Ø
External Power: click on to enable/disable an exter
-
nal 24Vdc PSU.
For the MIM module, you can enable Fast mode in
Style B or Style C/NO connection. When Fast Mode is
enabled, the activiation of the module will be detected
by the control panel within 2 seconds.
+
A short circuit fault will be detected quickly while its
restoration will be slow as with the other faults.
Default: disabled.
n
Output module parameters programming
Click on an entered Output Module, the relevant pro
gramming window will be shown as per the following
description.
FIRST section: as per the Detectors section.
SECOND section: Trigger zones; each Output module
can be triggered by up to 4 of the 32 available software
zones for FC501 panel. An Output module will be acti
vated when any of the selected zones are triggered, re
ach the status condition configured in the Fourth
section (Zone row).
Base: in this section, the base for the Output module
can be selected; click-on available bases (for
FC430SAM and FC430SAB only). Once the "sounder"
base is selected, a new programming tab labelled
"base" allowing access to the sounder base program
ming page, where the trigger zones, the trigger points,
the trigger condidtions can be selected and the following parameters can be configured:
Parameter Result
Enabled
When selected, the base is enabled. Otherwise the base is disabled
Label 20 characters base label
Silenceable
Sounds until "SILENCE/RESOUND
SOUNDERS" button is pressed
when selected. Otherwise sounds
until "RESET" button is pressed.
Set As SC1
When selected, the base behaves
as the Sounder Circuit 1 SC1
Monostable
When selected, the base sounds
until the monstable outputs time
elapses
Beacon: Activate the blinking or glowing (ON).
THIRD section: Trigger points. each output module can be
assigned to 3 Activation points : in this case the Output Mo
dule is activated when at least one of the Input points to
which it belongs is in a alarm status, indicate:
Ø
the loop which the device is connected to;
Ø
the device address.
FOURTH section: Options, these options will allow you
to select the conditions that will activate the output module:
Ø
Zone warning, Zone fault, Zone Delay to Alarm, Zone
Alarm, Zone Double Knock, Zone Test;
Ø
Point warning, Point fault, Point Delay to Alarm, Point
Alarm;
Ø
Panel warning, Panel fault, Panel delay to alarm, Pa
-
nel alarm,
Ø
Network fault.
It is also possible to program the Output Module as: Si
-
lenceable, Set as SC1, ACTIVE ON DISABLEMENT,
MONOSTABLE, TIMED WARNING (see Outputs pro
-
gramming).
Ø
Linked Delay: see the same option in the paragraph
“Panel Output Programming”.
For the following types of devices:
FC410LPAV (all versions)
FC430LPASB
FC430SAB (with FC430SB),
In addition to those certified to EN54-23:
FC410LPS-R/W
FC410LPBS
FC430LPBSB,
It is possible to separate the programming of the Soun
der and Beacon, in two different programming tabs. The
two tabs, for Sounder and Beacon, have the same pro
gramming options, except for "Set As SC1", which will
be present only for the Sounder output.
+
It is not possible to separately enable/disable the
two output channels.
+
The separate programming of the Sounder and Be
-
acon of the devices (named previously), it will be
possible also by Control Panel User Interface in the
Devices programming pages.
Pulse On: If the Pulse On option is disabled, the sounder sounds steady. If not, the sounder sounds a pulse (2
seconds on, 2 seconds off) as indicated by the following
options. In all cases, the tone of the sounder is based on
the selection in the Options page.
+
The sounder sounds continuously for the Fault,
Double Knock and Test events
+
Disable As General Options to make the Pulse
On options of the selected sounder different to the
settings in the General option > General Outputs
Settings page
Detector Alarm: If enabled, the sounder will pulse
when the programmed Alarm event is triggered by a
detector. Default: disabled.
+
The sounder will sound continuously when the pro
-
grammed Alarm event is triggered by a call point or
by the EVAC button, independently by the Detec
-
tor Alarm option set.
Delay to Alarm: If enabled, the sounder will pulse when
the programmed Delay to Alarm event occurs. Default:
disabled.
Warning: If enabled, the sounder will pulse when the
programmed Warning event occurs.
Default: enabled.
PC PROGRAMMING 39