Fieldpiece Instruments SM380V OPERATOR'S MANUAL

Fieldpiece®
SMAN™ Refrigerant Manifold + Micron Gauge (3 Port)
OPERATOR'S MANUAL Model SM380V
Contents
Important Notice . . . . . . 4
Class A2L/A2/A3 Refrigerant Safety Notice
Warnings
Quick Start . . . . . . . . 5
What’s Included
Description . . . . . . . . 6
Features Display Front View Rear View
Operation. . . . . . . . . 14
Buttons Recent Refrigerants VIEW Select AIR Select Superheat (SH) and Subcooling (SC) Target Superheat (TSH) Deep Vacuum Test Tightness (Pressure Test) Test for Noncondensables
Menu . . . . . . . . . . 22
Data Logging Auto Power Off (APO) Temperature Calibration Wireless Measurement Sources Target Superheat (TSH) Sources Units Vacuum Alarms Backlight Timer Advanced Pressure Calibration Firmware View and Update Restore User Settings Delete Log File Format Internal Flash Drive
Maintenance. . . . . . . . 35
Cleaning Battery Replacement Using Different Refrigerants
Specifications . . . . . . . 36
Temperature Pressure Deep Vacuum Wireless Compatibility Manifold Diagram
Certification and Module IDs . . 39
Limited Warranty . . . . . . 43
32
Important Notice
!
This is not a consumer product. Only qualified personnel trained in service and installation of A/C and/or refrigeration equipment shall use this product.
Read and understand this operator’s manual in its entirety before using your SMAN Refrigerant Manifold to prevent injury or damage to you or equipment.
Class A2L/A2/A3 Refrigerant Safety Notice
Systems using class A2L (mildly flammable), class A2 (flammable), or class A3 (highly flammable) refrigerants can be tested safely ONLY by qualified personnel explicitly trained in the use and handling of those refrigerants. This manual is in no way a replacement for proper training.
WARNINGS
Do not apply more than 800 psig to any port of the manifold. Ground properly when testing A2L/A2/A3 (hydrocarbon) refrigerants. Do not use in the vicinity of explosive substances. Inhalation of high concentrations of refrigerant vapor can block oxygen to
the brain causing injury or death. Refrigerant liquid can cause frostbite. Follow all equipment manufacturer’s testing procedures above those in
this manual in regards to properly servicing their equipment.
Quick Start
1. Install the included six AA batteries into rear battery compartment.
2. Press center blue button for 2 seconds to turn on your new SMAN manifold.
3. Connect your hoses and pipe clamps to the SMAN manifold and to the system.
4. View live pressures and temperatures.
5. Use arrow buttons to select a refrigerant and view calculations in real-time!
What’s Included
• SM380V SMAN Refrigerant Manifold (3 Port)
• (2) TC24 Type K Pipe Clamp Thermocouples
• (1) ATA1 Type K Bead Thermocouple w/Clip
• (1) Year Warranty
• Operator’s Manual
54
Description
SMAN™ Refrigerant Manifolds give you the
trust needed for doing the job right the first time.
Your new Fieldpiece manifold has been upgraded for ultimate field protection and long range wireless communication. The fully rubberized case seals and protects from dust, bumps, and light rain. Use the heavy duty hook to hang it in your work vehicle while protected by its large padded soft case.
Model SM380V is your testing hub at the jobsite. In addition to the included thermocouples, you can connect wirelessly to psychrometers, pipe clamps, and even a refrigerant scale. For example, assign one psychrometer (model JL3RH) to return air and another to supply air to view live temperature split across the evaporator directly.
View all your measurements and live calculations on the extra large LCD or from a distance on your mobile device. A rolling list of your 10 most recently used refrigerants is stored at the top of the main refrigerant list for quick selection.
Verify proper charge by comparing actual superheat (SH) with target superheat (TSH). Use the outdoor dry bulb thermocouple and an optional indoor psychrometer for live TSH calculations.
Pressure sensors automatically compensate for altitude and weather changes. Use the internal vacuum gauge for fast and convenient monitoring of your evacuations.
Features
Job Link® System Ready
- Long Wireless Range (350 feet/106 meters)
- Connect to Your Mobile Device Directly (page 38)
- Connect Job Link Tools Directly (page 38) Real-time Calculations
- Superheat and Subcooling
- Vapor Saturation and Liquid Saturation
- Target Superheat (requires model JL3RH for real-time)
- T1-T2 (3) Type K Thermocouple Jacks
- Suction Line
- Liquid Line
- Outdoor Ambient (3) 1/4” Ports Built-in Micron Gauge Tightness Test Recent Refrigerant List Sealed Sight Glass Heavy Duty Rubberized Construction Rugged Hanging Hook Operation in the Rain (IP54) Data Logging with USB Export
7
Display
°F: Temperature (Fahrenheit) °C: Temperature (Celcius)
Psig: Pressure (pounds/in2) Bar: Pressure MPa: Pressure (megapascals) kPa: Pressure (kilopascals) inHg: Negative Pressure (inches of mercury) cmHg: Negative Pressure (centimeters of mercury)
Microns: Vacuum (microns of mercury) Pascals: Vacuum mBar: Vacuum (millibar) mTorr: Vacuum (millitorr) Torr: Vacuum (equivalent to mmHg) Δ/min: Vacuum Rate (differential per minute) h:m:s: Hours:Minutes or Minutes:Seconds
SH: Superheat (suction line - vapor saturation) SC: Subcooling (liquid saturation - liquid line) VSAT: Vapor Saturation Temperature (from P-T chart) LSAT: Liquid Saturation Temperature (from P-T chart)
TSH: Target Superheat (calculated from IDWB and ODDB) T1-T2: Measurement Differential SLT : Suction Line Temperature (low side) LLT : Liquid Line Temperature (high side) ODDB: Outdoor Dry Bulb Temperature IDWB: Indoor Wet Bulb Temperature
LOG: Data Logging in Progress Job: Job Slot (1-9) of Data Log Span: Hours (Hrs) of Data Logging Interval: Seconds (Sec) Between Logged Measurements
R: Return Psychrometer S: Supply Psychrometer DB: Dry Bulb from Psychrometer WB: Wet Bulb from Psychrometer DP: Dew Point from Psychrometer %RH: Relative Humidity from Psychrometer BTU/LBM: Enthalpy from Psychrometer (BTU per pound mass) KJ/KG: Enthalpy from Psychrometer (kilojoules per kilogram) TΔT: Target Dry Bulb Split from Psychrometers ΔT: Dry Bulb Split from Psychrometers
Lb: Pounds (from wireless scale) Oz: Ounces (from wireless scale) Kg: Kilograms (from wireless scale) g: Grams (from wireless scale)
APO: Auto Power Off Enabled
: Top 10 Refrigerant Selected : Speaker Turned Off
: Battery Life Remaining
: Wireless Signal Strength
98
Pipe Clamp Storage Arms
Metal shorting blocks are for Rapid Rail™ Thermocouple model JL3PC (sold separately)
Display
Buttons
Suction
Line Port
Refrigerant Port
Connect to a refrigerant cylinder directly, to a recovery machine, or to a vacuum pump.
Sight Glass
Front View
Micro USB Port
Removable rubber cover
Liquid
Line Port
(LOW)
(HIGH)
Suction Line Port Valve Liquid Line Port Valve
Fieldpiece 8CFM Vacuum Pump model VP85 (sold separately)
Fieldpiece Recovery Machine model MR45 (sold separately)
1110
SM380V
1234
0000001234
Rear View
Battery Cover Screws
Steel Hanging Hook
Battery Door Finger Pull
4 Digit Job Link® System ID
Use when connecting to the Job Link Mobile App for testing and reporting
(LLT) Liquid Line
Thermocouple Jack
Shown not inserted enough
(ODDB) Outdoor
Thermocouple Jack
Shown without thermocouple
(SLT) Suction Line
Thermocouple Jack
Shown fully inserted
Thermocouple Bumpers
Bumpers help secure thermocouple plugs. Pipe clamp thermocouples have indents on the plug that line up with the bumper when fully inserted.
1312
Operation
Buttons
A beep sounds when a button is pressed. A double beep sounds when a button is pressed and the function is not possible at that time. The speaker can be muted altogether (page 22).
Press 2 sec to toggle power. Press to toggle backlight.
Scroll through refrigerants or change values.
ENTER: Confirm a changed value or activate an ALARM (page 18). MENU: Enter the menu (page 22) or exit a mode. VIEW: Display ODDB, TSH, or T1-T2 (page 15). AIR: Display SLT/LLT or various return and supply air measurements
from optional psychrometers (page 15).
WIRELESS ON/OFF: Toggle wireless communication ON/OFF. Turn
wireless OFF to increase battery life.
ZERO WEIGHT: Press 2 sec to zero (tare) weight from a wireless
scale (page 26).
TEST TIGHTNESS: Enter tightness test setup (page 20). ZERO PRESSURE: Press 2 sec to zero the displayed pressures.
VIEW Select
Press VIEW to cycle through ODDB (outdoor dry bulb), TSH (target superheat), and T1-T2 (middle display - bottom display).
ODDB: Live reading of the rear ODDB thermocouple jack. ODDB does
not show if set to manual value (page 27).
TSH: Live target superheat calculated from ODDB and IDWB. Each of
these measurements can be live or manually entered (page 17).
T1-T2: Live simple subtraction of the bottom display (T2) from the
middle display (T1). With SLT and LLT showing, you can check for
a temperature drop across a filter drier. With R and S showing, you can check the effect of the indoor unit. With TΔT and ΔT showing, you can see how close the actual ΔT is to the target.
AIR Select
Press AIR to display various calculations and measurements from Job Link system psychrometers you’ve assigned (page 26). The parameter is briefly shown when pressed, then shown at the top of the LCD.
Press AIR for >1 second to view SLT/LLT.
Recent Refrigerants ( )
A rolling list of your 10 most recent refrigerants, indicated by a When you power off your manifold, the current refrigerant is added automatically to this dynamic list of 10.
, is stored above the main list.
SLT : Live reading of suction line temperature. LLT : Live reading of liquid line temperature.
R: Live reading from return air psychrometer. S: Live reading from supply air psychrometer.
TΔT: Live target dry bulb split from psychrometers. ΔT: Live actual dry bulb split from psychrometers.
1514
Superheat (SH) and Subcooling (SC)
Superheat is the amount of heat added to refrigerant after changing to a vapor in the evaporator. Subcooling is the amount of heat removed from refrigerant after changing to a liquid in the condenser. View both live at the same time!
1. Use ARROWS to select the system refrigerant.
2. Close all manifold valves.
3. Connect EPA approved refrigerant hoses to LOW and HIGH side ports.
4. Fully plug pipe clamp thermocouples into SLT and LLT rear jacks.
5. Hand tighten both the LOW side hose to suction line service port and
the HIGH side hose to the liquid line service port.
6. Clamp the SLT thermocouple to the suction line between the
evaporator and compressor, at least 6 inches from the compressor.
7. Clamp the LLT thermocouple to the liquid line between the
condenser and metering device, as close to the service port as
possible.
8. Purge hoses as you open HIGH and LOW manifold valves.
9. View superheat and subcooling in real-time.
• Ensure system has stabilized before using superheat or subcooling to
adjust the charge of the system.
• To add or remove refrigerant connect the tank/cylinder/machine to
the center refrigerant port. Use manifold valves to precisely charge
or recover refrigerant as needed. Follow recommended charging or
recovery practices from equipment manufacturer and training.
• When superheat and/or subcooling cannot be calculated, “- - - - ”
will be displayed. If superheat and/or subcooling is negative, “Below
Typical Range” will show. In rare cases this is normal, but usually a
thermocouple is disconnected or the selected refrigerant is incorrect.
Target Superheat (TSH)
Compare target superheat (TSH) to actual superheat (SH) when charging fixed orifice air conditioning systems. TSH is continually calculated from indoor wet bulb (IDWB) and outdoor dry bulb (ODDB) temperatures.
IDWB: By default, this is a manually set value of 60.0°F.
For a live measurement, assign the optional model JL3RH wireless
psychrometer (page 26). ODDB: By default, this is the live measurement of the ODDB
thermocouple jack. If you prefer a static measurement, assign a
manual value (page 27).
1. Connect the included type K bead thermocouple to the ODDB
thermocouple jack. Use the alligator clip to locate the bead in a
shaded area of the condenser to measure the temperature of air
entering the condenser.
2. Press VIEW until ODDB is displayed to verify the measurement.
If you changed ODDB to a manually set value, it will be used to
calculate TSH but will not be displayed.
3. Measure IDWB after the filter, just in front of the indoor coil. If
a psychrometer is assigned, you can press AIR until wet bulb is
displayed to verify the measurement.
4. Press VIEW until TSH is displayed.
1716
Deep Vacuum
Follow recommended evacuation practices from equipment manufacturer and training. Alarms can be adjusted in the MENU (page 28).
1. Close all manifold valves (including shutoff valve to pump).
2. Setup your tools and equipment (see diagram).
Connect HIGH port to liquid line service port.
Connect LOW port to suction line service port.
Connect refrigerant (middle) port to vacuum pump making sure to
have a shutoff valve between the pump and manifold.
3. Turn on your vacuum pump.
4. Open shutoff valve between pump and manifold.
The vacuum sensor is now exposed to your pump, but it will not
display until HIGH/LOW manifold valves are opened. This ensures the
measurement is of the system and not just the manifold.
5. Open HIGH and LOW manifold valves.
6. Press ALARM to activate the low alarm.
The stopwatch starts. The rate of change is displayed in units
per minute. The smaller the rate of change, the closer you are to
stabilization. You may need to improve your setup if rate slows well
before reaching your desired vacuum (see Tips for Better Evacuations).
7. Once the the low alarm level is reached, the backlight blinks and
alarm sounds. Press any button (other than ENTER) to silence alarm.
8. Close shutoff valve to block the pump.
Do not close HIGH and LOW valves or you’ll block the system and
measure just the manifold!
9. Turn off your vacuum pump.
10. Press ALARM to activate the high alarm and start the stopwatch.
11. Once the high alarm level is reached, the backlight blinks, alarm
sounds, and the stopwatch stops. Press any button (other than
ENTER) to silence alarm.
12. Close HIGH and LOW manifold valves.
The vacuum sensor is now blocked from the system (page 39).
Tips for Better Evacauations
• Remove schrader cores and depressors with a core removal tool.
• Use shortest vacuum rated hoses with largest diameter available.
• Do not evacuate through hoses with low loss fittings.
• Inspect the rubber seals at both ends of your hoses for damage.
• Change pump oil before and during the job. Change pump oil on­the-fly without losing vacuum with Fieldpiece vacuum pumps.
• When the vacuum pump is blocked, a slow rise that stabilizes may signify moisture is still present in the system. A continuous rise to atmosphere indicates a leak. Check hoses, tools, or the system itself.
• Measurements are less representative of the entire system when the vacuum pump is on because pumping creates a pressure gradient. Block the pump and allow the system to stabilize before assuming the measurement is of the entire system.
1918
Test Tightness (Pressure Test)
After working on a refrigerant-side component of an emptied system, it’s a good idea to pressurize the system with dry nitrogen and check for pressure drops before evacuation.
1. Pressurize the system with dry nitrogen. Pressure levels vary with
the equipment you’re testing. Always check with the manufacturer.
2. Connect the low side (suction line) port to the system and wait for
the pressure to stabilize. You can connect the high side (liquid line)
as well to help monitor stability, but the pressure differential (P.diF)
calculation is only using the low side sensor.
3. Attach SLT clamp to the pipe you’re going to pressurize.
This temperature is used to compensate for any temperature changes
between the start and end of the test.
To deactivate temperature compensation, unplug or unassign SLT
before starting the test; SLT will not be shown or used.
4. Press TEST TIGHTNESS to prepare test.
5. Press ENTER to start the test.
The stopwatch starts.
Real-time compensated pressure change is labeled P.diF.
Real-time temperature is labeled SLT.
Real-time temperature change is labeled ΔT.
6. Press ENTER to stop the test.
The stopwatch, P.diF, and ΔT freeze.
If P.diF is negative, there may be a leak in the system.
If P.diF is positive, SLT or nitrogen temperature may be unstable.
High and low side pressures and SLT continue to display, but they are
no longer being used.
7. Press ENTER to exit the test.
Test for Noncondensables
If head pressure seems high even after cleaning coils, optimizing airflow, and other routine maintenance, you may have noncondensables trapped in the system. Noncondensables can reduce efficiency, performance, and put extra stress on system components. Noncondensables can enter the system in many ways, and your initial system service may be following years of poor service that introduced the noncondensables.
1. Use ARROWS to select the system refrigerant.
2. Unpower the compressor, but allow the condenser fan to run.
3. Connect high side port to the system to view system pressure.
4. Clamp one thermocouple to the discharge line.
5. Clamp the other thermocouple to the liquid line.
6. Clip the ODDB thermocouple to measure the air entering the
condenser.
7. Monitor all three temperatures until they all stabilize and show the
same value.
8. View the subcooling (SC) calculation on the display.
The closer SC is to 0.0°, the fewer noncondensables are trapped.
Depending on the system, a negative SC may suggest a need to
recover, evacuate, and charge with virgin refrigerant.
• To save battery life, the screen will turn off after 3 hours of testing, but will continue to test. Press any button to turn the screen on.
2120
Menu
Press MENU to enter the menu where most
settings are located. Use arrows to scroll through the menu and press ENTER to select one of the below menu items.
LogData: Enter data logging setup mode (page 23). (StopLog): If data logging, stop the log (page 23). AutoOff: Enter auto off timer setup mode (page 24). CalTemp: Enter calibration mode for Type K jacks (page 25). Wireless Sources: Enter wireless source setup mode (page 26). TSH Sources: Enter target superheat source setup mode (page 27). Units: Enter units setup mode (page 28). Vac Alarms: Enter vacuum alarm setup mode (page 28). Mute: If unmuted, mute the speaker. (Unmute): If muted, unmute the speaker. Backlight Timer: Enter backlight timer setup mode (page 29). Adv Pressure Cal: Enter advanced calibration mode for pressure
sensors (page 30).
F Ware: Enter firmware view and update mode (page 32). Restore Settings: Enter restore factory settings mode (page 33). (Delete Log File): If a log file is saved to the internal flash drive,
enter delete log file mode (page 34).
Format Drive: Enter format drive mode (page 34).
Data Logging
Log measurements and resulting calculations, such as Superheat, at chosen spans and intervals. Save up to 9 Jobs (logs) to the internal flash drive.
MENU/LogData
1. Use ARROWS to scroll through Jobs.
The display will alternate between the % free space on the drive and
the % of space the chosen Job uses.
2. Press ENTER to select.
If a Job already exists in that slot, use ARROWS then ENTER to choose
whether or not you want to save over that Job.
3. Use ARROWS to set the Span (total time).
It’s a good idea to use new batteries if setting up a long span. If
batteries run out during a Job, the log will automatically stop and
save, then the SMAN manifold will turn off.
4. Press ENTER to select.
5. Use ARROWS to set the Interval (time between measurements).
6. Press ENTER to select and begin logging data until the Span ends.
LOG will blink to indicate the log is still active.
• Press MENU to exit setup at any time.
• Press MENU and select StopLog to stop the Job and return to
standard operation. The Job will be saved.
• To save battery life, the screen will turn off after 3 hours of logging,
but will continue to log. Press any button to turn the screen on.
• Some buttons and features (including auto power off) are disabled
until the Job ends.
• Jobs are saved as .csv files.
• Connect to your computer via the micro USB port under the
removable rubber cover. View its internal flash drive just like any
other USB drive.
2322
Auto Power Off (APO)
To save battery life, your SMAN manifold automatically powers off after a set time of no button presses.
MENU/AutoOff
1. Use ARROWS to scroll through times (default is 30 min).
2. Press ENTER to select and exit. If changes were made, choose
whether or not you want to save changes.
• Press MENU to exit at any time. If changes were made, choose
whether or not you want to save changes.
• APO is automatically disabled when data logging.
Temperature Calibration
Thermocouples (T/C) are not calibrated directly. Instead, each T/C jack (ODDB, SLT, LLT) must be calibrated to the particular T/C that is plugged into it. Though it’s possible for a calibration to hold for years, it’s best practice to calibrate regularly if only to verify accuracy.
Calibration is quick and easy, requiring just a known temperature to calibrate to. Ice water is probably the most accurate and readily available known temperature (32.0°F, 0.0°C) in the field.
MENU/CalTemp
1. Stabilize a large cup of ice water by stirring. Pure, distilled water
will be the most accurate.
2. Immerse the sensing end of the thermocouple in the ice water.
3. Use ARROWS to select the temperature you want to calibrate (SLT,
LLT, or ODDB).
4. Press ENTER to select.
5. Use ARROWS to adjust the temperature to match 32.0°F (0.0°C)
making sure the ice water is continually stirred. The calibration
range is limited to ±7°F (±3.8°C) in order to help prevent mistakes.
6. Press ENTER to save and return to the list of temperatures.
• Press MENU to exit at any time. If changes were made, choose
whether or not you want to save changes.
• If you have a wireless thermocouple (model JL3PC) assigned and
wireless is on, calibration is for the wireless thermocouple.
• Calibration of a wireless thermocouple (model JL3PC) does not
override a wired thermocouple calibration. You can switch between
wired and wireless without having to recalibrate.
2524
Wireless Measurement Sources
Assign wireless Job Link system tools to core manifold measurements such as pipe temperature or to broader measurements such as refrigerant weights and psychrometrics.
Wireless OFF: Line temperatures (SLT and LLT) are automatically
assigned to their type K jacks. Wireless ON: SLT and LLT type K jacks DO NOT override an
assigned wireless source.
MENU/Wireless Sources
1. Use ARROWS to scroll through the list of measurements.
2. Press ENTER to select.
3. Turn on any wireless sources you want to assign.
If your Job Link system tool has a selector switch, ensure it’s set to
match the measurement.
4. Use ARROWS to scroll through detected measurement sources.
Job Link system tools are displayed by their 4 digit ID, usually found
on the back of the tool.
5. Press ENTER to select and return to the list of measurements.
• Press MENU to exit at any time. If changes were made, choose
whether or not you want to save changes.
• Most Job Link system tools have a switch that selects a side of the
system. Set it to match the measurement you’re assigning it to.
• Select Clear to set a source to its factory default source. This is
useful when you want to use a previously assigned tool at the job
site, but do not want to use it with the SMAN manifold.
• A wireless Return psychrometer is assigned to both Return air and
IDWB (page 17) when selected.
Target Superheat (TSH) Sources
Target superheat is calculated from outdoor dry bulb (ODDB) entering the condenser coil and indoor wet bulb (IDWB) entering the evaporator coil. Assign a wireless psychrometer to return air and plug in a thermocouple to ODDB for real-time comparison of target vs actual superheat.
MENU/TSH Sources
1. Use ARROWS to toggle between IDWB and ODDB.
2. Press ENTER to select.
3. Use ARROWS to scroll through detected measurement sources.
Job Link system tools are displayed by their 4 digit ID, usually found
on the back of the tool. ODDB cannot be set to wireless.
4. Turn on any wireless sources you want to assign.
If your Job Link system tool has a selector switch, ensure it’s set to
match the measurement.
5. Press ENTER to select and exit or go to next.
• Press MENU to exit at any time. If changes were made, choose
whether or not you want to save changes.
• Most Job Link system tools have a switch that selects a side of the
system. Set it to match the measurement you’re assigning it to.
• Select Clear to set a source to its factory default source. This is
useful when you want to use a previously assigned tool at the job
site, but do not want to use it with the SMAN manifold.
• A wireless Return psychrometer is assigned to both Return air (page
15) and IDWB when selected.
• Turning wireless on/off does not change the assigned source.
• If ODDB is set to a manually set value, the thermocouple jack is
deactivated even if a thermocouple is plugged in.
2726
Units
Each measurement can have its own unit of
measure.
Backlight Timer
The backlight turns off automatically after a set time of no button presses.
MENU/Units
1. Use ARROWS to scroll through the list of measurements.
2. Press ENTER to select.
3. Use ARROWS to scroll through units of measure.
4. Press ENTER to select and return to the list of measurements.
• Press MENU to exit at any time. If a change was made before
pressing ENTER, choose whether or not you want to save the change.
Vacuum Alarms
Set high and low vacuum alarms so you know when you’ve reached an appropriate vacuum (Low) and time how long it takes to rise after blocking the pump from the system (High).
MENU/Vac Alarms
1. Use ARROWS to toggle between high and low alarm.
2. Press ENTER to select.
3. Use ARROWS to adjust the alarm trigger.
4. Press ENTER to select and exit or go to next.
• Press MENU to exit at any time. If changes were made, choose
whether or not you want to save changes.
• The low alarm cannot go higher than the high alarm.
• The high alarm cannot go lower than the low alarm.
• Press ENTER (ALARM) while in deep vacuum to activate the next
alarm (None >> Low >> High >> None).
MENU/Backlight Timer
1. Use ARROWS to scroll through times (default is 2 min).
2. Press ENTER to select and exit. If changes were made, choose
whether or not you want to save changes.
• Press MENU to exit at any time. If changes were made, choose whether or not you want to save changes.
2928
Advanced Pressure Calibration
Typical HVACR service does not require this procedure, but you can occassionally calibrate the pressure sensors to maintain highest accuracy.
It works by measuring the temperature of virgin refrigerant and applying an offset to match the pressure to that refrigerant’s P-T chart.
1. Calibrate a beaded thermocouple to the ODDB jack (page 25).
2. Store a virgin refrigerant cylinder, upright and untouched, in the
stable ambient environment for at least 24 hours.
3. Leaving the cylinder in the same place it was left to stabilize,
connect the cylinder to either the HIGH or LOW side port.
4. Cap the 2 unused ports.
If you don’t have caps with seals, you can connect both ends of a
refrigerant hose to the unused ports or hose seats. Some refrigerant
will remain in the hoses which you need to recover after calibration.
5. Use ARROWS to select the refrigerant type in the cylinder.
6. Use tape to attach the ODDB thermocouple bead halfway up the
cylinder to measure the temperature of the refrigerant.
7. Press VIEW if ODDB is not shown.
8. Open both HIGH and LOW side manifold valves.
9. Open the refrigerant cylinder valve.
The pressure inside cylinder should now be displayed on both HIGH
and LOW side pressure sensors.
10. Allow the pressure readings and ODDB temperature to stabilize.
11. Press MENU.
12. Use ARROWS to show Adv Pressure Cal.
13. Press ENTER to initiate calibration of the pressure sensors.
14. Each pressure sensor will briefly display “Good” if successful or “Err”
if unsuccessful, then return to normal operating mode.
Troubleshooting an “Err” message
1. Measured pressure was less than 10 psig.
Refrigerant cylinder may be nearly empty.
Valves may be closed.
2. Measured pressure was not within ±3psig of VSAT pressure on the P-T chart.
Thermocouple may not have been calibrated properly.
Thermocouple may not have been attached properly to cylinder.
Thermocouple may have not been connected to ODDB jack.
Refrigerant cylinder pressure was unstable.
Refrigerant cylinder temperature was unstable.
Refrigerant selected did not match refrigerant in cylinder.
3130
Firmware View and Update
Firmware often becomes available as new
refrigerants and features become available.
Before entering this mode, download from www.fieldpiece.com and transfer from the computer to the manifold via the micro USB port on the side.
Or you can initiate an update over the air from your mobile device running the Job Link system mobile app while the version is displayed.
MENU/F Ware
1. View the firmware version on the top line, P/T chart on the
second line, and radio region on the bottom line.
2. If a new firmware file is found on the internal flash drive the new
versions will be shown. Choose whether or not you want to update.
3. Once installation begins you will see a bar moving across the
screen. “donE” will appear and your SMAN manifold will turn off when finished.
Press MENU to exit at any time before installation begins.
During installation, buttons are disabled.
User settings are not deleted.
Log files are not deleted.
Restore User Settings
Restore factory default user settings when you
want a fresh start.
MENU/Restore Settings
1. Use ARROWS to select Yes or No.
2. Press ENTER to select and exit.
• Press MENU to exit at any time. If changes were made, choose
whether or not you want to save changes.
• If you choose to restore, it may take a few seconds before returning to standard operation.
3332
Delete Log File
Clear up space by deleting old logs or just view
free space available.
MENU/Delete Log File
1. Use ARROWS to scroll through Jobs (logs). The display will alternate between the % free space on the drive and the % of space the chosen Job uses.
2. Press ENTER to select a Job to delete. Choose whether or not you want to delete that Job.
3. If you choose to delete, it may take a few seconds to finish. If no more Jobs are found, the manifold returns to standard operation.
• Press MENU to exit at any time.
Format Internal Flash Drive
Quickly clear up maximum space by
reformatting the internal flash drive. This deletes everything on the drive including log files, firmware update files, and any other files added manually.
MENU/Format Drive
1. Use ARROWS to select Yes or No.
2. Press ENTER to select and exit.
Maintenance
Cleaning
Wipe with damp cloth to clean the exterior.
Do not use solvents.
Battery Replacement
The batteries must be replaced when the battery life indicator is empty. Once the batteries are drained beyond operating voltage, “Low Bat” briefly appears and the manifold turns off.
Unscrew the 4 cover screws and pull out the rear battery cover. Replace the 6 AA batteries and properly dispose of the old ones.
Using Different Refrigerants
You can use different refrigerants, but be sure to purge your manifold with nitrogen before connecting to a system with a different refrigerant. Contamination can hurt system performance and cause damage.
Temperature Calibration
See page 25.
• Press MENU to exit at any time.
• If you choose to format, it may take a few seconds before returning to standard operation.
• User settings are not deleted.
Advanced Pressure Calibration
See page 30.
3534
Specifications
Display: LCD (5 inches diagonal) Backlight: Blue (adjustable duration) Low Battery Indication: is displayed when the battery voltage
drops below the operating level.
Over Range Display: OL for pressure, - - - - for temperature Auto Power Off: 30 minutes of inactivity (adjustable) Maximum Manifold Pressure: 800 Psig (5500 kPa) Battery Type: 6 x AA alkaline Battery Life: 350 hours typical
(without vacuum, backlight, and wireless)
Radio Frequency: 2.4 GHz Wireless Range: 350 feet (106 meters) line of sight.
Distance decreases through obstructions.
Data Port: Micro USB (for extracting data logs or updating firmware) Operating Environment: 32°F to 122°F (0°C to 50°C) at <75% RH Storage Environment: -4°F to 140°F (-20°C to 60°C) at <80% RH
(with battery removed)
Temperature Coefficient: 0.1 x (specified accuracy) per °C (0°C to
18°C, 28°C to 50°C), per 1.8°F (32°F to 64°F, 82°F to 122°F)
Weight: 4.03 lbs (1.83 kg) Water Resistant: Designed to IP54 US Patent: www.fieldpiece.com/patents Refrigerants: New refrigerants are continually being added so be
sure to visit www.fieldpiece.com for the latest firmware.
R448A
R422B
R414B
R407A
R290
R115
R11 R12 R13 R22 R23 R32 R113 R114
R116 R123 R124 R125 R134A R236FA R245FA
R401A R401B R402A R402B R403B R404A R406A
R407C R407F R408A R409A R410A R413A R414A
R416A R417A R417C R420A R421A R421B R422A
*Maximum pressure: 580 Psig (4000 kPa)
R422C R422D R424A R427A R428A R434A R438A
R449A R450A R452A R452B R453A R454B R458A
R500 R501 R502 R503 R507A R508B R513A R600
R600A R601 R601A R744* R1233ZD R1234YF R1234ZE
Temperature
Sensor Type: Type K thermocouple
(nickel chromium/nickel aluminum)
Jack Type: (3) Type K thermocouple Range: -50°F to 257°F (-46°C to 125°C), limited by the thermocouple
specification. Display range is -95°F to 999.9°F (-70°C to 537.0°C).
Resolution: 0.1°F (0.1°C) Accuracy: Shown accuracies are after field calibration.
±(1.0°F) -95°F to 200°F, ±(2.0°F) 200°F to 999.9°F; ±(0.5°C) -70°C to 93°C, ±(1.0°C) 93°C to 537.0°C
Pressure
Sensor Type: Absolute pressure sensors Port Type: (3) 1/4” standard NPT male flare fittings Pressure Range and Units: 580 Psig (English), 40.00 Bar (Metric),
4.000 MPa (Metric), and 4000 kPa (Metric)
Negative Pressure Range and Units:
29 inHg (English), 74 cmHg (Metric)
Resolution: 0.1 Psig; 0.01 Bar; 0.001 MPa; 1 kPa; 0.1 inHg; 1 cmHg Negative Pressure Accuracy:
29 inHg to 0 inHg: ±0.2 inHg; 74 cmHg to 0 cmHg: ±1 cmHg
Pressure Accuracy:
0 Psig to 200 Psig: ±1 Psig; 200 Psig to 580 Psig: ±(0.3% of reading + 1 Psig); 0 Bar to 13.78 Bar ±0.07 Bar;
13.78 Bar to 40.00 Bar: ±(0.3% of reading + 0.07 Bar); 0 MPa to 1.378 MPa: ±0.007 MPa;
1.378 MPa to 4.000 MPa: ±(0.3% of reading + 0.007 MPa); 0 kPa to 1378 kPa: ±7 kPa; 1378 kPa to 4000 kPa: ±(0.3% of reading + 7 kPa)
37
Deep Vacuum
Low Pressure Sensor High Pressure SensorDeep Vacuum Sensor
Sensor Type: Thermistor Port Type: (3) 1/4” standard NPT male flare fittings Range and Units:
50 to 9999 microns of mercury (English), 6 to 1330 Pascals (Metric),
0.06 to 13.3 mBar (Metric), 50 to 9999 mTorr (Metric),
0.05 to 10 Torr (Metric, equivalent to mmHg)
Best Resolution:
1 micron of mercury (below 2000 microns), 1 Pascal (below 250 Pascals),
0.001 mBar (below 2.5 mBar), 1 mTorr (below 2000 mTorr),
0.001 Torr (below 2.5 Torr)
Accuracy @ 77°F (25°C):
±(5% of reading + 5 microns of mercury), 50 to 1000 microns ±(5% of reading + 1 Pascal), 7 to 133 Pascal ±(5% of reading + 0.01 mBar), 0.067 to 1.33 mBar ±(5% of reading + 5 mTorr), 50 to 1000 mTorr ±(5% of reading + 0.005 Torr), 0.067 to 1 Torr
Wireless Compatibility
Latest compatibility at www.fieldpiece.com
Job Link System Minimum Device Requirement:
BLE 4.0 devices running iOS 7.1 or AndroidTM Kitkat 4.4
Wireless Measurement Source Assignments:
Suction line temperature: Fieldpiece model JL3PC (set to blue) Liquid line temperature: Fieldpiece model JL3PC (set to red) Supply air psychrometer: Fieldpiece model JL3RH (set to blue) Return air psychrometer: Fieldpiece model JL3RH (set to red) Refrigerant weight scale: Fieldpiece models SRS3, SRS3P
Manifold Diagram
LOW Port
LOW
Valve
REF
Port
HIGH Valve
Certifications and Module IDs
EN 300 328
2ALHR005
IC: Industry Canada
22518-BT005
Regulatory Compliance Mark
Waste Electrical and Electronic Equipment
Restriction of Hazardous Substances Compliant
IFETEL: Federal Telecom Institute
RCPFI2A19-0287
HIGH
Port
3938
FCC Statement
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
1. Reorient the receiving antenna.
2. Increase the separation between the equipment and receiver.
3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
4. Consult the dealer or an experienced radio/TV technician for help.
FCC Caution:
Any changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate this equipment.
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This device and its antenna(s) must not be co-located or operating
in conjunction with any other antenna or transmitter. IMPORTANT NOTE: FCC Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set
forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.
IC Statement
This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions:
1. This device may not cause interference.
2. This device must accept any interference, including interference that may cause undesired operation of the device.
L’émetteur/récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d’Innovation, Sciences et Développement économique Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes :
1. L’appareil ne doit pas produire de brouillage;
2. L’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
IMPORTANT NOTE: IC Radiation Exposure Statement:
This equipment complies with IC RSS-102 radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.
Cet équipement est conforme aux limites d’exposition aux rayonnements IC établies pour un environnement non contrôlé. Cet équipement doit être installé et utilisé avec un minimum de 20cm de distance entre la source de rayonnement et votre corps
4140
IFETEL Statement
La operación de este equipo está sujeta a las siguientes dos condiciones: (1) es posible que este equipo o dispositivo no cause interferencia perjudicial y (2) este equipo o dispositivo debe aceptar cualquier interferencia, incluyendo la que pueda causar su operación no deseada.
The operation of this equipment is subject to the following two conditions: (1) this device or device may not cause harmful interference, and (2) this device or device must accept any interference, including interference that may cause undesired operation.
Limited Warranty
This product is warranted against defects in material or workmanship for one year from date of purchase from an authorized Fieldpiece dealer. Fieldpiece will replace or repair the defective unit, at its option, subject to verification of the defect.
This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unreasonable use of the machine.
Any implied warranties arising from the sale of a Fieldpiece product, including but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to the above. Fieldpiece shall not be liable for loss of use of the machine or other incidental or consequential damages, expenses, or economic loss, or for any claim of such damage, expenses, or economic loss.
State laws vary. The above limitations or exclusions may not apply to you.
Obtaining Service
Visit www.fieldpiece.com/rma for the latest information on how to obtain service. Warranty for products purchased outside of the U.S. should be handled through local distributors. Visit our website to find your local distributor.
4342
SM380V
© Fieldpiece Instruments, Inc 2019; v18