Field Controls EvenAir T21WF, EvenAir T21 Installation And User Manual

INSTALLATION AND USER MANUAL
R
T21WF
THERMOSTAT WITH AIRFLOW CONTROL
R
E
L
D
C
O
N
T
R
O
L
S
Wi
Fi
WiFi
Sleeping
Airflow %
Day
Tu
Living
AM
Schedule
R
Cool
Set To
COOL
Living
SYSTEM
AUTO
FANMENU MODE
F
I
The EvenAir thermostat monitors the temperature at the sensor and the temperature at the thermostat every 2 minutes during heating and cooling calls. If the temperatures are different, the EvenAir thermostat automatically adjusts the modulating dampers 2% so that more airflow is directed to the space that needs it for a uniformly comfortable home.
COMPONENTS:
EvenAir T21WF Thermostat EvenAir TS51 or TS52 Wired Temperature Sensor(s) (sold separately) EvenAir AMT Type Motorized Damper, With Terminals (sold separately)
READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.
This device MUST be installed by a qualified agency in accordance with the manufacturer’s installation instructions.The definition of a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in, and is responsible for, the installation and operation of HVAC applicances, who is experienced in such work, familiar with all the precautions required, and has complied with all the requirements of the authority having jurisdiction.
Please retain these instructions after installation.
Installed By:_______________________________________ Phone: _____________________ Installation Date: _____________
P/N 780101703 3/18 Rev Awww.fieldcontrols.com
Thank you for purchasing the EvenAir System from Field Controls. The EvenAir products are compatible with any HVAC system having accessible 24VAC terminals.
FEATURES
SYSTEM MODES
Off, Heat, Cool, Auto
FAN MODES
Auto or Continuous
THERMOSTAT MODES
Hold, Schedule or Vacant
PROGRAMS PER DAY
Morning, Daytime, Evening and Night
PROGRAM FORMAT
Weekdays and weekend – 5/2
TEMPERATURE OVERRIDE
Temperature is held for 3 hours when adjusted in Schedule mode.
AIRFLOW OVERRIDE
The airflow to the living area or sleeping area can be adjusted. After 3 hours, the thermostat returns to automatic airflow control.
AIRFLOW CONTROL
Airflow control can be turned off and the thermostat will operate as a typical thermostat.
AIRFLOW LIMITS
Maximum airflow limits can be set for heating and cooling modes during installation.
NIGHTTIME OPERATION
At night, the EvenAir thermostat uses the temperature sensor in the sleeping area to control heating and cooling calls and directs more airflow to the sleeping area.
COMPATIBLE EQUIPMENT
Gas/electric equipment with 2-stage heating and 1-stage cooling or 1-stage heating and 2-stage cooling and heat pumps with 2-stage heating and 2-stage cooling.
TEMPERATURE SENSOR
One TS51 sensor or two TS52 temperature sensors can be used in the sleeping area.
MODULATING DAMPERS
Round or rectangular dampers using the AMT actuator and up to 1 inch static pressure.
WiFI
Connects to the home WiFi network to provide remote access via the internet using smart phone, tablet or PC.
POWER
Operates on 24VAC from the HVAC equipment using the R and C wires.
THERMOSTAT OVERVIEW
Press the touchscreen with your fingertip only, using a firm touch. Do not use a sharp object such as a pen or pencil.
!
The touchscreen is a resistive touch and responds differently than touchscreens found in smart phones/devices.
R
Displays the Thermostat Mode HOLD, SCHEDULE or VACANT
Displays the sleeping area airflow Displays WiFi status
Displays the living area airflow
Displays the time, day and schedule. MORNING, DAYTIME, EVENING or NIGHT
MENU Key
Displays User options.
MODE Key
Selects Thermostat Mode HOLD, SCHEDULE or VACANT
WiFi
Sleeping
Airflow %
Living
Day
Tu
AM
Schedule
Cool
Set To
Living
COOL
SYSTEM
AUTO
FANMENU MODE
Displays the heating or cooling temperature
UP/DOWN Keys
Displays the living area or sleeping area temperature.
SYSTEM MODE Key
OFF, HEAT, COOL or AUTO
FAN MODE Key
AUTO or ON
ENTER Key
Used to save options and return to thermostat operation
NEXT Key
Used to advance through options
page 2 of 16 P/N 780101703 3/18 Rev A
HOMEOWNER SECTION
HOMEOWNER
This manual is separated into two different sections: one for the Homeowner and one for the System Installer.
The Homeowner section contains information on features and operation of the thermostat along with optional user settings available to the homeowner.
THERMOSTAT OPERATION AND USER SETTINGS
Features EvenAir Thermostat Operation
1
Set Time and Day
2
Set System Mode
3
Set Fan Mode
4
Set Thermostat Mode
5
Changing Setpoint Temperature
Temperature Override
6
Displaying Upstairs Temperature
7
Overriding Automatic Airflow
8
9
Terminating Automatic Airflow
FEATURES
User Options
1
Set Schedule
2
Turn Automatic Airflow Control On/Off
3
Turn Nighttime Airflow Control On/Off
4
Set Nighttime Airflow in Heating
5
Set Nighttime Airflow in Cooling
Clean the Touchscreen
6
Turn Thermostat WiFi On
7
Start Linking WiFi Thermostat
8
Install Batteries
DISPLAYING THE LIVING AND BEDROOM AREA TEMPERATURE
The living area temperature is normally displayed. The bedroom area temperature can be displayed by touching Living on the touchscreen. The temperature will change to the bedroom space temperature, indicated by Sleeping. Touch Sleeping to return to displaying the Living area temperature.
NIGHTTIME AIRFLOW CONTROL
The Nighttime Airflow Control option is an energy saving feature where the thermostat uses the temperature sensor in the bedroom area to control heating and cooling calls and directs more airflow to the bedroom at night and less airflow to the unoccupied living . Nighttime Airflow Control begins at 10:00pm but can be changed by accessing the schedule in the User Options. The airflow to the bedroom space defaults to 130% but can be adjusted for both heating and cooling in the User Options. Nighttime Airflow Control is defaulted to On but can be turned Off in the User Options. The homeowner should consider turning this option off if bedrooms are located on the same floor as the living area and using the same airflow trunk as the living area.
AUTOMATIC OR MANUAL AIRFLOW CONTROL
Automatic Airflow Control is the thermostat default and is typically used by homeowners to maintain uniform comfort throughout the home. However, homeowners with unusual work schedules, home offices, etc. may want to use the manual airflow control feature. This features allows the homeowner to change the airflow level as desired and hold that level indefinitely. This feature needs to be enabled using Installer Option 18. The homeowner then needs to turn automatic airflow control off using the User Options. The Nighttime Airflow Control option is still enabled but can be turned off, if desired, using the User Options.
AIRFLOW OVERRIDE
On occasion, homeowners may want to direct more airflow to an area. For example, during a party, more airflow may be desired in the living area. The homeowner sets the airflow level to the area and the thermostat will hold the airflow for 3 hours. After 3 hours, the thermostat returns to automatic airflow control.
area
area
AIRFLOW CONTROL TURNED OFF
In some installations, the EvenAir thermostat has been installed to control the system only. The thermostat operates just like any other thermostat. The airflow control options are disabled and airflow is no longer displayed on the thermostat.
WiFi REMOTE ACCESS
The EvenAir WiFi thermostat connects to the home’s WiFi network and provides remote access, via the internet, to your home’s heating and cooling system from anywhere using a smart phone, tablet or PC.
page 3 of 16 P/N 780101703 3/18 Rev A
HOMEOWNER SECTION
THERMOSTAT OPERATION
1
Set Time and Day
Touch here to change the time and day of the week.
CHANGE THE HOUR
AM
NEXT
CHANGE THE MINUTE
AM
NEXT
CHANGE THE DAY OF THE WEEK
We
AM
i
Depending on the mode, setting the time may reset the setpoint temperature to the factory default heating or cooling setpoint.
Set System Mode
2
Touch the SYSTEM key to display the SYSTEM MODES: OFF, HEAT, COOL or AUTO. In AUTO or OFF, the setpoint for the last system call is displayed.
Sleeping
Airflow %
Living
Day
Tu
MENU MODE
Sleeping
Airflow %
Living
Day
Tu
MENU MODE
Sleeping
Airflow %
Living
Day
Tu
MENU MODE
Sleeping
Airflow %
Living
Day
Tu
MENU MODE FAN
Schedule
AM
Schedule
AM
Schedule
AM
Schedule
AM
ENTER
ENTER
ENTER
Heat
Set To
Heat
Set To
Cool Set To
Heat
Set To
Sleeping
Airflow %
Living
Day
Tu
AM
Touch the UP/DOWN keys to change the HOUR.
Touch NEXT.
Touch the UP/DOWN keys to change the MINUTE.
Touch NEXT.
Touch the UP/DOWN keys to change the DAY OF THE WEEK.
Touch ENTER.
OFF
Heating and cooling systems are off.
OFF
Living
SYSTEM
AUTO
FAN
HEAT
Only heating calls are
Living
setpoint is displayed.
SYSTEM
“HEAT” will blink in
AUTO
an active heating call.
FAN
enabled and heating
HEAT
COOL
Only cooling calls are
Living
enabled and cooling
COOL
setpoint is displayed.
SYSTEM
“COOL” will blink in
AUTO
an active cooling call.
FAN
AUTO
Heating or Cooling
Living
calls are enabled. “HEAT” will blink in
AUTO
SYSTEM
an active heating call
AUTO
or “COOL” will blink in an active cooling call.
Schedule
Cool Set To
Living
COOL
SYSTEM
AUTO
FANMENU MODE
3
Set Fan Mode
Touch the key to change the FAN MODES -
FAN
AUTO or ON.
Sleeping
Airflow %
Living
Day
Tu
AM
MENU MODE
Sleeping
Airflow %
Living
Day
Tu
AM
MENU MODE
4
Set Thermostat Mode
Touch the key to display the THERMOSTAT
MODE
Schedule
Schedule
Cool Set To
Living
Cool Set To
Living
AUTO
Fan is activated only during heating or
COOL
cooling calls. This is
SYSTEM
the most commonly
AUTO
used setting.
FAN
ON
Fan is continuously on.
COOL
SYSTEM
ON
FAN
MODES: HOLD, VACANT and SCHEDULE.
Sleeping
Airflow %
Living
Day
Tu
AM
MODE
Sleeping
Airflow %
Living
Day
Tu
AM
MODE
Sleeping
Airflow %
Living
Day
Tu
AM
MODE
Changing the Setpoint Temperature
5
Cool Set To
Hold
Cool Set To
Vacant
Cool Set To
Schedule
HOLD MODE
Setpoint temperatures are set by the user.
Living
COOL
No schedule is used.
SYSTEM
AUTO
FANMENU
VACANT MODE
Setpoint temperatures are kept at the vacant
Living
COOL
temperatures set by
SYSTEM
the installer.
AUTO
FANMENU
SCHEDULE MODE
Setpoint temperatures are changed at
Living
COOL
scheduled times
SYSTEM
defined by the user.
AUTO
FANMENU
The UP/DOWN keys are used to change the setpoint temperature.
Sleeping
Airflow %
Living
Day
Tu
AM
MENU MODE
Schedule
Cool Set To
Living
Touch the UP key to raise setpoint temperature.
COOL
SYSTEM
Touch the DOWN
AUTO
key to lower setpoint
FAN
temperature.
An active heating call is indicated by HEAT blinking. An active cooling call is indicated by COOL blinking.
Sleeping
Airflow %
Living
Day
Tu
AM
MENU MODE
Schedule
Heat
Set To
Living
Touch here to display and change the opposing setpoint
COOL
temperature.
SYSTEM
AUTO
FAN
Touch the UP/DOWN keys to change the setpoint temperature for the opposing system. The thermostat will return to displaying the active setpoint after about 30 seconds.
page 4 of 16 P/N 780101703 3/18 Rev A
6
Temperature Override
To override the setpoint temperature:
Tu
Sleeping
Airflow %
Living
Day
Cool Set To
Schedule
Living
AM
Touch the UP/DOWN keys to adjust the setpoint temperature.
COOL
After 3 hours, the
SYSTEM
AUTO
thermostat returns to
FANMENU MODE
normal thermostat operation.
7
Displaying the Upstairs Temperature
The thermostat displays the temperature in the downstairs living area and is indicated by Living. The temperature in the upstairs sleeping area is indicated by Sleeping. When the thermostat enters Night Mode, the upstairs sleeping area temperature will be displayed, indicated by Sleeping.
MENU
MENU
Sleeping
Airflow %
Living
Day
We
Sleeping
Airflow %
Living
Day
We
Cool
Set To
Schedule
AM
Cool Set To
Schedule
Sleeping
AM
Press Living to display the upstairs Sleeping area temperature.
COOL
Living
SYSTEM
AUTO
FANMODE
The upstairs Sleeping area temperature is now displayed.
COOL
SYSTEM
Press Sleeping to
AUTO
FANMODE
display the Living area temperature.
8
Overriding Automatic Airflow
Sleeping
Airflow %
Living
We
Sleeping
Airflow %
We
Cool Set To
Hold
Eve
PM
MODE
Living
Eve
PM
Living
Hold
Touch the Airflow % area to override AUTOMATIC AIRFLOW
COOL
to the living area or
SYSTEM
the upstairs sleeping
AUTO
FANMENU
area.
Touch the UP key to increase the airflow to
Living
the sleeping area or
COOL
touch the DOWN key
SYSTEM
to increase airflow to
AUTO
FANMENU MODE
the living area.
Airflow % will blink to indicate airflow override. After 3 hours, the thermostat returns to automatic operation. The override range is defined by the installer during set up.
9
Terminating Airflow Override
Sleeping
Airflow %
Living
We
Sleeping
Airflow %
Living
We
Cool Set To
Hold
Eve
PM
MODE
Eve
PM
MODE
Living
Hold
Living
To terminate Airflow Override, touch the AIRFLOW% area.
COOL
SYSTEM
AUTO
FANMENU
Then touch the MODE key.
COOL
SYSTEM
AUTO
FANMENU
The thermostat returns to automatic airflow control. The AIRFLOW % returns to the airflow prior to the override.
HOMEOWNER SECTION
USER OPTIONS
Factory Set Schedule
The thermostat comes pre-set with the following energy-saving schedule for weekdays (Mon-Fri) and weekends (Sat-Sun). Using these settings can reduce your heating /cooling expenses.
Monday - Friday
Morn Day Even Nite
Saturday & Sunday
Morn Day Even Nite
1
Change Factory Set Schedule
Sleeping
MENU
Tu
Airflow %
Living
Day
Schedule
AM
SELECTING THE WEEKDAY OR WEEKEND SCHEDULE
WeTuMo ThFr
MENU NEXT ENTER
Schedule
SETTING THE MORNING SCHEDULE START TIME.
Morn
WeTuMo
ThFr
MENU NEXT ENTER
Schedule
AM
SETTING THE MORNING HEATING TEMPERATURE.
Morn
WeTuMo
ThFr
MENU NEXT ENTER
Schedule
AM
SETTING THE MORNING COOLING TEMPERATURE.
Morn
WeTuMo
ThFr
MENU
Schedule
AM
NEXT ENTER
Continue setting the start times, heating setpoints, cooling setpoints for the Day, Evening and Night schedules.
Touch ENTER to save the schedule.
Time Heat Cool
6:00 AM 8:00 AM 6:00 PM
10:00 PM
Time Heat Cool
6:00 AM 8:00 AM
6:00 PM
10:00 PM
Touch the
Cool
Set To
Living
key to display SCHEDULE. If no
COOL
key is touched, the
SYSTEM
thermostat returns to
AUTO
normal operation
FANMODE
after about 30 seconds.
Touch the UP key to select the weekday schedule (MoTuWeThFr) or touch the DOWN key to select the weekend schedule (SaSu). Touch NEXT.
Touch the UP/DOWN keys to change the Morning Start Time. Touch NEXT.
Heat
Set To
Touch the UP/DOWN keys to change the Morning Heating Setpoint. Touch NEXT.
Touch the
Cool
Set To
UP/DOWN keys to change Morning Cooling Setpoint. Touch NEXT.
70 62 70 62
70 62 70 62
MENU
75 83 75 78
75 83 75 78
2
Automatic Airflow Control On or Off
i
This option is only displayed if User Airflow Control has been turned On by the installer in the Installer Options.
i
Homeowners with an unusual schedule, home office, etc. may want to use this option.
i
With Automatic Airflow Control Off, the Nighttime Airflow option is still enabled. If desired, the homeowner can turn the Nighttime Airflow option off using User Options.
Touch the MENU key until the following thermostat screen is displayed.
Thermostat defaults
Airflow %
to Automatic Airflow Control On and automatically directs more airflow to where
MENU
NEXT
ENTER
it’s needed.
To turn Automatic
Airflow %
Airflow Control OFF, touch the DOWN key. The user must set the airflow when
NEXTMENU ENTER
Touch the key to save and go to next
MENU
airflow control is off.
option or touch the ENTER key to save the options and return to normal thermostat operation.
3
Nighttime Airflow Control On or Off
i
This option is not displayed if Nighttime Airflow Control has been turned off by the installer using the Installer Options.
i
If bedrooms are located downstairs, consider turning the Nighttime Airflow Control OFF.
NIGHTTIME AIRFLOW CONTROL defaults to On and is used to save energy. The thermostat uses the temperature sensor in the sleeping area for controlling heating and cooling calls. The airflow is increased to 130% to the sleeping area and the airflow is reduced to 70% to the unused living area. The thermostat displays the sleeping area temperature.
Upstairs
Airflow %
Night
Touch the MENU key to display NIGHTTIME AIRFLOW indicated by nAF On or Off.
MENU NEXT ENTER
Upstairs
Airflow %
Night
Touch the UP key to turn the option ON. Touch the DOWN key to turn the option OFF.
MENU NEXT ENTER
Touch the MENU key to save and go to next option or touch the ENTER key to save the options.
page 5 of 16 P/N 780101703 3/18 Rev A
3
Nighttime Airflow Control (cont.)
i
Default start time for Nighttime Airflow is 10:00pm but can be changed using User Option 1 to change the Night Schedule Start Time.
i
Default airflow level upstairs is 130%. If a different airflow level is desired, use User Option 4 to change the airflow level in heating and User Option 5 to change the airflow level in cooling.
4
Set the Nighttime Airflow in Heating
i
This option is not be displayed if Airflow Control has been turned off.
This option is used to change the default nighttime airflow in heating of 130% to a user desired airflow level, not to exceed installer limits.
Sleeping
Airflow %
Night
MENU ENTER
Touch the key to display NIGHTTIME,
MENU
Heat
NEXT
UPSTAIRS AIRFLOW IN HEATING indicated by nAF Heat.
Use the UP/DOWN keys to adjust the airflow.
Touch the MENU key to save and go to next option or touch the ENTER key to save the option.
Set the Nighttime Airflow in Cooling
5
i
This option is not displayed if Airflow Control has been turned off.
This option is used to change the default nighttime airflow in cooling of 130% to a user desired airflow level, not to exceed installer limits.
Sleeping
Airflow %
Night
MENU ENTER
Cool
NEXT
Touch the MENU key to display NIGHTTIME, UPSTAIRS AIRFLOW IN COOLING indicated by nAF Cool.
Use the UP/DOWN keys to adjust the airflow.
Touch the MENU key to save and go to next option or touch the ENTER key to save the options.
HOMEOWNER SECTION
USER OPTIONS (continued)
6
Clean the Touch Screen
This option disables the touch screen for 30 seconds to enable the user to clean the touch screen by wiping down with a soft, damp cloth.
Touch the MENU key to display CLEAN DISPLAY option indicated by CL. To
NEXT ENTERMENU
7
Turn Thermostat WiFi On
This option turns WiFi access On or Off.
exit the option, touch NEXT.
Touch ENTER to start the 30 second count
OFF
down. The touch screen is disabled during this time.
Touch the MENU key to display WiFi On or Off option indicated by NEt.
8
Start Linking WiFi Thermostat
This option starts the linking of the EvenAir thermostat to the home’s WiFi network.
Touch the MENU key to display WiFi linking option On or Off indicated by Lnc.
ENTER
Touch the UP key to select ON. Touch the ENTER key to start the linking sequence.
ENTER
During the linking sequence “WiFi” will blink indicating the thermostat is trying to link to the home network. Once the
Sleeping
Airflow %
WiFi
Living
Day
Tu
MENU MODE
Cool Set To
Schedule
Living
COOL
AM
SYSTEM
AUTO
FAN
thermostat has linked, “WiFi” will be on continuously indicating a connection.
INSTALL / REPLACE AA BATTERIES
Two AA batteries power the clock when 24VAC power is lost. Slide the battery cover downward and install the two AA batteries, paying attention to the polarity.
- + - +
MENU ENTER
NEXT
Touch the UP key to turn WiFi ON.
MENU ENTER
NEXT
User Options (Homeowner)
Factory Set Schedule
01
Monday through Friday
Morn
Day
Even
Nite
Saturday and Sunday
Morn
Day
Even
Nite
NA
Automatic Airflow Control (requires Installer Option 18
02
enabled or will not show up as a User Option
03
Nighttime Airflow Control Set the Nighttime Airflow in Heating (will only show if
04
Nighttime Airflow Control is ON) Set the Nighttime Airflow in Cooling (will only show if
05
Nighttime Airflow Control is ON)
06
Turning WiFi On/Off
07
Link Thermostat to Wireless network
08
Clean the Touch Screen (in seconds)
Schedule
Default Settings
Time Heat Cool
6:00 AM 8:00 AM 6:00 PM
10:00 PM
70 62 70 62
Time Heat Cool 6:00 AM 8:00 AM 6:00 PM
10:00 PM
70 62 70 62
Display Range Default
A Ac
n AF
nAF + Heat
nAF + Cool
nEt
Lnc
CL
On or Off
On or Off
%
%
On or Off
On or Off
N/A
130%
130%
75 83 75 78
75 83 75 78
On
On
Off
Off
30
Record User Selection if Changed
from Default Setting
Time Heat Cool
Time
Heat
Cool
Record User Selection if Changed
from Default Setting
N/A
N/A
page 6 of 16 P/N 780101703 3/18 Rev A
INSTALLER SECTION
This manual is separated into two different sections: one for the Homeowner and one for the System Installer.
The Installer section contains setup and installation information of the thermostat with optional user settings available to the homeowner.
INSTALLATION
i
!
CAUTIONS
Before installing the EvenAir comfort system, turn off all power to your HVAC system.
Read and follow all instructions carefully.
Read entire manual before installing EvenAir products.
Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes.
Use cautions when mounting components to surfaces that may have concealed wiring beneath the surface.
When servicing EvenAir system or accessing products, turn off all power to these items.
ATTENTION INSTALLER
1)
Install and wire components to the thermostat. (see Wiring section)
2)
Place the thermostat on the subbase. Do not install batteries.
3)
Turn power to the HVAC equipment On.
4)
Check for Error Messages. (see Error Message section)
5)
Set equipment options 1-5 if different than factory default settings. (see Installer Options section).
6)
Test the installation using the Installer Test Menu. (see Installer Test Menu section on page 13)
7)
Install batteries and set the time and day (see Installing Batteries and Set Time and Day section)
REMOVE SUBBASE
Place a slotted screwdriver in the slots as shown and rotate to remove subbase from the thermostat housing.
Airflow Control Off Option 17 turns off Airflow Control. The thermostat controls the system, dampers fully open, nighttime airflow control is disabled and airflow is no longer displayed on the thermostat.
User Airflow Control can be enabled using Option 18. User turns off automatic airflow control in the User Options.
Nighttime Airflow Control is defaulted to ON. If bedrooms are located downstairs, consider turning this option Off using the User Options if bedrooms are not on the same trunk.
ATTACH SUBBASE TO WALL
Attach the subbase to an interior wall and about 5-feet above the floor as shown using the screws and wall anchors supplied. The wires to the dampers,
HVAC equipment and the temperature sensor pass through the opening between the terminals.
R
C
WOB
EQUIPMENT
Y
G
W2E/Y2
TS
T21
COM
CLS
OPN
Sleeping
COM
CLS
OPN
Living
TS
page 7 of 16 P/N 780101703 3/18 Rev A
INSTALLER SECTION
INSTALL DAMPERS
Install a damper with an AMT actuator in the duct supplying air to the sleeping area and wire the terminals to the corresponding terminals on the T21. Install a second damper with an AMT actuator in the duct supplying air to the living area and wire it to the T21. Each damper uses 2.4VA of power.
Ensure that damper installation does not cause obstruction
!
to the damper blade.
When two or more dampers are required to define the sleeping or living area, the damper may be wired in parallel. LEDs on the damper actuator indicate when the damper is fully open (green) or fully closed (red). When properly installed, the dampers will never fully close.
Green LED
Red LED
WIRING
!
Warning!
Turn the power to the HVAC equipment off before wiring.
Gas/Electric, 2H/1C
Use 6-conductor, 18 or 20 gage, thermostat cable.
T21
Terminal
R C
W/OB
Y1
G
W2E/Y2
Gas/Electric, 1H/2C
Use 6-conductor, 18 or 20 gage, thermostat cable.
T21
Terminal
R
C
W/OB
Y1
G
W2E/Y2
Wire Color
Red
Blue
White Yellow Green Brown
Wire Color
Red
Blue
White Yellow Green Brown
Equipment
Terminal
R, Rc, Rh
C
W, W1
Y, Y1
G
W2
Equipment
Terminal
R, Rc, Rh
C
W, W1
Y, Y1
G
Y2
Function
24VAC Power Common Stg1 Heating
Cooling Fan Stg2 Heating
Function
24VAC Power Common Stg1 Heating
Stg1 Cooling Fan Stg2 Cooling
DAMPER WIRING
!
Warning!
Turn the power to the HVAC equipment off before wiring.
Use 3-conductor, 18 or 20 gage, thermostat cable to wire from the T21 Thermostat to the sleeping and living area dampers. There are separate terminals for the sleeping and living area dampers.
i
Ensure the damper for the sleeping area is wired to the terminals labeled SLEEPING and the damper for the living area is wired to the terminals labeled LIVING.
T21
Terminal
COM
CLS
OPN
Multiple dampers can be used to construct the sleeping or living zones. Daisy chain terminals– COM to COM, OPN to OPN and CLS to CLS.
Wire Color
White
Red
Green
Terminal
COM
CLS
OPN
FunctionDamper
Common Closes Damper Opens Damper
Heat Pump, 1 Compressor
Use 6-conductor, 18 or 20 gage, thermostat cable.
T21
Terminal
R
C
WOB
Y1
G
W2E/Y2
Wire Color
Red
Blue
White
Yellow
Green
Brown
Equipment
Terminal
R, Rc, Rh
C
O or B
Y, Y1
G
W, W2 or E
Function
24VAC Power
Common
Rev Valve
Compressor
Fan
Aux Heat
Heat Pump, 2-Compressor
Use 6-conductor, 18 or 20 gage, thermostat cable.
T21
Terminal
R
C
WOB
Y1
G
W2E/Y2
Wire Color
Red
Blue
White
Yellow
Green
Brown
Equipment
Terminal
R, Rc, Rh
C
O or B
Y, Y1
G
Y2
Function
24VAC Power
Common
Rev Valve
Stg1 Compressor
Fan
Stg2 Compressor
page 8 of 16 P/N 780101703 3/18 Rev A
INSTALLER SECTION
TEMPERATURE SENSOR WIRING
!
Warning!
Turn the power to the HVAC equipment off before wiring.
Use 2-conductor, 18 or 20 gage, thermostat cable to wire from the T21WF Thermostat to the temperature sensor in the sleeping area.
i
Single Sensor Installation Use one (1) Model TS51 sensor.
i
Dual Sensor Installation Use two (2) Model TS52 sensors.
T21WF
Terminal
TS TS
Wire Color
White
Red
HAND
TIGHTEN
Terminal
SNR SNR
Printed circuit board
Brass washer
Place wire between brass washer and the printed circuit board and hand tighten screw.
FunctionSensor
Thermistor Thermistor
WIRING DIAGRAM
Sleeping Area Damper
GE HP Y2
Y1
R
C
G
W2
G G Y Y W
C C R R
Y2
E
O or B
HVAC System
Model T21WF Thermostat (in living area)
W/OB
EQUIPMENT
W2E/Y2
TS
T21WF
Model AMT
PN 580011401
Damper Actuator Modulating 24VAC,2.4VA Made in USA
Living Area Damper
Model AMT
PN 580011401
Damper Actuator Modulating 24VAC,2.4VA Made in USA
F I E L D
F I E L D
C NO O LT SR
C NO O LT SR
OPN COM
OPN COM
Reference Electrical Wiring DWG: 780301202
CLS
CLS
COM
CLS
SleepingLiving
OPN
COM
CLS
OPN
TS
The TS5 sensor can be installed in a single gang box or directly to the wall using the hardware provided.
Model TS51 (one) Temperature Sensor for Sleeping Area
-OR-
Model TS52 (two) Temperature Sensors for Sleeping Area (temperatures are averaged)
page 9 of 16 P/N 780101703 3/18 Rev A
INSTALLER SECTION
INSTALLER OPTIONS
These set up features should only be accessed by a qualified installer during initial EvenAir thermostat installation set up. The homeowner would not normally access these product set up features.
Record Installed
Selection if Changed
Option
Description
01
Equipment Type Reversing Valve
02
(Only displayed if HP selected in Option 1)
03
Compressor Stages
04 Heating Stages Htg 0, 1 or 2 1
Fan Operation.
05
(Only displayed if GE selected in Option 1)
06
Compressor Minimum Off Time (minutes).
07
Gas Minimum Off Time (minutes).
08
Minimum Run Time (minutes). On-Off Temperature Differential
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
0 Cooling On 1 above setpoint, Off at setpoint. Heating On1 below setpoint, Off at setpoint. 1 Cooling On 1 above setpoint, Off .5 below setpoint. Heating On1 below setpoint, Off .5 above setpoint. 2 Cooling On 1 above setpoint, Off 1 below setpoint. Heating On1 below setpoint, Off 1 above setpoint.
Smart Recovery.
Vacant Heating Setpoint.
Vacant Cooling Setpoint.
Calibrate Living Area Sensor
Calibrate Sleeping Area Sensor.
Airflow Update Time
Night Level LCD Backlight
Airflow Control On or Off
Enable User Airflow Control
Up Stage Time Maximum Airflow in Heating to the
Sleeping Area. Maximum Airflow in Cooling to the Sleeping Area.
Maximum Airflow in Heating to the Living Area. Maximum Airflow in Cooling to the Living Area. Maximum Temperature Difference Between Sleeping and Living area.
Factory Restore
o o
o o o o
o o o o
Display
rEV
Cpr
Fan
Cot
HOt
r n t
O O
S r
+ Heat
V A C
V A C
+ Cool
C A L
C A L
A F t
BL
+ Night
AFC
UAC
USt
HAF+Heat
CAF+Cool
HAF+Heat
CAF+Cool
diF
Fr
GE or HP
0 or 1 (GE), 0 to 2 (HP)
GA(Down) or EL(Up)
o
0n(Up) or Off(Down)
1 to 20 minutes 2
On(Up) or Off(Down) On(Up) or Off(Down)
On(Up) or Off(Down)
5 to 30 minutes
100 to 160%
100 to 160%
100 to 160%
100 to 160%
No(Next or Enter) or Yes(UP Key then ENTER)
Range
Gas/Electric
o or b
0 to 9 0 to 9
0 to 9
0, 1 or 2
44 to 75
74 to 95
+/- 5
+/- 5
0 to 10F
Default
O
1 (GE),
2 (HP)
GA
2 0
2 1
Off
65
80
0
0
On
On
Off
10
150%
140%
150%
140%
2F
No
from Default Setting
N/A
INSTALLATION NOTES:
page 10 of 16 P/N 780101703 3/18 Rev A
INSTALLER SECTION
ACCESSING INSTALLER OPTIONS
To access the Installer Options, and
the hidden Enter key for 7 seconds until
HOLD the first Option appears on the screen.
Sleeping
Airflow %
Living
Day
Tu
AM
MODE
The hidden BACK key can be used to return to previous
TOUCH HOLD and this key for 7 seconds to access the Installer Options.
options.
Press the touchscreen with your fingertip
!
only, using a firm touch. Do not use a sharp object such as a pen or pencil.
The NEXT key is used to display the next
!
option.
The ENTER key is used to save options and
!
return to normal thermostat operation.
The hidden BACK key is used to return to
!
previous options and is located to the left of the NEXT key.
01 Selecting the Equipment Type
Factory Default: GE. Range: GE or HP
This option is used to select gas/electric or heat pump equipment.
Use the UP/DOWN keys to select gas/electric (GE) or heat pump (HP).
Touch NEXT or ENTER.
02 Reversing Valve
(Only displayed if Heat Pump equipment, HP is selected in Option 01)
Factory Default: O. Range: o or b
This option is used to select an O or B type reversing valve.
Use the UP/DOWN keys to select o for
O-Type or b for B-Type.
Touch NEXT or ENTER.
Schedule
TOUCH
Cool Set To
Living
Option
NEXT
Option
NEXT ENTER
COOL
SYSTEM
AUTO
FANMENU
ENTER
03 Setting the Compressor Stages
Factory Default: 1 . Range: 0 or 1
This option is used to set the number of compressor stages.
Use the UP/DOWN keys to set 0 or 1
Option
stage.
Touch NEXT or ENTER.
NEXT ENTER
04 Setting the Heating Stages
Factory Default: 1 Stage. Range: 0, 1 or 2
Use the UP/DOWN keys to set 0, 1 or 2
Option
stage.
Touch NEXT or ENTER.
NEXT ENTER
05 Setting the Fan Operation
(Only displayed if Gas/Electric equipment, GE, is selected in Option 01)
Factory Default: Gas. Range: GA or EL
Use the UP key to select “EL” for electric
Option
operation where the thermostat activates the indoor fan (G terminal) during
NEXT ENTER
heating calls or DOWN key to select GA for gas operation where the equipment plenum sensor activates the indoor fan in heating calls.
Touch NEXT or ENTER.
06 Compressor Minimum Off Time
Factory Default: 2 Min. Range: 0 to 9 Min.
Use the UP/DOWN keys to change the
Option
minimum off time (minutes) before restarting the compressor.
NEXT ENTER
Touch NEXT or ENTER.
07 Heating Minimum Off Time
Factory Default: 0 Min. Range: 0 to 9 Min.
Use the UP/DOWN keys to change the minimum off time (minutes) before restarting a gas furnace or electric strip heater.
Option
NEXT ENTER
08 Minimum Run Time
Factory Default: 2 Min. Range: 0 to 9 Min.
Use the UP/DOWN
keys to change the
Option
minimum run time
(minutes) before
turning a system off.
NEXT ENTER
Touch NEXT or ENTER.
09 Setting On-Off Temp Differential
Factory Default: #1. Range: 0, 1 or 2.
Use the UP/DOWN
keys to select 0, 1,
Option
2.
Touch NEXT or
ENTER.
Differential Mode0
Differential Mode1
Differential Mode2
o
1.0 On/Off Span.
o
1.5 On/Off Span.
o
2.0 On/Off Span.
NEXT ENTER
10 Smart Recovery
Factory Default: Off. Range: On or Off.
Smart recovery initiates a heating or cooling call
so that the space is at temperature when the
setback period ends.
Use the UP key to
select ON to turn on
Option
smart recovery or
the DOWN key to
select OF to turn
smart recovery off.
NEXT ENTER
Touch NEXT or ENTER.
11 Vacant Heating Setpoint
Factory Default: 65 F.
o
Range: 44 F to 75 F
Use the UP/DOWN
keys to select the
heating temperature
o o
Option
Heat
Vacant
when the space is
vacant.
NEXT ENTER
Touch NEXT or ENTER.
12 Vacant Cooling Setpoint
Factory Default: 80 F.
Use the
UP/DOWN
o
keys to select the cooling temperature when the space is vacant.
Touch NEXT or ENTER.
Range: 74 F to 95 F
o o
Option
NEXT ENTER
Cool
Vacant
Touch NEXT or ENTER.
page 11 of 16 P/N 780101703 3/18 Rev A
INSTALLER SECTION
13 Calibrate Living Area Temperature Sensor
Factory Default: None.
Use the UP/DOWN keys to change the Living area temperature to the temperature that the user feels is correct.
Touch NEXT or ENTER.
Range - +/-5
o
Option
Living
NEXT ENTER
14 Calibrate Sleeping Area Temperature Sensor
Factory Default: None.
Use the UP/DOWN keys to change the Sleeping area temperature to the temperature that the user feels is correct.
Touch NEXT or ENTER.
Range - +/-5
o
Option
Sleeping
NEXT ENTER
15 Airflow Update Time
Factory Default: 2 Min. Range: 1 to 20 Min.
This is the frequency, in minutes, that the damper position is updated.
UP/DOWN
Use the keys to set the time
Option
in minutes to update the sleeping and living area airflow.
NEXT ENTER
Touch NEXT or ENTER.
16 Night Level LCD Backlight
Factory Default: On. Range: On or Off.
The LCD has a low level backlight that can be used as a
Option
Night
night light.
Use the key to
UP
NEXT ENTER
turn the low level backlight ON or touch the key to turn
DOWN
OFF.
Touch NEXT or ENTER.
17 Airflow Control, On or Off
Factory Default: On. Range: On or Off.
This option turns the automatic airflow control on or off. If off, the dampers fully open, nighttime airflow options are disabled and airflow is no longer displayed on the thermostat.
UP
Use the key to select ON for airflow control or touch the
key to select
DOWN OFF to disable airflow control.
Touch NEXT or ENTER.
If Airflow Control was off and is now being turned on, the Nighttime Airflow option can be turned on using the User Options.
Sleeping
Airflow %
Living
Option
NEXT ENTER
18 Enable USER Airflow Control
Factory Default: Off. Range: On or Off.
Homeowners with an unusual work schedule, home office, etc. may want to use this option. When turned On, this option enables the user to turn off automatic airflow control in the User Options. Airflow is adjusted by the homeowner.
23 Maximum Airflow in Cooling to the Living Area
Factory Default: 140%. Range: 100% to 160%.
Use the
UP/DOWN keys to select the maximum allowable airflow in cooling to the living area.
Nighttime Airflow option is still enabled but can be turned off using the User Options.
Use the key to
UP
select ON to enable
Option
the user to turn off automatic airflow control in the user options.
Touch NEXT or ENTER.
NEXT ENTER
Touch NEXT or ENTER.
24 Maximum Temperature Differential
Factory Default: 2 F.
This is the maximum allowable temperature difference between the sleeping and living area temperatures. When the temperature difference is equal to or greater than the allowed differential,
o
Range: 0 to 10 F
the airflow is adjusted.
19 Upstaging Time
Factory Default: 10 min. Range: 5 to 30 min.
UP/DOWN
Use the keys to set the time at which second stage heating or cooling is activated.
Touch NEXT or ENTER.
Option
NEXT ENTER
Use the
UP/DOWN
keys to select the maximum allowable temperature difference between the sleeping and living area.
Touch NEXT or ENTER.
25 Factory Restore
For options 20 - 23, use the installer test o
n the following page to determine the
imum allowable airflow.
max
20 Maximum Airflow in Heating to Sleeping Area
Factory Default: 150%. Range: 100% to 160%.
UP/DOWN
Use the keys to select the maximum allowable airflow in heating to the sleeping area.
Touch NEXT or ENTER.
Sleeping
Airflow %
Option
Heat
NEXT ENTER
WARNING! Factory Restore resets ALL settings.
To exit this option, touch or NEXT ENTER, or the hidden Back key.
To restore factory settings, touch the
key to display
UP YES then touch ENTER.
21 Maximum Airflow in Cooling to the Sleeping Area
Factory Default: 140%. Range: 100% to 160%.
UP/DOWN
Use the keys to select the
Sleeping
Airflow %
Option
Cool
maximum allowable airflow in cooling to the sleeping area.
NEXT ENTER
Touch NEXT or ENTER.
22 Maximum Airflow in Heating to the Living Area
Factory Default: 150%. Range: 100% to 160%.
UP/DOWN
Use the keys to select the maximum allowable airflow in heating to the living area.
Touch NEXT or ENTER.
page 12 of 16 P/N 780101703 3/18 Rev A
Airflow %
Living
Option
Heat
NEXT ENTER
Airflow %
Living
Option
o o
Option
Option
Option
Cool
NEXT ENTER
NEXT
ENTER
NEXT ENTER
NEXT
ENTER
INSTALLER SECTION
ACCESSING THE TEST MENU
The Test Menu is used to test the Indoor Fan Operation, Allowable Heating Airflow Limits and Allowable Cooling Airflow Limits.
The Test Menu can also be used to perform the HERS Total Airflow test. TEST 05-06 activates a cooling call and opens both dampers to 100% enabling the installer to perform the test.
To access the Test Menu, and the hidden Next key for 7 seconds until the fan test screen (TEST 01) appears.
Sleeping
Airflow %
Living
Day
Tu
AM
TOUCH HOLD and this key for 7 seconds to access the Installer Options.
01-02 Testing Indoor Fan Operation
This test is used to verify that the indoor fan is operating correctly.
In TEST 1, the Fan is Off.
NEXT
Touch to go to TEST 2 to turn on the indoor fan. Verify the fan is operating and delivering airflow to the sleeping and living area.
NEXT
Touch to go to Testing Heating Airflow Limits.
TOUCH HOLD
Cool
Set To
Schedule
Sleeping
Airflow %
Living
Sleeping
Airflow %
Living
Living
Test
NEXT
Test
NEXT
COOL
SYSTEM
AUTO
FANMENU MODE
FANENTER
FANENTER
03-04 Testing Heating Airflow Limits
This test is used to determine the maximum allowable airflow to the sleeping area and the living area in HEATING.
In TEST 3, the system is Off.
NEXT
Touch to go to TEST 4 to activate heating. Verify the equipment is operating.
To determine the maximum allowable airflow to the Sleeping Area, touch
UP
the key until the airflow is too great and causes noise or annoyance. Lower the airflow using the key until it is acceptable. This is
DOWN the maximum allowable airflow in heating to the sleeping area. Record the airflow value.
Maximum Allowable Airflow in Heating
To determine the maximum allowable airflow to the living area, touch the DOWN
key until the airflow is too great and causes noise or annoyance. Increase the airflow using the key until it is acceptable. This is the maximum allowable airflow in heating to the living area. Record the airflow value.
Maximum Allowable Airflow in Heating
Touch to go to Testing Cooling Airflow
NEXT
Limits.
Sleeping
Test
Airflow %
Living
Sleeping
Test
Airflow %
Living
to the Sleeping Area
Sleeping
Test
Airflow %
Living
UP
to the Living Area
Heat
NEXT
ENTER
Heat
NEXT
ENTER
Heat
NEXT ENTER
05-06 Testing Cooling Airflow Limits
This test is used to determine the maximum allowable airflow to the Sleeping and Living Areas in COOLING.
The test can also be used to perform the HERS Total Airflow test. The test activates a cooling call and opens both dampers to 100%.
In TEST 5, the system is Off.
NEXT
Touch to go to TEST 6 to activate cooling. Verify the equipment is operating.
To determine the maximum allowable airflow to the sleeping area, touch
UP
the key until the airflow is too great and causes noise or annoyance. Lower the airflow using the key until it is acceptable. This is
DOWN the maximum allowable airflow in cooling to the sleeping area. Record the airflow value.
Maximum Allowable Airflow in Cooling
To determine the maximum allowable airflow to the Living Area, touch the
key until the
DOWN airflow is too great and causes noise or annoyance. Increase the airflow using the key until it is acceptable. This is the maximum allowable airflow in cooling to the living area. Record the airflow value.
Maximum Allowable Airflow in cooling
Touch to end testing and return to normal
ENTER
thermostat operation.
Sleeping
Test
Airflow %
Living
Sleeping
Test
Airflow %
Living
to the Sleeping Area
Sleeping
Test
Airflow %
Living
UP
to the Living Area
Cool
NEXT ENTER
Cool
NEXT
ENTER
Cool
NEXT ENTER
Enter the maximum airflow limits using Options 20 through 23 of the installer menu.
page 13 of 16 P/N 780101703 3/18 Rev A
INSTALLER SECTION
Error Messages:
!
Blank LCD
When the equipment is powered up, a blank LCD indicates that there is no power to the thermostat. Check the wiring from the thermostat to the equipment for errors.
No Power Message
nP is displayed when there is
no power to the system. If the message is displayed when the system is powered, check the wiring from the thermostat to the system for errors.
Sleeping
Airflow %
Tu
Day
Living
Cool Set To
Schedule
Living
AM
Sensor Error Message
nS is displayed when there
is an error with the temperature sensor(s). Check for open wires or shortages.
When the nS message is displayed, the thermostat will continue to control the system and automatically opens both dampers and disables airflow control until the sensor error is corrected.
Airflow %
Tu
Sleeping
Living
Day
Cool
Set To
Schedule
Living
AM
COOL
SYSTEM
AUTO
FANMENU MODE
COOL
SYSTEM
AUTO
FANMENU MODE
Install batteries only after successfully testing
!
the installation using the Installer Test Menu.
INSTALL BATTERIES
The batteries power the clock when 24VAC power is lost. Slide the battery cover downward and install the two AA batteries as shown.
Press the touchscreen with your fingertip only,
!
using a firm touch. Do not use a sharp object such as a pen or pencil. The touchscreen is a resistive touch and responds differently than touchscreens found in smart phones/devices.
Set Time and Day
Touch here to change the time and day of the week.
Sleeping
Airflow %
Tu
Day
Living
Cool Set To
Schedule
AM
Living
COOL
SYSTEM
AUTO
FANMENU MODE
CHANGE THE HOUR
Touch the UP/DOWN keys to change the HOUR. Touch NEXT.
AM
ENTER
NEXT
CHANGE THE MINUTE
Touch the UP/DOWN keys to change the MINUTE. Touch NEXT.
AM
ENTER
NEXT
CHANGE THE DAY OF THE WEEK
Touch the UP/DOWN keys to change the DAY OF THE WEEK.
We
AM
ENTER
Touch ENTER to save and return to normal thermostat operation.
page 14 of 16 P/N 780101703 3/18 Rev A
MAINTENANCE AND TROUBLESHOOTING
DAMPER OPERATION
Problem - No airflow to the sleeping area AND living area registers
Turn system off immediately. Both dampers may be wired backwards at the subbase or at the damper actuator (closing rather than opening).
Problem - No airflow to the sleeping area OR living area registers
Turn system off. One of the dampers may be wired backwards at the subbase or at the damper actuator (closing rather than opening).
Problem - When directing airflow to the sleeping area, the airflow is actually directed to the living area, and when directing the airflow to the living area, the airflow is actually directed to the sleeping area.
Turn system off. Check if the dampers are switched (sleeping area damper is wired to the living area terminals and the living area damper is wired to the sleeping area terminals.)
COMFORT CONCERNS
Problem - Downstairs bedroom is too cold or too hot at night.
The Nighttime Airflow Control option directs more airflow to the sleeping area and less airflow to the unoccupied living area. If the downstairs bedroom is on the same HVAC trunk as the living area, the downstairs bedroom may become uncomfortable at night. Turn off the Nighttime Airflow Control option using the User Options.
SENSOR INSTALLATION
Problem - nS message on thermostat.
Check that the sensor is wired correctly. Check for a short in the sensor wiring.
Problem - Sleeping area temperature reading very high or very low.
Check that the correct sensor(s) have been used. One TS51 sensor is used in a single sensor installation. Two TS52 sensors are used in a dual sensor installation.
Problem - The room temperature on the thermostat seems too high or too low.
The thermostat is factory calibrated within 1 degree. However, if a homeowner finds the temperature “feels” too high or too low, the thermostat can be calibrated to what the homeowner feels is the correct temperature using Installer option 13 for the living area and option 14 for the sleeping area.
SPARE PARTS AND ACCESSORY LIST
Field Controls
Part Number
580011101
580011102
580011301 580011302 580011401 580011405 580011406
Model
Number
T21
T21WF
TS51 TS52
AMT
IS
DS
MD-#
MD-LxH
Description Programmable wired thermostat w/ airflow control for GE equipment with 1H/1C, 2H/1C or 1H/2C,
or HP equipment with 2H/2C Programmable wired thermostat w/ airflow control for GE equipment with 1H/1C, 2H/1C or 1H/2C,
or HP equipment with 2H/2C. WiFi Enabled Wired temperature sensor for the sleep area. Single sensor installation. Wired temperature sensor for the sleep area. Dual sensor installation. Replacement modulating actuator control, 3 wire. Replacement idler shaft for AMT and AMJ actuators. Replacement drive shaft for AMT and AMJ actuators. EvenAir Round Balance Damper, 3 Wire. Sizes - 4” - 20” diameter. EvenAir Rectangular Balance Damper, 3 Wire. Sizes - 8”, 10” and 12” Heights, up to 24” Length.
page 15 of 16 P/N 780101703 3/18 Rev A
This manual may be downloaded and printed from the Field Controls website (www.fieldcontrols.com)
WARRANTY
For warranty information about this or any Field Controls product, visit:
www.fieldcontrols.com
Field Controls Technical Support
1.800.742.8368
fieldtec@fieldcontrols.com
Field Controls Customer Service
1.252.522.3031
sales@fieldcontrols.com
9154 Stellar Ct
Phone: 252.522.3031 Fax: 252.522.0214
Corona, CA 92883
c
Field Controls, LLC
www.fieldcontrols.com
2630 Airport Road
Kinston, NC 28504
P/N 780101703 3/18 Rev A
Loading...