FieldServer Gamewell FCI 7100 Series, FS-8700-112, Gamewell FS-8700-112 Driver Manual

Driver Version:
1.01
Document Revision:
1
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-112 Gamewell-FCI 7100 Series
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after April 2011
A Sierra Monitor Company
FS-8700-112 Gamewell-FCI 7100 Driver Manual Table of Contents
TABLE OF CONTENTS
1 FCI 7100 Series Serial Driver Description ........................................................................................................ 3
2 Driver Scope of Supply ................................................................................................................................... 4
2.1 Supplied by FieldServer Technologies for this driver ..................................................................................... 4
2.2 Provided by the Supplier of 3rd Party Equipment .......................................................................................... 4
2.2.1 Required 3rd Party Hardware ................................................................................................................. 4
3 Hardware Connections ................................................................................................................................... 5
4 Data Array Parameters ................................................................................................................................... 6
5 Configuring the FieldServer as a GAmewell-FCI 7100 Series Client ................................................................. 7
5.1 Client Side Connection Parameters ............................................................................................................... 7
5.2 Client Side Node Parameters ......................................................................................................................... 7
5.3 Client Side Map Descriptors........................................................................................................................... 8
5.3.1 FieldServer Related Map Descriptor Parameters ................................................................................... 8
5.3.2 Driver Related Map Descriptor Parameters ........................................................................................... 8
5.4 Map Descriptor Example 1 – Sensor / Module Events ................................................................................ 10
5.5 Map Descriptor Example 2 – Bit Storage ..................................................................................................... 11
6 Configuring the FieldServer as a Gamewell-FCI 7100 Series Server ............................................................... 12
Appendix A. Useful Features ................................................................................................................................ 13
Appendix A.1. Extending the Event Table ................................................................................................................ 13
Appendix A.1.1. Map Descriptor Parameters ................................................................................................... 13
Appendix A.1.2. Example 1: Index value of 'Trouble' is updated to a new value of 100 ................................. 13
Appendix A.1.3. Example 2: New Entry is added ............................................................................................ 13
Appendix A.2. Panel Synchronization ...................................................................................................................... 13
Appendix A.3. What happens when the panel sends a Reset Message .................................................................. 14
Appendix A.4. Networked Panels. ........................................................................................................................... 14
Appendix B. Troubleshooting ............................................................................................................................... 15
Appendix B.1. Driver Error Messages. ..................................................................................................................... 15
Appendix B.2. Driver Stats Exposed. ........................................................................................................................ 17
Appendix C. Reference ......................................................................................................................................... 19
Appendix C.1. Events and Event Categories ............................................................................................................ 19
Appendix C.2. How Data is stored ........................................................................................................................... 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
FS-8700-112 Gamewell-FCI 7100 Driver Manual Page 3 of 20
FieldServer Mode
Nodes
Comments
Client
1
1 Node per serial port. If there is more than one alarm panel they can be networked and configured to send event data to the primary panel. The driver can process messages which identify the node of origin.
Server
1
1 Node per serial port
1 FCI 7100 SERIES SERIAL D R I V E R DESC R I P T I ON
The FCI 7100 Series System Control Units are manufactured by Fire Control Instruments. A 7100 with an enabled serial port can transmit data to a FieldServer which can, in turn, make the data available to other devices including those which communicate using different protocols (e.g. BACnet)
This passive Client driver does not poll for data, nor does it send data or commands to the 7100. Messages received from the 7100 are ignored or stored on the FieldServer depending on the status of the panel. The method of message processing and location on the FieldServer is determined in the FieldServer configuration file. Once stored in the FieldServer the data is available to be read or written using other protocols such as BACnet.
No automatic panel data synchronization technique exists. The data in the FieldServer and the panel status have to be synchronized manually. This typically requires a panel reset.
Since the driver cannot send data or commands to the 7100 it cannot be used to acknowledge, silence or reset alarms and other events.
The driver can process the single line messages sent from 7100 firmware versions earlier than 2.20 and 3 line messages produced in firmware versions 2.20 and later. Processing of 3 line messages requires the 20 character System ID label to be defined.
The driver can process messages from networked panels. The driver connects to the main panel. Subsidiary panels are configured to send event data to the main panel which then sends messages to the FieldServer. If the panel is configured to send 3 line messages then the source node information is sent in the line preceding the event and the driver uses this to determine the panel at which the event originated and to store data appropriately.
The driver provides both client and server emulation. The server side of the driver is intended to support FieldServer’s Quality Assurance program and is not intended to provide complete emulation of a 7100 and is thus not fully documented. Should you require the Server side functionality to be documented and enhanced, please contact FieldServer’s sales group.
Max Nodes Supported
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
FS-8700-112 Gamewell-FCI 7100 Driver Manual Page 4 of 20
FieldServer Technologies Part #
Description
23069
RJ45-RJ11/12 Cable assembly for FS connection to FCI panel.
2 DRIVER SCOPE OF SUP PLY
2.1 Sup plied by FieldServer Technolo gies for this driver
2.2 Provide d b y t he Supplier of 3
rd
Party Eq ui pme n t
2.2.1 Requ i red 3
rd
Party Ha r d w a r e
FCI Panel must be equipped with a RS-232 Serial Printer Port. FCI Panel must be equipped with a PTRN module for isolation of the serial port.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
FS-8700-112 Gamewell-FCI 7100 Driver Manual Page 5 of 20
FCI 7100 Series Panel
FieldServer
Connect to one of the RS-232
Ports on the FieldServer
P1
18
FieldServer connects using
pre-assembled RJ45 to RJ11
cable (FS-8917-24) to J3 on
FCI 7100 board
Connector J3
FS Function
RJ45 Pin#
RJ11/12 Pin
RJ11/12 Function
Color
RX 1 2
TX
White
GND
4 3 GND
Green
TX 8 5
RX
Blue
Connect to J3. (Label on right)
3 HARDWARE CONNECTION S
Connector Pinouts
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
FS-8700-112 Gamewell-FCI 7100 Driver Manual Page 6 of 20
Section Title
Data_Arrays
Column Title
Function
Legal Values
Data_Array_Name
Provide name for Data Array
Up to 15 alphanumeric characters
Data_Array_Format
Provide data format. Each Data Array can only take on one format.
Float, Bit, Uint16, Sint16, Byte.
Data_Array_Length
Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.
1-10, 000 // Data Arrays
Data_Arrays
Data_Array_Name
, Data_Array_Format
, Data_Array_Length
DA_AI_01
, UInt16
, 200
DA_AO_01
, UInt16
, 200
DA_DI_01
, Bit
, 200
DA_DO_01
, Bit
, 200
4 DATA ARRAY PARAMETERS
Data Arrays are “protocol neutral” data buffers for storage of data to be passed between protocols. It is necessary
to declare the data format of each of the Data Arrays to facilitate correct storage of the relevant data.
Example
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Loading...