OGF - ZC Series
OPEN GAS FIREBOX
INSTALLATION & OPERATING INSTRUCTIONS
MODELS:
OGF - 2.7/ZC
OGF - 3.0/ZC
OGF - 3.5/ZC
FIREFOX INDUSTRIES PTY LTD
ACN 074 490 654
Factory 4, 15 Stud Road Bayswater, Victoria 3153 AUSTRALIA Ph: (03) 9720 9055 Fax: (03) 9720 9255
This appliance must be installed by
authorized personnel in accordance with
manufacturers instructions, gas fitting
regulations, AGA 601 code for installation
of gas burning appliances, electrical wiring
regulations and any other statutory
requirement. The guidelines here-in
have been tested and approved to
AS 4558/AG 108. AGA Approval No. 6386.
HOT AIR
OUTLETS
FLUE SPIGOT
FIREFOX ‘OGF-ZC’
FIREBOX
CONTROL COVER PANEL
GAS INLET
COLD AIR INTAKE
FAN SWITCH
ELECTRIC
CORD
GAS
FIREGRATE
‘GFG’
For the appropriate Gas Firegrate ‘GFG’
to be used in conjunction with the Gas
Firebox (OGF). See specification pages
on the back of booklet.
B
A
C
G
A
S
E
N
T
R
Y
CONTROL
COVER PANEL
DECORATIVE FRONT IRON

OGF - ZC Series
INSTALLATION REQUIREMENTS
DEFINITION
Installation of a Firefox OGF-ZC series open fronted steel firebox into a timber framed and
plasterboard enclosure in conjunction with the specified steel flueing system to draw and
exhaust combustion gases up and away from the gas log firegrate.
1. Ensure that any air extraction devices located in the vicinity of the fireplace will not cause a
negative air pressure (suction) which could cause a spillage of combustion gases into the room
where the firebox is located when in operation.
2. GAS SUPPLY REQUIREMENT: Provide a 12mm (1/2”) copper gas pipe into the chamber with a
tail approx. ¾ of the way into the firebox. An access hole is provided on the right hand side of the
unit 130mm up from the base and 140mm in from the front of the unit. For MJ/HR rating of the gas
firegrate burner refer to specification pages.
3. ELECTRICAL SUPPLY: The firebox is supplied with 1.5m of lead and a 3 pin plug located on the
lower left hand side of the unit. The lead must not rise above 100mm of the base level of the firebox.
If connecting to a wall mounted isolating switch, ensure that the switch is far enough away so as to
not obstruct the fitting of a decorative surround i.e. mantelpiece.
4. Construct timber framing as required to suit the selected Firefox firebox (See example detail).
. Maintain 25mm clearance to the sides and back of the firebox and 50mm clearance from the
top from combustible materials.
. Secure firebox into position with metal strapping.
. Plasterboard can be zero clearance to the perimeter face flange of the unit.
5. FLUEING REQUIREMENTS:
. Use the specified Twin Skin Flue system i.e. stainless steel inner flue PLUS the galvanized steel
outer flue casing.
. Secure inner stainless flues at each crimp joint with 4 pop rivets.
. Secure outer galvanized casing at each crimp joint with 4 x 25mm self tapping screws.
. A 25mm clearance to all combustible materials is required from the outer flue casing.
. Fit approved cowl as specified for the selected firebox/flue.
6. Permanent ventilation equal to the cross sectional area of the specified firebox flue must be
provided into the room/area the gas fire is located.
7. Use only the appropriate Firefox gas firegrate/burner (GFG) in conjunction with the selected
Firefox OGF/ZC firebox See GFG (GAS FIREGRATE) Specifications located in the following pages.
For installation and commissioning procedure of the gas burner/firegrate (GFG) refer to separate
details entitled:
INSTALLATION & OPERATING INSTRUCTIONS ‘GFG’ Series GAS FIREGRATES

OGF - ZC Series
e.g. Open Gas Firebox Installation into a Timber Framed Enclosure
PLASTER
BOARD
F.L.
GAS ENTRY
FRAME HEIGHT
BASE OF UNIT
6mm THK NON COMBUSTIBLE
FOREHEARTH & BASE UNDER
UNIT IF PLACING ON A
COMBUSTIBLE FLOOR
ALIGN FACE OF FIREBOX FLUSH
WITH PLASTERBOARD UNLESS
OTHERWISE SPECIFIED
TIMBER FRAME
25mm CLEARANCE
TO ALL COMBUSTIBLES
WHEN USING TWIN
SKIN FLUES
OUTER CASING (GALV.)
( SEE BELOW)
CLEAR FROM
TOP OF UNIT
50
FIREFOX GAS
FIREGRATE (’GFG’)
USE TWIN SKIN
FLUE WHERE
EXPOSED TO
COMBUSTIBLE
MATERIALS AND
MAINTAIN 25mm
CLEARANCE
600 MIN
ABOVE R/LINE
3600 MIN FLUE
RISE FROM TOP
OF UNIT
GAS COWL
ELEC.
SUPPLY
SWITCH
VARIABLE
(DEPENDS ON SELECTED SURROUND
CHECK SPEC./SELECTION)
FRAME
DEPTH
300
MIN
INNER FLUE (STAINLESS)
( SEE BELOW)
130
R.L
25
NOTE: DO NOT LOCATE ANY
EXTRACTION AIR DEVICE WHICH
MAY CAUSE A NEGATIVE AIR PRESSURE
IN THE ROOM WHERE
THE GAS FIRE IS LOCATED
VENTILATION OF 400cm2 IS
REQUIRED INTO THE ROOM
WHERE THE GAS FIRE IS LOCATED,
e.g. ROOF/CEILING SPACE OUTSIDE
WALL CAVITY OR SUB-FLR. AREA
PLUMBING & ELECTRICAL MUST BE
CARRIED OUT BY AN AUTHORISED
PERSON
FRAME WIDITH
GAS ENTRY INPUT
200
MIN
FOREHEARTH
25mm CLEARANCE
OGF - 35-ZC
950
775
460
229
280
52
140
A
C
B
EXAMPLE ONLY
This detail must be read in
conjunction with manufacturers
Installation Requirements &
Operating Instructions.
DIMENSIONAL REQUIREMENTS
MODEL
OGF - 27-ZC OGF - 30-ZC
A
B
C
770
705
430
178
229
830
740
440
203
254
INNER
FLUE
OUTER
CASING
Mj/hr
36 42
GAS INPUT REQUIREMENTS
CHECK DATA PLATE ON ‘GFG’ FOR CORRECT GAS TYPE

OGF - ZC Series
OPEN GAS FIREBOX SPECIFICATIONS
FRONT
TOP
RIGHT HAND SIDE
A
F
C
D
B
E
FLUE
SPIGOT
FLUE
SPIGOT
FAN
FAN
FAN
SWITCH
POWER
SUPPLY
POWER
SUPPLY
GAS PIPE
INLET
GAS PIPE
INLET
C
FLUE
SPIGOT
50
130
140
75
A
75
For installation and
commisioning procedure of
the Gas Firegrate/Burner
‘GFG’ refer to seperate
instructions entitled;
INSTALLATION & OPERATING
INSTRUCTIONS ‘GFG’ Series
FIREGRATES.
FIREBOX
MODEL
FIREBOX DIMENSIONS
A B C D E F
720 655 400 160 680 630
780 690 420 155 740 665
900 725 435 155 860 700
}
}
}
FLUE
INNER/OUTER
178
(7”)
229
(9”)
203
(8”)
254
(10”)
229
(9”)
280
(11”)
}
}
}
APPROPRIATE GAS
FIREGRATE ‘GFG’
GFG 2.7
GAS INPUT
NG LP
36 - 35 Mj Hr
41 - 40 Mj Hr
52 - 50 Mj Hr
GFG 3.0
GFG 3.5
OGF - 27/ZC
OGF - 30/ZC
OGF - 35/ZC

OGF - ZC Series
CLEARANCE TO COMBUSTIBLE DECORATIVE SURROUNDS
Decorative surrounds i.e. timber
mantelpieces/combustible moulding must be
50mm (min) clear of the face side edges and top
face edge of the firebox.
Upright legs and breast sections of
combustible surrounds must not project further
than 50mm (max) forward of the face of the firebox.
Mantle shelves must be 300mm (min)
clear above the top edge of the firebox and must
not project more than 250mm (max) forward of
the face of the firebox.
A non-combustible floor protector
(forehearth) at the base directly in front of the
firebox opening must be a minimum of 6mm
thick, project a minimum 300mm forward and
200mm on each side of the firebox opening.
MANTLEPIECE BREAST
LEG
50
MIN
50
MIN
50
MAX
250
MAX
300
MIN
FIREFOX
OGF UNIT

OGF - ZC Series
USER INSTRUCTIONS
Congratulations on having a FIREFOX
fan forced gas log fire installed in your
home. We are sure it will provide you with many
years of realistic fireside pleasure, comfort and
enjoyment.
It is important that you familiarize
yourself with the appliance by reading through
these instructions.
If your installer has not shown you how
to light the FIREFOX gas firegrate which has
been fitted into the unit, refer to the separate
booklet entitled INSTALLATION & OPERATING
INSTRUCTIONS - GFG SERIES (Gas Firegrates
-L/C effect) under Lighting Burner &
Commissioning and also familiarize yourself with
the USER INSTRUCTIONS contained there-in.
Your FIREFOX gas firebox incorporates
a sophisticated heat exchanger design which
collects heat and a 2 speed fan which transfers
the collected heat into the room/area where the
FIREFOX is located. The fan control switch is
located on the lower left hand front of the unit.
The fan can remain OFF whilist the gas firegate
is in operation. To boost heat output simply
select one of the two fan speeds avaliable i.e.
LOW or HIGH.
Your FIREFOX gas unit is relatively
maintenance free. However we recommend that
you have the appliance/installation checked once
a year to ensure correct operation.
SAFETY PRECAUTIONS
As with any live naked flame burning
apparatus, it is important in order to protect
against personal injury or property damage to
treat its operation with care and respect. A
safety screen/fireguard should be used for the
protection of children, elderly and infirm.
WARNING
DO NOT PLACE FOREIGN ARTICLES ON OR
AGAINST THE APPLIANCE.
DO NOT USE OR STORE FLAMMABLE
MATERIALS NEAR THE APPLIANCE.
DO NOT SPRAY AEROSOLS IN THE VICINITY
OF THE APPLIANCE WHILST IN OPERATION.
DO NOT USE GAS LOGS/COALS BURNERS
OTHER THAN THAT SPECIFIED FOR THE
APPLIANCE.
MAGNETIC TABS
SCREEN
LOCATING PINS