The Carrier DataLink driver allows the FieldServer to transfer data to and from devices over
either RS-232 or RS-485 using Carrier DataLink protocol. The FieldServer can emulate either a
Server or Client.
The Carrier DataLink Serial Driver allows variables to be read and written in system elements
connected to a Carrier Comfort Network communication bus. Up to 15 system elements may be
connected to a DataLink Device. Display, Occupancy, Set Point Tables and Carrier Comfort
Network (CCN) variables may be read or written.
The DataLink device provides a gateway to CCN devices. This driver polls the DataLink device
which in turn reads/writes data to the CCN devices.
Carrier limits the number of CCN devices that can polled from a DataLink Device as well as the
data that can be transferred between some CCN devices and the DataLink device. For
information on these limitations please consult the Carrier Corporation.
The driver is an active client driver. This means that it initiates read/write polls with the DataLink
device which is expected to provide responses. Server functionality is not intended to provide
full emulation of DataLink Devices but can be extended on request.
The driver is configured to allow data tables to be read from the CCN devices via the DataLink
device. As the tables typically contain more than one data element, the retrieved data is stored
in a number of consecutive FieldServer data array locations in the FieldServer. The individual
values cannot be scaled before they are stored. The driver can provide descriptions for each of
the table values retrieved. Descriptions are stored in ASCII in a separate data array.
The driver can be configured to read a specific variable from a CNN device and store its value
using optional scaling in a configurable location in a FieldServer data array.
The driver can be configured to write a value (using optional scaling) from a FieldServer data
array to a specific variable in a CNN device, provided that the variable allows its value to be
written.
The driver has no advanced knowledge of the CCN devices and their data tables. Therefore it
cannot validate table names or variable names specified in the configuration file. This means
that the driver handles each table in a generic way, without regard for the particular variables
that constitute the tables.
It is important that you understand the limitations and exclusions of this driver. Refer to Section
5.4 for more information.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
The FieldServer is connected to the Carrier DataLink device as shown below. Ensure that the
device to be connected to is in fact the DataLink device and not the DataPort device which is
similar looking.
Configure the DataLink Device according to manufacturer’s instructions. This driver requires
that the DataLink device’s DTPCONFIG table has been configured prior to connection with a
FieldServer. Consult the manufacturer’s information on connecting Carrier Device’s to CCN
network.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
4. Configuring the FieldServer as a Carrier DataLink Client
It is not possible to configure communication with a DataLink device until familiar with the data
available from the devices connected to the DataLink. The DataLink device does not provide a
method for discovering the data tables and variables that are available in all the Carrier devices.
In order to configure the Client it is necessary to know the names of the data tables available in
the devices connected via the CCN network to the data link. A partial list of available tables is
provided in Appendix A.1. If you know the table names and the variable names that you wish to
poll then you have enough information to complete the configuration. If you have table names
but do not know variable names then we provide a method of discovering the variable names.
This method is discussed in chapter 6. If you do not have the table names then you will need to
consult with the Carrier Corporation before proceeding.
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files
provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a Carrier DataLink Server.
The configuration file tells the FieldServer about its interfaces, and the routing of data required.
In order to enable the FieldServer for Carrier DataLink communications, the driver independent
FieldServer buffers need to be declared in the “Data Arrays” section, the destination device
addresses need to be declared in the “Client Side Nodes” section, and the data required from
the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to
do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.
4.1. Data Arrays/Descriptors
Section Title
Data_Arrays
Column Title Function Legal Values
Data_Array_Name Provide name for Data Array
Data_Format
Data_Array_Length
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Modbus station address of physical server node.
These correspond to the ‘devices’ configured in the
DTPConfig. Thus the Node_ID is not the address of
Node_ID
the final CCN device.
The DataLink DTPConfig table maps a device number
(1..15) to a bus number (0-239). Use the Node_ID to
tell the driver which device to use.
Protocol Specify protocol used CarrierDL
Port
Specify which port the device is connected to the
FieldServer
Up to 32 alphanumeric
characters
One of the Data Array names
from “Data Array” section
above
0 to maximum specified in
“Data Array” section above
RDBC, WRBC, WRBX
FS-8700
-
82 Carrier DataLink
Page
9
of 31
4.4.2. Driver Related Map Descriptor Parameters
Column
Title
Node_Name Name of Node to fetch data from
Data type. This parameter is not required
except when defining Map Descriptors
which write DOW (Day of Week) and
Time value to the Carrier devices. When
Data_Type
Length
Address This commonly used parameter is not required for this driver.
Table_Name
Field_Name*
Store_As*
a write Map Descriptor checks the data
type it uses the information to convert the
value extracted from the FieldServer’s
Data Arrays into a suitable format for a
write. Refer to Section 4.4.7.
Length of Map Descriptor. When reading
a compete table, set the length to the
maximum number of data values you
want stored. Additional information on the
length parameter is provided in Appendix
A.5.
The name of the table to be polled, e.g.
DISPLAY. Some system elements have
multiple instances of the same table
name. For example, the Terminal System
Manager has 64 Temperature Zone
configuration tables named TZONE1
though TZONE64. These tables are
accessed by using both the primary &
secondary table names, e.g. ‘TZCONF
TZONE1’
If you wish to read the whole table, leave
the field name blank or specify
‘EVERYTHING’.
Use the Ascii or AsciiLog format when you
are discovering the variables contained in
a table by reading a table. Refer to 1.1
Function Legal Values
One of the node names
specified in “Client Node
Descriptor” above
Occupancy_Time
Occupancy_DOW
1 – 1000
Only ASCII characters are
permitted.
When using the table
name parameter to specify
a primary and secondary
table, leave a single space
between the two names.
Only ASCII characters are
permitted. Field names
never contain spaces.
They may not be longer
than 10 characters long.
Ascii, AsciiLog, Values
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
This example illustrates how to read the entire contents of a table called ‘DISPLAY’. The Map Descriptor is connected to a node
using the node name and a node definition provides a connection to a port. Thus this Map Descriptor is connected to a port via its
node. The FieldServer will use that port to send this poll which will be generated every 5 seconds.
The value extracted from the response will be stored in the array called DA_DISPLAY. Ensure that it is suitable format for storing a
number – FLOAT is suggested. The driver stores the value of the 1
table elements whose values have been successfully stored at is stored at offset zero.
5. Configuring the FieldServer as a Carrier DataLink Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Instruction Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files
provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a Carrier DataLink Client.
The FieldServer can be configured to emulate a Carrier DataLink Device. The use is able to
define a variable number of data tables, allocating a table name a variable number of variables.
The FieldServer may be polled and will respond like a DataLink device. Remote clients can
force variable states by ending write variable commands.
The FieldServer does not emulate any of the alarm buffer/history features of the DataLink
Device.
All variables may be read or written without restriction.
The configuration file tells the FieldServer about its interfaces, and the routing of data required.
In order to enable the FieldServer for Carrier DataLink communications, the driver independent
FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual
node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to
the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to
do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.
Modbus station address of physical server node.
These correspond to the ‘devices’ configured in the
DTPConfig. Thus the Node_ID is not the address of
Node_ID
the final CCN device.
The DataLink DTPConfig table maps a device
number (1...15) to a bus number (0-239). Use the
Node_ID to tell the driver which device to use.
Protocol Specify protocol used CarrierDL
Example
// Server Side Nodes
Nodes
Node_Name, Node_ID, Protocol , Port
FAN1 , 1 , CarrierDL,
It is common to leave Server nodes
unconnected to a port. This means that the
FieldServer can respond with the node’s
data irrespective of which port the request
Function Legal Values
Up to 32
alphanumeric
characters
1-15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
5.3.1. FieldServer Specific Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Name of Data Array where
Data_Array_Name
Data_Array_Location Starting location in Data Array
Function Map Descriptor function Passive
data is to be stored in the
FieldServer
Up to 32 alphanumeric
characters
One of the Data Array names
from “Data Array” section
above
0 to maximum specified in
“Data Array” section above
5.3.2. Driver Specific Map Descriptor Parameters
Column Title Function Legal Values
One of the node
Node_Name Name of Node to fetch data from
Data_Type This commonly used parameter is not required for this driver.
Length of Map Descriptor. When reading a
Length
Address This commonly used parameter is not required for this driver.
Table_Name
Field_Name This is the field/table variable pneumonic.
Field_Description
Field_Units
On_String
compete table, set the length to the maximum
number of data values to be stored. Refer to
1.1.
The name of the table to be polled, e.g.
DISPLAY. Some system elements have
multiple instances of the same table name,
e.g. the Terminal System Manager has 64
Temperature Zone configuration tables
named TZONE1 though TZONE64. These
tables are accessed by using both the
primary & secondary table names, e.g.
‘TZCONF TZONE1’
Returned when a client does a table read. If
units have no meaning for the variable then
leave this field blank or use a single dash.
If the variable has a discrete state, use this
parameter to define the word that describes
the state when the variable’s value is 1.
OR
Use one of the keywords to tell the driver to
send the value of the associated array
elements as a number (keyword=NUMERIC),
names specified in
“Server Node
Descriptor” above
1 – 1000
ASCII characters
only. When using
this parameter to
specify a primary
and secondary table,
leave a single space
between the two
names.
ASCII characters
only. No spaces,
maximum length 10
characters.
ASCII string which
may contain spaces.
NUMERIC
TIME
STRING
DOW
Or any other ASCII
string which may not
contain spaces.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
as a time value formatted as hh:mm
(keyword=TIME) or as a string of bytes
(keyword=STRING) or as an occupancy
string (keyword=DOW).
When using the string keyword the driver
reads x consecutive array elements and
treats them like ASCII character values in
forming the response. X is defined by the
length parameter.
If the variable has a discrete state, use this
Off_String
parameter to define the word that describes
the state when the variable’s value is zero. If
you have used one of the above keywords,
An ASCII string
which may not
contain spaces.
simply put a dash in this field.
Always set the length to 1 unless you use the
Length
key word ‘STRING’ as the On_String
1
parameter.
5.3.3. Timing Parameters
Column Title Function
Specifies time server side waits before responding
Scada_Hold_Timeout
to client that node is offline on FieldServer client
side.
Legal
Values
>1.0s
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Display_MD10, passive, Node_1, DISPLAY, FLTSTAT, Filter Status
FS-8700
-
82 Carrier DataLink
Page
18
of 31
5.4. Driver Limitations and Exclusions
As a client:
• The Carrier DataLink driver is not capable of polling for alarm data. (The RA and AV
functions are not implemented).
• The Carrier DataLink driver dos not validate table or variable names.
• The Carrier DataLink driver does not support the Read Table command with the /C or /N
options.
• The Carrier DataLink driver records a timeout if the DataLink device does not provide the
‘?’ prompt within the user-configurable timeout period.
• Write-thru’s are not supported. The reason for this is that the driver read a composite
data set and the client side Map Descriptors do not contain enough information to format
a write.
As a server:
• The Carrier DataLink driver is not capable of serving alarm data. (RA and AV polls
produce an error response)
• The driver cannot set a discrete variable’s state unless it is set a value of one or zero.
• The driver server does not understand write table or write variable requests where the
requested state is a word like ON or OFF.
• The Carrier DataLink driver does not validate values or states, it simply stores the
values.
• All variables are may be read and written without limitation. The driver has not
implemented the Courier notion of Force Levels.
• There is no command buffer. One command can be processed at a time.
• The driver responds to all Read Table commands as if the /Y option was used. The
driver does not support the /C or /N options.
• The Carrier DataLink driver does not support the control character commands CTRLC/S/Q
General
• The Carrier DataLink driver is not capable of configuring the DataLink device. Software
provided by the Carrier Corporation is required to do this. The DataLink device requires
configuration, so that connects to the appropriate CCN devices on the CCN
communications network.
• The driver cannot be configured to act as what the Carrier Corporation identify as an
‘Alarm Acknowledger’.
• If the total length of the response from a read table query is more than 3000 bytes long,
the driver will produce an error.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
The following fragment from the error log is typical of the response to a Map Descriptor like the one above.
Ascii Dump Requested for MD=<Md1> Table=<DISPLAY>
DEV 02 DISPLAY
Desired Mode Off MODE
Equipment Status NORMAL ALARM
Controlling Setpoint 75.0 dF CSPT
Controlling Temperature -40.0 dF SPT
Space Temperature -40.0 dF RAT
Supply Air Temperature -40.0 dF SAT
Fan Mode Off FANSTAT
Cooling Capacity 0.0 % CCAP
Heating Capacity 0.0 % HCAP
FS-8700
-
82 Carrier DataLink
Page
23
of 31
Appendix A.3. Map Descriptor Length Explained
The Length parameter is specified as part of the Map Descriptor.
Appendix A.3.1. Client Reads a Table:
The length determines the number of table variables whose values are to be stored
when the response is received. If you do not know the length of the table in advance,
set the length to a large number (e.g. 100). If the table contains more elements than the
number defined in the length parameter, the additional data will be discarded.
Appendix A.3.2. Client reads a variable:
Response to a variable read takes many forms. The ‘value’ returned can be a number, a
state (like ON), a time or some other string. To store a number or the time set the length
to 1. When a state or string is returned, the driver looks it up in a table of state words. If
it makes a match then it returns the value that has been associated with the state word,
(e.g. ON = 1, OFF = 0). If it cannot make a match, it stores the string byte for byte in the
data array. The number of bytes stored is determined by the length parameter. Thus, if
the length is 1 and the string is ‘INTERRUPTED’ then the driver will store the ‘I’ in the
data array. If the length was two, then the driver would use two consecutive locations
and store ‘I’ and ‘N’.
Appendix A.3.3. Client writes a variable:
Always set the length to 1
Appendix A.3.4. Server:
The length parameter is used when the server returns a value that is a string. The
length is used to tell the driver how many characters to extract from consecutive array
location to form the response string. When the server returns a value that is a number,
state or time the length should always be 1.
Appendix A.4. How the Client stores the states/values of the Table Variables.
Appendix A.4.1. Discrete States
When a Carrier DataLink device reports the state of a table variable which has a discrete
state, it reports the state as a keyword like on/off. This driver has to convert the
keywords to numbers as most other remote devices are interested in the state as a
numeric value of 1 or 0.
The driver is programmed to recognize certain keywords. A list is provided below. The
driver is also capable of allowing the user to add to the table of predefined keywords by
specifying additional information in the configuration file.
State Word Value State Word Value
CLEAN 1 ALERT 2
DIRTY 0 EMSTOP 0
HEAT 1 ENABLE 1
COOL 0 Service 0
ON 1 OFF-local 1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
OFF 0 OFF-CCN 2
OPEN 1 OFF-time 3
CLOSE 0 Emergency 4
CLOSED 0 ON-local 5
ABNORMAL 1 ON-CCN 6
NORMAL 0 ON-time 7
ALARM 1 Redline 1
STOP 0 Shed 2
START 1 DSABLE 0
YES 1 LOCAL 0
NO 0 REMOTE 1
If the driver doesn’t recognize the state word it stores the characters of the state word as
decimal values based on their ASCII value. The number of characters stored is
dependent on the length parameter.
For example, say the driver responds, reporting a variable to be a state ‘INCREDIBLE’.
If the length parameter of the polling map descriptor is 1 then the driver stores a value of
73 (An uppercase ‘I’ is the seventy third character in the ASCII alphabet.). If the length
was 2 then the driver would also store the value 78 in the next array. The driver will store
a maximum of 100 characters. The driver recognizes discrete state words by checking
the 1st character of the value field. If it is a non-digit then it is regarded as a state word.
Appendix A.4.2. Extending the List of Discrete State Words
You can extend the list of state words the driver recognizes by modifying the
configuration file.
The following example adds three state words. If a device reports the state of the
variable as LIGHT then the driver will store the value of 1, if on the other hand the
state is reported as DARK then the driver will store the value zero.
You can use this method to change the values of any of the driver’s default state words
by duplicating the word and specifying a new value in the configuration file.
State Words. The
name will be
stripped of all
spaces between
the last character
and the comma.
Normally the values
will be 1 or zero for
the on/off states but
the driver does not
restrict the value.
Protocol must be
defined on every
line.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
If the driver receives a variable value reported in the format hh:mm then the driver stores
a number obtained by multiplying the hours by 60 and adding the minutes. The driver
recognizes a time value by checking the 3rd character for a colon and checking that the
1st character is a digit.
Value_Stored = hh * 60 + mm
Eg. 5:30pm is reported as 17:20 and is stored as 17*60 + 20 = 1040.
Appendix A.4.4. Numeric Values
The driver recognizes numeric values by checking the first character of the value field. If
it is a digit then the field is treated as a number.
Appendix A.4.5. Occupancy Strings / Values
If the value returned for a variable is 8 characters long and each of the characters is a
one or a zero then the driver regards this as an occupancy string and converts it to a
binary coded decimal value and stores this value.
Eg: 00101010 = 42 decimal
Appendix A.5. Timing Considerations
Reading a whole table can take several seconds depending on the table length. In addition
the response from the Carrier device can have small pauses after each line of response.
Thus, if you use the default timeout and IC_Timeout settings the communications may fail
when either one of the pauses exceeds the IC_Timeout setting or when the whole response
hasn’t been received by the time the timeout setting has elapsed.
For this reason it is recommended that the timeout be set to a value between 15 and 30
seconds and the IC_Timeout be set to a value between 7 and 15 seconds. Before setting
either of these to the maximum consider that the in the event of a real communications
failure, this set amount of time must elapse before the driver recognizes the timeout and
reports the node offline. Thus, it is best to start with a smaller value and increase it until
reliable communications have been achieved with the timeout settings.
The timeout can be set for the Map Descriptor, the node or the connection. This is more
fully explained in the FieldServer Configuration Manual. In summary, if you wish to apply a
single timeout to all messages to a device then set the timeout for the connection. If you
wish to override the connection timeout settings for a particular node the set the timeout for
that node too and if you wish to override the settings for a particular Map Descriptor then set
the timeout for that Map Descriptor.
The example below illustrates how to set the timeout parameters at the connection level.
Appendix B. Carrier DataLink Device Error Response
The following notes are provided from the protocol specification.
Message Explanation Action
Check the spelling of the
#1 Invalid
Command
#2 Invalid or NonExistent Table
#3 Level II
Communications
Error
#6 Device Not
Configured
#7 Variable Does
Not Exist
#8 Invalid Data The data was in an incorrect format. Verify the format of the data.
#9 Access
Restricted
#10 Limits
Exceeded
#11 Alarms Not
Available
#12 Cannot Force
Variable
#13 Parameter Not
Found
#14 Level II
Communications
NACK
The last command sent to the DataLink
device is not recognized.
The specified table does not exist in the
specified element.
A Communication error has occurred
due to other activity on the CCN
communication bus, a system element
failure, or an incorrect address. The
command will not be executed.
The specified system element’s bus and
the element number were not found in
the DTP-CONFG table.
The variable does not exist in the
specified table.
An attempt was made to read or write to
a table or variable type that is not
supported by the DataLink device.
The value that was typed is outside the
specified variable’s upper or lower limits
There are no alarms currently in the
alarm buffer.
The CCN system element does not
allow write access to the specified
variable.
The 8-character point (variable) name
used in the RT or WT command does
not exist.
The command was accepted but not
understood by the specified system
element, an attempt was made to write
to or read a variable with a higher force
level, or an attempt was made to write or
read from a UT203 controller.
command and verify that it
contains the required
parameters.
Check the spelling of the table
name(s). If using a WV or RV
command; verify that the table
contains the specified
variables.
Verify the COMM2 connector
is not disconnected and retype
the command.
Verify that the correct bus and
element number have been
entered in the DTP-CONFG
table corresponding to the
device number.
Check the spelling of the
variable name and verify that
the CCN variable exists in the
specified system element.
Check variable.
Verify the limits and adjust the
force value.
Reissue the command at later
time or adjust the alarm
priority level.
Choose different variable.
Check the spelling of the point
(variable) name and verify that
the point name exists in the
specified system element.
Retype the command after
checking the force priority and
after verifying that the correct
bus and element number is
entered in the DTP-CONFG
table.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
The driver reports statistics according to the FieldServer standards. The following notes
describe some aspects of standard statistic reporting which are peculiar to this driver.
All errors responses from the Carrier DataLink device are recorded as a PROCOL ERROR,
In addition to the standard FieldServer communication statistics described above and in the
FieldServer User’s Manual, this driver can also expose some driver statistics by writing data
to a data array. A special Map Descriptor is required. The driver recognizes the Map
Descriptor by its name which must be "Carrier-stats”.
The following example shows how this special Map Descriptor can be configured. You can
copy this section of text directly into your CSV file.
When the driver sees this Map Descriptor it uses the data array
example) to store driver specific statistics. Only one of these Map Descriptors may be
specified per FieldServer.
The driver stores the following data. The location in the data array is obtained by
multiplying the port number by 50 and then using the location offset indicated in the table
below.
DA_CARRIER_STATS
(in this
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
0 Number of Read Table messages sent
1 Number of Read Variable messages sent
2 Number of Write Table messages sent
3 Number of Write Var Messages sent
4 Number of bytes sent by client driver
5 Number of messages sent by client
6 Number of response messages received by client
Number of times client tries write with alternate format because original
7
method failed
9 Most recent response error
8 Number of times client receives an error response
10 Carrier Error: #1 Invalid Command"
11 Carrier Error: #2 Invalid or Non-Existent Table"
12 Carrier Error: #3 Level II communications Error"
13 Carrier Error: #4 Error not defined"
14 Carrier Error: #5 Error not defined"
15 Carrier Error: #6 Device Not Configured"
16 Carrier Error: #7 Variable Does not Exist"
17 Carrier Error: #8 Invalid Data"
18 Carrier Error: #9 Access Restricted"
19 Carrier Error: #10 Limits Exceeded"
20 Carrier Error: #11 Alarms not Available"
21 Carrier Error: #12 Cannot Force Variable"
22 Carrier Error: #13 Parameter Not Found"
23 Carrier Error: #14 Level II Communications NACK"
24 Some other error
25 Number of response bytes received by client
26 Number of times client has timeout out waiting for (response) prompt
When set then the server sends response whose var names have leading
27
spaces. This is used for QAA testing and diagnostic purposes only.
Customers should never set this value.
28 Number of times client cannot parse / recognize the value sting in a response
29 Number of times the server had to store a time greater than 24:00
30 Number of times the client sent a message with a time greater than 24:00
31
Number of times the client sent a message to a probable occupancy table
without the correct data types
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
The driver reports information and errors in the form of messages printed to the error log. Those
messages marked with a * are only printed once even if they occur repeatedly.
Error Message Explanation
Carrier:#1 FYI. The
MapDesc called <%s> is too
short
Carrier:#2 FYI. You could
have used a MapDesc called
<%s> to expose diagnostic
info.
Carrier:#3 Err. Illegal
Node_ID=%d Valid=1..15
Carrier:#4 FYI. Address has
no meaning. Best set to 1
MapDesc=<%s>
Carrier:#5 Err. For write, set
length to 1. MapDesc=<%s>
Carrier:#6 FYI. Field Name
Blank. Assumed
'EVERYTHING'.
MapDesc=<%s>
Carrier:#7 Err. Table name
required. MapDesc=<%s>
Carrier:#8 Err. Length
required. MapDesc=<%s>
Carr:#9 FYI. Duplicate
state=<%s>. Value has been
updated from=%d to=%d
Carr:#10 Err. No space.
Driver rejects value
state=<%s> value=%d
Carr:#11 FYI. User added
value state=<%s> value=%d
Carr:#12 Err. Length too
short to store all. MD=<%s>
Correct the error by editing the configuration CSV file, downloading the corrected file to the FieldServer
and then resetting the FieldServer.
The length of the Map Descriptor used to expose driver
statistics is too short. Set to at least 1000. This message may
be ignored§.
This message is a prompt and may be ignored. Read
Appendix C.1 for more information.
Valid node numbers are in the range 1 to 15 inclusive. Read
sections 4.3 or 5.3 for more information. §
You can ignore this message. The address parameter has no
meaning in the configuration of this driver. Remove the
parameter from the configuration or set its value to 1§
If the Field_Name parameter is left unspecified then the driver
assumes you intend reading the whole table by filling in the
Field_Name with the keyword EVERYTHING. Suppress this
message by specifying the Field_Name .§
Every Map Descriptor for this driver requires that you specify a
table name. Section 4.4.2 and Appendix A.1 provide additional
information. §
The length parameter must be set in the configuration file to a
value greater than zero. Refer to Appendix A.3.§
You have specified a discrete state word in the configuration
file which is a duplicate of one already in the list. The driver
uses the new value, thus changing the values for the driver’s
default discrete state words. You can ignore this message.
The driver has limited space to store discrete state keywords
added in the configuration file. The maximum is 150 words
including the driver’s defaults. Remove some of the keywords
you have added to the configuration file. §
You can ignore this message; it is for information only. Each
time a new discrete state word is added to the driver from the
configuration file, the driver reports the new word and its value.
The read table command resulted in more variables being
returned than you have reserved space for (with the length
parameter). Increase the length parameter§.
These messages are for FieldServer engineers. If printed in
the error log please call FieldServer support and report the
message.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Carrier:#15 Err. Alarm
commands not supported.
Carrier:#16 Err. Alarm
commands not supported.
The server does not support alarm functions. Polls beginning
AV or RA produce these errors. Re-configure your client not to
request this information. §
On the line immediately following this error the driver reports
Carr:#17 Err. MD=<%s>
discrete state word not
recognized.
the response that generated the error. The driver will store a
value that is the ASCII code for the first character of the
unrecognized word. Add a new discrete state word to the .CSV
file as described in Appendix A.4. §
This message may be ignored if your communications are
CarrDL:#18 FYI. Timeout
probably too short. Read
Manual.
operating reliably. Read Appendix A.5 for additional information
on timing considerations. The message is printed when the
driver detects that the configuration requires that a whole table
be read and the timeout value is set below the recommended
minimum of 15s for this operation.
This error message should only be produced by FST’s QA
CarrDL:#19 Err. Diagnostic.
Call Support.
testing procedure. If you see this error, call Tech Support after
taking a log. Instructions for taking a log may be found in the
Trouble Shooting Guide.
The message is printed once and suppressed for subsequent
occurrences. The message is printed when writing a time to a
CarrDL:#20* FYI. Invalid
Time(%02d:%02d) being
written. MD=%s
Carrier Device which is invalid as it is greater than 23:59.
Check the value in the Data Array being used for the write. It’s
possible an upstream device sent an invalid value. The driver
sends the message with the invalid time and it’s up to the
Carrier device to reject the setting.
The message is printed once and suppressed for subsequent
CarrDL:#21* FYI. Invalid
Time(%02d:%02d) being
stored. MD=%s
occurrences. The message is printed when the Server is
required to store an invalid time (>23.59). Check the value in
the Data Array being used for the write. The data is stored
despite the warning.
These errors occur when communications are operating
correctly but the CarrDL device cannot respond to the poll.
CarrDL:#23* Err. CarrDL
device reported errors.
Check exposed stats 8-23.
The reason error is reported in the driver stats (See Appendix
C.1) Stat #9, reports the error number of the most recent error
reported. The message is printed once and then suppressed.
These errors are most commonly produced when a table
name/ variable name does not exist or is mis-spelled
DOW and times require that the Data_Type be specified when
writing to enable the Driver to convert the value extracted from
CarrDL:#22* FYI. Read
notes for #22 in Manual.
MD=%s
the Data Array for formatting in the write message. This error
is printed if the table name or the field name contain the sub-
string “OCC”, the function is a write, and a Data_Type has not
been specified. In most cases the write will be rejected by the
Carrier device or the value may not be what you expect. Refer
to Section 4.4.7 for more information.
§
Correct the error by editing the configuration CSV file, downloading the corrected file to the FieldServer
and then resetting the FieldServer.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com