FieldServer QuickServer PS-QS-1010, QuickServer PS-QS-1011, QuickServer PS-QS-1510, QuickServer PS-QS-1511 Quick Start Manual

QuickServer Start-up
Guide
PS-QS-1010/1011, PS-QS-1510/1511
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after August 2012
Kernel Version: 6.04 Document Revision: 11
QuickServer Start-up Guide
Table of Contents
TABLE OF CONTENTS
1
2
Equipment Set-up
........................................................................................................................................................
4
Supplied
equipment .....................................................................................................................................................
4
1.1
1.2
BTL Mark – BACnet Testing
Laboratory ..........................................................................................................................
4
LonMark
Certification.....................................................................................................................................................
4
3 Mounting
.....................................................................................................................................................................
5
3.1 Dimensions .....................................................................................................................................................................
5
3.1.1
3.1.2
Dimension Drawing
PS-QS-1010/1510-XXXX .........................................................................................................
5
Dimension Drawing
PS-QS-1011/1511-XXXX .........................................................................................................
6
3.2
3.3
Wiring .............................................................................................................................................................................
7
Specifications..................................................................................................................................................................
8
4 Installing the QuickServer
...........................................................................................................................................
10
4.1 RS-485
..........................................................................................................................................................................
10
4.1.1
4.1.2
RS-485 Connection R2
port ...................................................................................................................................
10
RS-485 Connection R1 Port (Only on Non-LonWorks
QuickServers).....................................................................
10
4.2
4.3
4.4
QuickServer LonWorks – (PS-QS-1011/1511-XXX)
......................................................................................................
10
RS-232 (Only available on the PS-QS-1XXX
Models).....................................................................................................
11
Configure the DIP Switches
..........................................................................................................................................
11
4.4.1
4.4.2
4.4.3
Using A0 – A7 to set Node ID/Device
Instance. ....................................................................................................
11
Using B0 – B3 to set Baud Rate
............................................................................................................................
11
DIP Switches
S0-S3................................................................................................................................................
12
5 Operation .....................................................................................................................................................................
13
5.1
5.2
5.3
Power up the
device.....................................................................................................................................................
13
Connect the PC to the QuickServer over the Ethernet
port. ........................................................................................
13
Use the FieldServer Web GUI to Connect to the QuickServer
.....................................................................................
14
5.3.1
Using the Discovery Tool to Allocate the IP
address:............................................................................................
14
5.4 Set IP Address of the
QuickServer ................................................................................................................................
15
6 Configuring the
QuickServer .........................................................................................................................................
16
6.1
6.2
6.3
6.4
Retrieve the Sample Configuration
File........................................................................................................................
16
Change the Configuration File to Meet the Application
..............................................................................................
16
Load the Updated Configuration
file ............................................................................................................................
17
Test and Commission the
QuickServer .........................................................................................................................
18
Appendix A Useful
Features .................................................................................................................................................
19
Appendix A.1. QuickServer DIP Switch configuration
..............................................................................................................
19
Appendix A.1.1. Configure DIP switches
A0-A7 ....................................................................................................................
19
Appendix A.1.2. Configure DIP switches B0 – B3
..................................................................................................................
19
Appendix A.1.3. Configure DIP switches S0 – S3
..................................................................................................................
20
Appendix A.2. RS-422 (Only available on the FS-QS-12XX models)
.........................................................................................
21
Appendix A.2.1. Connection and Operation of the RS-422
QuickServer ...............................................................................
22
Appendix B Troubleshooting
Tips.........................................................................................................................................
23
App
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Serial and LonWorks Start-up Guide
Table of Contents
Appendix C Limited 2 year Warranty
...................................................................................................................................
24
Appendix D Reference
.........................................................................................................................................................
25
Appendix D.1. PS-QS-1010/1510-XXXX LED’s
...........................................................................................................................
25
Appendix D.1.1. LED
Functions .............................................................................................................................................
25
Appendix D.2. PS-QS-1011/1510-XXXX LED’s
..........................................................................................................................
26
Appendix D.3. QuickServer FS-QS-101X DCC
...........................................................................................................................
27
Appendix D.4. Compliance with UL Regulations
......................................................................................................................
27
Appendix D.5. Address DIP Switch Settings
.............................................................................................................................
28
Appendix D.6. Baud DIP Switch
Settings ..................................................................................................................................
30
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 4 of 30
QuickServer is a high performance, cost effective Building and Industrial Automation multi-protocol gateway providing protocol translation between serial, Ethernet, and LonWorks devices and networks.
QuickServer Gateway.
Preloaded with the two selected drivers (on the PS-QS-1011/1500 one of those drivers is LonWorks). A sample configuration file is also pre-loaded onto the QuickServer.
All instruction manuals, driver manuals, configuration manuals and support utilities are available on the USB drive provided in the optional accessory kit, or on-line at www.fieldserver.com/QS_Support/
Accessory kit (Optional) (Part # FS-8915-36-QS) including:
7-ft CAT5 cable with RJ45 connectors at both ends
Power Supply -110/220V (p/n 69196)
DIN Rail mounting bracket
Screwdriver for connecting to terminals
USB Flash drive loaded with:
o
o
o
o
o
o o
QuickServer Start-up Guide FieldServer Configuration Manual FieldServer Utilities Manual All FieldServer Driver Manuals Support Utilities Any additional folders related to special files configured for a specific QuickServer Additional components as required - See Driver Manual Supplement for details
The BTL Mark on the ProtoNode RER is a symbol that indicates to a consumer that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing. The mark is a symbol of a high-quality BACnet product. For more information about the BACnet Testing Laboratory go to: http://www.bacnetinternational.net/btl/
LonMark International is the recognized authority for certification, education, and promotion of interoperability standards for the benefit of manufacturers, integrators and
end users.
LonMark International has developed extensive product certification
standards and tests to provide the integrator and user with confidence that products from multiple manufacturers utilizing LonMark devices will work together. FieldServer Technologies, manufacturer of the QuickServer has more LonMark Certified gateways than any other gateway manufacturer.
1 LonWorks is a registered trademark of Echelon Corporation Metasys is a registered trademark of Johnson Controls Inc. BACnet is a registered trademark of ASHRAE
2 . 2 L o n M a r k C e r t i f i c a t i o n
2 . 1 B T L M a r k – B A C n e t T e s t i n g L a b o r a t o r y
2 S U P P L I E D E Q U I P M E N T
1 E Q U I P M E N T S E T - UP
1
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 5 of 30
The following mounting options are available:
Product comes with tabs for wall or surface mount. These can be snapped off if not required.
DIN Rail Mounting Bracket - included in the Accessory Kit or ordered separately)
Din Rail
Tab
R1 Port
R2 Port
3 . 1 . 1 D i m e n s i o n D r a w i n g PS - Q S - 1 0 10/1510 - XXXX
3 . 1 D i m e n s i o n s
3 M O U N T I N G
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 6 of 30
LonWorks Port
R2 Port
3 . 1 . 2 D i m e n s i o n D r a w i n g PS - QS - 1 011/1511 - XXXX
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 7 of 30
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference
This device must accept any interference received, including interference that may cause undesired operation.
2
Specifications subject to change without notice
PS-QS-1010/1510-XXXX
PS-QS-1011/1511-XXXX
Available Ports
One 6-pin Phoenix connector, one RS­485 +/- ground port, power +/- frame ground port One 3-pin RS-485 Phoenix connector, one RS-485 +/- ground port One Ethernet-10/100 port
One 6-pin Phoenix connector, one RS-485 (or RS-232 or RS-422) +/- ground port, power +/- frame ground port 2-pin FTT-10 LonWorks port One Ethernet-10/100 port
Power Requirements
Input Voltage: 9-30VDC or 12-24VAC Input Power Frequency 50/60 Hz. Power Rating: 2.5 Watts Current draw @ 12V, 150 mA
Input Voltage: 9-30VDC or 12-24VAC Input Power Frequency 50/60 Hz. Power Rating: 2.5 Watts Current draw @ 12V, 279 mA
Approvals
TUV approved to UL 916 Standard RoHS Compliant FCC Part 15 Compliant DNP compliant OPC self-tested to conformance CE Mark BTL Mark
TUV approved to UL 916 Standard RoHS Compliant FCC Part 15 Compliant DNP compliant OPC self-tested to conformance LonMark Certification SPID: 80:00:95:46:00:84:04:01 Profiles: 0000 - Node object (1) 0001 - Open Loop Sensor Object (5) 0003 - Open Loop Actuator Object (5)
Surge Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Physical
Dimensions(excluding
the external power supply)
(WxDxH):
5.05 x 2.91 x 1.6 in. (12.82 x 7.39 x 4.06 cm) excluding mounting tabs
Weight:
0.4 lbs (0.2 Kg)
Environment:
Operating Temperature:
-40°C to 75°C (-40°F to167°F)
Humidity:
5 - 90% RH (non-condensing)
3 . 3 S p e c i f i c a t i o n s
2
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 8 of 30
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, p ursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his
expense. Modifications not expressly approved by FieldServer could void the user's authority to operate the equipment under FCC rules
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 9 of 30
Connect to the 3 pins on the left-hand-side of the 6 pin connector as shown.
For connection to RS-232 or RS-422, please refer to Appendix A.2
Connect to the 3-pin connector as shown.
Connect the QuickServer to the LonWorks terminal using a twisted pair non-shielded cable.
LonWorks Service Pin
LonWorks Terminal
To commission the QuickServer LonWorks port, insert a small screwdriver in the commissioning hole on the face of the QuickServer’s enclosure to access the Service Pin. See the instructions on the QuickServer as to which way to toggle the screwdriver during commissioning.
4 . 2 Q u i c k S e r v e r L o n W o r k s – ( PS - QS - 1 0 11/1511 - XXXX)
+ -
GND
4 . 1 . 2 RS - 4 8 5 C o n n e c t i o n R 1 P o r t (O n l y o n N o n - L o n W o r k s Q u i c k S e r v e r s
B+
A-
SG
4 . 1 . 1 RS - 485 C o n n e c t i o n R 2 p o r t
4 . 1 RS - 485
4 I N S T A L L I N G T H E Q U I C KS E R V E R
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 10 of 30
Refer to Appendix A.1 and Appendix A.1.3 for configuration example. The S0 - S3 DIP switch selection is read directly into a Data Array. This Data_Array value
can be used for customized configuration selection.
operations
such as
4 . 4 . 3 D I P S w i t c h e s S 0 - S3
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 11 of 30
Apply power to the device. Ensure that the power supply used complies with the specifications provided in.
Ensure that the cable is grounded using the Frame GND” terminal. 12-24VAC.
The QuickServer is factory set for 9-30VDC or
Ethernet Port
Disable any wireless Ethernet adapters on the PC/Laptop.
Disable firewall and virus protection software .
Connect an Ethernet cable between the PC and QuickServer or connect the QuickServer and the PC to the Hub/switch using a straight cat5 cable.
The Default IP Address of the QuickServer is 192.168.2.X, Subnet Mask is 255.255.255.0. If the PC and the QuickServer are on different IP Networks, assign a Static IP Address to the PC on the 192.168.2.X network.
5 . 2 C o n n e c t t h e P C t o t h e Q u i c k S e r v e r o v e r t h e E t h e r n e t p o r t .
PWR+
PWR- FG
5 . 1 P o w e r u p t h e d e v i c e
5 O P E R A T I O N
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 12 of 30
Install the Discovery tool from the USB drive or get it from our website http://fieldserver.com/techsupport/utility/utility.php
Use the Discovery tool to find the QuickServer, and launch the Web GUI from the Discovery tool
5 . 3 . 1 U s i n g t h e D i s c o v e r y T o o l t o A l l o c a t e t h e I P a d d r e s s :
5 . 3 U s e t h e F i e l d S e r v e r W e b G U I t o C o n n e c t t o t h e Q u i c k S e r v e r
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 13 of 30
From the GUI main home page, click on setup and then Network Settings to enter the Edit IP Address Settings menu.
Modify the IP address (N1 IP address field) of the QuickServer Ethernet port.
If necessary, change the Netmask (N1 Netmask field).
Type in a new Subnet Mask
If necessary, change the IP Gateway (Default Gateway field)
Type in a new IP Gateway
Note: If the FieldServer is connected to a router, the IP Gateway of the FieldServer should be set to the IP address of the router that it is connected to
Click Update IP Settings, then click on the System Restart to restart the Gateway and activate the new IP address. Note that the QuickServer will need to be pointed to the new IP address on the Web Browser before the GUI will be accessible again. Unplug Ethernet cable from PC and connect it to the network hub or router
5 . 4 S e t I P A d d r e s s o f t h e Q u i c k S e r v e r
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 14 of 30
The configuration of the QuickServer is provided to the QuickServer’s operating system via a comma-delimited file
called
.
If a custom configuration was ordered, the QuickServer will be programmed with the relevant device registers in the Config.csv file for the first time start-up. If not, the product is shipped with a sample config.csv that shows an example of the drivers ordered.
In the main menu of the PS-GUI screen, go to Setup, File Transfer, Retrieve.
Click on config.csv, and open or save the file
Refer to the FieldServer Configuration Manual in conjunction with the Driver supplements for information on configuring the QuickServer. See www.prosoft-technology.com/Support/for specific details.
6 . 2 C h a n g e t h e C o n f i g u r a t i o n F i l e t o M e e t t h e A p p l i c a t i o n
CONFIG.CSV”
6 . 1 R e t r i e v e t h e S a m p l e C o n f i g u r a t i o n File
6 C O N F I G U R I N G T H E Q U I C K S E R V E R
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 15 of 30
In the main menu of the FS-GUI screen, go to Setup, File Transfer, Update
Browse and select the .csv file, open, then click Submit
Once download is complete, click the System Restart Button (or simply cycle power to the QuickServer) to put the new file into operation. Note that it is possible to do multiple downloads to the QuickServer before resetting it.
6 . 3 L o a d t h e U p d a t e d C o n f i g u r a t i o n f i l e
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 16 of 30
Connect the QuickServer to the third party device(s), and test the application.
From the main menu of protocol.
PS-GUI click on View, Connections to see the number of messages on each
For troubleshooting assistance refer to Appendix B, or contact ProSoft technology Technical Support at www.prosoft-technology.com/Support/
.
6 . 4 T e s t a n d C o m m i s s i o n t h e Q u i c k S e r v e r
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 17 of 30
There are 3 DIP switches available on the QuickServer.
A – Address DIP Switch
B – Baud rate DIP Switch
S – Secondary DIP Switch
The following sections describe how to set up the DIP switches in the configuration file. To configure the use of the DIP switches, buffers need to be declared in the Data Arrayssection which will enable them.
To configure DIP switches A0-A7 to adjust the Device Id, BACnet MAC address, or both, the dynamic parameters field needs to be added to the configuration file.
To configure DIP switches B0-B3 to adjust the baud rate, the dynamic parameters field needs to be added to the configuration file.
Dynamic_Parameters Function , Data_Array_Name , Data_Array_Offset , Descriptor_Name Baud_Rate , DA_BAUD , 0 , P1
Appendix A.1.2. Configure DIP switches B0 – B3
Dynamic_Parameters
, Descriptor_Name , Node_Name_A , Title_A
, Low_Limit , 1 , 1
, High_Limit , 4194303 , 254
Function Change_Node_ID Change_System_MAC_Addr
, Data_Array_Name , DA_A , DA_A
, Data_Array_Offset , 0 , 0
Appendix A.1.1. Configure DIP switches A0-A7
Data_Arrays Data_Array_Name , Data_Format , Data_Array_Length , Data_Array_Function , Scan_Interval DA_A , UINT16 , 1 , Dip_Switches_A , 2s DA_B , BAUD , 1 , Dip_Switches_B , 2s DA_S , UINT16 , 1 , Dip_Switches_S , 2s
Appendix A.1. QuickServer DIP Switch configuration
Appendix A Useful Features
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 18 of 30
The S0 - S3 DIP switch selection is read directly into a Data Array. This Data Array value can be used for customized operations such as config file selection which allows a FieldServer to be loaded with several configurations / profiles that are selected based on a Data Array value. See the example below where a Config Table and Dynamic Parameter can be used in conjunction with the DIP Switches to achieve this type of customization. .
In this example, 5 configs will need to be downloaded to the QuickServer: config.csv (base config), profile1.csv, profile2.csv, profile3.csv and profile4.csv. The profile configs will be configured as per FieldServer standard configuration templates. The base config will be used to select the appropriate profile config to load.
Note: In this example the value 0 has no operation, so if 0 is read on the dip switches no profile will be loaded. Similarly values larger than 4 will be ignored.
Dynamic_Parameters
Function , Data_Array_Name , Data_Array_Offset , Config_Table_Name , Restart_Method
load_csv , DA_LOAD_CSV , 2 , csvfilenames , On_Change
Config_Table
Config_Table_Name , Table_String , Table_Index_Value
csvfilenames , profile1.csv , 1 // Profile config 1
csvfilenames , profile2.csv , 2 // Profile config 2
csvfilenames , profile3.csv , 3 // Profile config 3
csvfilenames , profile4.csv , 4 // Profile config 4
Data_Arrays Data_Array_Name , Data_Format , Data_Array_Length , Data_Array_Function , Scan_Interval DA_LOAD_CSV , UINT16 , 1 , Dip_Switches_S , 2s
Column Title
Function
Legal Values
Config_Table_Name
Provide name for Config Table
Up to 32 alphanumeric characters
Table_Index_Value
A unique value that will be used to identify which table entry needs to be used.
Table_String
A String value, representing the filename of the profile to be loaded for the corresponding Table_Index_Value.
1-10, 000
Restart_Method*
The specified config or profile is loaded on start-up. If the parameter is configured as On_Change, the QuickServer will restart and reload the specified config every time the Data_Array value changes. Otherwise the config or profile will remain unchanged even if the Data_Array value changes.
On_Change, Never, _
Appendix A.1.3. Configure DIP switches S0 – S3
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 19 of 30
Confirm that the network cabling is correct.
Confirm that the computer network card is operational and correctly configured.
Confirm that there is an Ethernet adapter installed in the PC’s Device Manager List, and that it is configured to run the TCP/IP protocol.
Check that the IP netmask of the PC matches the QuickServer. The Default IP Address of the QuickServer is
192.168.2.X, Subnet Mask is 255.255.255.0.
o
o
o
o
Go to Start|Run Type in ipconfig” The account settings should be displayed. Ensure that the IP address is 102.168.2.X and the netmask 255.255.255.0
Ensure that the PC and QuickServer are on the same IP Network, or assign a Static IP Address to the PC on the
192.168.2.0 network.
If using Windows XP or later, ensure that the firewall is disabled.
Ensure that all other Ethernet cards active on the PC, especially wireless adapters are disabled.
Refer to the FieldServer Troubleshooting Guide which can be found at www.fieldserver.com/QS_Support/ for further information
Before contacting Technical support to report an issue, go to Start|Programs|FieldServer utilities|Tools and run the FST_Diag program. Take a log (See ENote0058 in the folder called Library on the USB Flash Drive). Send this log together with a detailed description of the problem to
support@fieldserver.com
for evaluation.
Note that while all necessary documentation is shipped with the FieldServer on the USB flash drive, these
documents are constantly being updated.
www.fieldserver.com/QS_Support/
Newer versions may be available on the web at
Please Note that RFC standards allocate the IP address range of 192.0.0.0 through to 223.255.255.255 to be used in Class-C subnetting (i.e.: Subnets listed as 255.255.255.xxx, where xxx can vary based on filtering required).
Consequently, the IP stack for this product will not allow any IP addresses in this range to be allocated a subnet that does not fall within the Class C range.
Appendix B.3. Notes Regarding Subnets and Subnet Masks
Appendix B.2. Technical support
Appendix B.1. Communicating with the QuickServer over the Network
Appendix B Troubleshooting Tips
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 20 of 30
FieldServer Technologies warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. FieldServer Technologies will repair or replace any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by FieldServer Technologies personnel.
All warranties hereunder are contingent upon proper use in the application for which the p roduct was intended and do not cover products which have been modified or repaired without FieldServer Technologies approval or which have been subjected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables or to any damage resulting from battery leakage.
In all cases FieldServer Technology’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.
Except for the express warranty stated above, FieldServer Technologies disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of FieldServer Technologies for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product.
Appendix C Limited 2 year Warranty
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 21 of 30
LED’s
Light
Description RTC
To Be Determined
RUN
RUN LED will flash 20 seconds after power up, signifying normal operation. The QuickServer will be able to access FS-GUI (refer to Section Error! Reference source not found. for more information) once this LED starts flashing. During the first 20 seconds, the LED should be off
ERR
The ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on the FieldServer. If this occurs, immediately report the related system error” shown in the error screen of the FS-GUI interface to FieldServer Technologies for evaluation.
RX
On normal operation of PS-QS-1010, the RX LED will flash when a message is received on the field port of the QuickServer.
TX
On normal operation of PS-QS-1010, the TX LED will flash when a message is sent on the field port of the QuickServer
PWR
This is the power light and should show steady green at all times when the QuickServer is powered.
Appendix D.1.1. LED Functions
Appendix D.1. PS-QS-1010/1510-XXXX LED’s
Appendix D Reference
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 22 of 30
Note that the lid on top of the QuickServer has to be removed in order to see the LED’s
LON
TX
LON RX
RUN
PWR
SYS ERR
PIC RUN PIC ERR UNUSED UNUSED
COM ERR
CONFIG ERR
NODE OFFLINE
powered.
steady red light will indicate a communication error has occurred. To establish the cause of the
steady amber light will indicate a configuration error exists in the active configuration. See the
Light
Description
PWR
This is the power light and should show steady green at all times when the PS-QS-1011-XXXX is
SYS ERR (LED1)
The SYS ERR LED will flash once on power up and flash once 15 seconds after power up. A steady red light will indicate there is a system error on the PS-QS-1011-XXXX. If this occurs, immediately report the related system error” shown in the error screen of the FS_GUI interface to FieldServer Technologies for evaluation.
COMM ERR (LED2)
The COMM ERR LED will flash once on power up and flash once 15 seconds after power up. A
error, go to the error screen of the RUI interface.
Config ERR (LED3)
The Config ERR LED will flash once on power up and flash once 15 seconds after power up. A
Error Screen in the Remote User Interface for a description of the configuration error.
Node Offline (LED4)
The Node Offline LED will flash once on power up and flash once 15 seconds after power up. If the Node Offline LED stays on solid, a Node Offline condition has occurred.
RUN (PIO)
The RUN LED will start flashing 20 seconds after power indicating normal operation. The PS-QS­1011-XXXX will be able to access FS-GUI once this LED starts flashing.
PIC RUN (LED5)
The PIC RUN LED will flash indicating normal operation.
PIC ERR (LED6)
The PIC ERR LED will go on solid indicating there is a PIC error.
Appendix D.2. PS-QS-1011/1511-XXXX LED’s
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 23 of 30
port of the QuickServer.
Lon port of the QuickServer.
For UL compliance, the following instructions must be met when operating the QuickServer.
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.
The interconnecting power connector and power cable shall:
Comply with local electrical code.
Be suited to the expected operating temperature range.
Meet the current and voltage rating for the QuickServer/Net
Furthermore, the interconnecting power cable shall:
Be of length not exceeding 3.05m (118.3”)
Appendix D.4. Compliance with UL Regulations
Driver
Code
BACnet/IP – BACnet MS/TP
0285
BACnet/IP – LonWorks
0131
JCI Metasys N2 – LonWorks
0097
JCI Metasys N2– BACnet MS/TP
0309
JCI Metasys N2– BACnet/IP
0122
Modbus RTU – BACnet MS/TP
0367
Modbus RTU – BACnet/IP
0104
Modbus RTU – JCI Metasys N2
0038
Modbus RTU – LonWorks
0085
Modbus TCP – BACnet/IP
0237
Modbus TCP – LonWorks
0154
Modbus TCP – BACnet MS/TP
0419
Modbus TCP – JCI Metasys N2
0117
SNMP – BACnet/IP
0333
SNMP – LonWorks
0337
SNMP – JCI Metasys N2
0150
Add BACnet MS/TP - LonWorks
0345
Appendix D.3. QuickServer PS-QS-101X DCC
Light
Description
LON-TX LED
On normal operation of PS-QS-1011/1511-XXXX, the TX LED will flash when a message is sent on the Lon
LON-RX LED
On normal operation of PS-QS-1011/1511-XXXX, the RX LED will flash when a message is received on the
LON-SRV LED (next to Lon port)
The LON-SRV LED will flash if the PS-QS-1011/1511-XXXX is configured for implicit addressing and not commissioned. LED will be off if the PS-QS-1011/1511-XXXX is configured for implicit addressing and commissioned or if it is configured for explicit addressing. LED 7
Not used
LED 8
Not used
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 24 of 30
Be constructed of materials rated VW-1 or FT-1 or better.
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in a Restricted Access Area requiring a key or a special tool to gain access
This device must not be connected to a LAN segment with outdoor wiring.
Address
A0
A1
A2
A3
A4
A5
A6
A7
0
Off
Off
Off
Off
Off
Off
Off
Off
1
On
Off
Off
Off
Off
Off
Off
Off
2
Off
On
Off
Off
Off
Off
Off
Off
3
On
On
Off
Off
Off
Off
Off
Off 4 Off
Off
On
Off
Off
Off
Off
Off
5
On
Off
On
Off
Off
Off
Off
Off
6
Off
On
On
Off
Off
Off
Off
Off
7
On
On
On
Off
Off
Off
Off
Off
8
Off
Off
Off
On
Off
Off
Off
Off
9
On
Off
Off
On
Off
Off
Off
Off
10
Off
On
Off
On
Off
Off
Off
Off
11
On
On
Off
On
Off
Off
Off
Off
12
Off
Off
On
On
Off
Off
Off
Off
13
On
Off
On
On
Off
Off
Off
Off
14
Off
On
On
On
Off
Off
Off
Off
15
On
On
On
On
Off
Off
Off
Off
16
Off
Off
Off
Off
On
Off
Off
Off
17
On
Off
Off
Off
On
Off
Off
Off
18
Off
On
Off
Off
On
Off
Off
Off
19
On
On
Off
Off
On
Off
Off
Off
20
Off
Off
On
Off
On
Off
Off
Off
21
On
Off
On
Off
On
Off
Off
Off
22
Off
On
On
Off
On
Off
Off
Off
23
On
On
On
Off
On
Off
Off
Off
24
Off
Off
Off
On
On
Off
Off
Off
25
On
Off
Off
On
On
Off
Off
Off
26
Off
On
Off
On
On
Off
Off
Off
27
On
On
Off
On
On
Off
Off
Off
28
Off
Off
On
On
On
Off
Off
Off
29
On
Off
On
On
On
Off
Off
Off
30
Off
On
On
On
On
Off
Off
Off
31
On
On
On
On
On
Off
Off
Off
32
Off
Off
Off
Off
Off
On
Off
Off
33
On
Off
Off
Off
Off
On
Off
Off
34
Off
On
Off
Off
Off
On
Off
Off
35
On
On
Off
Off
Off
On
Off
Off
36
Off
Off
On
Off
Off
On
Off
Off
37
On
Off
On
Off
Off
On
Off
Off
Appendix D.5. Address DIP Switch Settings
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 25 of 30
Address
A0
A1
A2
A3
A4
A5
A6
A7
38
Off
On
On
Off
Off
On
Off
Off
39
On
On
On
Off
Off
On
Off
Off
40
Off
Off
Off
On
Off
On
Off
Off
41
On
Off
Off
On
Off
On
Off
Off
42
Off
On
Off
On
Off
On
Off
Off
43
On
On
Off
On
Off
On
Off
Off
44
Off
Off
On
On
Off
On
Off
Off
45
On
Off
On
On
Off
On
Off
Off
46
Off
On
On
On
Off
On
Off
Off
47
On
On
On
On
Off
On
Off
Off
48
Off
Off
Off
Off
On
On
Off
Off
49
On
Off
Off
Off
On
On
Off
Off
50
Off
On
Off
Off
On
On
Off
Off
51
On
On
Off
Off
On
On
Off
Off
52
Off
Off
On
Off
On
On
Off
Off
53
On
Off
On
Off
On
On
Off
Off
54
Off
On
On
Off
On
On
Off
Off
55
On
On
On
Off
On
On
Off
Off
56
Off
Off
Off
On
On
On
Off
Off
57
On
Off
Off
On
On
On
Off
Off
58
Off
On
Off
On
On
On
Off
Off
59
On
On
Off
On
On
On
Off
Off
60
Off
Off
On
On
On
On
Off
Off
61
On
Off
On
On
On
On
Off
Off
62
Off
On
On
On
On
On
Off
Off
63
On
On
On
On
On
On
Off
Off
64
Off
Off
Off
Off
Off
Off
On
Off
65
On
Off
Off
Off
Off
Off
On
Off
66
Off
On
Off
Off
Off
Off
On
Off
67
On
On
Off
Off
Off
Off
On
Off
68
Off
Off
On
Off
Off
Off
On
Off
69
On
Off
On
Off
Off
Off
On
Off
70
Off
On
On
Off
Off
Off
On
Off
71
On
On
On
Off
Off
Off
On
Off
72
Off
Off
Off
On
Off
Off
On
Off
73
On
Off
Off
On
Off
Off
On
Off
74
Off
On
Off
On
Off
Off
On
Off
75
On
On
Off
On
Off
Off
On
Off
76
Off
Off
On
On
Off
Off
On
Off
77
On
Off
On
On
Off
Off
On
Off
78
Off
On
On
On
Off
Off
On
Off
79
On
On
On
On
Off
Off
On
Off
80
Off
Off
Off
Off
On
Off
On
Off
81
On
Off
Off
Off
On
Off
On
Off
82
Off
On
Off
Off
On
Off
On
Off
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 26 of 30
Address
A0
A1
A2
A3
A4
A5
A6
A7
83
On
On
Off
Off
On
Off
On
Off
84
Off
Off
On
Off
On
Off
On
Off
85
On
Off
On
Off
On
Off
On
Off
86
Off
On
On
Off
On
Off
On
Off
87
On
On
On
Off
On
Off
On
Off
88
Off
Off
Off
On
On
Off
On
Off
89
On
Off
Off
On
On
Off
On
Off
90
Off
On
Off
On
On
Off
On
Off
91
On
On
Off
On
On
Off
On
Off
92
Off
Off
On
On
On
Off
On
Off
93
On
Off
On
On
On
Off
On
Off
94
Off
On
On
On
On
Off
On
Off
95
On
On
On
On
On
Off
On
Off
96
Off
Off
Off
Off
Off
On
On
Off
97
On
Off
Off
Off
Off
On
On
Off
98
Off
On
Off
Off
Off
On
On
Off
99
On
On
Off
Off
Off
On
On
Off
100
Off
Off
On
Off
Off
On
On
Off
101
On
Off
On
Off
Off
On
On
Off
102
Off
On
On
Off
Off
On
On
Off
103
On
On
On
Off
Off
On
On
Off
104
Off
Off
Off
On
Off
On
On
Off
105
On
Off
Off
On
Off
On
On
Off
106
Off
On
Off
On
Off
On
On
Off
107
On
On
Off
On
Off
On
On
Off
108
Off
Off
On
On
Off
On
On
Off
109
On
Off
On
On
Off
On
On
Off
110
Off
On
On
On
Off
On
On
Off
111
On
On
On
On
Off
On
On
Off
112
Off
Off
Off
Off
On
On
On
Off
113
On
Off
Off
Off
On
On
On
Off
114
Off
On
Off
Off
On
On
On
Off
115
On
On
Off
Off
On
On
On
Off
116
Off
Off
On
Off
On
On
On
Off
117
On
Off
On
Off
On
On
On
Off
118
Off
On
On
Off
On
On
On
Off
119
On
On
On
Off
On
On
On
Off
120
Off
Off
Off
On
On
On
On
Off
121
On
Off
Off
On
On
On
On
Off
122
Off
On
Off
On
On
On
On
Off
123
On
On
Off
On
On
On
On
Off
124
Off
Off
On
On
On
On
On
Off
125
On
Off
On
On
On
On
On
Off
126
Off
On
On
On
On
On
On
Off
127
On
On
On
On
On
On
On
Off
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 27 of 30
Address
A0
A1
A2
A3
A4
A5
A6
A7
128
Off
Off
Off
Off
Off
Off
Off
On
129
On
Off
Off
Off
Off
Off
Off
On
130
Off
On
Off
Off
Off
Off
Off
On
131
On
On
Off
Off
Off
Off
Off
On
132
Off
Off
On
Off
Off
Off
Off
On
133
On
Off
On
Off
Off
Off
Off
On
134
Off
On
On
Off
Off
Off
Off
On
135
On
On
On
Off
Off
Off
Off
On
136
Off
Off
Off
On
Off
Off
Off
On
137
On
Off
Off
On
Off
Off
Off
On
138
Off
On
Off
On
Off
Off
Off
On
139
On
On
Off
On
Off
Off
Off
On
140
Off
Off
On
On
Off
Off
Off
On
141
On
Off
On
On
Off
Off
Off
On
142
Off
On
On
On
Off
Off
Off
On
143
On
On
On
On
Off
Off
Off
On
144
Off
Off
Off
Off
On
Off
Off
On
145
On
Off
Off
Off
On
Off
Off
On
146
Off
On
Off
Off
On
Off
Off
On
147
On
On
Off
Off
On
Off
Off
On
148
Off
Off
On
Off
On
Off
Off
On
149
On
Off
On
Off
On
Off
Off
On
150
Off
On
On
Off
On
Off
Off
On
151
On
On
On
Off
On
Off
Off
On
152
Off
Off
Off
On
On
Off
Off
On
153
On
Off
Off
On
On
Off
Off
On
154
Off
On
Off
On
On
Off
Off
On
155
On
On
Off
On
On
Off
Off
On
156
Off
Off
On
On
On
Off
Off
On
157
On
Off
On
On
On
Off
Off
On
158
Off
On
On
On
On
Off
Off
On
159
On
On
On
On
On
Off
Off
On
160
Off
Off
Off
Off
Off
On
Off
On
161
On
Off
Off
Off
Off
On
Off
On
162
Off
On
Off
Off
Off
On
Off
On
163
On
On
Off
Off
Off
On
Off
On
164
Off
Off
On
Off
Off
On
Off
On
165
On
Off
On
Off
Off
On
Off
On
166
Off
On
On
Off
Off
On
Off
On
167
On
On
On
Off
Off
On
Off
On
168
Off
Off
Off
On
Off
On
Off
On
169
On
Off
Off
On
Off
On
Off
On
170
Off
On
Off
On
Off
On
Off
On
171
On
On
Off
On
Off
On
Off
On
172
Off
Off
On
On
Off
On
Off
On
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 28 of 30
Address
A0
A1
A2
A3
A4
A5
A6
A7
173
On
Off
On
On
Off
On
Off
On
174
Off
On
On
On
Off
On
Off
On
175
On
On
On
On
Off
On
Off
On
176
Off
Off
Off
Off
On
On
Off
On
177
On
Off
Off
Off
On
On
Off
On
178
Off
On
Off
Off
On
On
Off
On
179
On
On
Off
Off
On
On
Off
On
180
Off
Off
On
Off
On
On
Off
On
181
On
Off
On
Off
On
On
Off
On
182
Off
On
On
Off
On
On
Off
On
183
On
On
On
Off
On
On
Off
On
184
Off
Off
Off
On
On
On
Off
On
185
On
Off
Off
On
On
On
Off
On
186
Off
On
Off
On
On
On
Off
On
187
On
On
Off
On
On
On
Off
On
188
Off
Off
On
On
On
On
Off
On
189
On
Off
On
On
On
On
Off
On
190
Off
On
On
On
On
On
Off
On
191
On
On
On
On
On
On
Off
On
192
Off
Off
Off
Off
Off
Off
On
On
193
On
Off
Off
Off
Off
Off
On
On
194
Off
On
Off
Off
Off
Off
On
On
195
On
On
Off
Off
Off
Off
On
On
196
Off
Off
On
Off
Off
Off
On
On
197
On
Off
On
Off
Off
Off
On
On
198
Off
On
On
Off
Off
Off
On
On
199
On
On
On
Off
Off
Off
On
On
200
Off
Off
Off
On
Off
Off
On
On
201
On
Off
Off
On
Off
Off
On
On
202
Off
On
Off
On
Off
Off
On
On
203
On
On
Off
On
Off
Off
On
On
204
Off
Off
On
On
Off
Off
On
On
205
On
Off
On
On
Off
Off
On
On
206
Off
On
On
On
Off
Off
On
On
207
On
On
On
On
Off
Off
On
On
208
Off
Off
Off
Off
On
Off
On
On
209
On
Off
Off
Off
On
Off
On
On
210
Off
On
Off
Off
On
Off
On
On
211
On
On
Off
Off
On
Off
On
On
212
Off
Off
On
Off
On
Off
On
On
213
On
Off
On
Off
On
Off
On
On
214
Off
On
On
Off
On
Off
On
On
215
On
On
On
Off
On
Off
On
On
216
Off
Off
Off
On
On
Off
On
On
217
On
Off
Off
On
On
Off
On
On
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
Page 29 of 30
Address
A0
A1
A2
A3
A4
A5
A6
A7
218
Off
On
Off
On
On
Off
On
On
219
On
On
Off
On
On
Off
On
On
220
Off
Off
On
On
On
Off
On
On
221
On
Off
On
On
On
Off
On
On
222
Off
On
On
On
On
Off
On
On
223
On
On
On
On
On
Off
On
On
224
Off
Off
Off
Off
Off
On
On
On
225
On
Off
Off
Off
Off
On
On
On
226
Off
On
Off
Off
Off
On
On
On
227
On
On
Off
Off
Off
On
On
On
228
Off
Off
On
Off
Off
On
On
On
229
On
Off
On
Off
Off
On
On
On
230
Off
On
On
Off
Off
On
On
On
231
On
On
On
Off
Off
On
On
On
232
Off
Off
Off
On
Off
On
On
On
233
On
Off
Off
On
Off
On
On
On
234
Off
On
Off
On
Off
On
On
On
235
On
On
Off
On
Off
On
On
On
236
Off
Off
On
On
Off
On
On
On
237
On
Off
On
On
Off
On
On
On
238
Off
On
On
On
Off
On
On
On
239
On
On
On
On
Off
On
On
On
240
Off
Off
Off
Off
On
On
On
On
241
On
Off
Off
Off
On
On
On
On
242
Off
On
Off
Off
On
On
On
On
243
On
On
Off
Off
On
On
On
On
244
Off
Off
On
Off
On
On
On
On
245
On
Off
On
Off
On
On
On
On
246
Off
On
On
Off
On
On
On
On
247
On
On
On
Off
On
On
On
On
248
Off
Off
Off
On
On
On
On
On
249
On
Off
Off
On
On
On
On
On
250
Off
On
Off
On
On
On
On
On
251
On
On
Off
On
On
On
On
On
252
Off
Off
On
On
On
On
On
On
253
On
Off
On
On
On
On
On
On
254
Off
On
On
On
On
On
On
On
255
On
On
On
On
On
On
On
On
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
QuickServer Start-up Guide
4 Auto-baud is only supported for BACnet MS/TP
Baud
B0
B1
B2
B3
Auto
4
Off
Off
Off
Off
110
On
Off
Off
Off
300
Off
On
Off
Off
600
On
On
Off
Off
1200
Off
Off
On
Off
2400
On
Off
On
Off
4800
Off
On
On
Off
9600
On
On
On
Off
19200
Off
Off
Off
On
20833
On
Off
Off
On
28800
Off
On
Off
On
38400
On
On
Off
On
57600
Off
Off
On
On
76800
On
Off
On
On
115200
Off
On
On
On
Appendix D.6. Baud DIP Switch Settings
ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call
+1 661.716.5100
Page 30 of 30