Field Controls FC155HRV, FC200HRV, FC150ERV Operation And Installation Manual

69-Field
0412
Heat Recovery Ventilators
Operation and Installation Manual
This product earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US EPA. It meets ENERGY STAR requirements only when used in Canada.
*
FC95HRV*
FC155HRV
FC200HRV*
FC150ERV
All manuals and user guides at all-guides.com
all-guides.com
Getting to Know your Heat and Energy Recovery Ventilator Ventilation and Control Options
How the Dehumidistat Works (Colder Climates) Glossary and Additional Information
Warranty........................................................................................3
Healthy Home System Control (HHSC)
Dehumidistat .................................................................................4
Dehumidistat Ventilation Control .................................................5
Optional Vent Timer Control ........................................................6
Maintenance Routine for HRV .....................................................7
Technical Data - Model FC95HRV ...........................................8-9
Technical Data - Model FC155HRV ..........................................10
Technical Data - Model FC200HRV ..........................................11
Technical Data - Model FC150ERV...........................................12
Installation Methods....................................................................13
Installation Diagrams.............................................................14-16
Installation
Suspend the Unit with the Adjustable Hanging Straps ...............17
Drain Connection and Grilles .....................................................18
Weatherhood Installation ............................................................19
Installation of the Dehumidistat or
Dehumidistat Ventilation Control ...............................................20
Installation and Operation of 20 Minute and
20/40/60/ Minute Timers.............................................................21
Installation of the Healthy Home System Control (HHSC) ..22-23 Installation of the HHSC with the DH1
and 20/40/60 Minute Timers (test a)...........................................24
Installation of the DHVC Ventilation Control
with 20/40/60 Minute Timers (test c)..........................................25
Interlocking HRV/ERV to an Air Handler/Furnace Blower Setting “Standby” when using a Main Control Operating the HRV/ERV without a Main Control and
Adding Dry Contacts..................................................................26
Balancing the Air Flows..............................................................27
Balancing the Air Flows with a Pitot Tube.................................28
Air Flow Balancing using the Door Ports ...................................29
Balancing Dampers .....................................................................30
Troubleshooting your HRV/ERV System...................................31
Wiring Diagram ..........................................................................32
2
Table of Contents
IMPORTANT -
PLEASE READ THIS MANUAL
BEFORE INSTALLING UNIT.
CAUTION
Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed, by measuring the air flows of the HRV, by using the balancing procedure found in this manual. NEVER install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment.
WARNING
Disconnect the power from the unit before cleaning or servicing.
To prevent electrical shock, it is extremely important to confirm the polarity of the power line that is switched by the safety (disconnect) switch. The hot line (black) is the proper line for switching. Use either a voltmeter or test lamp to confirm the absence of a voltage between the disconnect switch and ground (on the cabinet) while the door is open. This procedure must be followed, as dwellings are occasionally wired improperly. Always enure the proper grounding of the unit.
ATTENTION
Do not apply electrical power to the unit until after the completion of the installation (including the installation of low voltage control wiring).
Ensure the Installation and wiring is in accordance with CEC, NEC, and local electrical codes.
Due to ongoing research and product development, specifications, ratings, and dimensions are subject to change without notice.
Plug the unit into a standard designated (120 VAC) electrical outlet with ground.
•The use of an extension cord with this unit is not recommended. If the installation requires further wiring, have a licensed electrician make all of the electrical connections. The recommended circuit is a separate 15 amp/120 volt circuit.
NOTE
Due to ongoing research and product
development, specifications, ratings, and
dimensions are subject to change without notice.
All manuals and user guides at all-guides.com
3
Thank you for purchasing a Field Control Heat/Energy Recovery Ventilator (HRV/ERV). The HRV/ERV provides fresh air to your home while recovering energy from the air it exhausts. There are numerous benefits to a properly installed, operated, and maintained HRV/ERV:
Exhausts the stale, contaminated air, found in today’s tight buildings.
Recovers the majority of the energy contained in the exhausted stale air.
Uses the recovered energy to preheat or precool the fresh outdoor air introduced into the house
Distributes the fresh air throughout your home.
Getting to Know your Heat and Energy Recovery Ventilator (FC Series)
Optional Controls are available to adjust the amount of ventilation in your home:
The Healthy Home System™ Control (HHSC) will automatically deliver fresh air to your home.
The Dehumidistat Control (DHI) can be used in conjunction with the HHSC to provide additional ventilation for high indoor humidity levels.
The Dehumidistat Ventilation Control (DHVC) is a manual control which features ON/OFF, High speed, Low Speed, and an electronic dehumdistat.
*Refer to the individual control pages of this manual for more information about these controls.
Ventilation and Control Options*
High indoor humidity levels, during the heating season, have become a problem in many well insulated, tight homes. Excessive condensation on the windows is a visual sign of high indoor humidity levels. High indoor humidity levels can result in mold and mildew and the eventual degradation of the building structure itself.
Your HRV/ERV reduces indoor humidity levels when the outdoor air is drier than the indoor air. These conditions usually occur during the heating season when outdoor temperatures are less than 15°C (59°F). During the heating season, the operation of the HRV/ERV may reduce indoor humidity levels sufficiently to eliminate the need for further dehumidification.
If your home requires further dehumidification, use the dehumidistat feature located on any optional main control (refer to the Operation and Installation Manual for Optional Control information). This feature aggressively addresses high indoor humidity levels by initiating high speed ventilation when the indoor humidity levels rise above the adjustable set point on the control.
Refer to the main control instructions located in the Operation and Installation Manual for instructions on how to set the dehumidistat. The dehumidistat function on the main control should be set to OFF for all seasons except the heating season, because a dehumidifying effect occurs only when the outdoor air is dryer than the indoor air. Set the RH level to 80 to turn the dehumidistat OFF. (Refer to the control instructions for information on how to set the Dehumidistat). DEHUMIDISTAT DISABLE - automatically disables the dehumidistat function on the main control when outdoor temperatures exceed 15°C (59°F) for a full 24 hour period. All other HRV features and functions operate normally while the dehumidistat function is disabled. DEHUMIDISTAT RE-ENABLE - automatically re-enables the dehumidistat function if either the outdoor temperature drops below 15°C (59°F) for a full 24 hour period or if the HRV is reset (unplugged for 30 seconds).
How the Dehumidistat Works (Colder Climates)
DEFROST MODE - To ensure reliable operation during cold weather, the HRV automatically cycles through its defrost mode when the outdoor temperatures drop below freezing.
HRV/ERV - a Heat Recovery Ventilator (HRV/ERV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. During the winter months, heat recovered from the stale air, before it is exhausted to the outdoors, warms the incoming cold fresh air. During the summer months, when the indoor space is air conditioned, the HRV/ERV helps to cool the incoming fresh air with the cool exhausted stale air.
SELF-TEST - Each time the HRV/ERV is powered/energized, the self-test function automatically initiates. The HRV/ERV cycles through the available speeds and tests the damper motor operation. The HRV/ERV defaults back to the previous operational mode and speed selection after the self-test (approximately 60 seconds in duration).
STANDBY - The HRV/ERV is powered/energized and waiting for ventilation to be initiated by an external control.
TIMERS - These optional controls may be installed at specific exhaust locations (bathrooms etc.) to initiate high speed ventilation.
Heat Recovery Ventilators (HRV) carry a Lifetime Warranty on the heat recovery core and a 5 (five) year replacement parts warranty. Energy Recovery Ventilators (ERV) carry a 5 (five) year warranty
on the energy recovery core and a 5 (five) year replacement parts warranty.
Glossary and Additional Information
Warranty
All manuals and user guides at all-guides.com
Your HRV/ERV system produces a dehumidifying effect when outdoor humidity levels are lower than indoor humidity levels. These conditions occur normally when outdoor termperatures are below 60°F. An additional dehumidification effect is achievable with the Optional Dehumidistat (Part DH1).
The Optional DH1 Control may be combined with the Healthy
Home System Control (HHSC). The DH1 will initiate high speed
ventilation when the moisture level in the home exceeds the set
point on the control. Once the humidity in the house is reduced,
the HRV will revert back to the HHSC automatic setting. The
Dehumidistat should be set to OFF for all seasons except the
heating season.
Dehumidistat (Part DH1)
Healthy Home System Control (HHSC)
Dehumidistat Indicator LEDs
Set to the desired humidity level. High speed ventilation will initiate when the indoor moisture level exceeds the set point on the control.
Dehumidistat Adjust button
Th e H ea lt hy Home Sy st em Control ( HHSC) a ct iv at es th e HRV/ERV automatically to deliver fresh air into your home.
Setting the Control
The duration of the ventilation rate is adjustable on the HHSC. Your installer sets up this control during the installation of your system . Refer to the instructions that came with the HHSC for the setup information.
The Healthy Home System™ Control (HHSC)
4
All manuals and user guides at all-guides.com
The Dehumidistat Ventilation Control offers ON/OFF, High Speed/Low speed plus an electronic dehumidistat.
Key Features
2 Speed Fan setting (Low/High)
Electronic Dehumidistat
Instruction Card is inserted in the control
Slim-line design
Connect to 3 wire 20 gauge low voltage wire.
Turning on the Control
Press and release the ON/OFF button. The "ON Indicator Light" will illuminate.
Adjusting the Ventilation Speed
The unit will normally operate at low speed. Press and release the SPEED button to initiate high speed ventilation. The "High Speed Indicator LED" will illuminate.
Humidity Control
Your unit will produce a dehumidifying effect when outdoor humidity levels are lower than indoor humidity levels. Never use the dehumidistat feature when outdoor temperatures are above 59° F (15° C).
Setting the Dehumidistat
Press and r el ease t he D EHUMIDI ST AT b ut ton until t he DEHUMIDISTAT LED is at the desired setting. After 5 seconds the dehumidistat light will either flash or be on continuous.
A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation. A continuous light indicates the humidity level is lower than the setting.
5
The Dehumidistat Ventilation Control Part #DHVC
Instruction card
Dehumidistat Indicator LEDs
ON/OFF button
High/Low Speed button
High Speed Indicator LED
On indicator light
*Install a jumper between 2 (ON) and 3 (RED) on the HRV/ERV terminal block to configure the ON/OFF button to ON/STANDBY. Refer to “Setting Standby when using a Main Control in this manual.
ATTENTION
All manuals and user guides at all-guides.com
The timer will override the Operational Mode (regardless of the setting) and initiate high speed ventilation. Upon completion of the timer cycle, the HRV/ERV returns to your selected Operational Mode and speed setting.
Lifestyle 20/40/60 Minute Timer
Initiates high speed ventilation for 20, 40 or 60 minutes. The 20/40/60 Minute Status Lights indicate high speed operation.
Lockout Mode is useful if you wish to disable the timer. Set lockout by holding the Select Button for 5 seconds. Unlock by holding for 5 seconds.
Optional Vent Timer Control (VTC)
Select Button
20/40/6 0 Mi nu te Status Lights
If the system does not have a main control
installed, the HRV/ERV Terminal Block must have
a jumper installed between 2 (ON) and 3 (RED).
Refer to “Operating the HRV/ERV without a Main
Control” in this manual.
ATTENTION
6
All manuals and user guides at all-guides.com
all-guides.com
1. Inspect Exterior Hoods at least once a month.
Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen).
WARNING: Blockage of hoods may cause an imbalance.
2. Clean Air Filters (clean twice a year)
The standard filters equipped with your HRV are removable and washable.
a) simply open access door and slide core out
b) remove filter clips
c) once clips are removed filters can be taken off the core to be
rinsed with water or a combination of mild soap and water. Do not clean in the dishwasher
d) to re-assemble, place clean filter(s) (wet or dry) back into their
positions against the core and return clips to their original position
e) slide core back into its’ original position
3. Clean Core Twice a Year
a) open access door.
b) carefully grip ends of core and pull evenly outward. Core may
be snug, but will slide out of the channel
c) once removed from the cabinet remove filters
d) wash core in warm soapy water (do not use dishwasher)
e) install the clean filters
f) install clean core
Note: Core installation label on the outer end of the core.
To install the clean core:
a) first mount the bottom flange of the core guide into the bottom
H channel approximately 1/4” (6mm)
b) mo unt t he left or right s id e fla ng e of th e cor e guide
approximately 1/4” (6mm) followed by the other side
c) mount the top flange of the core guide into the top H channel
approximately 1/4” (6mm).
d) with all four corners in place and the core straight and even,
push hard in the centre of the core until the core stops on the back of the cabinet.
NOTE: Core will appear to stick out from cabinet approximately 1/8 (3mm). This is designed this way so that the access door will fit tight against the core.
4. Motors - Maintenance Free
5. Drain (condensate) Line - Clean once a year
Inspect drain line, drain spout, and “P trap for blockage, mould or kinks. Flush with warm soapy water and replace if worn, bent or unable to clean.
6. Clean Duct Work if Required
The duct work running to and from the HRV may accumulate dirt.
Wipe and vacuum the duct once every year. You may wish to
contact a Heating/Ventilation company to do this.
7. General Maintenance - Twice a Year
Wipe down the inside of the cabinet with a damp cloth to remove
dirt, bugs, and debris that may be present.
8. Cleaning the Fans
Fans may accumulate dirt causing an imbalance and/or excessive
vibration of the HRV. A reduction in the air flow may also occur.
In new construction this may result within the first year due to
heavy dust and may oc cur periodically after that ov er time
depending on the outdoor conditions.
unplug the HRV and open the service door
remove the core
remove ducting (metal and/or flexible insulated type) from the red and/or blue ports which are connected immediately in-line with the fan assembly
use a small brush, such as an old toothbrush or pipe cleaner, and insert first
(a) through the lar ge o pe ning of the fan
assembly and then
(b) through the sma ll er o pening in the end
of the fan assembly.
scrub individual fan blades until clean. Avoid moving or damaging balancing flat weight, clip is usually found on one or more of the fan blades
vacuum and wipe
reassemble making sure ducting is reattached firmly and insulation and moisture barrier are sealed and taped
Before attempting this task, thought should be given to having a qualified service technician complete the service work.
Maintenance Routine for HRV
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power unit OFF at disconnect switch(es). Unit may have multiple power supplies.
WARNING
7
All manuals and user guides at all-guides.com
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. The unit has a 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of the cabinet designed to accept the “S” hooks and hanging straps supplied with the unit.
DEFROST
Recirculating defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
WEIGHT 52 lbs. (23.6 kg) SHIPPING WEIGHT 56 lbs (25.4 kg)
ELECTRONICS
Built-in Relay for Interfacing to furnace
OPTIONAL CONTROLS
# DHVC Ventilation Control
2 Speed Fan setting (Low/High) Dehumidistat
#HHSC Healthy Home System Control
Automatically activates the unit to deliver fresh air into your home
#DH1 Dehumidistat
Initiates high speed ventilation when the indoor humidity level exceeds the set point
OPTIONAL TIMERS
#VTC Ventilation Timer Control - Initiates high speed ventilation
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length
OPTIONAL ACCESSORIES
#WH 185 Weatherhoods, Two - 5” (125 mm) c/w 1/4” (6 mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
All units conform to CSA and UL standards.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency thermal **Latent Efficiency moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency takes into account all power inputs
Performance (
HVI certified)
N
et supply air flow in cfm (L/s) against external static pressure
E
.S.P
(external static pressure) [cfm (L/s)]
@
0.1" (25 Pa) 76 (36)
@
0.2" (50 Pa) 73 (34)
@ 0.3" (75 Pa) 70 (33)
@ 0.4" (100 Pa) 66 (31)
@ 0.5" (125 Pa) 60 (29)
Max. Temperature Recovery 88%
Sensible Effectiveness @ 60 cfm (28 L/s) 32°F (0°C) 88%
*Sensible Efficiency @ 60 cfm (28 L/s) 32°F (0°C) 75%
*Sensible Efficiency @ 61 cfm (29 L/s) -13°F (-25°C) 68%
VAC @ 60HZ 120
WATTS / Low speed. 59
WATTS / High speed 150
Amp rating 0.9
Static Press ure (in w.g.)
Air Flow (cfm)
Speed 2
Speed 1
20
30
40
50
60
70
0 0.1 0.2 0.3 0.4 0.5 0.6
80
1 - Low Speed
2 - High Speed
Removable
Heat Recovery
Core
Drain Pan
Drain spout
FRONT TOP
minimum
18 inches (4 59 mm)
required for
service a ccess
Threaded inserts ( 4) at corners
SUPPLY
Fresh air
from outside
5" round col lar
SUPPLY
Fresh air
to building
6" round
(conv. to oval)
collar
EXHAUST
Stale Air
to outside
5" round col lar
EXHAUST
Return air
from building
6" round (co nv. to oval)
collar
18.5"
(470 mm)
18.5"
(470 mm)
16"
(406 mm)
SIDE
Hanging
straps (4)
24.5" (622 mm)
DIMENSIONS FC95HRV inches (mm)
Model FC95HRV
8
All manuals and user guides at all-guides.com
Port Configuration and Airflow Model FC95HRV
In order to make the HRV as space efficient as possible, the INDOOR supply and return ports are converted from round to oval shape. Overall size of the port remains the same. Simply bend a standard duct fitting to the correct shape, and attach to the oval port using the same method as for a round port.
FC95HRV Air Flow
Stale air enters the FRONT-RIGHT side port. The air passes down
the front half of the core, then up the back half of the core and out
the RIGHT-REAR port.
Fresh outdoor air enters the LEFT-REAR port and passes down
the back half of the core. Then the fresh outdoor air passes up the
front half of the core and out the LEFT-FRONT port. This
configuration allows the air to actually travel through the core
twice, which makes the FC95HRV nearly as efficient as a double
core unit.
Round port bent to oval
9
All manuals and user guides at all-guides.com
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of the cabinet designed to accept the “S” hooks and hanging straps supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD. Balancing ports are located in the door.
WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg)
ELECTRONICS
Built-in Relay for Interfacing to furnace
OPTIONAL CONTROLS
# DHVC Ventilation Control
2 Speed Fan setting (Low/High) Dehumidistat
#HHSC Healthy Home System Control
Automatically activates the unit to deliver fresh air into your home
#DH1 Dehumidistat
Initiates high speed ventilation when the indoor humidity level exceeds the set point
OPTIONAL TIMERS
#VTC Ventilation Timer Control - Initiates high speed ventilation
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length
OPTIONAL ACCESSORIES
#WH 186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh
screen
DIMENSIONS FC155HRV inches (mm)
Model FC155HRV
All units conform to CSA and UL standards.
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*
Sensible Efficiency thermal **Latent Efficiency moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(
external static pressure) [cfm (L/s)]
@
0.1" (25 Pa) 144 (68)
@
0.2" (50 Pa) 134 (63)
@ 0.3" (75 Pa) 125 (59)
@ 0.4" (100 Pa) 113 (53)
@
0.5" (125 Pa) 92 (43)
@ 0.6" (150 Pa) 73 (34)
Max. Temperature Recovery 78%
Sensible Effectiveness @
65 cfm (31 L/s) 32°F (0°C) 73%
*Sensible Efficiency @ 65 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency @ 68 cfm (32 L/s) -13°F (-25°C) 66%
VAC @ 60HZ 120
WATTS / Low speed. 49
WATTS / High speed 120
Amp rating 1.4
2
1
20
40
60
80
100
120
140
160
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Static Pre ssur e (in w .g.)
Air Flow (cfm)
2 - High Speed *
1 - Low speed
*
Manufacturers Data
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
BA LANC ING DA MPE R
33 5/8"
(850mm)
STALE AIR
FROM INSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
14 3/4"
(375)
19"
(48 3)
*All Duct Connec tions 6" ( 150mm)
CO NDEN SATE DR AIN S
FI LTE RS
BL OWER S
*NO TE: Fro nt cle aran ce of 25 inch es (6 35 mm)
is r ecom mend ed for s ervi cing u nit.
RE CIRC ULATI NG
DE FROS T
DAM PER
MOT OR
CO RE
BA LANC ING DA MPER
10
All manuals and user guides at all-guides.com
DIMENSIONS FC200HRV
inches (mm)
Model FC200HRV
All units conform to CSA and UL standards.
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of the cabinet designed to accept the “S” hooks and hanging straps supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2
- 1/2" (12 mm) OD. Balancing ports are located in the door.
WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs (33.5 kg)
ELECTRONICS
Built-in Relay for Interfacing to furnace
OPTIONAL CONTROLS
# DHVC Ventilation Control
2 Speed Fan setting (Low/High) Dehumidistat
#HHSC Healthy Home System Control
Automatically activates the unit to deliver fresh air into your home
#DH1 Dehumidistat
Initiates high speed ventilation when the indoor humidity level exceeds the set point
OPTIONAL TIMERS
#VTC Ventilation Timer Control - Initiates high speed ventilation
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length
OPTIONAL ACCESSORIES
#WH 186 Weatherhoods, Two -6” (150 mm) c/w 1/4” (6 mm) mesh
screen
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*S
ensible Efficiency thermal **Latent Efficiency moisture
N
ote: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(
external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 207 (97) @
0.2" (50 Pa) 200 (94) @ 0.3" (75 Pa) 184 (87) @ 0.4" (100 Pa) 171 (80) @
0.5" (125 Pa) 152 (71) @
0.6" (150 Pa) 130 (61) @ 0.7" (175 Pa) 116 (55) @ 0.8" (200 Pa) 86 (40)
Max. Temperature Recovery 74%
Sensible Effectiveness @ 66 cfm (31 L/s) 32°F (0°C) 74%
*
Sensible Efficiency
@ 66 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency @ 109 cfm (51 L/s) -13°F (-25°C) 62%
VAC @ 60HZ 120
WATTS / Low speed. 87
WATTS / High speed 164
Amp rating 1.4
LOW
Hi 1
Hi 2
Hi 3
40
60
80
100
120
140
160
180
200
220
0 0.1 0.2 0. 3 0.4 0. 5 0.6 0. 7 0.8 0. 9
Static Pressure (in w.g.)
Air Flow (cfm)
Hi 3 - High Speed Hi 2 - Medium High Speed Hi 1 - Medium Speed Low - Low speed * Manufacturers Dat a
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
BA LANC ING DA MPE R
33 5/8"
(850 mm)
STALE AIR
FROM INSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
14 3/4"
(375 mm)
19"
(48 3 mm)
*All Duc t Con nec tion s 6" (150 mm )
CO NDEN SATE DR AINS
FI LTE RS
BL OWER S
*NO TE: Fro nt cle aran ce
of 2 5 inch es (63 5 mm) is r ecom mend ed for s erv icin g unit .
RE CIRC ULATIN G
DE FROS T
DAM PER
MOT OR
CO RE
BA LANC ING DA MPE R
All Duct Connections 6” (160 mm)
INSTALLER SELECTABLE HIGH SPEED SETTINGS
Adjustable DIP switches are located on the circuit board. Hi3 is the factory setting. Refer to the Operation and Installation manual for the adjustment instructions.
11
All manuals and user guides at all-guides.com
all-guides.com
12
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FRESH AIR
TO INSIDE
143/4"
(375)
19"
(483)
*All Duct Connections 6"(150mm)
FILTERS
BLOWERS
*NOTE: Front clearance of 25 inches (635 mm)
is recommended
for servicing unit.
MOTOR
ENTHALPIC CORE
33-5/8"
(850)
BALANCING
DAMPER
BALANCING
DAMPER
CORE
Model FC150ERV
DIMENSIONS FC150ERV inches (mm)
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
All units conform to CSA and UL standards.
Static Pressure (in w.g.)
Air Flow (cfm)
20
40
60
80
100
120
140
160
180
200
220
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1 - Low speed
2 - High Speed
2
1
*Sensible Efficiency thermal **Latent Efficiency moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency takes into account all power inputs
Performance
N
et supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 151 (71)
@
0.2" (50 Pa) 140 (66)
@ 0.3" (75 Pa) 131 (62)
@
0.4" (100 Pa) 123 (58)
@ 0.5" (125 Pa) 107 (50)
@ 0.6" (150 Pa) 98 (46)
@ 0.7" (175 Pa) 81 (38)
@0.8 " (200 Pa) 60 (28)
S
ensible Effectiveness
@ 64 cfm (30 L/s) 32°F (0°C) 81%
*
Sensible Efficiency
@
64 cfm (30 L/s) 32°F (0°C) 69%
T
otal Efficiency 50%
@ 64 cfm (30L/s) 95°F (35°C) 47%
VAC @ 60HZ 120
WATTS / Low speed. 63
WATTS / High speed 173
A
mp rating 1.4
LATENT RECOVERY/MOISTURE TRANSFER CORE
The cross-flow energy recovery core transfers heat and water vapor between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE ERV
Four threaded inserts at corners of case designed to accept the "S" hooks and hanging straps supplied with the unit.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Door balancing ports.
WEIGHT 75 lbs. (34Kg) SHIPPING WEIGHT 77lbs. (35Kg)
ELECTRONICS
Built-in Relay for Interfacing to furnace
OPTIONAL CONTROLS
# DHVC Ventilation Control
2 Speed Fan setting (Low/High) Dehumidistat
#HHSC Healthy Home System Control
Automatically activates the unit to deliver fresh air into your home
#DH1 Dehumidistat
Initiates high speed ventilation when the indoor humidity level exceeds the set point
OPTIONAL TIMERS
#VTC Ventilation Timer Control - Initiates high speed ventilation
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length
OPTIONAL ACCESSORIES
#WH 186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh
screen
WARRANTY
Units carry a five (5) year warranty on the enthalpic (ERV) core and a 5 year replacement parts warranty.
All manuals and user guides at all-guides.com
13
The Three Methods of Installation
Th e fo ll owing three installation m ethods are for the HRV/ERV system:
The Simplified installation.
The Partially Dedicated Installation
The Fully Dedicated Installation
Simplified Installations
The Simplified Installation draws stale air from the cold air return duct of the air handler/furnace and introduces an equal amount of fresh air farther downstream into the cold air return. Refer to "Simplified Installation Diagrams".
The air handler/furnace blower must be running when the unit is operating for this system to be effective. Refer to
"Interlocking the HRV/ERV to an Air Handler/Furnace Blower".
Partially Dedicated Installations
The Partially Dedicated Installation draws stale air from specific points in the house and introduces an equal amount of fresh air into the cold air return. Refer to "Partially
Dedicated Installation Diagrams".
Stale air ducts should be installed in areas of the home where the poorest indoor air quality exists (bathrooms and kitchen). Each location with a stale air duct should have a timer to initiate high speed ventilation. Refer to "Optional Timers" in this manual.
The air handler/furnace blower should be running when the HRV is ope rating to eve nly dis tr ibute the f re sh air throughout the house. Refer to "Interlocking the HRV/ERV to an Air Handler/Furnace Blower".
Fully Dedicated Installations
The Fully Dedicated Installation draws stale air from specific points in the house and delivers fresh air to specific locations of the house. This system is not connected to an air h andle r/f urnac e. Refer to " The Ful ly D edi cated Installation Diagrams" in this manual.
Stale air ducts should be installed in areas of the home where the poorest indoor air quality exists (bathrooms and kitchen). Each location with a stale air duct should have a timer which will initiate high speed ventilation. Refer to "Optional Timers" in this manual.
Fresh air ducts should be installed to all bedrooms and living areas, excluding bathrooms, kitchen and utility areas. Grilles should be located high on a wall or in ceiling locations. Grilles that diffuse the air comfortably are recommended. Refer to "Grilles" in this manual. Special care should be taken in locating grilles if the floor is the only option available. Areas such as under baseboard heaters will help to temper the air.
Optional in-line duct heaters are available for mounting in the supply duct work to add heat if required.
Installing the Ducting Between the HRV/ERV & Living Areas in the House
A well designed and installed ducting system will allow the HRV/ERV to operate at its maximum efficiency.
All ducts should be kept short and have as few bends or elbows as possible to maximize airflow. Forty-five degree elbows are preferred to 90° elbows. Use "Y" tees instead of straight tees whenever possible.
All duct joints must be fastened with screws, rivets or duct sealant and wrapped with mastic or quality duct tape to prevent leakage. Mastic is preferred but if duct tape is used, we recommend aluminum foil duct tape.
Galvanized (rigid) ducting from the HRV/ERV to the living areas in the house is recommended whenever possible althoug h flexibl e duct c an be u sed in m oderati on if necessary.
A short length (approximately 12 inches or 300mm) of non- me tallic flexible ins ul at ed duct should b e conn ec te d between the HRV/ERV and the supply/exhaust duct system to avoid possible noise transfer through the duct system.
All ducts running through attics and unheated spaces must be sealed and insulated to code.
Installation Methods
ATTENTION
Applicat ion s such a s greenh ous es, a tri ums , swi mming p ool s, saunas, etc . h ave u niq ue ven tilation requirement s whi ch sho uld be addressed with an isolated ventilation system.
All manuals and user guides at all-guides.com
DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN
Installation Notes
Unit is normally balanced on HIGH speed with the furnace blower ON.
A minimum separation of 40 inches (1m) is recommended between the two direct connections.
The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.
Weatherhood arrangement is for drawing purposes only. Six feet (2m) minimum separation is recommended. The Weatherhood must also be 18" (460mm) above grade minimum.
The airflow must be confirmed on site using the balancing procedures found in this manual
Spring-Loaded Backdraft Damper
Install the Backdraft Damper with the leaf hinge vertical. The damper is installed on the “Stale Air to Outside Collar”.
4” (102mm) Backdraft Damper Part No. 99-RSK4 5” (127mm) Backdraft Damper Part No. 99-RSK5 6” (152mm) Backdraft Damper Part No. 99-RSK6 8” (203mm) Backdraft Damper Part No. 99-RSK8
The Stale Air to Outside air duct requires a Backdraft Damper.This damper prevents outdoor air from entering the HRV during the operation of the Furnace/ Air Handler while the HRV is in standby, OFF or Recirculate.
WARNING
RETURN AIR
40" (1m) MINIMUM
Outdoors
Cool Air
Return
3' min.
recommended
Forced Air
Furnace
Dampers for balancing airflows
Backdraft Damper
Leaf Hinge
Simplified Installation Diagrams
Simplified Installation (Return/Return Method)
Key Points
The HRV/ERV must be balanced.
It is mandatory that the furnace blower run continuously or HRV/ERV operation be interlocked with the furnace blower. (Refer to Interlocking the HRV/ERV to an Air Handler/Furnace Blower.”)
The duct configuration may change depending on the HRV/ERV model. See specifications for your unit.
Check local codes / authority having jurisdiction for acceptance.
A backdraft damper is required in the exhaust air duct to prevent outdoor air from entering the unit when the Furnace/Air Handler is running and the unit is in Standby, OFF or Recirculate.
Sizing the Ductwork
It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended.
The amount of air (cfm) that an HRV/ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system. Static pressure is a measure of resistance imposed on the blower by length of duct work plus the number of fittings used in the duct work.
DIRECT CONNECTION of the SUPPLY AIR STREAM and
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN.
14
(not included)
All manuals and user guides at all-guides.com
DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN
(Stale air drawn from key areas of home)
Forced Air
Furnace
Outdoors
EXHAUST AIR from various parts of home. i.e. bathrooms (if required), kitchens (if required).
Cool Air
Return
Return Air
3' min.
recommended
Installation Notes
Unit is normally balanced on HIGH speed with the furnace blower ON.
Weatherhood arrangement is for drawing purposes only. Six feet (2m) minimum separation is recommended. The Weatherhood must also be 18" (460mm) above grade minimum.
The airflow must be confirmed on site using the balancing procedures found in this manual.
Dampers for balancing airflows
Backdraft Damper
leaf hinge
Spring-Loaded Backdraft Damper
Install the Backdraft Damper with the leaf hinge vertical. The damper is installed on the “Stale Air to Outside Collar”.
4” (102mm) Backdraft Damper Part No. 99-RSK4 5” (127mm) Backdraft Damper Part No. 99-RSK5 6” (152mm) Backdraft Damper Part No. 99-RSK6 8” (203mm) Backdraft Damper Part No. 99-RSK8
The Stale Air to Outside air duct requires a Backdraft Damper.This damper prevents outdoor air from entering the HRV during the operation of the Furnace/Air Handler while the HRV is in standby, OFF or Recirculate.
WARNING
Partially Dedicated Installation Diagrams
Partially Dedicated System
This installation enables stale air to be drawn from the poorest air quality areas of the home (bathrooms, kitchen).
Key Points
The HRV/ERV must be balanced.
It is recommended that the furnace blower run continuously or HRV/ERV operation be interlocked with the furnace blower to evenly distribute the fresh air throughout the house.(Refer to Interlocking the HRV/ERV to an Air Handler/Furnace Blower.”)
The duct configuration may change depending on the HRV model. See specifications for your unit.
Check local codes/authority having jurisdiction for acceptance.
A backdraft damper is required in the exhaust air duct to prevent outdoor air from entering the unit when the Furnace/Air Handler is running and the unit is in Standby, OFF or Recirculate.
Sizing the Ductwork
It is th e responsi bi li ty of the inst al ler to ensure al l ductwork is sized and installed as designed to ensure the system will perform as intended.
The amount of air (cfm) that an HRV/ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system. Static pressure is a measure of resistance imposed on the blower by length of duct work plus the number of fittings used in the duct work.
15
(not included)
All manuals and user guides at all-guides.com
Outdoors
Installation Notes
Unit is normally balanced on HIGH speed with the furnace blower ON.
Weatherhood arrangement is for drawing purposes only. Six feet (2m) minimum separation is recommended. The Weatherhood must also be 18" (460mm) above grade minimum.
The airflow must be confirmed on site using the balancing procedures found in this manual.
Dampers for balancing airflows
Stale air from various parts of home. i.e. bathrooms (if required) Kitchens (if required)
Fresh air to house - main living areas. bedrooms, livingroom, rec. room, etc.
Fully Dedicated Installation Diagrams
Fully Dedicated System
This is a stand alone HRV/ERV system which is not connected to a force air system. Stale air is drawn from key areas of the home (bathroom, kitchen) while fresh air is supplied to main living areas.
Key Points
The HRV/ERV must be balanced.
The duct configuration may change depending on the HRV/ERV model. See specifications for your unit.
Check local codes / authority having jurisdiction for acceptance.
16
All manuals and user guides at all-guides.com
all-guides.com
Installation
STEP 4. Level the unit from left to right and front to back.
- Adjust the unit down by lifting up on the buckle.
- Adjust the unit up by pulling down vertically on the Hand Loops while lifting up the bottom of the cabinet.
Location
Install the unit in a heated space that provides convenient space for service access. A typical location is in either a mechanical room or an area close to the outside wall within close proximity to where the weatherhoods are mounted. If a basement area is inconvenient or non- existent, install the unit in a utility or laundry room.
Attic installations are not recommended due to:
A) the complexity of work to install
B) freezing conditions in the attic
C) difficulty of access for servicing and cleaning
Leave sufficient clearance at the front of the access door for servicing the air filters and core. The recommended clearance is a minimum of 25" (635 mm) for opening and closing the door. Field Controls provides four straps for hanging the unit from the basement floor joists.
Hand Loops
Buckles
Pull down on the hand loops while lifting the bottom of the unit.
I
mproper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
WARNING
Unit must be installed level to ensure proper condensate drainage. Due to the broad range of installation and operational conditions, consider the possibility of condensation forming on either the unit or connecting ducting. Objects below the installation may be exposed to condensate.
CAUTION
Hand Loops
Screws (not included)
Buckles
Joist
Washers (not included)
Hanging Strap grommets
“S” hooks
Note:This illustration of the unit may vary from the unit you are installing.
DETAIL
Suspend the Unit with the Adjustable Hanging Straps
STEP 1. Insert the screws and washers (not included) through
the Hanging Strap grommets and fasten to the joists.
STEP 2. Unscrew the 4 machine screws located on the upper
side of the unit. Attach the "S" hooks and reinsert the machine
screws.
STEP 3. Hook the bottom grommets of the straps through the "S" hooks. Pull down vertically on the hand loops while lifting up the bottom of the cabinet. Repeat at opposite end of the unit.
Hand Loops
Straps
STEP 5. Fold the hand loops and excess strap and secure with a
nylon tie (not included).
Use 4 screws and 4 washers (not incldued) to attach the hanging straps to the floor joists. The washer must be wider than the eyelet of the grommet on the hanging strap.
By design, the adjustable hanging straps reduce the possibility of noise, resonance, and harmonics.
Note: Do not pull the Hand Loops in a horizontal or lateral direction during the installation/adjustment process.
17
All manuals and user guides at all-guides.com
Drain Connection (HRV only)
Grilles
Drain Connection
The HRV may produce some condensation during a defrost cycle. This water should flow into a nearby drain, or be taken away by a condensate pump.
The HRV cabinet has prepunched holes for the drain (see below). Insert the drain spout through the hole in the drain pan. Be sure to install the "O ring" which seals each spout to the pan. HAND TIGHTEN the washer and lock nut which hold the drain spout in place.
Construct a P-Trap using the plastic tee connector. Cut two lengths of 1/2" drain hose (not included) and connect the other ends to the two drain spouts. Position the "T" fitting to point upward and connect the drain line. Tape or fasten base to avoid any kinks. Pour a cup of water into the drain pan of the HRV after the drain connection is complete. This creates a water seal which will prevent odors from being drawn up the hose and into the fresh air supply of the HRV.
Adjustable grilles should be used to balance the flow rates into and out of various rooms. The grilles should not be adjusted after balancing the unit.
Grilles or diffusers should be positioned high on the wall or in the ceiling. Kitchen Exhaust grilles must never be connected to the range hood. They should be installed at least 4 feet (1.2 m) horizontally away from the stove.
Field supplied balancing dampers should be installed external to the unit to balance the amount of stale air being exhausted with the amount of fresh air being brought into the house. Refer to Air flow Balancing section.
The Techgrille
The TECHGRILLE is a round, fully adjustable grille, which provides superior, quiet air distribution.
4” (100 mm) Part No. 99-EAG4
5” (125 mm) Part No. 99-EAG5
6” (150 mm) Part No. 99-EAG6
The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point or freeze protection must be provided.
CAUTION
D
RAIN
SPOUT
ZIP TIE
TO DRAIN
TEE
CONNECTOR
DRAIN
SPOUT
P
RE-PUNCHED HOLES (2)
D
RAIN PAN DRAIN PAN
1/2 " I.D.
D
RAIN HOSE
DRAIN HOSE PLUMBING
DRAIN
SPOUT
DRAIN
SPOUT
TO DRAIN
1/2" HARD PIPE
TEE
JOINT
PRE-PUNCHED HOLES (2)
DRAIN PA N D RAIN PAN
HARD PIPE PLUMBING
Drain trap and tubing MUST be below bottom of door with 1/4" per foot downwards slope away from unit.
CAUTION
Note: Secondary drain pan may be required to protect from condensate leakage.
CAUTION
Do not mount exhaust grille within 4’ (1.2m) (horizontally) of a stove to prevent grease from entering the unit.
18
All manuals and user guides at all-guides.com
19
Weatherhood Installation
Installing the Ducting from the Weatherhoods to the HRV/ERV
The inner and outer liners of the flexible insulated duct must be clamped to the sleeve of the weatherhoods (as close to the outside as possible) and the appropriate port on the HRV/ERV. It is very important that the fresh air intake line be given special attention to make sure it is well sealed. A good bead of high quality caulking (preferably acoustical sealant) will seal the inner flexible duct to both the HRV/ERV port and the weatherhood prior to clamping.
To minimize air flow restriction, the flexible insulated duct that connects the two outside weatherhoods to the HRV/ERV should be stretched tightly and be as short as possible.
Twisting or folding the duct will severely restrict air flow.
Hard (rigid) ducting which has been sealed and insulated should be used for runs over 10’ (3.3 m). Refer to your building code.
Intake Weatherhood Requirements
Should be located upstream (if there are prevailing winds) from the exhaust outlet
At least 6' (2 m) from the exhaust weatherhood
At least 6' (2 m) away from dryer vents and furnace exhaust (medium or high efficiency furnaces)
A minimum of at least 6' (2 m) from driveways, oil fill pipes, gas meters, or garbage containers
At least 18" (460 mm) above the ground, or above the depth of expected snow accumulation
At least 3' (1 m) from the corner of the building
Do not locate in a garage, attic or crawl space
Exhaust Weatherhood Requirements
At least 6' (2 m) from the ventilation air intake
At least 18" (460 mm) above ground or above the depth of expected snow accumulation
At least 3' (1 m) away from the corner of the building
Not near a gas meter, electric meter or a walkway where fog or ice could create a hazard
Not into a garage, workshop or other unheated space
When installing the weatherhood, its outside perimeter must be sealed with exterior caulking.
Weatherhoods
Fixed covered weatherhoods have a built-in bird screen with a 1/4" (6 mm ) mes h to p revent f or ei gn objects f ro m entering the ductwork.
5” (125 mm) Part No.WH 185 6” (150 mm) Part No.WH 186
Weatherhood Installation
1. Thermal Collar slides over galvanized sleeve of Weatherhood.
2. Fasten Thermal Collar to Belt.
3. Slide the Insulated Flexible Ducting over theWeatherhood's galvanized sleeve and fasten it to the Thermal Collar.
4. Hood is hinged to allow for easy access for cleaning of bird screen.
W
1/4" (6 mm) SCREEN
(front view)
EXTERIOR
WALL
SCREEN
(side view)
C
OLLAR IS SUPPLIED TO
ENSURE VAPOUR BARRIER
IS 100% SEALED TO
WALL PLATE
12" galvanized
pipe supplied
36" (1m)
recommended min.
36" (1m)
recommended min.
6' (2m)
recommended min.
18" (460mm) min.
18" (460mm) min.
OUTSIDE CORNER
INTAKE
EXHAUST
INSIDE CORNER
CAUTION
Weatherhood arrangement - requires a minimum of 6' (2m) separation and a minimum of 18" (460mm) above the ground, or above the depth of expected snow accumulation.
ATTENTION
Local codes may require greater distances for exhaust and intake.
All manuals and user guides at all-guides.com
20
Installation of the Dehumidistat or Dehumidistat Ventilation Control
Standard Series Controls may be installed onto a flush mounted 2" x 4" electrical switch box or it may be surface mounted onto a wall.
Only 1 master control should be installed to a ventilation system (the Face Plate on this illustration may not be exactly the same as yours).
1. Remove the Operating Instructions Card from the top of the Control (Figure A).
2. Separate the Face Plate from the Back Plate by firmly pulling apart (Figure B). Be careful not to damage Face Plate Contact Pins.
3. Place the Back Plate of the control in the desired location on the wall and pencil mark the wall in the center of the Wire Opening, Top Screw Hole and Bottom Screw Hole (Figure C).
4. Remove the Back Plate and drill a 3/8" opening in the wall to allow for the Wire Opening and a 1/8" hole for the Wall Anchors for the top and bottom screw holes (Figure D).
5. Pull 3/20 wire through the opening in the wall and the Wire Opening of the Back Plate (Figure C).
6. Connect Red, Green and Yellow to the Wiring Terminals located on the Back Plate (Figure C).
7. Secure a single wire to the Wire Retainer located on the Back Plate (Figure C).
8. Attach the Back Plate to the wall using the 2 supplied screws and anchors.
9. Att ac h the Face Pl ate t o the Back Pl ate ( Figure B). Note: Be careful to correctly align the Face Plate to avoid damaging the Face Plate Contact Pins.
10. Insert the Operating Instructions Card into the control (Figure A).
11. Connect the 3/20 wire to the Terminal Block located on ventilator (Figure E).
ATTENTION
Pay special attention not to damage the Contact Pins when attaching and detaching the Face Plate. (Figure B)
Operating Instructions Card
Figure A -
Face Plate
Figure E
Terminal Block located on ventilator
Yellow to YELLOW #4
Red to RED #3
Green to GREEN #5
Use 3/20 wire
Red #3
Yellow #4
Green #5
Back
Plate
Figure B
Face Plate Contact Pins
Face Plate
Separate the Face Plate from the Back Plate.
Side View
P
Figure C
Front View of Back Plate
Wire Opening
Wiring Terminals
Wire Retainer
TOP
Top Screw Hole
Bottom Screw Hole
Drill a 1/8” hole for the Top Screw and Anchor
Figure D
Drill holes in wall
Drill a 3/8” hole for the Wire opening
Drill a 1/8” hole for the Bottom Screw and Anchor
Correct Installation of Back Plate
Wall Face
Dehumidistat Sensor Openings to room air allow accurate sensor readings.
Figure F
Back Plate
Face Plate Contact Pins
Face Plate
All manuals and user guides at all-guides.com
21
Installation and Operation of 20/40/60 Minute Timer
Operating your 20/40/60 Minute Timer
Press and release the Select Button to activate high speed override. The High Speed Status Light will illuminate and the unit will run on high speed ventilation for 20 minutes.
The 20/40/60 Minute timers provide an extended override time of 20 - 40 additional minutes simply by pressing and releasing the select button.
The High Speed Status Light will dim after 10 seconds of run time.
The High Speed Status Light will flash during the last 5 minutes of the cycle.
All timers connected to the unit will illuminate for the duration of the override when the Select Button is pressed.
Lockout Mode
Lockout Mode is used to disable the timers.
The timer can be set to lockout mode by pressing and holding the Select Button for five seconds. After five seconds, the High Speed Status Light will flash; release the
Select Button. The timer is now in lockout mode. If the Select Button is pressed during lockout mode the High Speed Status Light will momentarily illuminate but no
override will be initiated.
If lockout mode is initiated when the timer is activated, the timer will continue its timed sequence but will not allow any further overrides to be initiated. Lockout mode can be unlocked by pressing and holding the Select Button for five seconds. After five seconds the High Speed Status Light will stop flashing. Release the Select Button and the timer will now operate normally.
Terminal Block Connections
(from Timer to Terminal Block) Yellow on timer to YELLOW #4 Red on timer to RED #3 Green on timer to GREEN #5
Red #3
Yellow #4
Green #5
High Speed Status Lights
Select Button
initiates high speed ventilation for 20, 40 or 60 minutes.
Yellow
Red
Green
NOTE ABOUT TIMERS
Timers mount in standard 2” x 4” electrical boxes.
Wire multiple timers individually back to the unit.
Use 3/20 low voltage wire
If the system does not have a main control
installed, the HRV Terminal Block must have a
jumper installed between 2 (ON) and 3 (RED).
Refer to “Operating the HRV without a Main
Control” in this manual.
ATTENTION
All manuals and user guides at all-guides.com
all-guides.com
22
Installation of the Healthy Home System™ Control (HHSC)
Choose a Location
The HHSC controller can be installed anywhere in your home. To simplify the installation, locate the HHSC control near the HVAC system and/or the HRV/ERV, since the HHSC does not require routine adjustment or occupant interaction.
To provide the occupants with direct access to the functions of the controls, install optional accessory controls throughout the house.
How To Install the Controller
1. Separate the HHSC controller cover from the wall plate (mounting base) to expose mounting holes (see illustration).
2. Route wires through large hole in the mounting base. Mount base against wall and mark wall through 3 mounting holes.
3. If mounting on a metal or wood surface, drill three 1/8-in. pilot holes in wall where marked for the supplied mounting screws. If mounting on drywall or other surface, drill appropriate holes for wall anchors or other means of attachment.
4. Secure mounting base to wall with either the 3 screws provided or other fasteners, while ensuring that all wires extend through the hole in mounting base.
5. Adjust length and routing of each wire to reach the proper terminal and connector block on mounting base, while leaving a 1/4 in. length of extra wire. Strip only 1/4 in. of insulation from each wire to prevent adjacent wires from shorting together when connected.
6. Connect wires to their respective terminals on the connector block. (Figure 1) Both (R) and (C) must be connected for proper operation. Improper wiring or installation may damage the controller. Ensure wiring is correct before proceeding with installation or turning the unit on.
7. Push any excess wire into wall and against mounting base.
8. Snap cover onto base, while ensuring pins align with sockets in connector.
9. Once powered the HHSC automatically enters into operating mode.
Complete the Wiring Connections
1. Refer to subsequent wiring diagrams in this manual that correspond to the desired control configuration.
NOTE: Disregard any wiring schematic(s) included with the HHSC Control Installation Instructions that do not pertain to
HRV/ERV control. The HHSC is also typically used to control an FAD fresh air damper.
2. Complete all wiring connections before restoring power to the HVAC system and HRV/ERV.
Programming the HHSC Control
1. Balance the fresh and stale airflows as instructed in this manual.
2. Determine the cfm flow rate as instructed in this manual.
3. To obtain the desired rate of fresh air exchange, refer to the HHSC Control Installation Instructions to determine the On/Off timer settings for the HHSC Control. Use the
cfm flow rate determined in step 2 as the computed or
measured fresh air flow rate (as calculated in the HHSC instructions). To ensure adequate ventilation, ensure that the “Fan On” time is equal to or greater than the “Vent On” time, as programmed in the HHSC Control.
4. For continuous operation of the HRV/ERV, set “Fan On” and “Vent On” to “Un” (unlimited), and “Fan Off and “Vent Off” to any setting except “Un”. This setting also causes the HVAC fan to run continuously.
NOTE: The HHSC Control is factory programmed with the default settings of the two On/Off timer values. No configuration is required to use these factory default settings.
Default settings: FAN OFF 20 minutes FAN ON 10 minutes VENT ON 10 minutes VENT OFF 20 minutes
Illustration of HHSC Control with cover off
All manuals and user guides at all-guides.com
23
Installation of the Healthy Home System™ Control (HHSC)
1
2
3
4
5
6
7
8
9
10
LO
ON
R
Y
G
HI
C
NO
NC
BK
FACTORY-INSTALLED JUMPER DO NOT REMOVE
LO
HI
24C
*
R
C Wt
Gt
Gf
V
HHSC CONTROL
RCWYG RYWG
THERMOSTAT
FURNACE OR HEAT PUMP
HRV/ERV WIRING TERMINALS
12V/24 VAC Field wiring, 20 AWG min. required
* Connect V Terminal on the HHSC Control to the Hi Terminal (instead of Lo) for a shorter ventilation period.
Setting up the HHSC Control
The duration of the ventilation rate is adjustable on the Healthy Home System™ Control (HHSC). Refer to the instructions that accompanied the HHSC for setup information.
The Healthy Home System™ Control (HHSC)
All manuals and user guides at all-guides.com
24
Installation of the HHSC with the DH1 and 20/40/60 Minute Timers (test a)
1
2
3
4
5
6
7
8
9
10
L
O
ON
R
Y
G
HI
C
NO
NC
BK
FACTORY-INSTALLED JUMPER DO NOT REMOVE
LO
HI
24C
*
R
C
Wt
Gt
Gf
V
HHSC CONTROL
RCWYGRYWG
THERMOSTAT
FURNACE OR HEAT PUMP
HRV/ERV WIRING TERMINALS
12V/24 VAC Field wiring, 20 AWG min. required
* Connect V Terminal on the HHSC Control to the Hi Ter minal (instead of Lo) for a shorter ventilation period. ** One DH-1 Dehumidistat and/or one or more VTC timer controls may be connected as shown. Connect all
R
ed, Yellow, and Green control terminals to the corresponding HRV/ERV terminals.
%
8
0
2
0
R
YG
Y
R
G
Y
R
G
VTC VENTTIMER CONTROL (OPTIONAL)**
VTC VENTTIMER CONTROL (OPTIONAL)**
DH1 DEHUMIDISTAT (OPTIONAL)**
Setting up the HHSC Control
The duration of the ventilation rate is adjustable on the Healthy Home System Control™ (HHSC). Refer to the instructions that accompanied the HHSC for setup information.
The Healthy Home System™ Control (HHSC)
All manuals and user guides at all-guides.com
25
Installation of the DHVC Ventilation Control with 20/40/60 Minute Timers (test c)
1
2
3
4
5
6
7
8
9
10
L
O
ON
R
Y
G
HI
C
NO
NC
BK
FACTORY-INSTALLED JUMPER FOR STANDBY-OFF OPERATION. SEE “SETTING STANDBY” SECTION OF INSTALLATION INSTRUCTIONS
LO
HI
24C
RCW
Y
GRYWG
T
HERMOSTAT
FURNACE OR HEAT PUMP
HRV/ERV WIRING TERMINALS
12V/24 VAC Field wiring, 20 AWG min. required
* Connect V Terminal on the HHSC Control to the Hi Ter minal (instead of Lo) for a shorter ventilation period. ** One DH-1 Dehumidistat and/or one or more VTC timer controls may be connected as shown. Connect all
Red, Yellow, and Green control terminals to the corresponding HRV/ERV terminals.
R
Y
G
Y
R
G
Y
R
G
V
TC VENTTIMER CONTROL
(OPTIONAL)**
V
TC VENTTIMER CONTROL
(OPTIONAL)**
DHVC VENTILATION C
ONTROL
N
OTE:These connections are not necessary
if the system is configured as fully dedicated (no central HVAC connections).
%
80
2
0
H
IG
H
All manuals and user guides at all-guides.com
26
Interlocking the HRV/ERV to an Air Handler/Furnace Blower
Connecting the HRV/ERV as illustrated will ensure the Air Handler/Furnace Blower Motor is operating whenever the HRV/ERV is ventilating.
The HRV/ERV must be interlocked to the Furnace/Air Handler with a Simplified Installation (Return/Return Installation) and should be interlocked with a Partially Dedicated Installation.
Wire Connector
Furnace Terminal Strip
Furnace Thermostat
H
RVTerminal Block
Operating the HRV/ERV without a Main Control and Adding Dry Contact Controls
CAUTION
Consideration should be given to competing air flows whe n con nec tin g the H RV/ ERV i n conjunction with an Air Handler/Furnace Blower system.
Setting “Standby” when using a Main Control
CAUTION
Building codes in some areas require “fully-
off functionality. Check with your local
building authority before modifying the unit
to “standby -off”.
Unintentional operation of the HRV by the
end user may occur if the unit is modified
from “fully-off” to “standby-off”.
The HRV/ERV will be fully-off when the OFF position is selected on the Main Control. Timers and /or other controls will not function when the HRV/ERV is in the OFF position. The fully-off feature can be modified to s ta ndby-off by adding a j um pe r on the Terminal Block between 2 (ON) and 3 (RED). “Standby” can also be achieved by setting the main control to the ON position and selecting speed 0*. Timers and /or additional controls will initiate high speed venti la tion when activated
.
* Speed 0 is not available on all controls
The Terminal Block
(located on the HRV/ERV)
A jumper must be in place between 2 (ON) and 3 (RED) on the Terminal Block to activate the HRV/E RV for tim ers and /or dry contac t controls.
Adding Dry Contact Controls
Low Speed - A jumper between 2 (ON) and
1 (LOW) initiates low speed ventilation. High Speed - A jumper between 2 (ON) and
6 (HI) initiates high speed ventilation. Dehumidistat - A dry contact for a dehumidistat
is connected between 2 (ON) and 10 (BLK).
The Terminal Block
(located on the HRV/ERV)
The HRV/ERV must have a Jumper in place between 2 (ON) and 3 (RED) on the Terminal Block when installing the unit without a Main Control.
All manuals and user guides at all-guides.com
all-guides.com
27
A positive or negative pressure may occur in the house
HRV/ERV may not operate at its maximum efficiency
The unit may not defrost properly
Air Flow Measuring Gauges
The magnehelic gauge and the digital manometer are suitable instruments for the balancing of air flows.
A magnehelic gauge with a scale of 0 to .25" w.c. is suitable for accurately measuring air duct velocity. The value on the gauge will be velocity pressure. A digital manometer requires the ability to display differential pressures at 3 digits of resolution.
Gauge Attachments
When sampling an air flow, various attachments are available for use on a magnehelic gauge or digital manometer.
The following illustration shows a magnehelic gauge with a scale of 0 to .25" w.c. with a pitot tube attachment. This combination will measure the system air velocity pressure accurately, regardless of the duct size or shape (either round or rectangular).
Balancing Preparation
Prior to performing the air balancing procedure, perform the following steps:
Seal the ductwork system
Confirm the installation and proper operation of all the components of the HRV/ERV
Fully open the balancing dampers
Turn off all household exhaust devices (range hood, clothes dryer, bathroom fans)
Set the HRV/ERV at high speed
Prior to balancing the unit, first adjust air flows in branch lines to specific areas of the house
If the outdoor temperature is below 0˚C (32˚F), ensure the unit is not running in defrost
Place the magnehelic gauge on a level surface and adjust it
to zero
If the s ystem is a S impli fied o r Parti ally D edicate d installation, operate the furnace/Air Handler at high speed
M
A
G
N
E
H
E
LI
C
DUCT
AIR
FLOW
Pitot tube
High Pressure Side
Low Pressure Side
Magnehelic gauge
Pitot tube and gauge
Balancing the Air Flows
Continuous, excessive, positive pressure may drive moist indoor air into the external walls of the building. Once inside the external walls, moist air may condense (in cold weather) and degrade structural components or cause locks to freeze. Continuous, excessive, negative pressure may have several undesirable effects. In some geographic locations, soil gases such as methane and radon gas may be drawn into the home through basement or ground contact areas, and may also cause the backdrafting of vented combustion equipment.
ATTENTION
Magnehelic Gauge with a scale of 0 to .25” w.c.
Magnehelic Gauge (scale of 0 to .25” w.c.) with a Pitot Tube Attachment
Balancing the air flows is critical to ensuring that the amount of air introduced from the outside of the building equals the amount of air exhausted to the outside of the building. If these two air flows are not properly balanced, the following issues may occur:
All manuals and user guides at all-guides.com
28
Balancing the Air Flows with a Pitot Tube
STEP 1. D
rill a 3/16” hole in the duct (ideally 3 feet downstream of
a
ny elbows or bends and 1 foot upstream of any elbows
or bends) in the Fresh Air and Stale air streams.
Stale Air From Building
Balancing Damper
Balancing Damper
Fresh Air to Building
Drill 3/16” holes in Stale & Fresh Air ducts.
STEP 2. Insert the Pitot tube with the tip facing towards the air
stream in the Stale Air From Building air stream. Move the Pitot tube around in the duct (facing towards the airflow) and take an average reading. Record the reading.
Magnehelic Gauge must be level.
Pitot tube tip facing t
owards the air stream.
STEP 3. Repeat Step 2 to measure the Fresh Air to Building duct.
Magnehelic Gauge must be level.
Pitot tube tip facing towards the air stream.
STEP 4.
A) Review the readings and damper down the duct with the highest duct velocity pressure. Repeat Step 2 and Step 3 until both ducts show indentical readings. For this example, the Fresh Air to Building air stream has the highest duct velocity pressure.
B) Upon completion of balancing, seal the holes (foil tape recommended).
Determining the cfm
After balancing the air flows, calculate the cfm flow rate.
Example
This example shows how to determine the air flow for a 6” diameter duct. As shown in the illustration, the duct velocity pressure reads 0.025” w.c. on the magnehelic gauge. Use the chart that came with the magnehelic gauge to determine a duct velocity of 640 feet per minute for a duct
velocity pressure of 0.025” w.c.
Cfm Calculation
cfm = feet per minute x cross section area of duct
= 640 x 0.196 = 125
Cross Section Area of some common round duct sizes:
0.087 for 4” diameter duct
0.136 for 5” diameter duct
0.196 for 6” diameter duct
0.267 for 7” diameter duct
Magnehelic Gauge reading .025” w.c.
All manuals and user guides at all-guides.com
29
Air Flow Balancing using the Door Ports FC155HRV & FC200HRV only
Door balancing ports (not on all models) are designed to be used in conjunction with a Magnehelic Gauge or Digital Manometer to
measure the Stale and Fresh airflows for balancing.
Step 1
Prepare the air flow measuring device (i.e. Magnehelic Gauge or Digital Manometer) by connecting the hoses to the low and high pressure side of the gauge.
Step 2
Insert the hoses into the rubber fittings from the optional Door Port Adapter Kit (part # 99-182). Use light pressure and rotate until fitting is snug. Do not extend the hose past the rubber fitting.
Step 3
Open the HRV Door. Remove the 4 Door Port Covers by carefully pushing them out from the back side of the door (use the blunt end of a large drill bit etc.).
Step 4
Close the HRV Door. Initiate power and operate the HRV on high speed. Operate the forced air system on high speed (if the HRV is connected to the forced air system) .
Step 5
Insert the 2 rubber fittings from the gauge to the STALE AIR Balancing Ports (upper right and lower left). Seal the FRESH AIR Balancing Ports (upper left and lower right) with tape. Record your reading.
Step 6
Insert the 2 rubber fittings from the gauge to the FRESH AIR Balancing Ports (upper left and lower right). Seal the STALE AIR Balancing Ports (upper right and lower left) with tape. Record your reading.
Step 7
Refer to the "Airflow Reference Chart" for your model and determine the FRESH AIR and STALE AIR flow rates (the chart is located on the lower portion of this page).
Step 8
Damper down the higher airflow and repeat Steps 5 to 7 as required until both airflows are identical (balanced).
Step 9
Remove the tape and rubber fittings and reinstall the 4 Door Port Covers.
MODEL 200
0 230
153
156
Manometer Reading
Airflow Numbers
(CFM)
(in. w.g.)
0.100 98 91
0.110 102 96
0.120 107 101
0.130 111 107
0.140 115 112
0.150 120 117
0.160 124 122
0.170
128 127
0.180 133 132
0.190 137 137
0.200 141 142
0.210 145 147
0.220 149 152 .
0.240 157 161
0.250 161 166
0.260
165 171
0.270 169 175
0.280
173 180
0.290 177 184
0.300 181 189
0.310
185 193
0.320 189 198
0.330 192 202
0.340
196 207
0.350 200 211
0.360
203 215
MODEL 155
0 180
142
129
Airflow Numbers
(CFM)
Pressure
(in. w.g.)
Fresh Air Stale Air
0.100 93 80
0.105 96 83
0.110 99 86
0.115 102 89
0.120 105 92
0.125 108 96
0.130 111 99
0.135 114 102
0.140 117 105
0.145 120 108
0.150 123 111
0.160 130 117
0.170 136 123 .
0.190 148 135
0.200 154 141
0.210 160 147
0.220 166 154
0.230 172 160
0.240 178 166
0.250 184 172
0.260 191 178
0.270 197 184
0.280 203 190
0.290 209 196
0.300 215 202
0.310 221 209
Pressure
Manometer Reading
Fresh Air Stale Air
Magnehelic Gauge hoses connected to STALE AIR balancing ports
Illustration of measuring STALE airflow using a Magnehelic Gauge.
Magnehelic Gauge hoses connected to FRESH AIR balancing ports
Illustration of measuring FRESH airflow using a Magnehelic Gauge.
Fresh Air B
alancing Ports (top-left, b
ottom-right)
S
tale Air Balancing Ports (top-right, b
ottom-left)
Illustration of a door with door ports
Airflow Reference Charts
FC200HRV
FC155HRV
All manuals and user guides at all-guides.com
30
Push and turn with slotted screwdriver. Damper automatically locks when pressure is released.
Observe the location of the screws when connecting ductwork to the collar. Screws should be located no further than 1/2” from the outside edge of the collar and they should be no longer than 3/4”.
1/2”
Balancing Dampers
Installations where the HRV is ducted directly to the r etu rn of the furnace/ Air Handler may require additional dampening on the fresh air to building duct. This is due to the high return static pressures found in some furnace installations.
The FC155HRV and FC200HRV models have factory installed Balancing Dampers located in the “Fresh Air to Building” and “Stale Air from Building” collars.
All other units require the installation of balancing dampers (not included) in the “Fresh Air to Building” and “Stale Air from Building” ductwork. Refer to the installation diagrams in this manual for the Simplified, Partially Dedicated, and Fully Dedicated systems.
NOTE
Illustration of Adjusting the Factory Installed Balancing Damper
Illustration of Connecting ductwork to the Balancing Damper Collars
All manuals and user guides at all-guides.com
31
SYMPTOM CAUSE SOLUTION
Poor Air Flows
Supply air feels cold
Dehumidistat is not Operating
Humidity Levels are too High Condensation is appearing on the windows
Humidity Levels are too Low
HRV and/or Ducts Frosting up
Condensation or Ice Build Up in Insulated Duct to the Outside
Water in the bottom of the HRV
1/4” (6 mm) mesh on the outside hoods is plugged
filters plugged
core obstructed
house grilles closed or blocked
dampers are closed if installed
poor power supply at site
ductwork is restricting HRV
improper speed control setting
HRV airflow improperly balanced
poor location of supply grilles, the airflow may irritate the occupant
outdoor temperature extremely cold
outdoor temperature is above 15°C (59°F)
improper low voltage connection
external low voltage is shortened out by a staple or nail
check dehumidistat setting it may be on OFF
dehumidistat is set too high
HRV is undersized to handle a hot tub, indoor pool, etc.
lifestyle of the occupants
moisture coming into the home from an unvented or unheated crawl space
moisture is remaining in the washroom and kitchen areas
condensation seems to form in the spring and fall
HRV is set at too low a speed
dehumidistat control set too low
blower speed of HRV is too high
lifestyle of occupants
HRV air flows may be improperly balanced
HRV air flows are improperly balanced
malfunction of the HRV defrost system
incomplete vapour barrier around insulated duct
a hole or tear in outer duct covering
drain pans plugged
improper connection of HRV’s drain lines
HRV is not level
drain lines are obstructed
HRV heat exchange core is not properly installed
clean exterior hoods or vents
remove and clean filter
remove and clean core
check and open grilles
open and adjust dampers
have electrician check supply voltage at house
check duct installation
increase the speed of the HRV
have contractor balance HRV
locate the grilles high on the walls or under the baseboards, install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant (eg. over a sofa)
turn down the HRV supply speed. A small duct heater (1kw) could be used to temper the supply air
placement of furniture or closed doors is restricting the
movement of air in the home
if supply air is ducted into furnace return, the furnace fan may need to run continuously to distribute ventilation air comfortably
d ehu midis tat is f uncti oni ng nor mally ( see Ho w t he
Dehumidistat Works” in this manual)
check that the correct terminals have been used
check external wiring for a short
set the dehumidistat at the desired setting
set dehumidistat lower
cover pools, hot tubs when they are not in use
avoid hanging clothes to dry, storing wood and venting clothes dryer inside. Heating wood may have to be moved outside
vent crawl space and place a vapour barrier on the floor of the crawl space
ducts from the washroom should be sized to remove moist air as effectively as possible, use of a bathroom fan for short periods will remove additional moisture
on humid days, as the seasons change, some condensation may appear but the homes air quality will remain high with some HRV use
increase speed of the HRV
set dehumidistat higher
decrease HRV blower speed
humidity may have to be added through the use of humidifiers
have a contractor balance HRV airflows
Note: minimal frost build-up is expected on cores before unit initiates defrost cycle functions
have HVAC contractor balance the HRV
ensure damper defrost is operating during self-test
tape and seal all joints
tape any holes or tears made in the outer duct covering
ensure that the vapour barrier is completely sealed
ensure O-Ring on drain nozzle sits properly
look for kinks in line
check water drain connections
make sure water drains properly from pan
Troubleshooting your HRV/ERV System
All manuals and user guides at all-guides.com
all-guides.com
32
LEAVE FOR HOMEOWNER
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION
Installing Contractor _________________________________________Telephone / Contact _____________________
Serial Number______________________________________________Installation Date ________________________
Model _________________________________________________________________________________________
Residential Wiring Diagram Models FC95HRv, FC155HRV, FC200HRV, and FC150ERV
K6 K5
K7 K3 K4
P4 BLUE
K2
AUTO- TRANSFORMER
H
IGH VOLTAGE
12/24V LOW VOLTAGE
LEGEND
CAPACITOR
B
R
O
WN
BLACK
GREEN
DIRECT MOUNTED CAPACITOR
B
R
O
W
N
WHITE
SEE DEFROST DETAIL
P1
P3
Note: If any of the original wire supplied with the unit must be replaced, use only TEW certified wire.
IMPORTANT: Control low voltage is 12/24VAC. DO NOT CONNECT EXTERNAL POWER SOURCES TO THE UNIT.
DEFROST DETAILS (Not Applicable to FC150ERV)
P1
12
3
4
PIN 1 - BLACK PIN 2 - ORANGE PIN 3 - RED PIN 4 - SPARE
PCB PLUG - IN
RED
BLACK
PLUG IN
BI-DIRECTIONAL
ORANGE
RED
BLACK
ORANGE
CONNECTOR
DAMPER MOTOR
AUTO-TRANSFORMER DETAIL
PINS 1, 2, AND 3 ARE OPTIONAL
3
2
2
1
1
5
6
4
P3
P6
P3
PIN 1 - BLUE PIN 4 - RED PIN 2 - YELLOW PIN 5 -WHITE PIN 3 - BROWN PIN 6 - BLACK
P6
PIN 1 - GREEN PIN 2 - GREEN
PLUG IN CONNECTOR
AUTO
TRANSFORMER
FAN
MOTOR
P1
12
3
4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SPARE
PCB PLUG - IN
GREEN
WHITE
BLACK
ON
LOW
RED
YEL
GRN
H
I
C
OM
NO
NC
BLK
FC95HRV
P7 C
OMMS
P9
T4
P5
Field Controls FC95HRV, FC155HRV, FC200HRV, FC150ERV
Thermistor (
Not on all units)
NOTE: Jumper between
2 ON and 3 RED
LO VENT
HI VENT
24COM
ABNC
NO
COM
24VAC
COIL
24VAC
COIL
NC
NO
COM
BROWN
BLUE
RED
59-FCWIRING REV. A
All manuals and user guides at all-guides.com
Loading...