finder 48.31, 48.52, 48.72, 48.61, 48.81 User Manual

...
Page 1
1 & 2 Pole relay interface modules,
15.8 mm wide.
Ideal interface for PLC and electronic systems
48.31 - 1 Pole 10 A (screw terminal)
48.52 - 2 Pole 8 A (screw terminal)
48.72 - 2 Pole 8 A (screwless terminal)
AC coils or DC sensitive coils
retaining clip
Supply status indication and EMC coil
suppression module as standard
Identification label
UL Listing (certain relay/socket combinations)
35 mm rail (EN 50022) mounting
48 Series - Relay interface modules 8 - 10 - 16 A
1 CO (SPDT) 2 CO (DPDT)
10/20 8/15
250/400 250/250
2,500 2,000
500 400
0.37 0.3
10/0.3/0.12 8/0.3/0.12
300 (5/5) 300 (5/5)
AgNi AgNi
12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230
12 - 24 - 125 12 - 24 - 125
1.2/0.5 1.2/0.5
(0.8…1.1)U
N
(0.8…1.1)U
N
(0.73…1.75)U
N
(0.73…1.75)U
N
0.8 UN/0.4 U
N
0.8 UN/0.4 U
N
0.2 UN/0.1 U
N
0.2 UN/0.1 U
N
10 · 106/20 · 10
6
10 · 106/20 · 10
6
200 · 10
3
100 · 10
3
7/4 (AC) - 12/12 (DC) 7/4 (AC) - 12/12 (DC)
6 (8 mm) 6 (8 mm)
1,000 1,000
–40…+70 –40…+70
IP 20 IP 20
1 pole, 10 A
Screw terminal
35 mm rail (EN 50022) mounting
2 pole, 8 A
Screw terminal and screwless terminal
35 mm rail (EN 50022) mounting
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220V A
Minimum switching load mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (U
N
) V AC (50/60 Hz)
V DC
Rated power AC/sens. DC VA (50 Hz)/W
Operating range AC
sens. DC
Holding voltage AC/DC
Must drop-out voltage AC/DC
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC1 cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 µs)
kV
Dielectric strength between open contacts V AC
Ambient temperature range °C
Protection category
Approvals relay (according to type)
COM
NO
NC
11
14
12
COM
NO
NC
11
14
12
DCAC
A2
A1
A2
A1
+
21 11
24 14
22 12
COM
NO
NC
21 11
24 14
22 12
COM
NO
NC
DCAC
A2
A1
A2
A1
+
48.31 48.52/72
1
48.31 / 48.52 Screw terminal
48.72 Screwless terminal
For outline drawing see page 5
Features
Page 2
2 CO (DPDT)
10/20
250/400
2,500
500
0.37
10/0.3/0.12
300 (5/5)
AgNi
12 - 24 - 125
—/0.5
(0.8…1.5)U
N
—/0.4 U
N
—/0.1 U
N
—/20 · 10
6
100 · 10
3
12/12 (DC)
6 (8 mm)
1,000
–40…+70
IP 20
2
21 11
24 14
22 12
COM
NO
NC
DC
A2
A1
+
2 pole, 10 A
Screw terminal and screwless terminal
35 mm rail (EN 50022) mounting
48.62/82
1 & 2 Pole relay interface modules,
15.8 mm wide.
Ideal interface for PLC and electronic systems
48.61 - 1 Pole 16 A (screw terminal)
48.81 - 1 Pole 16 A (screwless terminal)
48.62 - 2 Pole 10 A (screw terminal)
48.82 - 2 Pole 10 A (screwless terminal)
AC coils or DC sensitive coils
retaining clip
Supply status indication and EMC coil
suppression module as standard
Identification label
UL Listing (certain relay/socket combinations)
35 mm rail (EN 50022) mounting
48 Series - Relay interface modules 8 - 10 - 16 A
1 CO (SPDT)
16*/30
250/400
4,000
750
0.55
16/0.3/0.12
500 (10/5)
AgCdO
12 - 24 - 110 - 120 - 230
12 - 24 - 125
1.2/0.5
(0.8…1.1)U
N
(0.8…1.5)U
N
0.8 UN/0.4 U
N
0.2 UN/0.1 U
N
10 · 106/20 · 10
6
100 · 10
3
7/4 (AC) - 12/12 (DC)
6 (8 mm)
1,000
–40…+70
IP 20
1 pole, 16 A
Screw terminal and screwless terminal
35 mm rail (EN 50022) mounting
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220V A
Minimum switching load mW (V/mA)
Standard contact material
Coil specification
Nominal voltage (U
N
) V AC (50/60 Hz)
V DC
Rated power AC/sens. DC VA (50 Hz)/W
Operating range AC
sens. DC
Holding voltage AC/DC
Must drop-out voltage AC/DC
Technical data
Mechanical life AC/DC cycles
Electrical life at rated load AC1 cycles
Operate/release time ms
Insulation between coil and contacts (1.2/50 µs)
kV
Dielectric strength between open contacts V AC
Ambient temperature range °C
Protection category
Approvals relay (according to type)
48.61/81
21 11
24 14
22 12
COM
NO
NC
21 11
24 14
22 12
COM
NO
NC
DCAC
A2
A1
A2
A1
+
* For currents >10 A, contact terminals
must be connected in parallel (21 with 11, 24 with 14, 22 with 12).
48.61 / 48.62 Screw terminal
48.81 / 48.82 Screwless terminal
For outline drawing see page 5
Features
Page 3
3
Example: 48 series, 35 mm rail (EN 50022) mount, screw terminal relay interface module, 2 CO (DPDT) 8 A contacts, 24 V sensitive DC coil,
green LED + diode, 99.02 coil indication.
A: Contact material
0 = Standard
B: Contact circuit
0 = CO (nPDT)
Series
Type
Screw terminal
3 = 35 mm rail mount (EN 50022) 5 = 35 mm rail mount (EN 50022) 6 = 35 mm rail mount (EN 50022)
Screwless terminal
7 = 35 mm rail mount (EN50022) 8 = 35 mm rail mount (EN50022)
No. of poles
1 = 1 pole for 48.31, 10 A
48.61,48.81, 16 A
2 = 2 pole for 48.52, 48.72, 8 A
48.62, 48.82, 10 A (48.62, 48.82 DC only)
Coil version
7 = Sensitive DC 8 = AC (50/60 Hz)
Coil voltage
See coil specifications
5 2 0 07
D: Special versions
0 = Standard
C: Options
5 = Standard for DC:
green LED + diode (polarity +A1)
6 = Standard for AC:
green LED + Varistor
5 0
Ordering information
ABCD
... .
02448
Technical data
48 Series - Relay interface modules 8 - 10 - 16 A
Insulation 48.31/61/62 48.52 48.31/61/62
Insulation according to EN 61810-1 insulation rated voltage V 250 250 400
rated impulse withstand voltage kV 4 4 4 pollution degree 3 2 2
overvoltage category III III III Insulation between coil and contacts (1.2/50 µs) kV 6 (8 mm) Dielectric strength between open contacts V AC 1,000 Dielectric strength between adjacent contacts V AC 2,000 (48.52); 2,500 (48.62)
Conducted disturbance immunity
Burst (5...50)ns, 5 kHz, on A1 - A2 EN 61000-4-4 level 4 (4 kV) Surge (1.2/50 µs) on A1 - A2 (differential mode) EN 61000-4-5 level 3 (2 kV)
Other data
Bounce time: NO/NC ms 2/5 Vibration resistance (5…55)Hz: NO/NC g 10/4 (for 1 pole) 15/3 (for 2 pole) Power lost to the environment without contact current W 0.7
with rated current W 1.2 (48.31)
1.3 (48.52/72)
1.2 (48.61/62/81/82)
Wire strip length mm 8
Screw torque Nm 0.5
Max. wire size Screw terminal Screwless terminal
solid cable stranded cable solid cable stranded cable
mm2 1x6 / 2x2.5 1x4 / 2x2.5 2x(0.2...1.5) 2x(0.2...1.5)
AWG 1x10 / 2x14 1x12 / 2x14 2x(24...18) 2x(24...18)
Page 4
4
48 Series - Relay interface modules 8 - 10 - 16 A
1240
16
8
(A)
10
6
10
5
10
7
Cycles
Contact specification
Cycles
F 48 - Electrical life (AC) v contact current
Types 48.31/61/81
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100·103can be expected.
In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load. Note: the release time for the load will be increased.
1240
16
8
(A)
10
6
10
5
10
7
F 48 - Electrical life (AC) v contact current
Types 48.62/82
20 60
100 140 180 220
20
10
6 4
2
1
0.2
0.1
H 48 - Maximum DC1 breaking capacity
Types 48.31/52/61/72/81
DC breaking current (A)
DC voltage (V)
2 contacts in series
single contact
Resistive load - cosϕ = 1 Inductive load- cosϕ = 0.4
Resistive load - cosϕ = 1 Inductive load- cosϕ = 0.4
62
0
8
4
(A)
10
6
10
5
10
7
Cycles
F 48 - Electrical life (AC) v contact current
Types 48.52/72
Resistive load - cosϕ = 1 Inductive load- cosϕ = 0.4
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of ≥ 100·103can be expected.
In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load. Note: the release time for the load will be increased.
20 60
100 140 180 220
20
10
6
4
2
1
0.2
0.1
H 48 - Maximum DC1 breaking capacity
Types 48.62/82
DC breaking current (A)
DC voltage (V)
2 contacts in series
single contact
limit for 48.31
48.61/81 current limit
48.31 current limit
48.52/72 current limit
Page 5
Coil specifications
*U
min
= 0.8 UNfor 48.61, 48.62, 48.81 and 48.82
**U
max
= 1.5 UNfor 48.61, 48.62, 48.81 and 48.82
Combinations
Nominal Coil Operating range Rated coil
voltage code consumption
U
N
U
min
U
max
I at UN(50Hz)
VVVmA
12 8.012 9.6 13.2 90.5
24 8.024 19.2 26.4 46 110 8.110 88 121 10.1 120 8.120 96 132 11.8 230 8.230 184 253 7.0
AC coil data
Nominal Coil Operating range Rated coil
voltage code consumption
U
N
U
min
* U
max
** I at U
N
VVVmA
12 7.012 8.8 21 41 24 7.024 17.5 42 22.2
125 7.125 91 219 4
DC coil data (0.5 W sensitive)
Code Type of socket Type of relay Module Retaining clip
48.31 95.03 40.31 99.02 095.01
48.52 95.05 40.52 99.02 095.01
48.61 95.05 40.61 99.02 095.01
48.62 95.05 44.62 99.02 095.01
48.72 95.55 40.52 99.02 095.91.3
48.81 95.55 40.61 99.02 095.91.3
48.82 95.55 44.62 99.02 095.91.3
48 Series - Relay interface modules 8 - 10 - 16 A
1 - Max. permitted coil voltage. 2 - Min. pick-up voltage with coil at ambient temperature.
60
2.0
-20
1.0
0.5
1.5
04020
U U
N
80
2
1
(°C)
R 48 - DC coil operating range v ambient temperature
60
2.0
-20
1.0
0.5
1.5
04020
U U
N
80
48.61/62/81/82
48.31/52/72
2
1
(°C)
48.61/62/81/82
48.31/52/72
R 48 - DC coil operating range v ambient temperature
1 - Max. permitted coil voltage. 2 - Min. pick-up voltage with coil at ambient temperature.
5
14
21
COM
24
NO
11
12
22
NC
A2
COIL
A1
15.8
95.6
32.5
22.6
30.3 34.7 30.6
73.7
24.6 4 4
1
7
.5
1
7
.5
3
2
2
5
.9
78.6
6
0
.9
7
5
.3
15.8
15.8
48.31 / 48.52 / 48.61 / 48.62 Screw terminal
48.72 / 48.81 / 48.82 Screwless terminal
Outline drawing
Page 6
48 Series - Relay interface modules 8 - 10 - 16 A
095.18
8-way jumper link for screw terminal version 095.18 (blue) 095.18.0 (black) Rated values 10 A - 250 V
060.72
Sheet of marker tags, plastic, 72 tags, 6x12 mm 060.72
Accessories
6
How to code and identify retaining clip and packaging options for sockets.
Example:
Packaging codes
5 2 0 07 5 002448 ASP
A Standard packaging B Blister packaging
SP Plastic retaining clip
....
110.5
5.1
7 3.3
15 1515.815.815.815.815.8
10.3
Loading...