FieldServer Honeywell Zellweger IR-148 FS-8700-102, Honeywell Zellweger IR-148 Driver Manual

Driver Version:
1.02
Document Revision:
3
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after September 2009
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-102 Honeywell Zellweger IR-148
A Sierra Monitor Company
FS-FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Table of Contents
TABLE OF CONTENTS
1 Honeywell Zellweger IR-148 Description ........................................................................................................ 3
2 Driver Scope of Supply ................................................................................................................................... 3
2.1 Supplied by FieldServer Technologies for this driver ..................................................................................... 3
3 Hardware Connections ................................................................................................................................... 4
3.1 Connection Notes .......................................................................................................................................... 4
4 Data Array Parameters ................................................................................................................................... 5
5 Configuring the FieldServer as a Honeywell Zellweger IR-148 Client .............................................................. 6
5.1 Client Side Connection Descriptors ............................................................................................................... 6
5.2 Client Side Node Descriptors ......................................................................................................................... 7
5.3 Client Side Map Descriptors........................................................................................................................... 7
5.3.1 FieldServer Related Map Descriptor Parameters ................................................................................... 7
5.3.2 Driver Related Map Descriptor Parameters ........................................................................................... 7
5.3.3 Map Descriptor Example. ....................................................................................................................... 8
6 Configuring the FieldServer as a Honeywell Zellweger IR-148 Server ............................................................. 9
6.1 Server Side Connection Descriptors .............................................................................................................. 9
6.2 Server Side Node Descriptors ...................................................................................................................... 10
6.3 Server Side Map Descriptors........................................................................................................................ 11
6.3.1 FieldServer Specific Map Descriptor Parameters ................................................................................. 11
6.3.2 Driver Specific Map Descriptor Parameters ......................................................................................... 11
6.3.3 Map Descriptor Example 1 Server using Data Array: ........................................................................... 12
6.3.4 Map Descriptor Example 2: - Server using INI file: ............................................................................... 13
Appendix A. Useful Features ................................................................................................................................ 14
Appendix A.1. How Data is stored by the Driver. .................................................................................................... 14
Appendix A.1.1. One Set of consecutive Data Array elements per point/sensor. ............................................. 14
Appendix A.1.2. Extended storage ................................................................................................................... 14
Appendix B. Reference ........................................................................................................................................ 16
Appendix B.1. Supported Functions at a glance ...................................................................................................... 16
Appendix B.2. Driver Error Messages ...................................................................................................................... 16
Appendix B.3. Driver stats ....................................................................................................................................... 17
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Page 3 of 17
FieldServer Mode
Nodes
Comments
Client
3
Tested only 2 Nodes (IR-148 8 Point and IR-148 4 point) on separate networks
Server
3
Developed to test Client side of the Driver.
FieldServer Technologies PART #
Description
FS-8917-16
RJ45 to terminal connector cable.
1 Honeywell Zellweg er IR-148 Descr i pt ion
The Honeywell Infrared Gas Monitor (Model IR-148) detects solvents and gases such as HCFCs, HFCs and PFCs. IR­148 can have 1, 4 or 8 sampling points. This InfraTox driver reports gas values, alarms and troubles for each point.
The serial driver can emulate a Client or a Server. The FieldServer and Zellweger device are connected using a RS­485 network.
As a Client:
The driver listens passively for messages from the IR-148 unit and stores data extracted from the messages. The driver cannot poll the IR-148 device for Data. The driver records some additional data age information (which is
stored in the FieldServer’s Data Arrays) because messages do not always contain information about all sensors and
depending on the IR-148 operational mode (e.g. Locked mode.), may never contain information other than for one sensor.
As a Server:
The server side if this driver has been developed primarily to test the Client side driver as part of FieldServer’s QA program. The driver sends messages reporting the state of the samples. The server driver can also be locked to report the status/value of one particular sample channel.
It is possible to connect up to three Honeywell Zellweger units (IR-148) on one RS-485 network provided that one unit is configured as a single point unit (IR-148 1 point), one as a 4-point unit (IR-148 4 point) and the other as an 8 point unit (IR-148 8-point). At this stage one device with 8 points and one with 4 points have been tested seperately.
To allow for the possibility that the device is connected on a RS-485 network with other devices (such as the relay module option) messages that are not 49 bytes long and which do not begin with 0xB1 will be ignored. The Driver will, however, provide statistics for the ignored as well as the processed messages.
To see supported messages and the way the Driver stores Data, refer to Appendix A.1
Max Nodes Supported
2 Driver Sc op e of Supply
2.1 SUPPLIED BY FIELD SERVER TECHNOLOGIES FOR THI S DRIVER
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Page 4 of 17
FS-8917-16
FS-X40
OR
FS-X30
GND
-
+
GND
-
+
FG
R1R2
Connect to R1 or R2 Port
+
-
G
OTHER DEVICES
INFRATOX UNIT
+
-
G
OTHER DEVICES
INFRATOX UNIT
ORANGE/WHITE
BROWN
BLUE/WHITE
FS-X20
Serial
3 Hardware Connect i o ns
The FieldServer is connected to the Honeywell Zellweger IR-148 Device as shown in connection drawing.
Configure the device according to manufacturer’s instructions
3.1 CONNE CTION NOTES
Other devices must not transmit Honeywell Zellweger IR-148 49 byte messages If connecting to the X-20, the serial port must be configured for RS-485 connection. It is possible to connect to serial ports on the X-30 and X-40 with the use of a RS-232 to RS-485 convertor. If connection problems are experienced when connecting with RS-485, remove the GND wire.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Page 5 of 17
Section Title
Data_Arrays
Column Title
Function
Legal Values
Data_Array_Name
Provide name for Data Array
Up to 15 alphanumeric characters
Data_Array_Format
Provide data format. Each Data Array can only take on one format.
Float, Bit, UInt16, SInt16, Packed_Bit, Byte, Packed_Byte, Swapped_Byte
Data_Array_Length
Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.
1-10,000 // Data Arrays
Data_Arrays
Data_Array_Name
, Data_Format
, Data_Array_Length
DA_R1
, Float
, 100
DA_R2
, Float
, 100
DA_CTL_R1
, Uint16
, 1
DA_CTL_R2
, Uint16
, 1
4 Data Array Par am eters
Data Arrays are “protocol neutral” data buffers for storage of data to be passed between protocols. It is necessary to declare the data format of each of the Data Arrays to facilitate correct storage of the relevant data.
Example
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual Page 6 of 17
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected to the FieldServer
P1-P8 (with 232/485 converter), R1­R21
Protocol
Specify protocol used
InfraTox or Infra-Tox
Baud*
Specify baud rate
19200 (Vendor limitation)
Parity*
Specify parity
None (Vendor limitation)
Data_Bits*
Specify data bits
8 (Vendor limitation)
Stop_Bits*
Specify stop bits
1
// Client Side Connections
Connections
Port
, Protocol
, Baud
, Parity
, Stop_Bits
R1
, InfraTox
, 19200
, None
, 1
5 Configuring th e Fi e l dServer as a Honeywell Zel l weger IR-148 Client
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Honeywell Zellweger IR-148 Server having one or eight sensors.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Honeywell Zellweger IR-148 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
5.1 CLIENT SIDE CONNECTION DESC RIPTORS
Example
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com