24 VAC SYSTEM CONTROL KIT
Model: CK-43
Tubing
MG1 Barometric
Draft Control
The CK-43 is designed for use with the SWG Series Power
Venter for controlling Natural Gas and L.P. Gas Draft Induced
appliances.
Control kits control the operation of SWG Power Venters. Control
Kits can also control the operation of Field Draft Inducers and
Combustion Air Systems.
I
TEMS INCLUDED IN KIT
1) Junction box with mounted pressure switch and
relay/timer.
1) 1 Ft. Length of 1/4 inch aluminum tubing.
1) 1/4 inch tubing connector
1) Flexible conduit connector
1) 4" MG1 Barometric Draft Control or 5" AF Barometric
Draft Control
This device MUST be installed by a qualified agency in accordance with the manufacturers installation
instructions.
The definition of a qualified agency is: any i ndividual, fir m, corporation or compa ny which eith er in pers on or through a repr esentative is
engaged in, and is responsible for, the installation and operation of gas ap pliances, who is experienced in such work, familiar with all
the precautions required, and has complied with the requirements of the authority having jurisdiction.
DO NOT DESTROY
THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT
2630 Airport Road · Kinston, NC 28504
Phone: 252-522-3031· Fax: 252-522-0214
www.fieldcontrols.com
INSTALLATION INSTRUCTIONS
M
OUNTING JUNCTION BOX
The junction box can be mounted at the venter or remotely mounted away from
the venter. (See Figure 1 & Figure 2)
1. Remove one of the knockouts from the side of the junction box where the
pressure switch is mounted. Install the flexible conduit connector onto the
CK-43 junction box and secure with fastening nut. If remote mounting the
CK-43 junction box, mount the flexible conduit connector onto a 2" x 4"
installer supplied junction box.
2. Fasten the flexible conduit from the SWG Venter into the conduit
connector. Mount the CK-43 junction box or installer supplied
junction box onto the wall or floor joist without straining the
flexible conduit. Fasten the CK-43 junction box through the four
dimpled locations on the base of the box. (See Figure 3)
P
RESSURE SWITCH SENSING TUBE INSTALLATION
1. Attach the 1/4 inch tubing connector to the pressure tube on the
SWG Venter. (See Figure 3)
Figure 1
2. Connect the supplied 1/4" aluminum tubing to the tubing
connector. Route the tubing to the CK-43 junction box and
connect the tubing to the pressure switch. When routing the
tubing, avoid kinking the tubing by bending the tubing too
sharply.
For remote mounted CK-43 Junction Box, use a 1/4" OD copper,
aluminum or plastic tubing and route the tubing to avoid contact with
any heat source.
Figure 2
Figure 3
Page 2
DRAFT CONTROL INSTALLATION
See Figure 4 for typical vent
system layout.
CAUTION: This draft control is
shipped as a single acting draft
control. If the draft control is not
being used on a gas draft induced
furnace, remove the gate stop on
the draft control ring before
installing.
C
OLLAR INSTALLATION
This control is shipped with a collar
patterned to fit a single wall round
vent pipe. To attach this collar to
the flue, see Figure 5 and follow
the instructions below.
1. Bend outward the two ears at
the front corners of the collar.
Bend 90 degrees, 1/4 inch
behind the single hole on the
straps.
Figure 4
2. Insert clamping screw in ears on collar and bolt the remainder of
the collar together.
3. Hold the collar against the side of the flue in the exact position it
is to be installed (shown by dotted lines) and mark the outline
of the collar on the flue.
4. Cut a hole in the flue about 1/2" inside of this outline.
5. Make a series of cuts about 1/2" apart from the edge of this hole
to the outline marks.
Figure 5
6. Strap the collar to the flue pipe.
7. Bend the tabs formed by the series of cuts outward against the inside of the collar to make a tight joint.
8. Refer to Insertion of Draft Control Section.
Page 3