Figaro TGS2611 Application Notes

APPLICATION NOTES FOR TGS2611
Application Notes for Methane Gas Detectors using TGS2611
The TGS2611 methane gas sensor has been presorted into groupings which will allow users to simplify the manufacturing process for methane gas detectors. This brochure offers example application circuits and important technical advice for designing and manufacturing gas detectors which use classified
TGS2611 sensors.
Page
an ISO9001 company
Introduction......................................................................................................2
Detector Circuit Design
Basic Circuit with T emperature Compensation............................................2
Selecting a Load Resistor .................................................................................2
Compensation for Internally Generated Heat..............................................3
Heater Breakage Detection Circuit.........................................................3
Sensor Malfunction Detection Circuit.........................................................3
Prevention of Intermittent Alarming..............................................................4
Alarm Prevention during W armup................................................................4
Alarm Delay Circuit..........................................................................5
Application Circuit...................................................................................5
Manufacturing Process
Handling and Storage of Sensors..........................................................5
L Selection...............................................................................................5
R
PCB Assembly....................................................................................5
Sensor Assembly..................................................................................5
Final Assembly.................................................................................................6
Preheating of Final Assembly.....................................................................6
Gas Test..............................................................................................6
Storage of Finished Products..........................................................................6
Anticipated Performance at 10%LEL of Methane...........................................................6
Pre-calibrated Sensor Module...........................................................................................7
Appendix...............................................................................................................8
See also Technical Brochure ‘Technical Information on Usage of TGS Sensors for Toxic and Explosive Gas Leak Detectors’.
Revised 08/03
IMPORTANT NOTE: OPERATING CONDITIONS IN WHICH FIGARO SENSORS ARE USED WILL VARY WITH EACH CUSTOMER’S SPECIFIC APPLICATIONS. FIGARO STRONGLY RECOMMENDS CONSULTING OUR TECHNICAL STAFF BEFORE DEPLOYING FIGARO SENSORS IN YOUR APPLICATION AND, IN PARTICULAR, WHEN CUSTOMER’S TARGET GASES ARE NOT LISTED HEREIN. FIGARO CANNOT ASSUME ANY RESPONSIBILITY FOR ANY USE OF ITS SENSORS IN A PRODUCT OR APPLICATION FOR WHICH SENSOR HAS NOT BEEN SPECIFICALLY TESTED BY FIGARO.
TGS2611-J00 is a UL recognized component in accordance with the requirements of UL2075. Please note that component recognition testing
has confirmed long term stability in 60ppm of methane; other characteristics shown in this brochure have not been confirmed by UL as part of component recognition.
1
APPLICATION NOTES FOR TGS2611
To facilitate ease in manufacturing gas detectors, both Figaro TGS2611-J00 and TGS2611-B00 methane gas sensors are individually marked with an ID number (see Figure 1) indicating a factory presorted classification which corresponds to narrow ranges of sensor resistance in methane. When the sensor’s ID number is properly used, the calibration process can be greatly simplified, eliminating long preconditioning time and the complicated handling of calibration gas.
1. Detector Circuit Design
1-1 Basic circuit with temperature compensation Figure 2 shows an example of a basic circuit for gas detection, including temperature compen­sation for variations caused by ambient temperature fluctuations. Typical values for the circuit components are as follows:
RL : refer to Table 1 R
TH : 4.7k
Ω (±
3%), B=3977 (±5%) RA : 11.5kΩ (±1%) RB : 4.32kΩ (±1%) RC : 8.25kΩ (±1%)
The values for components related to temperature compensation should be chosen so that Vref is one-half of the Vc value at standard temperature (20˚C). The Vref curve should approximate the temperature dependency curve of the VRL when compensation is properly done.
1-2 Selecting a load resistor (R
L)
To optimize resolution of the output signal at the desired alarming concentration, it is neces­sary to adjust the resistance of the load resistor (RL). It is recommended that RL be selected at a value which is equal to the sensor’s resistance (Rs) at the alarming concentration (i.e. Rs/RL =
1.0). Please refer to the brochure “General Information for TGS Sensors” for more details.
Since the ID number corresponding to sensor resistance in methane gas is indicated on the sensor cap, the load resistor value can be selected according to Table 1. For example, for an alarm setting at 10% LEL, when using a sensor having an ID number of 7, the R
L value should be set at
1.27k. By using the recommended RL, the VRL
value at the alarming point typically will be 2.5V, which is equal to half of the circuit voltage (Vc).
Sensor
code
TGS2611
984AA
TGS2611-J00 TGS2611-B00
Fig. 1 - Sensor markings
Voltage
regulator
78M05
D.C. input
#DI
10679.0517.0095.0115.0
2070.1787.0946.0265.0
3081.1668.0517.0916.0
4003.1359.0787.0186.0
5034.150.1668.0057.0
6085.151.1359.0528.0
7047.172.150.1909.0
8019.104.151.100.1
9001.245.172.101.1
0123.296.104.112.1
1155.278.145.133.1
2108.250.296.174.1
3190.362.278.126.1
4104.394.250.287.1
5147.347.262.269.1
6121.410.394.251.2
7135.423.347.273.2
8199.456.310.316.2
9194.520.423.378.2
0240.624.456.361.3
1256.678.420.484.3
2223.763.524.438.3
3260.809.578.422.4
4278.894.663.546.4
Note: Lower explosion limit (LEL) of methane = 50,000ppm
Vc = 5.0 ± 0.2V
4 1
Fig. 2 - Basic circuit with
temperature compensation
rosneS
Table 1 - Recommended RL by sensor ID
Lot #
#07
ID #
3
2
TGS 2611
R
L
RLk( htiw) ± ecnarelot%1
LEL%5 LEL%01 LEL%51 LEL%02
A
R
B
R
C
R
TGS2611 314AE #07
REF
V
RL
V
TH
R
+
-
Alarm signal (Active = 'L')
Comparator
GND
Revised 08/03
2
APPLICATION NOTES FOR TGS2611
)
1-3 Compensation for internally generated heat Depending on the design of the case and the PCB, there is often a difference between the temperature near the thermistor’s placement in the detector and the ambient temperature. Therefore it is recommended to measure the actual temperature difference between the inside and the outside of the detector and select the value of RC according to Table 2. When RC is selected in this manner and used in the basic circuit (Figure 2), the result would be that Vref=1/2 Vc.
1-4 Heater breakage detection circuit Figure 3 shows an example of how breakage of the sensor’s heater wire and/or heater element can be detected. By adding R
E (3.57Ω±1%) into
the circuit and monitoring VRE, a malfunction can be considered to have occurred when VRE (0.2V typ.) drops to near 0V. Please note that a circuit voltage (Vc) of 5.2V should be applied to a circuit which incorporates a heater malfunction detection circuit.
∆∆∆∆∆ )C˚(T
k(cR )
052.8
586.7
0151.7
5156.6
0243.6
T= (temp near themistor)-(temp outside detector)
Table 2 - Effect on selection of Rc by temperature
differential inside and outside of detector
Vc=5.2V
78M05
Heater breakage
signal
(Active = 'L')
GND
56mA (typ.)
R
0.05~0.1V
E
0.2V (typ.
+
-
1-5 Sensor malfunction detection circuit Breakage of lead wires to the sensor’s electrodes and/or sensor element can be detected by using a circuit such as that shown in Figure 4. This involves replacing R
C with RC1 and RC2, selecting
their values so that RC1/RC235. Since VRL is
normally greater than 70mV in any atmospheric conditions, by comparing VRL to a reference voltage of 70mV, breakage of the lead wires and/ or sensor element can be considered to have occurred if VRL drops below 70mV.
Figure 3 - Heater breakage detection circuit
C
V
C1
R
C2
R
Figure 4 - Sensor malfunction detection circuit
(RE = 3.57Ω±1%)
A
R
B
R
70mV (typ.)
TH
R
REF
V
+
RL
V
(RC1/RC2 35)
-
Sensor breakage
signal
(Active = 'L')
GND
Revised 08/03
3
Loading...
+ 5 hidden pages