Fire-Lite 411 User Manual

Digital Alarm
Communicator/Transmitter
411
Document #50921 11/07/2005 Rev.
P/N 50921:D ECN 05-465
© 2005
D
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warn­ing devices, and a fire alarm control panel with remote notifi­cation capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat de­tectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede­termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, com­munications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medi­cation. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A main­tenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized profes­sional fire alarm installers only. Adequate written records of all inspections should be kept.
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for indoor dry opera­tion at 0-49° C/32-120° F RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the elec­tronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recom­mended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications sec­tion for maximum allowable I.R. drop from the specified de­vice voltage.
and at a relative humidity of 93 ±2%
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is com­pletely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or out-
side aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the
Technical Services Department if any problems are antici­pated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can ra-
diate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause in­terference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environ­ment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Notes
4 411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Table of Contents
CHAPTER 1: Product Description ...........................................................................................................................................8
1.1: Product Features..........................................................................................................................................8
FIGURE 1-1: 411 Digital Communicator............................................................................................8
1.2: Specifications ..............................................................................................................................................9
1.3: Circuits ........................................................................................................................................................9
1.3.1: Power Requirements .........................................................................................................................9
1.3.2: Channels/Inputs.................................................................................................................................10
1.3.3: Primary and Secondary Phone Lines ................................................................................................10
1.3.4: Earth Ground.....................................................................................................................................10
1.4: Controls and Indicator.................................................................................................................................10
FIGURE 1-2: 411 Indicator .................................................................................................................10
1.5: Digital Communicator Operation................................................................................................................11
1.6: Telephone Requirements and Warnings ......................................................................................................11
1.6.1: Telephone Circuitry - PH1 & PH2....................................................................................................11
1.6.2: Digital Communicator: .....................................................................................................................11
1.6.3: Telephone Company Rights and Warnings:......................................................................................12
1.6.4: For Canadian Applications................................................................................................................12
1.7: Operational Modes ......................................................................................................................................13
1.7.1: Normal Mode ....................................................................................................................................13
1.7.2: Real Time Clock Mode.....................................................................................................................13
1.7.3: Program Mode...................................................................................................................................13
1.7.4: Troubleshoot Mode...........................................................................................................................13
1.7.5: Default Mode ....................................................................................................................................13
CHAPTER 2: Installation ..........................................................................................................................................................14
2.1: Mounting Options .......................................................................................................................................14
FIGURE 2-1: 411 Enclosure................................................................................................................14
2.2: Operating Power..........................................................................................................................................14
2.3: Input Channels.............................................................................................................................................14
FIGURE 2-2: Typical FACP Connection to 411.................................................................................15
FIGURE 2-3: Style B Channel Connections........................................................................................16
2.4: Telephone Circuits.......................................................................................................................................17
TABLE 2-1: Wiring Phone Jacks ........................................................................................................17
2.5: Optional Programmer..................................................................................................................................18
FIGURE 2-4: Programmer Connection to 411 ....................................................................................18
2.6: UL Power-limited Wiring Requirements ....................................................................................................19
CHAPTER 3: Modes of Operation............................................................................................................................................20
3.1: Normal Mode ..............................................................................................................................................20
3.1.1: Programmer Key Functions ..............................................................................................................21
FIGURE 3-1: Programmer Keypad .....................................................................................................21
3.1.2: Programmer Display .........................................................................................................................22
3.2: Real Time Clock Mode ...............................................................................................................................22
3.3: Program Mode.............................................................................................................................................24
3.3.1: DACT Programming.........................................................................................................................25
TABLE 3-1: Ademco Contact ID Format - Primary ...........................................................................27
TABLE 3-2: 4+2 Standard and 4+2 Express Formats - Primary.........................................................27
TABLE 3-3: All 3+1, 4+1 and 4+2 Expanded Formats - Primary ......................................................28
TABLE 3-4: Ademco Contact ID Format - Secondary .......................................................................30
TABLE 3-5: 4+2 Standard and 4+2 Express Formats - Secondary.....................................................31
TABLE 3-6: All 3+1, 4+1 and 4+2 Expanded Formats - Secondary ..................................................32
3.4: Default Mode...............................................................................................................................................36
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 5
Table of Contents
3.5: Troubleshoot Mode......................................................................................................................................36
FIGURE 3-2: Handset/Speaker Connection ........................................................................................36
CHAPTER 4: Central Station Communications......................................................................................................................37
TABLE 4-1: Format Selection Addresses ( 20 and 50) Programming ................................................38
TABLE 4-2: Format Selection Address Explanation...........................................................................39
4.0.1: Transmittal Priorities.........................................................................................................................40
4.0.2: Ademco Contact ID Format Event Code Description.......................................................................41
TABLE 4-3: Compatible UL Listed Receivers....................................................................................42
Appendix A: Programming Sheets .......................................................................................................................43
A.1: Digital Communicator Options Program Sheets .......................................................................................43
A.2: Digital Communicator Options Program Sheet (Factory Defaults) ..........................................................45
Appendix B: Event Codes/Transmission Format Programming Sheets ..........................................................47
B.1: 4+2 Standard & 4+2 Express Formats Primary B.2: 4+2 Standard & 4+2 Express Formats Secondary B.3: 4+2 Standard & 4+2 Express Formats Primary B.4: 4+2 Standard & 4+2 Express Formats Secondary B.5: All 3+1, All 4+1 and 4+2 Expanded Formats for Primary B.6: All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary B.7: All 3+1, All 4+1 and 4+2 Expanded Formats for Primary B.8: All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary B.9: Ademco Contact ID Format Primary
Central Station ................................................................................50
B.10: Ademco Contact ID Format Secondary B.11: Ademco Contact ID Format Primary
Central Station (Factory Defaults) ...............................................51
B.12: Ademco Contact ID Format Secondary
Central Station ................................................................47
Central Station ............................................................47
Central Station ................................................................48
Central Station ............................................................48
Central Station ...............................................49
Central Station ...........................................49
Central Station (Factory Defaults) ................49
Central Station (Factory Defaults) ...........49
Central Station ..........................................................................50
Central Station (Factory Defaults) ...........................................51
Appendix C: Ademco Contact ID Format Event Code Description .................................................................52
Appendix D: Wire Requirements .........................................................................................................................56
TABLE 4-4: Wire Specifications.........................................................................................................56
Appendix E: Operational Modes ..........................................................................................................................57
TABLE 4-5: Operational Modes..........................................................................................................57
6
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
This digital communicator has been designed to comply with standards set forth by the following regulatory agen­cies:
• Underwriters Laboratories Standard
• NFPA 72 National Fire Alarm Code
• CAN/ULC - S527-M87 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards This digital communicator complies with the NFPA 72 National Fire Alarm Code for:
Central Station Signaling Systems Protected Premises Unit (Automatic, Manual and Waterflow) Local Fire Alarm Systems (Automatic, Manual, Waterflow and Sprinkler Supervisory) Proprietary Fire Alarm Systems (Protected Premises Unit) Remote Station Fire Alarm Systems Automatic Fire Detectors Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems Inspection, Testing and Maintenance for Fire Alarm Systems
Underwriters Laboratories Documents:
UL 217 Smoke Detectors, Single and Multiple Station UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1076 Proprietary Burglar Alarm Units and Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1635 Digital Alarm Communicator System Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired CAN/ULC - S524-M91 Standard for Installation of Fire Alarm Systems
Other:
NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 7
Product Description
CHAPTER 1 Product Description
The 411 is a three input/channel, dual line, digital alarm communicator transmitter which can be used as a slave com­municator with UL listed fire and nonfire control panels. The three inputs are compatible with normally open relay contacts, require End-Of-Line (EOL) resistors, are supervised and are fully programmable. The 411 interfaces with the public switched telephone network and is compatible with most central station receivers. A total of fifteen popu­lar communications formats are supported, including Ademco Contact ID. The communicator also contains a unique
DACT option that eliminates 'dialer runaway'. It restricts the transmission of any trouble event to 10 attempts in a 24 hour period. Power supplied must be 12 or 24 volts, filtered and nonresettable. The Fire-Watch 411 Series DACT
Programmer is available for 411 programming. The 411 comes in a small 6.841" (17.376 cm) X 4.595" (11.671 cm) X 1.00" (2.54 cm) metal enclosure, providing a variety of mounting options.
1.1 Product Features
FIGURE 1-1: 411 Digital Communicator
• Three input channels
• Dual telephone lines
Dual telephone line voltage detectAlternating phone lines for 24 hour
test messages
1 2 3 4 5 6
1
2
3
• Program locations for entering up to
20-digit central station and service terminal telephone numbers
• Surface mount technology
• Compact in size
• Separate external keypad and display
1 2 3
FI RE-WATCH 4 11
provides means of programming dig-
ital communicator in program mode
provides means of testing phone circuits in troubleshoot mode
• 6.841" (17.376 cm) X 4.595" (11.671 cm) X 1.0" (2.54 cm) metal enclosure facilitates internal and external
control panel mounting
• Communicates vital status of monitored control panel:
fire alarmhost control panel troublefire supervisoryAC (mains) power loss (programmable)
411COVER.CDR
other
• Communicates vital status of 411 digital communicator:
digital communicator troublestelephone Line 1 and 2 voltage faultPrimary Central Station number communication faultSecondary Central Station number communication faultsystem off-normal (local Program Mode entered)24 Hour normal test24 Hour abnormal test (24 hour test message with previously reported alarm or trouble still active)
• Trouble Resound - if a trouble is silenced and the cause of the trouble is not cleared, the panel will resound the
trouble buzzer every midnight, until the trouble is cleared.
8
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Specifications
• LED for Communication Fail (visible with cover on)
• Piezo sounder
• Local piezo silence switch which silences onboard piezo sounder (accessible without removing cover)
• Real time clock
• Extensive transient protection
• Option that prevents 'dialer runaway'
1.2 Specifications
Operating Power
The 411 may be powered from UL listed control panels that output nonresettable and power-limited 12 or 24 VDC power. The configuration of Jumper J4 determines whether 12 VDC power is to be supplied directly to the 411 circuit board or 24 VDC power is to be supplied and then internally regulated down to 12 VDC.
DC Power - TB1 Terminals 1(+) and 2(-), Terminal 3 is Earth Ground
• J4 Jumper removed - Filtered, nonresettable and power-limited 24 VDC (nominal) power must be supplied at TB1 Terminals 1(+) and 2(-). Operating voltage provided must be within 21.3 to 24.0 VDC (UL tested range:
-15%, +10%). Current requirements are 78 mA in standby and 126 mA
• J4 Jumper installed - Filtered, nonresettable and power-limited 12 VDC (nominal) power must be supplied at TB1 Terminals 1(+) and 2(-). Operating voltage provided must be within 11.2 to 12.4 VDC (UL tested range:
-15%, +10%). Current requirements are 78 mA in standby and 126 mA
1
while communicating.
1
while communicating.
2
Channels/Inputs
- TB2 Terminals 1 through 6
Programmable Channels 1 through 3 Power-limited circuitry Fully supervised Operation: All channels NFPA Style B (Class B). Requires Normally Open contact to trigger Normal Operating Voltage: 12 VDC Maximum Line Resistance: 100 ohms per channel Alarm Current: 3.34 mA End-of-Line Resistor: 2.2K ohms, ½ watt (P/N 27070) Short Circuit Current: 3.8 mA per channel/input
1.3 Circuits
The 411 circuit board utilizes surface mount technology and contains a MicroController Unit (MCU), dual modular phone line jacks, piezo sounder and two connectors for input, output and power wiring.
1.3.1 Power Requirements
Voltage for the digital communicator may be a power-limited, filtered, nonresettable nominal 12 VDC [11.2 to
12.4 VDC (UL tested range: -15%, +10%)] or nominal 24 VDC [21.3 to 24.0 VDC (UL tested range: -15%, +10%)]. Jumper J4 is used to select the power source.
1. A maximum of 240 mA is possible with all input channels active, the 411 communicating, the Programmer connected and Lamp Test active.
2. Channels/inputs do not support 2-wire smoke detectors.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 9
Controls and Indicator
1.3.2 Channels/Inputs
Three input channels are provided on the 411 digital communicator which are used for connection to the control panel being monitored. Each input can be programmed to monitor the control panel for:
• fire alarm activation
• trouble activation
• fire supervisory activation
• AC loss activation
Each input channel is configured as a Class B circuit and must be wired to a Normally Open contact.
1.3.3 Primary and Secondary Phone Lines
Modular jacks are used to interface the primary and secondary phone lines to the public telephone network.
1.3.4 Earth Ground
Connect a separate earth ground wire to TB1 terminal 3 for transient protection.
Note: If zero ohms impedance exists between the 411 circuitry and earth ground, a ground fault will be indicated at the host FACP.
1.4 Controls and Indicator
FIGURE 1-2: 411 Indicator
Comm. Fail
LED
1 2 3 4 5 6
1 2 3
1
2
3
FI RE-WATCH 4 11
Front Panel Switch
• Silence Switch - press to silence local 411 piezo sounder
411 Piezo Sounder
• The 411 piezo sounder is used to locally annunciate DACT troubles. DACT troubles include input channel
open circuit, phone line 1 or 2 voltage fault, phone number 1 or 2 communication fault, total communication failure and communications disabled.
Piezo Silence
Switch
411COVER.CDR
Front Panel Indicator
• Communication Fail - yellow LED
10
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Digital Communicator Operation
1.5 Digital Communicator Operation
The 411 has been designed to be compatible with a wide variety of fire alarm, nonfire and combination control panels. Numerous formats are also available for communication to a central station. Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the Primary and Secondary phone lines. The digital communicator provides the following functions:
• Line Seizure- takes control of the phone lines, disconnecting any premises phones using the same lines
• Off/On-Hook - perform on and off-hook status to phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone®, programmable to rotary
• Discern proper Central Station 'ACK' and 'Kiss-off' tone(s)
• Transmit data to the Central Station(s)
• Verify data has been accepted by the Central Station(s)
• Hang-up and release phone lines
• Communicate in a variety of formats (Refer to Table 4-1, “Format Selection Addresses ( 20 and 50) Program­ming,” on page 38).
1.6 Telephone Requirements and Warnings
1.6.1 Telephone Circuitry - PH1 & PH2
DC Ringer Equivalence Number (REN) = 0.5B AC Ringer Equivalence Number = 1.3 Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be con­nected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
1.6.2 Digital Communicator:
Before connecting the 411 to the public switched telephone network, the installation of two RJ31X jacks is necessary. The following information is provided if required by the local telephone company:
Manufacturer: Fire•Lite Alarms Inc./Notifier
One Fire-Lite Place
Northford, CT 06472 Product Model Number: 411 FCC Registration Number: OAAUSA-25431-AL-E Ringer Equivalence 0.5B
Note: The FCC ID label is located on the inside cover.
Important! The DACT must not 9th Edition.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 11
be used to dial a phone number that is call-forwarded per requirements of UL 864
Telephone Requirements and Warnings
1.6.3 Telephone Company Rights and Warnings:
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this digital communicator. How­ever, the telephone company is required to give advance notice of such changes or interruptions. If the digital com­municator causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the digital communicator activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The digital communicator must be connected to the public switched telephone network upstream of any private tele­phone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
1.6.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equip­ment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician.
“The Ringer Equivalence Number number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
(REN) assigned to each terminal device provides an indication of the maximum
12
Representative: NOTIFIER, CANADA
10 Whitmore Road Woodbridge, Ontario L4L 7Z4
IC Certificate Number: 2132 9028 A Ringer Equivalence Number (REN): 0.2
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Operational Modes
1.7 Operational Modes
1.7.1 Normal Mode
Normal Mode is the standard mode of operation in which the 411 digital communicator monitors the host control panel status as well as telephone line voltage and other internal circuits. In addition to locally annunciating commu­nication fail, the digital communicator transmits system status information to UL listed central station receivers. Transmitted data includes fire alarm, fire alarm trouble, supervisory alarm and AC loss information. Specific digital communicator troubles are also transmitted.
1.7.2 Real Time Clock Mode
Real Time Clock Mode allows the user to change the digital communicator’s internal 24 hour clock. Connecting an external Programmer allows access to the various Modes of operation. While the communicator is in Real Time Clock Mode, it does not monitor channel inputs.
1.7.3 Program Mode
Program Mode is used to change the programmed functions of the 411 digital communicator. While the communica­tor is in Program Mode, it does not monitor channel inputs.
1.7.4 Troubleshoot Mode
Troubleshoot Mode may be used for testing the telephone line interconnect wiring. Connection from the 411’s mod­ular jacks, through the RJ31X jacks and into the telephone network may be easily checked. In this mode, the Pro­grammer keypad acts similar to a telephone touchpad. While the communicator is in Troubleshoot Mode, it does not monitor channel inputs.
1.7.5 Default Mode
Default Mode may be used to return all 411 programming back to the factory default settings.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 13
Installation
CHAPTER 2 Installation
2.1 Mounting Options
The 411 with enclosure may be mounted in the cabinet of the Fire•Lite/Notifier control panel which is being monitored or in any enclosure UL listed for fire protective use. When using with other than Fire•Lite/Notifier control panels, the 411 may be mounted in any enclosure UL listed for fire protective use. Mounting tabs are provided for ease of mounting.
FIGURE 2-1:411 Enclosure
Mounting bracket
0.187“
(0.475 cm)
6.841“ (17.376 cm)
Mounting
bracket
(11.671 cm)
0.187“
(0.475 cm)
4.595“
1.000“
(2.54 cm)
411BKBOX.CDR
1.000“ (2.54 cm)
Mounting bracket
Bottom
Mounting bracket
2.2 Operating Power
CAUTION: Disconnect all power before servicing the 411. The digital communicator may be damaged by removing
!
and/or inserting components or interconnecting cables while the unit is energized.
12VDC or 24VDC nominal power connections are made to TB1 on the 411 circuit board. When jumper J4 is installed, the 11.2 to 12.4 VDC operating voltage range (UL tested range: -15%, +10%) for the digital communicator must be power-limited, filtered, nonresettable. This 12 VDC nominal operating power can be supplied directly to the 411 by a UL listed 12 VDC power supply listed for fire protection or by a nonresettable 12 VDC output from a control panel. Alternatively, removing J4 Jumper on the digital communicator circuit board allows the 411 to be supplied by a power-limited, nonresettable 21.3 to 24.0 VDC (UL tested range: -15%, +10%). This 24 VDC nominal operating power can be supplied by a UL listed 24 VDC power supply, which, in order to comply with UL 864 must be listed for Fire Protective Signaling Systems or by a nonresettable 24 VDC output from a control panel. This nom­inal 24 VDC power is then internally regulated by the digital communicator to 12 VDC operating power.
Note that upon power-up, the 411 will immediately annunciate a DACT trouble since the communicator is factory defaulted to 'communicator disabled' at program location 64.
2.3 Input Channels
The 411 digital communicator has three channel inputs. Each channel is supervised for opens (trouble) and shorts (alarm) by the digital communicator. Each channel is a Style B (Class B) Initiating Device Circuit designed to accept any normally-open contact device. Since channels do not latch, a reset switch is not provided by the 411. The com­municator transmissions to a central station track the state of the inputs. Refer to Figure 2-3, “Style B Channel Con­nections,” on page 16 for information on wiring Style B circuits.
14
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Input Channels
FIGURE 2-2:Typical FACP Connection to 411
24 VDC nonresettable power
Supervisory
Relay
Alarm Relay
Trouble Relay
+ -
Channel 1
Channel 2
Channel 3
2.2K EOLS P/N 27070
TB2
TB1
J4 Not Installed
J1
U10
U8
R41
J4
J2
PH1
PH2
411
9200-411.CDR
Typical FACP MS-9200
Each input channel monitors a normally open device and may be programmed as follows:
• fire alarm
• host control panel trouble
• fire supervisory
•AC Loss
Programming the input channel automatically programs the transmitted event code, however, the event code can be changed since it is fully programmable. Event code transmissions can be tailored to the specific application and requirements of the Central Station.
AC Loss Reporting:
Any channel programmed for AC Loss, will transmit a specific AC loss signal only if the assigned Normally Open contact provides this function. Some panels provide an option that will automatically delay the trig­ger of their system trouble relays upon loss of AC. If this is provided by the host panel, program no additional delay in the 411. Be certain to verify the method employed by the host panel to be monitored.
The factory default programming for each channel is as follows:
Channel 1 - fire alarmChannel 2 - host control panel troubleChannel 3 - fire supervisory
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 15
Input Channels
2
Channel Labels
Note that space is provided for labeling the function of each channel. Write the function that has been programmed for each channel in the white boxes located to the right of the channel designator.
FIGURE 2-3:Style B Channel Connections
Channel/Input Labels
Inputs are power-limited,
supervised
Normally Open Contact Device
2.2K EOL Resistor P/N 27070
1 2 3 4 5 6
1 2 3
1
3
FI RE-WATCH 4 11
411_CHL.CDR
16
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Telephone Circuits
2.4 Telephone Circuits
Provision to connect two independent telephone lines is available via two telephone jacks labeled PH1 (Primary) and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage of an RJ31X style interconnection. (RJ31X jacks must be ordered separately).
CAUTION: It is critical that the 411 be located as the first device on the incoming telephone circuit to properly function.
TABLE 2-1: Wiring Phone Jacks
Incoming Telco Phone
Tip
Ring
Green Wire
Red Wire
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
(Primary Lines)
Lines
Ring
To Premises Phone
Tip
(Secondary Lines)
Incoming Telco Phone
Green Wire
Tip
Red Wire
Ring
Lines
Ring
To Premises
Phone
Tip
RJ31X JACK
Note: Shorting bars
inside RJ31X Jack
removed during male
plug insertion
7 foot Cable (MCBL-7)
Not supplied - Order
Separately
Primary Phone Line PH1
411
J2
Modular
Female Con-
nector
Secondary Phone Line
PH2
RJ31X JACK
PH1
Male Plug Connectors
PH2
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 17
411JACK.CDR
Optional Programmer
A
8888
2.5 Optional Programmer
The optional Fire-Watch 411 Series DACT Programmer is used to:
switch between the digital communicator's five Modes of operationset the digital communicator's 24 hour internal clock in Real-Time Clock Modeprogram the 411 digital communicator in Program Modetest the telephone lines interconnect in Troubleshoot Modereturn all digital communicator programming to the factory default settings in Default Mode
To use the 411 Series DACT Programmer:
1. Remove all power from the 411
2. Remove the two screws holding the 411 cover in place and remove the cover
3. Connect the Programmer cable to connector J2 located in the upper right corner of the 411. Note that the key
on the connector must align with the slot in the J2 connector
4. Reapply power to the 411
5. Operate the Programmer by pressing the MODE key. Enter the appropriate four digit Mode code and then
press the [ENTER/STORE] key.
Note that it is not possible to switch from Normal Mode to any other mode if any of the four Channels is programmed for fire alarm or fire supervisory, and is active, that is, in alarm (shorted).
FIGURE 2-4: Programmer Connection to 411
TB2
Programmer
Cable attached to Programmer
J2 connector
J1
U10
U8
LAMP TEST
123 F
456 E
0BC
J2
PH1
MODE
D987
1ST
EVENT
ENTER STORE
18
411
R41
TB1
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
J4
411-PRO.CDR
PH2
UL Power-limited Wiring Requirements
2.6 UL Power-limited Wiring Requirements
The three 411 input channels are power-limited circuits. Power supplied to the 411 must be power-limited 12 or 24 volts, filtered and nonresettable. Do not
connect nonpower-limited wiring to any circuits on the 411.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 19
Modes of Operation
CHAPTER 3 Modes of Operation
The 411 digital communicator has five operational modes:
• Normal Mode
• Real Time Clock Mode
•Program Mode
• Troubleshoot Mode
• Default Mode
The operational mode for the digital communicator is Normal Mode. The operator is able to switch between any modes of operation provided no alarm events are active in the system. It should be noted that the digital communica­tor will not respond to input activations while in any mode except Normal Mode.
Access to any other Mode requires connection of the optional Fire-Watch 411 Series DACT Programmer which consists of a keypad and display. Refer to Figure 3-1, “Programmer Keypad,” on page 21:
3.1 Normal Mode
Normal Mode is the standard (default) mode of operation for the 411 digital communicator. The communicator continuously monitors and reports to a central station, the status of the three input channels as well as the status of the digital communicator itself. If no activity is detected on the three input channels (no shorts or opens) and the commu­nicator is operating free of internal troubles, the digital communicator will display the following conditions:
Communication Fail LED is offOnboard piezo sounder is offCommunicator is not transmitting to the Central Station
The 411 digital communicator transmits system status reports to a central station via the public switched telephone network. Two supervised telephone line connections are made to interface the digital communicator to the telephone lines. Both telephone lines are supervised by the 411 for proper voltage.
The 411 is capable of line seizure on both the primary and secondary telephone line interfaces. Any time the digital
communicator detects the necessity to call the Central Station, line seizure will disconnect any local premises phones sharing the same telephone line. Sharing of phone lines, for fire systems, must be approved by the Local Authority Having Jurisdiction. All transmissions to the Central Station will be sent over the Primary phone line. In the event of
a noisy or faulty phone line, transmissions will be sent over the backup Secondary phone line.
Transmission options exist to:
• send reports to the secondary phone number as backup only
• send reports to both the primary and secondary phone numbers
• send reports to the first available central station phone number
If 10 total attempts to communicate are unsuccessful, the digital communicator will turn on the Communication Fail LED.
The 411 meets NFPA 72 requirements for Remote Station Protective Signaling Service and Central Station Signaling Service reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting premises. See “Central Station Communications” on page 37, for additional information.
20
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Normal Mode
The 411 can be switched from Normal Mode to any other Mode, provided no channel programmed for fire alarm or fire supervisory is active, that is, in alarm (shorted). The Fire-Watch 411 Series DACT Programmer must be con­nected to the 411 in order to change from mode to mode.
3.1.1 Programmer Key Functions
FIGURE 3-1:Programmer Keypad
PR411KEY.CDR
Select operating mode
Increment memory address
Address entry keys are 0 to 9
Data entry keys are 0 to 9 and A to F
Decrement memory address
One press = first memory address
Two presses = type any address
Save data, go to next address
MODE KEY
Pressing the MODE key followed by a valid 4-digit numerical code and the [ENTER/STORE] key selects one of the five modes of operation. To enter Normal Mode from any other mode, press the MODE key followed by
6676 and then [ENTER/STORE].
6676 spells NORM on a Touch-Tone® phone.
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key. Note that as
information is entered into the 411, the digits will scroll across the Programmer display from right to left.
___6 __66 _667 6676
A pause of up to 10 seconds between each number is allowed while entering the code.
LAMP TEST KEY
Pressing the Lamp Test key on the Programmer, while the digital communicator is in Normal Mode, will cause the front panel LED and all segments of the four 7-segment display on the programmer to light. Lamp Test works only in Normal Mode.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 21
Real Time Clock Mode
1st EVENT KEY
This key, along with the UP and DOWN arrow keys, are used only in Program Mode. Press the 1st EVENT key at any time to display the first program memory address and its content. The following may be displayed on the Programmer:
00_F
(data)
(address)
If the 1st EVENT key is pressed a second time, the following will be displayed on the Programmer display:
0.
Digit to be programmed
The contents of any address can be viewed by entering the digits of the desired address. For example, to view the contents of address 86, press the '8' key on the keypad. '8' will appear as the first digit in the display, a blank will appear in the position of the second digit and the decimal point will move one position to the right, indicating that the next digit can now be entered.
8_.
Digit to be programmed
Press the '6' key on the keypad. '6' will appear as the second digit on the display and the decimal point will move one position to the right. Press the [ENTER/STORE] to view the contents of address 86.
86_.
DOWN ARROW
Use the DOWN arrow key to decrement the memory address and view its content.
UP ARROW
Use the UP arrow key to increment the memory address and view its content.
[ENTER/STORE]
Stores entry into nonvolatile E
2
memory located on the 411 printed circuit board, then increments to the next
higher address.
3.1.2 Programmer Display
Four 7-segment red LED characters provide visual display of information in the various modes of operation.
3.2 Real Time Clock Mode
Real Time Clock Mode is entered by pressing the MODE key followed by the 4-digit entry code 2525 and pressing the [ENTER/STORE] key.
2525 spells CLCK on a Touch-Tone® phone.
22
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Real Time Clock Mode
If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key. Note that as information is entered into the 411, the digits will scroll across the Programmer display from right to left.
___2 __25 _252 2525
A pause of up to 10 seconds between each number is allowed while entering the code. After pressing the [ENTER/ STORE] key, the digital communicator will be in Real Time Clock Mode. A maximum of 10 minutes idle time is
allowed at this point before beginning program entries and between each key stroke, otherwise, the digital communi­cator will return to Normal Mode. Note that the time is not stored until the fourth and final digit is selected and the [ENTER/STORE] key is pressed. If the 411 returns to Normal Mode prior to entering the fourth digit, no changes will be stored and the original time is retained.
On entering Real Time Clock Mode, 0.001 will appear on the Programmer display:
0.001
Digit to be programmed
The time is displayed in military time. Note the position of the decimal point in the display. This indicates that the first digit to be programmed is the one to the left of the decimal point. To program the first hour digit, press the cor­responding number on the Programmer keypad and then press the [ENTER/STORE] key. For example, to program 2:00 PM (1400 in military time), press '1' on the keypad and then the [ENTER/STORE] key. The number '1' will appear as the far left digit and the decimal point will move one position to the right indicating that the second digit from the left is now ready for programming.
10.01
Digit to be programmed
Enter the second hour digit (4 in this example) and press the [ENTER/STORE] key. The number '4' will appear as the digit second from the left and the decimal point will move one position to the right indicating that the third digit from the left is now ready for programming.
140.1
Digit to be programmed
Enter the first minute digit (0 in this example) and press the [ENTER/STORE] key. The number '0' will appear as the digit third from the left and the decimal point will move one position to the right indicating that the fourth digit from the left is now ready for programming.
1400.
Digit to be programmed
Enter the second minute digit (0 in this example) and press the [ENTER/STORE] key. The number '0' will appear as the digit fourth from the left. Following the entry of the fourth and final digit, the operating mode will immediately switch to Normal Mode, indicating that programming of the time is now completed.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 23
Program Mode
To exit Real Time Clock Mode before completing clock programming, press the MODE key, followed by the 4-digit code for an alternate mode and then the [ENTER/STORE] key. During Real Time Clock Mode, if no key is pressed within 10 minutes, the communicator will revert to Normal Mode.
Note that upon power-up, the internal clock starts running at 00:00 midnight. It must be changed so that the 411 can accurately call in test signals to the Central Station. Upon power loss, the clock reverts to 00:00 midnight and must be reset.
3.3 Program Mode
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below:
Program feature
or option
Trouble Call Limit N
Permitted in
UL 864? (Y/N)
Possible settings
Program Address 89 = 0 (factory default): unlimited calling to Central Station for any trouble condition
Program Address 89 = 1: limits call for each unique trouble to 10 within a 24 hour period
Settings permitted
in UL 864
Program Address 89 = 0 for unlimited Central Station trouble calls
All programming selections made during Program Mode are stored in nonvolatile Electrically-Erasable Programma­ble Read-Only Memory (EEPROM). This ensures that the 411 will retain all entries made in Programming Mode even if power is removed.
The user must program the primary and secondary phone numbers, account numbers, 24-hour test report times and verify event codes for each Central Station account. The 411 is shipped with the program options/features already factory programmed. Alternative options/features may be programmed if desired. If all factory default settings are acceptable, programming is complete.
Program Mode is entered by pressing the MODE key followed by the 4-digit program mode entry code 7764 and pressing the [ENTER/STORE] key.
7764 spells PROG on a Touch-Tone® phone.
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key. Note that as
information is entered into the 411, the digits will scroll across the Programmer display from right to left.
___7 __77 _776 7764
A pause of up to 10 seconds between each number is allowed while entering the code. After pressing the [ENTER/ STORE] key, the digital communicator will be in Program Mode. A maximum of 10 minutes idle time is allowed at
this point before beginning program entries and between each key stroke, otherwise, the digital communicator will return to Normal Mode. All entries made prior to the 10 minute time-out are valid and are stored.
24
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Program Mode
Once in Program Mode, the digital communicator will:
Ignore all other keys other than those mentioned in this sectionDisplay 00_F on the Programmer displayContinue to communicate any events not previously acknowledged at a central station prior to entering
Programming Mode
While in Program Mode, the first three locations on the left of the Programmer display represent the memory address and the last location (farthest right) represents the contents of the memory address. The first address displayed is shown below:
00_F
(data)
(address)
When desired changes have been completed, exit Programming Mode by pressing the MODE key, followed by the 4-digit code for an alternate mode and then the [ENTER/STORE] key. During Program Mode, if no key is pressed within 10 minutes, the communicator will revert to Normal Mode.
The Programmer cable should not be removed from the 411 unless the communicator is in Normal Mode. If the Pro­grammer cable is removed while the 411 is in a Mode other than Normal Mode, the communicator will automatically revert to Normal Mode following a 10 minute when the cable is removed, the 411 will revert to Normal Mode following a 20 minute
time-out period. Note that if the Programmer is in Troubleshoot Mode
time-out period.
3.3.1 DACT Programming
Primary Central Station Phone Number (00 - 19)
The first twenty addresses (00 - 19) are factory set to 'F' (00_F to 19_F). Programming is done as follows:
 If your phone number is 484-7161, press 4.  The display will read 00_4.  Press [ENTER/STORE] to save the entry to memory and increment to the next address 01_F.  Enter the remaining numbers in their respective addresses as shown below:
Entry
4 8 4 7 1 6 1 F F F F F F F F F F F F F
Address
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19
Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as dialed numbers and the hexadecimal digits representing the following functions:
• A = * on a Touch-Tone phone keypad
• B = # on a Touch-Tone phone keypad
• C = look for secondary dial tone for up to two seconds (then dial anyway)
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must remain in all unused phone number addresses)
New FCC regulations allow extra digits to the carrier ID code, to identify the long distance carrier. The expanded phone number field of 20 digits facilitates this function. Simply enter the digits required by the telephone company if desired.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 25
Program Mode
Primary Central Station Number Communication Format (20)
One location is needed to select the Communication Format to the primary phone number. Address 20 is used for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0' through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK 1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK 2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK 3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK 4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK 5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK 6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK 7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK 8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK 9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK E: Contact ID, DTMF, 1400/2300 ACK F: Future use
Consult the Central Station for proper Format selection. For any Format chosen, all event codes are automati­cally programmed by the 411. Refer to Table 3-2, “4+2 Standard and 4+2 Express Formats - Primary,” on page 27, Table 3-3, “All 3+1, 4+1 and 4+2 Expanded Formats - Primary,” on page 28 and Table 3-1, “Ademco Con­tact ID Format - Primary,” on page 27.
Event Codes - Setting Entries
The Format selected in address 20 will cause the digital communicator to automatically program addresses 138 - 201 with the factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior to altering the event code settings. An entry of all zeros for any event code will cause the communicator to NOT transmit the report. Transmission of reports to either or both Central Station phone numbers may be disabled.
Upon accessing the first address (address 138) shown in Table 3-2 , the following may be displayed on the Program­mer 7-Segment Display, if the corresponding Format was selected in address 20.
1381
(data)
(address)
The first three locations on the left of the Programmer display represent the memory address 138 of the Format previ­ously selected in address 20. The last location 1 (farthest right) represents the contents of memory address 138 (which is the first digit of the event code).
The following Tables list the data which is automatically programmed for each Format that can be selected in address
20. The addresses shown in each Table contain the Setting data which is automatically programmed by the 411. To change the value, key in the new digit and then press the [ENTER/STORE] key to save the new value. Use the Up and Down Arrow keys to increment to the next address or decrement to the previous address.
26
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Program Mode
Ademco Contact ID Format Primary Central Station Event Codes
If 'E' is entered for address 20, the following data is automatically programmed for the Primary Central Station phone number event codes. Enter '000' for the Setting to disable the report to the Central Station. The Channel # is not programmable.
TABLE 3-1: Ademco Contact ID Format - Primary
Channel/
Address Description Setting
138 - 140 Primary # Input Channel 1 Active Event Code 110 001 141 - 143 Primary # Input Channel 2 Active Event Code 373 002 144 - 146 Primary # Input Channel 3 Active Event Code 200 003 147 - 149 not used 150 - 152 Primary # Input Channel 1 Fault Event Code 380 001 153 - 155 Primary # Input Channel 2 Fault Event Code 380 002 156 - 158 Primary # Input Channel 3 Fault Event Code 380 003 159 - 161 not used 162 - 164 Primary # Phone Line 1 Voltage Fault Event Code 351 000 165 - 167 Primary # Phone Line 2 Voltage Fault Event Code 352 000 168 - 170 Primary # Phone Number 1 Comm. Fault Event Code 354 001 171 - 173 Primary # Phone Number 2 Comm. Fault Event Code 354 002 174 - 176 Primary # System Off Normal Fault Code 308 000 177 - 179 Primary # System Test Message 602 000 180 - 182 Primary # System Abnormal Test Message 608 000 183 - 185 not used 186 - 188 not used 189 - 191 not used 192 - 194 not used
Input #
4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes
If 1, A or C is entered for address 20, the following data is automatically programmed for the Primary Central Sta­tion phone number event codes. Enter '00' for the Setting to disable the report to the Central Station.
TABLE 3-2: 4+2 Standard and 4+2 Express Formats - Primary
Address Description Setting
138 - 139 Primary # Input Channel 1 Active Event Code 11 140 - 141 Primary # Input Channel 2 Active Event Code FF 142 - 143 Primary # Input Channel 3 Active Event Code 83 144 - 145 not used 146 - 147 Primary # Input Channel 1 Fault Event Code F1 148 - 149 Primary # Input Channel 2 Fault Event Code F2 150 - 151 Primary # Input Channel 3 Fault Event Code F3 152 - 153 not used 154 - 155 Primary # Phone Line 1 Voltage Fault Event Code 64 156 - 157 Primary # Phone Line 2 Voltage Fault Event Code 65 158 - 159 Primary # Phone Number 1 Comm. Fault Event Code 6A 160 - 161 Primary # Phone Number 2 Comm. Fault Event Code 6B 162 - 163 Primary # System Off Normal Fault Code 6F 164 - 165 Primary # Input Channel 1 Active Restoral Code E1 166 - 167 Primary # Input Channel 2 Active Restoral Code E2 168 - 169 Primary # Input Channel 3 Active Restoral Code E3 170 - 171 not used 172 - 173 Primary # Input Channel 1 Fault Restoral Code D1 174 - 175 Primary # Input Channel 2 Fault Restoral Code D2 176 - 177 Primary # Input Channel 3 Fault Restoral Code D3 178 - 179 not used 180 - 181 Primary # Phone Line 1 Restoral Code A4 182 - 183 Primary # Phone Line 2 Restoral Code A5 184 - 185 Primary # Phone Number 1 Restoral Code AA 186 - 187 Primary # Phone Number 2 Restoral Code AB 188 - 189 Primary # System Off Normal Restoral Code AF 190 - 191 Primary # System Test Message 99
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 27
Program Mode
TABLE 3-2: 4+2 Standard and 4+2 Express Formats - Primary
Address Description Setting
192 - 193 Primary # System Abnormal Test Message 91 194 - 195 not used 196 - 197 not used 198 - 199 not used 200 - 201 not used
All 3+1, 4+1 and 4+2 Expanded Formats Primary Central Station Event Codes
If 0, 2, 3, 4, 5, 6, 7, 8 ,9, B or D is entered for address 20, the following data is automatically programmed for the Primary Central Station phone number event codes. Enter '0' for the Setting to disable the report to the Central Station.
TABLE 3-3: All 3+1, 4+1 and 4+2 Expanded Formats - Primary
Address Description Setting
138 Primary # Input Channel 1 Active Event Code 1 139 Primary # Input Channel 2 Active Event Code F 140 Primary # Input Channel 3 Active Event Code 8 141 not used 142 Primary # Input Channel 1 Fault Event Code F 143 Primary # Input Channel 2 Fault Event Code F 144 Primary # Input Channel 3 Fault Event Code F 145 not used 146 Primary # Phone Line 1 Voltage Fault Event Code 6 147 Primary # Phone Line 2 Voltage Fault Event Code 6 148 Primary # Phone Number 1 Comm. Fault Event Code 6 149 Primary # Phone Number 2 Comm. Fault Event Code 6 150 Primary # System Off Normal Fault Code 6 151 Primary # Input Channel 1 Active Restoral Code E 152 Primary # Input Channel 2 Active Restoral Code E 153 Primary # Input Channel 3 Active Restoral Code E 154 not used 155 Primary # Input Channel 1 Fault Restoral Code D 156 Primary # Input Channel 2 Fault Restoral Code D 157 Primary # Input Channel 3 Fault Restoral Code D 158 not used 159 Primary # Phone Line 1 Restoral Code A 160 Primary # Phone Line 2 Restoral Code A 161 Primary # Phone Number 1 Restoral Code A 162 Primary # Phone Number 2 Restoral Code A 163 Primary # System Off Normal Restoral Code A 164 Primary # System Test Message 9 165 Primary # System Abnormal Test Message F 166 not used 167 not used 168 not used 169 not used
Primary Central Station Number Account Code (21 - 24)
The four locations at addresses 21 - 24 default to all '0's. Valid entries are 0 - 9 and A - F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 20, enter three digits (one digit each in locations 21, 22 and 23 - location 24 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into address 20, enter four digits (one each in locations 21, 22, 23 and 24).
28
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Program Mode
Primary Central Station Number 24 Hour Test Time (25 - 28)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four locations, from addresses 25 - 28. The default is 00:00 (12:00 midnight). The limits for each location are as fol­lows (do not use values of A - F as entries).
25: enter 0, 1 or 2 26: enter 0 - 9 27: enter 0 - 5 28: enter 0 - 9
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (29)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter 1 = 12 hour, 2 = 8 hour or 3 = 6 hour.
Secondary Central Station Phone Number (30 - 49)
Addresses 30 - 49 are factory set to 'F' (30_F to 49_F). Programming is typically done as follows:
 If your phone number is 484-7161, press 4.  The display will read 30_4.  Press [ENTER/STORE] to save the entry to memory and increment to the next address 31_F.  Enter the remaining numbers in their respective addresses as shown below:
Entry
4 8 4 7 1 6 1 F F F F F F F F F F F F F
Address
30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49
Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as dialed numbers and the hexadecimal digits representing the following functions:
• A = * on a Touch-Tone phone keypad
• B = # on a Touch-Tone phone keypad
• C = look for secondary dial tone for up to two seconds (then dial anyway)
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must remain in all unused phone number addresses)
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 29
Program Mode
Secondary Central Station Number Communication Format (50)
One location is needed to select the Communication Format to the secondary phone number. Address 50 is used for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0' through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK 1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK 2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK 3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK 4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK 5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK 6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK 7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK 8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK 9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK E: Contact ID, DTMF, 1400/2300 ACK F: Future use
The Format selected in address 50 will cause the digital communicator to automatically program addresses 202 - 265 with the factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior to altering the event code settings. An entry of all zeros for any event code will cause the communicator to NOT transmit the report. Transmission of reports to either or both Central Station phone numbers may be disabled.
Refer to “Central Station Communications” on page 37 for information on Format reporting.
Upon accessing the first address which is 202 (Refer to Table 3-5, “4+2 Standard and 4+2 Express Formats - Second­ary,” on page 31), the following may be displayed on the Programmer’s 7-Segment Display, if the corresponding For­mat was selected in address 50.
2021
(data)
(address)
The first three locations on the left of the Programmer’s display represent the memory address 202. The last location 1 (farthest right) represents the contents of memory address 202 which is the first digit of the event code.
The following Tables list the data which is automatically programmed for each Format that can be selected in address
50. The addresses shown in each Table contain the event code Setting data which is automatically programmed by the 411. To change the value, key in the new digits and then press the [ENTER/STORE] key to save the new value. Use the Up and Down Arrow keys to increment to the next address or decrement to the previous address.
Ademco Contact ID Format Secondary Central Station Event Codes
If E is entered for address 50, the following data is automatically programmed for the Secondary Central Station phone number event codes. Enter '000' for the Setting to disable the report to the Central Station.
30
TABLE 3-4: Ademco Contact ID Format - Secondary
Address Description Setting
202 - 204 Secondary # Input Channel 1 Active Event Code 110 001 205 - 207 Secondary # Input Channel 2 Active Event Code 373 002 208 - 210 Secondary # Input Channel 3 Active Event Code 200 003
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Channel/
Input #
Program Mode
TABLE 3-4: Ademco Contact ID Format - Secondary
Channel/
Address Description Setting
Input #
211 - 213 not used 214 - 216 Secondary # Input Channel 1 Fault Event Code 380 001 217 - 219 Secondary # Input Channel 2 Fault Event Code 380 002 220 - 222 Secondary # Input Channel 3 Fault Event Code 380 003 223 - 225 not used 226 - 228 Secondary # Phone Line 1 Voltage Fault Event Code 351 000 229 - 231 Secondary # Phone Line 2 Voltage Fault Event Code 352 000 232 - 234 Secondary # Phone Number 1 Comm. Fault Event Code 354 001 235 - 237 Secondary # Phone Number 2 Comm. Fault Event Code 354 002 238 - 240 Secondary # System Off Normal Fault Code 308 000 241 - 243 Secondary # System Test Message 602 000 244 - 246 Secondary # System Abnormal Test Message 608 000 247 - 249 not used 250 - 252 not used 253 - 255 not used 256 - 258 not used
4+2 Standard and 4+2 Express Formats Secondary Central Station Event Codes
If 1, A or C is entered for address 50, the following data is automatically programmed for the Secondary Central Sta­tion phone number event codes. Enter '00' for the Setting to disable the report to the Central Station.
TABLE 3-5: 4+2 Standard and 4+2 Express Formats - Secondary
Address Description Setting
202 - 203 Secondary # Input Channel 1 Active Event Code 11 204 - 205 Secondary # Input Channel 2 Active Event Code FF 206 - 207 Secondary # Input Channel 3 Active Event Code 83 208 - 209 not used 210 - 211 Secondary # Input Channel 1 Fault Event Code F1 212 - 213 Secondary # Input Channel 2 Fault Event Code F2 214 - 215 Secondary # Input Channel 3 Fault Event Code F3 216 - 217 not used 218 - 219 Secondary # Phone Line 1 Voltage Fault Event Code 64 220 - 221 Secondary # Phone Line 2 Voltage Fault Event Code 65 222 - 223 Secondary # Phone Number 1 Comm. Fault Event Code 6A 224 - 225 Secondary # Phone Number 2 Comm. Fault Event Code 6B 226 - 227 Secondary # System Off Normal Fault Code 6F 228 - 229 Secondary # Input Channel 1 Active Restoral Code E1 230 - 231 Secondary # Input Channel 2 Active Restoral Code E2 232 - 233 Secondary # Input Channel 3 Active Restoral Code E3 234 - 235 not used 236 - 237 Secondary # Input Channel 1 Fault Restoral Code D1 238 - 239 Secondary # Input Channel 2 Fault Restoral Code D2 240 - 241 Secondary # Input Channel 3 Fault Restoral Code D3 242 - 243 not used 244 - 245 Secondary # Phone Line 1 Restoral Code A4 246 - 247 Secondary # Phone Line 2 Restoral Code A5 248 - 249 Secondary # Phone Number 1 Restoral Code AA 250 - 251 Secondary # Phone Number 2 Restoral Code AB 252 - 253 Secondary # System Off Normal Restoral Code AF 254 - 255 Secondary # System Test Message 99 256 - 257 Secondary # System Abnormal Test Message 91 258 - 259 not used 260 - 261 not used 262 - 263 not used 264 - 265 not used
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 31
Program Mode
All 3+1, 4+1 and 4+2 Expanded Formats Secondary Central Station Event Codes
If 0, 2, 3, 4, 5, 6, 7, 8 ,9, B or D is entered for address 50, the following data is automatically programmed for the Secondary Central Station phone number event codes. Enter '0' for the Setting to disable the report to the Central Station.
TABLE 3-6: All 3+1, 4+1 and 4+2 Expanded Formats - Secondary
Address Description Setting
202 Secondary # Input Channel 1 Active Event Code 1 203 Secondary # Input Channel 2 Active Event Code F 204 Secondary # Input Channel 3 Active Event Code 8 205 not used 206 Secondary # Input Channel 1 Fault Event Code F 207 Secondary # Input Channel 2 Fault Event Code F 208 Secondary # Input Channel 3 Fault Event Code F 209 not used 210 Secondary # Phone Line 1 Voltage Fault Event Code 6 211 Secondary # Phone Line 2 Voltage Fault Event Code 6 212 Secondary # Phone Number 1 Comm.Fault Event Code 6 213 Secondary # Phone Number 2 Comm. Fault Event Code 6 214 Secondary # System Off Normal Fault Code 6 215 Secondary # Input Channel 1 Active Restoral Code E 216 Secondary # Input Channel 2 Active Restoral Code E 217 Secondary # Input Channel 3 Active Restoral Code E 218 not used 219 Secondary # Input Channel 1 Fault Restoral Code D 220 Secondary # Input Channel 2 Fault Restoral Code D 221 Secondary # Input Channel 3 Fault Restoral Code D 222 not used 223 Secondary # Phone Line 1 Restoral Code A 224 Secondary # Phone Line 2 Restoral Code A 225 Secondary # Phone Number 1 Restoral Code A 226 Secondary # Phone Number 2 Restoral Code A 227 Secondary # System Off Normal Restoral Code A 228 Secondary # System Test Message 9 229 Secondary # System Abnormal Test Message F 230 not used 231 not used 232 not used 233 not used
Secondary Central Station Number Account Code (51 - 54)
The four locations at addresses 51 - 54 default to all '0's. Valid entries are 0 - 9 and A - F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 50, enter three digits (one digit each in locations 51, 52 and 53 - location 54 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into address 50, enter four digits (one each in locations 51, 52, 53 and 54).
Secondary Central Station Number 24 Hour Test Time (55 - 58)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four locations, from addresses 55 - 58. The default is 00:00 (12:00 midnight). The limits for each location are as fol­lows (do not use values of A - F as entries):
55: enter 0, 1 or 2 56: enter 0 - 9 57: enter 0 - 5 58: enter 0 - 9
32
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Program Mode
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (59)
The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter 1 = 12 hour, 2 = 8 hour or 3 = 6 hour.
AC Loss Reporting Delay (60)
Enter a digit of 0 - 9 or A - F corresponding to the number of hours to be delayed in reporting the loss of AC power. The factory default is '0' for no delay. The valid entries are '0' = no delay; '1' = 1 hours; '2' = 2 hours; '3' = 6 hours; '4' = 7 hours; '5' = 8 hours; '6' = 9 hours; '7' = 10 hours; '8' = 11 hours; '9' = 12 hours; 'A' = 13 hours; 'B' = 14 hours; 'C' = 15 hours; 'D' = 16 hours; 'E' = 17 hours; 'F' = 18 hours. Note: Use when the host panel has a
dedicated relay output. Verify the delay period programmed at the host panel. Location 60 is valid for all inputs programmed as AC Loss.
Backup Reporting (61)
Leaving address 61 at '0' means that reports will be transmitted to the secondary Central Station phone number only if attempts to communicate to the primary Central Station phone number are unsuccessful. Programming a '1' causes all reports to be transmitted to both the primary and secondary Central Station phone numbers. Pro­gramming a '2' causes reports to go to the first available receiver.
!
CAUTION: Do not alter this entry while the digital communicator is active.
Reserved for Future Use (62)
Reserved for Future Use (63)
Communicator Enable/Disable (64)
Leaving address 64 at the factory default setting of '0' prevents the digital communicator from transmitting status information to the Central Station(s). An entry of '1' in this location enables communication to the Central Station(s).
Note that upon power-up, the 411 will immediately annunciate a DACT trouble since the communicator is factory defaulted to 'communicator disabled' at program location 64.
Input Channel Function Selections - When selecting Input Channel functions, be certain to match the host panel relay output functions with the Input Channel functions. Test all wiring connections completely. All Input Channels require Normally Open contact closure to trigger. Input Channels do not latch
Input Channel 1 Function Selection (65)
1
.
Factory default for Channel 1 is '0' for activation on Fire Alarm. Enter '1' for Host Control Panel Trouble; '2' for Fire Supervisory; '4' for AC Loss.
Input Channel 2 Function Selection (66)
1
Factory default for Channel 2 is '1' for activation on Host Control Panel Trouble. Enter '0' for Fire Alarm; '2' for Fire Supervisory; '4' for AC Loss.
Input Channel 3 Function Selection (67)
1
Factory default for Channel 3 is '2' for activation on Fire Supervisory. Enter '0' for Fire Alarm; '1' for Host Control Panel Trouble; '4' for AC Loss.
1. Changing the input function will automatically change the corresponding Primary and Secondary event codes to reflect the new input function. The Communication Format should be programmed first, followed by the Input Channel Function.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 33
Program Mode
Reserved for Future Use (68)
Input Channel 1 Delay Timer (69 - 71)
1
The Delay Timer is used to delay activation of the digital communicator when the Input Channel is activated. Input Channel 1 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, host control panel trouble and fire supervi-
sory, must not
be delayed. A delay, therefore, cannot be selected for inputs programmed for these fire applica-
tions.
Input Channel 2 Delay Timer (72 - 74)
1
The Delay Timer is used to delay activation of the digital communicator when the Input Channel is activated. Input Channel 2 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, host control panel trouble and fire supervi-
sory, must not
be delayed. A delay, therefore, cannot be selected for inputs programmed for these fire applica-
tions.
Input Channel 3 Delay Timer (75 - 77)
1
The Delay Timer is used to delay activation of the digital communicator when the Input Channel is activated. Input Channel 3 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, host control panel trouble and fire supervi-
sory, must not
be delayed. A delay, therefore, cannot be selected for inputs programmed for these fire applica-
tions.
Reserved for Future Use (78 - 80)
1
Touchtone/Rotary Select for Primary Phone (81)
A '0' programmed in this address by the factory, triggers Touchtone dialing over the primary phone line. Select '1' for rotary dialing.
Make/Break Ratio for Primary Phone (82)
This address is used only if a '1' has been programmed for address 81. The Make/Break ratio is factory set to '0' which is 67/33 ratio, but may be changed to '1' which is 62/38 ratio.
Touchtone/Rotary Select for Secondary Phone (83)
A '0' programmed in this address by the factory, triggers Touchtone dialing over the secondary phone line. Select '1' for rotary dialing.
Make/Break Ratio for Secondary Phone (84)
This address is used only if a '1' has been programmed for address 83. The Make/Break ratio is factory set to '0' which is 67/33 ratio, but may be changed to '1' which is 62/38 ratio.
1. This timer does not delay LED activation and is not used for channels programmed as AC Loss circuits.
34
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Program Mode
Reserved for Future Use (85)
Reserved for Future Use (86)
Reserved for Future Use (87)
Reserved for Future Use (88)
Trouble Call Limit (89)
Factory default setting of '0' in address 89, allows the digital communicator to call the Central Station each time any DACT trouble and any active Channel programmed for host panel trouble is detected by the 411. Program­ming a '1' in this address enables the Trouble Call Limit feature, which limits the number of 411 and Input Chan­nel Trouble calls to the Central Station to 10 calls for each unique trouble event within a 24 hour period. Separate limit counters keep track of each unique type of trouble (i.e. open input channel). To clear the limit counters, dis­able and then enable this location. Note that the number of phone line (communication) faults called to the Cen­tral Station are not limited by this feature.
No subsequent restoral message is sent to the Central Station(s) for a particular trouble whose limit of 10 calls has been reached. Local DACT annunciation will still track the particular trouble and restoral.
Reserved for Future Use (90 - 93)
Reserved for Future Use (94 - 113)
Reserved for Future Use (114 - 115)
Reserved for Future Use (116)
Reserved for Future Use (117 - 136)
Reserved for Future Use (137)
Programming Event Code Settings (138 - 265)
Event Code Settings, corresponding to the Formats selected for the Primary Central Station phone number in address 20 and the Secondary Central Station phone number in address 50, are automatically set to factory default values. Refer to Table 3-2, “4+2 Standard and 4+2 Express Formats - Primary,” on page 27, Table 3-3, “All 3+1, 4+1 and 4+2 Expanded Formats - Primary,” on page 28 and Table 3-1, “Ademco Contact ID Format - Primary,” on page 27 for format designated by address 20. Refer to Table 3-5, “4+2 Standard and 4+2 Express Formats ­Secondary,” on page 31, Table 3-6, “All 3+1, 4+1 and 4+2 Expanded Formats - Secondary,” on page 32 and Table 3-4, “Ademco Contact ID Format - Secondary,” on page 30 for format designated by address 50. The Event Code Settings can be altered. Consult your Central Station prior to changing the event code settings.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 35
Default Mode
3.4 Default Mode
To return all program entries to their factory original settings, perform the following steps only when the system is idle (i.e. the communicator is not active) and there are no active fire alarms or fire supervisories in the system:
Press the MODE key followed by the 4-digit code 3337 and press the [ENTER/STORE] key.
3337 spells DEFP (DEFault Programming) on a Touch-Tone® phone.
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key. Within five seconds, repeat this entry by again pressing the MODE key followed by the 4-digit code 3337 and pressing the [ENTER/STORE] key. The display will read 3337 while the E
2
nonvolatile memory (storage area for all pro­gramming options) is being reprogrammed with the original default settings. When reprogramming is complete, the display will be blank.
3.5 Troubleshoot Mode
To access the Troubleshoot Mode, press the MODE key followed by the digits 8768 and then the [ENTER/STORE] key.
8768 spells TROU on a Touch-Tone
®
phone.
Once in this mode, the 411 will continue to communicate any events not yet acknowledged at a central station prior
to
entering Troubleshoot Mode. The UP arrow, DOWN arrow and 1st EVENT keys do not function in this mode.
Telephone Line Testing
Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/STORE] causes seizure of the Pri- mary phone line, which in turn, lights the red LED 1 on the circuit board near the PH1 connector, signifying that the Primary phone line is active. After a delay of three seconds, the 411 goes off-hook to acquire a dial tone.
The Programmer keypad may be used as a telephone touchpad for number dialing. Once the first digit is pressed, the display will move the C or D character one position to the left, while placing the digit to be dialed on the farthest right display position. Continue to press the phone numbers to be dialed. Successive depressions of the [ENTER/ STORE] key hangs up and picks up the phone (places the phone on or off the hook).
The secondary phone line may be tested by pressing the E key for touchtone dialing or the F key for rotary dialing and then following the same procedure used for the primary phone line. A handset may be temporarily connected across transformer T1 of the 411 as indicated in Figure 3-2. The handset, when connected across T1, may be used only as an amplifier/speaker or telephone with the keypad used for number dialing.
FIGURE 3-2:Handset/Speaker Connection
TB2
J1
U10
U8
J2
PH1
Both Primary and Secondary Lines
36
TB1
R41
PH2
J4
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
411BRD.CDR
Central Station Communications
CHAPTER 4 Central Station Communications
The 411 digital communicator transmits system status reports to Central Stations via the public switched telephone network. Two supervised telephone line connections are made to interface the communicator to the telephone lines. Two 7-foot telephone cords P/N MCBL-7 may be used for this purpose (not supplied - order separately).
The digital communicator supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble sig­nal will sound and the trouble condition will be reported to a central station over the remaining good phone line.
The digital communicator comes with line seizure capability provided for both the primary and secondary telephone line interfaces. Any time that the DACT needs to make a call to a central station, line seizure will disconnect any local premises phones sharing the same telephone line. All transmissions to central stations will be sent over the Pri­mary Central Station phone line. In the event of noisy phone lines, transmissions will be sent over the backup Sec­ondary phone line.
Two phone numbers must be programmed, the Primary Central Station phone number and the Secondary Central Sta­tion phone number. There are three options for transmission to the Central Station:
• All reports are always sent to the Primary Central Station phone number with the Secondary Central Station number for emergency backup purposes only
• All reports are sent to both Central Station phone numbers
• Reports are sent to the first available Central Station phone number only
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 37
Central Station Communications
The digital communicator is capable of reporting detailed messages depending upon the Format in use. Table 4-1 shows the data reporting structure for each of the pulsed formats as well as the Ademco Express Formats. Ademco Express Formats allow a typical data message to be transmitted to the Central Station in under 5 seconds. Pulsed for­mats typically require 15 to 20 seconds in comparison. Table 4-2 defines each letter code used in Table 4-1 . See “Ademco Contact ID Format Event Code Description” on page 41 for a description of the data reporting structure for Ademco Contact ID Format.
TABLE 4-1: Format Selection Addresses ( 20 and 50) Programming
Format #
0, 2, 4, 6, 8
Report
3+1/4+1/Standard
4+1 Express
Fire Alarm SSS(S) FA
Fire Alarm Restore SSS(S) RFA
Channel/Input Trouble
(Channel/Input Open)
Channel/Input Trouble
Restore
SSS(S) TZ
SSS(S) RTZ
System Trouble SSS(S) TS
System Trouble Restore SSS(S) RTS
AC Loss SSS(S) P
AC Loss Restore SSS(S) RP
Fire Supervisory Condition SSS(S) V
Fire Supervisory Condition
Restore
SSS(S) RV
Format #
3, 5, 7, 9
3+1/4+1/Expanded
SSS(S) FA
FAFA FA(FA) 2
SSS(S) RFA
RFARFARFA (RFA) 2
SSS(S) TZ
TZTZTZ(TZ) Z
SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSS(S) TS
TSTSTS(TS) Y
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSS(S) P PPP(P) Z
SSS(S) RP
RPRPRP(RP) Z
SSS(S) V
VVV(V) Z SSS(S) RV
RVRVR(RV) Z
Format #
1, A, C
4+2/Standard 4+2
Express
SSSS FAFA2 SSSS FAZ
SSSS RFARFA2 SSSS RFAZ
SSSS TZTZ2 SSSS TZZ
SSSS RTZRTZ2 SSSS RTZZ
SSSS TSTS2 SSSS TSY
SSSS RTSRTS2 SSSS RTSY
SSSS PP2 SSSS PP2
SSSS RPRP2 SSSS RPRP2
SSSS VV2 SSSS VZ
SSSS RVRV2 SSSS RVZ
Test Report SSS(S) X SSS(S) X SSSS XX2 SSSS XX2
Format #
B, D
4+2/Expanded
38
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Central Station Communications
TABLE 4-2: Format Selection Address Explanation
Where:
SSS or SSSS = Subscriber ID FA = Fire Alarm (1st digit) FA2 = Fire Alarm (2nd digit) Z = Channel/Input Number RFA = Fire Alarm Restore (1st digit) RFA2 = Fire Alarm Restore (2nd digit) TZ = Zone Trouble (1st digit) TZ2 = Zone Trouble (2nd digit) RTZ = Zone Trouble Restore (1st digit) RTZ2 = Zone Trouble Restore (2nd digit) TS = System Trouble (1st digit) TS2 = System Trouble (2nd digit) RTS = System Trouble Restore (1st digit) RTS2 = System Trouble Restore (2nd digit) P = AC Loss (1st digit) P2 = AC Loss (2nd digit) RP = AC Loss Restore (1st digit) RP2 = AC Loss Restore (2nd digit) V = Fire Supervisory Condition (1st digit) V2 = Fire Supervisory Condition (2nd digit) RV = Fire Supervisory Condition Restore (1st digit) RV2 = Fire Supervisory Condition Restore (2nd digit) X = Test Report (1st digit) X2 = Test Report (2nd digit) Y = Trouble corresponding to the following:
1 = Not Used 2 = Not Used 3 = Not Used 4 = Telco Primary Line Fault 5 = Telco Secondary Line Fault 6 = Not Used 7 = Not Used 8 = Not Used 9 = Not Used A = Communication Failure Primary Number B = Communication Failure Secondary Number C = Not Used D = Not Used E = Not Used F = System Off Normal
Note that for Expanded Reporting, the digital communicator automatically adds the digit corresponding to the Channel/Input number, and the second digit corresponding to any system trouble condition. Only the first digit shown in Table 3-3 and Table 3-6 is programmable.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 39
Central Station Communications
4.0.1 Transmittal Priorities
The digital communicator transmits highest priority events first. Events in terms of priority are listed below in descending order:
1. Fire Alarm (highest priority level)
2. Fire Supervisory
3. System Troubles
Host Panel Trouble (active input programmed for trouble) AC Fail (after delay) Channel/Input faults Telephone line fault Communication trouble System Off Normal
4. Restoral Reports
Fire Alarm Fire Supervisory Host Panel Trouble AC Channel/Input fault Telephone line Communication System Off Normal
5. System Test
40
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Central Station Communications
4.0.2 Ademco Contact ID Format Event Code Description
This section describes the various Event Codes and their messages which are available for the Ademco Contact ID Format. The reporting structure for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC
Where: SSSS = Four digit Subscriber ID Account Code (addresses 21 - 24 and 51 - 54) 18 = Identifies transmission as Contact ID to the receiver at the Central Station Q = Event Qualifier where 1 = New Event and 3 = New Restore XYZ = Event code (shown in Tables) GG = Group number CCC = Channel/Input number
Notes:
1. 18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
alarm and trouble report.
2. Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or
R
for New Restore.
3. GG Group Number is fixed at '00' and cannot be changed.
4. CCC Channel/Input Number is transmitted as '001' for Channel/Input 1, '002' for Channel/Input 2, '003' for
Channel/Input 3.
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows:
Time
Date Rcvr/Line ID SSSS QXYZ GG CCCC
11:28 03/25 11 7777 E110 00 C001 - general fire alarm on Channel/Input 1 11:28 03/25 11 7777 E111 00 C002 - smoke detector alarm on Channel/Input 2 11:28 03/25 11 7777 E380 00 C003 - fault on Channel/Input 3 11:28 03/25 11 7777 R110 00 C001 - Channel/Input 1 alarm restored 11:28 03/25 11 7777 R111 00 C002 - smoke detector Channel/Input 2 restored 11:28 03/25 11 7777 R380 00 C003 - Channel/Input 3 fault restored
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 41
Central Station Communications
The following table contains UL listed receivers compatible with the 411 digital communicator.
TABLE 4-3: Compatible UL Listed Receivers
Format #
(Addresses 20 and 50)
0 4+1 Ademco Express
1 4+2 Ademco Express
2 3+1/Standard/1800/2300
3 3+1/Expanded/1800/2300
4 3+1/Standard/1900/1400
5 3+1/Expanded/1900/1400
6 4+1/Standard/1800/2300
7 4+1/Expanded/1800/2300
8 4+1/Standard/1900/1400
9 4+1/Expanded/1900/1400
A 4+2/Standard/1800/2300
B 4+2/Expanded/1800/2300
C 4+2/Standard/1900/1400
D 4+2/Expanded/1900/1400
Ademco
685 (1)
9000 (2)
Silent Knight
ITI
CS-4000 (3)
FBI
CP220FB
Models 1 & 2
Osborne Hoffman
Radionics
6000/6500 (5)
Sescoa
3000R (7)
Surguard
MLR-2 (9)
                             
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(4)
(8)

(5, 6)

    
(5)
    
(5)
   
E Ademco Contact ID
(1) With 685-8 Line Card with Rev. 4.4d software. (2) With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software. (3) Rev. 4.0 software. (4) FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8 software. (5) Model 6500 with Rev. 600 software. (6) Model 6000 with Rev. 204 software. (7) With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software. (8) Model 2 only. (9) Version 1.62 software.
IMPORTANT! The compatibility table provides a list of compatible receivers and associated software versions for the receivers. Changes in the hardware and/or software by the receiver manufacturers may affect the receiver com­patibility with the 411.
It is the installer’s responsibility to ensure that the monitoring service receiver is compatible with the 411. After com­pleting the installation, communication between the 411 and the Central Station Receiver must be tested and verified.

42
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Programming Sheets
Appendix A Programming Sheets
A.1 Digital Communicator Options Program Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
R00R01R02R03R04R05R06R07R08R09R10R11R12R13R14R15R16R17R18R
Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.
R
Primary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
20
R21R22R23R R25R26R27R R
Primary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
29
Primary Central Station Account Code: Valid entries are 0 to 9 and A to F.
24
Primary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
28
R30R31R32R33R34R35R36R37R38R39R40R41R42R43R44R45R46R47R48R
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
R
Secondary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
50
R51R52R53R R55R56R57R R
Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
59
R
AC Loss Reporting Delay. Enter '0' for no delay; '1' for 1 hours; '2' for 2 hours; '3' for 6 hours; '4' for 7 hours;
60
'5' for 8 hours; '6' for 9 hours; '7' for 10 hours; '8' for 11 hours; '9' for 12 hours; 'A' for 13 hours; 'B' for 14 hours; 'C' for 15 hours; 'D' for 16 hours; 'E' for 17 hours; 'F' for 18 hours.
R
Backup Reporting. Enter '0' to report to Secondary phone number as backup only; '1' to report to both Primary
61
and Secondary phone number for all reports/messages; '2' reports go to first available receiver.
Secondary Central Station Account Code: Valid entries are 0 to 9 and A to F.
54
Secondary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
58
19
49
R
Reserved for Future Use.
62
R
Reserved for Future Use.
63
R
Communicator Enable/Disable. Enter '0' to disable communication to Central Station; '1' to enable. Default
64
entry of '0' causes the 411 to annunciate a DACT trouble immediately on power-up.
R
Input Channel 1 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
65
visory; '4' for AC loss.
R
Input Channel 2 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
66
visory; '4' for AC loss.
R
Input Channel 3 Function Selection. Enter '0' for fire alarm; '1' for host control panel trouble; '2' for fire super-
67
visory; '4' for AC loss.
R
Future use.
68
R69R70R
delay. Does not delay Input Channels programmed for fire functions.
R72R73R
delay. Does not delay Input Channels programmed for fire functions.
R75R76R
delay. Does not delay Input Channels programmed for fire functions.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 43
Input Channel 1 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no
71
Input Channel 2 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no
74
Input Channel 3 Delay Timer. Enter 0 - 179 seconds delay. Factory default is '000' for no
77
Programming Sheets
7879 
Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
81
Make/Break Ratio for Primary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
82
Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
83
Make/Break Ratio for Secondary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
84
Future use.
85
Future use.
86
Future use.
87
Future use.
88
Trouble Call Limit. Enter a '0' to disable this feature; '1' to enable Trouble Call Limit. Factory default is '0' for
89
disabled.
909192 
94 9596 9798 99100101102103104105106107108109110
111112113
114
115
Future use.
80
Future use.
Future use.
Future Use.
93
   
Future use.
116
117118119120121 122123 124125 126127128129130131132133
134 135 136
Future use.
137
Future use
.
44
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Programming Sheets
A.2 Digital Communicator Options Program Sheet (Factory Defaults)
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
F F F F F F F F F F F F F F F F F F F F
R00R01R02R03R04R05R06R07R08R09R10R11R12R13R14R15R16R17R18R
Addresses 00 to 19 store the Primary Central Station phone number. Enter 'F' to represent the end of number.
E
R
Primary Central Station Communication Format: 'E' for Ademco Contact ID Format.
20
0 0 0 0
R21R22R23R
0 0 0 0
R25R26R27R
0
R
Primary Number Test Time Interval. '0' for 24 hours.
29
F F F F F F F F F F F F F F F F F F F F
R30R31R32R33R34R35R36R37R38R39R40R41R42R43R44R45R46R47R48R
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
E
R
Secondary Central Station Communication Format. 'E' for Ademco Contact ID Format.
50
0 0 0 0
R51R52R53R
0 0 0 0
R55R56R57R
0
R
Secondary Number Test Time Interval. '0' for 24 hours.
59
2
R
AC Loss Reporting Delay. '2' for 2 hour delay.
60
0
R
Backup Reporting. '0' to report to Secondary Central Station phone number as backup only.
61
1
R
Future Use.
62
0
R
Future Use.
63
0
R
Communicator Enable/Disable. '0' disables communication to Central Station.
64
0
R
Input Channel 1 Function Selection. '0' for fire alarm.
65
1
R
Input Channel 2 Function Selection. '1' for host control panel trouble.
66
2
R
Input Channel 3 Function Selection. '2' for fire supervisory.
67
4
R
Future Use.
68
0 0 0
R69R70R
0 0 0
R72R73R
0 0 0
R75R76R
71
74
77
Primary Central Station Account Code.
24
Primary Central Station 24-hour Test Time. '0000' = 12:00 midnight.
28
Secondary Central Station Account Code.
54
Secondary Central Station 24-hour Test Time: '0000' = 12:00 midnight.
58
Input Channel 1 Delay Timer. '000' for no delay. Does not delay fire functions.
Input Channel 2 Delay Timer. '000' for no delay. Does not delay fire functions.
Input Channel 3 Delay Timer. '000' for no delay. Does not delay fire functions.
19
49
0 0 0
R78R79R
0
R
Touchtone/Rotary Select for Primary Phone. '0' for touchtone dialing.
81
0
R
Make/Break Ratio for Primary Phone. '0' for 67/33 ratio.
82
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 45
Future Use.
80
Programming Sheets
0
Touchtone/Rotary Select for Secondary Phone. '0' for touchtone dialing.
83
0
Make/Break Ratio for Secondary Phone. '0' for 67/33 ratio.
84
1
Future Use.
85
0
Future Use.
86
1
Future Use.
87
7
Future Use.
88
0
Trouble Call Limit. '0' for disabled feature.
89
0 0 0 0
909192
F F F F F F F F F F F F F F F F F F
949596979899
F F
112113
0 3
114
0
116
F F F F F F F F F F F F F F F F F
117118119120121122123124125 126127128129130131132133
F F F
134 135136
0
137
Future Use
Future Use.
115
Future Use.
Future Use.
Future Use.
93
.
Future Use
100101102103104105106107108109110 111
.
46
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Event Codes/Transmission Format Programming Sheets
Appendix B Event Codes/Transmission Format
Programming Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
B.1 4+2 Standard & 4+2 Express Formats Primary Central Station
138139140141142143144145146147148149150151152153
154155156157158159160161162163164165166167168169
170171172173174175176177178179180181182183184185
186187188189190191192193194195196197198199200201
B.2 4+2 Standard & 4+2 Express Formats Secondary Central Station
202203204205206207208209210211212213214215216217
218219220221222223224225226227228229230231232233
234235236237238239240241242243244245246247248249
250251252253254255256257258259260261262263264265
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 47
Event Codes/Transmission Format Programming Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
B.3 4+2 Standard & 4+2 Express Formats Primary Central Station
11FF8392F1F2F3F4
138139140141142143144
64656A6B6FE1E2E3
154155156157158159160
93D1D2D3D4A4A5AA
170171172173174175176
ABAF999171727374
186187188189190191192
145146147148149150151152153
161162163164165166167168169
177178179180181182183184185
193194195196197198199200201
B.4 4+2 Standard & 4+2 Express Formats Secondary Central Station
11FF8392F1F2F3F4
202203204205206207208
209210211212213214215216217
64656A6B6FE1E2E3
218219220221222223224
93D1D2D3D4A4A5AA
234235236237238239240
ABAF999171727374
250251252253254255256
225226227228229230231232233
241242243244245246247248249
257258259260261262263264265
48
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Event Codes/Transmission Format Programming Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
B.5 All 3+1, All 4+1 and 4+2 Expanded Formats for Primary Central Station
138139140141142143144145146147148149150151152153
154155156157158159160161162163164165166167168169
B.6 All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary Central
Station
202203204205206207208209210211212213214215216217
218219220221222223224225226227228229230231232233
B.7 All 3+1, All 4+1 and 4+2 Expanded Formats for Primary Central
Station (Factory Defaults)
1F8 9 FFFF66666EEE
138139140141142143144145146147148149150151152153
9 DDDDAAAAA9 F7777
154155156157158159160161162163164165166167168169
B.8 All 3+1, All 4+1 and 4+2 Expanded Formats for Secondary Central
Station (Factory Defaults)
1F8 9FFFF66666EEE
202203204205206207208209210211212213214215216217
9 DDDDAAAAA9 F7777
218219220221222223224225226227228229230231232233
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 49
Event Codes/Transmission Format Programming Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
B.9 Ademco Contact ID Format Primary Central Station
138139140141142143144
154155156157158159160
170171172173174175176
186187188189190191192
145146147148149150151152153
161162163164165166167168169
177178179180181182183184185
193194
B.10 Ademco Contact ID Format Secondary Central Station
202203204205206207208
218219220221222223224
234235236237238239240
250251252253254255256
209210211212213214215216217
225226227228229230231232233
241242243244245246247248249
257258
50
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Event Codes/Transmission Format Programming Sheets
B.11 Ademco Contact ID Format Primary Central Station (Factory Defaults)
1103732003013803
R
138R139R140R141R142R143R144R145R146R147R148R149R150R151R152R153
8038038035135235
R
154R155R156R157R158R159R160R161R162R163R164R165R166R167R168R169
4354308602608411
R
170R171R172R173R174R175R176R177R178R179R180R181R182R183R184R185
416412413
R
186R187R188R189R190R191R192R193R194
B.12 Ademco Contact ID Format Secondary Central Station (Factory
Defaults)
1103732003013803
R
202R203R204R205R206R207R208R209R210R211R212R213R214R215R216R217
8038038035135235
R
218R219R220R221R222R223R224R225R226R227R228R229R230R231R232R233
4354308602608411
R
234R235R236R237R238R239R240R241R242R243R244R245R246R247R248R249
416412413
R
250R251R252R253R254R255R256R257R258
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 51
Ademco Contact ID Format Event Code Description
Appendix C Ademco Contact ID Format Event
Code Description
EVENT CODE CLASSIFICATIONS
1 0 0
ALARMS
M e d i c a l F i r e Panic Bur­glary Gen­eral 24 Hour
2 00
SUPERVISORY
Fire
3 00
TROUBLES
System Sounder/ Relay System Peripheral Commu­nication Protective Loop Sensor
400
OPEN/CLOSE
REMOTE ACCESS
Open/Close Remote Access Access Con­trol
5 00
DISABLES/
BYPASSES
System Sounder/ Relay System Peripheral Commu­nication
EVENT MESSAGE
Medical Alarms - 100 100 Medical EMERG - Personal Emergency - # 101 Pendant transmitter EMERG - Personal Emergency - # 102 Fail to report in EMERG - Fail to Check-in - #
Fire Alarms - 110 110 Fire Alarm FIRE - Fire Alarm - # 111 Smoke FIRE - Smoke Detector - # 112 Combustion FIRE - Combustion - # 113 Waterflow FIRE - Waterflow - # 114 Heat FIRE - Heat Sensor - # 115 Pull station FIRE - Pull Station - # 116 Duct FIRE - Duct Sensor - # 117 Flame FIRE - Flame Sensor - # 118 Near Alarm FIRE - Near Alarm - #
600
TEST/
MISC.
Tes t
52
Panic Alarms - 120 120 Panic Alarm PANIC - Panic - # 121 Duress PANIC - Duress 122 Silent PANIC - Silent Panic - # 123 Audible PANIC - Audible Panic - #
Burglar Alarms - 130 130 Burglary BURG - Burglary - # 131 Perimeter BURG - Perimeter - # 132 Interior BURG - Interior - # 133 24-Hour BURG - 24-Hour - # 134 Entry/Exit BURG - Entry/Exit - # 135 Day/Night BURG - Day/Night - # 136 Outdoor BURG - Outdoor - # 137 Tamper BURG - Tamper - # 138 Near Alarm BURG - Near Alarm - #
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Ademco Contact ID Format Event Code Description
EVENT MESSAGE
General Alarms - 140 140 General Alarm ALARM - General Alarm - # 141 Polling loop open ALARM - Polling Loop Open - # 142 Polling loop short ALARM - Polling Loop Short - # 143 Expansion module failure ALARM - Exp. Module Fail - # 144 Sensor tamper ALARM - Sensor Tamper - # 145 Expansion module tamper ALARM - Exp. Module Tamper - #
24 Hour Non-Burglary - 150 and 160 150 24-Hour Non-Burg ALARM - 24-Hr. Non-Burg - # 151 Gas detected ALARM - Gas Detected - # 152 Refrigeration ALARM - Refrigeration - # 153 Loss of heat ALARM - Heating System - # 154 Water leakage ALARM - Eater Leakage - # 155 Foil break ALARM - Foil Break - # 156 Day trouble ALARM - Day Zone - # 157 Low bottled gas level ALARM - Low Gas Level - # 158 High temp ALARM - High Temperature - # 159 Low temp ALARM - Low Temperature - # 161 Loss of air flow ALARM - Air Flow - #
Fire Supervisory - 200 and 210 200 Fire supervisory SUPER. - Fire Supervisory - # 201 Low water pressure SUPER. - Low Water Pressure - # 202 Lox CO2 SUPER. - Low CO2 203 Gate valve sensor SUPER. - Gate Valve - # 204 Low water level SUPER. - Low Water Level - # 205 Pump activated SUPER. - Pump Activation - # 206 Pump failure SUPER. - Pump Failure - #
System Troubles - 300 and 310 300 System trouble TROUBLE - System Trouble 301 AC loss TROUBLE - AC Power 302 Low system battery TROUBLE - System Low Battery 303 RAM checksum bad TROUBLE - Bad RAM Checksum (Restore not applicable) 304 ROM checksum bad TROUBLE - Bad ROM Checksum (Restore not applicable) 305 System reset TROUBLE - System Reset (Restore not applicable) 306 Panel program changed TROUBLE - Programming Changed (Restore not applicable) 307 Self-test failure TROUBLE - Self Test Failure 308 System shutdown TROUBLE - System Shutdown 309 Battery test failure TROUBLE - Battery Test Failure 310 Ground fault TROUBLE - Ground Fault - # 311 No battery TROUBLE - No Battery
Sounder/Relay Troubles - 320 320 Sounder/Relay TROUBLE - Sounder Relay - # 321 Bell 1 TROUBLE - Bell/Siren #1 322 Bell 2 TROUBLE - Bell/Siren #2 323 Alarm relay TROUBLE - Alarm Relay 324 Trouble relay TROUBLE - Trouble Relay 325 Reversing TROUBLE - Reversing Relay 326 Bell 3 TROUBLE - Bell/Siren #3 327 Bell 4 TROUBLE - Bell/Siren #4
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 53
Ademco Contact ID Format Event Code Description
EVENT MESSAGE
System Peripheral Troubles - 330 and 340 330 System peripheral TROUBLE - Sys. Peripheral - # 331 Polling loop open TROUBLE - Polling Loop Open 332 Polling loop short TROUBLE - Polling Loop Short 333 Expansion module failure TROUBLE - Exp. Module Fail - # 334 Repeater failure TROUBLE - Repeater Failure - # 335 Local printer paper out TROUBLE - Printer Paper Out 336 Local printer failure TROUBLE - Local Printer
Communication Troubles - 350 and 360 350 Communication TROUBLE - Communication Trouble 351 Telco 1 fault TROUBLE - Phone Line #1 352 Telco 2 fault TROUBLE - Phone Line #2 353 Long range radio xmitter fault TROUBLE - Radio Transmitter 354 Fail to communicate TROUBLE - Fail to Communicate 355 Loss of radio supervision TROUBLE - Radio Supervision 356 Loss of central polling TROUBLE - Central Radio Polling
Protection Loop Troubles - 370 370 Protection loop TROUBLE - Protection Loop - # 371 Protection loop open TROUBLE - Protection Loop Open - # 372 Protection loop short TROUBLE - Protection Loop Short - # 373 Fire Trouble TROUBLE - Fire Loop - #
Sensor Troubles - 380 380 Sensor trouble TROUBLE - Sensor Trouble - # 381 Loss of supervision - RF TROUBLE - RF Sensor Supervision - # 382 Loss of supervision - RPM TROUBLE - RPM Sensor Supervision - # 383 Sensor tamper TROUBLE - Sensor Tamper - # 384 RF transmitter low battery TROUBLE - RF Sensor Batt. - #
Open/Close - 400 400 Open/Close OPENING CLOSING 401 Open/Close by user OPENING - User # CLOSING - User # 402 Group Open/Close OPENING - Group User #CLOSING - Group User # 403 Automatic Open/Close OPENING - Automatic CLOSING - Automatic 404 Late Open/Close OPENING - Late CLOSING - Late 405 Deferred Open/Close Opening not used Closing not used 406 Cancel OPENING - Cancel Closing not used 407 Remote arm/disarm OPENING - Remote CLOSING - Remote 408 Quick arm Opening not applicable CLOSING - Quick arm 409 Keyswitch Open/Close OPENING - Keyswitch CLOSING - Keyswitch
Remote Access - 410 411 Callback request made REMOTE - Callback Requested Restore not applicable 412 Success - download/access REMOTE - Successful Access Restore not applicable 413 Unsuccessful access REMOTE - Unsuccessful Access Restore not applicable 414 System shutdown REMOTE - System Shutdown 415 Dialer shutdown REMOTE - Dialer Shutdown 416 Success - upload/access REMOTE - Successful Access Restore not applicable
54
Access Control - 420 421 Access denied ACCESS - Access Denied - User # Restore not used 422 Access report by user ACCESS - Access Gained - User # Restore not used
System Disables - 500 and 510
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Ademco Contact ID Format Event Code Description
EVENT MESSAGE
Sounder/Relay Disables - 520 520 Sounder/Relay disable DISABLE - Sounder/Relay - # 521 Bell 1 disable DISABLE - Bell/Siren - #1 522 Bell 2 disable DISABLE - Bell/Siren - #2 523 Alarm relay disable DISABLE - Alarm Relay 524 Trouble relay disable DISABLE - Trouble Relay 525 Reversing relay disable DISABLE - Reversing Relay 526 Bell 3 disable DISABLE - Bell/Siren - #3 527 Bell 4 disable DISABLE - Bell/Siren - #4
System Peripheral Disables - 530 and 540
Communication Disables - 550 and 560 551 Dialer disabled DISABLE - Dialer Disable 552 Radio transmitter disabled DISABLE - Radio Disable
Bypasses - 570 570 Zone bypass BYPASS - Zone Bypass - # 571 Fire bypass BYPASS - Fire Bypass - # 572 24-Hour zone bypass BYPASS - 24-Hour Bypass - # 573 Burglar bypass BYPASS - Burg. Bypass - # 574 Group bypass BYPASS - Group Bypass - #
Test Misc. - 600 601 Manual trigger test TEST - Manually Triggered Restore not applicable 602 Periodic test report TEST - Periodic Restore not applicable 603 Periodic RF transmission TEST - Periodic Radio Restore not applicable 604 Fire test TEST - Fire Test Restore not used 605 Status report to follow STATUS - Status Follows Restore not applicable 606 Listen-in to follow LISTEN - Listen-in Active Restore not applicable 607 Walk test mode TEST - Walk Test Mode 608 System abnormal test TEST - System Abnormal Test
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 55
Wire Requirements
Appendix D Wire Requirements
It is important to use the correct type of wire, wire gauge and wire run length per each 411 circuit. Reference the fol­lowing table to specify wire requirements and limitations for each digital communicator.
TABLE 4-4: Wire Specifications
CIRCUIT CONNECTIONS WIRE REQUIREMENTS
CIRCUIT
TYPE
Channels/Inputs
Power Input
Nominal
12 V DC or
24 VDC
CIRCUIT
FUNCTION
Connects to
normally open
contact trig-
gers DACT
Powers 411
WIRE TYPE AND
LIMITATIONS
Untwisted,
unshielded wire (Do
not exceed 100
ohms).
Voltage limits
12 VDC (11.2 to
12.4 VDC - UL
tested range: -15%,
+10%)
24 VDC (21.3-24.0
- UL tested range: ­15%, +10%)
RECOMMENDED
MAX. DISTANCE
FEET (METERS)
10,000 (3,000m)
8,000 (2,400m) 4,875 (1,450m)
3,225 (980m)
not applicable
12 AWG (3.25 mm 14 AWG (2.00 mm 16 AWG (1.30 mm 18 AWG (0.75 mm
WIRE GUAGE
2
) Signal 88202 Belden 9583 WPW999
2
) Signal 88402 Belden 9581 WPW995
2
) Signal 88602 Belden 9575 WPW991
2
) Signal 88802 Belden 9574 WPW975
12 - 18 AWG
(3.25 mm
2
- 0.75 mm2)
56
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Operational Modes
Appendix E Operational Modes
TABLE 4-5: Operational Modes
CODE ACTIVITY NOTES
6676 (NORM) Returns to normal operation Fire protection is on.
2525 (CLCK) Enters Real-Time Clock Mode
7764 (PROG) Enters Program Mode
3337 (DEFP)
Returns digital communicator to factory
default program settings
8768 (TROU) Allows testing of both telephone lines. Fire protection is off during Troubleshoot Mode.
Allows programming of digital communicator.
Program digital communicator time.
Fire protection is off.
Fire protection is off.
Fire protection is off during Default Mode.
411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D 57
Index
Numerics
411
see DACT
A
AC Loss Reporting 15, 33
B
Backup Reporting 33
C
Central Station
Communication 37
Channel 9, 14
Alarm Current 9 Default Programming 15 Delay Timer 34 Function Selection 33 Labels 16 Line Resistance 9 Operating Voltage 9 Programming 10, 15 Style B 9
Class B
see Style B Communication Fail 10 Communicator Disabled 14
D
DACT 8
MS-9200 Connection 15
Programming 25 Default Mode 13, 36 Description 8 Dialer Runaway 8 Digital Alarm Communicator
Transmitter
see also DACT 8
E
Earth Ground 10 Enclosure 14 End-Of-Line Resistor 8, 16
Channel 9 EOL
see End-Of-Line Resistor Event Code 15, 26, 35
F
FCC Registration 11 Features 8 Fire-Watch 411 Series DACT
Programmer
see Programmer Format 26, 30, 38
I
Indicator 10
see also LED 10 Inputs
see Channels
J
Jumper J4 9, 14
12 VDC 9
24 VDC 9
L
LED 9 Line Seizure 11, 20
M
Modes of Operation 13, 20, 57 Mounting 8, 14
N
Normal Mode 13, 20
O
Off/On-Hook 11
P
Phone 10, 11
Circuit 11, 17
Line Testing 36 Phone Connector - Male 11 Piezo
see Sounder Power 8
Operating 9, 14
12 VDC 9, 14 24 VDC 9, 14 Current Requirements 9
UL Tested Range 9 Program Mode 13, 24 Programmer 8, 18
Connection 18 Display 22 Key Functions 21
1st Event 22
Down Arrow 22
Enter/Store 22
Lamp Test 21
Mode 21
Up Arrow 22
Operation 18
R
Real Time Clock Mode 13, 22 Receivers
UL Listed 42
REN
see Ringer Equivalence Number Ringer Equivalence Number 11 RJ31X 17
see Phone Connector - Male
S
Silence
see also switch 9 Sounder 9, 10 Specifications 9 Status
Control Panel 8
DACT 8 Style B 9 switch
Control 10
Silence 9
T
Time
Power-up 24
Setting 24
Transmittal Priorities 40 Trouble Call Limit 35 Trouble Resound 8 Troubleshoot Mode 13, 36
U
UL Power-limited Wiring 19
W
Wire Specifications 56
58 411 Communicator Document #50921 Rev. D 11/07/2005 P/N 50921:D
Limited Warranty
The manufacturer warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. The manufacturer does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than the manufacturer or as expressly authorized by the manufacturer in writing, or is serviced by anyone other than the manufacturer or its authorized distributors. This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department.
This writing constitutes the only warranty made by the manufacturer, with respect to its products. The manufacturer, does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that the manufacturer, is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER’S PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
Warn-GL-04-2005.fm
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
©2005 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Loading...