A Sierra Monitor Company
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-60 Gardner Denver Auto Sentry
ES/RS2000
Effective for all systems manufactured after May 1, 2001
APPLICABILITY & EFFECTIVITY

FS-8700-60 Gardner Denver Manual Table of Contents
TABLE OF CONTENTS
1. Gardner Denver Auto Sentry ES/RS2000 Description.......................................1
2. Driver Scope of Supply........................................................................................ 2
1.01 Supplied by FieldServer Technologies for this driver ....................................... 2
1.02 Provided by the Supplier of 3rd Party Equipment.............................................. 2
2.1.1. Required 3rd Party Hardware.........................................................................2
2.1.2. Required 3rd Party Software..........................................................................2
2.1.3. Required 3rd Party Configuration...................................................................2
2.1.4. Optional Items...............................................................................................2
3. Hardware Connections ........................................................................................3
1.03 Hardware Connection Tips / Hints.................................................................... 3
4. Configuring the FieldServer as a Gardner Denver Auto Sentry ES/RS2000
Client..............................................................................................................................4
1.04 Data Arrays/Descriptors ................................................................................... 4
1.05 Client Side Connection Descriptions ................................................................ 5
1.06 Client Side Node Descriptors ...........................................................................6
1.07 Client Side Map Descriptors............................................................................. 6
4.1.1. FieldServer Related Map Descriptor Parameters..........................................6
4.1.2. Driver Related Map Descriptor Parameters................................................... 7
4.1.3. Timing Parameters........................................................................................7
4.1.4. Map Descriptor Example 1 – Polling all available Controller Data.................8
4.1.5. Map Descriptor Example 2 - Polling only specific data items ........................ 9
4.1.6. Map Descriptor Example 3 - Polling all data and isolating specific data items
9
Appendix 1. Advanced Topics.................................................................................10
Appendix 1.1. Can I use only Passive Client mapdescs ? ...................................... 10
Appendix 1.2. Data length of specific polls versus “All” data polls ........................... 10
Appendix 2. Revision History..................................................................................11
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

FS-8700-60 Gardner Denver Manual Page 1 of 11
1. Gardner Denver Auto Sentry ES/RS2000 Description
The Gardner Denver Auto Sentry ES/RS2000 driver allows the FieldServer to transfer
data from devices over either RS-232 or RS-485 using Gardner Denver Auto Sentry
ES/RS2000 protocol. The driver can be configured to communicate with ES Controllers
with software versions V2.0X, V2.1X and RS2000 Controllers with software versions
V4.0X
The client driver implements the following functionality:
• Polls controllers for service and maintenance data.
• Polls controllers for operating mode data.
• Polls controllers for operating data.
The driver can poll up to 8 units connected to one ES/RS2000 Controller. It always sets
the active unit on the ES/RS2000 Controller before polling for data even if consecutive
polls are for the same unit. This is done to prevent synchronization problems.
Gardner Denver ES/RS2000 Controllers implements three message types for which the
driver can poll. The driver does not validate the message data fields for correct values
although it does validate data field lengths For example, shutdown codes reported by
V2.1 ES Controllers range from 0 to 27. If a code of 28 is reported, the driver will not
flag it as an error since codes have to be interpreted by the operator. However, a
message length longer than 2 digits will be reported as an error.
Max Nodes Supported
FieldServer Mode Nodes Comments
Client 1
A client node can communicate with up to 8 units
connected to a ES/RS2000 Controller
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

FS-8700-60 Gardner Denver Manual Page 2 of 11
2. Driver Scope of Supply
1.01 Supplied by FieldServer Technologies for this driver
FieldServer Technologies
PART #
Description
FS-8915-10 UTP cable (7 foot) for RS-232 use
FS-8917-03 RJ45 to DB9M connector adapter
FS-8700-60 Driver Manual
1.02 Provided by the Supplier of 3rd Party Equipment
2.1.1. Required 3rd Party Hardware
Part # Description
- ES/RS2000 controller
2.1.2. Required 3rd Party Software
None.
2.1.3. Required 3rd Party Configuration
The ES/RS2000 Controller must be set up in the correct mode to support either
RS-232 or RS-485 communications to an external monitoring system. Please
refer to manufacturer’s setup instructions.
2.1.4. Optional Items
PART # Vendor/Manufacturer Description
485LDRC B&B Electronics RS-232/RS-485 converter
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com