FINDER 55.34.9.220.0040, 55.32.9.110.0040, 55.34.8.110.0040, 55.34.8.024, 55.32.9.220.0040 Specification

...
Page 1
55.32 55.33 55.34
2 CO (DPDT) 3 CO (3PDT) 4 CO (4PDT)
10/20 10/20 7/15
250/400 250/400 250/250
2,500 2,500 1,750
500 500 350
0.37 0.37 0.125
300 (5/5) 300 (5/5) 300 (5/5)
AgNi AgNi AgNi
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240
6 - 12 - 24 - 48 - 60 - 110 - 125 - 220
1.5/1 1.5/1 1.5/1
(0.8…1.1)U
N
(0.8…1.1)U
N
(0.8…1.1)U
N
(0.8…1.1)U
N
(0.8…1.1)U
N
(0.8…1.1)U
N
0.8 UN/0.5 U
N
0.8 UN/0.5 U
N
0.8 UN/0.5 U
N
0.2 UN/0.1 U
N
0.2 UN/0.1 U
N
0.2 UN/0.1 U
N
20 · 106/50 · 10
6
20 · 106/50 · 10
6
20 · 106/50 · 10
6
200 · 10
3
200 · 10
3
150 · 10
3
9/3 9/3 9/3
444
1,000 1,000 1,000
–40…+85 –40…+85 –40…+85
RT I RT I RT I
2
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (U
N) V AC (50/60 Hz)
V DC
Rated power AC/DC VA (50 Hz)/W
Operating range AC
DC
Holding voltage AC/DC
Must drop-out voltage AC/DC
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC1 cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 µs)
kV
Dielectric strength between open contacts V AC
Ambient temperature range °C
Environmental protection
Approvals (according to type)
Features
Plug-in mount, general purpose 2, 3 & 4 Pole relays
55.32 - 2 Pole 10 A
55.33 - 3 Pole 10 A
55.34 - 4 Pole 7 A
Lockable test button and mechanical flag
indicator as standard on 2 & 4 pole types
AC coils & DC coils
UL Listing (certain relay/socket combinations)
Cadmium Free contacts (preferred version)
Contact material options
94 series sockets
Coil EMC suppression
Timer accessories 86 series
2 pole, 10 A
Plug-in 94 series sockets
3 pole, 10 A
Plug-in 94 series sockets
4 pole, 7 A
Plug-in 94 series sockets
FOR UL HORSEPOWER AND PILOT DUTY RATINGS SEE “General technical information” page V
55.32 55.33 55.34
55 Series - General purpose relays 7 - 10 A
Page 2
3
Example: 55 series plug-in relay, 4 CO (4PDT), 12 V DC coil, lockable test button and mechanical indicator.
Type Coil version A B C D
55.32/34 AC-DC 0 - 2 - 5 0 0 0 AC 0 - 2 - 5 0 2 - 3 - 4 - 5 0 AC 0 - 2 - 5 0 54 / DC 0 - 2 - 5 0 2 - 4 - 6 - 7 - 8 - 9 0 DC 0 - 2 - 5 0 74 - 94 /
55.33 AC-DC 0 - 2 - 5 00 0 AC 0 - 2 - 5 0 1 - 3 - 5 0 DC 0 - 2 - 5 0 1 - 6 - 7 - 8 - 9 0
55.12/13/14
AC-DC 0 - 2 - 5 00 0- 1
A: Contact material
0 = Standard AgNi 2 = AgCdO 5 = AgNi + Au (5 µm)
B: Contact circuit
0 = CO (nPDT)
Series Typ e
1 = PCB 3 = Plug-in
No. of poles
2 = 2 pole, 10 A 3 = 3 pole, 10 A 4 = 4 pole, 7 A
Coil version
8 = AC (50/60 Hz) 9 = DC
Coil voltage
See coil specifications
3 4 0 09
D: Special versions
0 = Standard 1 = Wash tight (RT III)
for 55.12, 55.13 and 55.14 only
C: Options
0 = None 1 = Lockable test button 2 = Mechanical indicator 3 = LED (AC) 4=
Lockable test button+mechanical indicator 5 = Lockable test button + LED (AC) 54 = Lockable test button + LED (AC)
+ mechanical indicator 6* = Double LED (DC non-polarized) 7* = Lockable test button + double LED
(DC non-polarized) 74* = Lockable test button + double LED
(DC non-polarized)
+ mechanical indicator 8* = LED + diode
(DC, polarity positive to pin A1/13) 9* = Lockable test button + LED + diode (DC,
polarity positive to pin A1/13) 94* = Lockable test button + LED + diode (DC,
polarity positive to pin A1/13)
+ mechanical indicator * Option not available for the 220 V DC version.
4 0
Ordering information
ABCD
... .
01255
Lockable test button and mechanical flag indicator (0010, 0040, 0050, 0054, 0070, 0074, 0090, 0094)
The dual-purpose Finder test button can be used in two ways: Case 1) The plastic pip (located directly above the test button) remains intact. In this case, when the test button is pushed, the contacts operate. When the test button is released the contacts return to their former state. Case 2)
The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in addition to the above function), when the test button is pushed and rotated, the contacts are latched in the operating state, and remain so until the test button is rotated back to its former position. In both cases ensure that the test button actuation is swift and decisive.
55 Series - General purpose relays 7 - 10 A
Selecting features and options: only combinations in the same row are possible. Preferred selections for best availability are shown in bold.
C: Option 3, 5, 54
LED (AC)
C: Option 6, 7, 74
Double LED (DC non-polarized)
C: Option 8, 9, 94
LED + diode (DC, polarity positive to pin A1/13)
Descriptions: options and special versions
1
2
3
Page 3
4
Contact specification
Technical data
55 Series - General purpose relays 7 - 10 A
F 55 - Electrical life (AC) v contact current
2 and 3 pole relays
Cycles
DC voltage (V)
DC breaking current (A)
H 55 - Maximum DC1 breaking capacity
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100·103can be expected.
In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load. Note: the release time for the load will be increased.
F 55 - Electrical life (AC) v contact current
4 pole relay
Cycles
contacts in series
2 & 3 pole current limit
4 pole current limit
Resistive load - cosϕ = 1 Inductive load - cosϕ = 0.4
Resistive load - cosϕ = 1 Inductive load - cosϕ = 0.4
Insulation according to EN 61810-1 2 pole - 3 pole 4 pole
Nominal voltage of supply system V AC 230/400 230 Rated insulation voltage V AC 400 250 Pollution degree 2 2
Insulation between coil and contact set
Type of Insulation Basic Basic Overvoltage category III III Rated impulse voltage kV (1.2/50 µs) 4 4 Dielectric strength V AC 2,000 2,000
Insulation between adjacent contacts
Type of insulation Basic Basic Overvoltage category III II Rated impulse voltage kV (1.2/50 µs) 4 2.5 Dielectric strength V AC 2,000 2,000
Insulation between open contacts
Type of disconnection Micro-disconnection Micro-disconnection Dielectric strength V AC/kV (1.2/50 µs) 1,000/1.5 1,000/1.5
Conducted disturbance immunity
Burst (5...50)ns, 5 kHz, on A1 - A2 EN 61000-4-4 level 4 (4 kV) Surge (1.2/50 µs) on A1 - A2 (differential mode) EN 61000-4-5 level 4 (4 kV)
Other data
Bounce time: NO/NC ms 1/4 Vibration resistance (5…55)Hz: NO/NC g 15/15 Shock resistance g 16 Power lost to the environment without contact current W 1
with rated current W 3 (2 pole) 4 (3 pole) 3 (4 pole)
Recommended distance between relays mounted on PCB mm ≥ 5
Page 4
Nominal Coil Operating range Resistance Rated coil
voltage code
consumption
U
N
U
min
U
max
R I at U
N
VVVΩ mA
6 9.006 4.8 6.6 40 150 12 9.012 9.6 13.2 140 86 24 9.024 19.2 26.4 600 40 48 9.048 38.4 52.8 2,400 20 60 9.060 48 66 4,000 15
110 9.110 88 121 12,500 8.8 125 9.125 100 138 17,300 7.2 220 9.220 176 242 54,000 4
5
Nominal Coil Operating range Resistance Rated coil
voltage code
consumption
U
N
U
min
U
max
R
I at UN(50Hz)
VVVΩ mA
6 8.006 4.8 6.6 12 200 12 8.012 9.6 13.2 50 97 24 8.024 19.2 26.4 190 53 48 8.048 38.4 52.8 770 25 60 8.060 48 66 1,200 21
110 8.110 88 121 4,000 12.5 120 8.120 96 132 4,700 12 230 8.230 184 253 17,000 6 240 8.240 192 264 19,100 5.3
AC coil dataDC coil data
Coil specifications
1 - Max. permitted coil voltage. 2 - Min. pick-up voltage with coil at ambient temperature.
55 Series - General purpose relays 7 - 10 A
Top flange mount adaptor for 55.32, 55.33, 55.34 056.25
Accessories
R 55 - DC coil operating range v ambient temperature R 55 - AC coil operating range v ambient temperature
1 - Max. permitted coil voltage. 2 - Min. pick-up voltage with coil at ambient temperature.
056.25 with relay
056.25
056.27 with relay
056.27
Top 35 mm rail (EN 60715) adaptor for 55.32, 55.33, 55.34 056.27
056.27 with relay
056.26
Rear flange mount adaptor for 55.32, 55.33, 55.34 056.26
056.26 with relay
056.27
056.27 with relay
056.25
056.25 with relay
056.26 056.26 with relay
056.27