays automatically change to energized
condition when programmed for Trouble.
411arele.wmf
Relay 1 - Shown Programmed for Alarm, Supervisory, or any other function except DACT Trouble and Host Panel Trouble (relay contacts shown in de-energized condition with power applied to 411UDAC)
Relay 2 - Shown Programmed for DACT Trouble or Host Panel Trouble (relay contacts shown in energized condition with power applied to 411UDAC)

Relay Programming

The relays are programmable for activation on fire alarm, host panel trouble, fire supervisory, total communication failure and DACT. Refer to “DACT Programming” on page 36. Addresses ‘85 ­88’ are used for programming relay functions and enable.
26 411UDAC Manual — P/N 51073:E 9/20/2013
Loading...
+ 58 hidden pages