Fiessler ESPE Type 4 Operating Instructions Manual

Fiessler Elektronik Kastellstr. 9 D 73734 Esslingen
Telefon: +49 711 / 91 96 97-0 Internet: http://www.fiessler.de Telefax: +49 711 / 91 96 97-50 eMail: info@fiessler.de
Infrared accident prevention safety curtains, ESPE Type 4
ULVT
Operating Instructions
ns
FIESSLER
E L E K T R O N I K
Optional
Barring from hazardous areas
Cordoning off areas
Restricting access to areas
Restricting access to areas via tilted mirrors
DIN EN ISO 9001
Reg.Nr. 96007
For over 40 years,
we have proved to be specialists in the area of optoelectronics. Our experience is your gain. Tell us your problems, and we will be pleased to advise you
2
FIESSLER
ELEKTRONIK
BA - ULVT
Section Contents Page
1 Safety Instructions 5
2 Prerequisites for the use of safety light barriers 6
Standards and application guidelines
3 System description and application areas 7
3.1 Features 7
3.2 Application areas 7
3.3 Structure 8
3.4 Function 8
3.5 LED displays 8
3.6 Operating modes (with/without restart interlock, with/without contactor check, equivalent/antivalent outputs) 9
4 Installation 10
4.1 Safe distances from hazardous areas 10
4.1.1 - Vertical protection for hazardous areas 10
4.1.2 - Horizontal protection for hazardous areas 11
4.2 Construction requirements 12
4.2.1 - Installation without additional screening 12
4.2.2 - Protection against reaching over or under barriers 12
4.2.3 - Protection against avoiding barriers through cascading or additional screening 12
4.2.4 - Distance from reflective surfaces 13
4.2.5 - Arrangement of two safety light barriers 13
4.3 Attachment of transmitters and receivers - Mounting and adjustment 14
4.4 Option: Multi-sided screening through tilted mirrors 15
4.5 Option: Assembly columns 15
5 Electric connection 17
5.1 Integrated connector plug 17
5.2 Electric connection ratings 17
5.3 Connectors 17
5.4 Connection examples 18
6 Commissioning 19
6.1 Commissioning 19
6.2 Adjustment instructions 19
6.3 Troubleshooting 20
7 Additional functions with safety switchgears 21
7.1 LSUW N1 Muting K switchgear - Muting (temporary bridging) 21
7.1.1 - Muting function with four muting sensors and time-out 22
7.1.2 - Muting function with four muting sensors without time-out 23
7.2 LSUW NSR 3-1 K switchgear (operating modes "B" and "C" only with system changeover from LSUW to ULVT) 24
7.2.1 - Cycle mode 24
7.2.2 - Safety mode with restart interlock "B" (only with system changeover from LSUW to ULVT) 25
7.2.3 Selection mode (between cycle and safety mode with restart interlock, switchover mode) 26
7.2.4 - Safety mode with restart interlock during dangerous movement "B1" only 27
7.2.5 - Safety mode without restart interlock with valve or contactor check "C" (only when changing system) 28
7.3 ULSG switchgear (potential-free switching contacts and universal power supply) 29
8 Terminology 30
9 Specifications 32
10 Dimensions drawing 34
11 Accessories 37
3
FIESSLER
ELEKTRONIK
Table of Contents
BA - ULVT
4
FIESSLER
ELEKTRONIK
BA - ULVT
All safety instructions are marked with this symbol and must be observed under all circumstances.
These operating instructions provide the user with important information concerning the proper use of the ULVT safety light barriers. The instructions are supplied with each light barrier and must be retained at the installation site of the light barrier.
All specifications of these operating instructions must be observed at all times.
Currently effective conditions and the regulations of the trade associations must also be adhered to. The operating instructions must be read before using the ULVT ... safety light barriers.
Qualified personnel
Installation, commissioning and maintenance must only be carried out by qualified personnel.
Danger sign
When operating a machine with ULVT ... safety light barriers, it must be ensured that nobody is located within a hazardous area. A danger sign to this effect must be attached to the machine.
Protect light barriers against flying objects resulting from the operation of the machine.
Caution, daily inspection (after 24 hours at the latest):
Before the start of a shift, the light barrier must be checked as follows: Using the test rod*, the light barrier is to be interrupted on the transmitting side from start to finish in such a way that the light field is only covered by this part. The green LED (or the yellow LED in the operating mode with restart interlock) must not light up from start to finish. * The diameter of the test rod must correspond to the obstacle size specified on the nameplate of the receiving side.
5
FIESSLER
ELEKTRONIK
The safe operation of the entire system can only be ensured through adherence to these operating instructions and the corresponding accident prevention regulations. These operating instructions comprise part of the light barrier and must be retained at the installation site.
Safety Instructions Please observe
BA - ULVT
When using safety light barriers, the effective standards and guidelines must be observed! (The local authorities or
trade associations will provide you with the relevant information.
On request by the customer, the Fiessler Elektronik company will carry out the initial approval and annual inspection. In addition, customer-training seminars concerning the implementation of the annual inspection are held at regular intervals.
6
FIESSLER
ELEKTRONIK
2 Prerequisites for the use of safety light barriers
- The unintentional repetition of a hazardous movement must be prevented by the appropriate safety facilities.
- The safety category (Type 4) of the accident-prevention light barrier should be at least the same as safety category of the machine.
- Approval:
Approval of the construction and the tests should be carried out by competent personnel who are in possession of all information provided by the supplier of the machine and the BWS.
- Annual inspection:
The operator must ensure that a competent person is assigned the task of inspecting the light barrier on a yearly basis. This person may, for example, comprise an employee of the light barrier manufacturer or of the operator.
BA - ULVT
- It must be possible for the hazardous condition of a machine to be eliminated by the sensor function.
- The safety distance between the protective field and the hazardous area must be large enough to ensure that when penetrating the protective field, the hazardous areas cannot be reached before the hazardous movement is interrupted or ended.
- Access to the hazardous area must only be possible through the protective field (reaching under, over or around the field must not be possible.
- Passing through the light barrier must only be possible if the restart interlock is activated subsequent to the light barrier being interrupted. A new command to activate the next hazardous movement must only be implemented via a dead-man switch. It must not be possible for this start button to be actuated from within the hazardous area: The switch must be located at a point from which the accessible area can be viewed without obstruction.
FIESSLER
ELEKTRONIK
3.1 Features
The ULVT safety light barriers are photo-electric guards and are characterized by the following:
- Safety category 4 pursuant to EN 954-1 and IEC 61496 Part 1 + 2, and/or EN 61496
- Integrated switchgear, contactor check and restart interlock activated via DIP switch
- Direct connection of contactors / valves, switching capacity of 0.5 A / 24 V
- Smallest safety distance through short response times: 6 ms to 25 ms, depending on construction length
- Detection of smallest obstacles from range of 14 mm / 30mm to 7 m /24 m
- 13 to 247 beams at protective field heights of 100 mm to 1900 mm
- Microprocessor monitoring of the safety functions
- Reverse-read semi-conductor outputs with line interruption, short-circuit and cross-circuit monitoring
- Integrated self-diagnostics with fault indication
- Muting and cycle mode with optional safety switchgear
- Protection category IP 65
3.2 Application areas
The ULVT safety light barriers are designed to protect hazardous areas, cordon off areas, and prevent access. Protection of fingers, hands and body, for example in
- Presses for the processing of metal, wood, plastic, rubber, leather and glass
- Filter presses
- Folding and bending machines
- Injection moulding machines
- Processing centres and welding presses
- Automatic placement machines
- Robots
- Palletizing machines
Using tilted mirrors, the protective field can be "wrapped around" a hazardous area, thus ensuring protection from several sides
(Fig. 7/4).
7
Fig. 7/1 Protecting in hazardous areas
Fig. 7/2 Cordoning off areas
Fig. 7/3 Restricting access to areas
3 Features
Fig 7/4 Restricting access to areas via tilted mirrors
BA - ULVT
FIESSLER
ELEKTRONIK
8
3.3 Structure
The ULVT safety light barriers consist of two components: The light transmitter and receiver. The distance between the two components and the installation height are calculated from the width and height of the protective field (Fig. 8/1).
Due to its modular structure, protective field heights between 100 mm and 1900 mm can be attained (Table 8/1). Special sizes can be implemented for installation-dependent dimensions. The transmitter and receiver and synchronous, i.e., at any one time, only one light beam and one receiving element are active. Synchronization is implemented by the first light beam and first receiving element. An electric connection between the transmitter and receiver is therefore not required.
3.4 Function
The transmitter generates infrared light beams which are switched on an off in quick succession. The parallel light beams at a distance of 7.5 mm are assessed by two single-chip microcontrollers. The beam distance produces a definition of 14 mm.
If an object is located within the protective field, i.e., at least one of the light beams is blacked out, the two outputs of the receiver will stop the hazardous movement of the machine and/or prevent a start. In the operating mode with restart interlock, the machine can only be restarted by actuating the start button when the protective field is free again.
3.5 LED displays
Several LEDs on the receiver indicate the current operating status (Fig. 8/3). If the system test detects an internal or external fault, the machine will be switched off immediately and the LEDs on the transmitter and/or receiver indicate the fault status to the user. Self-diagnostics system: A fault diagnostics program is available for trained service personnel. This program provides precise and on-site localization of the fault. When a fault is present, the flashing LEDs together with a fault code provide visual output of the detected fault and display in the diagnostics device.
3 System description and application areas
Fig. 8/1 The transmitter and receiver form the protective field
Table 8/1 Standard construction sizes
Fig. 8/3 LEDs indicate the operating and/or fault status
Test rod dia. = Obstacle size
Protective field width
Protective field height
Transmitter
Receiver
Yellow ON Transmitter active Yellow OFF Transmitter off Yellow flashing Fault
Green ON Light barrier free Red ON Light bar.interrupted
Orange ON
Contamination (no reserve)
Yellow ON Start prompt Orange flashing Fault Yellow flashing Fault
Sender ein
Transmitter on
123
ULVT Send
er
TÜV Rheinland
AA
AA
Made in Germany
D-73734 Esslingen, Kastellstr.9 0711/3 45 19 44
ULVT Transmitter/Emetteur
BWS Typ4, ESPE Type4, ESPS Type4
Emetteur en marche
ULVTE Em fänger
Made in Germany
D-73734 Esslingen, Kastellstr.9 0711/91 96 97 -0
1234567
3:OSSD2
6: 0V
5:
2: EDM
7: 24VDC
±20%
4: OSSD1
1: Start
ULVT Receiver/Récepteur
interdiction de redŽmarrage
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
BWS Typ4, ESPE Type4 , ESPS Type4
Wiederanlauf
Justierhilfe
LS
LS frei
unterbrochen
sperre
Fig 8/2 Dimensions
26 mm
11 mm
59 mm
40 mm
61 mm
ULVTE Empfänger
Made in Germany
D-73734 Esslingen, Kastellstr.9 0711/91 96 97 -0
1234567
3:OSSD2
6: 0V
5:
2: EDM
7: 24VDC
±20%
4: OSSD1
1: Start
ULVT Receiver/Récepteur
interdiction de redŽmarrage
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
BWS Typ4, ESPE Type4 , ESPS Type4
FIESSLER
Wiederanlauf
Justierhilfe
LS
LS frei
unterbrochen
sperre
E L E K T R O N I K
Protective field height
Construction length L
BA - ULVT
Protective
field height
(mm)
SH
Construc-
tion length
(mm)
BL
Order data
smallest
obstacle
14mm
reaction
time (ms)
14mm
Order data
smallest
obstacle
30mm
reaction
time
(ms)
30mm
100 196 ULVT100 /13 6 ULVT100 /7 5
200 296 ULVT200 / 26 7 ULVT200 / 14 6
300 396 ULVT300 / 39 8 ULVT300 / 21 6
400 496 ULVT400 / 52 9 ULVT400 / 28 7
500 596 ULVT500 / 65 10 ULVT500 / 35 7
600 696 ULVT600 / 78 11 ULVT600 / 42 8 700 796 ULVT700 / 91 12 ULVT700 / 47 9 800 896 ULVT800 / 104 13 ULVT800 / 56 9
900 996 ULVT900 / 117 14 ULVT900 / 63 10
1000 1096 ULVT1000 / 130 15 ULVT1000 / 70 10 1100 1196 ULVT1100 / 143 17 ULVT1100 / 77 11 1200 1296 ULVT1200 / 156 18 ULVT1200 /84 12 1300 1396 ULVT1300 / 169 19 ULVT1300 / 91 12
1400 1496 ULVT1400 / 182 20 ULVT1400 / 98 13
1500 1596 ULVT1500 / 195 21 ULVT1500 / 105 13
1600 1696 ULVT1600 / 208 22 ULVT1600 / 112 14
1700 1796 ULVT1700 / 221 23 ULVT1700 / 119 15 1800 1896 ULVT1800 / 234 24 ULVT1800 / 126 15 1900 1996 ULVT1900 / 247 25 ULVT1900 / 133 16
FIESSLER
ELEKTRONIK
9
3.6 Operating modes
The DIP switches in the connector cover enable the following operating modes to be selected:
- Safety mode with / without restart interlock
- With / without contactor check
- equivalent / antivalent outputs
(Fig. 9/1)
In the condition when delivered, the preset operating mode comprises safety mode with restart interlock, contactor check and equivalent outputs.
The following operating modes can be set:
Caution! The operating mode may only be selected when no voltage is present. If the DIP switches are actuated during operation, the light barrier will switch off the outputs and go to locking status. This is indicated by flashing of the yellow and orange LEDs. Locking status will only be ended once the power supply has been switched off.
The switchgears ULSG, LSUW NSR 3-1-K and LSUW N1-Muting K are available for additional functions such as potential-free output contacts or muting (Refer to Section 7 for further information and electric connection).
FIESSLER
E L E K T R O N I K
Typ: ULSG 230V
TÜV Rheinland
AA
AA
2311819 14 12 15 13 17 16 21 20
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 970
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
Nr./Baujahr No./year of construction No./année de fabrication .................................
Ansprechzeit response time temps de réponse 20 mS Temp. temp. temp. -10… + 55 °C Schutzart enclosure rating degré de protection IP 20 Versorgung supply voltage tension d'alimentation 230 VAC -15% +10 %, 50Hz Kontaktbel. contact max. charge contact maxi. 2 A, 250 VAC
Made in Germany
SK230V 115V 24V - +LS -LS A1 A2N
Without contactor check With contactor check
The operating mode with contactor check serves to monitor the driven succeeding contactors.
After each interruption of the light path and before each release of the switching outputs, it is checked whether the succeeding contactors have fallen. Only then will a new release be possible. If the contactors do not respond within 300 ms, the light barrier switches off the outputs and goes into locking status.
Without restart interlock With restart interlock
With the operating mode with restart interlock selected, a button must be connected to the start button input for a start release of the operating movement.
When the protective field is free, the yellow LED lights up on the receiver as a start prompt. Only once the start button has been pressed will the outputs of the ULVT be switched to active.
Equivalent outputs Antivalent outputs
In the equivalent outputs operating mode, both PNP outputs are failsafe and monitored internally for short-circuits and cross-circuits. With a free light path, both outputs are high (+24 V). In the antiva­lent outputs operating mode, output 1 is high (+24 V) and output 2 low (0 V) when the light path is free. Output 2 is not failsafe in this operating mode. This operating mode is only permissible in conjunction with the safety switchgears LSUW NSR 3-1K, LSUW N1-Muting K, or another safe sequential phase control device which monitors output 2!
3 System description and application areas
Fig. 9/1 The operating modes can be
set using the DIP switches. The condition when delivered is shown here.
6
A
1
2
3
7
4
5
8
10
9
17
B
C
12
13
14
15
16
18
19
20
21
22
D
11
FIESSLER
E L E K T R O N I K
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
LSUW NSR 3-1 K
No./year of construction response time
t
emp. enclosure rating supply voltage contact max
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
.................................
30 mS
-10… + 55 °C IP 20 230 VAC -15% +10 %, 50Hz 2 A, 250 VAC
Netz
tension
power
LS Frei
BS libre
LC free
output interupted
sortie interrompue
Ausgang unterbrochen
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
LS unterbrochen
BS interrompue
LC interrupted
Made in Germany
TÜV Rheinland
AA
AA
TÜV Rheinland
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
123456
off
123456
off
123456
off
123456
off
123456
off
123456
off
123456
off
11 142 65341 1715 20 21 22 D79 1210 B CA
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
LSUW N1 Muti
ng
No./year of construction response time
t
emp. enclosure rating supply voltage contact max
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
Net
z tension
power
LS Frei
BS libre
LC free
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
LS unterbrochen
BS interrompue
LC interrupted
Made in Germany
TÜV Rheinland
.................................
30 mS
-10… + 55 °C IP 20 230 VAC -15% +10 %, 50Hz 2 A, 250 VAC
LC muted
BS desaktiveéLS gebrückt
Achtung Vor Abziehen der Klemmleiste Netzspannun
g
abschalte
n
A
ttention
Turn off the supply voltage !
Attention Couper l'alimentation !
Safety switchgear Additional function
ULSG LSUW NSR 3-1-K LSUW N1 Muting K
Muting (bridging)
X
Cycle mode - safety and control mode for
cyclic penetration of the protective field (with either 1-cycle or 2-cycle mode
X
Potential-free output contacts
X X X
Selection mode
(connection for mode selection switch)
X
Start interlock
X X
Safety mode with restart interlock only during the operating movement
X
BA - ULVT
FIESSLER
ELEKTRONIK
10
4.1 Safe distance from hazardous area
The safe distance (S) between the accident-preventing light barrier and hazardous area must be big enough to ensure that when
the protective field is penetrated, the hazardous area cannot be accessed before the hazardous movement has been ended. In addition, it must be ensured that reaching over, under or around, or walking behind the protective field is prevented by additional mechanical screening or further light barriers. To this end, please also refer to EN 999 and
other effective national and international safety regulations.
4.1.1 Vertical light barrier protection of hazardous areas
The safe distance S is calculated as follows:
- K = Grabbing speed or approach speed For the grabbing speed K, a speed of 2000 mm/s is preset. If the calculation
for S produces a value greater than 500 mm, the calculation can be repeated with 1600mm/s if this does not lead to a value lower than 500 mm (smin > 100 mm)
- T = t1 + t2 t1 = Response time of the safety device t2 = Run-on time of the machine
With ULVT light barriers, the response time of the safety
device t1 depends on the number of beams (refer to Table 10/1).
When using the ULVT with the optional safety
switchgears, the response time of the switchgears is added to t1:
For LSUW N1 Muting switchgear: 20 ms For LSUW NSR 3-1K switchgear: 25 ms For ULSG switchgear: 6 ms
The run-on time of the machine t2 must be specified by the machine manufacturer.
- C = 8 (d - 14 mm) d = Definition of the safety device (minimum detectable obstacle size) The definition capacity d ( = 14 mm or 30mm) is specified on the nameplate of the ULVT light barrier,
for d =14mm => C=0, for d= 30 0> C= 128mm
Calculation examples for the safe distance with vertical area protection using ULVT light barriers
Example 1:
ULVT100/13 safety light barrier Run-on time t2 of the machine from 75 ms
S = 2000 mm/s x (0.075s + 0.006s) S = 162 mm
Example 2:
ULVT500/35 safety light barrier ULSG safety switchgear Run-on time t2 of the machine from 75 ms
S = 2000 mm/s x (0.075s + 0.007s + 0.006s) +8(30mm-14mm) S = 304 mm
Table 10/1 Response time t1 of the ULVT light barriers (standard form factors)
S
Nachlaufweg der Maschine
4 Installation - Safe distances
S = (K x T) + C
Fig. 10/1 Vertical protection of hazardous areas
For S = 100 mm to 500 mm: For S > 500 mm:
S = (2000 mm / s . T)
S = (1600 mm / s . T)
BA - ULVT
Run-on path of the machine
Protective field
height / no of
smallest
obstacle
14mm
reaction
time
(ms)
14mm
Protective field
height / no of
smallest
obstacle
30mm
reaction
time
(ms)
30mm
ULVT100 /13 6 ULVT100 /7 5 ULVT200 / 26 7 ULVT200 / 14 6 ULVT300 / 39 8 ULVT300 / 21 6 ULVT400 / 52 9 ULVT400 / 28 7 ULVT500 / 65 10 ULVT500 / 35 7 ULVT600 / 78 11 ULVT600 / 42 8 ULVT700 / 91 12 ULVT700 / 47 9
ULVT800 / 104 13 ULVT800 / 56 9
ULVT900 / 117 14 ULVT900 / 63 10 ULVT1000 / 130 15 ULVT1000 / 70 10 ULVT1100 / 143 17 ULVT1100 / 77 11 ULVT1200 / 156 18 ULVT1200 /84 12 ULVT1300 / 169 19 ULVT1300 / 91 12 ULVT1400 / 182 20 ULVT1400 / 98 13 ULVT1500 / 195 21 ULVT1500 / 105 13 ULVT1600 / 208 22 ULVT1600 / 112 14 ULVT1700 / 221 23 ULVT1700 / 119 15 ULVT1800 / 234 24 ULVT1800 / 126 15 ULVT1900 / 247 25 ULVT1900 / 133 16
4.2 Horizontal protection of hazardous areas
FIESSLER
ELEKTRONIK
11
4 Installation - Safe distances
Calculation examples for the safe distance with horizontal protection of hazardous areas using ULVT light barrier:
Example: ULVT1200/156 light barrier Response time t1 of light barrier: 18 ms Run-on time t2 of machine: 50 ms H = 200 mm
The safe distance is:
S = (1600 mm / s x (0.050 s + 0.018)) +
(1200 mm - 0.4 x 200 mm)
S = 1229 mm
With the ULVT 1200/156, the protective field depth is 1200 mm. A distance a between protective field and machine of 53 mm provides a safe distance
S = 1253 mm
Formula for calculating the safe distance with horizontal protection of hazardous areas using a light barrier:
Here: K = 1600 mm/s C = 1200mm-0.4H, but smaller than 850
mm, whereby H is the height in mm of the protective field above the reference level, e.g. floor.
With a height of the protective field above the floor of > 300 mm, a risk of crawling under exists. This must be considered in risk assessment.
The following condition thus applies for H 300 mm:
1200 - 0.4 x H > 850 mm
The distance a of the end of the protective field (last beam to front edge of hazardous area) must be no more than:
Example: Height 200 mm
a = 200 / 15 + 40 mm a = 53 mm
S = (1600 mm / s x T) + (1200 mm - 0,4 H)
a = H / 15 + 40 mm
S = Safe distance
Start of protective field (first beam) to front edge of hazardous area
H
Front edge of hazardous area
H = Height of protective field to reference level
S = (K x T) + C
a = Distance from last beam of protective
field to front edge of hazardous area
S
a
BA - ULVT
4.2.1 Installation without additional screening
The light transmitter (a) (Fig. 12/1) and the light receiver (b) form the light barrier (c). If the light beams are interrupted, e.g. by a hand, a pilot circuit is opened and the closing action is prevented / stopped. In the opposite example, it is not possible to avoid the ULVT light barrier from the working side, which means that additional screening is not required.
In order to prevent the walking behind the protective field, the distance between the ULVT safety light barrier and the machine must be _< 75 mm.
4.2.2 Protection against reaching under and over
In a normal working process (Fig. 12/2a), the operator inserts the workpiece when sitting down. Due to the run-on time of the machine, the ULVT safety light barrier (a) is mounted slightly in
front of the hazardous area (
refer to Section 4.1). However, the light barrier height selected here leaves an unprotected
gap at the top of the light barrier. Fig. 12/2b shows how reaching over the light barrier can lead to an accident. The proper rectification of this problem is illustrated in Fig.
12/2c, where a ULVT safety light barrier with a larger
protective field height has been attached.
FIESSLER
ELEKTRONIK
12
4 Installation - Construction requirements
Fig. 12/1 Installation without additional screening
Fig. 12/2a.b.c Protection against reaching under or over.
12/2.a
12/2.b 12/2.c
If the distance between the vertical ULVT safety light barrier and the machine needs to be greater than 75 mm (e.g. in order to maintain
the safe distance to the hazardous area), the possibility of walking behind the protective field must be eliminated through an additional ULVT safety light barrier and/or cascading of two light barriers (
Fig. 12/3 and 12/4) or a
protective bar.
Fig. 12/3 Protection against walking behind through cascading of two light barriers
In cascading, varying form factors can becombined (e.g. main sensor with 1100 mm protective field height and succeeding sensor with 200 mm protective field).
When combining main and succeeding sensors, the max. beam number of 247 must be ob­served
The main and succeeding sensors are supplied with premanufactured connecting cable.
interdiction de
redŽmarrage
ULVT
Empfänger
7654321
1. 24V±20%
2. 0V
3. PE
4. A1
5. A2
6. Schützhilfsöffner
7. Start-Taster
ULVT Receiver/Récepteur
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
BWS Typ4, ESPE Type4 , ESPS Type4
FIESSLER
E L E K T R O N I K
unterbrochen
sperre
Fig. 1274 Cascading of two safety light barriers
BA - ULVT
Wrong! Right!
4.2.3 Protection against walking behind through cascading or additional screening
Wrong!
Right!
4.2.4 Distance from reflective surfaces To prevent the avoidance and non­detection of an obstacle due to
reflecting objects, the ULVT safety light barrier must be assembled with a minimum distance a (
Fig. 13/1) from the
reflective object.
The minimum distance a can be established from the table:
4.2.5 Arrangement of two ULVT... safety light barriers
To eliminate the mutual clashing of two ULVT... safety light barriers, the following must be observed when arranging two light barriers
:
FIESSLER
ELEKTRONIK
13
Installation range in m Up to 3 4567 Distance a in mm 130 175 219 262 306
Empfänger
SenderEmpfänger
AAAAAA
A
SenderEmpfänger
Sender
Empfänger
SenderEmpfänger
Sender
Empfänger
Sender
4 Installation - Construction requirements
Fig. 13/1 Distance from reflective surfaces
Fig. 13/2 Arrangement of 2 light barriers
AAAAAAAAAAAAAAAAAAA
A
max. 5
o
a
max. 5
o
Hazardous area
Reflective object (e.g. container)
ULVT receiver
ULVT transmitter
Approach direction
Interrupted beam
Central beam
Container
BA - ULVT
Receiver Transmitter
Receiver Transmitter
Receiver Transmitter
Transmitter Receiver
Receiver Transmitter
Receiver Transmitter
4.3 Installation of transmitter and receiver
When installing the transmitter and receiver, it must be ensured that connectors of both devices are located on the same side. The receiver and transmitter must be installed with parallel faces.
Attachment and adjustment
The supplied fastening brackets serve the attachment and adjustment of the light barrier. Together with the shifting tenon blocks, the latches enable a universal attachment. The swivel the longitudinal axis, turn the respective adjusting screw on one of the fastening brackets whilst both screws on the other fastening bracket are loose. To swivel the lateral axis, turn both screws of a fastening bracket at the same time whilst both screws on the other fastening bracket are loose.
Rubber-metal connection
In the event of intense vibrations, please use rubber-metal connections which can be obtained as optional accessories.
Wall mounting example
FIESSLER
ELEKTRONIK
djusting screws with counter nuts for swivelling along longitudinal and lateral axes.
Further adjustment information is provided in Section 6, "Commissioning".
Bore dia.: 7 mm for attachment of light barrier
4 Installation - Installation of transmitter and receiver
M6 x 15 DIN 912
50 x20 x 2
A
A
A
A
A
A
A
40 X 90 x 6
40 X 90 x 6
50 x20 x 2
M8 DIN 912 M8 DIN 127
M6 DIN 934 M6 DIN 127
Longitudinal axis
Lateral axis
Fig. 14/1 Installation with parallel faces
Fig. 14/2 Swivelling along longitudinal and lateral axis
Depends on run­on time of machine
Machine
Important:
In order to ensure error-free operation, both the light transmitter and light receiver
must attached to stable, distortion-free and face-parallel constructions. Install the fastening brackets so that the adjusting screws remain easily accessible. Make sure that the shape is not distorted. Otherwise a perfect visual adjustment will not be possible. Adjust one fastening bracket whilst the adjusting screws on the other fastening bracket are loose.
BA - ULVT
14
4.4 Multi-sided screening through tilted mirrors
Using tilted mirrors, the protective field can be "wrapped around" a hazardous area, thus providing protection from several sides (Fig. 15/1 and Fig. 15/2). Here, the law of reflection applies, whereby the angle of incidence is the same as the angle of reflection. This means for that tilting of 90° requires the mirror to be installed at an angle of 45°. For this purpose, the tilted mirrors for ULVT feature swivelling attachments.
Reflection loss: Each reflection via a mirror weakens the transmitted signal. For this reason, the max. range and number of
mirror reflections must be observed when using mirrors. The transmitter, receiver and mirrors must always be assembled vertically and checked using a spirit level.
Operational reliability can only be ensured when the mirrors are assembled in a stable manner. Refer to Section 6 for precise adjusting information.
4.5 Assembly columns
For installation in an open area (e.g. for the multi-sided protection of hazardous areas), the ULVT light barriers and titled mirrors can supplied as premanufactured assembly columns.
FIESSLER
ELEKTRONIK
15
4 Installation - Operation via tilted mirrors
Column for ULVT and mirrors
Elongated assembly slot for M12
Top cover (mirror)
Front and top lid (transmitter, receiver)
4 adjusting screws for assembly column
BA - ULVT
Base plate as drilling template for M12 base attachment and for supporting the adjusting screws
Fig. 15/1 Arrangement of 2 tilted mirrors
Fig. 15/2 Arrangement of 1 tilted mirror
Mirror
Mirror
Receiver
Receiver
Mirror
Transmitter
Transmitter
Hazardous area Hazardous area
Fig. 15/3 Assembly columns for light barrier and mirrors
Installation of the columns
1. Provide electric connection of transmitter and receiver
2. Optically align the transmitter, receiver and mirrors
3. Check for correct function
4. Drill the holes and attach the columns The transmitter, receiver and mirror columns are
attached horizontally at the same height. A precise spirit level must be used to check this. With vertical arrangement, the 4 adjusting screws are used on the respective posts. The columns can be rotated using the elongated assembly slots. In addition, the mirror can be rotated by loosening the M8 hexagon nut on the connecting rod located below the top cover. The supplied black base plate assists the fitter in drilling the M12 holes in the floor for the columns. It must be ensured that the columns are aligned as shown in the opposite drawing.
Fine tuning is carried out as described in Section 6, "Commissioning". The front and top covers must be removed for this purpose. The front cover must be reattached once assembly and adjustment has been completed.
FIESSLER
ELEKTRONIK
16
A
A
A
AA
90o
4 Installation - Assembly columns
Fig. 16/3 Installation of the columns
140
1250
10
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
AA
A
110
R7
M8
27
30
200
200
140
1250
10
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
AAA
A
110
200
DIN 970-M8
DIN 970-M8
Fig. 16/1 Assembly column with ULVT light barrier Fig. 16/2 Assembly column with mirrors
BA - ULVT
5.1 Integrated connector plug
The ULVT construction series is supplied with PG threaded joints as standard. Various conventional connector plugs can also be obtained as optional accessories.
The electric connection is implemented via terminal screws in the connector cover (Fig. 17/1). The cover can be removed once the 4 screws have been loosened.
The transmitter and receiver require a power supply of 24 V DC. The ULSG switchgear performs the power failure bridging of 20 ms pursuant to EN 60204 and is thus suitable as the power supply for ULVT light barriers. The receiver is equipped with 2 inputs and 2 outputs. The transmitter is connected via one 3-pin cable and the receiver via one 5 to 7-pin cable (depending on operating mode). The permissible cable cross-section is max. 1.5 mm2. The cables must be routed separately from power lines.
5.2 Electric connection ratings
5.3 Connectors
- Outputs 1 and 2 (OSSD 1 and OSSD 2) The outputs are not potential-free and must not be switched in series or parallel, but must be connected and processed separately! In the operating mode with
equivalent outputs
, both PNP outputs are failsafe and feature internal short-circuit and cross-circuit monitoring. Both outputs are high (+24 V) when the light path is free. In the operating mode with
antivalent outputs
, output 1 is high (+24 V)
and output 2 low (0 V) when the light path is free. Output 2 is not failsafe
in this operating mode. This operating mode is only permissible in conjunction with the safety switchgears LSUW NSR 3-1K, LSUW N1­Muting K, or another safe sequential phase control device which monitors output 2!
- Input contactor check (EDM) If the operating mode with
contactor check
is set, the auxiliary contacts k1 and k2 of the driven contactors k1 and k2 must be connected to the contactor check input in series and with +24 V as shown in Fig. 17/2. The OSSD1 and OSSD 2 of the ULVT will only switch on the two contactors when contactor check input has detected the idle status of the contactors (+24 V at contactor check input). Once the contactors have been driven, both of them must respond within 300 ms. The two auxiliary contacts must then be open (0 V at contactor check input). If the operating mode
without contactor check
is set, the input
contactor check must be unoccupied.
FIESSLER
ELEKTRONIK
17
5 Electric connection - Connection of receiver and transmitter
The electric connection must only be carried out when no voltage is present.
ULVTS transmitter ULVTE receiver
Power supply 24 V DC, + 20% - 10%, SELV 24 V DC, ±20%, SELV Current draw max. 250 mA max. 250 mA (without load)
Outputs -
OSSD 1 and 2
: Failsafe PNP outputs,
max. 0.5 A, short-circuit and cross-circuit monitoring (in
operating mode with
antivalent outputs
, output 2 is a non
-
failsafe PNP output, max 20 mA
)
Inputs -
Inputs contactor check and start button:
0 V to 24 V DC _+ 20%, 10 mA
Electric connection
Integrated connector plug with PG9 as strain relief,
alternatively conventional connector plug.
Integrated connector plug with PG9 as strain relief,
alternatively conventional connector plug.
Connecting cable 3-pin max. 1.5 mm2 5 to 7-pin (depending on operating mode) max. 1.5 mm2 Protection category IP 65 IP 65
OSSD 2
OSSD 1
3
4
7
+24V DC±20%
0V
6
K 1 K 2
Fig. 17/2 Outputs 1 and 2
0V
7
2
+24V DC±20%
Eingang Schützkontrolle
6
Hilfsöffner k1
Hilfsöffner k2
Fig. 17/3 Input contactor check
1234 567
3: OSSD1
5:
2: EDM
7: 24VDC ±20%
4: OSSD2
1: Start
123456
off
1234567
1
2
3
6: 0V
Fig. 17/1 Integrated connector plug with terminal screws in connector cover
Receiver 7-pin, transmitter 3-pin.
BA - ULVT
auxiliary contact 1
auxiliary contact 2
input contactor check
- Input start button
If the operating mode with
restart interlock
is set, a button must be connected on the start button input for the start release of the operating movement (Fig. 18/1).
With a free protective field, the yellow LED on the receiver lights up as a start prompt. Only once the start button has been pressed will the two outputs OSSD1 and 2 of the ULVTE receiver be switched to active.
If the operating mode
without restart interlock
is set, the start button
input (start) must be unoccupied).
5.4 Connection examples
5.4.1 Operating mode with restart interlock / contactor check
5.4.2 Operating mode without restart interlock / contactor check
5.4.3 PLC drive
When connecting to a safe stored program control (PLC) the outputs of the ULVT must be connected to seperate inputs of the PLC
FIESSLER
ELEKTRONIK
18
5 Electric connection - Connection of receiver and transmitter
Caution! Error-free operation can only be ensured when the safety light barrier is connected according to one of the following
connection diagrams (and/or as shown in Section 7), and also complies with effective national and international accident prevention regulations! Any deviation from these connection specifications can lead to hazardous conditions and is therefore not permitted.
7654321
+24V DC±20%
0V
OSSD 2 OSSD 1 Schützkontrolle
Start-Taster
K2 K1
k1
k2
1234567
Erde
123
+24V DC+20%-10%
0V
Erde
7654321
123
+24V DC±20%
0V
OSSD 2
OSSD 1
K2 K1
+24V DC+20%-10%
0V
1234567
Erde
Erde
unbelegt unbelegt
7
6
5
4
3
2
1
1
2
3
+24V DC±20%
0V
OSSD 2 E1 OSSD 1 E2
+24V DC+20%-10%
0V
12
3
4
5
6
7
Erde
Erde
unbelegt unbelegt
Sicherheits-
SPS
0V
7
1
+24V DC±20%
Start-Taster
6
Eingang Start-Taster
Fig. 18/1 Start button input
Receiver
Transmitter
Receiver
Transmitter
Receiver
Transmitter
Note: The functional ground (marked GND in the opposite connection examples) must be connected at the transmitter and receiver in order to ensure EMC resistance.
BA - ULVT
Contactor check
Start button
GND
GND
Start button
Input start button
GND
GND
GND
GND
Unoccupied Unoccupied
Unoccupied Unoccupied
Safety
PLC
6.1 Commissioning
Prior to commissioning, the appropriate operating mode for the respective application case must be set via the DIP switches in the terminal strip compartment (refer to Section 3.5). When delivered, the operating mode with restart interlock, contactor check and equivalent outputs is set (refer to Section 5).
6.1 Adjustment information
The visual alignment is advantageously carried out with intensely dimmed ambient lighting in order to be able to better detect the LED indications of the receiver even from a long range.
When aligning, it must be ensured that the housing shapes do not become distorted.
An adjustment laser can be obtained for the precise alignment of the ULVT light barriers, particularly where large distances are involved. The device is attached to the front panel of the transmitter and receiver. When the button is pressed, the laser lights up red light spot which can also be seen from long distances. The light spot must hit the centre of the opposite device. This test should be performed at both ends of the transmitter and receiver. The arrangement must be adjusted if necessary.
Adjustment with operation via tilted mirrors: Place the adjustment laser onto the front panel of the transmitter, switch it on and swivel the transmitter until the light spot hits the centre of the mirror. Then adjust the mirror so that the light spot also hits the centre of the second mirror / receiver.
Adjustment LED: The orange LED extinguishes when sufficient light reserve is present.
Fine tuning
Subsequent to face-parallel installation and/or alignment using the adjustment laser, fine tuning is carried out by means of the adjusting screws on the supplied fastening brackets, provided that the orange LED is lit.
The swivel along the longitudinal axis, the respective adjusting screw on one of the fastening brackets is turned whilst both screws on the other fastening bracket are loose. To swivel the lateral axis, both screws of a fastening bracket are turned at the same time whilst both screws on the other fastening bracket are loose.
Subsequently, the green or yellow LED on the receiver should light up, and the orange LED must have extinguished.
Test rod: Using the test rod, the light barrier is to be interrupted on the transmitting side from start to finish in such a way that the
light field is only covered by this part. The green LED must not light up from start to finish. The diameter of the test rod must correspond to the obstacle size specified on the nameplate of the receiving side.
FIESSLER
ELEKTRONIK
19
Light barrier free and correctly adjusted
Outputs active Outputs not active,
(Prompt for start release with start button)
Light barrier free, but insufficient reserve
Outputs active
To swivel along longitudinal or
lateral axis until orange LED
extinguishes
Outp
Outputs not active,
(Prompt for start release with start button) To swivel along longitudinal or lateral axis
until orange LED extinguishes
6 Commissioning
Longitudina l axis
Lateral axis
interdiction de redŽmarrage
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
unterbrochen
sperre
interdiction de redŽmarrage
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
unterbrochen
sperre
interdiction de redŽmarrage
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
unterbrochen
sperre
interdiction de redŽmarrage
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ajustement
libre
interrompu
unterbrochen
sperre
Operating mode Without restart interlock With restart interlock
BA - ULVT
6.3 Troubleshooting
The prerequisite for the troubleshooting process is a correctly adjusted light barrier (refer to Section 6.2)
Please observe: Solvents can damage the plexiglass panels of the transmitter and receiver. As an alternative, light barriers with silicate glass can be delivered. Welding spots can burn into the silicate glass panels. This is prevented by a
replaceable protective panel made out of PVC. Maintenance information: The ULVT... system is maintenance-free depending on the construction. The protective panels in
front of the transmitter and receiver should simply be cleaned at regular intervals with a solvent-free detergent. This does not, however, release the obligation to carry out the prescribed annual inspection pursuant to EN 61496, ZH 1/281 and/or ZH 1/597.
FIESSLER
ELEKTRONIK
20
Operating / fault status Possible causes Remedy
Yellow LED off No power supply Check power supply
Yellow LED flashing Internal error, transmitter inactive
Switch off power supply and then switch on again. If yellow LED still flashes: Transmitter defective, replace transmitter
6 Commissioning - Troubleshooting
Transmitter
Operating / fault status Possible causes Remedy
No LED illuminated No power supply Check power supply Green LED off
Red LED on Orange LED on Yellow LED off
a) Transmitter inactive b) Light path interrupted c) Light barrier maladjusted or very dirt d) Max. range exceeded
a) Check transmitter b) Remove obstacle from light path c) Readjust and/or clean system d) Check range
Green LED off Red LED on Orange LED off Yellow LED on
(no fault) Operating mode with restart interlock active, prompt for start release
Press start button
Green LED off Red LED off Orange LED on Yellow LED off
a) Insufficient reserve, light barrier maladjusted or slightly dirty
b) Max. range exceeded a) Readjust and/or clean system
a) Readjust and/or clean system b) Check range
Green LED and/or Orange LED flashing
a) In operating mode with contactor check: Contactors not responding or fal­len b) Operating mode setting does not match the electric wiring and/or DIP switches are not set as specified in Sect. 3.5. c) Internal error
a) Check auxiliary contact k1 and k2 and/or wiring b) Check operating mode setting c) Switch off power supply and then switch on again If LED still flashes: Check operating mode setting; if correct mode set ­receiver defective, replace receiver.
Receiver
interdiction de redŽmarrage
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
unterbrochen
sperre
Sender ein
Transmitter on
Emetteur en marche
interdiction de redŽmarrage
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
unterbrochen
sperre
interdiction de redŽmarrage
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
unterbrochen
sperre
interdiction de redŽmarrage
Wiederanlauf
Justierhilfe
LS
LS frei
restart interlock
adjustment
LC interrupt
LC free
Aide d«ˆjustement
libre
interrompu
unterbrochen
sperre
Sender ein
Transmitter on
Emetteur en marche
BA - ULVT
7.1 Muting
(Bridging unit) for the short-term bridging of a safety light barrier during a material movement into and out of a manufacturing cell and/or for the safe differentiation between a human operator and fork-lift truck (Fig. 21/1).
Application: The NSUW N1 Muting switchgear is used if a safety light barrier needs to be bridged or differentiate between man and material flow for a certain period of time during an operating cycle, e.g. for protection against bending machines, palletizing machines, narrow-passage high-bay storage, certain types of presses.
Functional description: In combination with a vertical ULVT safety light barrier and four muting sensors, the LSUW N1 Muting switchgear enables a differentiation between man and material flow to be made.
Fig. 21/1 Muting application example For the muting functions, the following components are required and can be obtained
from us:
1. LSUW N1 Muting K switchgear
2. Safety light barrier, e.g. ULVT 900
3. Four muting sensors, e.g. light barriers, inductive sensors, camshaft controller.
4. Muting lamp (max. 230 V, 60 W, min. 24 V AC or DC max. 0.5 A, min. 50 mA) In order to prevent the safety light barrier from being constantly bridges through intentional manipulation, a twin-channel time-
out is provided which withdraws the muting function after a configurable time between 3 and 90 seconds. This time is set by Fiessler Elektronik in accordance with customer specifications. A switching option is also available, whereby operation without time-out is possible.
The muting lamp, which indicates the bridging status, is monitored. If the muting lamp is connected or is defective, bridging will not be possible.
Both muting sensor channels must be connected via separate cables in order to rule out a short-circuit. If the muting sensors require a power supply, the power supplies of the two muting channels must also routed via separate cables. The connection to the intended + supply terminals and - terminal strip must be implemented separately.
For application which do not permit the interruption of a hazardous movement, which only the sounding of an alarm, a key switch must be used as the start button. It must only be possible to remove the key in open status.
The alarm is activated when the mains voltage is applied to this system. The alarm can be deactivated by pressing the key start button.
Before pressing the key start button, it must be checked whether any person is located within the hazardous area. The key start button must be installed at a point where the protected area can be seen.
To ensure the error-free function of the bridging, the distance S (Fig. 21/2) must the same or smaller than the length of the pallet, the fork-lift truck or the reflector band on the conveyor vehicle.
However, the distance S must also be large enough to prevent the simultaneous interruption of the muting sensors LS 2A and LS 1B / LS 2B by a human operator.
If necessary, the distance H to the accessible area, or distance S, must be enlarged.
FIESSLER
ELEKTRONIK
21
7 Additional functions with safety switchgears - Muting
Fig. 21/1 Muting application example
LSUW N1 Muting K switchgear
LS 1A / LS 2A
LS 1B / LS 2B
LSUW N1
Palette
S
LS 1A / LS 2A
LS 1B / LS 2B
ULVT
S
LSUW
LS 1A / LS 2A LS 1B / LS 2B
S
H
Fig 21/2 Distance S must be smaller than the length of the pallet, the fork-lift truck or the reflector band
Fig. 21/3 and Fig 21/4 Distance S must be large enough to prevent the simultaneous interruption of the muting sensors
BA - ULVT
ULVT
We will be happy to provide you with individual advice for planning your application with muting function. The applications shown here are examples only.
7.1.1 Muting function with four muting sensors and time-out
e.g. high-bay protection, pallet conveyor systems
Connection diagram for muting function with four muting sensors and time-out
FIESSLER
ELEKTRONIK
22
Function: During bridging, the ULVT safety light barrier can be interrupted without the alarm being activated and/or the entire system being switched off.
Bridging continues for as long as either the contacts of the two muting sensors LS 1A and LS 2A or LS 1B and LS 2B, or all four, are open, but for no longer than the set time.
If the ULVT safety light barrier is interrupted and not bridged at the same time by the muting sensors, the alarm is activated via contact B-11 (potential-free break contact) and the system switched off via the output contacts 20-21 and 16-17. This enables differentiation between man and material flow.
A restart and deactivation of the alarm is possible by pressing the start button when the ULVT safety light barrier is free.
Before pressing the key start button, it must be ensured that no person is located within the hazardous area. For safety reasons, the minus and plus lines must be routed as shown in the connection diagram. The cabling for muting channels 1 (LS 1A/B) and 2 (LS 2A/B) must be implemented separately.
228
123
1234567
k1 k2
XXXXX
X
M 2,0 A
12
19
8
22C
8
126
6
127
6
12
14
k1 k2
K2
15
13
M 2,0 A
4
3
6
-
7 +
2
3 +
2
1
5
1
-
++ ++
-- --
K1
M 2,0 A
M 2,0 A
16
13
7
A
D
14
2
5
4
E
3
18
9
15
F
10
11
B
17
21
20
6
8
19
12
C
12
22
1
FIESSLER
E L E K T R O N I K
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
LSUW N1 Muting K
No./year of construction response time
t
emp. enclosure rating supply voltage contact max.
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
Netz
tension
power
LS Frei
BS libre
LC free
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
LS unterbrochen
BS interrompue
LC interrupted
Made in Germany
TÜV Rheinland
AA
AA
TÜV Rheinland
LS gebrückt
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
L1
230VAC
N
L1
115VAC
LC muted
BS desactiveé
24VDC
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
0 V DC
OSSD2
OSSD1
EDM
Start
.................................
25 mS
-10… + 55 °C IP 20 230 VAC -15% +10 %, 50Hz 2 A, 250 VAC
AAAAAAA
A
AAAAAAA
A
AAAAAAA
A
AAAAAAA
A
A
AAAAAA
A
A
AAAAAA
A
A
AAAAAA
A
A
AAAAAA
A
AAAAAAAA
LS 1 A LS 2A LS 1B LS 2B
LSUW
Transportband
LSUW
Transportband
Alarm
LS 1 A LS 2A LS 1B LS 2B
7 Additional functions with safety switchgears - Muting
LSUW N1 Muting K switchgear
ULVT
BA - ULVT
ULVTS Transmitter
ULVTE Receiver
Set operating mode:
Without contactor check
Without restart interlock
(both functions are
performed by switchgear)
antivalent outputs
Muting-Sensor
LS 1B
in muting status
contacts open
Muting sensor
LS 2B
in muting status
contacts open
Muting-Sensor
LS 2A
in muting status
contacts open
Voltage depending on type of contactor, muting lamp and alarm signal generator
L1 = 230 V AC
or 24 V DC
Contactor monitoring
Start button
X = For interruption of hazardous movement
Muting
lamp
Alarm
Spark arresting
sections
N or 0V
24V DC
0V
Muting-Sensor
LS 1A
in muting status
contacts open
Cable routing: Separately from power lines. The cable routing for the contactor check (terminals D & 22) must prevent short-circuiting of wires.
If the sum of the currents to terminals B, 10, 17 & 21 exceeds 2A, separate fuse protection of M 2.0 A must be provided for the contacts.
The hazardous movement must only be activated via
output contacts 16-17 and 20-21.
The output contacts are potential-free, monitored, guided make contacts are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W.
With inductive load, the load (not the contacts) is to be switched at the same time as the spark arresting sections (e.g. 0.22 uF, 220 .
The contact B-11 serves as an alarm path and is not permitted to activate the hazardous closing movement.
When performing electric welding work on the machine, the terminal strip of the switchgear is to be removed, otherwise the vagrant welding currents may cause destruction of the installed electronics.
Optional power supply: Terminal 1 & 2: 230 VAC -15% + 10%
or
Terminal 1 & 3: 115 VAC -15% + 10%
or
Terminal A & 12: 24 VDC -10% + 20%
L1NL1
For supply with 230 / 115 VAC: Bridge F- 14
For supply with 24VDC Bridge F- A
We will be happy to provide you with individual advice for planning your application with muting function. The applications shown here are examples only.
Conveyor belt
Conveyor belt
7.1.2 Muting function with four muting sensors without time-out
e.g. high-bay protection, when the loading vehicle can be parked in the entrance area
Connection diagram for muting function with four muting sensors without time-out
FIESSLER
ELEKTRONIK
23
Function: During bridging, the ULVT safety light barrier can be interrupted without the alarm being activated and/or the entire system being switched off.
Bridging continues for as long as either the contacts of the two muting sensors LS 1A and LS 2A or LS 1B and LS 2B, or all four, are closed.
If the ULVT safety light barrier is interrupted and not bridged at the same time by the muting sensors, the alarm is activated via contact B-11 (potential-free break contact) and the system switched off via the output contacts 20-21 and 16-17. This enables differentiation between man and material flow.
A restart and deactivation of the alarm is possible by pressing the start button when the ULVT safety light barrier is free.
Before pressing the key start button, it must be ensured that no person is located within the hazardous area. For safety reasons, the minus and plus lines must be routed as shown in the connection diagram. The cabling for muting channels 1 (LS 1A/B) and 2 (LS 2A/B) must be implemented separately.
228
8
225
8
126
6
124
6
++ ++
-- --
6 4
8
5
k1 k2
XXXXX
X
M 2,0 A
k1 k2
K2
M 2,0 A
K1
M 2,0 A
M 2,0 A
16
13
7
A
D
14
2
5
4
E
3
18
9
15
F
10
11
B
17
21
20
6
8
19
12
C
12
22
1
FIESSLER
E L E K T R O N I K
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
LSUW N1 Muting K
No./year of construction response time
t
emp. enclosure rating supply voltage contact max.
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
Netz
tension
power
LS Frei
BS libre
LC free
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
LS unterbrochen
BS interrompue
LC interrupted
Made in Germany
TÜV Rheinland
AA
AA
TÜV Rheinland
.................................
25 mS
-10… + 55 °C IP 20 230 VAC -15% +10 %, 50Hz 2 A, 250 VAC
LS gebrückt
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
L1
230VAC
N
L1
115VAC
LC muted
BS desactiveé
24VDC
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
0 V DC
123
1234567
12
19
12
14
15
13
4
3
6
-
7 +
2
3 +
2
1
5
1
-
OSSD2
OSSD1
EDM
Start
LS 1A / LS 2A
LS 1B / LS 2B
LSUW
Reflektorband
LS 1A / LS 2A
LS 1B / LS 2B
LSUW
Alarm
7 Additional functions with safety switchgears - Muting
LSUW N1 Muting K switchgear
BA - ULVT
ULVT
Cable routing: Separately from power lines. The cable routing for the contactor check (terminals D & 22) must prevent short-circuiting of wires.
If the sum of the currents to terminals B, 10, 17 & 21 exceeds 2A, separate fuse protection of M 2.0 A must be provided for the contacts.
The hazardous movement must only be activated via output contacts 16-17 and
20-21.
The output contacts are potential-free, monitored, guided make contacts are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W.
With inductive load, the load (not the contacts) is to be switched at the same time as the spark arresting sections (e.g. 0.22 uF, 220 .
The contact B-11 serves as an alarm path and is not permitted to activate the hazardous closing movement.
When performing electric welding work on the machine, the terminal strip of the switchgear is to be removed, otherwise the vagrant welding currents may cause destruction of the installed electronics.
ULVTS Transmitter
ULVTE Receiver
Set operating mode:
Without contactor check Without restart interlock
(both functions are
performed by switchgear)
antivalent outputs
Muting sensor
LS 1B
in muting status
contacts closed
Muting sensor
LS 2B
in muting status
contacts closed
Muting sensor
LS 2A
in muting status
contacts closed
Muting sensor
LS 1A
in muting status
contacts closed
24V DC
0V
L1NL1
We will be happy to provide you with individual advice for planning your application with muting function. The applications shown here are examples only.
Reflector band
Voltage depending on type of contactor, muting lamp and alarm signal generator
Contactor monitoring
X = For interruption of hazardous movement
Muting
lamp
Alarm
Spark arresting
sections
Optional power supply: Terminal 1 & 2: 230 VAC -15% + 10%
or
Terminal 1 & 3: 115 VAC -15% + 10%
or
Terminal A & 12: 24 VDC -10% + 20%
For supply with 230 / 115 VAC: Bridge F- 14
For supply with 24VDC Bridge F- A
7.2.1 Cycle mode "A"
(Safety and control mode through cyclic penetration of the protective field) e.g. Manual insertion work with 30 sec. work monitoring for controlling presses with a table height of 750 mm.
Connection diagram for operating mode "A"
FIESSLER
ELEKTRONIK
24
Functional example: (Press: 1-cycle and 2-cycle mode) Having switched on the safety facility, the protective field must
be penetrated in order to carry out a startup test. Having subsequently pressed the start button with the protective field free and one or two interruptions and re-release, the output contacts (16-17, 20-21) close and the machine movement is started.
If the protective field is penetrated during a hazardous movement of the press, this returns immediately to the upper dead centre. A new operating stroke will only be performed once the start button has been pressed and the light barrier tested by means of one or two penetrations of the protective field.
The checking path 6-7 is used to perform an additional check of the hydraulic valves or the contactor. The activation of a new operating stroke or a hazardous movement will only be performed if both or valves K1 and K2 had fallen when the protective field, and the protective field is subsequently free again.
After 30 sec., the operating monitoring activates the restart interlock if the protective field was not penetrated or re­released in the meantime.
A reset of the cycle counter circuit is performed through the short-term interruption of terminal 10 - 11 (approx. 20 ms) via a switch on the machine.
When activating the closing movement via contactors K1 and K2, the respective make contacts of K1 and K2 must be switched in series!
When switching between the operating modes with 1-cycle and 2-cycle mode, the restart interlock must be activated in accordance with EN 61496. This can be implemented by switching off the transmitter during the switchover.
In this operating mode, it must be ensured that it is not possible to walk behind the light barrier!
(Refer to Section 4.2)
123
1234567
12
X
12
13
15
14
4
3
6
-
7 +
2
3 +
2
1
5
1
-
OSSD1
EDM
Start
6
FIESSLER
E L E K T R O N I K
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
A
1
2
3
7
4
5
8
10
9
17
B
C
12
13
14
15
16
LSUW NSR 3-1 K
No./year of construction response time
t
emp. enclosure rating supply voltage contact max
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
.................................
30 mS
-10… + 55 °C IP 20 24VDC/115VAC/230VAC
-15% +10 %, 50Hz
2 A, 250 VAC
18
Netz
tension
power
LS Frei
BS libre
LC free
output interupted
sortie interrompue
Ausgang unterbrochen
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
19
20
21
22
LS unterbrochen
BS interrompue
LC interrupted
D
Made in Germany
11
TÜV Rheinland
AA
AA
TÜV Rheinland
N
L1 230 VAC
L1 115 VAC
0 V DC
+24VDC
k1 k2
XXX
X
M 2,0 A
K1
K2
M 2,0 A
k1 k2
M 2,0 A
M 2,0 A
M 2,0 A
OSSD2
7 Additional functions with safety switchgears - Time operation "A"
LSUW NSR 3-1 K switchgear
The hazardous movement must only be activated via output contacts 16-17 and 20-21.
The output contacts are potential-free, monitored, guided make contacts are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W. With inductive load, the load (not the contacts) is to be switched at the same time as the spark arresting sections (e.g. 0.22 uF, 220 . Optional power supply:
The contact 18 - 19 serves as an alarm path and is not permitted to activate the hazardous closing movement.
To increase the switching reliability, collateral contacts should be used on terminals 5, 6, 7, 8, 9, 10, 11, D and 22. No external potential must be connected to these terminals.
When performing electric welding work on the machine, the terminal strip of the switchgear is to be removed, otherwise the vagrant welding currents may cause destruction of the installed electronics.
Cable routing:
- Separately from power lines.
- The cable routing for the contactor check (terminals 6 & 7) must prevent short-circuiting of wires.
- On terminals 4, 5, 8, 9, the max. cable length is limited to <= 1m.
ULVTS Transmitter
ULVTE Receiver
Set operating mode:
Without contactor check Without restart interlock
(both functions are
performed by switchgear)
antivalent outputs
Voltage depending on type of contactor
L1 = 230 V AC
or 24 V DC
Contactor monitoring
Start button
X = For interruption of hazardous movement
Spark arresting
sections
N or 0V
24V DC
0V
With bridge: 1-cycle
Without bridge: 2-cycle
Reset of counting circuit of end or
pressure span at lower dead
centre UT
Fuses to be sized so that contact touching is prevented reliably!
L1
N
L1
BA - ULVT
Connection diagram for operating mode "A"
Optional power supply: Terminal 1 & 2: 230 VAC -15% + 10%
or
Terminal 1 & 3: 115 VAC -15% + 10%
or
Terminal A & 12: 24 VDC -10% + 20%
X
X
For 230 V AC and 115 V AC : terminal 3
For 24 V DC : terminal C
7.2.2 Safety mode with restart interlock during the entire "B" cycle
(Only when changing systems from LSUW to ULVT and retaining the switchgear)
e.g. For applications with manual cyclic penetrations of the protective field and restart via start button.
(Refer to ZH 1/281 and ZH 1/597 for example) Presses with table heights below 750 mm with additional safety devices. Presses without control. Rapid stamping machines which do not require cyclic testing.
Connection diagram for operating mode "B"
FIESSLER
ELEKTRONIK
25
Functional example
Having switched on the safety facility, the protective field must be penetrated in order to carry out a startup test. Having subsequently pressed the start button with the protective field free, the output contacts 16-17 and 20-21 close and the machine movement is started.
If the protective field of the light barrier is penetrated, the contacts 16-17 and 20-21 are opened and the machine stopped.
The checking path 6-7 is used to perform an additional check of the hydraulic valves or the contactor. The activation of a new operating stroke or a hazardous movement will only be performed if both or valves K1 and K2 had fallen when the protective field, and the protective field is subsequently free again.
When activating the closing movement via contactors K1 and K2, the respective make contacts of K1 and K2 must be switched in series!
The start button must be installed at point where the hazardous area can easily be seen, and where it cannot be actuated from within the hazardous area without the light barrier being interrupted.
123
1234567
12
12
13
15
14
4
3
6
-
7 +
2
3 +
2
1
5
1
-
EDM
Start
6
FIESSLER
E L E K T R O N I K
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
A
1
2
3
7
4
5
8
10
9
17
B
C
12
13
14
15
16
LSUW NSR 3-1 K
No./year of construction response time
t
emp. enclosure rating supply voltage contact max
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
.................................
30 mS
-10… + 55 °C IP 20 24VDC/115VAC/230VAC
-15% +10 %, 50Hz
2 A, 250 VAC
18
Netz
tension
power
LS Frei
BS libre
LC free
output interupted
sortie interrompue
Ausgang unterbrochen
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
19
20
21
22
LS unterbrochen
BS interrompue
LC interrupted
D
Made in Germany
11
TÜV Rheinland
AA
AA
TÜV Rheinland
N
L1 230 VAC
L1 115 VAC
0 V DC
+24VDC
k1 k2
XXX
X
M 2,0 A
K1
K2
M 2,0 A
k1 k2
M 2,0 A
M 2,0 A
M 2,0 A
OSSD2
OSSD1
X
Voltage depending on type of contactor
L1 = 230 V AC
or 24 V DC
X = For interruption of hazardous movement
Spark arresting
sections
N or 0V
Fuses to be sized so that contact touching is prevented reliably!
7 Additional functions with safety switchgears (only for system change) "B"
LSUW NSR 3-1 K switchgear
Cable routing:
- Separately from power lines.
- The cable routing for the contactor check (terminals 6 & 7) must prevent short-circuiting of wires.
- On terminals 4, 5, 8, 9, the max. cable length is limited to <= 1m.
The hazardous movement must only be activated via output contacts 16-17 and 20-21.
The output contacts are potential-free, monitored, guided make contacts are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W. With inductive load, the load (not the contacts) is to be switched at the same time as the spark arresting sections (e.g. 0.22 uF, 220 . Optional power supply:
The contact 18 - 19 serves as an alarm path and is not permitted to activate the hazardous closing movement.
To increase the switching reliability, collateral contacts should be used on terminals 5, 6, 7, 8, 9, 10, 11, D and 22. No external potential must be connected to these terminals.
When performing electric welding work on the machine, the terminal strip of the switchgear is to be removed, otherwise the vagrant welding currents may cause destruction of the installed electronics.
L1
24V DC
Start button
0V
N
L1
BA - ULVT
Optional power supply: Terminal 1 & 2: 230 VAC -15% + 10%
or
Terminal 1 & 3: 115 VAC -15% + 10%
or
Terminal A & 12: 24 VDC -10% + 20%
ULVTS Transmitter
ULVTE Receiver
Set operating mode:
Without contactor check Without restart interlock
(both functions are
performed by switchgear)
antivalent outputs
Contactor monitoring
X
X
For 230 V AC and 115 V AC : terminal 3
For 24 V DC : terminal C
7.2.3 Selection mode (between cycle mode and safety mode with restart interlock, switchable operation)
Connection diagram for operating mode "AB"
FIESSLER
ELEKTRONIK
26
Function
(1-cycle and 2-cycle mode "A", refer to Section 7.2) (Safety mode with restart interlock "B", refer to Section 7.3)
Using the BU operating mode selector, one of the three operating modes, 1-cycle, 2-cycle or safety mode with restart interlock, can be selected.
When switching between the operating modes, the restart interlock must be activated in accordance with EN 61494. This can be implemented by switching off the transmitter during the switchover.
In the 1-cycle and 2-cycle operating modes, it must be ensured that it is not possible to walk behind the light barrier! (Refer to Section 4.4)
6
FIESSLER
E L E K T R O N I K
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
A
1
2
3
7
4
5
8
10
9
17
B
C
12
13
14
15
16
LSUW NSR 3-1 K
No./year of construction response time
t
emp. enclosure rating supply voltage contact max
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
.................................
30 mS
-10… + 55 °C IP 20 24VDC/115VAC/230VAC
-15% +10 %, 50Hz
2 A, 250 VAC
18
Netz
tension
power
LS Frei
BS libre
LC free
output interupted
sortie interrompue
Ausgang unterbrochen
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
19
20
21
22
LS unterbrochen
BS interrompue
LC interrupted
D
Made in Germany
11
TÜV Rheinland
AA
AA
TÜV Rheinland
N
L1 230 VAC
L1 115 VAC
0 V DC
+24VDC
k1 k2
XXX
X
K1
K2
M 2,0 A
M 2,0 A
BU4
BU2
BU3
BU1
BU5
M 2,0 A
k1 k2
M 2,0 A
M 2,0 A
123
1234567
12
12
13
15
14
4
3
6
-
7 +
2
3 +
2
1
5
1
-
OSSD2
OSSD1
EDM
Start
X
7 Additional functions with safety switchgears - Selection mode "AB"
LSUW NSR 3-1 K switchgear
BU1 BU2 BU3 BU4 BU5
1-cycle mode 2-cycle mode
Safety mode with restart interlock
Cable routing:
- Separately from power lines.
- The cable routing for the contactor check (terminals 6 & 7) must prevent short-circuiting of wires.
- On terminals 4, 5, 8, 9, the max. cable length is limited to <= 1m.
The hazardous movement must only be activated via output contacts 16-17 and 20-21.
The output contacts are potential-free, monitored, guided make contacts are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W. With inductive load, the load (not the contacts) is to be switched at the same time as the spark arresting sections (e.g. 0.22 uF, 220 . Optional power supply:
The contact 18 - 19 serves as an alarm path and is not permitted to activate the hazardous closing movement.
To increase the switching reliability, collateral contacts should be used on terminals 5, 6, 7, 8, 9, 10, 11, D and 22. No external potential must be connected to these terminals.
When performing electric welding work on the machine, the terminal strip of the switchgear is to be removed, otherwise the vagrant welding currents may cause destruction of the installed electronics.
Start button
0V
Contactor monitoring
24V DC
L1
N
L1
BA - ULVT
Optional power supply: Terminal 1 & 2: 230 VAC -15% + 10%
or
Terminal 1 & 3: 115 VAC -15% + 10%
or
Terminal A & 12: 24 VDC -10% + 20%
Voltage depending on type of contactor
L1 = 230 V AC
or 24 V DC
X = For interruption of hazardous movement
Spark arresting
sections
N or 0V
Fuses to be sized
so that contact
touching is
prevented reliably!
ULVTS Transmitter
ULVTE Receiver
Set operating mode:
Without contactor check Without restart interlock
(both functions are
performed by switchgear)
antivalent outputs
X
X
For 230 V AC and 115 V AC : terminal 3
For 24 V DC : terminal C
7.2.4 Safety mode with restart interlock during the hazardous movement "B1"
e.g. For applications with manual cyclic penetrations of the protective field during a non-hazardous movement or machine
standstill.
Connection diagram for operating mode "B1"
FIESSLER
ELEKTRONIK
27
Functional example
Having switched on the safety facility, the protective field must be penetrated in order to carry out a startup test. Having subsequently pressed the start button with the protective field free, the output contacts 16-17 and 20-21 close and the machine movement is started.
If the protective field of the light barrier is penetrated during the hazardous movement, the contacts 16-17 and 20-21 are opened and the machine stopped.
The checking path 6-7 is used to perform an additional check of the hydraulic valves or the contactor. The activation of a new operating stroke or a hazardous movement will only be performed if both or valves K1 and K2 had fallen when the protective field, and the protective field is subsequently free again.
During the idling status of the operating materials, or during a non-hazardous opening movement (opened switch "S"), its is possible to access the operating materials at any time without having to press the start button.
When activating the closing movement via contactors K1 and K2, the respective make contacts of K1 and K2 must be switched in series!
In this operating mode, it must be ensured that it is not possible to walk behind the light barrier!
(Refer to Section 4.4)
123
1234567
12
12
13
15
14
4
3
6
-
7 +
2
3 +
2
1
5
1
-
OSSD2
OSSD1
EDM
Start
6
FIESSLER
E L E K T R O N I K
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
A
1
2
3
7
4
5
8
10
9
17
B
C
12
13
14
15
16
LSUW NSR 3-1 K
No./year of construction response time
t
emp. enclosure rating supply voltage contact max
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
.................................
30 mS
-10… + 55 °C IP 20 24VDC/115VAC/230VAC
-15% +10 %, 50Hz
2 A, 250 VAC
18
Netz
tension
power
LS Frei
BS libre
LC free
output interupted
sortie interrompue
Ausgang unterbrochen
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
19
20
21
22
LS unterbrochen
BS interrompue
LC interrupted
D
Made in Germany
11
TÜV Rheinland
AA
AA
TÜV Rheinland
N
L1 230 VAC
L1 115 VAC
0 V DC
+24VDC
k1 k2
XXX
X
M 2,0 A
K1
K2
M 2,0 A
k1 k2
M 2,0 A
M 2,0 A
M 2,0 A
S
X
7 Additional functions with safety switchgears - "B1"
LSUW NSR 3-1 K switchgear
Cable routing:
- Separately from power lines.
- The cable routing for the contactor check (terminals 6 & 7) must prevent short-circuiting of wires.
- On terminals 4, 5, 8, 9, the max. cable length is limited to <= 1m.
The hazardous movement must only be activated via output contacts 16-17 and 20-21.
The output contacts are potential-free, monitored, guided make contacts are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W. With inductive load, the load (not the contacts) is to be switched at the same time as the spark arresting sections (e.g. 0.22 uF, 220 . Optional power supply:
The contact 18 - 19 serves as an alarm path and is not permitted to activate the hazardous closing movement.
To increase the switching reliability, collateral contacts should be used on terminals 5, 6, 7, 8, 9, 10, 11, D and 22. No external potential must be connected to these terminals.
When performing electric welding work on the machine, the terminal strip of the switchgear is to be removed, otherwise the vagrant welding currents may cause destruction of the installed electronics.
Start button
0V
24V DC
L1
N
L1
BA - ULVT
Optional power supply: Terminal 1 & 2: 230 VAC -15% + 10%
or
Terminal 1 & 3: 115 VAC -15% + 10%
or
Terminal A & 12: 24 VDC -10% + 20%
ULVTS Transmitter
ULVTE Receiver
Set operating mode:
Without contactor check Without restart interlock
(both functions are
performed by switchgear)
antivalent outputs
Voltage depending on type of contactor
L1 = 230 V AC
or 24 V DC
Contactor monitoring
X = For interruption of hazardous movement
Spark arresting
sections
N or 0V
Fuses to be sized so that contact touching is prevented reliably!
X
X
For 230 V AC and 115 V AC : terminal 3
For 24 V DC : terminal C
7.2.5 Safety mode without restart interlock with valve or contactor check
(Only when changing systems from LSUW to ULVT and retaining the switchgear) e.g. For the protection of force-driven operating materials or the implementation of the restart interlock in the machine
Connection diagram for operating mode "C"
FIESSLER
ELEKTRONIK
28
Function
Having switched on the safety facility, the protective field must be penetrated in order to carry out a startup test. Subsequent to the re-release of the protective field, the output contacts 16-17 and 20-21 close and check contact 18-19 is interrupted. The output 18-19 serves as a check contact and is thus not permissible as a contact for activating the hazardous movement.
When the protective field is penetrated, the output contacts 16­17 and 20-21 open the check contact 18-19 closes.
The connecting contactor 6-7 also provides an additional check of the contactors which activate the hazardous movement.
In this operating mode, it must be ensured that it is not possible to walk behind the light barrier!
(Refer to Section 4.4)
123
1234567
12
12
13
15
14
4
3
6
-
7 +
2
3 +
2
1
5
1
-
OSSD2
OSSD1
EDM
Start
6
FIESSLER
E L E K T R O N I K
Schaltgerät BWS Typ 4
Switching unit ESPE Type 4
Boîtier de commande ESPS Type 4
Nr./Baujahr Ansprechzeit Temp. Schutzart Versorgung Kontaktbel.
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 97-0
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
A
1
2
3
7
4
5
8
10
9
17
B
C
12
13
14
15
16
LSUW NSR 3-1 K
No./year of construction response time
t
emp. enclosure rating supply voltage contact max
No./année de fabrication temps de réponse temp. degré de protection tension d'alimentation charge contact maxi.
.................................
30 mS
-10… + 55 °C IP 20 24VDC/115VAC/230VAC
-15% +10 %, 50Hz
2 A, 250 VAC
18
Netz
tension
power
LS Frei
BS libre
LC free
output interupted
sortie interrompue
Ausgang unterbrochen
output free
sortie libre
Ausgang frei
interdiction de redémarrage
restart interlock
Wiederanlaufsperre
19
20
21
22
LS unterbrochen
BS interrompue
LC interrupted
D
Made in Germany
11
TÜV Rheinland
AA
AA
TÜV Rheinland
N
L1 230 VAC
L1 115 VAC
0 V DC
+24VDC
k1 k2
XXX
X
M 2,0 A
K1
K2
M 2,0 A
k1 k2
M 2,0 A
M 2,0 A
M 2,0 A
X
7 Additional functions with safety switchgears - "C"
LSUW NSR 3-1 K switchgear
The hazardous movement must only be activated via output contacts 16-17 and 20-21.
The output contacts are potential-free, monitored, guided make contacts are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W. With inductive load, the load (not the contacts) is to be switched at the same time as the spark arresting sections (e.g. 0.22 uF, 220 . Optional power supply:
The contact 18 - 19 serves as an alarm path and is not permitted to activate the hazardous closing movement.
To increase the switching reliability, collateral contacts should be used on terminals 5, 6, 7, 8, 9, 10, 11, D and 22. No external potential must be connected to these terminals.
When performing electric welding work on the machine, the terminal strip of the switchgear is to be removed, otherwise the vagrant welding currents may cause destruction of the installed electronics.
0V
24V DC
L1
N
L1
BA - ULVT
Optional power supply: Terminal 1 & 2: 230 VAC -15% + 10%
or
Terminal 1 & 3: 115 VAC -15% + 10%
or
Terminal A & 12: 24 VDC -10% + 20%
Cable routing:
- Separately from power lines.
- The cable routing for the contactor check (te0rminals 6 & 7) must prevent short­circuiting of wires.
- On terminals 4, 5, 8, 9, the max. cable length is limited to <= 1m.
ULVTS Transmitter
ULVTE Receiver
Set operating mode:
Without contactor
check
Without restart
interlock
(both functions are
p
Voltage depending on type of contactor
L1 = 230 V AC
or 24 V DC
Contactor monitoring
X = For interruption of hazardous movement
Spark arresting
sections
N or 0V
Fuses to be sized so that contact touching is prevented reliably!
X
X
For 230 V AC and 115 V AC : terminal 3
For 24 V DC : terminal C
7.3 Potential-free switching contacts and universal power supply
The ULSG switchgear provides potential-free output contacts and a universal power supply (either 230 VAC, 115 VAC, or 24VDC connection). The ULSG switchgear performs the power failure bridging of 20 ms pursuant to EN 60204 and is thus suitable as the power supply for ULVT light barriers.
Anschlußschaltbild
FIESSLER
ELEKTRONIK
Connection examples
230 VAC connection / external contactors control hazardous movement
Having pressed the start button with a free protective field, the potential-free output contacts 13-14 and 15-16 close and the connected contactors K1 and K2 respond. When activating the closing movement via contactors K1 and K2, the respective make contacts of K1 and K2 must be switched in series!
The connecting pin 2 (EDM = contactor check) on the receiver also provides an additional check of the contactors or hydraulic valves which activate the hazardous movement. If the protective field is penetrated, the output contacts are opened and the movement interrupted. Operation can only be continued once the start button has been pressed. The activation of a new operating stroke or a hazardous movement will only be performed if both or valves K1 and K2 had fallen when the protective field, and the protective field is subsequently free again.
In the operating mode without restart interlock, the connecting pin 1 (start) on the receiver must be left free.
24 VDC connection / the output contacts 13­14 and 15-16 directly control the hazardous movement
Control of the hazardous movement of the operating material is performed directly via the potential-free output contacts 13-14 and 15-16.
The activation of the hazardous movement is implemented as described in the above example.
In the operating mode without restart interlock, the connecting pin 1 (start) on the receiver must be left free.
k1 k2
x
x
x
xxx
L1
N
4
3
6
-
7 +
2
3 +
K1
K2
M 2A
M 2A
k1
k2
FIESSLER
E L E K T R O N I K
Typ: ULSG 230V
TÜV Rheinland
23145 7 8 9 10 12 13 14 15
Schaltgerät BWS Typ 2 / 4
Switching unit ESPE Type 2 / 4
Boîtier de commande ESPE Type 2 / 4
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 970
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
Nr./Baujahr No./year of construction No./année de fabrication .................................
Ansprechzeit response time temps de réponse 6 mS + BWS / ESPE Temp. temp. temp. -10… + 55 °C Schutzart enclosure rating degré de protection IP 20 Versorgung supply voltage tension d'alimentation 230 VAC -15% +10 %, 50Hz Kontaktbel. contact max. charge contact maxi. 2 A, 250 VAC
Made in Germany
SK230V 115V
---------- 24V ---------
----- 0V -----
A1 A2N
2
1
5
16611
ST
1
-
OSSD2
OSSD1
EDM
Start
7 Additional functions with safety switchgears
ULSG switchgear
24V
0V
M 2A
FIESSLER
E L E K T R O N I K
Typ: ULSG 230V
TÜV Rheinland
23145 7 8 9 10 12 13 14 15
Schaltgerät BWS Typ 2 / 4
Switching unit ESPE Type 2 / 4
Boîtier de commande ESPE Type 2 / 4
Kastellstr.9 73734 Esslingen Tel. 0711/ 91 96 970
Achtung Vor Abziehen der Klemmleiste Netzspannung abschalten!
Attention
Turn off the supply voltage !
Attention Couper l'alimentation !
Nr./Baujahr No./year of construction No./année de fabrication .................................
Ansprechzeit response time temps de réponse 6 mS + BWS / ESPE Temp. temp. temp. -10… + 55 °C Schutzart enclosure rating degré de protection IP 20 Versorgung supply voltage tension d'alimentation 230 VAC -15% +10 %, 50Hz Kontaktbel. contact max. charge contact maxi. 2 A, 250 VAC
Made in Germany
SK230V 115V
---------- 24V ---------
----- 0V -----
A1 A2N
16611
ST
M
OSSD2
OSSD1
EDM
Start
4
3
6
-
7 +
2
3 +
2
1
51
-
ULVTE Receiver
ULVTS
Transmitter
L1 = 230 VAC or 24 VDC Voltage depending on type of contactor
Contactor monitoring
X = For interruption of hazardous movement
N or 0V
Set operating mode:
- With contactor check
- With restart interlock
- equivalent outputs
Terminal 1 & 3: 230 VAC -15% + 10%
or
Terminal 2 & 3: 115 VAC -15% + 10%
N or 0V
Terminal 4 & 7: 24 VDC -10% + 15%
When performing electric welding work on the machine, the terminal strip of the switchgear is to be removed, otherwise the vagrant welding currents may cause destruction of the installed electronics.
Cable routing: Separately from power lines. The hazardous movement must only be activated via output contacts 16-17 and 20-21. The output contacts are potential-free, monitored, guided make contacts are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W. With inductive load, the load (not the contacts) is to be switched at the same time as the spark arresting sections (e.g. 0.22 uF, 220 . hazardous closing movement. To increase the switching reliability, collateral contacts should be used on
BA - ULVT
29
ULVTE ReceiverULVTS
Transmitter
L1 = 230 VAC or 24 VDC Voltage depending on type of contactor
Set operating mode:
- With contactor check
- With restart interlock
- equivalent outputs
Start interlock
Subsequent to commissioning and/or a power interruption, the start interlock prevents a "re-release". A re-release is only possible once the protective field has been interrupted and reactivated.
Response time
The time period between penetration of the protective field and the switching process.
EPSE Type 4
The ULVT... safety light barriers comprise photo-electric guards. These devices are characterized by the fact that when the protective field generated by the transmitter and receiver is interrupted, a hazardous movement is interrupted or prevented.
One-cycle (two-cycle operating mode)
Subsequent to one (two) penetrations, the machine automatically performs an operating cycle and then waits for a maximum 30 seconds for one (two) penetrations. If the time period exceeds 30 seconds, the restart interlock is activated.
Installation range
(Fig. 30/1)
The minimum and/or maximum permissible distance between the transmitter and receiver. The permissible installation range is specified on the ULVT receiver.
Obstacle size
(Fig. 30/1)
The obstacle size indicates the minimum obstacle diameter that will definitely interrupt a hazardous movement through the safety light barriers. The following obstacle sizes are provided by the beam distances for the ULVT... safety light barriers:
Muting
Temporary and safe bridging of the ULVT safety light barriers during a material movement, e.g. into and out of a manufacturing cell, or in high-bay storage. Reliable differentiation between man and material flow is ensured.
Overrrun
The section of hazardous movement which occurs after penetration of the protective field. Overrrun traverse
(Fig. 30/2)
The path traversed during the run-on period (e.g. path of a ram, path of a point on a roller surface).
Overrrun period
Duration of the run-on period.
Protective field height
(Fig. 30/1)
Height of the protective field generated by the transmitter and receiver.
Safety mode
When the protective field is interrupted, the switching outputs are blocked, then automatically released subsequent to re-release of the protective field.
Self-monitoring
The automatic response of the photo-electric guard in the event of an internal malfunction.
Safe distance (Fig. 30/2)
The minimum distance S between safety light barrier and the nearest hazardous area, required in order to prevent injuries. In order to establish the minimum safe distance, the formulas from standard EN 999, the machine-specific C standards and the effective ZH guidelines are to be used.
Safety category 4
The ULVT safety light barriers belong to safety category 4 as per EN 945-1 and IEC 61496 / EN 61496. Devices of safety category 4 comprise self-monitoring photo-electric guards and represent the highest safety class for photo-
30
FIESSLER
ELEKTRONIK
Min. / max. installation range 0,3m / 7 m 0,3m / 24 m min. obstacle size 14 mm 30 mm min./max. protective field height 100 mm / 1900 mm 100 mm / 1900 mm
S
Nachlaufweg der Maschine
8 Terminology
protective field height
Installation range
Obstacle size
Fig. 30/2 Safe distance and overrun traverse
Fig. 30/1 Installation range, obstacle size, protective field height
BA - ULVT
overrun traverse
electric guards.
Beam spacing
The distance (gap) between the centres of the individual lenses on ULVT... safety light barriers is called the beam distance. The ULVT... safety light barriers are supplied with a lens grid of 7.5 mm.
Valve or contactor check
Prior to each release of the switching outputs, the contactor identifies whether the connected switching elements (relays, contactors or valves) have fallen. Only when this is so can a new release of the switching inputs be performed. This also prevents the dangerous failure of the switching elements (relays, contactors, valves) of the hazardous movement.
Restart interlock
The restart interlock prevents the automatic release of the switching outputs subsequent to the interruption and reactivation of the protective field (e.g. due to walking through the protective field).
31
FIESSLER
ELEKTRONIK
8 Terminology
BA - ULVT
FIESSLER
ELEKTRONIK
32
9 Specifications - Transmitter and receiver
ULVTS / ULVTECharacteristic data
Mechanical data
Operating data
Electric data
Safety category 4 pursuant to EN 954-1 and IEC 61496 / EN 61496
Protective field heights 100 mm ... 3000 mm (depending on number of beams)
Protective field width 0,3… 7 m , 0,3...24 m
Construction lengths 196 mm ... 1996 mm (depending on number of beams)
Definition 14 mm
Number of beams 13 ... 247 beams
Operating modes
(selected via DIP switches, see also Sections 3.5 and 7)
- With / without restart interlock
- With / without contactor check
- equivalent / antivalent outputs
- Muting (only with optional LSUW N1 Muting K switchgear)
- Cycle mode with 1 cycle / 2 cycles (only with optional LSUW NSR3-1 K switchgear)
- Safety mode with restart interlock only during the hazardous movement (only with optional LSUW NSR3-1 K switchgear)
Housing design
Aluminium profile, plastic-coated RAL 1020, yellow, end pieces made from non-corrosive, spherically reinforced plastic (polyamide). Plexiglass light outlet and inlet, optional with solvent-resistant silicate glass.
Attachment Shifting fastening brackets on rear side of housing
Weight
Transmitter: 0.45 kg to 4.5 kg depending on construction length Receiver: 0.5 kg to 5.0 kg depending on construction length
Protection category IP 65
Protection class
III
Operating ambient temperature
-10 bis 55 °C
Storage temperature
-25 bis 70 °C
ULVTS Transmitter ULVTE Receiver
Power supply 24 V DC, + 20 % - 10 %, SELV 24 V DC, ±20%, SELV
Current draw max. 250 mA max. 250 mA (no load)
Outputs -
OSSD 1 and 2: Failsafe PNP outputs, max. 0.5 A, short-circuit and cross-circuit monitoring (in operating mode with antivalent outputs, output 2 is not failsafe, max. 20 mA)
Inputs - Contactor check and start button inputs: 0 V to 24 VDC
_
Electric connection
Integrated connector plug with PG9 as strain relief, alternatively conventional connector plug
Integrated connector plug with PG9 as strain relief, alternatively conventional connector plug
Connecting cable 3-pol. max. 1,5 mm
2
5 to 7-pin (depending on operating mode), max. 1.5 mm2
BA - ULVT
FIESSLER
ELEKTRONIK
33
9 Specifications - Safety switching units
Safety category 4 pursuant to EN 954-1 and IEC 61496 / EN 61496
Operating modes
(selected via DIP switches, see also Sections 3.5 and 7)
- Muting (only with LSUW N1 Muting K switchgear)
- Cycle mode with 1 cycle / 2 cycles (only with LSUW NSR3-1 K switchgear)
- Safety mode with restart interlock only during the hazardous movement (only with LSUW NSR3-1 K switchgear)
Response time
LSUW N1 Muting K: 29 ms
- LSUW NSR3-1 K: 25 ms
- ULSG: 6 ms
Power supply Optionally 230 VAC/50 Hz + 10% -15%, 115 VAC/50 Hz + 10% - 15%, 24 VDC, +20% - 10%, reverse polarity protected
Current draw max. 250 mA
Outputs
The output contacts are potential-free, monitored (with ULSG only in conjunction with ULVT), guided make contact
s
are must be loaded with max. 2 A/250 VAC or 60 VDC, 30 W.
Inputs
Contactor check and start button inputs: 0 V to 24 VDC _+ 20%
Electric connection Plug-on terminal strip
Connecting cable max. 1,5 mm
2
Protection category IP 20
Protection class Shockproof
Operating ambient temp. -10 bis 55 °C Storage temperature -25 bis 70 °C
Optional LSUW NSR 3-1K / LSUW N1 Muting K / ULSG switchgearsCharacteristic data
Mechanical data
Operating data
Electric data
Housing design Insulated black housing, curved lid
Attachment Snap-on mounting on top hat rail DIN EN 50022-35, threaded mounting
Weight
ULSG: 1200 g LSUW NSR 3-1K / LSUW N1 Muting K: 1700 g
BA - ULVT
FIESSLER
ELEKTRONIK
34
ULVT transmitter / receiver
10 Dimensions drawings - Transmitter and receiver
26 mm
23 mm
PG 9
11 mm
59 mm
Schutzfeldhöhe
Baulänge
redŽmarrage
adjustment
ˆjustement
LC interrupt
interrompu
7: 24VDC ±20%
ULVTE Empfänger
D-73734 Esslingen, Kastellstr.9 0711/91 96 97 -0
1234 567
ULVT Receiver/Récepteur
Justierhilfe
LS frei
restart
LC free
libre
BWS Typ4, ESPE Type4 , ESPS Type4
FIESSLER
LS
unterbrochen
Wiederanlauf
sperre
E L E K T R O N I K
Made in Germany
3:OSSD1
6: 0V
5:
2: EDM
4: OSSD2
1: Start
61 mm
40 mm
Fig. 34/1 Dimensions of transmitter / receiver
Fig.34/2 Fastening brackets
7 mm
9 11 11 9
5,5
10,5
7 mm
5,5
10,5
9
11
11 9
M6
9mm
5,1mm
40 mm
5 mm dick
9mm
5,1mm
5 mm dick
M6
22 mm
12 mm
22 mm
22 mm
12 mm
22 mm
120 mm
100 mm
40 mm
Fastening brackets
Protective field height
Construction length
Housing design:
Aluminium profile, plastic-coated RAL 1020, yellow, end pieces made from non-corrosive, spherically reinforced plastic (polyamide). Plexiglass light outlet and inlet, optional with solvent-resistant silicate glass.
Attachment:
Shifting fastening brackets on rear side of housing
Shifting fastening brackets
Protective field
height (mm) / no. of beams
Construction
length (mm)
100 / X 196
200 / X 296 300 / X 396 400 / X 496 500 / X 596 600 / X 696 700 / X 796 800 / X 896
900 / X 996 1000 / X 1096 1100 / X 1196 1200 / X 1296 1300 / X 1396 1400 / X 1496 1500 / X 1596 1600 / X 1696 1700 / X 1796 1800 / X 1896 1900 / X 1996
BA - ULVT
Mounting with optionlal mounting angle
Mounting with optionlal mounting angle
for fastening angle,
Sick Typ FGS
FIESSLER
ELEKTRONIK
FIESSLER
E L E K T R O N I K
50
ø 7
110
30
11
50
5
32
35
10 Dimensions drawings -mounting angle
BA - ULVT
FIESSLER
E L E K T R O N I K
Fixing possiblities for Fastening angle Sick Typ FGS
Housing design:
Distortion-free aluminium dual-chamber profile, plastic-coated RAL 1021, yellow
Attachment:
Spherical head screw
Dimensions drawing Form factors
Installation information:
1. Insert the spherical head screw into the pocket hole as shown in the drawing.
2. Insert the press pin.
3. Screw in the hexagon screw and tighten using a 5 mm Allan key. The mirror can be attached to a holder with the aid of the spherical head screw.
Further installation options are provided by the threaded bores on the mirror profile.
FIESSLER
ELEKTRONIK
LP
116
44
7
60
90
LB ± 2 mm
36
M10
M10
Innensechskantschlüssel 5 mm
Druckstift
Schwenkbereich ± 30 °
Assembly drawing
* Attachment only via ball joint
10 Dimensions drawings - Tilted mirrors
For protective field height
Profile length LP
Attachment distance LB
Weight g
order no.
100 200 Central* 1667 usp100 200 300 195 2297 usp200 300 400 295 2927 usp300 400 500 395 3557 usp400 500 600 495 4187 usp500 600 700 595 4817 usp600 700 800 695 5447 usp700 800 900 795 6077 usp800
900 1000 895 6707 usp900 1000 1100 995 7337 usp1000 1100 1200 1095 7967 usp1100 1200 1300 1195 8597 usp1200 1300 1400 1295 9227 usp1300 1400 1500 1395 9857 usp1400 1500 1600 1495 10487 usp1500 1600 1700 1595 11117 usp1600 1700 1800 1695 11747 usp1700 1800 1900 1795 12377 usp1800 1900 2000 1895 13007 usp1900
BA - ULVT
Press pin
Allan key 5 mm
Swivel range _+ 30°
FIESSLER
ELEKTRONIK
37
10 Dimensions drawings - Switchgears
BA - ULVT
Optional LSUW NSR 3-1k / LSUW N1 Muting K safety switchgears
Housing design:
Insulated black housing, curved lid
Attachment:
Snap-on mounting on top hat rail DIN EN 50022-35, threaded mounting
Protection category:
IP 20 (For the ULSG and LSUW N1 Muting K switchgears, an attachment housing with protection category IP 55 is available.)
Electric connection:
Plug-on terminal strip
Weight:
ULSG: 800 g LSUW NSR 3-1K: 2500 g LSUW N1 Muting K: 2500 g
FIESSLER
ELEKTRONIK
38
11 Accessories
Accessories Order designation
Rubber-metal connection (for intense vibrations)
Refer to Page 14 Per bracket SM
mounting angle
Refer to Page 35 BW-K
Test rod (for daily function inspection)
Refer to Page 19 14 mm PS 14
Tilted mirror Refer to Page 35 SP 100 … SP 2000 Silicate glass
(solvent-resistant)
Refer to Page 20 UGL 100 … UGL 2000
Assembly columns for transmitter and receiver Refer to Page 15/16 MS 1250 SE
Assembly columns complete with tilted mirrors Refer to Page 15/16 MS 1250 US
Adjustment laser Refer to Page 19 JL2
EX-protection Refer to Page 19 EXP
BA - ULVT
FIESSLER
ELEKTRONIK
39
BA - ULVT
BA - ULVT
Doku Nr. 541 Stand 28.3.2001 / RK
0018452
Counting barriers
Hole seeking device
Safety switching mats
FIESSLER
E L E K T R O N I K
Turbidity sensors
FIESSLER
E L E K T R O N I K
Analog sag sensor
Safety light bars
TÜV Rheinland
Safety light barriers
TÜV Rheinland
FIESSLER
E L E K T R O N I K
Reference sensor
Switching end and measuring light barriers
Elevator light bars
EX-Light - Barrier Light-Barrier for general applications
?
Your application
Fiessler Elektronik Kastellstr. 9 D-73734 Esslingen Telefon: +49 711 / 91 96 97-0 Telefax: +49 711 / 91 96 97-50 www.fiessler.de E-Mail:info@fiessler.de
Single-beam safety light barriers
Alarm
AAAAAAAAAAAAA
A
AAAAAAAAAAAAA
A
AAAAAAAAAAAAA
A
AAAAAAAAAAAAA
A
AA
AA
Safety light bars with muting function
TÜV Rheinland
FIESSLER
E L E K T R O N I K
Sendeebene
Surface scanner
TÜV Rheinland
Folding press protection
Product range:
Loading...