Field Controls LS-550A Installation Manual

HIGH TEMPERATURE VENT LIMIT SWITCH
Models: LS-140A, LS-550A
Items Included: 1) High temperature vent limit switch 1) TCA-1 thermocouple junction block (LS-550A)
2) 2-1/2 to 5-1/2 inch hose clamps 1) 6 foot length of 12/2 wire (LS-550A)
4) Wiring quick connect terminals (LS-140A) 1) ROMEX connector
Installation of a High temperature vent limit switch is recommended for LP and Natural gas fired power vented and natural draft water heaters. This device is installed to limit the vent temperature in either plastic pipe (140 up tanks and/or inadequate venting. Wiring MUST be in accordance with the National Electrical Code and applicable local codes.
The Field Controls High temperature vent limit switch MUST be installed by a qualified agency in accordance with the manufacturer’s installation instructions.
The definition of a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in, and is responsible for, the installation and operation of gas appliances, who is experienced in such work, familiar with all the precautions required, and has complied with the requirements of the authority having jurisdiction.
Before and after adding this safety control on existing appliances, an installation inspection in accordance with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis is recommended to determine the operating condition of the appliance.
CAUTION: Disconnect Electrical Power When Wiring High tem perature vent limit switch
MODEL P/N
LS-140A 46564100 SILVER 15 A 120 AC 140 AUTOMATIC SPDT PLASTIC VENT APPLICATIONS LS-550A 46564200 SILVER 15 A 120 AC 550 AUTOMATIC SPDT B-VENT APPLICATIONS
0
F temperature limit) or B vent installations (5500 F temperature limit) caused by scaled
CONTACT
MATERIAL
LOAD RATING
AMPS VOLTS
LIMIT
SETPOINT °F
RESET
SWITCH
TYPE
APPLICATION
2630 Airport Road · Kinston, NC 28504
Phone: 252-522-3031· Fax: 252-522-0214
www.fieldcontrols.com
INSTALLATION OF LS-140A SWITCH ON A POWER VENTED WATER HEATERS WITH PLASTIC PIPE
1. Disconnect Electrical Power to the water heater and shut off the gas supply to the water heater.
2. Drill a 5/16” diameter hole through the side of the plastic vent pipe at least 2-inches above the outlet connection on the power venter on the water heater (See Figure 1).
3. Remove the housing cover of the limit switch.
4. Loosen the two hose clamps and route them through the two mounting tabs on the ends of the switch housing (See Figure 2).
5. Apply bead of high temperature silicone sealant round the base of the temperature probe (See Figure 3).
6. Insert the temperature probe into the 5/16” diameter hole in the vent pipe and secure the switch to the pipe with the two hose clamps (See Figure
4).
Figure 1
Figure 2
Wiring the LS-140A Limit switch
Wire the High temperature vent limit switch in accordance with the National Electrical Code, manufacturer's recommendations and/or applicable local codes.
THE UNIT MUST BE GROUNDED WHEN WIRED TO ANY 120 VOLT CONTROLS. Check ground circuit to make certain that the unit has been
properly grounded. The wiring should be protected by an over current circuit device rated at 15 amperes. Caution must be taken to ensure that the wiring does not come into contact with any heat source. All line voltage and safety control circuits, between the vent damper and the appliance, MUST be wired in accordance with the National Electrical Code for Class I wiring or equivalent methods.
BEFORE STARTING WIRING, TURN OFF ALL ELECTRICAL POWER TO THE APPLIANCE AT THE APPLIANCE SERVICE SWITCH OR CIRCUIT BREAKER!!
1. Locate the wire connection to the solenoid valve on the gas valve.
2. Cut one of the leads to the solenoid valve and attach a female wire connector to each wire (See Figure 5 and 6).
3. Attach the two male wire connectors to installer supplied wire leads (See Figure 7), connect them to the