Field Controls GSK-4, GSK-250M, GSK-3 User Manual

GAS SPILLAGE SENSING KIT
Model: GSK-3, GSK-4, GSK-250M
Installation of a spillage SAFETY Switch is recommended for LP and Natural gas fired systems with draft hoods, draft diverter, or gas barometric draft controls. This device is installed to detect flue gas spillage caused by a blocked flue system and/or inadequate draft. This device MUST be installed by a qualified installer in accordance with the manufacturer's installation instructions. Wiring MUST be in accordance with the National Electrical Code and applicable local codes.
CAUTION: Disconnect Electrical Power When Wiring Spillage Swit ch
MODEL P/N
GSK-3 46086400 GOLD 24VA mV-24AC 180 MANUAL SPST NC Gas-fired mV or 24VAC GSK-4 46086402 GOLD 24VA mV-24AC 200 MANUAL SPST NC
GSK-250M 46086404 SILVER 24VA mV-24AC 250 MANUAL SPST NC Steam Boilers
CONTACT
MATERIAL
LOAD RATING
AMPS VOLTS
SETPOINT °F RESET
SWITCH
TYPE
APPLICATION
Gas-fired mV or 24VAC,
where slower response
time is a requirement
INSTALLATION ON DRAFT HOODS I
N-LINE HORIZONTAL DRAFT HOOD (See Figures 1 & 2)
1. Two (2) switches are recommended on these hoods. Mount the switches approximately 2 1/2 inches from the opposite ends and sides of the draft hood opening. (See Figure 1)
2. The switch should not contact the metal. They should be mounted at least 3/4 inch below the hood opening. (See Figure 2) Mount with supplied sheet metal screw.
B
UILT-IN DRAFT HOOD (See Figures 3 & 4)
1. Two (2) switches are recommended on appliances without a factory supplied spill switch. Mount the switches approximately 3 inches
from the side of the draft hood opening and the second switch (if used) 3 inches from the opposite side of the draft hood. (See Figure
3) If the appliance has a factory built-in switch, mount a single switch 3 inches from the side opposite the factory switch.
2. The switch should not contact the metal. They should be mounted at least 1 inch below the hood opening. (See Figure 4) Mount with supplied sheet metal screw.
V
ERTICAL DRAFT HOOD
(See Figures 5 & 6 or Figure 13 for water heaters)
1. Two (2) switches are recommended on appliances without a factory supplied spill switch. Mount the spill switch onto the bottom edge of the draft hood and the second switch (if used) approximately 90 degrees from the first switch or 90 degrees from the factory supplied switch. (See Figure 5)
2. The switch should not contact the metal. They should be mounted at least 3/4 inch below the hood opening. (See Figure 6) Mount with supplied sheet metal screw.
Figure 1
Figure 2
Figure 3
Figure 4
Page 2
Figure 5
Figure 6