Field controls CK-65 User Manual

CONTROL KIT
P/N 46126600
P/N 46144700
Model: CK-65
Timer
Relay
Aluminum Tubing
WMO-1 Safety Kit
P/N 46086901
Designed for controlling oil fired heating appliances using a Honeywell R8184G or equivalent Primary Control. The control operates the burner motor and the power venter together. A solenoid valve is used to control burner operation.
ITEMS INCLUDED IN KIT:
1 - Junction box with mounted pressure switch and and solid state post
2630 Airport Road • Kinston, NC 28504
Phone: 252-522-3031 • FAX: 252-522-0214
www.fieldcontrols.com
INSTALLATION AND ADJUSTMENTS
Figure 2
ure 1
Figure 3
MOUNTING JUNCTION BOX:
The junction box can be mounted at the venter or remotely mounted away from the venter. (See Fig. 1 & Fig. 2)
1. Remove one of the knockouts from the side of the junction box where the pressure switch is mounted. Install the flexible conduit connector onto the CK-65 junction box and secure with fastening nut. If remote mounting the CK­65 junction box, mount the flexible conduit connector onto a 2" x 4" installer supplied junction box.
2. Fasten the flexible conduit from the SWG Venter into the conduit connector. Mount the CK-65 junction box or installer supplied junction box onto the wall or floor joist without straining the flexible conduit. Fasten the CK-65 junction box through the four dimpled locations on the base of the box. (See Fig. 3)
OIL FIRED SECONDARY SAFETY SWITCH
Installation of a SECONDARY SAFETY SWITCH is recommended for detecting flue gas spillage from a blocked flue system and/or inadequate draft.
Fig
1. Pierce a 5/8" dia. hole into the vent pipe near the appliance outlet. Remove one of the securing nuts from the pipe of the safety switch. Tighten the other securing nut onto the pipe as far as possible. (See Fig. 4)
2. Insert the threaded pipe end into the pierced hole, then install the securing nut, which was removed in Step 1, and tighten securely (See Fig. 5)
3. Wire safety switch in series into one side of the burner circuit. Refer to Unit Wiring Instructions.
CAUTION: If for any reason the system has shut down during operation, the cause of the system failure should be investigated and corrected before resetting the safety switch and restarting the system.
Figure 4
Page 2
PRESSURE SWITCH SENSING TUBE INSTALLATION:
1. Attach the 1/4 inch tubing connector to the pressure tube on the SWG Venter. (See Fig. 3)
2. Connect the supplied 1/4" aluminum tubing to the tubing connector. Route the tubing to the CK-65 junction box and connect the tubing to the pressure switch. When routing the tubing, avoid kinking the tubing by bending the tubing too sharply.
For remote mounted CK-65 Junction Box, use a 1/4" OD copper, aluminum or plastic tubing and route the tubing to avoid contact with any heat source.
PROVING SWITCH ADJUSTMENTS:
After proper air flow is established, the pressure switch adjustment is made by turning the pressure switch adjustment screw clockwise (See Fig. 6) until burner operation stops. Turn the adjustment screw counterclockwise until burner ignites. Turn the adjustment screw an additional 1/4 to 3/4 turn counterclockwise to ensure adequate switch adjustment.
WARNING: Failure to properly adjust the pressure switch as specified above could lead to improper operation of the pressure switch which will result in a hazardous condition and bodily harm!
Figure 5
Figure 6
POST PURGE TIMING ADJUSTMENT:
To adjust the post purge time, rotate the timer adjustment on the timer counterclockwise to increase the operation time. To decrease the operation time, rotate the timer adjustment clockwise. (See Fig. 7) Typical post purge
Figure 7
time should be between 3 to 5 min.
WIRING INSTRUCTIONS
CAUTION: DISCONNECT ELECTRICAL POWER WHEN WIRING POWER VENTER
Wire the venter motor and controls in accordance with the National Electrical Code, manufacturer's recommendations and/or applicable local codes. UNITS MUST BE GROUNDED. Check ground circuit to make certain that the unit has been properly grounded. The wiring should be protected by an over current circuit device rated at 15 amperes. CAUTION must be taken to ensure that the wiring does not come into contact with any heat source. All line voltage and safety control circuits, between the venter and the appliance, MUST be wired in accordance with the National Electrical Code for class one wiring or equivalent methods. Refer to wiring diagrams A and B for typical wiring installations.
Page 3
Wiring Diagram A
Page 4
Wiring Diagram B Typical Wiring With Phelon Control
SYSTEM CONTROL CHECK OUT PROCEDURES:
1. Adjust the thermostat to call for heat and observe the power venting system for proper operation sequence. (Repeat if necessary)
a. Thermostat calls for heat. b. Relay is energized and venter motor starts. c. Pressure switch closes and burner starts. d. Thermostat is satisfied, the burner stops and venter motor should operate for approximately 3
to 5 minutes.
2. While system is operating, disconnect power to the venter motor. This should open the pressure switch contacts and stop burner operation.
3. Allow vent system to cool. Disconnect the vent pipe between the venter inlet and the appliance outlet. Block the vent pipe with a noncombustible material. Activate the heating system with the main burner operating. Allow approximately 2 minutes or less for the secondary safety switch to deactivate the burner. Reset safety switch and repeat.
TROUBLE SHOOTING HINTS
1. Main burner does not fire when thermostat calls for heat with venter operating. a. Check pressure switch adjustment b. Check fuel flow c. Check wiring connections between pressure switch and burner d. Check pressure switch for continuity across terminals, during venter operation
2. Venter does not activate when thermostat calls for heat: a. Jump wire the terminals L1 and M to ensure motor operation b. Check wiring.
3. Flue gas odor: a. Check system draft. b. Check post purge venting time. c. Check for negative pressure in building.
Page 5
DO NOT DESTROY
THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT
Installation Information
Model No.: ___________________________________
Installer’s Name: ______________________________
Installer’s Company:____________________________
Phone No.:___________________________________
Date of Installation: ____________________________
Page 6
Page 7
Page 8
P/N 46294900 Rev A 05/00
Loading...