FieldServer FS-8700-80 User Manual

Driver Version:
1.05
Document Revision:
6
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after November 2011
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-80 McQuay MicroTech® Open Protocol
A Sierra Monitor Company
McQuay Micro Tech Open Protocol Driver Manual Table of Contents
TABLE OF CONTENTS
1 McQuay Micro Tech Open Protocol Description ............................................................................................. 4
1.1 MicroTech Unit and System Controllers ........................................................................................................ 4
1.1.1 McQuay Equipment Types recognized by the driver. ............................................................................. 4
1.1.2 McQuay equipment not currently recongnized by the driver: ............................................................... 4
1.1.3 McQuay MicroTech network products used in conjunction with the driver: ......................................... 5
1.1.4 About MicroTech Network Architecture ................................................................................................ 6
1.2 Applying a FieldServer gateway to different MicroTech situations ............................................................... 6
1.2.1 Single standalone MicroTech 200 Series unit controller ........................................................................ 6
1.2.2 Multiple standalone MicroTech 200 Series unit controllers ................................................................... 7
1.2.3 Multiple standalone MicroTech “non-200 Series” unit controllers ........................................................ 7
1.2.4 Existing MicroTech network (Custom MicroTech Monitor software, NMP Panel, etc) .......................... 7
1.2.5 Existing MicroTech Open Protocol network ........................................................................................... 9
1.2.6 Replacing a BACdrop Gateway panel .................................................................................................... 9
1.3 MicroTech Communication Port Configuration ........................................................................................... 11
1.4 Reference Documents ................................................................................................................................. 12
2 Driver Features ............................................................................................................................................ 13
3 Driver Scope of Supply ................................................................................................................................. 13
3.1 Supplied by FieldServer Technologies for this driver ................................................................................... 13
3.2 Provided by Supplier of 3rd Party Equipment............................................................................................... 13
4 Hardware Connections ................................................................................................................................. 14
5 Data Array Parameters ................................................................................................................................. 15
6 Configuring the FieldServer as a McQuay Micro Tech Open Protocol Client ................................................. 16
6.1 Client Side Connection Parameters ............................................................................................................. 16
6.2 Client Side Node Parameters ....................................................................................................................... 17
6.3 Client Side Map Descriptors......................................................................................................................... 18
6.3.1 FieldServer Related Map Descriptor Parameters ................................................................................. 18
6.3.2 Driver Related Map Descriptor Parameters ......................................................................................... 18
6.3.3 Timing Parameters ............................................................................................................................... 18
6.3.4 Map Descriptor Example 1 – Read Everything. .................................................................................... 19
6.3.5 Map Descriptor Example 2 – Read a particular Data Field. ................................................................. 19
6.3.6 Map Descriptor Example 3 – Write. ..................................................................................................... 20
7 Configuring the FieldServer as a McQuay Micro Tech Open Protocol Server ................................................ 21
7.1 Server Side Connection Paramaters ............................................................................................................ 21
7.2 Server Side Node Parameters ...................................................................................................................... 22
7.3 Server Side Map Descriptors........................................................................................................................ 22
7.3.1 FieldServer Specific Map Descriptor Parameters ................................................................................. 22
7.3.2 Driver Specific Map Descriptor Parameters ......................................................................................... 23
7.3.3 Timing Parameters ............................................................................................................................... 23
7.3.4 Map Descriptor Example – Strategy 1. ................................................................................................ 24
7.3.5 Map Descriptor Example – Strategy 2. ................................................................................................ 24
Appendix A. Useful Features ................................................................................................................................ 25
Appendix A.1. Scaling .............................................................................................................................................. 25
Appendix A.1.1. User Scaling: ........................................................................................................................... 25
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Table of Contents
Appendix A.1.2. Device Scaling: ....................................................................................................................... 25
Appendix A.2. Direct Addressing ............................................................................................................................. 26
Appendix A.3. Direct Addressing Example 1– Reading direct address. ................................................................... 27
Appendix A.4. Direct Addressing Example 2 – Controlling Bytes per Field – Reading ............................................. 27
Appendix A.5. Advanced Map Descriptor Example 3 – Controlling Bytes per Field – Writing ................................ 28
Appendix B. Troubleshooting ............................................................................................................................... 29
Appendix B.1. Connection Problems ....................................................................................................................... 29
Appendix B.2. Negative Acknowledgement - NAK .................................................................................................. 29
Appendix B.3. Node ID problems............................................................................................................................. 29
Appendix B.4. Server Side Configuration – Consecutive Addresses ........................................................................ 30
Appendix B.5. Configuring the OPM to enable communication between the FieldServer and McQuay devices ... 30
Appendix B.5.1. Configuring multiple McQuay devices to communicate to a FieldServer without an OPM:... 30
Appendix C. Reference ......................................................................................................................................... 32
Appendix C.1. Error Messages ................................................................................................................................. 32
Appendix C.2. Statistics ........................................................................................................................................... 34
Appendix C.3. McQuay Equipment Types recognized by the driver. ...................................................................... 35
Appendix C.4. Device Scaling Method ..................................................................................................................... 35
Appendix C.5. Data Field Name Tables .................................................................................................................... 35
Appendix C.5.1. Equipment Type: 200CFC 200 Series Centrifugal Chiller ......................................................... 35
Appendix C.5.2. Equipment Type: 050RPC Reciprocating Chiller ..................................................................... 37
Appendix C.5.3. Equipment Type: 100CFC 100 Series Centrifugal Chiller ......................................................... 38
Appendix C.5.4. Equipment Type : 001ASC Air Cooled Screw Chiller ................................................................ 40
Appendix C.5.5. Equipment Type : Self-Contained Units (SCUs) ....................................................................... 41
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 4 of 43
Code
Description
200CFC
200 Series Centrifugal Chiller
100CFC
100 Series Centrifugal Chiller
001ASC
Air Cooled Screw Chiller – V2.2 Single Compressor Only
000SCU
Self Contained Unit
0050RPC
Reciprocating Chiller
Rooftop Unit
Water Cooled Screw Chiller
Code
Description
Global Scroll chiller
Unit Ventilator
Water Source Heat Pump (WSHP)
MicroTech 2000 WSHP (through MCG (MicroTech Communications Gateway panel)
1 MCQUAY MICRO TECH OPEN PROTOCOL DESCRIPTION
This document describes the FieldServer driver used to transfer data between a FieldServer and MicroTech® unit and/or network of controllers manufactured by McQuay International. Transfers are done using the controller's Data Terminal Communications Protocol. In this document the protocol is referred to as the McQuay MicroTech® Open Protocol. MicroTech controls are legacy products that may require the use of a FieldServer device in order to support existing applications in need of unit or network controller replacements and/or integration into a Building Automation System (BAS).
1.1 MicroTech Unit and Syst em Controllers
McQuay International has provided BAS manufacturers licensed access to stand-alone MicroTech unit controllers. The network access, which is called Open Protocol™, allows a BAS to monitor status and change limited control parameters in McQuay International HVAC equipment. Monitoring and controlling MicroTech unit controllers may have required the use of a MicroTech system panel, depending on the unit type, number of units and other network requirements. There are multiple combinations of MicroTech unit controllers and/or system panels (i.e. Open Protocol networks) that could use a FieldServer device. FieldServer-supported devices, McQuay Open Protocol controller descriptions, and network architecture diagrams are all described in the following section.
The McQuay MicroTech® Open Protocol driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using McQuay MicroTech® Open Protocol. The FieldServer can emulate either a Server or Client.
1.1.1 McQuay Equipm ent Types recogn ized by the driv er.
1.1.2 McQuay equipm ent not currently reco ngnized by the driver:
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 5 of 43
CB
PS
SBC
J1 connector
RJ-45
J22
L2
L1
GRD
“Etherne t” po rt
“Netwo rk” port
“PC” por t
Flash memory chip
Ethernet status LEDs
Speaker
5 Vdc power in
1.1.3 McQuay MicroTech network products us ed in conjunction wit h the driver:
1.1.3.1 MicroTech BACdrop™ panel
The MicroTech BACdrop gateway integrates a MicroTech network into a BACnet™ building automation system (BAS) facilitating monitoring and control of McQuay International equipment from the BAS. The gateway translates between BACnet objects on an Ethernet® network and McQuay memory locations on a proprietary MicroTech network.
The BACdrop gateway is a passive device. It receives, translates, and re-transmits messages including both data and control signals from one network to the other network in either direction but does not perform any supervisory control for the various MicroTech controllers connected to it. Figure 1 shows the important features of the BACdrop panel.
Figure 1. BACdrop Panel
1.1.3.2 OPM – Open Protocol Master Panel
The OPM Panel is used when two or more MicroTech controllers need to be interfaced with a BAS by means of a single-point connection. The OPM acts as a passive communications link between MicroTech controllers and the BAS and does not perform any supervisory control for the various MicroTech controllers connected to it. When an OPM is used, all supervisory control (scheduling, overrides, chiller sequencing) is handled by the BAS. The maximum number of unit controllers per OPM depends on the BAS. For example, the OPM Panel could combine a McQuay centrifugal chiller, a McQuay applied rooftop unit, and several unit ventilators into a network that a BAS could connect to with a single cable. Figure 2 shows the important features of the OPM panel.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 6 of 43
Port A
Port B
HI
LO
F1
L1
Port A Select
1 2 3
3
21
Hex
switches
Communication ports
Red status
LED
Green status LED
Figure 2. OPM Panel
1.1.3.3 Alternatives to the OPM Panel
The following MicroTech network controllers, which perform specific supervisory control tasks, can be used as substitutes for the OPM Panel:
RMC (Remote Monitoring and Control panel – Applied Air product) CSC (Chiller System Controller panel – chiller product) RMS (Remote Monitoring and Sequencing panel – chiller product) LWC (Loop Water Controller – WSHP product)
1.1.4 About M ic roTech Network Architecture
All controllers in a MicroTech network are assigned a level: level 1, level 2, or level 3. All networks must have one level 1 controller to coordinate communications. Multiple level 2 controllers connect to the level 1 controller with a communications trunk. A trunk is defined as an isolated section of the daisy-chained network wiring. The network wiring between all controllers is a trunk. Multiple level 3 controllers can be connected to a level 2 controller with a separate trunk; however, this is typically not done in BACdrop applications. The maximum allowable length of a communications trunk is 5000 ft (1524 m). See Figures 6 and 7 for examples of field wiring.
1.2 Apply ing a FieldServer gateway to diffe re nt MicroTech situation s
There are multiple scenarios where a FieldServer gateway device may be applied to one or more MicroTech controllers. The most common are listed below, followed by a brief description of each one.
1.2.1 Single st andalone MicroTech 200 Series unit controller
When a FieldServer device is connected to a single MicroTech unit controller, the FieldServer connects to the “A” port of the MicroTech controller. The unit controller is typically a level 2 device with a Comm Port Configuration of “L2 TTY/Slave”. MicroTech Level 2 devices must have an address with a non-zero value to the left of the decimal point and "00" to the right of the decimal point (for example, 01.00, 02.00, 03.00, etc). For a level 2 device, the left side (the non-zero portion) of the address is set with the controller's rotary hex switches.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 7 of 43
1.2.2 Multiple st andalone MicroTech 20 0 Series unit controllers
1.2.2.1 MicroTech Addressing and Network Archit ecture
When a FieldServer device is connected to two or more MicroTech controllers, a level 1 MicroTech controller is required to coordinate communications. Typically the level 1 device in this situation is an Open Protocol Master Panel (an "OPM"). However, the OPM Panel is no longer available from McQuay, so another MicroTech device may function as the Level 1 device. A 200 Series MicroTech unit controller (for example, a Self-Contained Unit (SCU) controller) can be re-configured as a level 1 device. Thus if a site has several SCUs, one of them can be re­configured as level 1 and the FieldServer connects to the "A" port of that unit controller. A Level 2 daisy chain is then connected from the “B” port of the level 1 SCU to the “B” port of the remaining Level 2 SCU's.
It is also possible to use a supervisory MicroTech network controller as the level 1 device which coordinates communications between the FieldServer device and multiple level 2 MicroTech controllers. Examples of supervisory controllers are the RMC, CSC, and RMS panels.
Another alternative is to use an NMP (Network Master Panel) controller. An NMP is the level 1 device used in a MicroTech network (see Figure 3). The NMP coordinates communications of all level 2 and level 3 MicroTech controllers in this type of network. The NMP also coordinates unit time scheduling, processes alarms, and does other functions. If an NMP is used in this way, it is necessary to “corrupt” its checksums so that the NMP application code no longer runs. The process of corrupting checksums can be performed with MicroTech Monitor® software using the read/write screen. Please contact the McQuay Controls Customer Support group at 866-462­7829 for more information about using Monitor software.
1.2.3 Multiple st andalone MicroTech “ no n-200 Se ries” unit controllers
If a FieldServer gateway device is applied to a site that has several “standalone” unit controllers that have never
been networked together, there are certain guidelines that must be followed. First, a level 1 device is required to coordinate the communications between the FieldServer device and the MicroTech unit controllers. Typically an OPM Panel is used for this purpose. However, the OPM is no longer available from McQuay. If the multiple unit controllers are “non-200 Series” MicroTech controllers such as Unit Ventilators (UVs) or Water Source Heat Pumps (WSHPs), a Level 1 MicroTech controller must be added to the network to coordinate communications of the Level 2 UVs or WSHPs.
In addition, network wiring would be required to be installed. The FieldServer would be wired to the “A” port of the Level 1 device. A “level 2 daisy-chain” would be required from the “B” port of the level 1 device to the “B” port of each level 2 device. See Figures 6 and 7 for network wiring details.
1.2.4 Existing MicroTech netwo rk (Custom M icroTech Monitor soft ware, NMP Panel, etc)
1.2.4.1 With level 3 devices (Unit Vents or WSHPs)
If a FieldServer gateway device is applied to a site that has an existing “MicroTech network” (meaning that it has custom MicroTech Monitor software for that site and an NMP Panel) and Unit Vents or WSHPs, changes are required as follows:
The checksums in the NMP’s application code must be corrupted so that the NMP no longer functions as a
Network Master Panel. The FieldServer device connects to the A port of the NMP.
Level 2 LMPs (Local Master Panel) must be removed from the network. The RS-485 daisy chain connecting all of the Unit Vents or WSHPs must be connected directly to the “B”
port of the Level 1 NMP.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 8 of 43
T
M
M
S
T
S
T
S
Level 1
Laptop PC
RS 232
RS 485
T
S
Port B
Port A
NMP
LMP
MCG RTU
LWC
Port B
Port A
Port B
Port B
Port B
Port A Port A
Port A
Level 2 Trunk
Level 2
Level 3
T
S
WSHP
Port B
Port A
T
S
WSHP
Port B
Port A
T
S
MT 2000
WSHP Port B
Port A
T
S
Port B
Port A
MT 2000
WSHP
Different application code must be downloaded into all Unit Vents and WSHPs.
In the case of Unit Vents, the “Level 3 network code” for use in a MicroTech network must be
replaced with “Level 2 standalone” Unit Vent code.
In the case of WSHPs, the “Level 3” code for use in a MicroTech network must be replaced with
“Level 2 standalone” WSHP code.
See Figure 3 for details.
Figure 3. MicroTech Network Configurations with Level 1 NMP Supervisory Controller
Port Configuration
M=Master S=Slave T=TTY (for PC connection)
Notes:
A PC running MicroTechMonitor connects to an NMP through it’s a Port configured as “TTY” The A Port of a Level 2 MCG is configured as “USER” to communicate with the MCG’s SLTA. MicroTech WSHP’s on a MicroTech network require a LMP (Level 2 Local Master Panel) above them. MicroTech 2000 WSHP’s with LonWorks code (vs LonMark code) are installed below an MCG.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 9 of 43
1.2.4.2 With no level 3 devices
If a FieldServer gateway device is applied to a site that has an existing “MicroTech network” (meaning that it has custom MicroTech Monitor software for that site and an NMP Panel) with only level 2 controllers and no level 3 devices (such as Unit Vents or WSHPs), changes are required as follows:
The checksums in the NMP’s application code must be corrupted so that the NMP no longer functions as a
Network master Panel. The FieldServer device connects to the “A” port of the NMP.
No network wiring changes are necessary
1.2.5 Existing MicroTech Open P ro tocol net work
If a FieldServer gateway device is applied to a site that has an existing “Open Protocol network”, the following assumptions are made:
The site has either an OPM Panel or some other level 1 MicroTech controller that is functioning as an
OPM.
Any Unit Vents or WSHPs in the network are already running the proper “Level 2” application code
required for an “Open Protocol” network.
No network wiring changes are necessary. See Figure 7 for details
1.2.6 Replacin g a BACdrop Gat eway panel
1.2.6.1 Connected a Single Micro Tech unit controlle r
When a FieldServer device is used to replace a BACdrop panel that has been connected to one MicroTech unit controller, some re-wiring is necessary. The RS-485 network terminals of the BACdrop panel are connected to the
“B” Port of the MicroTech controller, but the FieldServer connects to the “A” port of the MicroTech controller. The unit controller will be a level 2 device with a Comm Port Configuration of “L2 TTY/Slave”. MicroTech Level 2
devices must have an address with a non-zero value to the left of the decimal point and "00" to the right of the decimal point (for example, 01.00). For a level 2 device, the left side (the non-zero portion) of the address is set with the controller's rotary hex switches.
1.2.6.2 Connected to Multiple MicroTech unit control lers
When a FieldServer device is used to replace a BACdrop panel that has been connected to multiple MicroTech unit controllers with no Level 1 supervisory panel such as an RMC, CSC, or RMS, a Level 1 device must be added. If the unit controllers are 200 Series MicroTech, this can be accomplished by re-configuring one of the unit controllers to be Level 1. The alternative to re-configuring one of the existing unit controllers to be a Level 1 device is to add a level 1 device such as an OPM, RMC, CSC, or RMS, but this may be difficult because all of these control panels are obsolete and no longer available. For a typical BACdrop network, the BACdrop panel is the level 1 controller and the unit controllers are level 2 controllers. See Figures 4 and 6 for details.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 10 of 43
RTU UV
Up to 63 MicroTech controllers per BACdrop
BACnet on ISO 8802-3 (Ethernet), 10BaseT
MicroTech
BACdrop
(level 1)
Chiller UV UV UVSCU
Level 2
MicroTech
Level 1
BACnet BAS
by others
Main "front end" PC for BAS
MicroTech network (RS-485)
Chiller
Level 2
MicroTech
Up to 63 MicroTech controllers per BACdrop
BACnet BAS
by others
BACnet on ISO 8802-3 (Ethernet), 10BaseT
MicroTech
BACdrop
(level 2)
Level 1
ChillerChiller
Main "front end" PC for BAS
CSC
Chiller
MicroTech network (RS-485)
All data requests from BACnet BAS to MicroTech level-2 controllers are routed through level-1 MicroTech controller
Figure 4. MicroTech Architecture
1.2.6.3 Connected to multiple MicroTech unit controllers and a supervisory panel su ch as an RMC,
CSC, or RMS panel When a FieldServer device will be replacing a BACdrop Gateway panel that was connected to multiple MicroTech unit controllers with a Level 1 supervisory panel such as an RMC, CSC, or RMS, some re-wiring may be necessary. The FieldServer device must be wired to the A Port of the Level 1 device. The B Port of the Level 1 device is then wired to the B Port of all Level 2 devices with a daisy chain. See Figure 5 for details.
Figure 5. Level 2 BACdrop Panel with Level 1 Supervisory Panel
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 11 of 43
TS2
BACdrop
Hot Neutral
100 – 240 Vac Power
L2 L1
GRD
Notes:
1. Twisted, shielded pair cable must meet the following minimum requirements: 300 V, 60°C, 20 AWG, polyethylene insulated, with a PVC outer jacket and drain wire (Belden 8762 or equivalent). Some local codes may require the use of plenum rated cable.
2. 10BaseT Ethernet cable. To directly connect a PC to the Ethernet port, a hub or a special crossover cable must be used.
3. Cable length must not exceed 5000 ft (1524 m).
4. Standard serial cable. A null modem is not required.
See notes 1 & 3
Self-contained AC
Port B
GND
TB7
Reciprocating
chiller
Port B
139
TB4
Screw chiller
Port B
55
BLK
WHT
B+
B–
138
137
54
53
Comm B
UVC (325)
1
2
PNK
GRY
Comm B
UVC (125)
4
5
PNK
GRY
RJ-45
3rd-party BAS
See note 2
TB1
Centrifugal chiller
(series 200)
Port B
858684
TB2
Applied rooftop
Port B
130
128
129
Legend
Field wiring terminal Field wiring: discrete
Factory wiring
Field wiring: twisted, shielded pair cable with drain wire (see note 1)
B+
Crimp or solder splice
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
BLK
WHT
Comm B
UVC (325)
1
2
PNK
GRY
Comm B
UVC (325)
1
2
PNK
GRY
Comm B
UVC (325)
1
2
PNK
GRY
Ethernet
DB9
PC
PC
+
GRD
Network
See note 4
Field wiring: 10BaseT Ethernet Standard serial cable
1.3 MicroTech Comm unicat ion Port Configuration
In addition to the rules about MicroTech architecture and addressing, there is also a critical parameter called the Comm Port Configuration. The Comm Port Configuration must also be set correctly for a unit controller to be able to communicate. This comm port configuration for level 1 devices is different to level 2 devices. While it is necessary to know this for proper unit controller setup and for troubleshooting communication problems, it is not critical from the FieldServer side for programming or routing.
A level 1 device must have its communication port configuration set up as “Level 1 TTY/Slave”. To change this
configuration, connect to the unit controller with MicroTech Monitor software through the “A” port, proceed to the “Read/Write” screen, read memory address “0A11”, and change the value to “C1” (Level 1 TTY/Slave). After doing this, the controller must also have its rotary hex switches set to the Level 1 address of “00” to make the unit controller’s network address 00.00. Please note that power must be cycled to the controller for this new hex
switch setting to take effect.
Figure 6. MicroTech Network with BACdrop Panel as Level 1 Device
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 12 of 43
Document
Description
Location
IM 474
Open Protocol Master (OPM) Panel
www.mcquay.com
IM 689
BACdrop Gateway for MicroTech
www.mcquay.com
IM 658
Network Master Panel (NMP)
Contact McQuay
CD 573875Y
Microtech Open Protocol Wiring Diagrams
Contact McQuay
IM 444
Remote Monitoring and Control (RMC) Panel
Contact McQuay
IM 498
Remote Monitoring and Sequencing (RMS) Panel
Contact McQuay
IM 618
MicroTech Chiller System Controller (CSC) Panel
Contact McQuay
*Or other Level 1 Device (CSC, etc.)
Figure 7. MicroTech Network with OPM Panel as Level 1 Device
1.4 Reference Documents
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
McQuay Micro Tech Open Protocol Driver Manual Page 13 of 43
FieldServer Technologies Part #
Description
FS-8917-16
RJ45 to terminal connector cable.
Part #
Description
McQuay Motor Mount Connector for Port A connection
2 DRIVER FEATURES
When emulating a Client, the driver enables the FieldServer to request ‘Everything’ from the McQuay, allow specific fields to be read or written and apply device scaling to be applied.
When emulating a Server, the driver provides an emulation of the byte memory of a device and responds to read and write requests.
The following important points and limitations should be noted.
Arising from a feature of the McQuay MicroTech® Open Protocol is the peculiarity that when a multi-byte
value is written to a McQuay device, the write is done one byte at a time (one byte of data can be transferred per poll/response message pair) allowing for the possibility that the multi byte value is only partially correct until all the messages have been completed.
The vendor equipment is limited to a maximum of 9600 baud. Given that each message packet can only
transfer one byte of data and that some data of interest is multi-byte, users of this protocol should expect low data transfer rates.
Port expansion is not supported for this driver. Each MicroTech® controller is shipped from the factory with a unique job site password. The passwords
are provided by the McQuay International representative at the time of startup.
The driver does not validate passwords when configured as a Server. This means that requests to read or
write data will succeed even if the password supplied with the request is incorrect.
3 DRIVER SCOPE OF SUPPLY
3.1 Sup plied by FieldServ er Technologies for this driver
3.2 Provided by Supplier of 3
rd
Party Equipment
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Loading...
+ 30 hidden pages