Field controls CAS-2B, CAS-2C, CAS-2W User Manual

COMBUSTION AIR SYSTEM
Model: CAS-2B, 2C & 2W
AIR BOOT™
4” VRV
4” IAH HOOD
ITEMS INCLUDED IN KIT:
1 - Air Boot™ 1 - Set of Gaskets 1 - 4” VRV 1 - 4” IAH Hood 1 - Burner Coupling Set 2 - Mounting Bolts 1 - Flow Restrictor Pan (CAS-2B ONLY)
NOTE: For burner inputs up to 2.0 GPH at 100 PSI input pressure or equivalent.
This device MUST be installed by a qualified agency* in accordance with the manufacturer’s installation instructions.
The definition of a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in, and is responsible for, the installation and operation of oil appliances, who is experienced in such work, familiar with all the precautions required, and has complied with all the requirements of the authority having jurisdiction.
“The Air Boot™ models CAS-2B, CAS-2C and CAS-2W are for use only on the designated burner(s) as described in these instructions only when the specific burner includes this Air Boot™ when shipped from the burner manufacturer or where the burner instructions specifically reference the models CAS-2B, CAS-2C or CAS-2W Air Boot™ as an optional air intake system .”
NOTE: This product brings combusti on air only to the burner; must have adequate venting air in accordance with NFPA-31.
CAS-2B BECKETT-AF/AFG CAS-2C CARLIN-EZ-1/CRD/FRD
CAS-2W WAYNE-MSR
2630 Airport Road · Kinston, NC 28504
Phone: 252-522-3031· Fax: 252-522-0214
www.fieldcontrols.com
INSTALLER SUPPLIED ITEMS:
Duct Piping and Elbows 90° Elbows;
¼ “ NPT Female x ¼” NPT Male for routing oil line
THE PURPOSE OF THE VRV
The Vacuum Relief Valve is a safety device to guard against combustion problems associated with directly connecting oil burners to the outside. Typical problems can be caused by blockage of the intake termination, icing up of the duct work and effects of leeward side wind effects on a building.
VRV O
PERATION
The VRV gate operates on changes in the vacuum pressure generated by the inlet to the oil burner. The VRV gate will remain closed during normal burner operation. During an abnormal operation (i.e., blockage of the intake or change in external building pressures) an increased negative pressure on the intake of the burner causes a reduction in burner air flow. Under this condition, the VRV gate opens, stabilizing and maintaining proper air flow to the burner. The VRV gate closes again once the abnormal condition is corrected.
INSTALLATION
Figure 1
Figure 2
1. Remove the oil pump and air bands from the burner housing. Install the sealing gaskets onto the burner housing. Failure to install the ring gasket onto the burner housing will result in unlevel boot, noisy operation, and improper CO
2
readings. (See Figure 1) Install mounting spacer onto Air Boot™. (See Figure 2) Position the Air Boot™ over the burner housing on the intake. The Air Boot™ can be mounted onto the burner in a horizontal or vertical position. Install mounting spacer onto Air Boot™. Align the holes in the
Figure 3
Page 2
Air Boot™ with the holes in the housing and re-attach the oil pump. (See Figure 3) Important: Replace
pump coupling with the coupling supplied with kit or pump operation problems may occur. Note that the
Air Boot™ may be oriented either vertically or horizontally as space allows. The round spacer plate attached to the Air Boot™ must be removed and rotated 90° if vertical mounting is needed.
2. FOR LOW FIRING RATE APPLICATIONS WITH BURNER INPUTS UP TO .75 GPH (CAS-2B ONLY) a. Insert flow restrictor pan in the
inlet collar with the flat of the pan inward. (See Figure 4)
b. Push the pan in all the way,
approximately 5/8” from the air adjustment blades. (See Figure
5)
Mount VRV tee assembly or
90° elbow onto the Air Boot™ intake. Fasten using three (3) sheet metal screws spaced 120° apart on all joints. (See Figure 6)
Figure 4
3. Assemble VRV balance weight onto the gate. Screw the weight all the way in. Then attach lock nut and knurl nut. (See Figure 7)
4. Mount the VRV assembly onto the tee and fasten with a screw and
nut in collar tabs. To ensure proper operation, check the gate for being level across the pivot points and plumb. (See Figure 8)
5. Refer to Figure 9 for general installation layout.
T
ERMINATION LOCATION GUIDELINES
1. Mount intake hood 12 inches above finished grade. If mounting on the side of a building prone to drifting snow, mount 12 inches above the snow line.
2. Mount at least 12 inches from either side of the vent termination and on the same wall if sidewall venting.
Figure 5
Figure 6
3. Always mount with the inlet vent termination opening pointing down.
NOTE: Make sure hood is kept free of debris.
Page 3
Loading...
+ 5 hidden pages