Field Controls B794589 User Manual

COMBUSTION AIR SYSTEM
MODEL: CAS-4JR
This product is designed for use with any natural gas or LP burning furnace, water heater, or boiler with a 24 VAC control system. It may be used with a residential water heater with additional hardware. It may also be used with more than one appliance. The CAS unit mechanically draws air into a structure and disperses it near the combustion air intake of an appliance. Refer to Diagram A and Table 1 for guidance in setting up the CAS system based on the size and length of the connecting ductwork and the input rating of the appliance.
ITEMS INCLUDED IN KIT:
1- CAS fan unit 1- 4" galvanized intake Air Vent Hood 2- Mounting brackets to secure the CAS to a wall 2- Wire/conduit connector(s) 1- Instruction Sheet
READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.
This device MUST be installed by a qualified agency in accordance with the manufacturer's installation instructions. The definition of a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in, and is responsible for, the installation and operation of HVAC appliances, who is experienced in such work, familiar with all the precautions required, and has complied with all the requirements of the authority having jurisdiction.
Please retain these instructions after installation.
www.fieldcontrols.com
Installation Date:
GENERAL SYSTEM OPERATION
The thermostat (wall thermostat, or Aquastat) calls for heat and energizes a relay which activates the CAS 1. unit. After the CAS fan has come up to speed, an internal air pressure switch closes and completes the circuit to allow the burner to fire. If the appliance is power vented, the venter and CAS activate simultaneously. After the CAS comes up to speed, a pressure switch in the unit closes and allows the appliance to fire. After the heating requirement has been satisfied, the thermostat circuit will open and deactivate the burner 2. and CAS unit. For power vented systems with a post purge device, the power venter and CAS operate for a period of time 3. after the burner has shut off to purge remaining flue gases from the vent system.
INSTALLATION SAFETY INSTRUCTIONS CAUTION: This device must be installed by a qualified installer in accordance with the manufacturer's installation
instructions.
This combustion air system must be installed by a qualified installer. "Qualified Installer" shall mean an individual 1. who has been properly trained or a licensed installer. Plan the system layout before installation to avoid the possibility of accidental contact with concealed wiring or 2. plumbing inside walls. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.3.
SIZING AND SETUP
Diagram A shows the maximum equivalent length and size of duct pipe that should be used when installing the CAS system. Using the chart will help ensure that the proper amount of air is drawn into the structure as needed by the appliance. The defined regions shown correspond to the CAS airflow characteristics when using 4" and 6" diameter sheet metal duct pipe. Follow the guidelines below to properly size and set up the CAS.
Determine the maximum input firing rate of the appliance, or the maximum total combined input firing rate of 1. multiple appliances that will be used. On Diagram A, locate the point that corresponds to the maximum total combined input firing rate along the 2. horizontal axis. Draw a vertical line through the point on the horizontal axis.3. Draw a horizontal line through the point where the vertical line intersects the 4" duct pipe curve.4. The horizontal line will intersect the vertical axis of the graph at the maximum allowable equivalent length of 5. 4" duct pipe, for the given firing rate. Position the motorized CAS unit according to the guidelines in the "Installation" section.6. Determine where the intake air vent hood will be located based on the recommendations in the 7. "Installation" section. Calculate the total equivalent length of duct pipe including elbows and fittings needed to connect the CAS unit 8. to the vent hood. DO NOT add any equivalent length for the intake hood; the hood effect is figured into the graph. Using Table 1, verify that the calculated total equivalent length of pipe does not exceed the maximum length 9. of 4" pipe as found in Step 5. If so, repeat Step 5, drawing a horizontal line where the vertical line drawn intersects the next larger size duct pipe curve and verify from steps 6-8 that the total equivalent length does not exceed that as found in Step 5 for the larger size duct pipe. EXAMPLE:10. A gas fired appliance firing at 100,000 BTU/hr where the CAS unit needs to be placed 30 equivalent feet from the intake hood.
page 2
0
20
40
60
80
100
120
140
160
180
200
220
240
260
280
300
50,000 60,000 70,000 80,000 90,000 100,000 110,000
CAS-4JR SIZING CHART
Max. Equivalent Duct Length, feet
Input Firing Rate, BTU/hour
Max. equivalent length of 4" pipe available when using the 4" CAS hood
Max. equivalent length of 6" pipe available when using the 4" CAS hood
Table 1
TOTAL INPUT OF APPLIANCE MAXIMUM EQUIVALENT FEET OF DUCT PIPE
(BTU/hr) 4" Pipe 5" Pipe 6" Pipe
50,000 230 300 300 60,000 16 0 300 300 70,000 105 300 300 80,000 70 214 300 90,000 40 122 300
100,000 25 76 180
110,000 15 46 80
page 3
Diagram A
Loading...
+ 5 hidden pages